BLUE BRUTE

MEETS AWWA C900

Building essentials for a better tomorrow

BLUE BRUTE

PVC C.I.O.D. Distribution Pipe DR 25 / DR18 / DR14 Pressure Class 165, 235 and 305 psi Ring-Tite Joints 4"-12"

BLUE BRUTE
CONTENTS

01 02 03 04 05 06 07 08

PRODUCT DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . 2 SURGE DESIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 SHORT FORM SPECIFICATION . . . . . . . . . . . . . . . . . . . . 6 DIMENSIONS AND WEIGHTS . . . . . . . . . . . . . . . . . . . . . 8 FLOW/FRICTION CHARTS . . . . . . . . . . . . . . . . . . . . . . . 9 DEFLECTION CHART . . . . . . . . . . . . . . . . . . . . . . . . . . 14 SHORT FORM INSTALLATION GUIDE/WARNING . . . . . 15 WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

01
PRODUCT DESCRIPTION
AWWA C900 BLUE BRUTE
FOR USE IN DISTRIBUTION, MUNICIPAL WATER SYSTEMS AND OTHER SERVICES DESCRIPTION
JM Eagles Blue Brute pipe, produced in blue or white, conforms to the AWWA C900 specification, with gaskets meeting ASTM F477 and joints in compliance with ASTM D3139. Blue Brute water pipe has the longterm hydrostatic strength to meet the high safety requirements commonly needed by municipal water systems. This pipe conforms to AWWA C900-07 Pressure Class 165 psi (DR 25), 235 psi (DR 18), 305 psi (DR 14); for sizes 4"-12" in diameter. Note: Please contact JM Eagle Sales Department for availability and locations.

APPLICATIONS
These products are typically used for distribution pipelines of potable water. However, this pipe may be used for gravity sewer, force main, and water reclamation projects.

LONG LAYING LENGTHS


The standard laying length of Blue Brute PVC pipe is 20 feet. This means that more ground can be covered during installation while eliminating the cost of unnecessary joints.

PURPLE RECLAIM AND GREEN SEWER FORCE MAIN


JM Eagle also manufactures this pipe in purple, specifically for reclaimed water systems and green for sewer force main applications. This pipe is made to the same requirements as our standard products. The only difference is that the pigment used is purple or green. These products will not be marked with UL or NSF listing marks. Additionally, the purple pipe will be marked: Reclaimed Water... Do Not Drink and the green pipe will be marked Forced Sewer. * For lengths of 14 feet, Non-Hydrotested DR 18 Sewer Pipe is available upon request.

LISTING STANDARDS ANSI/NSF STANDARD 61, UL 1285, FM APPROVAL


See Short Form Specification.

QUALITY CONTROL
Without exception, each length of pipe is hydrostatically tested and subject to inspection by our quality control inspectors throughout every step of the manufacturing process. JM Eagles Quality Management System is ISO 9001:2000 registered.* Copies of the registration certificates are available on our website at www.jmeagle.com. * JM Eagle is in the process of obtaining the ISO 90012000 registration of Quality Management System for all locations.

BLUE BRUTE

LIGHT WEIGHT
A 20 foot length of 8" DR 18 Blue Brute water pipe weighs approximately 184 pounds. Installers prefer it because it goes into the ground quicklythus saving on installation costs.

SERVICE LIFE
Because it is nonmetallic, the pipe does not lose strength due to either potable water corrosion or external galvanic soil conditions.

INSTALLATION
This product should be installed in accordance with JM Eagle Publication JME-03B, Blue Brute, Big Blue and Ultra Blue (C900/C905/C909) Installation Guide and Pressure Pipe Tapping Guide.

CORROSION RESISTANCE
Blue Brute PVC pipe is unaffected by electrolytic or galvanic corrosion, or any known corrosive soil or water conditions. You dont have to worry about tuberculation, or the need for costly lining, wrapping, coating, or cathodic protection.

FLOW CAPACITY
This PVC water pipe has a smooth interior that stays smooth over long years of service with virtually no loss in carrying capacity. Its coefficient of flow is C = 150 (Hazen & Williams) the best available in common use water systems. This capacity often allows savings in pumping costs as well as savings on the size of pipe required.

SAVE IN HANDLING COSTS


Blue Brute PVC pipe is designed for installed-cost savings. Most sizes can be handled manually, so there is no need for costly installation equipment. Use the backhoe for excavating and backfilling only. Dig more trench, lay pipe faster, and save more in cost per foot installed.

FIELD CUTTING AND BEVELING


Blue Brute pipe can be field cut with a power saw or ordinary handsaw. This eliminates the need to invest in costly cutting equipment. The pipe can also be beveled without the use of any expensive or complicated machinery.

BLUE BRUTE

PRODUCT DESCRIPTION
AWWA C900 BLUE BRUTE
(CONTINUED) CAST IRON O.D.
Available in 4", 6", 8", 10", and 12" trade sizes, this pipe can be connected directly into cast/ductile iron fittings and pipe. Connections to products with other O.D. regimens can be done using commonly available adapters or transition gaskets. Dimensions should be checked for use with butterfly valves.

RING-TITE JOINT
Spigot pipe ends are supplied from the factory with bevels.

Rieber sealing ring provides tight, flexible seal.

RING-TITE JOINTS WITH LOCKED-IN GASKETS


JM Eagles Ring-Tite joint can be assembled quickly. Seated in a deep groove, the flexible elastomeric Rieber * gasket provides a tight seal that protects the line from shock, vibration, earth movement and compensates for expansion and contraction of pipe lengths. Theres no field mixing or application of cement. Its a simple push-together joint that remains tight under normal operating conditions. The factory installed Rieber gaskets provide a tight, flexible seal that resists rolling during installation. Special gasket types are available for use with certain chemical and petroleum products. Spigot pipe ends are supplied from the factory with bevels. The bell is an integral part of the pipe length with the same strength. Joints meet or exceed ASTM D3139 for joint tightness, including a 22 in. Hg vacuum for one hour, under deflection with no leakage.
Note: Other types of gaskets may be provided. JM Eagle is in the process of converting all gasketed products to the Rieber ring gasket. * Rieber is a registered trademark of TI Specialty Polymer Products Inc.

The bell is an integral part of the pipe length with the same strength.

ACCESSORIES
JM Eagles Blue Brute PVC pipe is compatible with all the items required for smooth installation of distribution pipelines.

BLUE BRUTE

02
SURGE DESIGN
It is important to note that for the same conditions of interrupted flow, the surge pressures generated in pipe with high tensile moduli will be greater than the surges in low moduli (PVC) pipe of similar dimensions. As the modulus of tensile elasticity for a piping material increases, the resultant pressure surge, or water hammer, caused by a change in flow velocity also increases. For example, an instantaneous 2 fps (0.6 mps) flow velocity change in an 8" water main will create surge pressures as shown in Table 1 for different pipe materials. For all system designs, surge pressures should be examined with the pipe material in use.

TABLE 1

PRESSURE SURGES IN 8 IN. WATER MAIN


In Response to 2 fps (0.6 mps) Instantaneous Flow Velocity Change. PRESSURE SURGE psi 100.0 88.7 29.4 kPa 689 611 202

PIPE PRODUCT Class 50 DI Pipe Class 150 AC Pipe 165 psi (DR 25) PVC Pipe

Pressure surges in PVC pipe of different dimension ratios in response to a 1 fps (0.3 mps) instantaneous flow velocity change are shown in Table 2.

TABLE 2

DESIGN TABLE FOR PVC PIPE-PRESSURE SURGE VS. DIMENSION RATIO


In Response to 1 fps (0.3 mps) Instantaneous Flow Velocity Change. PRESSURE SURGE DIMENSION RATIO 14 18 25 psi 19.8 17.4 14.7 kPa 137 120 101

BLUE BRUTE

03
SHORT FORM SPECIFICATION
AWWA C900 BLUE BRUTE
SCOPE
This specification designates general requirements for 4" through 12" C.I.O.D.s pipe produced in blue or white unplasticized polyvinyl chloride (PVC) plastic pressure pipe with integral bell and spigot joints for the conveyance of water and other fluids. This pipe shall meet the requirements of AWWA Standard C900, Polyvinyl Chloride (PVC) Water Distribution Pipe. Pipe installation and usage shall be in compliance with JM Eagle Publication JME-03B, Blue Brute, Big Blue and Ultra Blue C900/C905/C909 Installation Guide and Uni-Bell Publication UNI-PUB-08-07, Tapping Guide for PVC Pressure Pipe.

QUICK BURST TEST


Randomly selected samples tested in accordance with AWWA C900 and UL 1285 shall withstand, without failure, the pressures listed below when applied for 60-70 seconds. PRESSURE CLASS (psi) DR AWWA C900-97/FM 1612 100 150 200 AWWA C900-07 165 235 305 MINIMUM BURST PRESSURE AT 73F (psi) 535 755 985

MATERIALS
All pipe shall be made from quality PVC resin, compounded to provide physical and mechanical properties that equal or exceed cell class 12454 as defined in ASTM D1784.

HYDROSTATIC PROOF TESTING


Each standard length of pipe is tested up to 400 psi for Pressure Class 165; 600 psi for Pressure Class 235; 800 psi for Pressure Class 305 for a minimum of 5 seconds. The integral bell shall be tested with the pipe.

25 18 14

STANDARD LAYING LENGTHS


Standard laying lengths are 20 feet for all sizes. Other lengths of 14 feet, Non-Hydrotested pipe is available upon request.

DROP IMPACT TEST


Pipe shall withstand, without failure using Tup B and Flat Rate Holder B, at 73F, a tup impact energy of 100 ft-lbf for all Pressure Class of 4"-12" trade sizes. There shall be no visible evidence of shattering or splitting when the energy is imposed.

PIPE
Where specified as such, all pipe shall be suitable for use as pressure conduit. Provisions must be made for expansion and contraction at each joint with an elastomeric gasket. The bell shall consist of an integral wall section with a factory installed, solid cross section Rieber or other elastomeric gasket, which meets the requirements of ASTM F477. The bell section shall be designed to be at least as hydrostatically strong as the pipe barrel and meet the requirements of AWWA C900. The joint design shall meet the requirements of ASTM D3139 under both pressure and 22 in. Hg vacuum. Sizes and dimensions shall be as shown in this specification.

BLUE BRUTE

TESTING REQUIREMENTS PER AWWA C900


TEST LONG TERM PRESSURE TEST 1000 hours (psi) EXTRUSION QUALITY OF PVC PIPE BY ACETONE IMMERSION TEST METHOD ASTM D2152 FLATTENING TEST Tests extrusion quality and ductility under slow loading conditions. (Flattening Capability) HYDROSTATIC PROOF TEST (each piece) (psi) PRESSURE CLASS C900-07 165 psi 350 20 min 40% of OD between the plates within 2 - 5 min 330 235 psi 500 20 min 40% of OD between the plates within 2 - 5 min 470 305 psi 650 20 min 40% of OD between the plates within 2 - 5 min 610

TYPICAL PHYSICAL AND CHEMICAL PROPERTIES


PROPERTY Fiber Hoop Stress at 73 F Minimum Short Term Bursting Strength (psi) 1,000 Hour Strength (psi) min Working Pressure Rating 73 F (% of rating at 73 F) 80 F (% of rating at 73 F) 100 F (% of rating at 73 F) Chemical Resistance at 73 F Acids Salts - Bases Physical Properties of Compound Std. Test Specimens Minimum Tensile Strength (psi) at 73 F Thermal Expansion (in / 100 ft / 50 F Change) Fire Resistance Flame Spread Smoke Development Coefficient of Flow Hazen & Williams Mannings N Value AWWA C900 BLUE BRUTE PVC PIPE 6400 4200 100% 88% 62% Excellent Excellent 7000 2" Self Extinguishing 10 330 C = 150 N = 0.009 E162 E84 D638 ASTM TEST METHOD D1599 D1598

* For data, sizes, or classes not re ected in these charts, please contact JM Eagle for assistance.

BLUE BRUTE

04
DIMENSIONS AND WEIGHTS
SUBMITTAL AND DATA SHEET
PIPE SIZE (IN) AVERAGE O.D. (IN) NOM. I.D. (IN) MIN. T. (IN) MIN. E (IN) APPROX. D9 (IN) APPROX. WEIGHT (LBS/FT) PRESSURE CLASS 165 psi (DR 25) 4 6 8 10 12 4 6 8 10 12 4 6 8 10 12 4.80 6.90 9.05 11.10 13.20 4.80 6.90 9.05 11.10 13.20 4.80 6.90 9.05 11.10 13.20 4.39 6.31 8.28 10.16 12.08 4.23 6.09 7.98 9.79 11.65 4.07 5.86 7.68 9.42 11.20 0.192 0.276 0.362 0.444 0.528 0.267 0.383 0.503 0.617 0.733 0.343 0.493 0.646 0.793 0.943 5.25 6.40 7.05 8.20 8.80 5.25 6.40 7.05 8.20 8.80 5.25 6.40 7.05 8.20 8.80 5.57 8.00 10.50 12.88 15.31 5.87 8.43 11.06 13.57 16.13 6.17 8.87 11.63 14.27 16.97 1.9 3.9 6.7 10.1 14.4 2.6 5.3 9.2 13.9 19.7 3.2 6.7 11.6 17.6 25.1 PRESSURE CLASS 235 psi (DR 18)*

PRESSURE CLASS 305 psi (DR 14)*

Consult JM Eagle for CSA and other listing availability prior to shipment. Note: *FM Approvals Pressure Class 150 psi for DR 18 and 200 psi for DR 14. * Contact your JM Eagle sales representative for location availability.

I.D. : Inside Dameter O.D. : Outside Diameter T. : Wall Thickness

D : Bell Outside Diameter E : Distance between Assembly Mark to the end of spigot.

BLUE BRUTE

05
FLOW/FRICTION CHARTS
FLOW/FRICTION LOSS, BLUE BRUTE PVC PIPE
4" C.I.O.D. (AWWA C900) ACTUAL O.D. 4.80 INCH DR 25 (165 psi) VELOCITY FT/S 0.424 0.530 0.636 0.742 0.847 0.953 1.059 1.271 1.483 1.589 1.695 1.907 2.119 2.648 3.178 3.708 4.237 5.297 6.356 7.415 8.475 9.534 10.593 12.712 14.831 DR 18 (235 psi) PRESSURE DROP psi/100 FT 0.010 0.015 0.021 0.028 0.035 0.044 0.053 0.075 0.099 0.113 0.127 0.158 0.192 0.291 0.408 0.542 0.694 1.050 1.471 1.957 2.506 3.117 3.789 5.311 7.066 DR 14 (305 psi) VELOCITY FT/S 0.493 0.616 0.739 0.863 0.986 1.109 1.232 1.479 1.725 1.849 1.972 2.218 2.465 3.081 3.697 4.313 4.930 6.162 7.394 8.627 9.859 11.092 12.324 14.789 17.254 PRESSURE DROP psi/100 FT 0.012 0.018 0.025 0.033 0.043 0.053 0.064 0.090 0.120 0.136 0.154 0.191 0.232 0.351 0.492 0.655 0.839 1.268 1.777 2.364 3.027 3.765 4.576 6.415 8.534 FLOW (GAL/MIN) 20 25 30 35 40 45 50 60 70 75 80 90 100 125 150 175 200 250 300 350 400 450 500 600 700 PRESSURE DROP VELOCITY psi/100 FT FT/S 0.008 0.012 0.017 0.023 0.029 0.037 0.045 0.062 0.083 0.094 0.106 0.132 0.161 0.243 0.341 0.453 0.580 0.877 1.230 1.636 2.095 2.606 3.167 4.439 5.906 0.456 0.570 0.684 0.798 0.912 1.026 1.140 1.368 1.597 1.711 1.825 2.053 2.281 2.851 3.421 3.991 4.562 5.702 6.842 7.983 9.123 10.264 11.404 13.685 15.965

Based on calculation methods and design tables set forth by the Uni-Bell PVC Pipe Association, Handbook of PVC Pipe Design and Construction.

BLUE BRUTE

FLOW/FRICTION CHARTS
(CONTINUED) FLOW/FRICTION LOSS, BLUE BRUTE PVC PIPE
6" C.I.O.D. (AWWA C900) ACTUAL O.D. 6.90 INCH

DR 25 (165 psi) FLOW (GAL/MIN) VELOCITY PRESSURE DROP FT/S psi/100 FT 50 60 70 75 80 90 100 125 150 175 200 250 300 350 400 450 500 600 700 800 1000 0.513 0.615 0.718 0.769 0.820 0.923 1.025 1.282 1.538 1.794 2.051 2.563 3.076 3.589 4.101 4.614 5.126 6.152 7.177 8.202 10.253 0.008 0.011 0.014 0.016 0.018 0.023 0.027 0.042 0.058 0.078 0.099 0.150 0.210 0.280 0.358 0.446 0.542 0.759 1.010 1.294 1.956

DR 18 (235psi) VELOCITY FT/S 0.552 0.662 0.772 0.827 0.882 0.993 1.103 1.379 1.655 1.930 2.206 2.758 3.309 3.861 4.412 4.964 5.516 6.619 7.722 8.825 11.031 PRESSURE DROP psi/100 FT 0.009 0.013 0.017 0.019 0.022 0.027 0.033 0.050 0.070 0.093 0.119 0.179 0.251 0.334 0.428 0.533 0.647 0.907 1.207 1.546 2.337

DR 14 (305 psi) VELOCITY FT/S 0.596 0.716 0.835 0.895 0.954 1.073 1.193 1.491 1.789 2.087 2.385 2.982 3.578 4.175 4.771 5.367 5.964 7.156 8.349 9.542 11.927 PRESSURE DROP psi/100 FT 0.011 0.015 0.021 0.023 0.026 0.033 0.040 0.060 0.084 0.112 0.143 0.217 0.304 0.404 0.518 0.644 0.783 1.097 1.460 1.869 2.826

Based on calculation methods and design tables set forth by the Uni-Bell PVC Pipe Association, Handbook of PVC Pipe Design and Construction.

10

BLUE BRUTE

FLOW/FRICTION LOSS, BLUE BRUTE PVC PIPE


8" C.I.O.D. (AWWA C900) ACTUAL O.D. 9.05 INCH

FLOW (GAL/MIN) 100 125 150 200 250 300 350 400 450 500 600 700 800 1000 1200 1400 1600 2000

DR 25 (165 psi) VELOCITY FT/S 0.596 0.745 0.894 1.192 1.490 1.788 2.086 2.384 2.682 2.980 3.576 4.172 4.768 5.960 7.152 8.344 9.536 11.920 PRESSURE DROP psi/100 FT 0.007 0.011 0.016 0.027 0.040 0.056 0.075 0.096 0.119 0.145 0.203 0.270 0.346 0.523 0.732 0.975 1.248 1.887

DR 18 (235 psi) VELOCITY FT/S 0.641 0.802 0.962 1.283 1.604 1.924 2.245 2.566 2.887 3.207 3.849 4.490 5.132 6.415 7.698 8.981 10.264 12.829 PRESSURE DROP psi/100 FT 0.009 0.013 0.019 0.032 0.048 0.067 0.089 0.115 0.142 0.173 0.243 0.323 0.413 0.625 0.876 1.165 1.492 2.256

DR 14 (305 psi) VELOCITY PRESSURE DROP FT/S psi/100 FT 0.693 0.866 1.040 1.386 1.733 2.079 2.426 2.772 3.119 3.466 4.159 4.852 5.545 6.931 8.317 9.704 11.090 13.862 0.011 0.016 0.022 0.038 0.058 0.081 0.108 0.138 0.172 0.209 0.293 0.390 0.499 0.754 1.057 1.407 1.802 2.724

Based on calculation methods and design tables set forth by the Uni-Bell PVC Pipe Association, Handbook of PVC Pipe Design and Construction.

BLUE BRUTE 11

FLOW/FRICTION CHARTS
(CONTINUED) FLOW/FRICTION LOSS, BLUE BRUTE PVC PIPE
10" C.I.O.D. (AWWA C900) ACTUAL O.D. 11.10 INCH

DR 25 (165 psi) FLOW (GAL/MIN) VELOCITY PRESSURE DROP FT/S psi/100 FT 175 200 250 300 350 400 450 500 600 700 800 1000 1200 1400 1600 2000 2500 3000 0.693 0.792 0.990 1.189 1.387 1.585 1.783 1.981 2.377 2.773 3.169 3.962 4.754 5.547 6.339 7.924 9.905 11.886 0.008 0.010 0.015 0.021 0.028 0.035 0.044 0.054 0.075 0.100 0.128 0.194 0.271 0.361 0.462 0.699 1.056 1.480

DR 18 (235 psi) VELOCITY FT/S 0.746 0.853 1.066 1.279 1.492 1.706 1.919 2.132 2.559 2.985 3.411 4.264 5.117 5.970 6.823 8.528 10.661 12.793 PRESSURE DROP psi/100 FT 0.009 0.012 0.018 0.025 0.033 0.042 0.053 0.064 0.090 0.120 0.153 0.231 0.324 0.432 0.553 0.835 1.263 1.770

DR 14 (305 psi) VELOCITY FT/S 0.807 0.922 1.152 1.383 1.613 1.843 2.074 2.304 2.765 3.226 3.687 4.609 5.530 6.452 7.374 9.217 11.522 13.826 PRESSURE DROP psi/100 FT 0.011 0.014 0.021 0.030 0.040 0.051 0.064 0.077 0.109 0.144 0.185 0.280 0.392 0.521 0.668 1.009 1.526 2.139

Based on calculation methods and design tables set forth by the Uni-Bell PVC Pipe Association, Handbook of PVC Pipe Design and Construction.

12

BLUE BRUTE

FLOW/FRICTION LOSS, BLUE BRUTE PVC PIPE


12" C.I.O.D. (AWWA C900) ACTUAL O.D. 13.20 INCH

FLOW (GAL/MIN) 300 350 400 450 500 600 700 800 1000 1200 1400 1600 2000 2500 3000 3500 4000 4500

DR 25 (165 psi) VELOCITY FT/S 0.840 0.981 1.121 1.261 1.401 1.681 1.961 2.241 2.802 3.362 3.922 4.482 5.603 7.004 8.405 9.805 11.206 12.607

DR 18 (235 psi)

DR 14 (305 psi) VELOCITY FT/S 0.978 1.141 1.304 1.467 1.629 1.955 2.281 2.607 3.259 3.911 4.563 5.214 6.518 8.147 9.777 11.406 13.036 14.665 PRESSURE DROP psi/100 FT 0.013 0.017 0.022 0.027 0.033 0.047 0.062 0.080 0.120 0.169 0.224 0.287 0.434 0.657 0.920 1.225 1.568 1.950

PRESSURE DROP VELOCITY PRESSURE DROP psi/100 FT FT/S psi/100 FT 0.009 0.012 0.015 0.019 0.023 0.032 0.043 0.055 0.083 0.117 0.155 0.199 0.301 0.455 0.637 0.848 1.085 1.350 0.904 1.055 1.206 1.357 1.507 1.809 2.110 2.412 3.015 3.617 4.220 4.823 6.029 7.536 9.044 10.551 12.058 13.565 0.011 0.014 0.018 0.023 0.028 0.039 0.051 0.066 0.100 0.140 0.186 0.238 0.359 0.543 0.761 1.013 1.297 1.613

Based on calculation methods and design tables set forth by the Uni-Bell PVC Pipe Association, Handbook of PVC Pipe Design and Construction.

BLUE BRUTE 13

06
DEFLECTION CHART
Blue Brute Deection By Depth of Burial : :

BLUE BRUTE DEFLECTION BY DEPTH OF BURIAL


6 5

% Deflection

4 3 2 1 0 5 10 15 20 25 30 35 40 45 50

DR25 DR18 DR14

Depth of Burial (ft)

: : Deections computed using a unit weight of backll at 120 lbs/cft and assume no internal pressure or live load. : : Pipe embedment used in calculations is Class 1, 2, 3, or 4, as dened in ASTM D2321 with appropriate compaction to achieve an E'=1000 psi. Based on calculation methods and design tables set forth by the Uni-Bell PVC Pipe Association, Handbook of PVC Pipe Design and Construction.

14

BLUE BRUTE

07
SHORT FORM INSTALLATION GUIDE/ WARNING
This information is furnished in order to provide a brief review of the installation requirements for JM Eagle Blue Brute PVC pipe. It is not intended to serve as or replace the function of the FULL VERSION product installation guide available upon request. 1. Check to see that the gasket is properly seated in the bell groove, and that the bell and spigot are clean before assembly. 2. Apply the approved lubricant supplied with the pipe to the spigot end of the pipe, paying particular attention to the bevel. The coating should be equivalent to a brush coat of enamel paint. 3. Assemble the joint only to and not over the stop mark provided on the spigot end. 4. If undue resistance to insertion of the spigot is encountered, or the assembly mark does not reach the flush position, disassemble the joint and check the position of the rubber gasket, and remove any debris. 5. Curvature of the pipe shall be accomplished through longitudinal bending of the pipe barrel in accordance with the following table. Deflection of the joint is not allowed and may cause leakage. PIPE SIZE (IN) 4 6 8 10 12 RADIUS (FT) 100 150 200 250 300

6. Prior to backfilling, check to see that the assembly mark is flush with the end of the bell. 7. All taps performed on JM Eagles pressure products, shall be in accordance with Uni-Bell Publication UNI-PUB-08-07, Tapping Guide for PVC Pressure Pipe.

WARNING : RUPTURE HAZARD


IMPROPER INSTALLATION OR MISUSE OF TAPPING TOOLS MAY CAUSE PIPES UNDER HIGH PRESSURE TO RUPTURE AND RESULT IN HIGH VELOCITY AIRBORNE FRAGMENTATION LEADING TO SERIOUS INJURIES AND/OR DEATH. BEFORE AND DURING INSTALLATION, ALWAYS: Consult and follow the FULL VERSION of the product installation guide Closely follow job speci cations Use protective gear and equipment BEFORE AND DURING TAPPING, ALWAYS: Consult and follow Uni-Bell Publication UNI-PUB-08-07, Tapping Guide for PVC Pressure Pipe. Use the correct tapping tools Bleed air from pipes at high spot before tapping Use protective gear and equipment Please contact JM Eagle Product Assurance at (800) 621-4404 to obtain FULL VERSION of the appropriate installation guide or for further assistance.

BLUE BRUTE 15

08
WARRANTY
JM EAGLE PRODUCTS LIMITED WARRANTY J-M Manufacturing Co., Inc. (JM Eagle ) warrants that its standard polyvinyl chloride (PVC), polyethylene (PE), conduit/ plumbing/solvent weld and Acrylonitrile-Butadiene-Styrene (ABS) pipe Products (Products) are manufactured in accordance with applicable industry specifications referenced on the Product and are free from defects in workmanship and materials. Every claim under this warranty shall be void unless in writing and received by JM Eagle within thirty (30) days of the date the defect was discovered, and within one (1) year of the date of shipment from the JM Eagle plant. Claims for Product appearance defects, such as sun-bleached pipe etc., however, must be made within thirty (30) days of the date of the shipment from the JM Eagle plant. This warranty specifically excludes any Products allowed to become sun-bleached after shipment from the JM Eagle plant. Proof of purchase with the date thereof must be presented to the satisfaction of JM Eagle, with any claim made pursuant to this warranty. JM Eagle must first be given an opportunity to inspect the alleged defective Products in order to determine if it meets applicable industry standards, if the handling and installation have been satisfactorily performed in accordance with JM Eagle recommended practices and if operating conditions are within standards. Written permission and/or a Return Goods Authorization (RGA) must be obtained along with instructions for return shipment to JM Eagle of any Products claimed to be defective. The limited and exclusive remedy for breach of this Limited Warranty shall be, at JM Eagles sole discretion, the replacement of the same type, size and like quantity of non-defective Product, or credits, offsets, or combination of thereof, for the wholesale purchase price of the defective unit. This Limited Warranty does not apply for any Product failures caused by users flawed designs or specifications, unsatisfactory applications, improper installations, use in conjunction with incompatible materials, contact with aggressive chemical agents, freezing or overheating of liquids in the product and any other misuse causes not listed here. This Limited Warranty also excludes failure or damage caused by fire stopping materials, thread sealants, plasticized vinyl Products or damage caused by the fault or negligence of anyone other than JM Eagle, or any other act or event beyond the control of JM Eagle. JM Eagles liability shall not, at any time, exceed the actual wholesale purchase price of the Product. The warranties in this document are the only warranties applicable to the Product and there are no other warranties, expressed or implied. This Limited Warranty specifically excludes any liability for general damages, consequential or incidental damages, including without limitation, costs incurred from removal, reinstallation, or other expenses resulting from any defect. IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE SPECIFICALLY DISCLAIMED AND JM EAGLE SHALL NOT BE LIABLE IN THIS RESPECT NOTWITHSTANDING JM EAGLES ACTUAL KNOWLEDGE THE PRODUCTS INTENDED USE. JM Eagles Products should be used in accordance with standards set forth by local plumbing and building laws, codes, or regulations and the applicable standards. Failure to adhere to these standards shall void this Limited Warranty. Products sold by JM Eagle that are manufactured by others are warranted only to the extent and limits of the warranty of the manufacturer. No statement, conduct or description by JM Eagle or its representative, in addition to or beyond this Limited Warranty, shall constitute a warranty. This Limited Warranty may only be modified in writing signed by an officer of JM Eagle.

16

BLUE BRUTE

PLANT LOCATIONS
ADEL 2101 J-M Drive Adel, Georgia 31620 BATCHELOR 2894 Marion Monk Road Batchelor, Louisiana 70715 BUCKHANNON Old Drop 33, Mudlick Road Buckhannon, West Virginia 26201 BUTNER 2602 West Lyon Station Road Creedmoor, North Carolina 27522 CAMERON PARK 3500 Robin Lane Cameron Park, California 95682 COLUMBIA 6500 North Brown Station Road Columbia, Missouri 65202 CONROE 101 East Avenue M Conroe, Texas 77301 FONTANA 10990 Hemlock Avenue Fontana, California 92337 HASTINGS 146 North Maple Avenue Hastings, Nebraska 68901 KINGMAN 4620 Olympic Way Kingman, Arizona 86401 MAGNOLIA 2220 Duracrete Drive Magnolia, Arkansas 71753 MCNARY 31240 Roxbury Road Umatilla, Oregon 97882 MEADVILLE 15661 Delano Road Cochranton, Pennsylvania 16314 PERRIS 23711 Rider Street Perris, California 92570 PUEBLO 1742 E. Platteville Boulevard Pueblo West, Colorado 81007 STOCKTON 1051 Sperry Road Stockton, California 95206 SUNNYSIDE 1820 South First Street Sunnyside, Washington 98944 TACOMA 2330 Port of Tacoma Road Tacoma, Washington 98421 TULSA 4501 West 49th Street Tulsa, Oklahoma 74107 VISALIA 8875 Avenue 304 Visalia, California 93291 WHARTON 10807 US 59 RD Wharton, Texas 77488 WILTON 1314 W. Third Street Wilton, Iowa 52778 MEXICO PLASTICS TECHNOLOGY DE MXICO S DE R.L. DE S.A. Av. Montes Urales No. 8 y 10 Parque Industrial Opcin, Carretera 57 Qro. -S.L.P. Km. 57.8 C.P. 37980 San Jos Iturbide, Guanajuato Mxico
* Our Mexico location is a joint venture between JM Eagle and Plastics Technology

GLOBAL HEADQUARTERS 5200 West Century Boulevard Los Angeles, California 90045 REGIONAL OFFICE Nine Peach Tree Hill Road Livingston, New Jersey 07039

J-M Manufacturing Co., Inc. and PW Eagle, Inc. are doing business as JM Eagle.

JM Eagle

Tacoma Sunnyside McNary

THE LEADER IN PIPE INNOVATION THE HIGHEST LEVEL OF QUALITY THE LARGEST BREADTH OF PRODUCT THE WIDEST CAPACITY EXPRESS DELIVERY

Cameron Park Stockton Visalia Kingman Fontana Perris Pueblo

Hastings

Wilton

Meadville Buckhannon

Columbia Tulsa Magnolia Adel Conroe Wharton Batchelor

Butner

Mexico

PLANT LOCATIONS
GLOBAL HEADQUARTERS:
5200 West Century Blvd Los Angeles, CA 90045 T: 800.621.4404 F: 800.451.4170
Building essentials for a better tomorrow