HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM

STANDARD FEATURES
 UL Listed, FM Approved Clean Agent Fire Suppres-
sion product.
 Colorless
 Odorless
 Safe for people
 Electronically nonconductive
 Non corrosive
 Free of residue
 Does not contain chlorine or bromine
 Complies fully with the standards of ASTM D6064
and NFPA 2001

PRODUCT DESCRIPTION
Hochiki's HFC-227ea by Chemori, is a safe and effective fire extinguishing agent that is used for total flooding fire
suppression systems. HFC-227ea is stored as a liquid and dispensed into the hazard as a colorless, electrically non
-conductive vapor that is clear and does not obscure physical vision. It leaves no residue and has acceptable toxicity
for use in occupied spaces at design concentration. Hochiki HFC-227ea is suitable for use on Class A, Class B, and
Class C fires, does not displace oxygen, has zero ozone-depleting potential, and low global-warming potential with a
short atmospheric lifetime. It contains no chlorine or bromine and fully complies with NFPA 2001 and ASTM D6064
standards. Cylinder sizes range from 20 lb. up to 1,200 lb., and each cylinder is pre-filled according to specific de-
sign flow calculations for the hazard. Common applications include computer and server rooms, libraries, telecom-
munications, medical facilities, vehicles, and much more.

PHYSICAL AND CHEMICAL CHARACTERISTICS


Chemical Name Heptafluoropropane (CF3CHFCF3)
General Colorless, Odorless Liquified Gas
Molecular Weight 170.03
Boiling Point -16.4°C/2.48°F
Freezing Point -131°C/-203.8°F
Vapor Pressure @ 21°C / 70°F 58.8 psia
Critical Temperature 101.7°C/215.1°F
Critical Pressure (psia) 422.3 psia
Vapor Density (AIR = 1) 6.04
Water Reactive No
Specific Gravity (H2O = 1) 1.46
Percent Volatile (by volume) n/a
Evaporation Rate (Butyl acetate = 1) n/a
Viscosity @ 20°C / 68°F n/a
Water Solubility (V/V @ 20°C / 68°F) 260mg/L
Ozone Depletion Potential 0
Estimated Atmospheric Lifetime (years) 31-42

PRODUCT LISTINGS

Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 800-845-6692 or technicalsupport@hochiki.com Page 1 of 5 F0262 Rev1 08/2020
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Clean Agent Cylinders (360 Psi System)
The Clean Agent cylinders are manufactured, tested and stamped in accordance with DOT 4BW500 or DOT
4BA500. All cylinders are equipped with a back pressure type valve. A piston in the valve bore is equipped with a
rubber seal that keeps the HFC-227ea Clean Agent under pressure within the cylinder. A small hole in the piston
allows cylinder pressure to be equalized on both sides of the piston. Since the area at the top of the piston is greater
than the area at the bottom of the piston, the net force seals the piston against the valve discharge outlet. When the
cylinder pressure on the top of the piston is relieved by means of automatic or manual activation, there is only cylin-
der pressure acting against the piston seal, and the piston slides to it’s full open position, allowing cylinder discharge
through the distribution piping network.
Attached to the bottom of the cylinder valve is a siphon tube, which is straight and runs from the top of the cylinder to
the bottom of the cylinder. The cylinder must be installed in an upright position (valve on top).
There is a 1/8” NPT outlet stamped “P” on the cylinder valve. This outlet transmits cylinder pressure to an optional
low pressure supervisory switch, which when used, monitors the internal pressure of the cylinder. Another 1/8” NPT
outlet stamped “M” on the cylinder valve is available for use as a pressure source to drive the piston actuators on a
multiple cylinder system or to actuate a pressure operated switch in the event of the cylinder discharge.
Cylinder Model
HFC-227ea Clean Agent cylinders are available in the following capacities:
NOTE:
Part Number Cylinder Size Max Fill at 70 lb/ft3 Min Fill at 30 lb/ft3 Valve Size
1. Each of the basic sizes can be filled with one
1260-01340 35 LB 35 LB 16 LB 1” Valve pound increments to meet the exact amount of
1260-01350 70 LB 71 LB 31 LB 1” Valve HFC-227ea Clean Agent required, within their fill
ranges.
1260-01360 100 LB 101 LB 44 LB 1” Valve
1260-01370 150 LB 152 LB 66 LB 1 1/2” Valve 2. *add -”SS” if valve is Stainless Steel
1260-01380 250 LB 253 LB 109 LB 1 1/2” Valve Temperature Range: 32°F (0° C) to 130°F (54.4°C)
1260-01390 375 LB 379 LB 163 LB 2 1/2” Valve
System Operating Pressure: 360 psi at 70°F
1260-01400 560 LB 561 LB 241 LB 2 1/2” Valve (25.3kgƒ / cm2 at 21.1°C)

Cylinder Dimensions
Part Number A B C
1260-01340 10” 17.607” 22.336”
1260-01350 10” 28.04” 32.769”
1260-01360 12.75” 27.127” 32.706”
1260-01370 12.75” 37.127” 42.706”
1260-01380 16” 39.883” 45.462”
1260-01390 16” 57.16” 64.462”
1260-01400 20” 55.516” 65.76”

Cylinder Bracket
The cylinder bracket is manufactured from galvanized steel band formed to the radius of the cylinder with flanges for
bolting to the continuous slot metal framing channel of 12-gauge steel with corrosion resistant paint or galvanized.
The channel must be supplied by the installer. The cylinder bracket must be secured to a surface that the bracket will
withstand a load up to 5 times of the cylinder weight. This precaution is to have the bracket safely support the weight
of the cylinder and the reaction force of the HFC-227ea Clean Agent during discharge.

Cylinder Part Number Cylinder O.D D E F G Bracket Part #


1260-01340 10.75” 11” 14” 12.6” 2” 1260-01720
1260-01350 10.75” 11” 14” 12.6” 2” 1260-01720
1260-01360 12.80” 13” 16.05” 14.65” 2” 1260-01730
1260-01370 12.80” 13” 16.05” 14.65” 2” 1260-01730
1260-01380 16.00” 16.25” 19.2” 17.7” 2” 1260-01740
1260-01390 16.00” 16.25” 19.2” 17.7” 2” 1260-01740
1260-01400 20.00” 20.25” 23.2” 21.7” 2” 1260-01760

P/N: 1260-01770

For the 20 lb to 250 lb cylinders - One cylinder bracket must be used / For the 375 lb to 650 lb cylinders - Two cylinder brackets must be used

Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 2 of 5 Specifications subject to change without notice.
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Engineered Clean Agent Cylinders (360 Psi System)
The 800 lb, 1000 lb and 1200 lb cylinders are filled with one pound incre-
ments in order to meet the exact amount of agent required. By using Chem-
ori’s Flow Calculation Software Version CR 4.00, the two-phase and the two
-component flow of agent and nitrogen through the distribution piping net-
work in quasi-steady state from the initiation of the discharge to the final gas
blow down can be estimated and predicted. The cylinder is equipped with a
stainless steel valve that offers excellent flow characteristics for the liquefied
gas, allowing for long pipe runs and has a greater coverage area.
Temperature Range: 32°F (0° C) to 130°F (54.4°C)
P/N: 1260-01430 P/N: 1260-01420 P/N: 1260-01410
Operating Pressure: 360 psi at 70°F (25.3kgƒ / cm2 at 21.1°C)
Height to Discharge
Part Number Cylinder Size Max Fill at 70 lb/ft3 Min Fill at 30 lb/ft3 Valve Size Diameter Total Height
Outlet
1260-01410 800 LB 806 LB 353 LB 4” Valve 30.00” 56.792” 47.002”
1260-01420 1000 LB 1008 LB 439 LB 4” Valve 30.00” 64.154” 54.364”
1260-01430 1200 LB 1211 LB 519 LB 4” Valve 30.00” 71.516” 61.726”
The cylinder is equipped with a stainless steel back pressure type valve in which a piston installed within the valve is
equipped with a rubber seal that keeps the clean agent under pressure within the cylinder. A small hole in the piston
allows the pressure within the cylinder to be equalized on both sides of the piston. Since the area at the top of the
piston is greater than the area at the bottom of the piston, the net force seals the piston against the valve discharge
outlet. When the cylinder pressure on the top of the piston is relieved by means of automatic or manual activation,
there is only cylinder pressure acting against the piston seal; hence, the piston slides to its full open position, allow-
ing cylinder discharge through the distribution piping network.
The cylinder must be installed in an upright position (valve on top) in which each cylinder installation shall use a top
plug adapter. The available accessories include electric solenoid, pressure gauge, liquid level indicator, and bracket
as described in the following manner.

3” and 4” Valve Accessories


Description Usage
Electric Solenoid available in: To automatically start and operate the clean agent discharge based on the operating
-24 VDC 15 Watts (4” Valve) / (3” Valve) specification requirement

Low Pressure Supervisory Switch To monitor the internal pressure of the cylinder

Pressure Gauge, 360 psi For quick visual inspection of the cylinder’s internal pressure

Piston Actuator For use as a pressure operated switch in the event of the cylinder discharge of
multiple cylinders installation
Liquid Level Indicator To measure the weight of the clean agent inside of the cylinder.
Highly recommended for ease of maintenance
Cylinder Bracket To support the weight of cylinder and the reaction force of the clean agent during discharge

Cylinder Bracket
The cylinder bracket is manufactured from galvanized steel band formed to the
radius of the cylinder with flanges for bolting to the continuous slot metal framing
channel of 12-gauge steel with corrosion resistant paint or galvanized. The
channel must be supplied by the installer. The cylinder bracket must be secured
to a surface that the bracket will withstand a load up to 5 times of the cylinder
weight. This precaution is to have the bracket safely supports the weight of the
cylinder and the reaction force of the HFC-227ea Clean Agent when discharge. P/N: 1260-01770

Part Number Diameter A B C D E F


1260-01770 30.00” 29.125” 33.250” 31.750” 1.5” 14.00” 2”

Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 3 of 5 Specifications subject to change without notice.
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Discharge Nozzles

Part Number Description


1260-02300 1/2” (180°) Sidewall
1260-02310 1/2” (360°) Central
1260-02320 3/4” (180°) Sidewall
1260-02330 3/4” (360°) Central
1260-02340 1” (180°) Sidewall
1260-02350 1” (360°) Central
1260-02360 1 1/4” (180°) Sidewall
1260-02370 1 1/4” (360°) Central
1260-02380 1 1/2” (180°) Sidewall
1260-02390 1 1/2” (360°) Central
1260-02400 2” (180°) Sidewall
1260-02410 2” (360°) Central

DESCRIPTION
Chemori Discharge Nozzles are designed to control the flow of Clean Agent in a uniform, pre-determined pattern and
concentration. The nozzles are intended to finish the release of Clean Agent in 10 seconds or less when introduced
within the design limitations as stated in the Installation Instruction Manual.
Discharging Nozzles are available in sizes of 1/2”, 3/4”, 1”, 1-1/4”, 1-1/2” and 2”. Each discharge nozzle comes in two
configurations: 180 and 360 degree distribution patterns. Deflector plates are available as a choice where sensitive
ceiling tiles must be protected.
Discharge Nozzles are made of aluminum with female pipe threads. The orifice size of the discharge nozzle is deter-
mined by the hydraulic flow calculations. All nozzles are rated for a maximum hazard height of 16ft. If hazards ex-
ceed 16ft in height, a second tier of nozzles must be used.
Discharge Nozzles are also available in Brass and Stainless Steel materials.

Discharge Nozzles Selection - Sidewall 180°


Typically to be installed adjacent to the center of the one wall of one enclosure. It’s discharge path will be across the
enclosure. At no time shall the area coverage be exceeded.

Discharge Nozzle Selection - Central 360°


Typically to be installed at the center of the enclosure. It’s discharge path will be across the enclosure. At no time
shall the area coverage be exceeded.

Installation
Please refer to Chemori Installation, Maintenance & Service Technical Manual for Discharge Nozzles Area Coverage
and Application Selections.

Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 4 of 5 Specifications subject to change without notice.
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Instructional Signs

CAUTION CAUTION CAUTION


(When Alarm Sound ... ) (Do Not Enter Room ... ) (Operation of Manual Station ...)
(CR 50230) (CR 50231) (CR 50232)
The purpose of this caution sign is The purpose of this caution sign is The purpose of this caution sign is
to alert personnel to evacuate the to prevent personnel from entering to instruct personnel as to use of
protected area. a protected area. Agent Release Manual Pull Station.
The sign should be conspicuously The sign should be conspicuously This sign should be installed
located near alarm devices. located outside the entrance door adjacent to all Agent Release
to the protected area. Manual Pull Stations.

DESCRIPTION
Instructional signs shall be provided at entrances to and inside of all protected areas. Hochiki offers a few diverse
“standard” signs to conform to NFPA and other industry necessities. All signs are made of durable plastic and
backed with a strong adhesive for easy installation. Signs are typically installed at all entrances (e.g. CAUTION -
Room Protected by HFC-227ea) and near any devices for which the additional explanation is helpful. Custom made
instructional signs are available upon request.

Part Number Description


1260-02550 Caution Label - “When Alarm Sounds . . .”
1260-02560 Caution Label - “Do Not Enter . . .”
1260-02570 Caution Label - “Operation of Manual . . .”
1260-02580 Caution-Room Protected

Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 5 of 5 Specifications subject to change without notice.