VFD Panel Wiring and Control Details
VFD Panel Wiring and Control Details
1 3
QAC1
1 3 5 4A DP
12 14 2 4
MCB U1 V1 W1
N LC1
Q0 11 250KW INPUT
630A -TR1 1 2 5 PE CHOKE
/3.1
I> I> I>
TP,MCCB 500VA
ATAM 415V/120VAC U2 V2 W2
2 4 6
Aux.
TAPPING +/- 5%
Control
Transformer 3 4
1 3
QAC2
6A DP 2 4
MCB -PE
CU IF
1 0
10A 2 4 STO_A SAFE_TORQUE
DP MCB 3.0 / X120VN:1 STO_B OFF: STO is locked
3
NETWORK REMOVE THE
-X120V SIEMENS IT-NET SCREW FOR
1 2 FUNCTIONAL
11 GROUNDING
R1
BRAKE RESISTOR
BRAKE RESISTOR
/2.6 7 3
BRAKE RELAY
VFD RUN
DC LINK
DC LINK
SHIELD
N.C.
XLOAD U2 V2 W2 PE(2) SH(1) XDC DCN DCP XBR F3 R2 R1 XBREL .
COOLING COOLING
FAN-1 8" FAN-2 8"
CF1 L1 L2 CF2 L1 L2 PE
L1 L2 L1 L2
M M
415VAC 415VAC
1~ 1~
PE PE R Y B
PE
PE PE
U1 V1 W1
M
R Y B N M1
250kW,415V,3Φ 3~
Das er Salaam,Tanzania | +255 (0)22 2128969,2128973 | A REVISED COMMENTS 29.04.24 VJMANI JK Drn. VJ MANI Proj. Ref. : P-4329 + VFD PANEL
SPEED INCREASE
SPEED DECREASE
DISPLAY & KEYPAD
START/STOP
4-20mA SPEED
REFERENCE
3
1 2 13 13
13
XAO1 1 2 SS1 PB3 PB4
/3.1 -K1
/3.9 C1 C2 /3.1 14 14
14
/3
IE
1
D1 x X21 . X132 1 2 X132 3 4 X130 10 11 32 31 34 X133 5 6 7 8 16 17 9 28 69 X22 XPM
/1.5
BOP-2/IOP IF
+10V OUT
GND
AI 0+
AI 0-
AI 1+
AI 1-
GND IN
+24V IN
DI COM 2
DI 0
DI 1
DI 2
DI 3
DI 4
DI 5
+24V OUT
GND
DI COM 1
USB TO PC
AI 1
AI 0
I/U
I/U
I
..
U
ANALOG_INPUT_1
U
ANALOG_INPUT_0 SIEMENS
F-DI 0
MMC-CARD
U
XMMC .
RS485/ USS/ MODBUS
ADDRESS:
T1 MOTOR
T2 MOTOR
OFF ON
DO 0 COM
DO 2 COM
DO 0 NO
DO 2 NO
DO 0 NC
DO 2 NC
R
DO 1+
AO 0+
AO 1+
DO 1-
GND
GND
X128 X132 14 15 X132 12 13 X130 26 27 X132 21 22 X134 18 19 20 X134 23 24 25
IE IE 14 14
R1 R2
24VDC 24VDC
13 13
-XAI1 1 2 3 4
VFD VFD
SPEED FEEDBACK CURRENT FEEDBACK RUN FAULT
5 9 /3.7 5 9 /3.8
1 1
5 9 /3 5 9 /3
1 1
6 10 /3.3 6 10 /3.4
2 2
7 11 /1.1 7 11 /3.1
3 3
Das er Salaam,Tanzania | +255 (0)22 2128969,2128973 | A REVISED COMMENTS 29.04.24 VJMANI JK Drn. VJ MANI Proj. Ref. : P-4329 + VFD PANEL
TB DETAILS :
FUTURE INTERLOCK
X120VL:1 / 1.4 PLC START/STOP
XF1
1
FUTURE
INTERLOCK
2
X1 XF1
1 2 1 2
11
Q0
/1.0 14 12
MCCB
Aux.
11
R2
/2.6 4-20mA
7 3
VFD TRIP SPEED CURRENT SPEED
FEEDBACK FEEDBACK REFERENCE
1
1 2
SS1
/3.9 3POLE
/3 2 WAY SS A1 A2
/2.4 MANUAL AUTO
11 X1 1
XAI1 XAO1
PB1 +PLC
1 2 3 4 1 2
STOP PUSH 12 10 10
BUTTON
START/ R1 R2
STOP
/2.6 6 2 /2.6 6 2
COMMEND
13 43
PB2 K1 TRIP AUTO
/3.1 ON/OFF
START PUSH 14 44
X1 2 TO CUSTOMER FEEDBACK FEEDBACK
BUTTON FEEDBACK
A1 x1 x1
K1 H2 H3
120VAC
120VAC 120VAC
A2 x2 x2
GREEN AMBER
/2.6 9 /2.6 9
2
Das er Salaam,Tanzania | +255 (0)22 2128969,2128973 | A REVISED COMMENTS 29.04.24 VJMANI JK TB DETAILS Drn. VJ MANI Proj. Ref. : P-4329 + VFD PANEL