Cooling Water System
Cooling Water System
Cooling Water System
AND
NET WORK
F E D C B A
RAW WATER IN
THROUGH TUBEWELL #
5-A
3 Kg/cm2 CW SUPPLY TO
AMMONIA, POWER HOUSE AND
NITRIC ACID PLANTS
New Cooling Tower
Designed by Societe Hamon France
Capacity 30,000 m3/hr
Basin capacity 10,000 m3
Type Double cross flow induced
draft
No. of cells 6
Inner dimension of each cell 12.92 x 20.50 m
Fan blades 6
Height of fan stack 6.44 m
Return water temperature 43 0C
Supply water temperature 34 0C
Range 9 0C
Wet bulb temperature 29 0C
Basin depth 4m
Pump head above basin curb 12 m
IMPORTANT SPECIFICATION OF WEST & EAST
SIDE COOLING TOWER
NEW C.T OLD C.T BALCKE DIRTY C.T
C.T
System 10000 3000 500 500
volume
(m3)
Supply 34 34 34 47
Temp.(c)
Return 43 43 43 57
Temp.(c)
Temp. 9 9 9 10
Diff(c)
2201
LP steam driven pump 6500 580 750 3.2 Sigmond Pulsometer
JAT/JBT/JCT
Fouling
Biological growth
Corrosion
Scaling
Chemical Treatment
Besides treating the circulating
cooling water in large industrial
cooling tower systems to minimize
scaling and fouling, the water should
be filtered and also be dosed with
biocides and algaecides to prevent
growths that could interfere with the
continuous flow of the water.For
closed loop evaporative towers,
corrosion inhibitors may be used, but
caution should be taken to meet local
environmental regulations as some
COOLING TOWER CHEMICALS
Product Concentrati Function Dosing
on Scheme
Continuum 6ppm Mild steel Cotinuuous
AEC3192 corrosion inhibitor Based on blow
Flogard MS6208 6ppm down
(Packing: 25 kg Bags )
Chemicals for Cooling Water
Treatment
BIOCIDE: SYNCEM 387)
It is a 50% aqueous solution of Tetra-
alkyl phosphonium chloride. It is a
broad spectrum biocide used to control
microbiological fouling in cooling water
systems. It is effective slims & can also
be used to clean badly fouled system.
Recommended dosage range to clean a
fouled system is 20-60 ppm twice a
week. Routine treatment 10-30 ppm
o n c e a w e e k
(Dosage: 120 kg / 15 days, Packing: 30
COOLING WATER
CONSUMPTION AT PLANTS
CW Consumption
Ammonia
13800 13800
Nitric Acid
8470 7330
LCO2
74 70
Urea
1375 1750
NP
2750 2750
CAN
3102 2232
LINE C
565 500
COOLING WTER SUPPLY TO UREA PLANT AT
FOLLOWING EQUIPMENTS
COOLING WATER OPERATING PRESSURE 3.2 Kg
COOLING WATER SUPPLY TEMPERATURE 34C
COOLING RETURN TEMPERATURE 43C
Absorption tower 1
2 NH3 evaporator
3 Cooler condenser
COOLING WTER SUPPLY TO HNO3
PLANT AT FOLLOWING EQUIPMENTS
Low pressure C.W supply to following equipments
1 Steam/surface condenser
2 BFW pump bearing and glands
3 B.W circulation pumps and bearing oil jacket
4 Lube oil cooler of compressor set i. e AEG steam
turbine and tail gas turbine
5 Seal air cooler (labyrinth seal of tail gas turbine
1 P.A COMPRESSOR
A Lube oil cooler
B Inter stage cooler
2 I.A COMPRESSOR
A Lube oil cooler
B inter stage and after stage cooler
C First and second stage jackets
COOLING WTER SUPPLY TO UTILITY
PLANT AT FOLLOWING EQUIPMENTS
3 TURBINE HALL
A Condenser of turbines
B lube oil cooler
C Generator air cooler
D lube oil cooler and control oil cooler of KK turbine
4 BIOLER HOUSE
A FD fan, KK turbine, Lube oil cooler
B BFW Pump lube oil cooler
CN-SECTION
1- CN Reactor
2- Surface Condenser
COOLING WTER SUPPLY TO CAN PLANT
AT FOLLOWING EQUIPMENTS
CAN SECTION
1- Surface Condenser
3- NH3-Evaporator
COOLING WTER SUPPLY TO HNO3
LINE-C PLANT AT FOLLOWING
EQUIPMENTS
COOLING WATER OPERATING PRESSURE 3.2 Kg/cm2
COOLING WATER SUPPLY TEMPERATURE 34 C
COOLING RETURN TEMPERATURE 43 C
1 - Reactor Jacket
2 - Cooler Condenser
3 - Absorption Tower
4 - Air Compressor interstage cooler
5 - Lube oil cooler
6 - Air chamber of 6KV motor