Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

TeSys D contactor - 4P

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Product data sheet

Specifications

TeSys D contactor - 4P(2 NO + 2


NC) - AC-1 <= 440 V 60 A 220 V AC
50/60 Hz coil
LC1D40008M7

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys

Product name TeSys D

Product or component type Contactor

Device short name LC1D

Contactor application Resistive load

Utilisation category AC-1

Poles description 4P

Power pole contact composition 2 NO + 2 NC

[Ue] rated operational voltage Power circuit: <= 690 V AC 25...400 Hz


Power circuit: <= 300 V DC

[Ie] rated operational current 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit

Control circuit type AC at 50/60 Hz

[Uc] control circuit voltage 220 V AC 50/60 Hz

[Uimp] rated impulse withstand 6 kV conforming to IEC 60947


voltage

Overvoltage category III

[Ith] conventional free air 60 A (at 60 °C) for power circuit


thermal current

Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand 320 A 40 °C - 10 s for power circuit


current 720 A 40 °C - 1 s for power circuit
72 A 40 °C - 10 min for power circuit
165 A 40 °C - 1 min for power circuit

Associated fuse rating 80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit

Average impedance 1.5 mOhm - Ith 60 A 50 Hz for power circuit

[Ui] rated insulation voltage Power circuit: 600 V CSA certified


Power circuit: 600 V UL certified
Power circuit: 690 V conforming to IEC 60947-4-1

Electrical durability 1.4 Mcycles 60 A AC-1 at Ue <= 440 V

Power dissipation per pole 5.4 W AC-1

Front cover Without

Mounting support Plate

Oct 27, 2021 1


Rail

Standards CSA C22.2 No 14


EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508

Product certifications RINA


GL
UL
GOST
BV
LROS (Lloyds register of shipping)
DNV
CCC
CSA
UKCA

Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²solid without cable end

Tightening torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm

Operating time 4...19 ms opening


12...26 ms closing

Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability 6 Mcycles

Maximum operating rate 3600 cyc/h 60 °C

Complementary
Coil technology Without built-in suppressor module

Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz


0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA 140 VA 60 Hz cos phi 0.75 (at 20 °C)


160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in 13 VA 60 Hz cos phi 0.3 (at 20 °C)


VA 15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation 4…5 W at 50/60 Hz

Environment
IP degree of protection IP20 front face conforming to IEC 60529

Protective treatment TH conforming to IEC 60068-2-30

Pollution degree 3

Ambient air temperature for -40…60 °C


operation 60…70 °C with derating

Ambient air temperature for -60…80 °C


storage

Operating altitude 0...3000 m

Fire resistance 850 °C conforming to IEC 60695-2-1

Flame retardance V1 conforming to UL 94

Mechanical robustness Vibrations contactor open: 2 Gn, 5...300 Hz


Vibrations contactor closed: 4 Gn, 5...300 Hz

2
Oct 27, 2021
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 10 Gn for 11 ms

Height 127 mm

Width 85 mm

Depth 125 mm

Product weight 1.44 kg

Packing Units
Unit Type of Package 1 PCE

Number of Units in Package 1 1

Package 1 Weight 1.47 kg

Package 1 Height 11.2 cm

Package 1 width 13.5 cm

Package 1 Length 15.2 cm

Unit Type of Package 2 S02

Number of Units in Package 2 5

Package 2 Weight 7.605 kg

Package 2 Height 15 cm

Package 2 width 30 cm

Package 2 Length 40 cm

Package 3 Height 73.5 cm

Offer Sustainability
Sustainable offer status Green Premium product

REACh Regulation REACh Declaration

REACh free of SVHC Yes

EU RoHS Directive Compliant


EU RoHS Declaration

Toxic heavy metal free Yes

Mercury free Yes

RoHS exemption information Yes

China RoHS Regulation China RoHS declaration


Pro-active China RoHS declaration (out of China RoHS legal scope)

Environmental Disclosure Product Environmental Profile

Circularity Profile End of Life Information

WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins

California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov

Contractual warranty
Warranty 18 months

Oct 27, 2021 3