05 SM6 - Installation & Maintenance Guildline
05 SM6 - Installation & Maintenance Guildline
05 SM6 - Installation & Maintenance Guildline
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Corrosive atmosphere
Ambient air
temperature
40C
35C, on average over 24h
5C
Environment
Altitude
Humidity
Pollution:
SO2 = sulphur dioxide, H2
S = hydrogen sulphide
NOTE 1: Condensation can be expected where sudden temperature changes occur in period of high
humidity.
NOTE 2: To withstand the effects of high humidity and condensation, such as a breakdown of insulation or
corrosion of metallic parts, switchgear designed for such conditions and tested accordingly should be used.
NOTE 3: Condensation may be prevented by special design of the building or housing, by suitable ventilation
and heating of the station or by use of dehumifying equipment.
Schneider Electric - Field Services Division
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
10
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
11
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
12
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
13
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
14
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
15
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
16
Remark
Visual inspection
1.
2.
3.
4.
5.
Switchgear compartment
Busbars compartment
Connection / switchgear compartment
Operating mechanism cabinet
LV Control cabinet
Disassembly
1.
2.
3.
4.
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
17
Remark
Clean / Grease
1.
2.
3.
4.
5.
6.
7.
8.
Busbar compartment
Clean compartment / enclosure / busbars
Check presence of tension
Connection / switchgear compartment
Clean compartment / enclosure / clusters / earth disconnector splitters
Grease earth disconnector clusters / links / contacts
Operating mechanism
Clean mechanical links (do NOT grease)
Inspection
1.
2.
3.
4.
5.
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
18
Remark
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
19
Remark
Inspection of MV fuses
1.
2.
3.
Tests
1.
2.
3.
Reassembly
1.
2.
3.
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
20
ProDiag
ProCorona
ProFusion
IR Thermography (non proprietary tool)
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
21
Thanks!
Make the most of your energy
Operation training for electrical engineer - NESTLE Viet nam Tri An Plant
22