TeSys D contactor - 4P
TeSys D contactor - 4P
TeSys D contactor - 4P
Specifications
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys
Poles description 4P
[Ie] rated operational current 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
Irms rated making capacity 800 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 800 A at 440 V for power circuit conforming to IEC 60947
Associated fuse rating 80 A gG at <= 690 V coordination type 1 for power circuit
80 A gG at <= 690 V coordination type 2 for power circuit
Connections - terminals Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible without cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 1…35 mm²solid without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…25 mm²solid without cable end
Tightening torque Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm
Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm
Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Complementary
Coil technology Without built-in suppressor module
Environment
IP degree of protection IP20 front face conforming to IEC 60529
Pollution degree 3
2
Oct 27, 2021
Shocks contactor closed: 15 Gn for 11 ms
Shocks contactor open: 10 Gn for 11 ms
Height 127 mm
Width 85 mm
Depth 125 mm
Packing Units
Unit Type of Package 1 PCE
Package 2 Height 15 cm
Package 2 width 30 cm
Package 2 Length 40 cm
Offer Sustainability
Sustainable offer status Green Premium product
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony
trioxide, which is known to the State of California to cause cancer. For more information go to
www.P65Warnings.ca.gov
Contractual warranty
Warranty 18 months