Vapour Absorption Refrigeration System and Vapour Compression Refrigeration System

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1/ 9

Vapour Absorption Refrigeration System

And
Vapour Compression Refrigeration System
Refrigeration:

*Process of reducing & maintaining the temperature of a body below the


general temperature of its surroundings.
OR
*Process of removing the heat from a substance under a controlled
condition.
OR
*Continuous Extraction of heat from a body whose temperature is already
below the temperature of its surroundings.
Types of Refrigeration:

1)Vapour Compression Refrigeration System


2)Vapour Absorption Refrigeration System
Advantage of Vapour Absorption Machine (VAM)over
Compression Cycle Refrigeration Plant
Vapour Absorption Machine Compression Cycle Refrigeration
(VAM) Plant
1)low running cost on cheap fuels like 1)High running cost due to Electricity as Energy
-Agro fuels
Input
-Furnace oil
-Waste heat
2)High maintenance cost
2)Very low maintenance cost due to no 3)Frequent outage on plant need stand by
reciprocating parts having high wear & tear compressor
3)High plant availability due to no reciprocating 4)Loss of efficiency at part load due to fixed
parts mechanical losses & motor electrical losses
4)No loss of efficiency at part load. Efficiency
5)Possibility of fouling due to lube oil on
improves at part load
5)No fouling of evaporator surfaces due to evaporator surfaces
lubricating oil. 6)Large D.G set needed on standby
6)Small size standby D.G set is sufficient 7)High foundation cost due to reciprocating
7)Low foundation cost due to no reciprocating compressor
parts
8)low life of compressor
8)Long life plant At least 25 years
9)loss of efficiency with usage due to compressor
9)No loss of efficiency with usage
parts wear & tear
Cost Analysis

Absorption System Compression System


(Operational Cost) (Operational Cost)
• Capacity 110 RT • Capacity 110 RT
• Type of Energy HP Steam@8bar • Type of Energy Electricity
• Specific Steam 4 Kg/hr-RT • Specific Elect Consumption 0.7 KW/TR-HR
• Total Elect/Hr 77 KW
Consumption
• Daily Operation 22 Hr
• Total Steam/HR 440 Kg/hr
• Total Elect Consumption /Day 1694 KW
• Daily Operation 22 Hrs
• Cost of Energy 5.5 Rs/KW
• Total steam consumption /Day 9680 Kg
• Total Cost of Energy /Day 9317 Rs
• Cost of Steam 0.6 Rs/Kg • Total Operating Cost/Day 9317 Rs
• Total cost of energy /Day 5808 Rs • Total Cost of operation /Year 3400705 Rs
• Power required for m/c/Day 30 KW • Maintenance cost 20000 Rs
• Cost of power 5.5 Rs/KW • Total Operation Cost 3420705 Rs
• Cost of power requd for m/c/Day 165 Rs
• Total operating cost /Day 5973 Rs
• Total Cost of operation per year 2179984 Rs
• Maintenance Cost 15000 Rs
• Total operation cost 2194984 Rs
Cost Analysis

Compression System
Absorption System
(Capital Cost) (Capital Cost)
• Equipment cost including 2750000 Rs • Equipment cost including 2100000 Rs
Taxes & Duties Taxes & Duties
• Depreciation Rate 80% • Depreciation Rate 25%
• Depreciation Amount 2200000 Rs • Depreciation Amount 525000 Rs
• Saving in corporate Tax@35% 770000 Rs • Saving in corporate Tax@35% 183750 Rs
• Effective Cost 1980000 Rs • Effective Cost 1916250 Rs
Thank You