Installation & Troubleshooting Guidelines For API Seal Flush Plans
Installation & Troubleshooting Guidelines For API Seal Flush Plans
Installation & Troubleshooting Guidelines For API Seal Flush Plans
2
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
Springs Secondary
Sealing
Secondary
Members
Sealing
Members
Adaptive
Hardware
3
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
4
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
5
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
6
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
7
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
A variety of seal flush arrangements may be used
depending on
pump construction
the type of seal assembly being used
the seal chamber pressure
fluid properties
operating conditions such as temperature, viscosity, etc.
It is essential that the correct seal flush arrangement
be installed and operated properly
8
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
9
Installation & Troubleshooting Guidelines
for API Seal Flush Plans-Introduction
API Piping Plan Summary (* = not covered)
01*,02*………Pump feature flush plan
11,12*,13,14…By pass Flush- Flush plans intended to keep the
seal area clean and remove seal generated heat
21,22*,23…….Cooling Flush plan - Flush plans intend to cool
the seal area
31,32,33*…….Slurry Flush Plan - Flush plan intended to keep
the slurries away from the sealing area.
41*…………....a combination plan for cooling and slurry
51*,52,53……..Dual Seal Flush plans
61,62………….Atmospheric flush plans to provide for a
suitable atmosphere outside the seal area or
behind the primary seal faces-Quench
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice
Gauge
Valve
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice
Gauge
Valve
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice
Orifice
Rotameter
Gauge
Block Valve Pressure
Valves Pressure Gauge
Gauge
Rotameter
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Line up procedure-Plan 14
The line from discharge should be the same
temperature from the connection at the pump case to
the primary seal flush port on the primary seal flange
or the seal chamber tap.
The line to suction should be the same temperature
from the seal flush port on the primary seal flange to
the suction connection.
Both lines should be the same temperature as the
pump case
2
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 14 Orifice
Cold Service
Line from discharge-when the seal flush
line is clogged in a cold service, you will Orifice
find the line hotter at the seal flush port
connection on the seal flange or seal
chamber tap. The line will cool as you
move toward the origin of the seal flush.
The heat you measure at this point is
radiating up the seal flush line and is
generated by the mechanical seal. This
differential may be quite small for plan 14
is the seal chamber pressure is high
enough to generate some flow through the API Piping Plan 14
line to suction. Line from seal flange through
orifice to pump suction and line from
pump discharge to seal flange or seal
chamber tap
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Orifice
Troubleshooting-Plan 14 Orifice
Cold Service
Line to suction-if the line from
discharge is operating properly, it
may not be possible to detect that
this line is plugged. If vapors
are accumulating at the top of the
seal chamber, the line will be
warmer at the primary seal flange
and cool as you move away from it
toward the suction connection due
to heat generation at the seal.
Otherwise a flow indicator is
helpful to detect failure of this line.
API Piping Plan 14
Line from seal flange through
orifice to pump suction and line from
pump discharge to seal flange or seal
chamber tap
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and Orifice
Troubleshooting-Plan 14
Hot Service
Line from discharge-when the Orifice
seal flush line is clogged in a hot
service, you will find the line cold.
It may be hot at the origin and
also at the flush port connection
on the seal flange or seal chamber
tap, but it will become cold as you
move away from the connections.
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Heat Exchanger
Gauge
Valve
Heat Exchanger
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
3
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice
Preventive Maintenance and
Troubleshooting- Plan 21
Clogged or closed seal flush
line-when the seal flush line
is clogged or closed, you will Heat Exchanger
find the seal flush line and
heat exchanger cold. The
seal flush line may be hot at
the origin and at the flush
port connection, but it will
become cold as you move
away from the connections. API Piping Plan 21
Line from discharge through
orifice and cooler to seal flange
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice
Preventive Maintenance and
Troubleshooting-Plan 21
Loss of cooling water flow-if
cooling water flow is lost,
the seal flush line will be hot Heat Exchanger
throughout its entire length.
The cooling water lines will
be hot near the heat
exchanger and become
cooler as you move away
from the heat exchanger. API Piping Plan 21
Line from discharge through
orifice and cooler to seal flange
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice
Preventive Maintenance
and Troubleshooting-Plan
21
Missing or oversized orifice-if
Heat Exchanger
the orifice is oversized or
missing, the temperature
drop in the flush line across
the cooler will be inadequate.
The temperature rise in the
cooling water lines across the
cooler will be excessive and
the heat exchanger case will
be hot API Piping Plan 21
Line from discharge through orifice
and cooler to seal flange
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Vent Valves
API
PIPING
To suitable drain
or disposal system
Long radius
PLAN 23
tubing bends Line from seal
required for Heat to cooler
all elbows Exchanger and back to
seal flange
18-24”
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
4
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 23
Unvented or closed valve in the
seal flush circulation lines-if the
system is not properly vented or a
valve is closed in the seal flush
circulation lines you will find the
seal lines and heat exchanger 18-24”
cold. The flush lines may be hot
at their origin, but will become
cold as you move away toward
the heat exchanger. The body of
the heat exchanger may also be
cold. API PIPING PLAN 23
Line from seal to cooler
and back to seal flange
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 23
Clogged or closed cooling water
system-if the cooling water system is
inoperable, you will find the process
lines entering and exiting the heat
exchanger at the same temperature.
The body of the heat exchanger will 18-24”
also be very hot. The cooling water
lines entering and exiting the heat
exchanger will be very hot at the
cover and both lines will cool as you
move away from the heat exchanger. API PIPING PLAN 23
Line from seal to cooler
and back to seal flange
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Pressure
Block Valve Gauge
Gauge
Valve
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
5
Installation & Troubleshooting Guidelines
for API Seal Flush Plans
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Hot Service-seal flush line plugged.
When the line from the cyclone
separator to suction is clogged, you
will find the cyclone itself hot and the
line to the seal flange. The connection
at the suction may be hot near the
pump case but will become cooler as
you move away from the connection.
The seal may leak erratically due to a
high flush rate. It will fail quickly
since it is being subjected to all the
API Piping Plan 31
abrasives present in the system. Line
from discharge through orifice
and cyclone separator to seal flange
5
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Hot Service-seal flush line
plugged. If the orifice is
plugged the line from the
pump case to the cyclone
will be cold. The lines to the
seal and the suction
connection may be hot since
fluid is flowing from the seal
back to the cyclone and then API Piping Plan 31
to suction. Line from discharge through orifice
and cyclone separator to seal flange
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Hot Service-seal flush line
plugged. Finally, if a valve is
closed in the line from the
cyclone to the seal, this line
will be cold but may be hot at
the seal connection or the
cyclone. The lines from the
pump case to the cyclone will
be hot since liquid is flowing API Piping Plan 31
from discharge to the cyclone Line from discharge through orifice
and then back to suction. and cyclone separator to seal flange
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Cold Service-seal flush
line plugged. When the
cyclone separator is
clogged in a cold service,
the line to the seal will be
hotter than the rest of the
line at the seal connection.
The lines will be cool in
all other locations
API Piping Plan 31
Line from discharge through orifice
and cyclone separator to seal flange
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Cold Service-seal flush line
plugged. If the line from the
cyclone to pump suction is
clogged, there will be no
physical evidence. The lines
will be the same temperature
in all locations since fluid is
flowing to the seal. The seal
may exhibit erratic leakage
due to the presence of solids API Piping Plan 31
and a high flush rate. Line from discharge through orifice
and cyclone separator to seal flange
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Cold Service-seal flush line
plugged. If the orifice is plugged,
there will be no physical evidence.
All lines will be cool since there is
flow from the seal to the cyclone
and then back to suction. The seal
may be operating fine unless there
is no enough differential pressure
between the seal chamber and
suction to provide adequate flow.
Then the connection at the seal
flange may be warm. API Piping Plan 31
Line from discharge through orifice
and cyclone separator to seal flange
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 31
Cold Service-seal flush line
plugged. A closed valve
between the cyclone separator
and the seal flange will result in
no flow to the seal. The
connection at the seal flange
may be warm. The lines will be
cool at all other locations since
there will be flow from pump
discharge to the cyclone and
back to suction. API Piping Plan 31
Line from discharge through orifice
and cyclone separator to seal flange
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Check Valve
Pressure
Indicator
Block
Flow Indicator
Pressure Valve
or Flow
Regulator
Pressure
Indicator External Source
of Clean Fluid
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
6
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Orifice To Suitable
Block and Vapor Recovery
Pressure Bleed Valve System
Gauge Fill Connection
Pressure High Level Switch Low Level
Switch Switch
Long Radius Temperature
Tubing Bends Indicator
Cooling
Required
Water Drain 18-24”
Connections Valve
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Line Up Procedure-API Plan 52 Continued
Check the gauge on the reservoir. There should
be no pressure (or the pressure reading should
be less than or equal to the flare header pressure
or the system to which the reservoir is vented).
Proceed with opening all valves for service
Check for leaks around valves and connections
in the flare connection line
Start pump per normal procedure
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
7
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance
and Troubleshooting-Plan
52
Pressure Increase-check to
make sure the line to the
flare header is not closed or
blocked. Block in the
cooling water and drain off
a small amount of buffer
fluid to check for water. API Piping Plan 52
The cooling coil may be Circulation of clean unpressurized
leaking.
buffer fluid from seal to external
reservoir and back to seal
8
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
8
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
8
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
8
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and Troubleshooting-Plan 53
The double seal reservoir should be checked on normal
operator rounds on a regular basis. The base level should
be checked for fluid loss or gain. The base pressure of the
system should also be monitored. The temperature of the
reservoir should be checked.
A pressure loss in the reservoir may be an indication of
either a primary or secondary seal leak. Small
fluctuations are acceptable since the supply pressure to
the pressure controller may also be variable. A pressure
loss can also be due to a defective controller.
8
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
8
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and Troubleshooting-Plan 53
A level loss in the reservoir is also a sign of a leaking
primary or secondary seal. A slowly decreasing level is
a normal symptom since both seals will have normal
leakage.
When a level loss is observed, also check the pressure
reading.
A level decrease in the reservoir may not be due to seal
leakage. Check all the seal circulation piping and
connections. Make sure the drain valve is closed.
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 53
Pressure Loss-check to make
sure the line from the pressure
source is not closed or blocked.
Block in the cooling water and
drain off a small amount of
buffer fluid to check for water.
The cooling coil may be
leaking. Check the pressure
controller. Check all lines and
connections for leaks. Make
API Piping Plan 53
sure the drain valve is closed. Circulation
of Clean Pressurized
Barrier Fluid from Seal to
Reservoir and back to Seal
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance
and Troubleshooting-Plan
53
Pressure rise-the pressure
regulator is either stuck or
defective. Tap on the
regulator to see if the
pressure will drop to the base
level. If not it must be
replaced or recalibrated. If a
bias regulator is being used,
API Piping Plan 53
the pressure sensor line may Circulation of Clean Pressurized
be plugged Barrier Fluid from Seal to
Reservoir and back to Seal
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 53
Level increase-the system has lost
pressure and pump product is
leaking into the barrier fluid past
the primary seal. Restore the
pressure to the reservoir. Check
the air or liquid supply line to
make sure there is pressure and
all valves are open. If the
pumpage is hazardous or toxic,
drain the reservoir and the seal
chamber and replace the barrier
API Piping Plan 53
fluid. Circulation
of Clean Pressurized
Barrier Fluid from Seal to
Reservoir and back to Seal
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 53
Level Loss-Refill
reservoir and monitor
level closely. If rapid loss
occurs a leak is present.
Check all piping and
connections for leaks.
Make sure the drain valve
is closed. Block in the
cooling water. The API Piping Plan 53
cooling coil may have a
Circulation of Clean Pressurized
leak.
Barrier Fluid from Seal to
Reservoir and back to Seal
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Check
Valve
Coalescing
Filter
Ball Valve
9
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and Troubleshooting-
Plan 53 Gas
A high gas panel pressure with typical flow on the
flow meter normally occurs when the regulator on
the panel has been set above the base pressure
reading -adjust the regulator on the gas panel in
the increasing direction. When making the
adjustment, do so slowly to avoid dropping the
panel below the desired base pressure reading
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and Troubleshooting-Plan 53 Gas
High flow readings in excess of 5-6 scfh can be caused by
loose fittings downstream of the flow meter or damage to
the seal faces
The first step is to leak check all fittings down stream of the flow
meter on the gas panel. A very small leak can cause a high flow
reading. If the fittings are leak free, call your maintenance
personnel to troubleshoot the mechanical seal assembly. A high
flow under these conditions usually means the seal is damaged in
some way.
Providing you can maintain the base pressure on the panel and an
elevated leak rate is not affecting process conditions, the pump can
continue to be operated until an orderly shut-down can be executed.
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and External Nitrogen Flow
Pressure Source Meter
Troubleshooting-Plan 53 Gas
No or low gas panel pressure with Pressure Gas Control
typical flow recorded on the flow meter Switch Panel
Pressure P.I.
Partially closed or closed supply valves- Regulator Flow Barrier
check to make sure the supply valves to Switch Inlet
the gas seal panel are fully open
Improperly adjusted regulator-adjust
the regulator toward the increasing Check
pressure direction only to obtain the Valve
Coalescing
baseline pressure. Filter
Variable supply pressure-check to
make sure the supply pressure to the Ball Valve
panel is at normal levels
API Piping
Plan 53 (Gas)
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
External Nitrogen Flow
Preventive Maintenance and Pressure Source Meter
Troubleshooting-Plan 53 Gas
No or low gas panel pressure with Pressure Gas Control
Switch Panel
typical flow recorded on the flow Pressure P.I.
meter Regulator Flow Barrier
Clogged filter element in coalescing Switch Inlet
filter-in the event these attempts
are unsuccessful, decommission the
Check
pump and take the gas panel out of Valve
service and check the coalescing Coalescing
filter. Proceed through the start-up Filter
procedure for the gas panel. If you Ball Valve
are still unsuccessful, contact
maintenance for assistance
API Piping
Plan 53 (Gas)
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
External Nitrogen Flow
Preventive Maintenance and Pressure Source Meter
Troubleshooting-Plan 53 Gas
Pressure Gas Control
A high gas panel pressure with Panel
Switch
typical flow on the flow meter Pressure P.I.
Regulator Flow
normally occurs when the Barrier
Switch Inlet
regulator on the panel has been
set above the base pressure
reading -adjust the regulator on Check
the gas panel in the increasing Valve
Coalescing
direction. When making the Filter
adjustment, do so slowly to avoid
Ball Valve
dropping the panel below the
desired base pressure reading
API Piping
Plan 53 (Gas)
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
External Nitrogen Flow
Preventive Maintenance and Pressure Source Meter
Troubleshooting-Plan 53 Gas
Pressure Gas Control
High flow readings in excess of 5-6 Switch Panel
scfh can be caused by loose fittings Pressure P.I.
Regulator Flow Barrier
downstream of the flow meter or Switch Inlet
damage to the seal faces
The first step is to leak check all fittings
down stream of the flow meter on the Check
gas panel. A very small leak can cause a Valve
high flow reading. If the fittings are leak Coalescing
free, call your maintenance personnel to Filter
troubleshoot the mechanical seal Ball Valve
assembly. A high flow under these
conditions usually means the seal is
damaged in some way.
API Piping
Plan 53 (Gas)
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
External Nitrogen Flow
Preventive Maintenance and Pressure Source Meter
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and
Troubleshooting-Plan 61
Pressure Reading on gauge in flare
line-check for cold line (light
hydrocarbons). Make sure the valve is
open to the flare header. Open the
drain valve to relieve pressure and
observe how quickly the pressure
reading returns. If the pressure builds
quickly (more than 2 psi in 5 minutes),
a seal leak has occurred. If the
pressure builds slowly, this is due to
normal seal leakage. The the flare line API Piping Plan 61
is probably blocked. Vent to Closed Vapor System
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
API Piping Plan 62 Block
Liquid or Gas Quench To Valves
Atmospheric Side of Seal Faces
Pressure Steam or
Regulator Other Gas
Or Liquid
Quench Supply
Connection
Drain Block
Connection Valve
To Drain or Trap
Suitable
Recovery System
1
Installation & Troubleshooting Guidelines
for API Seal Flush Plans
Pressure Regulator
Steam or
Block Other Gas
Quench
Valves Or Liquid
Connection
Block Supply
Wrap Copper Line
Valve
Around Suction or
Discharge Nozzle
and Insulate Trap
Drain To Drain or Suitable
Connection Recovery System
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Line Up Procedure-API Plan 62-Steam Quench Continued
Open the block valve for the steam quench. If a regulator and
gauge are used make sure the gauge shows the proper steam
pressure. If a needle valve is used, open the needle valve until
condensation is observed at the bushing or drain port on the seal
flange. Then start closing the needle valve until steam condensate
can be observed on a cold object (such as channel locks or a
mirror) held near the drain port. Note that it is common to see
some condensation dripping out of the seal flange at this point
since the pump is not up to full operating temperature
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Line Up Procedure-API Plan 62-Steam Quench Continued
Check for leaks around valves, fittings, and the orifice if used in
the quench line
Proceed with opening all valves for service
Start pump per normal procedure
Once running check to make sure the steam quench is still in
operation. Any condensation previously observed should
disappear as the pump comes up to full operating temperature
except for cold service pumps such as caustic service where there
will always be condensate present.
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
Preventive Maintenance and Troubleshooting-Plan 62-Steam
Quench
The steam quench should be checked regularly. If
a pressure gauge is used, it should be checked to
make sure the set point has been maintained.
Steam condensate should be visible on a cold object
held near the drain port.
The typical mode of failure is a clogged orifice, a
defective pressure controller, loss of pressure in the
line, or a closed valve.
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
1
Installation & Troubleshooting
Guidelines for API Seal Flush Plans
General Comment-Steam & Water Quench
The steam or water quench should be put in
service before the pump is put in service. It is not
a good practice to put a quench system in
operation while the pump is running or when it
has been prepared for service. It is possible to
shock a mechanical seal under these conditions
and cause a catastrophic seal failure. The
operator may be put at risk when this event
occurs