Maintenance and service Axis AX multisensor detectors give the choice of five operating
modes which respond as follows:
Axis AX detectors have been designed with a comprehensive
set of features to support maintenance and service, from Modes 1, 3 and 4 - multicriteria response
self-test capabilities to drift compensation warnings on dirty
Mode 2 - optical response only
detectors.
Mode 5 - heat response only
Specification
Digital communication protocol Discovery
Supply wiring Two wire supply, polarity sensitive
Sensitivity 1.2-2.1%/ft
Supply voltage (Vmin-Vmax) 17-28 Vdc
Sampling frequency Once per second
Modulation voltage 5-9V peak to peak
Supervisory current 500 μA
Switch-on surge current 1.0 mA
Alarm/operated current, LED on 4.0 mA
Status indicator
Alarm - Red
Fault - Flashing yellow
Isolate - Yellow
Poll - Flashing green
Materials
Housing: White flame-retardant polycarbonate.
Terminals: Tin-plated stainless steel
All data is supplied subject to change without notice. Specifications are typical at 24 V, 73 ° F and 50% RH unless otherwise stated.
Advanced, The Bridges, Balliol Business Park, Newcastle upon Tyne, NE12 8EW, UK T: +44 (0)345 894 7000, E: enquiries@advancedco.com,
W: www.advancedco.com