AVENAR detector 4000 is a new range of automatic fire In the case of the optical and chemical sensor, the
detectors featuring a superb accuracy and swiftness in response threshold (drift compensation) is actively
detection. The versions with two optical sensors adjusted. Manual or time-controlled switch-off of
(dual‑optical) are able to detect the lightest smoke. individual sensors is possible for adjustment to
The range includes versions with rotaries, manually extreme interference factors.
and automatically addressable, and versions without
Optical sensor (smoke sensor)
rotaries for automatic address setting.
The optical sensor uses the scattered-light method.
Functions An LED transmits light to the measuring chamber,
where it is absorbed by the labyrinth structure. In the
Sensor technology and signal processing event of a fire, smoke enters the measuring chamber
The individual sensors can be configured in the and the smoke particles scatter the light from the LED.
FSP-5000-RPS programming software. The amount of light hitting the photo diode is
All sensor signals are analysed continuously by the converted into a proportional electrical signal.
internal evaluation electronics (ISP - Intelligent Signal The dual-optical versions use two optical sensors with
Processing) and are linked with each other via an different wavelengths. The Dual-Ray technology works
inbuilt microprocessor. The link between the sensors with an infrared and a blue LED so that lightest smoke
means that the combined detectors can also be used is detected fast and reliably (TF1 and TF9 detection).
where light smoke, steam or dust must be expected
during the course of normal operation. Thermal sensor (temperature sensor)
A thermistor in a resistance network is used as a
Only if the signal combination corresponds to the
thermal sensor from which an analog-digital converter
characteristics of the application site, selected during
measures the temperature-dependent voltage at
the programming, the alarm is triggered automatically.
regular intervals.
This results in less false alarms.
Depending on the specified detector class, the
In addition, the time of the sensor signals on fire and
temperature sensor triggers the alarm status when the
fault detection is analysed, which leads to high
maximum temperature of 54 °C or 69 °C is exceeded
detection reliability for each individual sensor.
2 | AVENAR detector 4000
(thermal maximum), or if the temperature rises by a • Fault indication if heavy contamination is detected
defined amount within a specified time (thermal (instead of triggering a false alarm)
differential). In the event of wire interruption or short-circuit,
integrated isolators maintain the functional security of
Chemical sensor (CO gas sensor) the LSN loop.
The main function of the gas sensor is to detect
In the event of an alarm, individual detector
carbon monoxide (CO) generated as a result of a fire,
identification is transmitted to the fire panel.
but it will also detect hydrogen (H) and nitrous
monoxide (NO). The sensor signal value is proportional Further characteristics
to the concentration of gas. The gas sensor delivers • A red flashing LED visible 360° indicates the alarm.
additional information to effectively suppress • Connection to a remote indicator is possible.
deceptive values. • The strain relief for cables in false ceilings prevents
Since the service life of the gas sensor is limited, the C the cables from being unplugged accidentally from
sensor shuts down automatically after a maximum of 6 the terminals after installation. The terminals for
cable cross-sections up to 2.5 mm2 are very easily
years of operation. The detector will then still operate
accessible.
as a multi-sensor detector with dual-optical and
• The detectors have a dust-repellent labyrinth and cap
thermal sensor. It is recommended to exchange the
construction. The chamber maid plug (an opening
detector immediately in order to keep the higher with closing plug) on the bottom is used to clean the
detection reliability of the version with C sensor. optical chamber with compressed air (not required
Improved LSN features for the heat detector).
AVENAR detector 4000 offers all the features of the • The detector bases no longer have to be directed due
improved LSN technology: to the centralized position of the individual display.
• Flexible network structures, including T‑tapping They also have a mechanical removal lock (can be
without additional elements (no T-tapping feasible for activated and deactivated).
versions without rotaries)
Certifications and approvals
• Up to 254 LSN improved elements per loop or stub
line
Region Regulatory compliance/quality marks
• Automatic or manual detector addressing, with or
without auto-detection Europe CPR 0786-CPR-21402 FAH-425-T-R
• Power supply for connected elements via LSN bus
• Unshielded fire detection cable can be used CPR 0786-CPR-21403 FAP-425-DO-R
• Cable length up to 3000 m (with LSN 1500 A) CPR 0786-CPR-21405 FAP-425-DOTC-R
• Backwards compatibility to existing LSN systems and
central units CPR 0786-CPR-21404 FAP-425-DOT-R
• Monitoring of environmental electromagnetic impact CPR 0786-CPR-21398 FAP-425-O
for fast root-cause analysis (EMC values are displayed
on the panel) CPR 0786-CPR-21399 FAP-425-O-R
In addition, the range offers all the established CPR 0786-CPR-21400 FAP-425-OT
benefits of LSN technology. The panel programming
software can be used to change the detection CPR 0786-CPR-21401 FAP-425-OT-R
characteristics of the respective room utilization. Each Germany VdS G214100 FAP-425-O
configured detector can provide the following data:
• Serial number VdS G214099 FAP-425-O-R
• Contamination level of the optical section VdS G214098 FAP-425-OT
• Operating hours
• Current analog values VdS G214097 FAP-425-OT-R
– Optical system values: current measured value of VdS G214101 FAH-425-T-R
the scattered light sensor; the measuring range is
linear and shows different degrees of pollution, VdS G214104 FAP-425-DO-R
from slight to heavy. VdS G214103 FAP-425-DOT-R
– Contamination: the contamination value shows
how much the current contamination value has VdS G214102 FAP-425-DOTC-R
increased relative to the original condition.
VdS G119016 FAP-425-DOTC-R
– CO value: display of the currently measured
value. VdS G119017 FAP-425-O-R
The sensor is self-monitoring. The following errors are
VdS G119018 FAP-425-OT-R
indicated on the fire panel:
• Fault indication in the event of the failure of the VdS G119019 FAH-425-T-R
detector electronics
Europe CE FAP/FAH/FAD-425
• Continuous display of contamination level during
service CE FAP-425
3 | AVENAR detector 4000
Limits
Heed local guidelines. They overrule the following
limits.
Monitoring area
• FAH-425-T-R Max. 40 m2
Ordering information
MSC 420 Base extension with damp room sealing MH 400 Heating element
Extension for detector bases with surface-mounted usable at locations where the functional safety of the
cable feed detector might be impaired by condensation
Order number MSC 420 Order number MH 400
FNM-420-A-BS-RD Base sounder indoor, red TP4 400 Label plate small
analog addressable base sounder for indoor use, red, Support plate for detector identification.
delivered with cover Delivery unit is 50.
Order number FNM-420-A-BS-RD Order number TP4 400
Represented by:
The FMC-210-DM Double-action Call Points are used This does not reset the alarm on the fire panel.
for manual triggering, and can be used in the Local Individual call point identification with display of the
SecurityNetwork LSN and LSN improved. Form H call point address on the fire panel ensures the quick
Manual Call Points are designed for outdoor location of the triggered call point.
deployment, form G Manual Call Points are designed
Variants
for indoor deployment.
The designs of the manual call points for outdoor and
Functions indoor use are identical. The manual call points for
indoor use (form G) are available in red, blue, yellow,
5 and green. The manual call points for outdoor use
1 1
(form H) are available in red and blue.
Form H manual call points are equipped with an
2
especially resistant PC board layered with parylene.
4
Notice
3 The key must be ordered separately.
3 2
Improved LSN features
In the event of an alarm, the glass pane (2) is broken The manual call points offer all the features of the
first, then the manual call point (3) is pressed hard. improved LSN technology:
This activates the microswitch for alarm triggering and • Flexible network structures, including T-tapping
the indicator LED (4) blinks. A mechanism holds the without additional elements
pressed call point down. • Up to 254 LSN improved elements per loop or stub
line
The manual call point can be reset with the reset lever
• Automatic or manual detector addressing selectable
(5) or by closing the door of the manual call point (1).
via rotary switch, in each case with or without auto-
The indicator LED (4) goes out.
detection
2 | FMC‑210‑DM Double Action Call Points
FMC‑210‑DM‑G EN 54-11:2001/A1:2005, EN
‑R 54-17:2005
FMC‑210‑DM‑H EN 54-11:2001/A1:2005, EN
‑R 54-17:2005
Installation/configuration notes
Current consumption (mA) 0.26 FMC-210-DM-G-Y Manual call point indoor, yellow
Analog addressable manual call point with glass pane
Mechanics for indoor use, indirect alarm triggering (type B),
yellow
Dimensions W x H x D (mm) 135 x 135 x 40 Order number FMC-210-DM-G-Y
Housing material Plastic ASA FMC-210-DM-H-B Manual call point outdoor, blue
Colors Red RAL 3001 Analog addressable manual call point with glass pane
Blue RAL 5005 for outdoor use, indirect alarm triggering (type B),
Yellow RAL 1003 blue
Green close to RAL Order number FMC-210-DM-H-B
6002
FMC-210-DM-H-R Manual call point outdoor, red
Weight (g) Approx. 235 Analog addressable manual call point with glass pane
for outdoor use, indirect alarm triggering (type B), red
Environmental Order number FMC-210-DM-H-R
Accessories
Degree of protection (IEC IP 54
60529) Form H FMX-FSO-LSN FMX-FSO-LSN foilset operating panel
MCP
Degree of protection (IEC IP 52 For the labeling field of manual call points of the series
60529) Form G FMC-210, 1 unit = 10 sheets
Order number FMX-FSO-LSN
FMC‑210‑DM‑G‑R EN 54-11
Represented by:
u Immediate synchronization
The Base Sounders Indoor are used for signaling an Region Regulatory compliance/quality marks
alarm directly at the fire location. They can be
employed either as base sounders or stand-alone Europe CPR 0832-CPR-F1919 FNM-420-A-BS-
RD_FNM-420-A-BS-WH
sounders.
Germany VdS G 210003 FNM-420-A-BS-WH/-RD
Functions
Europe CE FNM-420-A-BS-WH, FNM-420-A-BS-RD
The device allows to select 32 types of alarm and
Poland CNBOP 0913/2011 FNM-420-A-BS-RD -A-BS-
evacuation tones (including DIN tone 33404, part 3) WH
for different requirements.
You can adjust the sound pressure by five levels Ukraine MOE UA1.016.0113307-11 FNM-420-A-BS-
WH_FNM-420-A-BS-RD
according to the operational environment. Depending
on the tone type and volume set, the sound pressure Installation/configuration notes
varies between 65 dB(A) and 92.1 dB(A).
Sounders of the same LSN loop and with the same • The device is intended for indoor use.
tone type provide immediate synchronization. The • The current consumption depends on the tone type
device maintains LSN loop functions in the event of selected and is maximum 3.85 mA.
wire interruption or short-circuit thanks to two • Devices with different LSN settings (classic and
integrated isolators. improved) cannot be synchronized.
Change of the device settings can be done in the • The maximum number of devices on each loop
FSP-5000-RPS programming software. depends on the cable diameter and the total current
of the loop.
Certifications and approvals Use the Bosch Planning Software for reliable loop
planning.
Complies with • The base sounder can be operated with an FNS-420-
• EN 54-3:2001 R LSN Strobe or an automatic detector from the
• EN 54-17:2005 420/425 series.
2 | FNM‑420‑A‑BS Base Sounder, Indoor
Connections (inputs/outputs) 0,28 mm² to 2,5 mm² FNM-420-A-BS-RD Base sounder indoor, red
analog addressable base sounder for indoor use, red
Dimensions (Ø x H) Order number FNM-420-A-BS-RD
Represented by:
u Quick installation
Region Certification
∅ 128 mm
Europe CE FNS-420-R LSN
MSS 401 / MSS 400
Installation/configuration notes
∅ 120 mm
MS 400
• The device is not certified to EN 54-23. It is not
suitable for fire alarm use within the EU.
Functions • The device can be connected exclusively to the fire
panels FPA-5000 and FPA-1200.
The LSN Strobe can be used with the FNM-420-A-BS /
• The device cannot be used with the MSS series
FNM-420U-A-BS Base Sounders or the MSS 400 / MSS
stand‑alone or conventional sounders.
401 LSN Detector Base Sounders providing a
2 | FNS‑420‑R LSN Optical Indication, Red
Parts included
Quant. Component
1 FNS‑420‑R LSN Strobe, Red
Technical specifications
Electrical
Mechanical
Dimension (H x W) 40 x 99.5 mm
Weight 67 g
Environmental conditions
Ordering information
Represented by:
technology.
Position Description
Functions
RΣ Overall line resistance with RΣ = RL/2 + RL/2 + REOL
Monitoring functions of the inputs
The FLM‑420‑I8R1‑S Octo‑input Interface Module RL/2 Line resistance
provides two monitoring functions:
The following line conditions will be reliably detected
1. Monitoring of a line by an EOL resistor
if the overall line resistance is within the specified
2. Monitoring of a potential‑free contact
range:
The monitoring functions of the eight inputs can be
selected individually by setting the corresponding Line condition Overall line resistance RΣ
addresses.
Standby 1500 Ω to 6000 Ω
Line monitoring with EOL resistor
The monitoring with EOL resistor can be activated Short circuit < 800 Ω
individually for each of the inputs. The EOL resistor
has a standard resistance of 3.9 kΩ. Interruption > 12 000 Ω
The interface module detects
2 | FLM‑420‑I8R1‑S Octo-input Interface Module with Relay
NC COM COM NO
IN+
+U
REL
0V
The interface module evaluates the operating
a1-
conditions "open" or "closed". The normal operating
LSN
b1+
condition can be programmed for each input. Contact
+ 1 -
SHIELD
monitoring has a pulse intensity of 8 mA.
LSN
+ 2 -
Change‑over contact relay
+U
The maximum contact load (resistive load) is 2 A /
0V
+ 3 -
30 V DC or 0.5 A / 42.4 V AC.
a2-
LSN
b2+
Address switches
+ 4 -
The addresses of the interface modules are set by
IN
rotary switches.
+ 5 -
In case of a connection to the fire panels FPA‑5000
and FPA‑1200 (improved version LSN mode), the
+ 6 -
operator can select automatic or manual addressing
with or without auto-detection. In LSN mode classic,
+ 7 -
connection to the fire panels BZ 500 LSN,
UEZ 2000 LSN and UGM 2020 is possible.
+ 8 -
Addre Operating mode
ss (A)
Parts included
Technical specifications
Electrical
LSN input voltage (V DC) 15 … 33
Inputs, independent 8
Contact load: Max. switching capacity (A / V DC; A / V AC) 2 / 30; 0.5 / 42.4
Min. switching capacity (mA / mV DC; mA / mV AC) 0.01 / 10; 0.01 / 10
Max. frequency (Hz) 100
Mechanical
4 | FLM‑420‑I8R1‑S Octo-input Interface Module with Relay
Environmental
Operating temperature (°C) -20 …+65
System limits
Max. cable length, not electrically isolated from LSN in total (m) 500
Ordering information
Represented by:
North America: Europe, Middle East, Africa: Asia-Pacific: China: Latin America and Caribbean:
Bosch Security Systems, Inc. Bosch Security Systems B.V. Robert Bosch (SEA) Pte Ltd, Security Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
130 Perinton Parkway P.O. Box 80002 Systems 203 Building, No. 333 Fuquan Road Via Anhanguera, Km 98
Fairport, New York, 14450, USA 5617 BA Eindhoven, The Netherlands 11 Bishan Street 21 North IBP CEP 13065-900
Phone: +1 800 289 0096 Phone: + 31 40 2577 284 Singapore 573943 Changning District, Shanghai Campinas, Sao Paulo, Brazil
Fax: +1 585 223 9180 Fax: +31 40 2577 330 Phone: +65 6571 2808 200335 China Phone: +55 19 2103 2860
security.sales@us.bosch.com emea.securitysystems@bosch.com Fax: +65 6571 2699 Phone +86 21 22181111 Fax: +55 19 2103 2862
www.boschsecurity.us www.boschsecurity.com apr.securitysystems@bosch.com Fax: +86 21 22182398 latam.boschsecurity@bosch.com
www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com
Description Connection
REL1 NC | COM | NO Relay (NC, COM and NO contact)
LSN b1+ | a- | b2+ LSN (in/out)
www.boschsecurity.com
2 | FLM‑420‑RLV1 Relay Interface Modules Low Voltage
FLM-420-RLV1-E 1 Relay Interface Module Low Voltage, type • FLM-420- RLV1-E Approx. 50 mm x 22 mm (Ø x H)
in-built • FLM-420- RLV1-D with Approx. 110 x 110 x 48 mm (W x H x D)
FLM-420- RLV1-D 1 Relay Interface Module Low Voltage, type adapter
DIN rail, with adapter and light pipe Weight Without / with packaging
• FLM-420- RLV1-E Approx. 35 g / 130 g
• FLM-420- RLV1-D Approx. 150 g / 235 g
Technical Specifications
Environmental conditions
Electrical
Permitted operating tempera- -20 °C to +55 °C
LSN ture
• LSN input voltage 15 V DC to 33 V DC (min. to max.) Permitted storage temperature -25 °C to +80 °C
• Max. current consump- 1.75 mA Permitted rel. humidity < 96% (non-condensing)
tion from LSN Classes of equipment as per Class III equipment
Relay (low voltage) Normally closed, common and normally IEC 60950
open contact (NC/COM/NO) Protection class as per IP 30
Contact load (ohm resistive IEC 60529
load) FLM‑420‑RLV1‑E
• Max. switching current • 1 A / 30 V DC
and voltage • 0.5 A / 42.4 V AC Ordering Information
• Min. switching current • 0.01 mA / 10 mV DC
FLM‑420‑RLV1‑E Relay Interface Module FLM-420-RLV1-E
and voltage • 0.01 mA / 10 mV AC
Low Voltage
• Max. frequency AC 100 Hz with 1 relay output, type in-built
Contact load (ohm resistive FLM‑420‑RLV1‑D Relay Interface Module FLM-420-RLV1-D
load) FLM‑420‑RLV1‑D Low Voltage
• Max. switching current • 5 A / 30 V DC with 1 relay output, DIN rail type
and voltage • 0.5 A / 42.4 V AC Accessories
• Min. switching current • 0.1 mA / 100 mV DC
FLM‑IFB126‑S Surface-mounted Housing FLM-IFB126-S
and voltage • 0.1 mA / 100 mV AC
as retainer for the interface modules ser-
• Max. AC frequency 100 Hz ies 420 type DIN rail (-D) or spare housing for
Minimum activation time of the > 20 ms type surface-mount (-S)
connected device
Mechanical
Connections
• FLM-420-RLV1-E 12 screw terminals
• FLM-420-RLV1-D 6 threaded terminals
Permitted wire cross-section
• FLM-420-RLV1-E 0.6 to 2.0 mm2
• FLM-420-RLV1-D 0.6 to 3.3 mm2
Address setting
• FLM-420-RLV1-E 8 DIP switches
• FLM-420- RLV1-D 3 rotary switches
www.boschsecurity.com
4 | FLM‑420‑RLV1 Relay Interface Modules Low Voltage
The FLM‑420‑O1I1 Output-input Interface Modules are • Auxiliary power supply from the fire panel
fitted with one output to control external devices and with • External power supply units.
one monitored input. Input monitoring functions
They are 2‑wire LSN elements for connection to the fire The FLM‑420‑O1I1 Output-input-Interface Module
panels FPA‑5000 and FPA‑1200 and offer the enhanced provides two monitoring functions:
functionality of LSN improved technology. 1. Monitoring of a line by an EOL resistor
2. Monitoring of a potential‑free contact
The input monitoring functions can be selected by setting
the corresponding addresses.
Functions
Line monitoring with EOL resistor
Semi-conductor output
The EOL resistor has a standard resistance of 3.9 kΩ.
The semi-conductor output is electrically isolated from the
The interface module detects
LSN loop and protected against short circuits.
• Standby
POW+ • Triggering in the event of a short circuit
OUT • Triggering in the event of line interruption.
RL/2
IN-
0V Position Description
RΣ Overall line resistance with RΣ = RL/2 + RL/2 + REOL
Functionality of the semi-conductor output
RL/2 Line resistance
Output power supply
The following line conditions will be reliably detected if
The power supply for loads connected to the output can
the overall line resistance is within the specified range:
be selected as:
www.boschsecurity.com
2 | FLM‑420‑O1I1 Output-input Interface Modules
Line condition Overall line resistance RΣ - Suitable for installation on a DIN-rail according to
EN 60715 with included adapter and
Standby 1500 Ω to 6000 Ω - For the FLM‑IFB126‑S surface-mounted housing.
Short circuit < 800 Ω
Interruption > 12.000 Ω
Certifications and Approvals
Contact monitoring
RL/2 Complies with
IN- • EN 54-17: 2005
IN • EN 54-18: 2005 + AC:2007
RL/2
IN+ Region Certification
The interface module evaluates the operating conditions Germany VdS G 209070 FLM-420-O1I1-E
"open" or "closed". The normal operating condition can be G 209069 FLM-420-O1I1-D
programmed for each input. Contact monitoring has a Europe CE FLM-420-O1I1-E
pulse intensity of 8 mA.
FLM-420-O1I1-D
Adress switches
CPD 0786-CPD-20714 FLM-420-O1I1-E
The address of the interface module is set using:
0786-CPD-20715 FLM-420-O1I1-D
• DIP switches in case of the FLM‑420‑O1I1‑E
Hungary TMT TMT-36/2010 szamu FLM-420-O8I2-S,
• Rotary switches in case of the FLM‑420‑O1I1‑D.
In improved version LSN mode, the operator can select FLM-420-O1I1-E, FLM-420-O1I1-D,
FLM-420-RLE-S
automatic or manual addressing with or without auto-
detection. MOE UA1.016-0070232-11 FLM-420-O1I1-
E
Address Address Mode UA1.016-0070263-11 FLM-420-O1I1-
rotary DIP D
switches switches
000 0 Loop/stub in improved version LSN mode
with automatic addressing (T-taps not pos-
sible) Installation/Configuration Notes
001 1 - 254 Loop/stub/T-taps in improved version LSN FLM‑420‑O1I1‑D
- mode with manual addressing
254
CL 0 0 255 Loop/stub in LSN mode classic
POW+ 0V POW+ OUT- IN- IN+
LSN features POWER IN OUT IN
line
• Unshielded cable can be used
Interface variants
The Output-input Interface Modules are available in
various designs: Description Connection
IN IN- | IN+ Input 1
• FLM‑420‑O1I1‑E in-built version:
- Suitable for standard device boxes according to OUT POW+ Reference potential (+)
EN 60670 and OUT- Output (switched negative potential)
- For a space-saving installation in all devices. POWER IN POW+ | 0V Power supply output
• FLM‑420‑O1I1‑D DIN-rail version:
LSN b1+ | a- | b2+ LSN (incoming / outgoing)
FLM‑420‑O1I1 Output-input Interface Modules | 3
+U
+
UEZ 2000 LSN and UGM 2020, the limitation to 500 m
applies to each Network Processing Converter (NVU).
0V
a1-
Parts Included
IN+
Type Qty. Component
FLM-420- O1I1-E 1 Output-input Interface Module, in-built ver-
Description Connection
sion
POWER IN POW+ | 0V- Power supply (interface module and
FLM-420-O1I1-D 1 Output-input Interface Module, DIN‑rail ver-
output)
sion, with adapter and light pipe
OUT POW+ Reference potential (+)
OUT- Output (switched negative potential)
IN -|+ Input Technical Specifications
LSN SHIELD Cable shielding (if available)
Electrical
0V | +U | +U Auxiliary power supply (support
points to loop through) LSN
LSN b2+ | a2- | b1+ | a1- LSN (incoming / outgoing)
• LSN input voltage 15 V DC to 33 V DC
• Can be connected to the fire panels FPA‑5000 and • Max. current consumption 1.9 mA
FPA‑1200. from LSN
• Programming is done with the programming software
Output
of the fire panel.
• The LSN connection is established by the two wires of • Max. switchable voltage of 30 V DC
the LSN line. semi-conductor output
• The power supply for the output is either fed by the • Max. switchable output 700 mA (depending on external power
auxiliary power supply from the fire panel or by an current supply)
external power supply unit. External power supplies
must be free-of-ground. • External power supply 5 V DC to 30 V DC
• The outputs OUT/OUT- are switched against the Input
negative potential of the interface module (POWER IN/ Line monitoring with EOL
0V). The positive potential (OUT/POW+) is either
supplied by the auxiliary power (AUX) from the fire • EOL resistor Nominal 3.9 kΩ
panel or by an external power supply unit. • Overall line resistance RΣ • Standby: 1500 Ω to 6000 Ω
• The maximum switchable voltage of the semi- with RΣ = RL/1 + RL/ • Short circuit: < 800 Ω
conductor output is 30 V DC. The maximum 2 + REOL • Line interruption: > 12.000 Ω
switchable current is 700 mA (depending on the
external power supply). Contact monitoring
• The activation of the input IN has to be carried out • Max. current strength 8 mA
electrically isolated from LSN (e.g. with relay contacts, (current pulse)
pushbutton, etc.). Minimum activation time of the 3.2 s
• The input must have a minimum activation time of input
3.2 s.
• A maximum cable length of 3 m is permitted per input
and output.
www.boschsecurity.com
4 | FLM‑420‑O1I1 Output-input Interface Modules
Description Connection
IN1+ | IN1- Input 1
IN2+ | IN2- Input 2
LSN b1+ | a- | b2+ LSN (in/out)
www.boschsecurity.com
2 | FLM‑420‑I2 Input Interface Modules
Position Description
RΣ Overall line resistance with RΣ = RL/2 + RL/2 + REOL
RL/2 Line resistance
www.boschsecurity.com
4 | FLM‑420‑I2 Input Interface Modules
Description Connector
NO / C / NC Relay 1
NO / C / NC Relay 2
b1+ / a- / b2+ LSN
FB2+ Relay 2, feedback +
www.boschsecurity.com
2 | FLM‑420‑RHV Relay High Voltage Interface Modules
Functions
Certifications and Approvals
Interface module variants
Two different versions of the interface module are Complies with
available: • EN54-17:2005
• FLM‑420‑RHV‑S for surface-mounting with housing • EN54-18:2005
• FLM‑420‑RHV‑D for installation on a DIN rail with
adapter. Region Certification
Relay and FAN function Germany VdS G 207053 FLM-420-RHV-S; FLM-420-
The interface modules have two change-over contact RHV-D
relays (Form C) for the controlled activation of external Europe CE FLM-420-RHV/-S/-D
elements. CPD 0786-CPD-20376 FLM-420-RHV
The relay contacts are protected with 10 A fuses which MOE UA1.016-0070267-11 FLM-420-RHV-
are built into the module. S_FLM-420-RHV-D
The maximum relay contact loads are (values apply to
resistive load):
• 10 A at 120 V AC / 230 V AC / 24 V DC Installation/Configuration Notes
• 6 A at 30 V DC.
• Can be connected to the fire panels FPA‑5000 and
Rotary switches FPA‑1200 and the classic LSN fire panels BZ 500 LSN,
The rotary switches can be used to select either the relay UEZ 2000 LSN and UGM 2020.
function (RLHV) or the fan control function (FAN) as well • National standards and guidelines must be taken into
account during the planning stage.
as to define the address of the interface module.
• It is not permitted
The following settings are possible: - to operate the relays with different voltages (high
voltage and low voltage)
Function selection (rotary switch 1) - to place two different AC line voltage phases on
RLHV Relay function used to control external elements the relay contacts.
FAN Fan control function
• The monitoring function is deactivated at the time of
delivery, and can be activated via the panel software.
Address setting (rotary switches 1-3) • The surface-mounted housing has two cable ducts on
000 Loop/stub in LSN mode improved version with automatic opposite sides:
addressing (T‑tap system not possible) - 2 x 2 pre-punched cable ducts for diameter up to
21 mm/to 34 mm (for conduits)
0 0 1 - 254 Loop/stub/T-tap system in LSN mode improved version
with manual addressing - 2 x 4 rubber bushes for inserting cables with
diameters of up to 8 mm.
CL 0 0 Loop/stub in classic LSN mode • In addition, there are cable ducts on the base of the
Features of LSN improved version surface-mounted housing:
The interface modules in the 420 series offer all the
- 1 x pre-punched cable ducts for diameter up to
21 mm (for conduit)
features of improved LSN technology: - 2 x 4 rubber bushes for inserting cables with
• Flexible network structures including T‑tapping diameters of up to 8 mm.
without additional elements • For a fire system operation according to EN 54‑2, the
• Up to 254 LSN improved elements per loop or stub interface modules used for the activation of fire
line protection equipment and whose outputs are not
• Unshielded cable can be used monitored, must be installed directly next to or within
• Downwards compatible with existing LSN systems and the device which shall be activated.
control panels.
Further performance characteristics
The status of the two relays is shown via a red and a
green LED.
FLM‑420‑RHV Relay High Voltage Interface Modules | 3
www.boschsecurity.com
4 | FLM‑420‑RHV Relay High Voltage Interface Modules
Patol Limited, Archway House, Bath Road, Padworth, Reading, Berkshire, RG7 5HR Tel: +44 (0)1189 701 701 Email: Info@patol.co.uk D1178-7
LDM-519-DDL
Digital Interface with Distance Display
There are three principle modes of supply & signalling operation :-
Figure 1 shows a typical minimum system where a discrete 24 Vdc supply is
Specification
employed. The repeat contacts may be employed to signal an alarm panel and/or Dimensions 105mm x 86mm x 58mm
initiate control systems.
LDM-519-DDL
(WHD):
4 to 20mA
FIRE
ALARM
REPEAT
CONTACTS
(2 SET)
Character Height: 8.5mm
LINEAR HEAT DETECTOR INTERPOSING FAULT
CABLE
FAULT
REPEAT
CONTACTS
(2 SET)
Unit Accuracy: +/- 1% (+/- 1 digit)
EOL TERMINATOR JB
SUPPLY 24Vdc
LHDC Tolerance: +/- 3%
Figure 2 shows a simple configuration with the unit directly connected to a fire Lock Time: 3s
panel trigger circuit.
LDM-519-DDL CONVENTIONAL
Voltage: 14 - 30Vdc (2 wire mode)
CIRCUIT
FIRE 20 - 30Vdc (relay mode)
Figure 2 CONTROL
PANEL > 10Vdc - Latched Fire
LINEAR HEAT DETECTOR INTERPOSING
ALARM
TRIGGER
< 6Vdc - Reset
CIRCUIT
CABLE
FAULT EOL &
ALARM Current Normal: < 1.5mA (2 wire mode) *
EOL TERMINATOR JB SUPPLY
RESISTORS
< 11mA (with Fault relay)
* Plus user defined monitoring circuit
Current Fire: < 13mA (2 wire mode)**
Figure 3 shows the configuration when an integral ADDRESS LOOP interface < 29mA (with both relays)***
module is fitted. Connection between the LDM-519-DDL and the addressable loop ** Plus user defined Fire (trigger) load.
module is conventional circuit connection of Fig.2. *** Plus 4 to 20mA loop current if used.
LDM-519-DDL Current Fault: < 700µA
Figure 3
Relay Contact: 1A @ 24Vdc / 120Vac
ALARM
LINEAR HEAT DETECTOR INTERPOSING
FAULT 2 WIRE ADDRESS LOOP
CABLE
Ordering Information
EOL TERMINATOR JB SUPPLY
ADDITIONAL ANALOGUE
LOOP ADDRESSABLE
INTERFACE FIRE ALARM
CIRCUIT CONTROL PANEL
Description Part Number
Notes: Configurations for Fig 2 & 3, is dependant on the voltage and current LDM-519-DDL 700-451
specifications of the LDM-519-DDL being compatible with the monitoring technique LDM-519-DDL-G 700-451(G)
and electrical characteristics of the Control Panel / Zone Monitor Unit. Galvanic Isolator - MTL 700-705
Fig 2 & 3 configurations are not suitable for LDM-519-DDL(G) or LDM-519-DDL(Z). Galvanic Isolator P+F 700-706
For detailed connections of IS circuits, contact Patol Ltd LDM-519-DDL-Z 700-451(Z)
Connections Zener Barrier - MTL 700-702
19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35/36
- + NO NC COM NO NC COM NO NC COM NO NC COM + - Cabling Used with the following Digital Cables:
A B 4 -20mA Site Zero Nylon 70°C 700-070
Loop Adjust
Output Pot. Nylon S.S* 70°C 700-071
LHDC Fire Relay -Norm. De-energised Fault Relay -Norm. Energised
Nylon 90°C 700-090
Supply Calibrate
Nylon S.S* 90°C 700-091
Fault Fire Trig. Cct. Trig. Cct. Calibrate
Remote
Relay Relay Alarm EOL/Mon. Test
Test Hytrel 180°C 700-180
Reset Zero
0V 24V Enable Enable Resistor Resistor Resistor
Adjust. Hytrel S.S* 180°C 700-181
- - + + - s c + c + s + s + s + Pot *Stainless Steel Braid
17/18
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Patol Limited, Archway House, Bath Road, Padworth, Reading, Berkshire, RG7 5HR Tel: +44 (0)1189 701 701 Email: Info@patol.co.uk D1178-7
Digital
Linear Heat Detection Cable LHDC
Features
SIL 2 Approved when used with
LDM-519-DIM or LDM-519-DDL module.
UL Listed.
UV and Chemical Resistant.
Early Detection of hazards at temperatures
well below flame point.
Rugged construction—Stainless Steel outer
armour available.
Fixed Alarm Trigger Temperature.
Compatible with many existing zone
monitors / Control Equipment.
Intrinsically Safe Configurable for
Hazardous Areas.
Applications
Cable Tunnels, Ducts & Mezzanines
Escalators & Moving Walkways
The Patol Digital Linear Heat Detection Cable is designed Petro-Chemical Storage Tanks / Rim Seal
Protection
to provide early detection of fire conditions and overheating
in circumstances where other forms of detection would not Paint Shops, Spray Booths & Climate
be viable, either due to an inability to sustain the Chambers
environment requirements or through prohibitive costs. Conveyors - Coal, Wood, Sulphur. etc
Extensive single zonal lengths of the Digital LHDC may be Ceiling Voids & Attic Spaces
installed with the ability to trigger alarms for hot spots Road & Rail Tunnel Carriageways
occurring on very small sections of the overall cable, with
the ability to identify the distance in meters. Nuclear Reactor Plant Areas
The LHDC may be employed in a wide variety of Refrigerated Stores & Cold Rooms
applications but is particularly suited where there is harsh Electrical Control & Switchgear Cabinets
environmental condition, a physical or hazardous Warehouse High Rise Pallet Racking
maintenance access constraint to protect the area, and / or
a requirement to cost effectively install detection in close Oil Rigs & Off Shore Platforms
proximity to the risk(s). Fume Cupboards & Glove Boxes
The primary mechanism of LHDC is that the inner cores Grain Silos & Agricultural Storage
insulating polymers are specially formulated such that the Road / Rail Vehicle Engine Compartments
polymers will plasticizes at a specific temperature, causing
the inner cores to make contact and send a signal to the Steam pipe Leaks & Trace Heating Faults
controller. Product Lines - Flanges, Valves & Pumps
Computer Room under Floor Cable Voids
Patol Limited, Archway House, Bath Road, Padworth, Reading, Berkshire, RG7 5HR Tel: +44 (0)1189 701 701 Email: Info@Patol.co.uk D1179-13
Digital
Linear Heat Detection Cable LHDC
Specification
Cable Construction No. of Cores: 2
Alarm 700-070 = 70°C
Temperature: 700-090 = 90°C
700-180 = 180°C
The Patol Digital PASSIVATED STEEL
Max Ambient 700-070 = 45°C
LHDC comprises of a CONDUCTORS
Temperature: 700-090 = 70°C
twisted pair twin core 700-180 = 150°C
cable. Each core is of Min Operating -65°C
tinned copper coated TEMPERATURE REACTIVE Temperature:
POLYMER INSULATION
spring steel and has a Min Installation -40°C
Temp:
special heat reactive
polymer insulation. OUTER PROTECTIVE SHEATH Outer Sheath: Nylon (70°C & 90°C - Black)*
(NYLON 12 RILSAN) Hytrel (180°C - Violet)*
Stainless Steel Armour Option*
700-090 Shown * UV & Chemical Resistant
Voltage Rating: 150Vdc (Dielectric Test 500Vdc)
Outer Diameter: 4.0mm ± 0.3mm
(Maximum) Stainless Steel Armour 4.5 ± 0.3mm
Weight:
Standard cable 1km reel 21kg
LHDC Digital may be used as a simple Armoured cable 500m reel 19kg
switch to operate a relay etc. However in Approval: UL Listed (180°C Pending)
most installations the minimum
requirement is that the LHDC circuit is
monitored for disconnections (Open Ordering Information
Circuit) by means of an EOL device and Description Part Number
an appropriate fire alarm channel or Nylon 70°C 700-070
address loop interface unit. Nylon S.S* 70°C 700-071
Nylon 90°C 700-090
STAINLESS STEEL ARMOUR Nylon S.S* 90°C 700-091
Nylon 180°C 700-180
700-071 Shown Nylon S.S* 180°C 700-181
*Stainless Steel Armour
Controllers and Termination boxes used with the
Intrinsically Safe Configuration above Digital cables:
LDM-519-DDL 700-451 (SIL 2 Approved)
CONTROL PANEL IS BARRIER LDM-519-DDL-G 700-451(G) (SIL 2 Approved)
LDM-519-DDL-Z 700-451(Z) (SIL 2 Approved)
LDM-519-DDLX 700-471
EOL LDM-519-DIM 700-441 (SIL 2 Approved)
LINEAR HEAT DETECTOR - LHDC
EOL & Through box refer to D1210
TERMINATOR JB INTERPOSING CABLE
If Required
700-451(G) suitable only for use with Galvanic Isolator
700-451(Z) suitable only for use with Zenner Barrier
Patol Limited, Archway House, Bath Road, Padworth, Reading, Berkshire, RG7 5HR Tel: +44 (0)1189 701 701 Email: Info@Patol.co.uk D1179-13
Fire Alarm Systems | Bosch EVAX System - High-rise Applications
Distributed Panels
The Distributed Panels communicate with the Master
Panel through the NetCom Loop. They typically
provide:
• Voice Evacuation Speaker Loops – dedicated data
and audio loops using a minimum of 18 AWG wire
with end-of-line resistors (EOLR).
• Fire Phone Loops – dedicated audio loop using a
minimum of 20 AWG twisted pair wiring with an
EOLR.
• Fan and Damper Loops – data loop using a minimum
20 AWG twisted pair wiring on which up to 32
modules can be attached. Each module provides two
points (one control and one monitor) for a total of 64
points on the circuit.
• Additionally, local Audio Amplifiers can be connected
to the Distributed Panels.
The Bosch Distributed Panels additional provide
specific accessories to support specific functions. The
HMB‑DP provides four audio circuits, the HMB‑DP/P
provides four Fire Phone circuits, and the HMB‑DP‑42
provides 16 audio circuits.
Region Certification
EVB‑BA100 Backup Audio Interface F.01U.201.682 • Type: Two 12 VDC Gel Cell in series
Represented by:
The panel controller is the central component of the The FSP-5000-RPS programming software enables
fire panel. All messages are shown on the color adaption to project- and country-specific
display. The entire system is operated via a touch requirements.
screen. The user-friendly user interface adapts to
various situations. This allows correct operation that is System overview
both simple and clear as well as targeted and intuitive.
B Touchscreen Operating the networked system through virtual buttons and variable display windows
Ethernet interface to
Status overview • •
Simultaneous control • •
Individual control •
Slots for functional modules (max number including slots for LSN 46 46
modules)
Panel redundancy
Network
Environmental
Represented by:
The fire panel allows mixed operation of analog kits also allow installation in 19" racks. Both housing
addressable and conventional technology. It supports types can be extended with up-to four housings to
connecting periphery in either stub or loop topologies. increase the number slots for the functional modules.
Analog addressable fire detectors, manual call points, The panel controller is the central component of the
signaling devices, inputs and outputs are identified fire panel. A color display shows all messages. The
and managed by the fire panel as single elements. As touch screen is for operation of the entire system. The
required by the building structure the peripherals are user-friendly interface adapts to various situations.
grouped software wise in logical zones. This causes correct operation that is simple and clear
The completely modular designed fire panel uses as well as targeted and intuitive.
functional modules that are clicked in a slot on a rail. Panels and keypads of the AVENAR series and of the
The rail provides power and internal communication FPA-5000 series (MPC-xxxx-B and MPC-xxxx-C) can be
to the functional modules. A wide range of functional combined in one panel network using the Ethernet
modules are available providing: addressable loops, and the CAN bus interfaces. The remote keypad is for
conventional zones, inputs and outputs, and decentralized operation of the panel or of the panel
interfaces to various devices. The fire alarm panel can network.
be equipped with 46 functional modules, of which a Integration into large-scale systems can be done by an
maximum of 32 can be analog addressable loop Ethernet interface to the Bosch Hierarchy panel
modules. This results in a tailor-made fire panel (UGM) or to Building Integration System (BIS).
suitable for medium to large size applications. Integration into third party management systems is
Two different types of housings are available to possible with the availability of OPC server and
assemble the fire panel: Software Development Kit.
• Wall mount housing A data interface enables monitoring and full control of
• Frame mount housing Bosch voice alarm systems. This makes the fire panel
The slim wall mount housings are for mounting a complete safety solution.
directly to the wall. Frame mount housings require an The fire panel is configured on a laptop using the
additional frame between the housing and the wall. FSP-5000-RPS programming software. The
The frame lets space for e.g. cabling, media programming software enables further adaptation,
converters, and larger batteries. Special installation e.g. to country-specific requirements and regulations.
Fire Alarm Systems - AVENAR panel 8000 2 | 10
2. Panel controller
X +AU
AU X3 +AU
X2 AU X +AU
X-5 +AU
X-6
OUT
troller or with keypad
1. Functional modules
– Analogue addressable loops: standard or high
performance
– Conventional detection zones
6
8 – Conventional notification zones
– In- and output interfaces
– Serial communication interfaces
7 – LED annunciators
2. Power supply
– Battery capacity
– Battery autonomy: up-to 72 hours standby and
additional 30 minutes alarm condition
5
IN
Alarm indication
OUT
NO2
NC1
NC2
+ - a -b + + - a -b +
C1
C2
3 9
ZONE4
Störung
ZONE3
CZM0004A
RMH0002A
Störung
ANI0016A
F1 F2
• Message type
ZONE2 RELAIS2
Störung Störung
ZONE1 RELAIS1
Störung Störung
• Set standard sensor sensitivity, set alternative display, and you can export the messages.
sensor sensitivity Additionally, you can connect a log printer via a serial
Each function key has a virtual status indicator. interface module for real-time printing incoming
At any time, an operator with sufficient user rights can messages.
control the function keys.
Languages
Overview of evacuation zones and outputs The operator can change the language of the user
At any time, the operator can get a clear overview of interface. A printed quick user guide for each language
each evacuation zone and of each output connected is supplied with the package. Following languages are
to the fire protection equipment. Each zone and each included: English, German, Bulgarian, Croatian, Czech,
output is marked with a programmable text label and Danish, Dutch, Estonian, French, Greek, Hungarian,
a clearly distinctive color reflecting the state: Green Italian, Latvian, Lithuanian, Polish, Portuguese,
shows idle state, power is available. Red shows an Romanian, Russian, Serbian, Slovak, Slovenian,
activation during fire alarm condition, and fuchsia an Spanish, Swedish and Turkish.
activation without a fire alarm condition. Yellow shows
Licenses
a fault or disabled state. An operator with sufficient
The panel controller is delivered with a hard coded
user rights is able to start the evacuation in selected
software license. This software license is implemented
zones and activate outputs connected to the fire
during production and cannot be modified, revoked or
protection equipment through the user interface.
transported. The license defines the maximum panel
Saving and printing messages network size and availability of certain features and
The history log keeps incoming alarms and events interfaces.
internally. The history log has a capacity to store
10000 messages. The messages can be shown on the
Fire Alarm Systems - AVENAR panel 8000 4 | 10
Status overview • •
Simultaneous control • •
Individual control •
Slots for functional modules (max number including slots for LSN 46 46
modules)
Panel redundancy
Network
RML 0008 Relay module For low voltage switching, with eight
A low-voltage changeover contact relays Interface Detection Points
Modules
i Notice
FLM-420/4CON Up to 2
Europe CPR 0786-CPR-21699 AVENAR panel 8000 System limits for each LSN module
• It is possible to combine LSN interface modules,
CE AVENAR panel 8000 | AVENAR keypad LSN detectors and notification appliances on one
8000 loop or stub line.
• For a mixed connection of LSN classic elements and
Installation/configuration notes LSN improved elements, a maximum of
127 elements are permitted.
• The FSP-5000-RPS programming software enables
• The use of unshielded cables is possible.
adaption to project- and country-specific
requirements. The programming software and the • Limits per LSN 0300 module:
associated documentation can be found at – Up to 127 LSN classic elements or 254 LSN im-
www.boschsecurity.com for those with access proved elements can be connected
rights. Information about the programming software – Current consumption of up to 300 mA
is also included in FSP-5000-RPS online help.
– Cable length of up to 1600 m
General planning instructions • Limits per LSN 1500 module:
• Country-specific standards and guidelines must be
considered during planning. – Up to 127 LSN classic elements or 254 LSN im-
proved elements can be connected
• The regulations issued by regional authorities and
institutions (e.g. fire service) must be adhered to. – Up to 1500 mA current consumption if LSN im-
• Please note that standards and guidelines may proved elements are connected
require that a maximum of one function in more – Up to 300 mA current consumption if LSN clas-
than one zone may fail. sic elements are connected
Fire Alarm Systems - AVENAR panel 8000 7 | 10
The distance between the upper edge of the hous- In CAN network, per panel (premium license) 1
ing and the center of the panel controller display is
around 11 cm. For example, if the eye level required In total Ethernet network (premium license) 1
is 164 cm, the housing upper edge installation di-
mension is 175 cm. Triggers (each trigger counts as one sounder group) 244
• For frame installation housings, a clearance of at
least 230 mm is required to the right of the last System limits per fire panel
housing to swivel out the installed housing (e.g. for
connection, maintenance or service). Per fire panel Max. number
• Sufficient space should be left below and next to
Sets, e.g. bypass group 192
the panel for any possible extensions, e.g. for an
These sets include sets which are automatically
additional power supply or an extension housing.
created for each LSN bus.
Building Management System
• If connected to a building management system Functional modules (with panel redundancy) 42
(Bosch Building Integration System BIS) via an
Ethernet interface using an OPC server, the Functional modules 46
following must be noted:
Printer 4
In a multi-building network, it is essential to clarify
with the network administrator whether the net- Alarm counters (external, internal, testing) 3
work is designed for multi-building connections
(e.g. no interference due to differences in ground- Entries in the event database 10000
ing potential).
FSP-5000-RPS configuration interfaces (USB) 1
Technical specifications
General system limits Maximum number of outputs (sounders, controls, etc.) 508
activated in parallel due to the same event
Panels/remote keypads/OPC servers in the Max. number
Configuration limits per fire panel
network
Ethernet / CAN 32 Configuration limits per fire panel (FSP-5000-RPS) Max. number
Timer channels 20
LSN elements Max. number
Time control programs 19
Stand-alone panel 4096
Configuration for a Specific Day 365
Per network panel 2048
Permission levels 4
Total network 32768
User profiles 200
Detection points Max. number Sum counters and counters (in total) 60000
Panel, without panel redundancy 512
Fire Alarm Systems - AVENAR panel 8000 8 | 10
Configuration limits per fire panel (FSP-5000-RPS) Max. number Component Power loss
Exportable objects including counters in the entire 2000 • 7.80 W (4 relays activated + key
panel cluster (without pre-defined system counters) deposit heating active)
Represented by:
Data subject to change without notice | 42008906891 | V6 | December 14, 2020 © Bosch Security Systems 2020
Fire Alarm Systems | FDP 0001 A Dummy Cover Plate
Parts Included
Qty. Components
1 FDP 0001 A Dummy Cover Plate
Ordering Information
FDP 0001 A Dummy Cover Plate FDP 0001 A
For available module slots
www.boschsecurity.com
2 | FDP 0001 A Dummy Cover Plate
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1749611275 | Cur: en-US, V18, 27 Jul 2010
Fire Alarm Systems | Panel Rails
Panel Rails
www.boschsecurity.com
u Plug-and-play rails
The Panel Rail Short and the Panel Rail Long are plug-
and-play rails made from glass-fiber-reinforced plastic CANH
CANL
+24V
GND
MID
Functions MPC
+5V
MID
MID
PRD 0004 A
2 | Panel Rails
24VM ID
C AN L
C AN H
+24V
G ND
M ID CANH
CANL
+24V
GND
+5V
MID
PRS-0002-C/
PRD 0004 A
24VM ID
C AN H
C AN L
+24V
G ND
M ID
RE
120W
Parts included
Type Qt Components
y.
PRS-0002-C 1 Panel Rail Short, for 2 modules
PRD 0004 A 1 Panel Rail Long, for 4 modules
1 Data transmission cable
Technical specifications
Electrical
Mechanics
Environmental conditions
Ordering information
Represented by:
www.boschsecurity.com
2 | BCM‑0000‑B Battery Controller Module
Description Connector
BCM BCM
24V +/- Output max. 2.8 A (battery buffered) 1 2
24V +/- Output max. 2.8 A (battery buffered) BCM BCM BCM BCM
5 6 7 8
MAIN +/- Power supply unit UPS
BCM BCM
MAIN FAULT Input fault, mains 4 3
1
Parts Included
BCM BCM
1 2
Qty. Components
BCM BCM BCM BCM
5 6 7 8 1 BCM-0000-B Battery Controller Module
BCM BCM 1 Cable set with 2 connection cables:
4 3
BCM/battery (90 cm) and battery/battery (17 cm)
Operating/display elements
• 1 green LED Power ON
• 3 yellow LEDs Trouble mains/batt. 1/batt. 2
• 1 key Batteries charge at V < 21 V and cen-
tral units start with battery current
Housing material ABS plastic, Polylac PA-766
(UL94 V‑0)
Housing color Satin finish, anthracite, RAL 7016
Dimensions Approx. 127 x 96 x 60 mm
(5.0 x 3.8 x 2.4 in.)
Weight
• Without packaging Approx. 195 g (6.9 ounces)
• With packaging Approx. 340 g (12 ounces)
Environmental conditions
www.boschsecurity.com
4 | BCM‑0000‑B Battery Controller Module
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T5696668939 | Cur: en-US, V16, 30 Sep 2010
Fire Alarm Systems | UPS 2416 A Universal Power Supply
www.boschsecurity.com
2 | UPS 2416 A Universal Power Supply
1 8
Technical Specifications
Electrical
6 FAULT Mains fault Permitted storage tempera- -20 °C ... 60 °C (-4 °F ... 140°F)
ture
7/8 RTH+ / RTH- Thermal sensor pos./neg.
Permitted relative humidity 95 %, non-condensing
Functions
Ordering Information
The Power Supply is protected against pole reversal and
UPS 2416 A Universal Power Supply UPS 2416 A
overvoltage.
plug-and-play power supply for the entire
The output voltage is monitored and regulated via the power supply to the control panel.
thermal sensor. If there is a fault, the FAULT output drops Accessories
to 0 V. CPB 0000 A Cable BCM/UPS CPB 0000 A
A green LED on the Universal Power Supply indicates Used to connect the BCM‑0000‑B Battery
operativeness. Controller Module to a UPS Power Supply,
cable length 150 cm
Installation/Configuration Notes
• The Power Supply Unit is inserted into a Power Supply
Bracket and is thus immediately ready for operation.
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1748961035 | Cur: en-US, V9, 27 Jul 2010
Fire Alarm Systems | HBC 0010 A Modular Panel Housing for 10 Modules
The HBC 0010 A can accommodate an MPC Operating and System Overview
Display Unit with Panel Controller, up to ten modules, as
7
well as batteries and Power Supplies.
8
The modular configuration means easy extension. 1 to BC M 2 to BC M 1 to N AC 1 to N AC 3 to N AC 5 to N AC 7 to N AC 9
10 A
to N AC 2 to N AC 4 to N AC 6 to N AC 8 to N AC 10
fr om Ba tt 3
25 A
25 A
fr om Ba tt 1 A
10 A 10 A 10 A 10 A
fr om Ba tt 1 B ( para llel)
9
2
10
3
11
4
12
5
13
6
Pos. Description
1 Housing
2 MPC Operating and Display Unit
3 Modules 3-6
4 Modules 7-10
5 Space for 2 batteries
6 Front Door Transparent (optional)
7 HPD 0000 A Power Distributor (optional)
8 Modules 1-2
www.boschsecurity.com
2 | HBC 0010 A Modular Panel Housing for 10 Modules
Pos. Description
9 Panel Rail for modules 1-2
10 Panel Rail for modules 3-6
11 Panel Rail for modules 7-10
12 Power Supply
13 2 x 12 V/28 Ah batteries
Installation/Configuration Notes
• Can be equipped with:
- 1 MPC Operating and Display Unit with Panel
Controller
- 1 PRS 0002 A Panel Rail Short, for 2 modules
- 2 PRD 0004 A Panel Rails Long, each for
4 modules
- HPD 0000 A Power Distributor
- 1 FPO‑5000‑PSB‑CH Power Supply Bracket for
Panel Housings
- 2 x 12 V/28 Ah batteries
• Can be extended with:
- FDT 0001 A Large Front Door Transparent, lock
right side
- FDT 0002 A Large Front Door Transparent, lock
left side
Parts Included
Pos. Description
1 Housing
Ordering Information
HBC 0010 A Modular Panel Housing for HBC 0010 A
10 Modules
for surface-mounting, flush-mounting or in-
stallation in 482.6 mm (19") racks
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1745789579 | Cur: en-US, V14, 27 Jul 2010
Fire Alarm Systems | Power Supply Brackets
www.boschsecurity.com
2 | Power Supply Brackets
Environmental conditions
Ordering Information
FPO-5000-PSB1 Power Supply Bracket FPO-5000-PSB1
for PSS 0002 A and PSB 0004 A
FPO-5000-PSB-CH Power Supply Bracket FPO-5000-PSB-CH
for HCP 0006 A, HBC 0010 A and
HBE 0012 A
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1742095627 | Cur: en-US, V19, 27 Jul 2010
Fire Alarm Systems | UPS 2416 A Universal Power Supply
www.boschsecurity.com
2 | UPS 2416 A Universal Power Supply
1 8
Technical Specifications
Electrical
6 FAULT Mains fault Permitted storage tempera- -20 °C ... 60 °C (-4 °F ... 140°F)
ture
7/8 RTH+ / RTH- Thermal sensor pos./neg.
Permitted relative humidity 95 %, non-condensing
Functions
Ordering Information
The Power Supply is protected against pole reversal and
UPS 2416 A Universal Power Supply UPS 2416 A
overvoltage.
plug-and-play power supply for the entire
The output voltage is monitored and regulated via the power supply to the control panel.
thermal sensor. If there is a fault, the FAULT output drops Accessories
to 0 V. CPB 0000 A Cable BCM/UPS CPB 0000 A
A green LED on the Universal Power Supply indicates Used to connect the BCM‑0000‑B Battery
operativeness. Controller Module to a UPS Power Supply,
cable length 150 cm
Installation/Configuration Notes
• The Power Supply Unit is inserted into a Power Supply
Bracket and is thus immediately ready for operation.
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1748961035 | Cur: en-US, V9, 27 Jul 2010
Fire Alarm Systems | BAT 100 LSN Display Panel
The BAT 100 LSN Display Panel is a universally usable 3 Keys for "LED test" or "buzzer off"
remote parallel display with up to 96 LEDs (e.g. for a
maximum of 96 detector zones). 4 Tamper contact
• EN54-18:2005 Mechanics
FPA-5000
Special features
FPA-1200
LED flash frequency 1.25 Hz
Ordering information
Qty. Component
Technical specifications
Electrics
Operating voltage
Current consumption
• LSN part 3 mA
Represented by:
North America: Europe, Middle East, Africa: Asia-Pacific: China: Latin America and Caribbean:
Bosch Security Systems, Inc. Bosch Security Systems B.V. Robert Bosch (SEA) Pte Ltd, Security Bosch (Shanghai) Security Systems Ltd. Robert Bosch Ltda Security Systems Division
130 Perinton Parkway P.O. Box 80002 Systems 203 Building, No. 333 Fuquan Road Via Anhanguera, Km 98
Fairport, New York, 14450, USA 5617 BA Eindhoven, The Netherlands 11 Bishan Street 21 North IBP CEP 13065-900
Phone: +1 800 289 0096 Phone: + 31 40 2577 284 Singapore 573943 Changning District, Shanghai Campinas, Sao Paulo, Brazil
Fax: +1 585 223 9180 Fax: +31 40 2577 330 Phone: +65 6571 2808 200335 China Phone: +55 19 2103 2860
security.sales@us.bosch.com emea.securitysystems@bosch.com Fax: +65 6571 2699 Phone +86 21 22181111 Fax: +55 19 2103 2862
www.boschsecurity.us www.boschsecurity.com apr.securitysystems@bosch.com Fax: +86 21 22182398 latam.boschsecurity@bosch.com
www.boschsecurity.asia www.boschsecurity.com.cn www.boschsecurity.com
The ATB 420 LSNi may be used to drive LEDs or other Europe CE ATB 420
low current consuming devices to display the status
and events of field devices. Parts included
It is freely programmable according to application
requirements. Quantity Component
The ATB 420 LSNi module has integrated isolators for 1 ATB 420 LSNI Display module
maintaining the function of the elements on the LSN
loop in the event of wire interruptions or shortcircuits. 1 Accessory bag with terminals for
crimping
Notice
For crimping the supplied terminals you need a
LED 16 - LED 1 crimp tool, an upper crimp die and a lower crimp
LED 32 - LED 17 die for conductor cross section 28 to 22 AWG or
22 to 18 AWG.
-+
Technical specifications
The display module has 32 outputs, each with
• 600 Ω resistor Electrics
• 5V
And permanent ground, 5 V are switched. Operating voltage
• LSN part 3 mA
Special features
• other functions All outputs off: 10mA@24V, Output flashing frequency 1.25 Hz
15mA@8V
All outputs on, max. load: Ordering information
65mA@24V, 170mA@8V
ATB 420 LSNI Display module
Mechanics Display module
Order number ATB 420 LSNI
Dimensions (H x W x D) 163 x 60 x 13.5 mm
Weight 50g
Environmental conditions
Represented by:
!) 0 2 5"5"* )1
+) " ) ! 6 * * !
) !
! ! . 7 !
! ! (
* ) ) ! )! !
* ) !
)! !)
$ * )! ,
+ * !
) ! ) * $ ! !
- !) !!
0 *8 1)
. + )! * $ )
/! ) )!
$ + /! /!
)! /! * ! $ -
* ) ! . !8
0 ! " . 8
" )! !
. 8
1 ) ) *2
) . !8
*! *
* !
. 3 *
4 ! !
! )
! " !
* $*
! )
9:;
#&
"
$ A
! !
$ 8 ! " *
" ! "!) = +
! #5 ! ! /! "
)!
) 6 !
! ! &7
47
!) * ) "
* * 5 2 52 53$
+ 2 5 !)
2 "! )
" ! "
$ ! "!
) *
* !
!) ! 5*
* ) !
* ! )
> ! ** ) *
! * 0&71
?:;
*!
*
0
&%
! . 4*>0H)" "8 1
( - % . 4* 9B>H0H)"
" 1
0
= . 4* 9B>I0H)"
1 " 1
! . 4* 9B>H0H)" . 4*>B0?9H)"
" 1 8 &$1
. 4* 9B>I0H)" L . /* "!
0
= " 1 !) !
1 . 4*>B8 &$0H)1 ! ")!
. . /$ ! ) (!
* *! %
J&K K9B>;8+ * * -== =
!==**= =
! **>B
! ")!
H:;
>& */
!)C *! :;IIH'BH'>:9:7 ) BH"9B9B U ! 9B9B
Engineered Solutions - BIS - Automation Engine (AUE) 4.8
Fire protection systems today are most often required Commands can be automated by user-defined rules in
by law, intrusion detection is crucial, and the the BIS state machine (see BIS overview and basic
monitoring of vital building systems like HVAC is package), or invoked manually by right-clicking
essential to keeping an enterprise running. detector icons inside a location map.
This software provides some of the key functions of Like BIS and the other engines, the Automation Engine
building integration - to connect to vital building runs on a standard PC with a Windows operating
systems, to monitor, control and to check for system. The platform can be a single computer, a
malfunctions. client-server structure with a central server and client
Capitalizing on all the common BIS features together workstations, or a federated system with multiple BIS
with its own special functions, the Automation Engine servers, each with their own clients.
allows sytem integrators to tailor an alarm and The Automation Engine supports OPC DA/AE for
security management system to specific requirements. legacy integrations as well as OPC UA (Unified
Architecture) for modern, high-performance and high-
System overview security integrations.
The Automation Engine (AUE) is one of the main
modules in the BIS family. It runs either as the only
engine or in combination with the other engines.
Its main function is to connect, monitor and control
security and safety systems, usually fire and intrusion
panels. However, it is also possible to display live
images in action plans or miscellaneous documents.
For more complex video applications, we advise the
use of the Video Engine or Bosch VMS.
The Automation Engine uses all the general features of
BIS such as display of interactive location maps and
action plans. Alarms received can then be displayed
along with all necessary information and customized
action buttons.
Engineered Solutions - BIS - Automation Engine (AUE) 4.8 2|2
Functions
Installation/configuration notes
Represented by:
Data subject to change without notice | 80835540363 | V1 | November 06, 2020 © Bosch Security Systems 2020
Fire Alarm Systems | FMC‑420RW Single Action Call Points LSN improved
FMC‑420RW Single Action Call Points are used for Resettable single action call points:
manual triggering and can be employed in both the
Local SecurityNetwork (LSN) and the LSN improved 2
version.
Functions 4
Single action call points with glass pane:
1
Represented by:
The FAD-420-HS-EN Duct detector housing with base C,D Mounting flange for sample tube or ventilation tube
with integrated FAD-425-O-R Detector detects smoke
in ventilation ducts. Smoke particles in the air are E Connection board
reliably detected and reported to the fire panel by the
LSN improved bus system. Functions
1 Air sampling housing with connection board, Detector base Ordering information
and installation material
FAD-420-HS-EN Duct detector housing with base
1 D344-1.5 sample tube (length 45.7 cm) air sampling housing with connection board and
1 Ventilation tube detector base for FAD-425-O-R. The detector must be
ordered in addition.
2 D344-TF air filter for sample and ventilation tube Order number FAD-420-HS-EN
Accessories
Notice FAD-425-O-R Duct detector, optical
Please note that the FAD-420-HS-EN does not Analog addressable optical detector for use in air
come with the required FAD-425-O-R Detector. sampling housing FAD-420-HS-EN
The FAD-425-O-R Detector has to be ordered in Order number FAD-425-O-R
addition.
FAD-RB-DIBT Relay board for DIBT application
relay board for DIBT applications
Technical specifications
Order number FAD-RB-DIBT
FAD-420-HS-EN Duct detector housing with base
D344-1.5 Sample tube, duct 1.5'/45.7cm
Electrical length 45.7 cm (1.5 ft)
Order number D344-1.5
Operating voltage 24 V DC (15 … 33 V DC)
D344-3 Sample tube, duct 3'/91.4cm
Maximum current consumption Approx. 0.55 mA (approx. length 91.4 cm (3 ft)
0.75 mA when FAD‑RB‑DIBT Order number D344-3
Relay Board is installed)
D344-5 Sample tube, duct 5'/152cm
Electromagnetic susceptibility EN 50130‑4
length 1.52 m (5 ft)
(EMS)
Order number D344-5
Electromagnetic emission (EME) EN 61000‑6‑3
D344-TF Duct tube filters, 20pcs
Replaceable filters for duct detector sampling tubes,
Mechanics
available in packages of 20
Dimensions (H x W x D) 16.5 x 39.5 x 11 cm Order number D344-TF
Permissible operating 0 °C … 50 °C
temperature
3 | FAD-420-HS-EN Duct detector housing with base
Represented by:
The D296 Long-range beam smoke detector (24V) is transmitting. Pressing the Aim Mode button on the
used in clear open structures such as arenas, atriums, transmitter allows transmission while the cover is off.
auditoriums, ballrooms, churches, factories, museums, For fine tuning which requires a measurable voltage at
and warehouses. Each detector consists of a the receiver, the covers must be off and transmission
transmitter, a receiver, and a remote indicator plate. is necessary.
Because the transmitter and receiver typically mount
Alarm Operation
on the ceiling or high on walls or columns, they
The transmitter emits a pulsed infrared beam. The
provide an effective and unobtrusive means of
receiver measures the intensity of the beam over a
supervising public areas for fire protection.
period of time and compares this data with an alarm
The D344-RL Remote indicator plate, included with the
threshold. Select one of six levels of sensitivity for the
detector, provides a convenient means of verifying
alarm threshold through a switch on the receiver.
detector status. Install it anywhere within 500 ft
If the receiver senses signal strength below the preset
(152 m) of the beam receiver (when using 18 AWG
alarm threshold in excess of the alarm period it signals
[ISO 0.75 mm2] wire). The indicator plate has three
an alarm.
LEDs to indicate normal, trouble, and alarm
conditions, and test points to monitor the detector Signal Loss Compensation
circuit. The receiver automatically compensates for the
gradual loss of signal due to dust and dirt build-up on
Functions the cover. The receiver measures the intensity of the
pulsed infrared beam emitted by the transmitter over a
Aim Mode
period of time and compares this data with a preset
When the cover is removed from the receiver, the
trouble threshold. When 50% of the signal is lost or
receiver goes into aim mode. When the cover is
the signal gains 20%, the receiver sends a trouble
removed from the transmitter, the transmitter stops
signal to the control panel.
2 | D296 Smoke detector, long-range beam 24V
When the dust and dirt build-up is cleaned or the Lateral Spacing Between Systems
blockage is removed, the detector automatically For adequate coverage, the lateral spacing between
resets. adjacent detector systems must not exceed 60 ft
(18 m).
Tamper Detection
If the covers to the transmitter or receiver are Wiring
removed, the detector sends a trouble signal to the System wire terminals accept 18 AWG to 12 AWG (ISO
control panel. 0.75 mm2 to 4 mm2) solid wires.
Represented by:
Description Connection
AUX 2+ | 1/2- | 1+ Output power supply 4‑wire detectors 001 Loop/stub/T-taps in LSN mode improved FPA-5000
- version with manual addressing FPA‑1200
OUT1 + | - Stub 1 or loop out 254
OUT2/IN1 - | + Stub 2 or loop in
CL 0 0 Loop/stub in LSN mode classic BZ 500 LSN
PWR IN Input power supply (from LSN or external UEZ 2000 LSN
LSN AUX or EXT.PWR + | - source) UGM 2020
• Loop wiring of the conventional zone (class A) does • Max. line current 80 mA per line (±10% at 25 °C)
not require an EOL resistor as it is already integrated
in the interface module. • Max. line resistance 50 Ω per line (max. 2 x 25 Ω)
• The power supply is provided via the two wires on
the auxiliary LSN power supply or by an external • Galvanic isolation from Yes
power supply unit. External power supply units must LSN
be free-of-ground.
Input power supply (PWR IN)
• The surface-mounted housing has two cable ducts on
opposite sides: • Voltage 24 to 30 V DC
– 2 x 2 pre-punched cable ducts for diameter up to
21 mm/to 34 mm (for conduits) • Residual ripple < 150 mV
– 2 x 4 rubber bushes for inserting cables with
diameters of up to 8 mm Output power supply 4‑wire
• In addition, there are cable ducts on the base of the detector (AUX)
surface-mounted housing: • Voltage 23.5 V DC to 30 V DC
– 1 x pre-punched cable duct for diameter up to (rated voltage 24 V DC)
21 mm (for conduits)
– 2 x 4 rubber bushes for inserting cables with • Residual ripple < 300 mV
diameters of up to 8 mm
• For operating the fire alarm system according to • Max. current (supply to 200 mA per output (can be switched
EN 54-13: 4‑wire detector) in parallel)
– it is necessary to terminate every conventional
EOL resistor for stub wiring of
zone with EOL modules
conventional zone (class B)
– conventional 4-wire detectors must be supplied
by an external power supply. The FLM‑420/4‑CON • With calibration value 2.2 kΩ
Conventional Interface Module must be supplied
by the auxiliary LSN power supply • Without calibration 2.2 kΩ / 3.9 kΩ
• Observe the maximum line resistance of 25 Ω for value
conventional lines with manual call points or
The following figures include the power consumption
automatic fire detectors.
of the internal module hardware and the conventional
Parts included line(s) supervision. The power consumption of the
connected devices is excluded:
Type Qt Component
Max. current consumption 1x 2x 1x 2x
y. (PWR IN) 2.2k 2.2k 3.9k 3.9k
Ω* Ω* Ω* Ω*
FLM-420/4-CON-S 1 Conventional Interface Module for 4-wire
LSN, with surface-mounted housing, • Standby 36 50 31 40
cable with EOL resistor (3k92) mA mA mA mA
FLM-420/4-CON- 1 Conventional Interface Module for 4-wire • Lines open or short 25 28 25 28
D LSN, with adapter for installation on a mA mA mA mA
DIN rail in accordance with EN 60715,
light pipe, cable with EOL resistor (3k92) • 1 device on alarm at 69 112 65 103
the line (820 Ω mA mA mA mA
2 2.2 kOhm resistors alarm res.)
Color
Dimensions
Environmental conditions
• FLM-420/4-CON-S IP 54
• FLM-420/4-CON-D IP 30
Ordering information
Represented by:
The Wheelock ASWP Series consists of 24 V, square horn NYC/MEA 151‑93‑E, Vol. 26
strobes for use with a WPBB‑R Weatherproof Back Box in CBFP City of Chicago Bureau of Fire Protection
outdoor and extreme environment applications. The series
ADA Complies with Americans with Disabilities
includes wall and ceiling mount models. The strobe is listed Act
as 75 cd on axis at -31°F (‑35°C). Choose between ANSI Complies with American National Stand-
continuous horn or temporal pattern (Code 3) tone when ards Institute ANSI 117.1
constant voltage from the fire alarm control panel (FACP) NFPA Complies with National Fire Protection As-
is applied. Each tone has three field-selectable volume sociation NFPA 72
levels. OSHA Complies with Occupational Safety and
Synchronize these horn strobes with the SM (single) or Health Administration OSHA 29
DSM (dual) modules or a compatible control panel. The Part 1910.165
audible response can be silenced while maintaining strobe
activation, a requirement in some jurisdictions.
Installation/Configuration Notes
Note These products are not suitable for
hearing‑impaired applications. Compatible Products
The following products are compatible with the ASWP
Weatherproof Horn Strobe:
www.boschsecurity.com
2 | ASWP Series Weatherproof Horn Strobes
The knockout hole on top of the back box is sized for a High Volume Setting: 91 dBA
half‑inch conduit and matching connector. A proper Medium Volume Setting: 88 dBA
watertight conduit fitting must be used. Low Volume Setting: 83 dBA
Mount these horn strobes on the indicated back box for the Temporal (Code 3) Horn
indicated applications: High Volume Setting: 87 dBA
Medium Volume Setting: 84 dBA
Conduit Surface Flush
Applications Mounted Mounted Low Volume Setting: 79 dBA
WPBB‑R • • Trademarks
All models have an attractive cover plate for a clean, Trademark names are used throughout this document. In
finished appearance. most cases, these designations are claimed as trademarks
or registered trademarks in one or more countries by their
Wiring
respective owners. Rather than placing a trademark symbol
Note Do not use these units in coded or pulsed in every occurrence of a trademark name, Bosch Security
signaling circuits. Systems, Inc. uses the names only in an editorial fashion
The input terminals accept wires with diameters between and to the benefit of the trademark owner with no intention
18 AWG (1.2 mm) and 12 AWG (2.3 mm). of infringing the trademark.
Quant. Component
1 Horn strobe
1 Cover plate
1 Hardware pack
1 Literature pack
Technical Specifications
Environmental Considerations
Ordering Information
ASWP‑2475W‑FR Weatherproof ASWP-2475W-FR
Wall‑mount Horn Strobe (red)
Red, 24 V, wall‑mount device for use with a
WPBB‑R Weatherproof Back Box in outdoor
and extreme environment applications
ASWP‑2475C‑FR Weatherproof ASWP-2475C-FR
Ceiling‑mount Horn Strobe (red)
Red, 24 V, ceiling‑mount device for use with a
WPBB‑R Weatherproof Back Box in outdoor
and extreme environment applications
ASWP‑2475C‑FW Weatherproof ASWP-2475C-FW
Ceiling‑mount Horn Strobe (white)
White, 24 V, ceiling‑mount device for use with
a WPBB‑R Weatherproof Back Box in outdoor
and extreme environment applications
Accessories
WPBB‑R Weatherproof Back Box WPBB-R
Used to surface mount the ASWP Series
Weatherproof Horn-strobes for outdoor or se-
vere environment applications
www.boschsecurity.com
4 | ASWP Series Weatherproof Horn Strobes
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T3461921035 | Cur: en-US, V5, 4 Jul 2010
Fire Alarm Systems | FLM‑420‑NAC Signaling Device Interface Modules
Description Connector
b IN / a IN NAC zone input
b OUT / a OUT NAC zone output
0 V / 24 V Ext. power supply
a1- / b1+ LSN in
a2- / b2+ LSN out
2 | FLM‑420‑NAC Signaling Device Interface Modules
Dimensions
Weight
System limits
Further characteristics
Represented by:
u Efficient LED
The remote indicator is used when the automatic • In LSN periphery the sum of all cable lengths
detector is installed in a place hidden or not visible, between LSN devices and remote indicators as well
like in closed rooms, false ceilings or walls. It is as between LSN interface modules and conventional
recommended to mount the remote indicator in devices must not exceed 500 m.
corridors or access pathways of the corresponding • If you use unshielded cables, the cable length
building sections or rooms. between LSN device (e.g. detector) and remote
indicator is restricted to a maximum of 3 m.
Certifications and approvals • If connected to a non-LSN detector, then the current
has to be externally limited to maximum 30 mA.
Region Regulatory compliance/quality marks
Parts included
Europe CPR 0786-CPR-21481 FAA-420-RI-DIN/
FAA-420-RI-ROW Quantity Component
Poland ITB 020-UWB-2643/W FAA-420-RI-DIN / 1 Remote indicator
FAA-420-RI-ROW
Europe CE FAA-420-RI-DIN/-ROW Technical specifications
• You can connect only one detector per remote Current feed 3 to 30 mA
indicator. However, it is possible to indicate an alarm
from more than one detector on an LSN bus via Permissible wire gauge 0.4 to 1.3 mm
configuring the panel with the Remote Programming
Dimensions 85 x 85 x 28 mm
Software FSP-5000-RPS respectively.
Weight 45 g
Represented by:
Technical Specifications
www.boschsecurity.com