Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Tank Vessel Overflow Line Sizing

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Overflow - !

Help

Tank/Vessel Overflow Line Sizing


NOTE:

The program has two parts: the first is for sizing the overflow, and second is for calculating the
capacity of an overflow.
Always begin a new case by retrieving the original file. Direct entry of data in cells that originally
contain table lookups could cause functions to be lost, or incorrect calculations. I format cells
requiring entry colored RED; calculated values are black.

1.) Enter identification at [C4].


2.) Enter total liquid inflow at [C7].
3.) Enter fluid at [G7], use [=], then go to fluid name in table (A44. D92) eg. [=A92] is WATER. The Specific
Gravity at G8 will be automatically looked up in the table, if the fluid is in table. If not, enter directly in [G8].
4.) Enter liquid head (inches) at [C9].
5.) Select the pipe schedule "10" or "40" with the drop-down at [F13].
6.) The required overflow inside diameter is shown at [F18].
7.) The recommended size overflow is given at row 22 and is based on the schedule previously selected.
The look-up tables follow schedule 40 pipe through 12 inch and standard (STD) weight above 12 inch.
This latter part of the program is set up to automatically calculate the capacity of the overflow prviously
chosen. By comparing capacities to the inflow, the area for future inflow increase can be determined.
To use this part separately:
8.)
9.)
10.)
11.)

Enter identification at [C27].


Enter specific gravity at [D29].
Enter liquid head (inches) at [D30].
Enter overflow ID at [D33], use pipe table if appropriate.
Calculated overflow capacity is indicated at [E38].
Print out using direct Excel commands. This application is provided by Chemical
Engineers Resource Website, visit
cheresources.com
@
for additional selections.
Print out using direct EXCEL commands.

<<<<<<<< Psafety January 2001, by Don Coffman >>>>>>>>


The

originator

of these spreadsheet(s) specifically excludes

all warranties,

expressed or implied, as to the a c c u r a c y of the data and other information set forth
and assumes N O liability for any losses or damage resulting from the u s e of the
materials or application of the data.
Consistent with G O O D E N G I N E E R I N G P R A C T I C E , the burden rests with the U S E R
of these spreadsheets to review A L L calculations, and assumptions. The U S E R I S
FULLY RESPONSIBLE for the results or decisions based on calculations.
This Spreadsheet Requires M A C R O S to be E N A B L E D to A S S U R E proper operation.
See the Workbook Help Sheet for Additional Instructions on Use.
dmcoffman@aol.com

overflow

Psafety January 2001

4/24/2004

Tank/Vessel Overflow Line Sizing


DEVICE : Tank #2501; Overflow Tag: 03000

Vessel

Vessel Inflow:
7000
gpm
W: 3500000 lb/hr
P:
4
inch
or 0.1443001 psig

Fluid

Liquid: WATER
Specific Gravity:
1.000
Density:
62.4
Frictional Loss, N:
1.5

Select Overflow Pipe Schedule :

7
W

dia := ( 2.79 10 ) N
( P D)

lb/cu. ft.
(simple overflow)

Schedule 10

0.25

= 27.469139 inch

-- A 30-inch overflow is recommended --

Selected Overflow Capacity


DEVICE : Tank #2501; Overflow Tag: 03000
sp.gr. =
P=
D=
N=
d=

W :=

overflow

1.000
4.000
1.000
1.5
29.376

inch = 0.1443001 psi


62.4 =
62.4
lb/cu.ft.
(for simple o'flow)
inch (overflow ID)

P D d4
= 4002794.2 lb/hr or 8,005.6 gpm
(
7)
N

2.79

10

Psafety January 2001

4/24/2004

Tank/Vessel Overflow Line Sizing


DEVICE : Tank #2501; Overflow Tag: 03000

Vessel

Vessel Inflow: 78.358024 m /hr


W: 21.766118 kg/sec
P: 0.1016 meter
or 996.35564 Pa

Fluid

Liquid: WATER
Specific Gravity:
1.000
Density:
1000
Frictional Loss, N:
1.5

Select Overflow Pipe Schedule :

kg/cu. meter
(simple overflow)

Schedule 40

0.25

3
W

dia := ( 808 10 ) N
( P D)

= 154.93964 mm

-- A 200 mm overflow is recommended --

Selected Overflow Capacity


DEVICE : Tank #2501; Overflow Tag: 03000
sp.gr. =
P=
D=
N=
d=

W :=

overflow

1.000
0.1016
1.000
1.5
202.74

P D d4
(
3
N 80810 )

meter = 0.9962896 kPa


1000 =
1000
kg/cu. meter
(for simple o'flow)
millimeter (overflow ID)

= 37.266652 kg/sec or 134.2 cu. meter/hr

Psafety January 2001

LIQUID
Overflow Selection Information
sp. gr.
ACETIC ACID 100%
1.050
Case Selection Test -- A 30-inch overflow is recommended -ACETIC ACID 70%
1.010 Schedule 10
Schedule 10 1
ACETONE
0.789 Schedule 40
AMINE OXIDE
Schedule 10 Lookup Table Schedule 40 Lookup Table
0.950
Piping
AMMONIA 26%
0.905
Size
schd 10S next nom next i.d. nominal schd 40 next nom
AMMONIA 100%
0.682
1/2
0.001
1/2
0.674
0.001
1/2
0.622
BENZENE 26%
0.844
1/2
0.674
3/4
0.884
0.622
3/4
0.824
BLACK LIQUOR 50%
1.250
3/4
0.884
1
1.097
0.824
1
1.049
BLACK LIQUOR 63%
1.330
1
1.097
1 1/4
1.422
1.049
1 1/4
1.38
BLACK LIQUOR 68%
1.360
1 1/4
1.422
1 1/2
1.682
1.380
1 1/2
1.61
BRINE, CALCIUM CHLORIDE 25% 1.230
1 1/2
1.682
2
2.157
1.610
2
2.067
BRINE, SODIUM CHLORIDE 25% 1.190
2
2.157
2 1/2
2.635
2.067
2 1/2
2.469
CARBON DIOXIDE
1.102
2 1/2
2.635
3
3.26
2.469
3
3.068
CAUSTIC 20%
1.223
3
3.260
3 1/2
3.76
3.068
3 1/2
3.548
CAUSTIC 50%
1.530
3 1/2
3.760
4
4.26
3.548
4
4.026
CHLORINE LIQUID
1.467
4
4.260
6
6.357
4.026
6
6.065
DOWTHERM A
0.995
6
6.357
8
8.329
6.065
8
7.981
ETHANOL 100%
0.789
8
8.329
10
10.42
7.981
10
10.02
ETHANOL 40%
0.935
10
10.420
12
12.39
10.020
12
11.938
ETHANOL 95%
0.804
12
12.390
14
13.624
11.938
14
13.25
ETHYL CHLORIDE
0.923
14
13.624
16
15.624
13.250
16
15.25
ETHYLENE GLYCOL
1.110
16
15.624
18
17.624
15.250
18
17.25
FREON, R11
1.410
18
17.624
20
19.564
17.250
20
19.25
FREON, R12
1.170
20
19.564
22
21.564
19.250
22
21.25
FREON, R22
1.440
22
21.564
24
23.5
21.250
24
23.25
FUEL OIL #2
0.876
24
23.500
26
25.376
23.250
26
25.25
FUEL OIL #6
0.993
26
25.376
28
27.376
25.250
28
27.25
GASOLINE
0.751
28
27.376
30
29.376
27.250
30
29.25
GLYCEROL, 100%
1.260
30
29.376
32
31.376
29.250
32
31.25
HYDROCHLORIC 31.5%
1.159
32
31.376
34
33.312
31.250
34
33.25
ISOPROPYL ALCOHOL
0.785
34
33.312
36
35.376
33.250
36
35.25
KEROSENE
36
36+
0.811
35.376
35.250
LUBE OIL MOBIL 634
0.884
METHANOL 100%
0.796
METHANOL 40%
0.937
METHANOL 90%
0.824
METHYL CHLORIDE
0.998
MULTITHERM PG-1
0.875
NITRIC ACID 60%
1.370
NITRIC ACID 95%
1.500
OIL, VEGETABLE HARDENED
0.920
OIL, VEGETABLE UNHARDENED 0.880
SULPHUR DIOXIDE
1.434
SULPHURIC 110%, FUMING
1.840
SULPHURIC ACID 60%
1.500
SULPHURIC ACID 98%
1.830
TOLUENE
0.862
TURPENTINE
0.864
WATER
1.000

overflow

Psafety January 2001

You might also like