S-SERIES Pressure Switches

Switches for Pressure to 8000 psig, Vacuum, Differential, or Level Control with General Purpose, Watertight or Explosion-Proof Enclosures
Features:
Set point repeatability, +1% of operating range. All wiring terminals, adjustments and visual scales are accessible from the front of the switch. Choice of general purpose, watertight or explosionproof enclosures. Choice of fixed or full-range adjustable deadband. Choice of single or two-stage units. Manual reset units available. Mounts in any position. Rugged and vibration resistant. Visual adjustment scales in psi and bars. External adjusting nuts. Separate electrical, pressure and adjusting chambers. Wide selection of transducer wetted materials suitable for air, water, oil or corrosive fluids. Mix and match switch and transducer components for increased stock flexibility or to change pressure ranges in field.

Standard Electrical Ratings


SA, SB, SC, SD and SE Series 15 Amp Res., 125 VAC 10 Amp Res., 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp Res., 125 VDC 1/4 Amp Res., 250 VDC

General Description:
ASCO S-Series pressure switches consist of a switch unit and a transducer unit. They can be ordered separately for customer stocking and/or field assembly or as a complete factory-assembled unit.

SPDT
NO C NC

Switch
S-Series pressure switch units incorporate the unique ASCO TRI-POINT alternating fulcrum balance plate to control the operation of one or more electrical snapaction swtiches. The electrical snap-action switch together with the adjusting mechanism is a fully-tested, self-contained subassembly.

^ %
Standard Temperature Ratings
Ambient: -4F (-20C) to 140F (60C) Fluid: For Buna N or Neoprene Diaphragm -4F (-20C) to 180F (82C) For Viton Diaphragm -4F (-20C) to 250F (121C) For 316 SS Diaphragm -50F (-45C) to 300F (149C)

Transducer
Transducer unit incorporates a diaphragm/piston type pressure sensor, and is also a fully-tested, self-contained subassembly.

Operation
When pressure is applied to the transducer it is converted into movement of the piston. This piston movement is then used to control the operation of the electrical snap-action switch in the switch unit.
14

Options (See pages 34-35)

4
Enclosures
ASCO TRI-POINT S-Series switches are available in three standard enclosures. All of these enclosed units are made in accordance with NEMA and UL standards. General Purpose Type 1. These enclosures are designed for indoor use to protect personnel from accidental contact with the equipment. S-Series general purpose switch units consist of a copper-free* aluminum die-cast body with a formed copper-free* aluminum cover; two 3/4 conduit hubs with one plug are provided. Watertight Type 4. Watertight and dust-tight enclosures are intended for use indoors and outdoors to protect the enclosed equipment against splashing or falling water, windblown dust and water, hose directed water, and severe external condensation. S-Series watertight switch units have a copper-free* aluminum die-cast body and a formed copper-free* aluminum cover with Buna N gaskets; two 3/4 conduit hubs with one plug are provided. Explosion-Proof Types 7 and 9. Type 7 enclosures are intended for use in locations defined by the National Electrical Code as Class I. Type 9 enclosures are intended for Class II locations.

123

Class I locations are those in which flammable gases are or may be present in the air in sufficient quantities to produce explosive or ignitable mixtures. Class I locations are classified by group letter, which defines particular atmospheres. Division 1 locations are areas where the hazardous concentration exists continuously, intermittently or periodically under normal operating conditions. Division 2 locations are those where the hazardous vapors are present only in case of accidental rupture or breakdown of equipment. ASCO TRI-POINT explosion-proof enclosures with letter B, C or D in the fifth position are listed for Class I, Groups B, C, and D, Division 1. They are also suitable for the less stringent Division 2 environment. Class II locations are those which are hazardous because of the presence of combustible dust. All ASCO TRI-POINT explosion-proof enclosures are listed for Groups E, F, and G locations. The switch body and cover are die-cast copper-free* aluminum with a Buna N gasket. Two 3/4 conduit hubs with one plug are provided.

Dimensions (inches)
S-Series Pressure

With Types TD - TV Transducers

With Types TA - TC Transducers

1/4 NPT VENT CONNECTION ON DOUBLE CHAMBER TRANSDUCERS


3.5

ADDITIONAL SPACE REQUIRED FOR REMOVAL OF COVER


3.7

ADDITIONAL SPACE REQUIRED FOR REMOVAL OF COVER

3.5

2.2 1.5

1.6

2.3

1.03

1.03 1.6 2.3

3/4 NPT FOR CONDUIT CONN. BOTH ENDS


7.4

3/4 NPT FOR CONDUIT CONN. BOTH ENDS

7.5

1.0

11/32 DIA. FOR MOUNTING (2PLACES)


1.0

4.3

11/32 DIA. FOR MOUNTING (2PLACES)

4.1
2.2

3.2 3.7

4.06

1.7

1/4 NPT

1/4 OR 1/2 NPT


2.9
1

7.0

ON TV SERIES ADD 7/16" TO THESE DIMENSIONS


3.2 7.0

* Less than 0.6% copper.

15

S-SERIES Pressure Switches


How to Select and Order

(to 8000 psig)

ASCO S-Series switches consist of two components, the switch unit and the transducer unit.

How to Select
1. Select the adjustable operating range based on desired actuation pressure. 2. Check that proof pressure is sufficient. 3. Read across and select the desired S-Series switch unit with the proper enclosure. 4. Continue across and select a matching transducer unit compatible with the fluid.

Select S-Series pressure switch


SA Switch Unit
Single-Stage Adjustable Deadband units allow independent adjustment of the set and reset points over the full operating range of the switch. The minimum difference between set and reset points is the deadband listed below; the maximum difference is the full range of the switch .

SB, SD or SE Switch Unit


SB Switch Unit: Single-Stage Fixed Deadband units have an adjustable set point and a non-adjustable automatic reset point. SD Switch Unit: Manual reset on decreasing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure. (To order, change second digit to letter D, e.g., S B 40D becomes S D 40D). SE Switch Unit: Manual reset on increasing pressure units operate automatically on decreasing pressure and must be reset manually on increasing pressure. (To order, change second digit to letter E, e.g., S B 40D becomes S E 40D).

How to Order
Factory assembled Simply order the switch and transducer unit by catalog number joined by a slash (/), e.g., SA40D/TA40A11. Field assembled Simply order the switch and transducer units separately by individual catalog number, e.g., one SA40D and one TA40A11.

General Purpose

Specifications

Adjustable Deadband
Adjustable Deadband Maximum Full Scale General Watertight ExplosionPurpose Enclosure Proof Catalog No. Catalog No.

Fixed Deadband or Manual Reset

Adjustable Operating Range (psig)

Proof Pressure (psig)

Minimum At Mid-Range Catalog (psig) 1 No.

Fixed Deadband At Mid-Range (psig) 1

General Watertight ExplosionPurpose Enclosure Proof Catalog No. Catalog No. Catalog No.

0 - 12 W.C. 0 - 27 W.C. 0 - 65 W.C. 15 - 140 W.C. 15 - 250 W.C. 25 - 400 W.C. 0.4 - 4.5 0.7 - 9.0 0.8 - 9.0 1.0 - 18 1.0 - 18 1.5 - 36 2 - 60 5 - 60 3 - 100 5 - 120 5 - 200 6 - 200 13 - 300 15 - 400 30 - 600 50 - 1000 75 - 1500 200 - 3500 500 - 8000 16

25 25 25 40 40 40 100 100 150 100 150 150 150 3000 200 3000 3000 400 600 600 900 1500 2300 5000 9000
1

1.5 W.C. 2.0 W.C. 2.5 W.C. 6 W.C. 10 W.C. 15 W.C. 0.4 0.6 1.4 1.1 1.6 2.2 3.6 6.0 6.0 10 14 12 18 24 36 75 115 225 450

SA40D SA30D SA20D SA20D SA10D SA10D SA40D SA30D SA40D SA20D SA30D SA20D SA10D SA30D SA10D SA20D SA10D SA10D SA10D SA10D SA10D SA10D SA10D SA10D SA10D

SA41D SA31D SA21D SA21D SA11D SA11D SA41D SA31D SA41D SA21D SA31D SA21D SA11D SA31D SA11D SA21D SA11D SA11D SA11D SA11D SA11D SA11D SA11D SA11D SA11D

SA42D SA32D SA22D SA22D SA12D SA12D SA42D SA32D SA42D SA22D SA32D SA22D SA12D SA32D SA12D SA22D SA12D SA12D SA12D SA12D SA12D SA12D SA12D SA12D SA12D

1.0 W.C. 1.2 W.C. 1.4 W.C. 3 W.C. 6 W.C. 8 W.C. 0.3 0.3 0.8 0.4 1.0 0.9 1.5 4.0 2.5 5.0 6.0 5.0 8 10 15 30 45 125 275

SB40D SB30D SB20D SB20D SB10D SB10D SB40D SB30D SB40D SB20D SB30D SB20D SB10D SB30D SB10D SB20D SB10D SB10D SB10D SB10D SB10D SB10D SB10D SB10D SB10D

SB41D SB31D SB21D SB21D SB11D SB11D SB41D SB31D SB41D SB21D SB31D SB21D SB11D SB31D SB11D SB21D SB11D SB11D SB11D SB11D SB11D SB11D SB11D SB11D SB11D

SB42D SB32D SB22D SB22D SB12D SB12D SB42D SB32D SB42D SB22D SB32D SB22D SB12D SB32D SB12D SB22D SB12D SB12D SB12D SB12D SB12D SB12D SB12D SB12D SB12D

All switch units above are in stock for immediate delivery.


Values shown are nominal.

4
Options Add appropriate suffix for desired option (see pages 34-35). Important Note: The third digit of each of the catalog numbers must be identical, e.g., SA 4 0D and TA 4 0A11.

123

Select transducer unit below

SA, SB, SC, SD and SE unit below


SC Switch Unit
Two-Stage Fixed Deadband units consist of two separate snap-action switches, each with an independently adjustable set point and non-adjustable reset point. The difference between the set and reset points of each switch is the deadband listed below; the minimum difference between the set points of the two switches is the separation.

Series TA-TC

Series TD-TQ

Standard connection is 1/4 NPT; (Optional 1/2 NPT add suffix B to catalog numbers TD thru TQ)

Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of the transducer. They are diaphragm/piston type transducers using an elastomer in contact with the fluid, backed by a piston cylinder. This allows high sensitivity for low pressures and strength for high pressures. Explosion Proof

Two-Stage Fixed Deadband


Separation Fixed Deadband At Mid-Range (psig) 1 Maximum Full Scale Minimum At Mid-Range (psig) 1 General Purpose Catalog No. Watertight Enclosure Catalog No. ExplosionProof Catalog No. Air, Oil or Gas Aluminum & Buna N Catalog No.

Transducer Units
Water, Air Oil or Gas Brass & Buna N Catalog No. Corrosive Fluids All 316 SS Catalog No. 316 SS & Viton 3 Catalog No.

1.2 W.C. 1.4 W.C. 1.6 W.C. 4.0 W.C. 7.0 W.C. 13.0 W.C. 0.4 0.4 1.0 0.6 1.2 1.4 2.2 5.5 3.5 7.0 8.5 7.0 10 14 20 40 60 150 300
2

2.4 W.C. 2.7 W.C. 6.5 W.C. 14 W.C. 25 W.C. 40 W.C. 0.7 0.9 1.6 1.8 1.8 3.6 6 8 10 12 20 20 30 40 60 100 150 350 800

SC40D SC30D SC20D SC20D SC10D SC10D SC40D SC30D SC40D SC20D SC30D SC20D SC10D SC30D SC10D SC20D SC10D SC10D SC10D SC10D SC10D SC10D SC10D SC10D SC10D

SC41D SC31D SC21D SC21D SC11D SC11D SC41D SC31D SC41D SC21D SC31D SC21D SC11D SC31D SC11D SC21D SC11D SC11D SC11D SC11D SC11D SC11D SC11D SC11D SC11D
3

SC42D SC32D SC22D SC22D SC12D SC12D SC42D SC32D SC42D SC22D SC32D SC22D SC12D SC32D SC12D SC22D SC12D SC12D SC12D SC12D SC12D SC12D SC12D SC12D SC12D

TA40A11 TA30A11 TA20A11 TB20A11 TB10A11 TC10A11 TD40A11 TD30A11 --TD20A11 --TE20A11 TE10A11 --TE10A11 ----TG10A11 TH10A11 TJ10A11 -----------

------------TD40A21 TD30A21 --TD20A21 --TE20A21 TE10A21 --TF10A21 ----TG10A21 TH10A21 TJ10A21 TK10A21 TL10A21 TM10A21 TN10B21 ---

----------------TE40A44 --TE30A44 TE20A44 TE10A44 --TF10A44 ----TG10A44 TH10A44 TJ10A44 -----------

TA40A32 TA30A32 TA20A32 TB20A32 TB10A32 TC10A32 TD40A42 TD30A42 --TD20A42 --TE20A42 TE10A42 TG33A42 TF10A42 TG23A42 TG13A42 TG10A42 TH10A42 TJ10A42 TK10A42 TL10A42 TM10A42 TN10B42 TQ10B42 17

All switch units and transducer units above are in stock for immediate delivery.
316 SS transducers increase deadband by 50%. Transducers ending in 32 have 303 SS process connections, not 316 SS.

S-SERIES Vacuum, Differential, Level Switches


How to Select and Order
ASCO S-Series switches consist of two components, the switch unit and the transducer unit.

How to Select
1. Select the adjustable operating range based on desired actuation point. 2. Check that proof pressure is sufficient. 3. Read across and select the desired S-Series switch unit with the proper enclosure. 4. Continue across and select a matching transducer unit compatible with the fluid.

Select S-Series pressure switch


SA Switch Unit
Single-Stage Adjustable Deadband units allow independent adjustment of the set and reset points over the full operating range of the switch. The minimum difference between set and reset points is the deadband listed below; the maximum difference is the full range of the switch .

SB, SD or SE Switch Unit


SB Switch Unit: Single-Stage Fixed Deadband units have an adjustable set point and a non-adjustable automatic reset point. SD Switch Unit: Manual reset on decreasing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure. (To order, change second digit to letter D, e.g., S B 30D becomes S D 30D). SE Switch Unit: Manual reset on increasing pressure units operate automatically on decreasing pressure and must be reset manually on increasing pressure. (To order, change second digit to letter E, e.g., S B 30D becomes S E 30D).

How to Order
Factory assembled Simply order the switch and transducer unit by catalog number joined by a slash (/), e.g., SA30D/TA34A11. Field assembled Simply order the switch and transducer units separately by individual catalog number, e.g., one SA30D and one TA34A11.

General Purpose

Specifications

Adjustable Deadband

Fixed Deadband or Manual Reset

Adjustable Operating Range (In W.C.) Vacuum

Proof Pressure (psig)

Adjustable Deadband At Mid-Range (In W.C.) 1 From/To

General ExplosionPurpose Watertight Proof Catalog No. Catalog No. Catalog No.

Fixed Deadband At Mid-Range (In W.C.) 1

General ExplosionPurpose Watertight Proof Catalog No. Catalog No. Catalog No.

0 15 PSI 0 0 15 15 25 0 0 0 15 15 25
Level

30 Hg 30 Hg 27 65 140 250 400 12 27 65 140 250 400 12 27 65 140 250 400

50 50 15 15 25 25 25 15 15 15 25 25 25 125 125 125 125 125 125

2 - 28 Hg 3 - 57 Hg 2 - 27 3 - 65 6 - 125 10 - 235 15 - 375 2 2 3 6 10 15 2 2 3 6 10 15 12 27 65 125 235 375 12 27 65 125 235 375

SA30D SA20D SA30D SA20D SA20D SA10D SA10D SA40D SA30D SA20D SA20D SA10D SA10D SA40D SA30D SA20D SA20D SA10D SA10D

SA31D SA21D SA31D SA21D SA21D SA11D SA11D SA41D SA31D SA21D SA21D SA11D SA11D SA41D SA31D SA21D SA21D SA11D SA11D

SA32D SA22D SA32D SA22D SA22D SA12D SA12D SA42D SA32D SA22D SA22D SA12D SA12D SA42D SA32D SA22D SA22D SA12D SA12D

1.2 Hg 1.7 Hg 1.2 1.4 3.0 6.0 8.0 1.0 1.2 1.4 3.0 6.0 8.0 1.0 1.2 1.4 3.0 6.0 8.0

SB30D SB20D SB30D SB20D SB20D SB10D SB10D SB40D SB30D SB20D SB20D SB10D SB10D SB40D SB30D SB20D SB20D SB10D SB10D

SB31D SB21D SB31D SB21D SB21D SB11D SB11D SB41D SB31D SB21D SB21D SB11D SB11D SB41D SB31D SB21D SB21D SB11D SB11D

SB32D SB22D SB32D SB22D SB22D SB12D SB12D SB42D SB32D SB22D SB22D SB12D SB12D SB42D SB32D SB22D SB22D SB12D SB12D

Differential

0 0 0 15 15 25

All switch units above are in stock for immediate delivery.

18

Values shown are nominal.

4
Options Add appropriate suffix for desired option (see pages 34-35). Important Note: The third digit of each of the catalog numbers must be identical, e.g., SA 3 0D and TA 3 4A11.

123

Select transducer unit below


The vacuum transducer has a spring which preloads the switch unit when no vacuum is applied. On application, the vacuum acts on a piston area to overcome the spring to operate the switch unit.

SA, SB, SC, SD and SE unit below


SC Switch Unit
Two-Stage Fixed Deadband units consist of two separate snap-action switches, each with an independently adjustable set point and non-adjustable reset point. The difference between the set and reset points of each switch is the deadband listed below; the minimum difference between the set points of the two switches is the separation.

Vacuum Transducer

The differential pressure transducer has two pressure sources acting on the piston area in opposite directions. The force output is proportional to the difference between these pressures, allowing the differential pressure to be contolled by adjustment of the switch unit. Differential Pressure Transducer The level control unit uses shop air between 15-125 psi. The air is regulated to between 1 and 1-1/2 SCFH through a tube to sense the liquid level within an open or vented tank. The static back pressure created by the liquid level against an air stream activates the level control.

Explosion Proof

Level Control Unit

Two-Stage Fixed Deadband


Separation Maximum Fixed Full Scale Deadband At Minimum At Mid-Range Mid-Range (In W.C.) 1 (In W.C.) 1 General Purpose Catalog No. ExplosionProof Catalog No. Air or Gas Watertight Catalog No. Aluminum & Buna N Catalog No.

Transducer Units
Water, Air Oil or Gas Brass & Buna N Catalog No. Corrosive Fluids 303 SS & Viton Catalog No. Level Control Units Aluminum & Buna N Catalog No.

1.7 Hg 2.0 Hg 1.7 2.0 4.0 7.0 13.0 1.4 1.7 2.0 4.0 7.0 13.0 1.4 1.7 2.0 4.0 7.0 13.0

3 Hg 8 Hg 2.7 6.5 14.0 25.0 40.0 2.4 2.7 6.5 14.0 25.0 40.0 2.4 2.7 6.5 14.0 25.0 40.0

SC30D SC20D SC30D SC20D SC20D SC10D SC10D SC40D SC30D SC20D SC20D SC10D SC10D SC40D SC30D SC20D SC20D SC10D SC10D

SC31D SC21D SC31D SC21D SC21D SC11D SC11D SC41D SC31D SC21D SC21D SC11D SC11D SC41D SC31D SC21D SC21D SC11D SC11D

SC32D SC22D SC32D SC22D SC22D SC12D SC12D SC42D SC32D SC22D SC22D SC12D SC12D SC42D SC32D SC22D SC22D SC12D SC12D

TV34A11 TV24A11 TA31A11 TA21A11 TB21A11 TB11A11 TC11A11 TA41A11 TA31A11 TA21A11 TB21A11 TB11A11 TC11A11 -------------

TV34A21 TV24A21 -----------------------------------

TV34A32 TV24A32 -----------------------------------

--------------------------TA05A11 TA05A11 TA05A11 TB05A11 TB05A11 TC05A11

All switch units and transducer units above are in stock for immediate delivery.

19

S-SERIES Combustion Switches


Pressure Switches Designed to UL or FM Requirements for Combustion Service
Features:
Set point repeatability, +1% of operating range. UL Listed in the gas and oil equipment list. FM Approved as pressure supervisory switches. Externally visible pressure setting scales. External adjusting nuts. Choice of fixed or full-range adjustable deadbands. Choice of single or two-stage units. Mounts in any position. Rugged and vibration resistant. Separate electrical, pressure and adjusting chambers. Mix and match switch and transducer components for increased stock flexibility or to change pressure ranges in field. Withstands high surge pressures.

General Description:
ASCO S-Series combustion switches consist of a switch unit and a transducer unit. They can be ordered separately for customer stocking and/or field assembly or as a complete factory-assembled unit.

Standard Electrical Ratings


SA, SD and SE Series 1 5 Amp Res., 125, 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp Res., 125 VDC 1/4 Amp Res., 250 VDC SB and SC Series 5 Amp Res., 125, 250 VAC 1/4 HP, 125 VAC 1/2 HP, 250 VAC .4 Amp Res., 125, VDC
1

Switch
S-Series combustion switch units incorporate the unique ASCO TRI-POINT alternating fulcrum balance plate to control the operation of one or more electrical snap-action swtiches. The electrical snap-action switch together with the adjusting mechanism is a fully-tested, self-contained subassembly.

SPDT
NO C NC

Transducer
Transducer unit incorporates a diaphragm/piston type pressure sensor, and is also a fully-tested, self-contained subassembly.

SD and SE Series not FM Approved.

^#

Operation
When pressure is applied to the transducer it is converted into movement of the piston. This piston movement is then used to control the operation of the electrical snap-action switch in the switch unit.

Standard Temperature Ratings


Ambient: -4F (-20C) to 140F (60C) Fluid: For Buna N or Neoprene Diaphragm -4F (-20C) to 180F (82C) For Viton Diaphragm -4F (-20C) to 250F (121C) For 316 SS Diaphragm -50F (-45C) to 300F (149C)

Options (See pages 34-35) Dimensions (See page 15)


20

123

UL Requirements
Underwriters Laboratories, Inc.s Standard UL 353 defines construction and performance requirements for limit controls.

Switch
S-Series combustion switch units when mated to the pressure transducers described below form pressure switches in accordance with UL requirements.

Class I locations are those in which flammable gases are or may be present in the air in sufficient quantities to produce explosive or ignitable mixtures. Class I locations are classified by group letter, which defines particular atmospheres. Division 1 locations are areas where the hazardous concentration exists continuously, intermittently or periodically under normal operating conditions. Division 2 locations are those where the hazardous vapors are present only in case of accidental rupture or breakdown of equipment. ASCO TRI-POINT explosion-proof enclosures with letter B, C or D in the fifth position are listed for Class I, Groups B, C, and D, Division 1. They are also suitable for the less stringent Division 2 environment. Class II locations are those which are hazardous because of the presence of combustible dust. All ASCO TRI-POINT explosion-proof enclosures are listed for Groups E, F, and G locations. The switch body and cover are die-cast copper-free* aluminum with a Buna N gasket. Two 3/4 conduit hubs with one plug are provided.

Transducers
Fuel Gas UL requires a pressure transducer with a secondary chamber. This chamber allows the gas to be vented to a safe location in the event of primary sensing element rupture. The double chamber with vent pressure transducers meet this requirement. Fuel Oil UL requirements for fuel oil applications waive the double chamber requirement, providing the sensing element is made of Type 316 or 321 SS. S-Series type 316 SS pressure transducers are designed to meet this requirement. General Service Pressure transducers for water, steam and air service may be of the single chamber design.

FM Requirements
Fuel Gas and Fuel Oil FM requires that fuel gas and fuel oil pressure supervisory switches shall have a visible external means of determining switch position. No specific constructions are required for the pressure transducer. Switch units with visual position indication (suffix V) in conjunction with single chamber pressure transducers will meet these requirements. General Service Standard switch units with an adjusting nut cover, when mated to single chamber transducers, meet FM requirements for general applications such as airflow interlocking switches.

Enclosures
ASCO TRI-POINT S-Series switches are available in three standard enclosures. All of these enclosed units are made in accordance with NEMA and UL standards. General Purpose Type 1. These enclosures are designed for indoor use to protect personnel from accidental contact with the equipment. S-Series general purpose switch units consist of a copper-free* aluminum die-cast body with a formed copper-free* aluminum cover; two 3/4 conduit hubs with one plug are provided. Watertight Type 4. Watertight and dust-tight enclosures are intended for use indoors and outdoors to protect the enclosed equipment against splashing or falling water, windblown dust and water, hose directed water, and severe external condensation. S-Series watertight switch units have a copper-free* aluminum die-cast body and a formed copper-free* aluminum cover with Buna N gaskets; two 3/4 conduit hubs with one plug are provided.

Enclosures
General Purpose Designed to Type 1 specifications for indoor applications. Die casting is copper-free* aluminum; covers are polycarbonate. Two 3/4 conduit hubs with one plug are provided.

Watertight Designed to Types 4 specifications for indoor/outdoor use. Die casting is copper-free* aluminum. Cover are polycarbonate and gaskets are Explosion-Proof Types 7 and 9. Type 7 enclosures neoprene. Two 3/4 conduit hubs with one plug are are intended for use in locations defined by the National provided. Electrical Code as Class I. Type 9 enclosures are intended for Class II locations. * Less than 0.6% copper.
21

S-SERIES Combustion Switches


How to Select and Order
ASCO S-Series switches consist of two components, the switch unit and the transducer unit.

How to Select
1. Select the adjustable operating range based on desired actuation pressure. 2. Check that proof pressure is sufficient. 3. Read across and select the desired S-Series switch unit with the proper enclosure. 4. Continue across and select a matching transducer unit compatible with the fluid.

Select S-Series pressure switch


SA Switch Unit
Single-Stage Adjustable Deadband units allow independent adjustment of the set and reset points over the full operating range of the switch. The minimum difference between set and reset points is the deadband listed below; the maximum difference is the full range of the switch .

SB, SD or SE Switch Unit


SB Switch Unit: Single-Stage Fixed Deadband units have an adjustable set point and a non-adjustable automatic reset point. SD Switch Unit: Manual reset on decreasing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure. (To order, change second digit to letter D, e.g., S B 30D becomes S D 30D). SE Switch Unit: Manual reset on increasing pressure units operate automatically on decreasing pressure and must be reset manually on increasing pressure. (To order, change second digit to letter E, e.g., S B 30D becomes S E 30D).

How to Order
Factory assembled Simply order the switch and transducer unit by catalog number joined by a slash (/), e.g., SA30D/TA31A11. Field assembled Simply order the switch and transducer units separately by individual catalog number, e.g., one SA30D and one TA31A11.

UL General Purpose

Specifications

Adjustable Deadband
Adjustable Deadband Maximum Full Scale

Fixed Deadband or Manual Reset

Adjustable Operating Range (psig) UL Listed

Proof Pressure (psig)

Minimum At Mid-Range (psig) 1

General Watertight ExplosionPurpose Enclosure Proof Catalog No. Catalog No. Catalog No.

Fixed Deadband At Mid-Range (psig.) 1

General Watertight ExplosionPurpose Enclosure Proof Catalog No. Catalog No. Catalog No.

0 0 15 15 25 0.8 1.0 1.5 1.5 2.0 2.0 3.0 2 2 2 15 15 25 0.4 0.8 1.0 1.5 2.0 3.0
1

27 W.C. 65 W.C. 140 W.C. 250 W.C. 400 W.C. 9.0 18 30 36 60 60 100 12 W.C. 27 W.C. 65 W.C. 140 W.C. 250 W.C. 400 W.C. 4.5 9.0 18 36 60 100

15 15 25 25 25 150 150 200 150 150 200 200 25 25 25 40 40 40 100 100 100 150 150 200
2

2.0 W.C. 2.5 W.C. 6.0 W.C. 10.0 W.C. 15.0 W.C. 1.4 4.6 4.0 3.3 5.4 5.0 9.0 1.5 W.C. 2.0 W.C. 2.5 W.C. 6.0 W.C. 10.0 W.C. 1 5.0 W.C. 0.4 0.6 1.1 2.2 3.6 6.0

SA30D SA20D SA20D SA10D SA10D SA40D SA30D SA30D SA20D SA10D SA20D SA10D SA40DV SA30DV SA20DV SA20DV SA10DV SA10DV SA40DV SA30DV SA20DV SA20DV SA10DV SA10DV

SA31D SA21D SA21D SA11D SA11D SA41D SA31D SA31D SA21D SA11D SA21D SA11D SA41DV SA31DV SA21DV SA21DV SA11DV SA11DV SA41DV SA31DV SA21DV SA21DV SA11DV SA11DV

SA32D SA22D SA22D SA12D SA12D SA42D SA32D SA32D SA22D SA12D SA22D SA12D -------------------------

1.2 W.C. 1.4 W.C. 3.0 W.C. 6.0 W.C. 8.0 W.C. 0.9 0.6 1.5 1.4 2.3 2.0 3.7 1.0 W.C. 1.2 W.C. 1.4 W.C. 3.0 W.C. 6.0 W.C. 8.0 W.C. 0.3 0.3 0.4 0.9 1.5 2.5

SB30D SB20D SB20D SB10D SB10D SB40D SB30D SB30D SB20D SB10D SB20D SB10D SB40DV SB30DV SB20DV SB20DV SB10DV SB10DV SB40DV SB30DV SB20DV SB20DV SB10DV SB10DV

SB31D SB21D SB21D SB11D SB11D SB41D SB31D SB31D SB21D SB11D SB21D SB11D SB41DV SB31DV SB21DV SB21DV SB11DV SB11DV SB41DV SB31DV SB21DV SB21DV SB11DV SB11DV

SB32D SB22D SB22D SB12D SB12D SB42D SB32D SB32D SB22D SB12D SB22D SB12D -------------------------

FM Approved

Values shown are nominal.

Manual reset units not available for FM.

22

4
Options Add appropriate suffix for desired option
(see pages 34-35).

123

Important Note: The third digit of each of the catalog


numbers must be identical, e.g., SA 3 0D and TA 3 1A11.

Select transducer unit below

SA, SB, SC, SD and SE unit below


SC Switch Unit
Two-Stage Fixed Deadband units consist of two separate snap-action switches, each with an independently adjustable set point and non-adjustable reset point. The difference between the set and reset points of each switch is the deadband listed below; the minimum difference between the set points of the two switches is the separation.

UL Listed

FM Approved

Standard connection is 1/4 NPT

Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of the transducer. They are diaphragm/piston type transducers using an elastomer in contact with the fluid, backed by a piston cylinder. UL requires a double chamber transducer for fuel gas service and single chamber 316 SS transducer for fuel oil service.

FM General Purpose

Two-Stage Fixed Deadband


Separation Fixed Deadband At Mid-Range (psig) 1 Maximum Full Scale Minimum At Mid-Range (psig) 1 General Purpose Catalog No. Watertight Enclosure Catalog No. ExplosionProof Catalog No. Aluminum & Buna N Catalog No.

Transducer Units

Brass & Buna N Catalog No.

All 316 SS Catalog No. Fuel Oil

316 SS & Viton 4 Catalog No.

Fuel Gas

1.7 W.C. 2.0 W.C. 4.0 W.C. 7.0 W.C. 13.0 W.C. 1.5 1.0 2.0 2.0 3.5 3.0 5.0 1.4 W.C. 1.7 W.C. 2.0 W.C. 4.0 W.C. 7.0 W.C. 13.0 W.C. 0.5 0.5 0.5 1.2 2.1 3.5
3

2.7 W.C. 6.5 W.C. 14.0 W.C. 25.0 W.C. 40.0 W.C. 1.6 1.8 3.0 3.6 6.0 6.0 10.0 2.4 W.C. 2.7 W.C. 6.5 W.C. 14.0 W.C. 25.0 W.C. 40.0 W.C. 0.7 0.9 1.8 3.6 6.0 10.0

SC30D SC20D SC20D SC10D SC10D SC40D SC30D SC30D SC20D SC10D SC20D SC10D SC40DV SC30DV SC20DV SC20DV SC10DV SC10DV SC40DV SC30DV SC20DV SC20DV SC10DV SC10DV

SC31D SC21D SC21D SC11D SC11D SC41D SC31D SC31D SC21D SC11D SC21D SC11D SC41DV SC31DV SC21DV SC21DV SC11DV SC11DV SC41DV SC31DV SC21DV SC21DV SC11DV SC11DV
4

SC32D SC22D SC22D SC12D SC12D SC42D SC32D SC32D SC22D SC12D SC22D SC12D -------------------------

TA31A11 TA21A11 TB21A11 TB11A11 TC11A11 --------------TA40A11F TA30A11F TA20A11F TB20A11 TB10A11 TC10A11 TD40A11 TD30A11 TD20A11 TE20A11 TE10A11 TF10A11

--------------TF32A21 ----TF22A21 TF12A21 ------------TD40A21 TD30A21 TD20A21 TE20A21 TE10A21 TF10A21

----------TE40A44 TE30A44 --TE20A44 TE10A44 --TF10A44 -------------------------

------------------------TA40A32F TA30A32F TA20A32F TB20A32 TB10A32 TC10A32 TD40A42 TD30A42 TD20A42 TE20A42 TE10A42 TF10A42 23

Fuel Gas and Fuel Oil

316 SS transducers increase deadband by 50%.

Transducers ending in 32 have 303 SS process connections, not 316 SS.