H365 Series: Addressable Heat Detectors
H365 Series: Addressable Heat Detectors
H365 Series: Addressable Heat Detectors
H365 Series
Addressable Heat Detectors
Addressable Devices
The Fire•Lite® Alarms H365(A), H365R(A), and H365HT(A)
addressable plug-in thermal detectors are designed for both perfor-
mance and aesthetics and are a direct replacement for the H355
Series. A new modern, sleek, contemporary design and advanced
thermal technologies make the H365(A) Series ideal for both system
operation and building design.
Exclusively for use with Fire•Lite’s addressable fire alarm control
panels, the H365(A) Series point ID capability allows each detector’s
address to be set with rotary, decimal address switches, providing
exact detector location for emergency personnel to quickly locate a
fire during its early stages, potentially saving precious rescue time
while also reducing property damage. Two LEDs on each sensor
light to provide a local, visible sensor indication.
The H365(A) Series includes fixed temperature, rate-of-rise and
high heat fixed temperature detectors that provide effective, intelli-
gent property protection for a variety of applications. Detectors are
available for both LiteSpeed™ and CLIP applications as designated.
Features
SLC LOOP: OPTIONS:
• Two-wire SLC loop connection • Remote LED output connection to optional RA100Z remote LED
• Unit uses base for wiring annunciator
ADDRESSING:
Installation
• Addressable by device
H365 Series plug-in intelligent thermal detectors use a detachable
• Rotary, decimal addressing
base to simplify installation, service and maintenance. Installation
(Refer to the Fire•Lite panel manuals for device capacity.)
instructions are shipped with each detector.
ARCHITECTURE: Mount detector base (all base types) on an electrical backbox which
• Designed to meet UL 268 7th Edition is at least 1.5" (3.81 cm) deep. For a chart of compatible junction
• Sleek, low-profile, stylish design boxes, see DF-60059.
• State-of-the-art thermistor technology for fast response NOTE: Because of the inherent supervision provided by the SLC loop,
end-of-line resistors are not required. Wiring “T-taps” or branches are
• Integral communications and built-in device-type identification
permitted for Style 4 (Class “B”) wiring only.
• Built-in tamper resistant feature When using relay or sounder bases, consult the I300(A) installation
• Built-in functional test switch activated by external magnet sheet I56-3626 for device limitations between isolator modules and iso-
lator bases.
OPERATION:
• Fixed temperature model (H365(A)) factory preset to 135°F Applications
(57°C) Use thermal detectors for protection of property. For further informa-
• Rate-of-rise model (H365R(A)), 15°F (8.3°C) per minute tion, refer to I56-6525, Applications Manual for System Smoke
• High-temperature model (H365HT(A)) factory preset to 190°F Detectors, which provides detailed information on detector spacing,
(88°C) placement, zoning, wiring, and special applications.
• 360°-field viewing angle of the two visual alarm indicators, LEDs
blink red in Normal condition and turn on steady red in Alarm Construction
• LEDs blink every time the unit is polled These detectors are constructed of fire-resistant plastic. The H365
Series plug-in intelligent thermal detectors are designed to commer-
MECHANICALS: cial standards and offer an attractive appearance.
• Sealed against back pressure
• SEMS screws for wiring of the separate base Operation
• Designed for direct-surface or electrical-box mounting Each H365 Series detector uses one of the panel’s addresses (total
• Plugs into separate base for ease of installation and maintenance limit is panel dependent) on the Fire•LiteJCI Signaling Line Circuit
• Separate base allows interchange of photoelectric, ionization and (SLC). It responds to regular polls from the control panel and reports
thermal sensors its type and the status. If it receives a test command from the panel
(or a local magnet test), it stimulates its electronics and reports an
OTHER SYSTEM FEATURES: alarm. It blinks its LEDs when polled and turns the LEDs on when
• Remote test feature from the panel commanded by the panel. The H365 Series offers features and per-
formance that represent the latest in thermal detector technology.
• Walk test with address display
• Low standby current
B224RB-WH: White, relay base (CSFM: 7300-1653:0216) CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack
B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216) CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: Mexico
www.firelite.com