Per Unit System Explaination - With Solved Example
Per Unit System Explaination - With Solved Example
The Per Unit System Allows engineers to analyze a single phase network where:
All P and Q quantities are three phase Voltage magnitudes are represented as a fractional part of their standard or base value All phase angles are represented in the same units as normally used
Advantages
1. Per-unit representation results in a more meaningful and correlated data. It gives relative magnitude information. 2. There will be less chance of missing up between single - and three-phase powers or between line and phase voltages. 3. The p.u. system is very useful in simulating machine systems on analog, digital, and hybrid computers for steady-state and dynamic analysis. 4. Manufacturers usually specify the impedance of a piece of apparatus in p.u. (or per cent) on the base of the name plate rating of power (P) and voltage (V). Hence, it can be used directly if the bases chosen are the same as the name plate rating. 5. The p.u. value of the various apparatus lie in a narrow range, though the actual values vary widely. 6. The p.u. equivalent impedance (Zsc) of any transformer is the same referred to either primary or secondary side. For complicated systems involving many transformers or different turns ratio, this advantage is a significant one in that a possible cause of serious mistakes is removed. 7. Though the type of transformer in 3-phase system, determine the ratio of voltage bases, the p.u. impedance is the same irrespective of the type of 3-phase transformer. (Y D , D Y, D D , or Y Y) 8. Per-unit method allows the same basic arithmetic operation resulting in per-phase end values, without having to worry about the factor '100' which occurs in per cent system.
Conversion Procedure
-Specify the MVA base. Typically this will be related to the rating of a generator, transformer, or transmission line. Just choose the one that will result in the least amount of computation. This base will remain constant throughout the system. -At any location in the circuit, specify a voltage base. This will typically be the nominal voltage for that particular location. -Determine the voltage base for all other areas in the circuit by adjusting by the turns ratio every time a transformer is encountered. -Having specified the voltage and MVA base throughout the system, current and impedance bases may be determined as:
-For each value, the per unit quantity is the actual value divided by the base value.
Set Up the Per Unit System Each region of the power system is uniquely defined by a standard voltage determined by the transformer windings, this sets base voltage The entire system is given a base power to which everything in the power flow is referred
Zone 2
Zone 3
Zone 4
VBase1
Z Base1 !
Base1
VBase 2
I Base1
VBase3
VBase 4
Example - 1
Given a one line diagram,
Vg ! 13.2kV
Ig
5 MVA 13.2 132 Y kV
Z line
10 j100;
10 MVA 138 Y - 69 kV
~
Find
Z load ! 300;
X l1 ! 0.1p.u.
X l 2 ! 0.08p.u.
Ig
5 MVA 13.2 132 Y kV
Z line ! 10 j100;
10 MVA 138 Y - 69 kV
Z load ! 300;
X l1 ! 0.1p.u.
X l 2 ! 0.08p.u.
S B ! 10MVA
Zone 1 VB1 ! 13.8kV
Z B1 ! I B1 ! VBl1l
2
SB 3 S B* 1 3V
l -l B1
13.8k
!
10 M
! 19.04;
10 M ! ! 418 .4 3 13.8k
SB 3 S B* 2 3V
l-l B2
138k
!
10 M
! 1904;
69k
2 !
10 M
! 476 ;
10 M ! ! 41.84 3 138 k
I B3 !
3 VBl -3l
10 M ! 83.67 3 69k
+ -
new p.u.
new B
Z load,p.u. !
2
X l1,p.u .
! 0.63
Vg, p.u. !
Vg VB1
Z line,p.u. !
! 0.183
X l 2 ! 0.08
+ -
Z load,p.u. ! 0.63
0.96 0r ! ! 1.35 26.4r I load,p.u. ! Z total,p.u. 0.709 26.4r Vload,p.u. ! I load,p.u. Z load,p.u. ! 0.8505 26.4r
* S load,p.u. ! Vload,p.u. I load,p.u. ! 1.148
Vg, p.u.
Ig
5 MVA 13.2 132 Y kV
Z line ! 10 j100;
10 MVA 138 Y - 69 kV
Z load ! 300;
Vload, p.u. ! 0.8505 26.4r S load, p.u. ! 1.148
X l1 ! 0.1p.u.
X l 2 ! 0.08p.u.
Zone 1
Zone 2
Zone 3
I g ! I g, p.u. I B1
I t -line ! I t -line,p.u. I B2