COMTRAXX® COM465IP Condition monitor with an integrated gateway for the connection
of Bender devices to Ethernet TCP/IP networks
Product description
The COMTRAXX® COM465IP series features a condition monitor and is integrated into the
existing EDP structure like any Ethernet-capable device. All Bender devices can be connected
via the integrated interfaces. In addition, third-party devices can also be integrated into
the system. The measured values, parameters and all other data can be checked and
parameterised via the web interface or the display.
It is possible to indicate and visualise alarms. By means of the visualisation application,
individual overview pages can be generated which are then displayed in a web browser.
Application
• Optimum display and visualisation of device and system states in the web browser
• Monitoring and analysis of compatible Bender products and third-party devices
COMTRAXX® COM465IP
• Specific system overview through individual system description
Device features • Selective notification to various users in the event of alarms
• Condition monitor for Bender systems • Numerous interfaces for data transfer to higher-level systems
• Integrated modular gateway between • Clear setting of device parameters. Storing, documenting and restoring parameters is
Bender systems and TCP/IP enables possible
remote access via LAN, WAN or Internet • Commissioning and diagnosis of Bender systems
• Range of functions adjustable through • Remote diagnosis, remote maintenance
function modules
Scope of functions (V4.5.0 and higher)
• Support of devices that are connected to
the internal or external BMS bus, via Basic device (without function modules)
BCOM, via Modbus RTU or Modbus TCP • Condition monitor with web interface
• Individual visualisation can be generated, • Interfaces for the integration of devices
which is displayed via the web browser
– Internal BMS bus (max. 150 devices) and external* BMS bus (max. 99 x 150 devices)
Data transfer interfaces – BCOM (max. 255 devices)
– Modbus RTU and Modbus TCP (max. 247 devices each)
• Remote display of the latest measured values, status/alarm messages and parameters*
• Gateway to Modbus TCP: Reading the latest measured values, status/alarm messages
from addresses 1…10 of each interface via Modbus TCP
• Gateway to Modbus RTU: Reading the latest measured values, status/alarm messages
from addresses 1…10 of the internal BMS interface via Modbus RTU
• Ethernet interface with 10/100 MBit/s for remote access via LAN, WAN or Internet
Approvals
• Setting of internal device parameters and parameters of devices connected via
Modbus RTU and Modbus TCP **
• Time synchronisation for all assigned devices
• History memory (20,000 entries)
• Data loggers, freely configurable (30 x 10,000 entries)
• 50 data points from third-party devices (via Modbus RTU or Modbus TCP) can be
integrated into the system
• A virtual device with 16 channels can be created
*) Indicating parameters of BMS bus devices is only possible when the gateway is connected to the internal BMS
bus.
**) Parameters can be set via web application and externally (via BMS/ICOM/BCOM),
but not via Modbus. The parameters of assigned devices can only be read; Function module C is necessary for
modification of settings!
2 COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP
Function module C
• Fast and easy parameter setting of all devices* assigned to the
gateway via web browser.
• Device backups of all devices in the system can be created and
restored.
*) Parameter setting of BMS bus devices is only possible when the gateway is
connected to the internal BMS bus.
COM465IP_D00217_10_D_XXEN/02.2022 3
COMTRAXX® COM465IP
3
COM465IP
COMTRAXX®
1 OFF
RMB ON OFF
RBMS ON
6 7 8 9 10
X1
4 5
1 - “ON” LED: Flashes during start-up. 7 - Modbus RTU terminating resistor switch
The LED lights permanently as soon as the device is ready for 8 - BMS bus terminating resistor switch
operation.
9 - Micro USB interface (currently without function) (plug X3)
2 - LEDs show activities on the different interfaces
10 - Mini HDMI interface (currently without function) (plug X4)
3 - Supply voltage: see nameplate and ordering information
4 - Modbus/RTU interface: Terminals AMB and BMB (plug X1) For UL applications, the following has to be observed:
– Maximum ambient temperature: 55 °C
5 - BMS bus (Bender measuring device interface):
– Use 60/75 °C copper wires only
Terminals ABMS and BBMS (plug X1)
6 - Ethernet port (RJ45) for connection to the PC network as well
as BCOM (plug X2)
4 COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP
Technical data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 BCOM
Rated voltage AC 250 V Interface/protocol Ethernet/BCOM
Rated impulse voltage/overvoltage category 4 kV/III BCOM system name (SYSTEM)
Pollution degree 3 BCOM subsystem address 1…255 (1)*
Protective separation (reinforced insulation) between BCOM device address 0…255 (0)*
(A1/+, A2/-) - [(AMB, BMB), (ABMS, BBMS), (X2), (X3, X4)] Modbus
Bender Modbus image V1, V2 (V2)*
Supply voltage
Modbus TCP
Supply voltage Us see ordering information
Interface/protocol Ethernet/Modbus TCP
Frequency range Us see ordering information
Operating mode client for Bender Modbus TCP devices and “third-party devices”
Power consumption see ordering information
Operating mode server for access to the process image and for Modbus control commands
Indications Parallel data access from different clients max. 25
LEDs: Modbus RTU
ON operation indicator Interface/protocol RS-485/Modbus RTU
ETHERNET IP data traffic Ethernet Operating mode master/slave (master)*
MODBUS RTU data traffic Modbus Baud rate 9.6…57.6 kBit/s
BMS data traffic BMS Cable length ≤ 1,200 m
Ethernet (terminal X2) lights during network connection, flashes during data transfer Cable shielded, one end of shield connected to PE
recommended: CAT6/CAT7 min. AWG23
Memory alternative: twisted pair, J-Y(St)Y min. 2x0,8
Individual texts (function module A only) unlimited number of texts each with 100 characters Connection X1 (AMB, BMB)
E-mail configuration and device failure monitoring max. 250 entries Connection type refer to connection “push-wire terminal X1”
Number of data points for “third-party devices” to Modbus TCP and Modbus RTU 50 Terminating resistor 120 Ω (0.25 W), can be connected internally
Number of data loggers 30 Supported Modbus RTU slave addresses 2…247
Number of data points per data logger 10,000 PROFINET
Number of history memory entries 20,000 Interface/protocol Ethernet/PROFINET
Operating mode Slave (IO-Device)
Visualisation
SNMP
Number of pages 50
Interface/protocol Ethernet/SNMP
Background image size 3 MB
Versions 1, 2c, 3
Interfaces Supported devices queries to all devices (channels) possible
Trap support yes
Ethernet
Port RJ45 Used ports
Cable length < 100 m 53 DNS (UDP/TCP)
Data rate 10/100 MBit/s, autodetect 67, 68 DHCP (UDP)
HTTP mode HTTP/HTTPS (HTTP)* 80 HTTP (TCP)
DHCP on/off (off)* 123 NTP (UDP)
toff (DHCP) 5…60 s (30 s)* 161 SNMP (UDP)
IP address 162 SNMP TRAPS (UDP)
nnn.nnn.nnn.nnn (192.168.0.254)* 443 HTTPS (TCP)
can always be reached via: 169.254.0.1 502 MODBUS (TCP)
Net mask nnn.nnn.nnn.nnn (255.255.0.0)* 4840 OPCUA (TCP)
Protocols (depending on function module selected) 5353 MDNS (UDP)
TCP/IP, Modbus TCP, Modbus RTU, DHCP, SNMP, SMTP, NTP 48862 BCOM (UDP)
BMS bus (internal/external) Environment/EMC
Interface/protocol RS-485/BMS internal or BMS external (BMS internal)* EMC EN 61326-1
Operating mode master/slave (master)*
Ambient temperatures
Baud rate BMS internal 9.6 kBit/s
Operating temperature -25…+55 °C
external 19.2; 38.4; 57.6 kBit/s
Transport -40…+85 °C
Cable length ≤ 1,200 m
Long-term storage -25…+70 °C
Cable shielded, one end of shield connected to PE
recommended: CAT6/CAT7 min. AWG23 Classification of climatic conditions acc. to IEC 60721:
alternative: twisted pair, J-Y(St)Y min. 2x0,8 Stationary use (IEC 60721-3-3) 3K22
Connection X1 (ABMS, BBMS) Transport (IEC 60721-3-2) 2K11
Connection type refer to connection “push-wire terminal X1” Long-term storage (IEC 60721-3-1) 1K22
Terminating resistor 120 Ω (0.25 W), can be connected internally Mechanical conditions acc. to IEC 60721:
Device address, internal/external BMS bus 1…150 (1)*/2…99 Stationary use (IEC 60721-3-3) 3M11
Transport (IEC 60721-3-2) 2M4
Long-term storage (IEC 60721-3-1) 1M12
COM465IP_D00217_10_D_XXEN/02.2022 5
COMTRAXX® COM465IP
Technical data
Connection Other
Connection type pluggable push-wire terminals Operating mode continuous operation
Push-wire terminals Mounting front-oriented, cooling slots must be ventilated vertically
Conductor sizes AWG 24…12 Degree of protection, internal components (IEC 60529) IP30
Stripping length 10 mm Degree of protection, terminals (IEC 60529) IP20
rigid/flexible 0.2…2.5 mm² Quick DIN rail mounting acc. to IEC 60715
flexible with ferrule, with/without plastic sleeve 0.25…2.5 mm² Screw mounting 2 x M4
Multiple conductor, flexible with TWIN ferrule with plastic sleeve 0.5…1.5 mm² Enclosure type J460
Enclosure material polycarbonate
Push-wire terminal X1
Flammability class UL94V-0
Conductor sizes AWG 24…16
Dimensions (W x H x D) 107.5 x 93 x 62.9 mm
Stripping length 10 mm
Documentation number D00216
rigid/flexible 0.2…1.5 mm²
Weight ≤ 240 g
flexible with ferrule without plastic sleeve 0.25…1.5 mm²
flexible with ferrule with plastic sleeve 0.25…0.75 mm² ( )* = factory settings
Ordering information
6 COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP
Application example
Web server Visualisation Integrated functions Additional hardware necessary
E-Mail notification Solution for BACnet
Backups Solution for OPC
Documentations …
Parameter
Data transfer
…
Ethernet
Modbus TCP
COM465DP COM465IP
BCOM
CP907-I
Modbus TCP
Modbus RTU
Modbus RTU iso685-D
PROFIBUS DP PEM PEM
COM465IP_D00217_10_D_XXEN/02.2022 7