Plant Islanding Operation
Plant Islanding Operation
Plant Islanding Operation
What is Island
• When our Plant Campus (NZP) electrically Isolate
from grid due to open of breaker known as Tie
breaker, the condition called Island .
Tie breaker may be open any of following conditions
• OVER CURRENT 375 AMP.
• OVER FREQUECY 51.7 Hz. With time delay 150 msec.
• OVER FREQUENCY with (DF/DT) 51.5Hz. & 0.7Hz/sec. time delay
100msec.
• Under Frequency 48.3 Hz. Time delay 150msec.
• Under frequency with (DF/DT) 48.5 & 0.9 Hz/Sec. time delay 100mSec
How do know
BTGO
• Tie breaker Feedback on EHTC page.
• Droop machine comes in speed mode.
• ISO mode machine come in Load + frequency mode.
• Islanded feedback on CILMS panel.
• Unit loads may vary.
SBO
• CILMS Screen Display Islanded.
• Unit DAVR mode change from PF mode to Voltage mode.
• ISO mode machine DAVR come in Voltage mode.
Points to be watch carefully
For BTGO/SI
• Frequency of Iso Machine (Min set point 48.3 Hz)
• Mode of all machine (ISO = Load + frequency,
Droop = Speed control)
• Main parameters of unit (MS pr., MS temp,
Flame condition, Bypass opening etc.)
• TG Lub oil system (Discharge Pr. & Header
pr.)
Change in Logics &
Other modifications
1. HPBP Fast open
• Previous
• Previously it was logic that whenever tie breaker
open close feedback gone there is HPBP fast
open for 3 Sec.
• Present
• Now there is HPBP fast open whenever tie-
breaker open & In Export Mode (Unit-2&3)
2.Frequency ref set point
Previous:-
• It was taken the same frequency whenever
tie- breaker open feedback.
Present:-
• Presently it is changed to Minimum 49.3 HZ.
3. TG lub oil Pump System
Previous :-
• Previously it was auto start on lub. oil disch.
Pressure low OR lub oil hdr. Pr. Low
Present :-
• Now it has been edited with turbine rpm
< 2930 rpm also. stand by pump will auto start.
• VFD installed in TG AOP of unit-1 (trial purpose)
SOP for Island
• After island confirmation BTGO should verify that the isochronous m/c
is in load control mode with frequency control influence ON and the
droop m/c is in speed control mode.
• SBO should keep the AVR of droop m/c in ‘Auto’ mode and verify the
AVR of isochronous machine is in ‘auto’ mode. This will ensure that
the machine which is in isochronous mode has become master and any
change which will be done for frequency and voltage in this machine
the other machine will follow the changes.
• BTGO must ensure that ISO Machine Frequency reference (FR) value
should be more than 48.3 Hz. (Minimum set point is 48.3 HZ) If not
then increase it more than 47.5 HZ through Frequency reference pop-up
(EHTC page)
• At the islanded condition, load sharing of among all m/c s can be done
by varying the speed of the droop m/c with proper communication
among BTGO of all units. Whenever load varying keep eagle-eyed on
all parameters
SOP for Island
• IF our all unit have no margin for increase the
load & frequency is going down below 48.5HZ
Then contact to NZP side for the reduce the
load for sustain the frequency.
• IF there is any requirement to increase the
frequency of our system then we can adjust
the frequency by the ISO machine with the
frequency reference set point.
SOP Of Island