Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Manual de Instalare Bariera IR DOP 6001 - ENG

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 14

IK-E343-001E 1

POLON 4000
INTERACTIVE FIRE DETECTION AND ALARM SYSTEM

DOP-6001
OPTICAL BEAM SMOKE DETECTOR

Installation and maintenance manual

IK-E343-001E

Edition I
2 IK-E343-001E

The DOP-6001 beam smoke detector, covered by this manual, complies with the requirements of the
following European Union directives:
CPD 89/106/EWG - on construction goods;
EMC 2004/108/WE - on electromagnetic compatibility
LVD 2006/95/WE - on low-voltage supply electric equipment.

The DOP-6001 detector has been approved with the EC Certificate of Conformity No. 1438/CPD/0219,
issued by the Scientific and Research Centre for Fire Protection (CNBOP) Józefów, Poland, an EU notified
authority No. 1438, confirming its compliance with the requirements of PN-EN 54-12: 2005 standard.
The certificate can be downloaded from www.polon-alfa.pl

1438

Polon-Alfa Spółka z ograniczoną odpowiedzialnością Sp. k.


Glinki 155 Street, PL 85-861 Bydgoszcz
11
1438/CPD/0219

PN-EN 54-12
DOP-6001 Beam smoke detector (operates using absorbed light beam,
addressable, conventional, undetachable)
Application – fire security
Technical data - IK-E343-001 manual.

Read the manual carefully before the detector assembling and commissioning. Any nonconformity with the
instructions contained in the manual may be harmful or may cause violation of the law in force

The manufacturer, POLON-ALFA shall not bear responsibility for any harms resulted from the unit
application discordantly to the requirements of this instruction.

A waste product, unsuitable for further use, shall be passed to


a waste electric and electronic equipment collection point.

NOTE: The manufacturer reserves the right to change product specifications at any time without prior notice.
IK-E343-001E 3

1 PURPOSE

The DOP-6001 Beam Smoke Detector is designed for smoke detection at the start of a fire. It is especially
suitable for protection of premises where, in the first phase of the fire, smoke appearance is expected and
in which, due to a large space area, installation of a greater number of spot smoke detectors would be
necessary. Beam smoke detectors (in comparison with spot smoke detectors) are sensitive to medium
smoke density value on a long path of the infrared radiation beam and therefore they are especially suitable
for application under high ceilings/roofs or in those places where smoke can be diffused over a large area
before detection.
Exemplary objects especially suitable for this type detector installation are: churches, cathedrals,
monumental buildings with valuable historic ceilings, theatres, sports halls, industrial shops, very high
rooms, in which spot detectors would be ineffective, and rooms with differentiated ceiling or roof design.
A distinctive feature of the DOP-6001 detector is its arrangement of a transmitter and a receiver in one
enclosure and interaction with a prism reflector or a reflector panel placed on the opposite wall. A single
casing embraces a laser target viewfinder that enables optical path axis alignment between the detector
and the reflector/reflector panel.
The DOP-6001 beam smoke detector is intended for installation in the POLON 4000 system fire detection
and alarm control panel lines. The detector operates in closed premises at ambient temperatures ranging
from –25 oC to +55 oC and relative humidity up to 95 % at 40 oC.

2 TECHNICAL SPECIFICATIONS
Operating voltage in a detection line 16.5 V ÷ 24.6 V
Max. current consumption in detection line < 300 μA
Detector address and sensitivity thresholds programmable at control panel
Detector operating voltage in a conventional line 10.5 V ÷ 24.0 V
Quiescent current in a conventional line 5 mA or 2.2 mA depending on system
Alarm current at 20 V 20 mA
Current at light beam break < 0.3 mA
Current at service signal – optics soiling < 0.3 mA
Sensitivity thresholds (to be chosen) 18 %; 30 %; 50 %
Operating distance
- with E39-R8 prismatic reflector (Fig. 6) from 5 m to 50 m
- with 4xE39-R8 reflector panel (Fig. 7) from 50 m to 100 m
Detector angular tolerance ± 0.5 °
Reflector angular tolerance ±5°
Number of detectors in POLON 4000 addressable line 64
Number of detectors in one conventional line 1
Power supply of laser viewfinder (during alignment) 6F22 (9 V) battery
Operating temperature range -25 °C ÷ +55 °C
Admissible ambient relative humidity up to 95 % at + 40 °C
Dimensions 129 x 80 x 84 mm
Mass (together with adjustment basis) 0.35 kg
Casing colour white (other on request)
Suitability in test fire detection TF1, TF2, TF3, TF4, TF5, TF7, TF8
4 IK-E343-001E

Fig. 1. DOP-6001 detector with prism reflector

3 PRINCIPLE OF OPERATION

The DOP-6001 detector consists of an infrared (IR) light transmitter and a receiver located in a single
enclosure, and an interoperating separate E39-8R prism reflector or 4xE39-8R reflector panel. The detector
principle of operation consists in continuous analysis of optical air transparency in a space between the
detector and the reflector (reflector panel).
The detector can be in one of four modes: supervision, alarm, fault – light beam break, and fault – caused
by contamination. If a certain, defined quantity of aerosol (smoke) is found in the air, reducing optical
transparency below a set threshold, then the detector enters an alarm mode. Complete interruption of the
radiation beam (or its reflection due to an object occurrence in its optical path) is signalled as a fault,
because even the largest smoke concentration in the air does not cause an entire break of the detector
optical path. When the air is clear, the detector is in supervision mode.
Long lasting detector operation, especially in high dust level premises, may lead to contamination (dust
build-up) of optical parts of the detector and the reflector/reflector panel. In order to maintain constant
sensitivity and fire detection ability during a long time period, the detector is equipped with automatic
compensation circuits to monitor its contamination and environ impact conditions. The circuits ensure the
same sensitivity threshold in the whole compensation range. At a certain contamination level, the detector
signals a fault mode denoting a necessity to undertake servicing and cleaning works. However, even in this
mode, the detector is still able to detect smoke and initiate an alarm. A contamination caused fault requires
cleaning works of the reflector/reflector panel and the detector front surface. After cleaning, the detector
adjusts to new external conditions and automatically changes its mode from fault to supervision.
Communication between the POLON 4000 system control panel and the DOP-6001 detectors is provided
using a two-wire detection line. A unique, fully digital communication protocol enables transmission of any
information from the control panel to the detector and vice versa, such as: surrounding conditions
evaluation (smokiness, temperature), their change tendency and the current analogue value of temperature
and smokiness density.
The DOP-6001 addressable smoke detector is equipped with an internal short circuit isolator, which cuts off
the efficient detection line from a shorted section, what enables the detector further unfailing operation.
Analysis function in the DOP-6001 detector is fulfilled by a microprocessor. After the detector optical path
alignment and initiation the analysis process at the control panel level (detectors in an addressable line), or
IK-E343-001E 5

pressing the START push button (detectors in a conventional line), microprocessor circuits analyses the
ambient temperature and the settled sensitivity threshold. A self-adjustment program is switched on after
entering these data into the detector memory. The self-adjustment process terminates after achieving a
reference value with  5 % tolerance. Afterwards, the decision criteria are drawn up for various fire
phenomena runs, for instance for fast or slow fire development. The data are kept in the detector non-
volatile memory and periodically checked. Any measured value change (against the assumed decision
thresholds) caused by a smoke, after triple verification, is treated by the microprocessor as a fire.

4 DESIGN
The DOP-6001 detector design is shown on Fig. 1 and Fig. 3. The detector casing, made of plastic, embraces
electronic circuits and optical elements of a transmitter and a receiver as well as a laser diode that
facilitates the detector easy optical alignment. The lenses for infrared beam focusing are covered with a
detachable filter. On the detector back side a connecting block is mounted, to connect power supply wires.
The detector is fastened to the wall with a metal adjustment basis. On the detector front part, illuminating
diodes are placed as well as the START push button that initiates the detector adjustment process.
The illuminating diode colour signals accordingly:
- green one – a state of the detector self-adjustment to the detector-reflector/reflector panel
distance, when the signal level is too high;
- yellow one – a state of the detector self-adjustment to the detector-reflector/reflector panel
distance, when signal level is too low;
- red one – an alarm mode;
- no light – a supervision mode after proper adjustment of the detector with the reflector/reflector
panel.
The START push button enables initiation of the detector adjustment process (self-adjustment) and the
detector parameters renewed set-up after optical parts cleaning works.

5 INSTALLATION
The DOP-6001 detector interoperates with a reflector panel and then its operating distance ranges from 50
m to 100 m, or with an E39-R8 prism reflector at the operating distance between 5 m and 50 m. It is
possible to install up to 64 DOP-6001 detectors in one POLON 4000 system addressable line.
The reflector or the reflector panel as well as the M42-00 00 00 service kit, containing test foils and an
adjustment mirror, are not included in the detector standard pack and should be ordered separately.
Up to 64 DOP-6001 detectors can be installed in one addressable detection line of the POLON 4000 system.
Only one DOP-6001 detector without end-of-line resistors can be installed in one conventional line.
In case the detector is seen with difficulty or is installed in a hardly accessible place, it is possible to connect
the WZ-31 additional operation indicator to be placed in a convenient and visible place.
Before installation, it is necessary to declare an alarm mode and a sensitivity threshold. The operations are
executed using appropriate jumpers placed on the back side of the detector casing, pursuant to Fig. 6. One
of the criteria taken into consideration when choosing sensitivity may be the distance between the detector
and the reflector/reflector panel, and so:
- for a distance from 5 m to 20 m – 18 % sensitivity is recommended;
- for a distance from 20 m to 50 m – 30 % sensitivity is recommended;
- for a distance from 50 m to 100 m – 50 % sensitivity is recommended.
6 IK-E343-001E

It is possible to set sensitivity level experimentally: adopting it to a certain environment in the case of the
detector difficult operating conditions. The DOP-6001 detector and the reflector/reflector panel are
mounted on opposite walls, pillars or other construction elements of the premises. The walls or pillars must
be stable and vibration-free. The detector adjustment basis should be mounted on a wall and the
reflector/reflector panel - on the opposite wall. The detector should be placed on the adjustment basis (Fig.
3) after preliminary connection of the wires to the connecting blocks in accordance with Fig. 4. The detector
should be fixed to the basis with three screws that are accessible from the front side (after removing the
cover). Then a 6F22 battery should be connected to the laser viewfinder contacts.
Before alignment, the mirror (part of the service kit) should be placed on the reflector panel and press
down, as it is shown on Fig. 9. With the help of three positioning screws, the detector laser beam should be
aimed at the centre of the reflector or the mirror from the service kit. The adjustment screws help in
precise alignment so that the laser beam returns to the detector front plate after being reflected from the
reflector. The mirror should be removed after proper regulation of the optical path between the detector
and the reflector. The prism reflector position cannot be adjusted and it is recommended to fix it to a flat
substrate with screws or glue.
The detector is properly aligned with the reflector/reflector panel when the reflected laser light illuminates
the detector. In such the situation the external battery should be disconnected, the detector cover should
be mounted and the START push button should be pressed. As a result, one of the diodes: yellow or green
shall be lit in a pulse manner. After ca. 40 sec. the diodes should switch off, what stands for a proper
adjustment of the infrared beam to the distance between the detector and the reflector/reflector panel.
During this adjustment process, the detector, being connected to a control panel, signals a fault mode. After
pressing the START push button and adjusting the distance between the detector and reflector/reflector
panel, the detector enters a supervision mode.
Note:
The detectors should not be exposed to direct sunlight operation.
The detector/reflector alignment with a help of a laser beam should be carried out in a dark room.

Fig. 2. DOP-6001 detector during optical path alignment


IK-E343-001E 7

6 OPERATING CONDITIONS AND MAINTENANCE

The DOP-6001 smoke detector long-lasting operation, especially in dusty premises, may result in
contamination (dust, dirt accumulation) of the optical part of the detector and of the reflector/reflector
panel. After exceeding a program determined contamination compensation range, the detector transmits a
fault signal to the control indicating the necessity to call a maintenance technician. The detector is still able
to detect fire threat and enter an alarm mode. The contamination caused fault notification entails cleaning
of the reflector/ reflector panel and the detector front plate. After cleaning the above mentioned elements,
the START push button (located inside the detector) should be pressed in order to adjust the detector to
new external conditions. After the adjustment, the detector automatically alters its mode from a fault to a
supervision one.
It is possible to check proper operation of the DOP-6001 detectors installed in fire detecting systems during
their maintenance inspection by concealing partly the detectors optical path. It can be carried out using a
special damping plastic foil with overprints appropriate to the detector three sensitivity levels – 18%; 30%;
50% (Fig. 10). A plastic sheet with overprint consistent with the detector set sensitivity level should be put
on the detector front plate, what should trigger an alarm mode. The DOP-40R detector testing foil with
overprints is included in the service kit.
During renovation or painting works carried out in the premises where detectors are installed, the
detector and reflector/ reflector panel should be taken out. Detectors which are damaged in the time of
painting and renovation works due to a fault of persons, who execute them, are not subject to warranty
repairs.

7 SAFETY CONDITIONS
7.1 Repairs and maintenance
Any maintenance works or periodic inspection shall be executed by skilled personnel employed by
companies being authorised or trained by POLON-ALFA. Any repairs must be carried out by the
manufacturer. POLON-ALFA bears no responsibility for the operation of any apparatus being serviced and
repaired by unauthorised personnel.

7.2 Works at height


Any detector installation works carried out at height must be executed with particular care utilising tools
and machinery in good working condition. Special attention shall be given to the stability of ladders,
platforms, etc. Any electric tool shall be used strictly obeying the safety rules specified in the manufacturer
instruction manuals.

7.3 Anti-dusting eye protection


It is obligatory to use protective anti-dusting glasses and masks during detector installation works that
produce high amount of dust, such as hole drilling for detector base mounting on ceilings/walls.

7.4 Eye protection against laser beam operating equipment


During the alignment of the detector optical path with the reflector/reflector panel using a laser viewfinder,
special eye protection against direct laser exposure (3R laser equipment class) must be provided.

8 STORAGE AND TRANSPORT


The detectors should be stored in closed premises at ambient temperature ranging from 0 oC to +40 oC and
relative humidity up to 80 % at +35 oC, free from volatile sulphur compounds as well as acid and alkaline
8 IK-E343-001E

vapours. The detectors should not be exposed to direct sun; heating devices should not directly influence
the detectors or their packing.
The detectors transportation should be carried out in transport packing using any transport means and
obeying the transport recommendations given on the packages and securing protection against possibility
of mechanical damage and impact of temperatures lower than –40 oC and higher than +70 oC and relative
humidity higher than 95 %.

9 DESIGN RECOMMENDATIONS
The DOP-6001 beam smoke detector operates properly, similarly to all other smoke detectors, in case it is
installed at the height not exceeding 12 m. When it is mounted higher (up to 20 m), another row of
detectors shall be provided at an intermediate level, with adequately larger number of detectors.
Maximum width (2D) of an area protected by one detector depends on the room height, according to the
following table:

Height Operation radius Distance from ceiling

H D At gradient up to 20 ° At gradient over 20 °

Up to 6 m 6m 0.2 m to 0.5 m 0.3 m to 0.5 m

From 6 to 12 m 6.5 m 0.3 m to 0.7 m 0.4 m to 1.0 m

Over 12 m 7m 0.6 m to 0.9 m 0.8 m to 1.2 m

The maximum area protected by one detector in case the detector/reflector panel distance is 100 m for the
ceiling height at 10 m amounts to (2D x 100 m) ca. 1300 m 2, so the detector can replace a dozen of spot
smoke detectors.
The distance between the detector IR beam and a side wall of room should not exceed D value and
between two adjacent detector beams – 2D. The distance from the IR beam to any obstacle (e.g. a wall,
perpendicular to a side wall) shall not be smaller than 0.5 m.
The beam detector should constantly “see” the co-operating reflector, it is necessary to install it in such a
way that its optical path is never – even temporarily – concealed by a moving object or equipment, such as
cranes, hoists, etc. In the premises where people stay, the minimum installation height should amount to
2.7 m (so that outstretched upwards arms do not disturb the optical path). This limitation is not valid in the
case of low, long or narrow spaces where people do not stay, e.g. cable channels, spaces above hanging
ceilings, etc.

NOTE: The data listed in the table, especially the D operation radius value, which depends on a roof height
come out from the calculations of the proportion of the beam detector arrangement versus spot detectors
installed in a fire test chamber and comply with the data pursuant to VdS 2095:2005.
It differs from the data stated in the PKN-CEN/TS 54-14:2006 technical specification in which the D radius is
the same for all heights and is equal to 7.5 m.
IK-E343-001E 9

Fig. 3. DOP-6001 design and overall dimensions

Note:
Only one detector (without an end-of-line resistor) can be installed in a conventional detection line,
therefore no line output to the next detector is provided.
10 IK-E343-001E

Fig. 4. DOP-6001 detector installation wires connection

Fig. 5. DOP-6001 detector internal connections and output terminals diagram


IK-E343-001E 11

Declared sensitivity levels:


- jumper in position 50 % – low sensitivity
- jumper in position 30 % – medium sensitivity
- jumper in position 18 % – high sensitivity
In the case of the POLON 4000 addressable system, a sensitivity threshold is declared in the control
panel and all jumpers should be taken out.
Interoperating line declaration:
- no jumper – POLON 4000 system addressable line
- jumper in ADC1 position – TELSAP side line behind ADC1 adapter
- jumpers in ADC38 and ADC1 position – ALFA 3800 side line behind ADC1 adapter
- jumpers in ADC38 and ADC1 position – IGNIS 1000 or CSP-35 system conventional line.
Fig. 6. Jumpers for detector operation declaration

Fig. 7. E39-R8 prism reflector


12 IK-E343-001E

Fig. 8. Reflector panel


IK-E343-001E 13

Fig. 9. DOP-6001 detector testing foil with overprints


14 IK-E343-001E

Fig. 10. Reflector panel assembly

IK-E343-001E/03.2012/04.2012

You might also like