Motor Protection Principles: Arijit Banerjee, Arvind Tiwari-GE Global Research Jakov Vico, Craig Wester - GE Multilin
Motor Protection Principles: Arijit Banerjee, Arvind Tiwari-GE Global Research Jakov Vico, Craig Wester - GE Multilin
Motor Protection Principles: Arijit Banerjee, Arvind Tiwari-GE Global Research Jakov Vico, Craig Wester - GE Multilin
Arijit Banerjee, Arvind Tiwari- GE Global Research Jakov Vico, Craig Wester- GE Multilin
Presented at 2008 Texas A&M Protective Relaying Conference College Station, TX April 1-3, 2008
Insulation lifetime decreases by half if motor operating temperature exceeds thermal limit by 10C for any period of time
110 100
For F class insulation, stator temperature of 165C causes motor lifetime to decrease to 50%
30 F-CLASS (155 C)
20 10 0 0 H-CLASS (180 C)
50
100
150
200
250
300
TEMPERATURE (C)
Rotor Conductors Deforming or Melting (for rotor limited - thermal limit is defined by motor stall time)
6
Motor Starting:
Previous state is Stopped & Current > 0 threshold. Motor current must increase to the level higher than overload pickup within seconds otherwise motor algorithm will declare the Running state.
Motor Running:
Previous state is Starting or Overloading & Current drops below overload pickup level.
Motor Overloading:
Previous state is Running & Current raises above overload pickup level. Thermal Capacity Used (TCU) begins to accumulate
C
B D
A. B. C. D.
F
Cold Running Overload Hot Running Overload Cold Locked Rotor Curve Hot Locked Rotor Curve
Set slightly above the motor service factor by 8-10% to account for measuring errors
If RTD Biasing of Thermal Model is used, thermal overload setting can be set higher Note: motor feeder cables are normally sized at 1.25 times motors full load current rating, which would limit the motor overload pickup setting to a maximum of 125%.
SF 1.0 1.15
11
TCU is defined as percentage of motor thermal limit utilized during motor operation.
A running motor will have some level of thermal capacity used due to Motor Losses. Thermal Trip when Thermal Capacity Used equals 100%
12
Overload Curve
Set the overload curve below cold thermal limit and above hot thermal limit If only hot curve is provided by mfgr, then must set below hot thermal limit
13
NEMA standard temperature rises for motors up to 1500HP and Service Factors 1 and 1.15 respectively.
AMBIENT
CLASS A
CLASS B
CLASS F
CLASS H
When motor is running below overload pickup, the TCU will rise or fall to value based on average current and HCR. HCR is used to calculate level of TCU by relay, at which motor will settle for current below overload pickup.
14
16
17
Starting current is proportional to system voltage during motor acceleration, thus voltage could be a good indication of the current level corresponding to the locked rotor conditions.
Voltage dependant dynamic thermal limit curve is employed to enhance the thermal model algorithm.
Motor relay will shift acceleration thermal limit curve linearly and constantly based on measured line voltage during a motor start.
18
Positive Sequence
Negative Sequence
19
Im - real motor current; K - unbalance bias factor; I1 & I2 - positive and negative sequence components of motor current. K factor reflects the degree of extra heating caused by the negative sequence component of the motor current. IEEE guidelines for typical and conservative estimates of K.
TYPICAL CONSERVATIVE
20
RTD bias model determines the Thermal Capacity Used based on the temperature of the Stator and is separate from the overload model for calculating Thermal Capacity Used.
Motor relay will use the calculated thermal capacity unless the RTD thermal capacity is higher. This function will not trip the motor at the max point temp unless the average current is greater than the overload pickup setting RTD biasing is a back up protection element which accounts for such things as loss of cooling or unusually high ambient temperature.
21
22
Overvoltage Protection
The overall result of an overvoltage condition is a decrease in load current and poor power factor.
Although old motors had robust design, new motors are designed close to saturation point for better utilization of core materials and increasing the V/Hz ratio cause saturation of air gap flux leading to motor heating. The overvoltage element should be set to 110% of the motors nameplate unless otherwise started in the data sheets.
23
Undervoltage Protection
The overall result of an undervoltage condition is an increase in current and motor heating and a reduction in overall motor performance. The undervoltage protection element can be thought of as backup protection for the thermal overload element. In some cases, if an undervoltage condition exists it may be desirable to trip the motor faster than thermal overload element. The undervoltage trip should be set to 90% of nameplate unless otherwise stated on the motor data sheets. Motors that are connected to the same source/bus may experience a temporary undervoltage, when one of motors starts. To override this temporary voltage sags, a time delay setpoint should be set greater than the motor starting time.
24
Unbalance Protection
Indication of unbalance negative sequence current / voltage Unbalance causes motor stress and temperature rise Current unbalance in a motor is result of unequal line voltages
Unbalanced supply, blown fuse, single-phasing
To limit the level of the ground fault current connect an impedance between the supplies neutral and ground. This impedance can be in the form of a resistor or grounding transformer sized to ensure maximum ground fault current is limited.
26
All phase conductors are passed through the window of the same CT referred to as the zero sequence CT Under normal circumstances, the three phase currents will sum to zero resulting in an output of zero from the Zero Sequence CTs secondary. If one of the motors phases were to shorted to ground, the sum of the phase currents would no longer equal zero causing a current to flow in the secondary of the zero sequence. This current would be detected by the motor relay as a ground fault.
27
For large cables that cannot be fit through the zero sequence CTs window, the residual ground fault configuration can be used. This configuration is inherently less sensitive than that of the zero sequence configuration owing to the fact that the CTs are not perfectly matched. During motor starting, the motors phase currents typically rise to magnitudes excess of 6 times motors full load current and are asymmetrical. The combination of non perfectly matched CTs and relative large phase current magnitudes produce a false residual current. This current will be misinterpreted by the motor relay as a ground fault unless the ground fault elements pickup is set high enough to disregard this error during starting
28
Differential Protection
Differential protection may be considered the first line of protection for internal phase-to-phase or phase-to-ground faults. In the event of such faults, the quick response of the differential element may limit the damage that may have otherwise occurred to the motor.
29
Differential Protection
Summation method with six CTs:
If six CTs are used in a summing configuration, during motor starting, the values from the two CTs on each phase may not be equal as the CTs are not perfectly identical and asymmetrical currents may cause the CTs on each phase to have different outputs. To prevent nuisance tripping in this configuration, the differential level may have to be set less sensitive, or the differential time delay may have to be extended to ride through the problem period during motor starting. The running differential delay can then be fine tuned to an application such that it responds very fast and is sensitive to low differential current levels.
30
Differential Protection
Biased differential protection - six CTs:
Biased differential protection method allows for different ratios for system/line and the neutral CTs. This method has a dual slope characteristic. Main purpose of the percent-slope characteristic is to prevent a mis-operation caused by unbalances between CTs during external faults. CT unbalances arise as a result of CT accuracy errors or CT saturation. Characteristic allows for very sensitive settings when the fault current is low and less sensitive settings when the fault current is high and CT performance may produce incorrect operating signals.
31
32
33
Starts/Hour
Conclusions
Induction & synchronous motors are valuable assets to todays industrial facilities.
The temperature rise of motor dictates its life When applied, thermal protection can prevent loss of motor life Additional protection elements such as overvoltage, undervoltage, unbalance, ground fault, differential, short circuit and stator RTD supplement the thermal model protection and provide complete motor protection.
35