Ch5 Synchronous Machine
Ch5 Synchronous Machine
machines
CONSTRUCTION OF SYNCHRONOUS MACHINES
Salient pole
Salient pole with
without field
field windings
windings – observe
laminations
CONSTRUCTION OF SYNCHRONOUS MACHINES
Two common approaches are used to supply a DC current to the field
circuits on the rotating rotor:
Slip rings are metal rings completely encircling the shaft of a machine but
insulated from it. One end of a DC rotor winding is connected to each of the
two slip rings on the machine’s shaft. Graphite-like carbon brushes
connected to DC terminals ride on each slip ring supplying DC voltage to
field windings regardless the position or speed of the rotor.
CONSTRUCTION OF SYNCHRONOUS MACHINES
Slip rings
Brush
CONSTRUCTION OF SYNCHRONOUS MACHINES
Slip rings and brushes have certain disadvantages: increased friction and
wear (therefore, needed maintenance), brush voltage drop can introduce
significant power losses. Still this approach is used in most small synchronous
machines.
On large generators and motors, brushless exciters are used.
A brushless exciter is a small AC generator whose field circuits are
mounted on the stator and armature circuits are mounted on the
rotor shaft. The exciter generator’s 3-phase output is rectified to DC
by a 3-phase rectifier (mounted on the shaft) and fed into the main
DC field circuit. It is possible to adjust the field current on the main
machine by controlling the small DC field current of the exciter
generator (located on the stator).
Since no mechanical contact occurs between the rotor and the stator,
exciters of this type require much less maintenance.
CONSTRUCTION OF SYNCHRONOUS MACHINES
A brushless exciter: a
low 3-phase current
is rectified and used
to supply the field
circuit of the exciter
(located on the
stator). The output of
the exciter’s
armature circuit (on
the rotor) is rectified
and used as the field
current of the main
machine.
CONSTRUCTION OF SYNCHRONOUS MACHINES
To make the
excitation of a
generator
completely
independent of any
external power
source, a small pilot
exciter is often
added to the
circuit. The pilot
exciter is an AC
generator with a
permanent magnet
mounted on the
rotor shaft and a 3-
phase winding on
the stator
producing the
power for the field
CONSTRUCTION OF SYNCHRONOUS MACHINES
A rotor of large
synchronous
machine with a
brushless exciter
mounted on the
same shaft.
Many synchronous
generators having
brushless exciters also
include slip rings and
brushes to provide
emergency source of
the field DC current.
CONSTRUCTION OF SYNCHRONOUS MACHINES
A large
synchronous
machine with
the exciter
and salient
poles.
The elementary 3-phase 2-pole synchronous generator has a stator
equipped with 3 coils displaced 120o from each other; although shown as
concentrated, they actually are distributed.
When the rotor is excited with dc and rotated, the resultant field will also
rotate so that sinusoidal voltages are generated in the 3 stator phases,
displaced 120o in time and having a frequency directly related to rotor
speed.
ROTATION SPEED OF SYNCHRONOUS GENERATOR
By the definition, synchronous generators produce electricity whose
frequency is synchronized with the mechanical rotational speed.
nm P
fe
120
Where fe is the electrical frequency, Hz;
nm is mechanical speed of magnetic field (rotor speed for
synchronous machine), rpm;
P is the number of poles.
Steam turbines are most efficient when rotating at high speed;
therefore, to generate 60 Hz, they are usually rotating at 3600 rpm
and turn 2-pole generators.
Water turbines are most efficient when rotating at low speeds (200-
300 rpm); therefore, they usually turn generators with many poles.
INTERNAL GENERATED VOLTAGE OF A
SYNCHRONOUS GENERATOR
EA 2 NC f K
where K is a constant representing the construction of the machine, is
flux in it and is its rotation speed.
V E A Estat
The net magnetic flux will be
Bnet BR BS
Rotor field Stator
field
Note that the directions of the net magnetic flux and the phase voltage are
the same.
EQUIVALENT CIRCUIT OF A SYNCHRONOUS
GENERATOR
Estat jXI A
The phase voltage is then V E A jXI A
Armature reactance can be modeled by the
following circuit…
However, in addition to armature reactance
effect, the stator coil has a self-inductance LA
(XA is the corresponding reactance) and the
stator has resistance RA. The phase voltage is
thus
V E A jXI A jX A I A RI A
EQUIVALENT CIRCUIT OF A SYNCHRONOUS
GENERATOR
XS X X A
Therefore, the phase voltage is
V E A jX S I A RI A
3V E A
Pmax
XS
POWER AND TORQUE IN SYNCHRONOUS
GENERATORS
3V E A sin
ind
m X S
MEASURING PARAMETERS OF SYNCHRONOUS
GENERATOR MODEL
The plot of armature current (or line current) vs. the field current is the short-
circuit characteristic (SCC) of the generator.
MEASURING PARAMETERS OF SYNCHRONOUS
GENERATOR MODEL
The magnetic
fields during
Since BS almost cancels BR, the short-circuit test
net field Bnet is very small.
MEASURING PARAMETERS OF SYNCHRONOUS
GENERATOR MODEL
EA
ZS R X
2
A
2
S X S since X S RA
I A, SC
MEASURING PARAMETERS OF SYNCHRONOUS
GENERATOR MODEL
VDC
2 RA
I DC
VDC 10
RA 0.2
2 I DC 2 25
MEASURING PARAMETERS OF SYNCHRONOUS
GENERATOR MODEL: EX
We observe that if XS was estimated via the approximate formula, the result
would be:
EA 311.8
XS 1.04
I A, SC 300
Which is close to the previous result.
The error ignoring RA is much smaller
than the error due to core
saturation. The equivalent circuit
THE SYNCHRONOUS GENERATOR OPERATING
ALONE
Leading PF
Lagging PF
Unity PF
THE SYNCHRONOUS GENERATOR OPERATING
ALONE
Vnl V fl
VR 100%
V fl
Where Vnl is the no-load voltage of the generator and Vfl is its full-load
voltage.
THE SYNCHRONOUS GENERATOR OPERATING
ALONE
V VT 3 277V
At no load, the armature current IA = 0 and the internal generated voltage
is EA = 277 V and it is constant since the field current was initially adjusted
that way.
a. The speed of rotation of a synchronous generator is
120 120
nm fe 60 1200rpm
P 6
which is 1200
m 2 125.7rad s
60
b.1. For the generator at the rated current and
the 0.8 PF lagging, the phasor diagram is shown.
The phase voltage is at 00, the magnitude of EA is
277 V,
THE SYNCHRONOUS GENERATOR OPERATING
ALONE: EXAMPLE
Two unknown quantities are the magnitude of V and the angle of EA.
From the phasor diagram:
Then:
V E X S I A cos X S I A sin 236.8V
2 2
A
VT 3V 410V
THE SYNCHRONOUS GENERATOR OPERATING
ALONE: EXAMPLE
and
VT 3V 535V
THE SYNCHRONOUS GENERATOR OPERATING
ALONE: EXAMPLE
Pconv 34.1
app 271.3N - m
m 125.7
e. The voltage regulation of the generator is
480 410
Lagging PF: VR 100% 17.1%
410
480 468
Unity PF: VR 100% 2.6%
468
480 535
Lagging PF: VR 100% 10.3%
535
TERMINAL CHARACTERISTICS OF SYNCHRONOUS
GENERATORS
All generators are driven by a prime mover, such as a steam, gas, water,
wind turbines, diesel engines, etc. Regardless the power source, most of
prime movers tend to slow down with increasing the load. This decrease in
speed is usually nonlinear but governor mechanisms of some type may be
included to linearize this dependence.
nnl n fl
SD 100%
n fl
Most prime movers have a speed drop from 2% to 4%. Most governors have
a mechanism to adjust the turbine’s no-load speed (set-point adjustment).
TERMINAL CHARACTERISTICS OF SYNCHRONOUS
GENERATORS
A typical
speed vs.
power plot
A typical
frequency vs.
power plot
P s p f nl f sys
Slope of curve, W/Hz Operating frequency of the
system
TERMINAL CHARACTERISTICS OF SYNCHRONOUS
GENERATORS
A similar relationship can be derived for the reactive power Q and terminal
voltage VT. When adding a lagging load to a synchronous generator, its
terminal voltage decreases. When adding a leading load to a synchronous
generator, its terminal voltage increases.
The plot of terminal voltage vs.
reactive power is not necessarily
linear.
Both the frequency-power and
terminal voltage vs. reactive
power characteristics are
important for parallel operations
of generators.
When a generator is operating alone supplying the load:
1. The real and reactive powers are the amounts demanded by the load.
2. The governor of the prime mover controls the operating frequency of the
system.
3. The field current controls the terminal voltage of the power system.
TERMINAL CHARACTERISTICS OF SYNCHRONOUS
GENERATORS: EXAMPLE
P s p f nl f sys
P
Therefore: f sys f nl
sp
TERMINAL CHARACTERISTICS OF SYNCHRONOUS
GENERATORS: EXAMPLE
After the real power of the generator is adjusted to the desired value, the
generator will be operating at a slightly leading PF acting as a capacitor that
consumes reactive power. Adjusting the field current of the machine, it is
possible to make it to supply reactive power Q to the system.
When a generator is working alone, its real and reactive power are fixed
and determined by the load.
When a generator is connected to an infinite bus, its frequency and the
terminal voltage are constant and determined by a bus.
When two generators of the same size are working in parallel, a change in
frequency (governor set points) of one of them changes both the system
frequency and power supplied by each generator.
2 Phase
3 Phase
SYNCHRONOUS MOTORS
Two magnetic fields are present in the machine, and the rotor field tends to
align with the stator magnetic field. Since the stator magnetic field is
rotating, the rotor magnetic field will try to catch up pulling the rotor.
The larger the angle between two magnetic fields (up to a certain
maximum), the greater the torque on the rotor of the machine.
SYNCHRONOUS MOTOR EQUIVALENT CIRCUIT
A synchronous motor has the same
equivalent circuit as synchronous
generator, except that the
direction of power flow (and the
direction of IA) is reversed. Per-
phase circuit is shown:
A change in direction of IA changes the Kirchhoff’s voltage law equation:
V E A jX S I A RA I A
Therefore, the internal generated voltage is
E A V jX S I A RA I A
We observe that this is exactly the same equation as the equation for the
generator, except that the sign on the current terms is reversed.
SYNCHRONOUS MOTOR VS. SYNCHRONOUS
GENERATOR
When the torque on the shaft of a synchronous motor exceeds the pullout
torque, the rotor can no longer remain locked to the stator and net
magnetic fields. It starts to slip behind them. As the motor slows down, the
stator magnetic field “laps” it repeatedly, and the direction of the induced
torque in the rotor reverses with each pass. As a result, huge torque surges
of alternating direction cause the motor vibrate severely. The loss of
synchronization after the pullout torque is exceeded is known as slipping
poles.
STEADY-STATE OPERATION OF MOTOR: EFFECT OF
TORQUE CHANGES
(a)
The angle θ is cosꜗ 0.85 = 31.8°, so the phasor current IA is equal to
Example:
Let us consider a large power system operating at 480 V. Load 1 is an
induction motor consuming 100 kW at 0.78 PF lagging, and load 2 is an
induction motor consuming 200 kW at 0.8 PF lagging. Load 3 is a
synchronous motor whose real power consumption is 150 kW.
a. If the synchronous motor is adjusted to 0.85 PF lagging, what is the line
current?
b. If the synchronous motor is adjusted to 0.85 PF leading, what is the line
current?
c. Assuming that the line losses are PLL = 3IL2RL, how du these losses compare
in the two cases?
STEADY-STATE OPERATION OF MOTOR: POWER
FACTOR CORRECTION
a. The real power of load 1 is 100 kW, and the reactive power of load 1 is
Q1 P1 tan 100 tan cos 1 0.78 80.2kVAR
The real power of load 2 is 200 kW, and the reactive power of load 2 is
Q2 P2 tan 200 tan cos 1 0.8 150kVAR
The real power of load 3 is 150 kW, and the reactive power of load 3 is
Q3 P3 tan 150 tan cos 1 0.85 93kVAR
The total real load is Ptot P1 P2 P3 100 200 150450kW
The total reactive load is Qtot Q1 Q2 Q3 80.2 150 93kVAR
b. The real and reactive powers of loads 1 and 2 are the same. The reactive
power of load 3 is
PLL 3I L2 RL 1344700RL
The transmission line losses in the second case are
PLL 3I L2 RL 96170RL
We notice that the transmission power losses are 28% less in the
second case, while the real power supplied to the loads is the same.
STEADY-STATE OPERATION OF MOTOR: POWER
FACTOR CORRECTION
The ability to adjust the power factor of one or more loads in a power
system can significantly affect the efficiency of the power system: the lower
the PF, the greater the losses in the power lines. Since most loads in a typical
power system are induction motors, having one or more over-excided
synchronous motors (leading loads) in the system is useful for the following
reasons:
1. A leading load supplies some reactive power to lagging loads in the
system. Since this reactive power does not travel along the transmission
line, transmission line current is reduced reducing power losses.
2. Since the transmission line carries less current, the line can be smaller for
a given power flow reducing system cost.
3. The over-excited mode of synchronous motor increases the motor’s
maximum
Usage torque. motors or other equipment increasing the overall
of synchronous
system’s PF is called power-factor correction. Since a synchronous motor
can provide PF correction, many loads that can accept constant speed
are driven by over-excited synchronous motors.
STARTING SYNCHRONOUS MOTORS
Consider a 60 Hz synchronous motor.
When the power is applied to the stator windings, the rotor (and,
therefore its magnetic field BR) is stationary. The stator magnetic
field BS starts sweeping around the motor at synchronous speed.
Note that the induced torque on the shaft
ind kBR BS
is zero at t = 0 since both magnetic fields are aligned.
At t = 0, assume that BS
(stator field) is vertical.
As BS sweeps along in s counter-clockwise direction, it
induces a voltage in bars of the amortisseur winding:
eind v B l
MOTOR STARTING BY AMORTISSEUR OR DAMPER
WINDINGS
PSCL 3I A2 RA
Since the current angle is irrelevant to the armature heating, synchronous
generators are rated in kVA rather than in KW.
The rotor (field winding) cupper losses are:
PRCL I F2 RF
Allowable heating sets the maximum field
current, which determines the maximum
acceptable armature voltage EA. These
translate to restrictions on the lowest
acceptable power factor:
The current IA can have different angles (that
depends on PF). EA is a sum of V and jXSIA.
We see that, (for a constant V) for some
angles the required EA exceeds its maximum
value.
SYNCHRONOUS MACHINE RATINGS
If the armature voltage exceeds its maximum allowed value, the windings
could be damaged. The angle of IA that requires maximum possible EA
specifies the rated power factor of the generator. It is possible to operate
the generator at a lower (more lagging) PF than the rated value, but only
by decreasing the apparent power supplied by the generator.
Synchronous motors are usually rated in terms of real output power and the
lowest PF at full-load conditions.