HFC 227ea - 08 2020
HFC 227ea - 08 2020
HFC 227ea - 08 2020
STANDARD FEATURES
UL Listed, FM Approved Clean Agent Fire Suppres-
sion product.
Colorless
Odorless
Safe for people
Electronically nonconductive
Non corrosive
Free of residue
Does not contain chlorine or bromine
Complies fully with the standards of ASTM D6064
and NFPA 2001
PRODUCT DESCRIPTION
Hochiki's HFC-227ea by Chemori, is a safe and effective fire extinguishing agent that is used for total flooding fire
suppression systems. HFC-227ea is stored as a liquid and dispensed into the hazard as a colorless, electrically non
-conductive vapor that is clear and does not obscure physical vision. It leaves no residue and has acceptable toxicity
for use in occupied spaces at design concentration. Hochiki HFC-227ea is suitable for use on Class A, Class B, and
Class C fires, does not displace oxygen, has zero ozone-depleting potential, and low global-warming potential with a
short atmospheric lifetime. It contains no chlorine or bromine and fully complies with NFPA 2001 and ASTM D6064
standards. Cylinder sizes range from 20 lb. up to 1,200 lb., and each cylinder is pre-filled according to specific de-
sign flow calculations for the hazard. Common applications include computer and server rooms, libraries, telecom-
munications, medical facilities, vehicles, and much more.
PRODUCT LISTINGS
Cylinder Dimensions
Part Number A B C
1260-01340 10” 17.607” 22.336”
1260-01350 10” 28.04” 32.769”
1260-01360 12.75” 27.127” 32.706”
1260-01370 12.75” 37.127” 42.706”
1260-01380 16” 39.883” 45.462”
1260-01390 16” 57.16” 64.462”
1260-01400 20” 55.516” 65.76”
Cylinder Bracket
The cylinder bracket is manufactured from galvanized steel band formed to the radius of the cylinder with flanges for
bolting to the continuous slot metal framing channel of 12-gauge steel with corrosion resistant paint or galvanized.
The channel must be supplied by the installer. The cylinder bracket must be secured to a surface that the bracket will
withstand a load up to 5 times of the cylinder weight. This precaution is to have the bracket safely support the weight
of the cylinder and the reaction force of the HFC-227ea Clean Agent during discharge.
P/N: 1260-01770
For the 20 lb to 250 lb cylinders - One cylinder bracket must be used / For the 375 lb to 650 lb cylinders - Two cylinder brackets must be used
Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 2 of 5 Specifications subject to change without notice.
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Engineered Clean Agent Cylinders (360 Psi System)
The 800 lb, 1000 lb and 1200 lb cylinders are filled with one pound incre-
ments in order to meet the exact amount of agent required. By using Chem-
ori’s Flow Calculation Software Version CR 4.00, the two-phase and the two
-component flow of agent and nitrogen through the distribution piping net-
work in quasi-steady state from the initiation of the discharge to the final gas
blow down can be estimated and predicted. The cylinder is equipped with a
stainless steel valve that offers excellent flow characteristics for the liquefied
gas, allowing for long pipe runs and has a greater coverage area.
Temperature Range: 32°F (0° C) to 130°F (54.4°C)
P/N: 1260-01430 P/N: 1260-01420 P/N: 1260-01410
Operating Pressure: 360 psi at 70°F (25.3kgƒ / cm2 at 21.1°C)
Height to Discharge
Part Number Cylinder Size Max Fill at 70 lb/ft3 Min Fill at 30 lb/ft3 Valve Size Diameter Total Height
Outlet
1260-01410 800 LB 806 LB 353 LB 4” Valve 30.00” 56.792” 47.002”
1260-01420 1000 LB 1008 LB 439 LB 4” Valve 30.00” 64.154” 54.364”
1260-01430 1200 LB 1211 LB 519 LB 4” Valve 30.00” 71.516” 61.726”
The cylinder is equipped with a stainless steel back pressure type valve in which a piston installed within the valve is
equipped with a rubber seal that keeps the clean agent under pressure within the cylinder. A small hole in the piston
allows the pressure within the cylinder to be equalized on both sides of the piston. Since the area at the top of the
piston is greater than the area at the bottom of the piston, the net force seals the piston against the valve discharge
outlet. When the cylinder pressure on the top of the piston is relieved by means of automatic or manual activation,
there is only cylinder pressure acting against the piston seal; hence, the piston slides to its full open position, allow-
ing cylinder discharge through the distribution piping network.
The cylinder must be installed in an upright position (valve on top) in which each cylinder installation shall use a top
plug adapter. The available accessories include electric solenoid, pressure gauge, liquid level indicator, and bracket
as described in the following manner.
Low Pressure Supervisory Switch To monitor the internal pressure of the cylinder
Pressure Gauge, 360 psi For quick visual inspection of the cylinder’s internal pressure
Piston Actuator For use as a pressure operated switch in the event of the cylinder discharge of
multiple cylinders installation
Liquid Level Indicator To measure the weight of the clean agent inside of the cylinder.
Highly recommended for ease of maintenance
Cylinder Bracket To support the weight of cylinder and the reaction force of the clean agent during discharge
Cylinder Bracket
The cylinder bracket is manufactured from galvanized steel band formed to the
radius of the cylinder with flanges for bolting to the continuous slot metal framing
channel of 12-gauge steel with corrosion resistant paint or galvanized. The
channel must be supplied by the installer. The cylinder bracket must be secured
to a surface that the bracket will withstand a load up to 5 times of the cylinder
weight. This precaution is to have the bracket safely supports the weight of the
cylinder and the reaction force of the HFC-227ea Clean Agent when discharge. P/N: 1260-01770
Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 3 of 5 Specifications subject to change without notice.
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Discharge Nozzles
DESCRIPTION
Chemori Discharge Nozzles are designed to control the flow of Clean Agent in a uniform, pre-determined pattern and
concentration. The nozzles are intended to finish the release of Clean Agent in 10 seconds or less when introduced
within the design limitations as stated in the Installation Instruction Manual.
Discharging Nozzles are available in sizes of 1/2”, 3/4”, 1”, 1-1/4”, 1-1/2” and 2”. Each discharge nozzle comes in two
configurations: 180 and 360 degree distribution patterns. Deflector plates are available as a choice where sensitive
ceiling tiles must be protected.
Discharge Nozzles are made of aluminum with female pipe threads. The orifice size of the discharge nozzle is deter-
mined by the hydraulic flow calculations. All nozzles are rated for a maximum hazard height of 16ft. If hazards ex-
ceed 16ft in height, a second tier of nozzles must be used.
Discharge Nozzles are also available in Brass and Stainless Steel materials.
Installation
Please refer to Chemori Installation, Maintenance & Service Technical Manual for Discharge Nozzles Area Coverage
and Application Selections.
Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 4 of 5 Specifications subject to change without notice.
HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM
Instructional Signs
DESCRIPTION
Instructional signs shall be provided at entrances to and inside of all protected areas. Hochiki offers a few diverse
“standard” signs to conform to NFPA and other industry necessities. All signs are made of durable plastic and
backed with a strong adhesive for easy installation. Signs are typically installed at all entrances (e.g. CAUTION -
Room Protected by HFC-227ea) and near any devices for which the additional explanation is helpful. Custom made
instructional signs are available upon request.
Hochiki America Corporation HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM Page 5 of 5 Specifications subject to change without notice.