Module I
Module I
M.JANAKI
Associate Professor,
School of Electrical Engineering.
Open Hrs:
Wednesday 10.00 AM to 11.00 AM
Friday 10.00 AM to 11.00 AM
Reference books
1. Generation
2. Transmission
3. Distribution
Prime mover converts primary sources of energy to mechanical energy.
Distribution Transmission
Nuclear
Sector Total (MW) %
(MW)
Sub-Total Other
Coal Gas Diesel Hydro
Thermal Renewable
All India 194,402.88 25,329.38 837.63 220,569.88 6,780.00 44,594.42 57,260.23 329,204.53 100
The various generating stations and distribution systems are
connected through transmission lines. This primary transmission
system in a state is called as ‘GRID’.
500 MW
Eastern
220 kV
220 kV
Malanpur Vindhyachal Korba Budhipadar
Western
Raipur Rourkela
Kolhapur 400 kV
Chandrapur Jeypore Talcher Balimela
1000 MW
500 MW 2500 MW
220 kV
220 kV
Belgaum Upper
Gazuwaka Kolar
Ramagundam Sileru
Southern
There are two types of Transmission
1. A.C Transmission
2. D.C Transmission
Limitation
1. Increased cost of insulation, transformer and switchgear
equipments.
Electric power can be transmitted in two ways
1. Overhead lines
2. Underground cables
Earth wire is used to shield the phase conductors from lighting strokes
Vibration damper is the spacer between conductors in one phase.
Transmission system Bundled conductors
2. Three phase transmission system with bundled conductors
(two stranded conductors/phase)
To carry more than one circuit
ROW
1. Resistance
2. Inductance
3. Capacitance
1. Resistance
2. Inductance
3. Capacitance
Inductance L in henry
I
I Current in amps
Capacitance : Any two conductors separated by an insulating material
has capacitance effect.
Across two overhead transmission lines, air is the insulation, so there
exist a capacitance.
q
Capacitance C in farad
V
q Charge on the conductor in coulomb
• Inductance
• Capacitance
Inductance
Flux Linkages :
L
I
Due to
L
I
1(a). Due to internal flux:
According to Ampere’s law, m.m.f around
any closed path is equal to the current
enclosed. From this, the magnetic field
intensity at a point ‘x’ metres from the
centre is
Ix
Hx
2x
Current density at ‘x’ is
I Ix
2
r 2
x
x 2 x2
Ix 2 I 2 I is the fraction of total current (I) at x.
r r
The magnetic field intensity at a point ‘x’ metres from the centre is
1 x2 x
Hx . 2 I I Amp-turns/m
2x r 2r 2
Flux density Bx
B x 0 r H x
x
B x 0 r I Wb/m2
2r 2
d Bx .1.dx
0 r xI
dx Wb
2r 2
From this, the flux linking the section dx is given by
x2
Flux linkage d 2 d
r
Relative permeability
x 0 xI
2
r 1
2. dx For non-magnetic
r 2r 2 materials
0 x I 3
dx
2r 4
Total flux linkages from centre upto the conductor surface is given by
0 x I
r 3
int dx
0 2r
4
0 I
Wb-turns per metre
8
1(b). Due to External flux: External flux
extends from surface of the conductor to
infinity.
I
Hx
2x
0 I
B x 0 H x Wb/m2
2x
Considering 1m length, dx thickness of cylindrical shell, the flux is
given by
0 I
flux d Bx .1.dx dx
2x
This flux links the total current in the conductor
0 I
d d dx
2x
Total flux linkages due to external flux
0 I
ext dx
r
2x
2. Flux linkages in parallel current carrying conductors
Flux linkages in conductor ‘A’ due to its own current IA
Int Ext
1. Inductance of a Single Phase Two-wire Line
IA Current in amps
Flux linking with conductor ‘A’
= +
Inductance of a single phase circuit in alternative form
Where r’ is the radius of fictitious conductor ( imaginary conductor, not
the existing conductor) with no internal flux, but inductance is same as
the actual conductor.
If load is balanced
IA + IB + IC = 0
A
Inductance of line ‘A’ LA
IA
A Flux linkages in Wb-turns
IA Current in amps
= + +
2(a). SYMMETRICAL SPACING
IA + IB + IC = 0
Inductance/phase/m
Inductance/phase/m
Why transposed?
(d1d 2 d3 )1/ 3
is called as GMD or equivalent
equilateral spacing.
Three phase transmission Three phase transmission
- Single circuit - Double circuit
Inductance/phase/m
GMD=(GMDab*GMDbc*GMDca)1/3
GMR=(GMRa*GMRb*GMRc)1/3
Unequal GMR and GMD
GMDab GMDbc
GMDca
When the physical structure of transmission system is not in equilateral
triangle, the transposition of conductors is done to get the same average radius and
distance.
GMR and GMD are radius and distance of
GMR equivalent equilateral triangle.
GMD=(GMDab*GMDbc*GMDca)1/3
GMR=(GMRa*GMRb*GMRc)1/3
GMR=(GMRa*GMRb*GMRc)1/p
GMD=(GMDab*GMDbc*GMDca)1/L
where
where
1. A single phase transmission line has two parallel conductors 3 m
apart, the radius of each conductor being 1 cm. Calculate the loop
inductance per km length of the line if the material of the conductor is
(i) copper (ii) steel with relative permeability of 100.
Ans:
Ds2 = 0.246 m
Ds = 3 DS1DS 2 DS 3 = 0.275 m
= 4.48 m = DBC
DCA = 6 m
Inductance/phase/km = 0.57 mH
5. Fig shows three phase double circuit overhead line. Conductor radius is
0.75 cm. Calculate the inductance/phase/km
Inductance/phase/km = 0.623 mH
6. Two conductors of a single phase line, each of 1 cm diameter, are
arranged in a vertical plane with one conductor mounted 1 m above the
other. A second identical line is mounted at the same height as the first
and spaced horizontally 0·25 m apart from it. The two upper and the two
lower conductors are connected in parallel. Determine the inductance per
km of the resulting double circuit line.
q
Capacitance C in farad
V
q Charge on the conductor in coulomb
Since the unlike charges attract each other, the potential difference
between the conductors is
Line-1
Capacitance between two conductors
Ic = series of two capacitances (w.r.t neutral)
Line-2
Capacitance of a 3-Phase Overhead Line
(i) Symmetrical spacing.
(ii) Unsymmetrical spacing.
Single phase transmission - single circuit
Capacitance/conductor/m
Capacitance/phase/m
Capacitance/phase/m
Three phase transmission Three phase transmission
- Single circuit - Double circuit
GMD=(GMDab*GMDbc*GMDca)1/3
GMR=(GMRa*GMRb*GMRc)1/3
EFFECT OF EARTH ON LINE CAPACITANCE
The electric flux lines due to an isolated (effect of earth neglected)
positively charged conductor emanate from the conductor and terminate
on to an imaginary conductor placed at infinity.
qb qa
But qb = - qa
2. A 200 km, 3-phase transmission line has its conductors placed at the
corners of an equilateral triangle of 2·5 m side. The radius of each
conductor is 1 cm. Calculate :
(i) line to neutral capacitance of the line,
(ii) charging current per phase if the line is maintained at 66 kV, 50 Hz.
1. Skin effect
2. Proximity effect
Disadvantages:
2. ….
SKIN EFFECT
An alternating current in a
conductor produces an alternating
magnetic field in and around the
conductor. When the intensity of current
in a conductor changes, the magnetic
field also changes. The change in the
magnetic field, in turn, creates an
electric field which opposes the change
in current intensity. This opposing
electric field is called “counter-
electromotive force” (counter EMF). The
counter EMF is strongest at the center of
the conductor, and forces the conducting
electrons to the outside of the conductor,
as shown in the diagram on the right.
SKIN EFFECT contd
Skin effect is the tendency of an
alternating electric current (AC) to
distribute itself within a conductor with the
current density being largest near the
surface of the conductor, decreasing at
greater depths.
The electric current flows mainly at
the "skin" of the conductor, between the
outer surface and a level called the skin
depth.
The skin effect causes the effective
resistance of the conductor to increase at
higher frequencies where the skin depth is
smaller, thus reducing the effective cross-
section of the conductor.
The skin effect is due to opposing
eddy currents induced by the changing
magnetic field resulting from the
alternating current.
The skin effect depends on following factors
1. Nature of material
2. Diameter of wire
3. Frequency of supply
4. Shape of wire.
b.
2.
3. Calculate inductance and capacitance per phase of a transmission
consisting 50mm2 ‘Hazel’ AAAC conductor. The conductors are
composed of 7 strands of aluminium alloy with diameter 3.3mm. The
inter-phase spacing is 50cm as shown fig.
a b
A B d3 C
GMR
d1 d2
A B C
d3
D3
D1 D2
GMR d1 d2
d3
d1 d2
GMR
d3
d1 d2
A B C
d3
4.
Enter radius of the conductor
=0.080914/0.7788
Enter number of phases =3
Enter number of circuits =2
Enter number of conductors/bundle
=1
Enter distances for GMR calculation
Enter Ds distance 2
=17.897
Enter Ds distance 3
=17.897
GMR_phase =
1.2034
Enter Ds distance 6
=16.5
Enter Ds distance 7
=16.5
GMR_phase =
1.2034 1.1555
Enter Ds distance 10
=17.897
Enter Ds distance 11
=17.897
GMR_phase =
GMR_final =
1.1872
Enter distances for GMD calculation
Enter Dm distance 1
=7.5208
Enter Dm distance 2
=15.89
Enter Dm distance 3
=15.429
Enter Dm distance 4
=6.8007
GMD_phph =
10.582
Enter Dm distance 5
=6.8007
Enter Dm distance 6
=15.89
Enter Dm distance 7
=15.429
Enter Dm distance 8
=7.5208
GMD_phph =
10.582 10.582
Enter Dm distance 9
=13.521
Enter Dm distance 10
=11
Enter Dm distance 11
=12.5
Enter Dm distance 12
=13.521
GMD_phph =
GMD_final =
11.213
2. Steel poles. The steel poles are often used as a substitute for
wooden poles. They possess greater mechanical strength, longer life
and permit longer spans to be used. Such poles are generally used for
distribution purposes in the cities. This type of supports need to be
galvanised or painted in order to prolong its life. The steel poles are of
three types viz., (i) rail poles (ii) tubular poles and (iii) rolled steel
joints.
3. RCC poles. The reinforced concrete poles have become very popular
as line supports in recent years. They have greater mechanical
strength, longer life and permit longer spans than steel poles. Moreover,
they give good outlook, require little maintenance and have good
insulating properties. Fig. shows R.C.C. poles for single and double
circuit.
The main difficulty with the use of these poles is the high cost
of transport owing to their heavy weight. Therefore, such poles are
often manufactured at the site in order to avoid heavy cost of
transportation.
1. A 200 km, 3-phase transmission line has its conductors placed at the
corners of an equilateral triangle of 2·5 m side. The radius of each
conductor is 1 cm. Calculate :
(i) line to neutral capacitance of the line,
(ii) charging current per phase if the line is maintained at 66 kV, 50 Hz.
[2.02 μF], [24.2 A]
(i) the sending end current (ii) sending end voltage (line-to-line)
(iii) sending end power factor (iv) transmission efficiency
Use nominal T method.
+
3. A 3-phase, 50 Hz, 100 km transmission line has the following
constants ;
Resistance/phase/km = 0·1 Ω
Reactance/phase/km = 0·5 Ω
Susceptance/phase/km = 10−5 siemen
(i) sending end current (ii) line value of sending end voltage
(iii) sending end power factor (iv) regulation
[(i) 177·6 A (ii) 76kV (iii) 0·905 lag (iv) 15·15%]