Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

H365 Series: Addressable Heat Detectors

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

DF-61011:C

H365 Series
Addressable Heat Detectors

Addressable Devices
The Fire•Lite® Alarms H365(A), H365R(A), and H365HT(A)
addressable plug-in thermal detectors are designed for both perfor-
mance and aesthetics and are a direct replacement for the H355
Series. A new modern, sleek, contemporary design and advanced
thermal technologies make the H365(A) Series ideal for both system
operation and building design.
Exclusively for use with Fire•Lite’s addressable fire alarm control
panels, the H365(A) Series point ID capability allows each detector’s
address to be set with rotary, decimal address switches, providing
exact detector location for emergency personnel to quickly locate a
fire during its early stages, potentially saving precious rescue time
while also reducing property damage. Two LEDs on each sensor
light to provide a local, visible sensor indication.
The H365(A) Series includes fixed temperature, rate-of-rise and
high heat fixed temperature detectors that provide effective, intelli-
gent property protection for a variety of applications. Detectors are
available for both LiteSpeed™ and CLIP applications as designated.

Features
SLC LOOP: OPTIONS:
• Two-wire SLC loop connection • Remote LED output connection to optional RA100Z remote LED
• Unit uses base for wiring annunciator
ADDRESSING:
Installation
• Addressable by device
H365 Series plug-in intelligent thermal detectors use a detachable
• Rotary, decimal addressing
base to simplify installation, service and maintenance. Installation
(Refer to the Fire•Lite panel manuals for device capacity.)
instructions are shipped with each detector.
ARCHITECTURE: Mount detector base (all base types) on an electrical backbox which
• Designed to meet UL 268 7th Edition is at least 1.5" (3.81 cm) deep. For a chart of compatible junction
• Sleek, low-profile, stylish design boxes, see DF-60059.
• State-of-the-art thermistor technology for fast response NOTE: Because of the inherent supervision provided by the SLC loop,
end-of-line resistors are not required. Wiring “T-taps” or branches are
• Integral communications and built-in device-type identification
permitted for Style 4 (Class “B”) wiring only.
• Built-in tamper resistant feature When using relay or sounder bases, consult the I300(A) installation
• Built-in functional test switch activated by external magnet sheet I56-3626 for device limitations between isolator modules and iso-
lator bases.
OPERATION:
• Fixed temperature model (H365(A)) factory preset to 135°F Applications
(57°C) Use thermal detectors for protection of property. For further informa-
• Rate-of-rise model (H365R(A)), 15°F (8.3°C) per minute tion, refer to I56-6525, Applications Manual for System Smoke
• High-temperature model (H365HT(A)) factory preset to 190°F Detectors, which provides detailed information on detector spacing,
(88°C) placement, zoning, wiring, and special applications.
• 360°-field viewing angle of the two visual alarm indicators, LEDs
blink red in Normal condition and turn on steady red in Alarm Construction
• LEDs blink every time the unit is polled These detectors are constructed of fire-resistant plastic. The H365
Series plug-in intelligent thermal detectors are designed to commer-
MECHANICALS: cial standards and offer an attractive appearance.
• Sealed against back pressure
• SEMS screws for wiring of the separate base Operation
• Designed for direct-surface or electrical-box mounting Each H365 Series detector uses one of the panel’s addresses (total
• Plugs into separate base for ease of installation and maintenance limit is panel dependent) on the Fire•LiteJCI Signaling Line Circuit
• Separate base allows interchange of photoelectric, ionization and (SLC). It responds to regular polls from the control panel and reports
thermal sensors its type and the status. If it receives a test command from the panel
(or a local magnet test), it stimulates its electronics and reports an
OTHER SYSTEM FEATURES: alarm. It blinks its LEDs when polled and turns the LEDs on when
• Remote test feature from the panel commanded by the panel. The H365 Series offers features and per-
formance that represent the latest in thermal detector technology.
• Walk test with address display
• Low standby current

DF-61011:C • 11/18/2019 — Page 1 of 3


Product Line Information B200SA-IV: Same as B200S-IV, ULC listing
NOTE: “-IV” suffix indicates CLIP and LiteSpeed device. B200SCOA-WH: White, Intelligent, programmable sounder base in
English/French (required in Canada for ULC applications with CO
NOTE: “A” suffix indicates Canadian version.
Series detector applications
H365: White, low-profile intelligent 135°F fixed thermal sensor, Lite-
B200SCOA-IV: Ivory Intelligent, programmable sounder base in
Speed only
English/French (required in Canada for ULC applications with CO
H365A: Same as H365 but with ULC listing Series detector applications, ULC listing
H365-IV: Ivory, low-profile intelligent 135°F fixed thermal sensor, B200S-LF-WH: White, Low Frequency Intelligent, programmable
LiteSpeed and CLIP sounder base. Produces a fundamental frequency of 520 Hz +/-
H365A-IV: Same as H365-IV but with ULC listing 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238)
H365R: White, low-profile intelligent rate-of-rise thermal sensor,
LiteSpeed only B200S-LF-IV: Ivory, Low Frequency Intelligent, programmable
sounder base. Produces a fundamental frequency of 520 Hz +/-
H365RA: Same as H365R but with ULC listing 10% with a square wave or its equivalent; designed to meet the
H365R-IV: Ivory, low-profile intelligent rate-of-rise fixed thermal sen- NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238)
sor, LiteSpeed and CLIP B200SR-WH: White, Intelligent sounder base capable of producing
H365RA-IV: Same as H365R-IV but with ULC listing sound output with ANSI Temporal 3 or continuous tone. Intended for
retrofit applications. (CSFM: 7300-1653:0213)
H365HT: White, low-profile intelligent 190°F fixed thermal sensor,
LiteSpeed only B200SR-IV: Ivory, Intelligent sounder base capable of producing
sound output with ANSI Temporal 3 or continuous tone. Intended for
H365HTA: Same as H365H but with ULC listing retrofit applications. (CSFM: 7300-1653:0213)
H365HT-IV: Ivory, low-profile intelligent 190°F thermal sensor, Lite- B200SRA-WH: Same as B200SR-WH with, ULC listing
Speed and CLIP
B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing
H365HTA-IV Same as H365H-IV but with ULC listing
B200SR-LF-WH: White, Low Frequency Intelligent, programmable
INTELLIGENT BASES sounder base. Produces a fundamental frequency of 520 Hz +/-
NOTE: For details on intelligent bases, see DF-60059. 10% with a square wave or its equivalent; designed to meet the
NFPA 72 sleeping space requirement. Intended for retrofit applica-
B300-6: White, 6” base, standard flanged low-profile mounting base
tions. (CSFM: 7300-1653:0238)
(CSFM: 7300-1653:0109)
B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable
B300-6-IV: Ivory,6” base, standard flanged low-profile mounting
sounder base. Produces a fundamental frequency of 520 Hz +/-
base (CSFM: 7300-1653:0109)
10% with a square wave or its equivalent; designed to meet the
B300A-6: Same as B300-6, ULC listed NFPA 72 sleeping space requirement. Intended for retrofit applica-
B300A-6-IV: Ivory, 6” standard flanged low-profile mounting base, tions. (CSFM: 7300-1653:0238)
ULC listed MOUNTING KITS AND ACCESSORIES
B300-6-BP: Bulk pack of B300-6, package contains 10 TR300: White, replacement flange for B210LP(A) base
B501-WHITE: White, 4” standard European flangeless mounting TR300-IV: Ivory, replacement flange for B210LP(A) base
base. UL/ULC listed (CSFM: 7300-1653:0109)
RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S.
B501-BL: Black, 4” standard European flangeless mounting base. single-gang electrical box. For use with B501(A) and B300-6(A).
UL/ULC listed (CSFM: 7300-1653:0109)
M02-04-00: Test magnet
B501-IV: Ivory color, 4” standard European flangeless mounting
base. UL/ULC listed (CSFM: 7300-1653:0109) M02-09-00: Test magnet with telescoping handle
B501-WHITE-BP: Bulk pack of B501-WHITE contains 10 CK300: Color Kit (includes cover and trim ring), white, 10-pack

B224RB-WH: White, relay base (CSFM: 7300-1653:0216) CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack

B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216) CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack

B224RBA-WH: White, relay base, ULC listing


B224RBA-IV: Ivory, relay base, ULC listing
B224BI-WH: White, isolator detector base (CSFM: 7300-1653:0216)
B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216)
B224BIA-WH: White, isolator detector base, ULC listing
B224BIA-IV: Ivory isolator detector base, ULC listing
B200S-WH: White, Intelligent addressable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3,
ANSI Temporal 4, continuous tone, marching tone, and custom tone.
Uses FlashScan protocol. (CSFM: 7300-1653:0213)
B200S-IV: Ivory, Intelligent addressable sounder base capable of
producing sound output in high or low volume with ANSI Temporal 3,
ANSI Temporal 4, continuous tone, marching tone, and custom tone.
Uses FlashScan protocol. (CSFM: 7300-1653:0213)
B200SA-WH: Same as B200S-WH, ULC listing

Page 2 of 3 — DF-61011:C • 11/18/2019


SYSTEM SPECIFICATIONS
Size: 2.0" (5.3 cm) high; base determines diameter
– B300-6: 6.1" (15.6 cm) diameter
– B501: 4" (10.2 cm) diameter
For a complete list of detector bases see DF-60983
Shipping weight: 3.4 oz. (95 g)
Operating temperature range:
• H365, H365R Series: –4°F to 100°F (–20°C to 38°C)
• H365H Series: –4°F to 150°F (–20°C to 66°C)
Detector spacing: UL approved for 50 ft. (15.24 m) center-to-cen-
ter, FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing
Relative humidity: 10% – 93% non-condensing
Thermal ratings: fixed-temperature set point 135°F (57°C), rate-of-
rise detection 15°F (8.3°C) per minute, high temperature heat 190°F
(88°C)
Mounting: B300-6(A) flanged base, included
See “Product Line Information: Intelligent Bases,” if using a dif-
ferent base.
ELECTRICAL SPECIFICATIONS
Voltage range: 15 - 32 volts DC peak
Standby current (max. avg.): 200µA @ 24 VDC (one communica-
tion every 5 seconds with LED enabled)
Max current: 4.5 mA @ 24 VDC (“ON”)

Listings and Approvals


Listings and approvals below apply to the H365 Series detectors. In
some cases, certain modules may not be listed by certain approval
agencies, or listing may be in process. Consult factory for latest list-
ing status.
• UL/ULC Listing: S2517
• FM Approved
• CSFM: 7272-0075:0501

LiteSpeed™ is a trademark and Fire•Lite® Alarms is a registered trademark of


Honeywell International Inc.
©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this
document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: Mexico
www.firelite.com

Page 3 of 3 — DF-61011:C • 11/18/2019