Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Alk V - 04 2011

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

ALK-V PHOTOELECTRIC SMOKE SENSOR

APPLICATION
The HOCHIKI America ALK-V Photoelectric Smoke Sensor is particularly suited to detecting optically dense smoke typical of fires involving materials such as soft furnishings, plastic, foam or other similar materials which tend to smolder and produce large visible smoke particles. Hochiki's unique design allows fast response to flaming fires as well as smoldering fires while eliminating false alarms.

OPERATION
The detection chamber consists of a light emitting diode (LED) and photodiode arrangement. The chamber is designed such that light emitted by the LED cannot normally reach the photo diode. In the event of fire, particles of smoke enter the chamber and scatter the light. As the smoke level increases, the scattering effect increases, causing more light to hit the photodiode. The chamber contains a unique baffle design which allows smoke to enter the chamber while preventing external light from affecting the photodiode. The photodiode input level is sampled to sense smoke density. When the smoke density exceeds a preset threshold the sensor transmits an interrupt to the fire control panel indicating a fire condition. The fire alarm control panel can adjust the sensor threshold to compensate for contamination. Up to 127 devices are permitted on each loop. A sensor address can be set by a hand held programming unit. The sensor mounts to an electronics free base and incorporates a locking mechanism for secure installation. The base provides mounting slots, terminals for field wiring and a third contact for a remote indicator/LED. The sensor incorporates dual LED's for easy viewing of sensor status.

STANDARD FEATURES

Shown without base

Low Profile - Only 2.0" high, including base Simple and reliable device addressing method Automatic compensation for sensor contamination Built-in fire test feature Uses the noise immune Digital Communication Protocol (DCP), which utilizes interrupts for fast response to fires Two built-in power/alarm LED's Programmble Non-polling LED's Non-directional smoke chamber Vandal resistant security locking feature Removable smoke labyrinth for cleaning or replacement Compatible with the AIE-EA ionization detector, ALG-V Photoelectric detector & the ATG-EA heat detector

SPECIFICATIONS
Operating Voltage Standby Current Alarm Current Transmission Method 17-41 VDC 390A 800A DCP - Digital Communication Protocol Maximum Humidity 95% RH Non-Condensing UL Ambient Installation 32F to 100 F Temperature Range (0 C to 37.8 C) Operating Temperature 14F to 122 F Range (-10 C to 50 C) Sensitivity Range 0.5 - 3.8%/FT@300FPM 0.5 - 2.74%/FT@2000FPM 0.5 - 2.68%/FT@4000FPM Air Velocity Range 0-4000 fpm Color & Case Material Bone PC, Black / ABS Blend Weight 3.4oz (5.1 oz. with 4" base) Bases 4" YBN-NSA-4 6" HSB-NSA-6 & ASB Hochiki America Corporation 7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 Phone: 714/522-2246 Fax: 714/522-2268 Technical Support: 800/845-6692 or technicalsupport@hochiki.com

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, photoelectric sensors HOCHIKI America Model ALK-V. The combination sensor head and twist lock base shall be UL listed compatible with a UL listed fire alarm control panel.

PRODUCT LISTINGS
California State Fire Marshal 7272-0410:173
Continued on back. Find latest revision at www.hochiki.com

3034568 S1383

F0076

04/2011

ENGINEERING SPECIFICATIONS, continued


The base shall permit direct interchange with the HOCHIKI America AIE-EA ionization type smoke sensor, ALG-V Photoelectric type smoke sensor, and the ATG-EA heat sensor. The sensitivity of the sensor shall be capable of being measured by the control panel. The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking feature shall be optional and can be implemented when required.

BASES
The HOCHIKI America except for ASB both YBN-NSA-4 and the HSB-NSA-6 mounting bases are electronics free and are a simple rugged design with screw terminals for wiring connections. A common mounting base allows sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided which is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using a small diameter screw driver.

TYPICAL WIRING DIAGRAMS


U.L. LISTED COMPATIBILE CONTROL PANEL

(+)

NOTE: Fire alarm control panel compatibility is required for DCP products. State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA, ALK-V, ALK-V, ALK-V2 and ATG-EA, bases and modules), to be used concurrently in a system's signaling line circuit.

(-)

U.L. LISTED POWER LIMITED SUPPLY

(+)

* * - OPTIONAL WIRING CONFIGURATIONS FOR REMOTE OUTPUT


(+)

U.L. LISTED COMPATIBILE CONTROL PANEL

(-)
U.L. LISTED POWER LIMITED SUPPLY

(+)

UL LISTED COMPATIBLE CONTROL PANEL

8mA Max.

NEXT DEVICE

NUMBER OF ASB BASES PERMITTED # of Bases Maximum Auxiliary 24VDC Power In Alarm Wire Resistance (Total Auxiliary Run Length)
8mA MAX.
OUTPUT

LOOP OUT

NEXT DEVICE

(Aux.)

(+)

FIGURE A

TOP VIEW

NOTE: Class A style 7 wire configuration requires the installation of short circuit isolators (SCI).
DO NOT CONNECT FOR CLASS B (STYLE 4) LOOP IN CONNECT FOR CLASS A (STYLE 6 OR 7)

AUX POWER

RED BLACK

RED BLACK

RED BLACK

127 75 60 50 30 20 15 10

1.4 ohms 2.4 ohms 3.0 ohms 3.6 ohms 6.1 ohms 9.1 ohms 12.2 ohms 18.3 ohms

CO ICA B ER V. RE I AM 7 B -06 AS C HIK-08 HO HA . RP SC G 3 TP

CO ICA B ER V. RE I AM 7 B -06 AS C HIK-08 HO HA . RP SC G 3 TP

Hochiki America Corporation ALK-V

DE TS C 2 TP

DE

1 TP S S5 6

1 TP

TS C 2 TP

S S5 6

RED BLK BLK

RED BLK BLK

2 C-0 03 21

2 C-0 03 21

RED

RED

FIGURE B

BOTTOM VIEW

NOTE: SLC maximum wiring resistance is 50 ohms.


Specifications subject to change without notice.