COMTRAXX® COM465IP

Condition monitor with integrated gateway


for the connection of Bender devices
to Ethernet TCP/IP networks

COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP Condition monitor with an integrated gateway for the connection
of Bender devices to Ethernet TCP/IP networks

Product description
The COMTRAXX® COM465IP series features a condition monitor and is integrated into the
existing EDP structure like any Ethernet-capable device. All Bender devices can be connected
via the integrated interfaces. In addition, third-party devices can also be integrated into
the system. The measured values, parameters and all other data can be checked and
parameterised via the web interface or the display.
It is possible to indicate and visualise alarms. By means of the visualisation application,
individual overview pages can be generated which are then displayed in a web browser.

Application
• Optimum display and visualisation of device and system states in the web browser
• Monitoring and analysis of compatible Bender products and third-party devices
COMTRAXX® COM465IP
• Specific system overview through individual system description
Device features • Selective notification to various users in the event of alarms
• Condition monitor for Bender systems • Numerous interfaces for data transfer to higher-level systems
• Integrated modular gateway between • Clear setting of device parameters. Storing, documenting and restoring parameters is
Bender systems and TCP/IP enables possible
remote access via LAN, WAN or Internet • Commissioning and diagnosis of Bender systems
• Range of functions adjustable through • Remote diagnosis, remote maintenance
function modules
Scope of functions (V4.5.0 and higher)
• Support of devices that are connected to
the internal or external BMS bus, via Basic device (without function modules)
BCOM, via Modbus RTU or Modbus TCP • Condition monitor with web interface
• Individual visualisation can be generated, • Interfaces for the integration of devices
which is displayed via the web browser
– Internal BMS bus (max. 150 devices) and external* BMS bus (max. 99 x 150 devices)
Data transfer interfaces – BCOM (max. 255 devices)
– Modbus RTU and Modbus TCP (max. 247 devices each)
• Remote display of the latest measured values, status/alarm messages and parameters*
• Gateway to Modbus TCP: Reading the latest measured values, status/alarm messages
from addresses 1…10 of each interface via Modbus TCP
• Gateway to Modbus RTU: Reading the latest measured values, status/alarm messages
from addresses 1…10 of the internal BMS interface via Modbus RTU
• Ethernet interface with 10/100 MBit/s for remote access via LAN, WAN or Internet
Approvals
• Setting of internal device parameters and parameters of devices connected via
Modbus RTU and Modbus TCP **
• Time synchronisation for all assigned devices
• History memory (20,000 entries)
• Data loggers, freely configurable (30 x 10,000 entries)
• 50 data points from third-party devices (via Modbus RTU or Modbus TCP) can be
integrated into the system
• A virtual device with 16 channels can be created
*) Indicating parameters of BMS bus devices is only possible when the gateway is connected to the internal BMS
bus.
**) Parameters can be set via web application and externally (via BMS/ICOM/BCOM),
but not via Modbus. The parameters of assigned devices can only be read; Function module C is necessary for
modification of settings!

2 COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP

Function module A Function module D


• Assignment of individual texts for devices, channels (measuring Quick and easy-to-create visualisation of the system. Integrated
points) and alarms. editor provides access to a variety of widgets and functions.
• Device failure monitoring. • Display on up to 50 overview pages, where e.g. room plans can
• E-mail notification to different users in case of alarms or system be stored. Navigation within these overview pages is possible.
errors. • Access to all measured values that are available in the system.
• Device documentation of any device in the system can be • Buttons and sliders can be used to send BMS test and reset
generated.* * It contains all parameters and measured values commands, as well as to control external devices via Modbus TCP.
belonging to the device, as well as device information such as
serial number and software version. Function module E
• System documentation can be created. It documents all devices • 100 virtual devices with 16 channels each can be created.
in the system at once.
*) Creating device documentation of BMS bus devices is only possible if the gateway Function module F
is connected to the internal BMS bus.
• 1,600 data points from third-party devices (via Modbus RTU or
Function module B Modbus TCP) can be integrated into the system.
• Reading the latest measured values, status and alarms messages Examples:
from all assigned devices. Uniform access to all assigned devices • To write parameters via Modbus, function modules B and C are
via Modbus TCP over integrated server. required.
• Reading the latest measured values, status and alarm messages • To read parameters via Modbus, function module B is required.
from all assigned devices via internal BMS. Uniform access to all
assigned devices via Modbus RTU. • Function modules A and D are required to be able to use a
visualisation in combination with the individual texts.
• Control commands: From an external application (e.g. visuali­
sation software or PLC), commands can be sent to BMS devices
via Modbus TCP or Modbus RTU.
• Access to alarms and measured values via SNMP (V1, V2c or V3).
SNMP traps are supported.
• Access via PROFINET to alarms and measured values.

Function module C
• Fast and easy parameter setting of all devices* assigned to the
gateway via web browser.
• Device backups of all devices in the system can be created and
restored.
*) Parameter setting of BMS bus devices is only possible when the gateway is
connected to the internal BMS bus.

COM465IP_D00217_10_D_XXEN/02.2022 3
COMTRAXX® COM465IP

Operating controls and connections


A1/+
A2/-

3
COM465IP
COMTRAXX®

1 OFF
RMB ON OFF
RBMS ON

6 7 8 9 10

X1

4 5

1 - “ON” LED: Flashes during start-up. 7 - Modbus RTU terminating resistor switch
The LED lights permanently as soon as the device is ready for 8 - BMS bus terminating resistor switch
operation.
9 - Micro USB interface (currently without function) (plug X3)
2 - LEDs show activities on the different interfaces
10 - Mini HDMI interface (currently without function) (plug X4)
3 - Supply voltage: see nameplate and ordering information
4 - Modbus/RTU interface: Terminals AMB and BMB (plug X1) For UL applications, the following has to be observed:
– Maximum ambient temperature: 55 °C
5 - BMS bus (Bender measuring device interface):
– Use 60/75 °C copper wires only
Terminals ABMS and BBMS (plug X1)
6 - Ethernet port (RJ45) for connection to the PC network as well
as BCOM (plug X2)

4 COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP

Technical data
Insulation coordination acc. to IEC 60664-1/IEC 60664-3 BCOM
Rated voltage  AC 250 V Interface/protocol  Ethernet/BCOM
Rated impulse voltage/overvoltage category  4 kV/III BCOM system name (SYSTEM)
Pollution degree  3 BCOM subsystem address 1…255 (1)*
Protective separation (reinforced insulation) between BCOM device address 0…255 (0)*
 (A1/+, A2/-) - [(AMB, BMB), (ABMS, BBMS), (X2), (X3, X4)] Modbus
Bender Modbus image  V1, V2 (V2)*
Supply voltage
Modbus TCP
Supply voltage Us  see ordering information
Interface/protocol  Ethernet/Modbus TCP
Frequency range Us  see ordering information
Operating mode  client for Bender Modbus TCP devices and “third-party devices”
Power consumption  see ordering information
Operating mode server for access to the process image and for Modbus control commands
Indications Parallel data access from different clients  max. 25
LEDs: Modbus RTU
ON  operation indicator Interface/protocol RS-485/Modbus RTU
ETHERNET IP  data traffic Ethernet Operating mode  master/slave (master)*
MODBUS RTU  data traffic Modbus Baud rate  9.6…57.6 kBit/s
BMS  data traffic BMS Cable length  ≤ 1,200 m
Ethernet (terminal X2)  lights during network connection, flashes during data transfer Cable shielded, one end of shield connected to PE
recommended: CAT6/CAT7 min. AWG23
Memory alternative: twisted pair, J-Y(St)Y min. 2x0,8
Individual texts (function module A only)  unlimited number of texts each with 100 characters Connection  X1 (AMB, BMB)
E-mail configuration and device failure monitoring max. 250 entries Connection type  refer to connection “push-wire terminal X1”
Number of data points for “third-party devices” to Modbus TCP and Modbus RTU 50 Terminating resistor  120 Ω (0.25 W), can be connected internally
Number of data loggers 30 Supported Modbus RTU slave addresses  2…247
Number of data points per data logger 10,000 PROFINET
Number of history memory entries 20,000 Interface/protocol  Ethernet/PROFINET
Operating mode  Slave (IO-Device)
Visualisation
SNMP
Number of pages 50
Interface/protocol  Ethernet/SNMP
Background image size 3 MB
Versions 1, 2c, 3
Interfaces Supported devices queries to all devices (channels) possible
Trap support yes
Ethernet
Port  RJ45 Used ports
Cable length < 100 m 53 DNS (UDP/TCP)
Data rate  10/100 MBit/s, autodetect 67, 68 DHCP (UDP)
HTTP mode HTTP/HTTPS (HTTP)* 80 HTTP (TCP)
DHCP  on/off (off)* 123 NTP (UDP)
toff (DHCP)  5…60 s (30 s)* 161 SNMP (UDP)
IP address 162 SNMP TRAPS (UDP)
nnn.nnn.nnn.nnn (192.168.0.254)* 443 HTTPS (TCP)
can always be reached via: 169.254.0.1 502 MODBUS (TCP)
Net mask  nnn.nnn.nnn.nnn (255.255.0.0)* 4840 OPCUA (TCP)
Protocols (depending on function module selected) 5353 MDNS (UDP)
 TCP/IP, Modbus TCP, Modbus RTU, DHCP, SNMP, SMTP, NTP 48862 BCOM (UDP)
BMS bus (internal/external) Environment/EMC
Interface/protocol  RS-485/BMS internal or BMS external (BMS internal)* EMC  EN 61326-1
Operating mode  master/slave (master)*
Ambient temperatures
Baud rate BMS  internal 9.6 kBit/s
Operating temperature  -25…+55 °C
 external 19.2; 38.4; 57.6 kBit/s
Transport  -40…+85 °C
Cable length  ≤ 1,200 m
Long-term storage  -25…+70 °C
Cable shielded, one end of shield connected to PE
recommended: CAT6/CAT7 min. AWG23 Classification of climatic conditions acc. to IEC 60721:
alternative: twisted pair, J-Y(St)Y min. 2x0,8 Stationary use (IEC 60721-3-3)  3K22
Connection  X1 (ABMS, BBMS) Transport (IEC 60721-3-2)  2K11
Connection type  refer to connection “push-wire terminal X1” Long-term storage (IEC 60721-3-1)  1K22
Terminating resistor  120 Ω (0.25 W), can be connected internally Mechanical conditions acc. to IEC 60721:
Device address, internal/external BMS bus  1…150 (1)*/2…99 Stationary use (IEC 60721-3-3)  3M11
Transport (IEC 60721-3-2)  2M4
Long-term storage (IEC 60721-3-1)  1M12

COM465IP_D00217_10_D_XXEN/02.2022 5
COMTRAXX® COM465IP

Technical data
Connection Other
Connection type pluggable push-wire terminals Operating mode  continuous operation
Push-wire terminals Mounting  front-oriented, cooling slots must be ventilated vertically
Conductor sizes AWG 24…12 Degree of protection, internal components (IEC 60529)  IP30
Stripping length 10 mm Degree of protection, terminals (IEC 60529)  IP20
rigid/flexible  0.2…2.5 mm² Quick DIN rail mounting acc. to  IEC 60715
flexible with ferrule, with/without plastic sleeve  0.25…2.5 mm² Screw mounting 2 x M4
Multiple conductor, flexible with TWIN ferrule with plastic sleeve 0.5…1.5 mm² Enclosure type  J460
Enclosure material polycarbonate
Push-wire terminal X1
Flammability class  UL94V-0
Conductor sizes AWG 24…16
Dimensions (W x H x D)  107.5 x 93 x 62.9 mm
Stripping length 10 mm
Documentation number  D00216
rigid/flexible 0.2…1.5 mm²
Weight  ≤ 240 g
flexible with ferrule without plastic sleeve 0.25…1.5 mm²
flexible with ferrule with plastic sleeve 0.25…0.75 mm² ( )* = factory settings

Ordering information

Supply voltage/frequency range Us


Power consumption Application Type Art. No.
AC/DC
Condition monitor with integrated gateway:
24…240 V, 50…60 Hz ≤ 6.5 VA/≤ 4 W COM465IP-230V B95061065
Bender system/Ethernet

Function modules Dimension diagram


62,9
Function module
Application Art. No. 107,5 48,5
(software licence)
Individual text messages for all devices/
channels, device failure monitoring, e-mail in Function module A B75061011
the event of an alarm, device documentation
Provision of data via via Modbus TCP, Modbus 62 40 33 93 45
Function module B B75061012
RTU, SNMP and PROFINET
Parameter setting of all integrated devices, Function module C B75061013
device backups

Visualisation application Function module D B75061014

Virtual devices Function module E B75061015

Integration of third-party devices Function module F B75061016

6 COM465IP_D00217_10_D_XXEN/02.2022
COMTRAXX® COM465IP

Application example
Web server Visualisation Integrated functions Additional hardware necessary
E-Mail notification Solution for BACnet
Backups Solution for OPC
Documentations …
Parameter
Data transfer

Ethernet

Modbus TCP
COM465DP COM465IP
BCOM

CP907-I
Modbus TCP

Modbus RTU
Modbus RTU iso685-D
PROFIBUS DP PEM PEM

ext. BMS bus


CP915
MK800
PEM PEM COMTRAXX®
MK800

BMS bus BMS bus BMS bus BMS bus

COM465IP_D00217_10_D_XXEN/02.2022 7
Bender GmbH & Co. KG
Londorfer Straße 65 • 35305 Grünberg • Germany
Tel.: +49 6401 807-0 • info@bender.de • www.bender.de

BENDER Group
COM465IP_D00217_10_D_XXEN / 02.2022 / © Bender GmbH & Co. KG, Germany – subject to change! The specified standards take into account the edition valid until 02.2022 unless otherwise indicated.