Gilgen FD20 Installation Manual
Gilgen FD20 Installation Manual
Gilgen FD20 Installation Manual
FD 20
Mounting and operating instructions
Original
Operator ...............................................................................................................................................
0548-990/02e
2014.12
FD 20 Mounting and operating instructions
TABLE OF CONTENTS
1 GENERAL REMARKS..................................................................................................5
1.1 Target group........................................................................................................5
1.2 Where to keep these instructions.......................................................................5
1.3 Adresses.............................................................................................................5
1.4 Auxiliary tools and service performances...........................................................6
2 SAFETY........................................................................................................................7
2.1 Appropriate use..................................................................................................7
2.2 Safety notices.....................................................................................................7
2.3 Safety regulations...............................................................................................7
2.3.1 Principles...............................................................................................7
2.3.2 Service..................................................................................................9
2.3.3 Safety devices.......................................................................................9
2.3.4 Malfunctions..........................................................................................9
2.3.5 Accessories/Spare parts.......................................................................9
3 PRODUCT DESCRIPTION.........................................................................................10
3.1 General remarks...............................................................................................10
3.2 Standard application......................................................................................... 11
3.3 Inverse application............................................................................................12
3.4 Automatic closing sequence control.................................................................12
3.5 Rating plate.......................................................................................................13
3.6 Technical data...................................................................................................13
3.7 Application limits without safety elements
according to EN 16005.....................................................................................14
3.8 Maximum wind-load capacity............................................................................15
4 MOUNTING................................................................................................................17
4.1 Preparation.......................................................................................................17
4.2 Mounting versions.............................................................................................18
4.3 General.............................................................................................................19
4.4 Normal rods pushing function / Lintel mounting................................................20
4.5 Sliding rods pulling function / Lintel mounting...................................................23
4.6 Sliding rods pushing function / Lintel mounting................................................25
4.7 Sliding rods pushing function / Leaf mounting..................................................27
4.8 Adjusting the pre-stressing of the closing spring..............................................29
4.9 Setting the accelerating function (forceful closing)...........................................31
4.9.1 Accelerating force................................................................................31
4.9.2 Forceful closing range.........................................................................32
5 ELECTRICAL CONNECTIONS..................................................................................33
5.1 Power supply....................................................................................................33
5.2 Cable layout......................................................................................................35
5.2.1 Lintel mounting....................................................................................35
5.2.2 Leaf mounting......................................................................................35
5.2.3 Strain relief..........................................................................................36
5.3 External elements.............................................................................................36
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 2 of 77
FD 20 Mounting and operating instructions
6 COMMISSIONING......................................................................................................37
6.1 Inverse application............................................................................................39
6.2 Closing sequence control.................................................................................40
6.3 Interlock operation............................................................................................43
6.4 Adhesive labels.................................................................................................44
6.4.1 Service sticker.....................................................................................44
6.4.2 Arrow sticker........................................................................................44
6.4.3 Glass sticker........................................................................................44
6.5 Mount the drive unit covering............................................................................45
7 CONTROL..................................................................................................................46
7.1 Main switch.......................................................................................................46
7.2 Program selector..............................................................................................46
7.3 Operating modes..............................................................................................46
7.4 Adjustings.........................................................................................................47
7.4.1 Motional parameters (PARAMETER)..................................................47
7.4.2 Configuration (CONFIG)......................................................................48
7.4.3 Installations with multiple door leaves (DOUBLE DOOR)...................49
7.4.4 Menu navigation..................................................................................50
8 SERVICE....................................................................................................................54
8.1 Service for pedestrian doors.............................................................................55
8.2 Fundamental checking......................................................................................56
9 TROUBLESHOOTING................................................................................................57
9.1 Malfunction with error-no..................................................................................57
9.1.1 Drive mechanism.................................................................................57
9.1.2 Operating.............................................................................................58
9.1.3 Safety elements...................................................................................58
9.1.4 Feeding...............................................................................................58
9.1.5 System................................................................................................59
9.1.6 Options................................................................................................59
9.1.7 Closing sequence / Interlock function..................................................59
9.2 Malfunction without error-no.............................................................................60
9.3 Software update via USB..................................................................................61
9.3.1 Preparation..........................................................................................61
9.3.2 Procedure............................................................................................62
9.3.3. LED display on the control..................................................................62
9.3.4 Possible errors....................................................................................62
10 SHUT-DOWN..............................................................................................................63
12 SPARE PARTS...........................................................................................................65
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 3 of 77
FD 20 Mounting and operating instructions
13 OPTIONS....................................................................................................................66
13.1 D-BEDIX...........................................................................................................66
13.1.1 Keys....................................................................................................66
13.1.2 Symbols...............................................................................................66
13.1.3 Operating modes.................................................................................67
13.1.4 Display of the door position.................................................................67
13.1.5 Menu level...........................................................................................68
13.1.6 Setting examples.................................................................................69
13.1.7 Error display........................................................................................70
13.2 KOMBI-D-BEDIX..............................................................................................71
13.3 Open position stop piece integrated in the drive unit........................................72
13.4 Connection plate for wooden door leaf (normal rods)..........................................72
13.5 Mounting plate..................................................................................................73
13.6 Mounting plate FD 20 Mod...............................................................................73
13.7 Continuous covering.........................................................................................74
13.8 Optional PCBs..................................................................................................75
13.8.1 Relay PCB...........................................................................................75
13.8.2 Radio PCB...........................................................................................76
14 APPENDIX..................................................................................................................77
Wiring diagram........................................................................................... E4-0141-713
Wiring diagram Relay PCB........................................................................ E4-0141-715
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 4 of 77
FD 20 Mounting and operating instructions
1 GENERAL REMARKS
The present instructions contains all instructions for mounting, commissioning, operation,
service (maintenance/checking) as well as troubleshooting. It is the basis guaranteeing
a faultless and safe operation of the installation and must be completely read and under-
stood before starting the work.
Experts are persons who, based on their professional training and experience, have suf-
ficient knowledge in the field of powered windows, doors and gates. They are sufficiently
familiar with the relevant federal regulations for work protection and accident prevention,
with the guidelines and generally recognized rules applicable for this field of technolo-
gy which enables them to evaluate if powered windows, doors and gates can be safely
operated.
Only the trained experts of the manufacturer or the supplier are counted among these
persons.
1.3 Adresses
Distribution agent/
After-sales service
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 5 of 77
FD 20 Mounting and operating instructions
• Company portrait
• Homepage
• E-shop (authorization)
• Solution Designer (the company's own product configuration system)
· Project administration
· Print out quotation and order confirmation for project
· Configuration of installations
· 3D-Visualization
· Calculate prices for normalized and standard doors
· Visualization of lists of parts
· Draw up work drawings
• News
• Info-News via E-mail
• Product brochures
• Product presentation (PowerPoint)
• Submission texts
• Reference list
• Test/homologation certificates
• CAD data
• Application sheets
• Plans of installations and cutouts
• Training courses
• Spare parts
• Maintenance contracts
• Around-the-clock service (not available in all the countries)
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 6 of 77
FD 20 Mounting and operating instructions
2 SAFETY
2.1 Appropriate use
The swing door drive mechanism FD 20 has been exclusively designed for operating
swing doors. Any other use beyond these application limits is deemed inappropriate and
inadmissible! In the event of an inappropriate use of this system, the safety of the user
may be jeopardized and/or the installation be damaged. The manufacturer declines all
responsibility for these injuries/damages!
Warning:
Involving danger to life and limb.
Attention:
A situation where material could be damaged or the function impaired.
Note:
Hints which facilitate the work.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 7 of 77
FD 20 Mounting and operating instructions
• In order not to create any dangerous squeezing and shearing points, no structural mo-
dification must be made within the door surroundings, without prior authorization from
Gilgen Door Systems. Furthermore, it is important that no objects (such as furniture,
pallets, etc.) be placed in the vicinity of the door.
• The door leaves and their fillings must be manufactured according to the applicable
standards (e.g. EN 16005). For the door leaf fillings, brake-proof material respectively
safety glass shall be used. Transparents door leaves (or their surfaces) must be clearly
recognizable, e.g. by means of a permanent marking or dyed materials.
• Door sills or other protruding elements of the door system are to be identified by war-
ning stickers or another appropriate marking means.
• In its assembled state, the installation must answer all the safety requirements specified
by the machinery directive.
• The swing door drive mechanism FD 20 may only be installed and operated in dry
rooms. If this condition cannot be fulfilled, the customer must provide sufficient protec-
tion from moisture.
• The swing door drive mechanism FD 20 must not be mounted within locations pre-
senting explosion hazards. The presence of flammable gases or smoke represents a
considerable safety hazard.
• All further interventions on and modifications of the installation that are not described in
the present instructions are forbidden!
• Wrapping materials (such as plastic foil, polystyrene foam, strings, ....) represent a
source of danger for children and must therefore be kept out of reach of the latter.
• The installation has been calculated, designed and manufactured on the basis of the
latest state-of-the-art technology and the generally recognized safety-relevant rules and
regulations. It may only be operated if it is in perfect condition, taking into account the
specifications of the present instructions. Any use beyond the defined application limits
is inadmissible!
• The installation is to be operated and maintained in such condition that the safety is
guaranteed at all times. An integral part of this condition is the appropriate use, the
compliance with the operating conditions prescribed by the manufacturer, as well as the
regular service (maintenance/checking).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 8 of 77
FD 20 Mounting and operating instructions
2.3.2 Service
In order to guarantee the safety of the users at all times, the installation must be checked
with regard to its safe condition before the first commissioning and during normal operati-
on, at least once a year, by a expert. The correct maintenance/checking must be confir-
med by entering the date and signature into the control booklet.
It is inadmissible to bypass, shunt or disable the safety devices. Any defective safety devi-
ces may not be disconnected in order to be able to continue the operation of the installa-
tion.
2.3.4 Malfunctions
If any malfunctions occur which might be detrimental to the safety of the users, the instal-
lation must be immediately taken out of operation. It may only be taken back into operati-
on after the malfunction has been repaired and all danger eliminated.
A safe and reliable function of the installation can only be guaranteed if it is operated with
the original Gilgen Door Systems accessories/spare parts. Gilgen Door Systems declines
all responsibility for damages resulting from unauthorized modifications of the installation
or from the use of foreign accessories/spare parts.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 9 of 77
FD 20 Mounting and operating instructions
3 PRODUCT DESCRIPTION
3.1 General remarks
The swing door drive mechanism FD 20 opens and closes the door leaf via a rod assem-
bly (is not shown in the illustration).
A
C B
D
E
F
G
B
H I
Drive mechanism
A Drive mechanism covering
B Side cover
C Spring unit for spring-powered closing respectively opening
D Direct current motor
E Gear
F Output shaft with eight-pointed star for the connection of the rod assembly
G Control
H Main switch
I Program selector keys
Control PCB J K L M N O P
J Connection program selector
K Connection terminals Q
X109
M CAN R
X114
X101
X115 X117 5V
N Processor
O Options connection S
X113
LED
5 V green = i.O.
30 V green = i.O.
SOK System green flashing = i.O.
OE Opening element blue = activ
SE Safety element yellow = activ
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 10 of 77
FD 20 Mounting and operating instructions
Normal rods
A B
C
E
D
Sliding rods
A B
G
F
A Clamping piece
B Rotating arm
C Joint
D Rod arms
E Door connection angle
F Glider
G Sliding rail
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 11 of 77
FD 20 Mounting and operating instructions
During normal operation, the opening and closing movements of the door leaf are moto-
rized. The automatically opening is performed via opening elements. The automatically
closing starts as soon as the programmed hold-open time has expired.
Attention:
For the Inverse application we advise to use an electric lock which maintains
the door leaf in the closed position. Without this electric lock, the drive unit
needs to apply a continuous closing pressure and push the leaf against the
spring power (at the cost of increased power consumption). An initial load is
acting on the electric load (spring power of the drive unit). For this reason (in
contrast to the fire protection application), the electric lock to be used must
be suitable for escape way applications (opening without mains power). The
starting delay TDelay must be > 0 s and the relieving force during unlocking
FDelay must be adjusted in accordance.
Attention:
If nothing but an impulse command is used for triggering the Inverse func-
tion, a maintained command is required (e.g. fire protection PCB FD 20-F).
Drive mechanism 1
Master
Drive mechanism 2
Slave
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 12 of 77
FD 20 Mounting and operating instructions
Rating plate
Adhesive tape
transparent
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 13 of 77
FD 20 Mounting and operating instructions
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 14 of 77
FD 20 Mounting and operating instructions
2500
2400
80
60
70
50
45
2300
40
km
k
km
km
k
m/
km
m/
/h
/h
/h
h(
2200
h(
/h
(3
(
18
245
12
10
(
20
80
0P
5P
0P
2100
Pa)
Pa)
Pa
a)
a)
a)
)
2000
800 900 1000 1100 1200 1300 1400 1500 1600
Clearance width in mm
2500
2400
45
50
2300
35
55
30
40
km
km
km
km
km
km
/h (
2200
/h
/h
/h
/h
/h
(
1
60 0Pa)
(
12
(
(6
(
45
00
150
80
(18
2100
0P
5P
km
Pa
Pa)
Pa
Pa)
a)
/h
a)
)
)
2000
800 900 1000 1100 1200 1300 1400 1500 1600
Clearance width in mm
2500
2400
55
2300
60
50
65
45
km
40
35
km
km
k
k
m/
km
km
2200
/h
/h
/h
/h
h(
/h
/h
(
(21
15
(1
12
180
(8
(6
2100
00
0P
0P
0P
0P
Pa
Pa
a)
Pa)
a)
a)
a)
)
)
2000
800 900 1000 1100 1200 1300 1400 1500 1600
Clearance width in mm
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 15 of 77
FD 20 Mounting and operating instructions
2500
2400
50
45
2300
30
40
35
25
k
km
km
km
m/
km
km
2200
/h
h(
/h
/h (
/h
/h
(
10
125
(4
(
(
80
60
30
55 50 Pa
2100
5P
0P
(1
km )
Pa
P
Pa)
Pa
a)
a)
a)
/h
)
2000
800 900 1000 1100 1200 1300 1400 1500 1600
Clearance width in mm
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 16 of 77
FD 20 Mounting and operating instructions
4 MOUNTING
4.1 Preparation
Attention:
Standard application
It is recommended that a door leaf stop piece be mounted by the customer.
Inverse application
It is imperative for the customer to install a door leaf stop piece!
This stop piece prevents the door leaf from being damaged in the manual
operating mode. As an option, an open position stop piece can be integrated
into the drive unit itself.
Attention:
The motor connector plug must be re-connected in the control unit, accor-
ding to the respective mounting version (Y = standard see chapter 4.2
Mounting versions). This in order to ensure the cushioning function.
C
B
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 17 of 77
FD 20 Mounting and operating instructions
Normal rods 0548-104 pushing function Normal rods 0548-104 pushing function
0548-104/01 KTL push. funct. 0548-104/01 KTL push. funct.
Lintel mounting see chapter 4.4 Lintel mounting see chapter 4.4
Lintel depth 0...250 mm Lintel depth 0...250 mm
Drive mechanism 0548-010 alu / 0548-011 inox Drive mechanism 0548-010 alu / 0548-011 inox
Motor connector plug Standard Y, Inverse X Motor connector plug Standard Y, Inverse X
see chapter 4.1 see chapter 4.1
Sliding rods 0548-105 pulling function Sliding rods 0548-105 pulling function
0548-105/01 KTL pull. function 0548-105/01 KTL pull. function
Lintel mounting see chapter 4.5 Lintel mounting see chapter 4.5
Lintel depth +150/-30 mm Lintel depth +150/-30 mm
Drive mechanism 0548-010 alu / 0548-011 inox Drive mechanism 0548-010 alu / 0548-011 inox
Motor connector plug Standard X, Inverse Y Motor connector plug Standard X, Inverse Y
see chapter 4.1 see chapter 4.1
Sliding rods 0548-105 pushing function Sliding rods 0548-105 pushing function
0548-105/01 KTL push. funct. 0548-105/01 KTL push. funct.
Lintel mounting see chapter 4.6 Lintel mounting see chapter 4.6
Lintel depth +150/-30 mm Lintel depth +150/-30 mm
Drive mechanism 0548-010 alu / 0548-011 inox Drive mechanism 0548-010 alu / 0548-011 inox
Motor connector plug Standard Y, Inverse X Motor connector plug Standard Y, Inverse X
see chapter 4.1 see chapter 4.1
Sliding rods 0548-105/02 pushing function Sliding rods 0548-105/02 pushing function
incl. sliding rail 830 mm incl. sliding rail 830 mm
Leaf mounting see chapter 4.7 Leaf mounting see chapter 4.7
Lintel depth +150/-30 mm Lintel depth +150/-30 mm
Drive mechanism 0548-010 alu / 0548-011 inox Drive mechanism 0548-010 alu / 0548-011 inox
Motor connector plug Standard Y, Inverse X Motor connector plug Standard Y, Inverse X
see chapter 4.1 see chapter 4.1
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 18 of 77
FD 20 Mounting and operating instructions
4.3 General
Warning:
The fastening bases must provide sufficient solidity. If necessary they have
to be reinforced by the appropriate means.
Attention:
The maximum admissible undulation of the fastening base is 1 mm. The
drive unit must be fastened without torsion and perpendicularly, using all the
six fixing holes!
Warning:
Tighten all the six M6 fixing screws (A) with a torque of 10 Nm!
A A A
A A A
Note:
Depending on the assembly situation of the drive unit, it may be advisable
to install the program selector on the opposite side (in order to guarantee an
optimal operating facility). Should this be required, the work must be carried
out according to chapter "Electrical connections".
Note:
In cases where it is planned to integrate an open position stop piece into the
drive unit (option), this stop piece must be mounted prior to the rod assembly
(see instructions for option).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 19 of 77
FD 20 Mounting and operating instructions
Procedure:
1. Mark out and drill the fastening holes on the lintel and the door leaf.
650
Chassis profile
424
Lower edge door frame
217
With clamping piece standard
17*
M6
76
* variable 10...22 mm
** adjust the dimensions accordin-
gly
36**
358 45
53
Lintel depth
689 0...250 ~398
103**
95
170
75
45
60 Clamping piece
standard
280 100
60
120
Options
0548-124 clamping piece -13 mm
0548-125 clamping piece +20 mm
0548-126 clamping piece +50 mm
adjust the dimensions accordingly
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 20 of 77
FD 20 Mounting and operating instructions
6. Position the lever arm (D) including the clamping 5. Fasten the rod arm (B) by means of the door
piece (C) perpendicularly with regard to the door connection angle (A) onto the door leaf.
leaf and screw the lever arm (D) down in this
position. 6. Completely open the door leaf (max. 110°).
forward to chapter 4.8 10. Position the rod arm (B) perpendicularly with
regard to the door leaf. Fasten the rod arm (B) by
means of the screw (F).
forward to page 22
Attention:
Check the motional sequence of the door leaf: The rods must not touch. If
the rod arm (B) juts out too much, it can be shortened if necessary.
320
C
27
43,5
74,5
36,5
A B D E
29 22 F
592
°
90
B
D B
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 21 of 77
FD 20 Mounting and operating instructions
Inverse application
A B C
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 22 of 77
FD 20 Mounting and operating instructions
Procedure:
1. Mark out and drill the fastening holes on the lintel and the door leaf.
Note:
The illustration shows a 38 mm sliding bolt. Depending on the situation, this
bolt can be replaced by the version 14 mm. This will change the respective
dimensions by minus 24 mm.
650
424 Chassis profile
217 Upper edge door leaf
standard
* variable 51...73 mm
56*
M6
** adjust the dimensions
accordingly
140
30**
420
700
Lintel depth
689 +150/-30
Clamping piece
standard
95
142**
Sliding bolt
185
38 mm
90
12**
110 620
26
280
60
Options
120
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 23 of 77
FD 20 Mounting and operating instructions
5. While mounting the drive unit, push the lever 6. Completely open the door leaf (max. 115°).
arm (B) back by the pre-stressing angle of 15°.
7. Insert glider (C) into guide profile (G) and screw
6. Push the guide profile (G) over the glider (C) and down the lever arm (B) on the drive unit.
hook it into the mounting profile (E).
8. Snap in the covering caps (D) on both sides.
7. On both sides insert and screw down the expansi-
on element (F) with 1,5 Nm. back to page 22
Attention:
Check the motional sequence of the door leaf:
The rods must not touch. If the glider (C) makes screeching noises, it needs
to be lubricated wih a little WD40.
G
E
F
1,5 Nm
H D
15°
400
27
76,5 / 52,5
89,5 / 65,5
D F A B C D EFC G
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 24 of 77
FD 20 Mounting and operating instructions
Procedure:
1. Mark out and drill the fastening holes on the lintel and the door leaf.
Note:
The illustration shows the 14 mm sliding bolt. Depending on the situation,
this bolt can be replaced by the version 38 mm. This will change the respec-
tive dimensions by plus 24 mm.
650
424 Chassis profile
217 Lower edge door frame
M6 standard
* variable 10...18 mm
62
700
Lintel depth
Clamping piece
689 +150/-30
standard
Sliding bolt
103**
14 mm
95
161
66
12**
110 620
26
280
60
120
Options
0548-124 clamping piece -13 mm
0548-125 clamping piece +20 mm
0548-126 clamping piece +50 mm
adjust the dimensions accordingly
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 25 of 77
FD 20 Mounting and operating instructions
6. Push the guide profile (G) over the glider (C) and 5. Hook the guide profile (G) into the mounting pro-
hook it into the mounting profile (E). file (E), on both sides insert and screw down (with
1,5 Nm) the expansion element (F).
7. On both sides insert and screw down (with
1,5 Nm) the expansion element (F). 6. Completely open the door leaf (max. 115°).
8. Snap in the covering caps (D) on both sides. 7. Insert glider (C) into guide profile (G) and screw
down the lever arm (B) on the drive unit.
forward to chapter 4.8
8. Snap in the covering caps (D) on both sides.
back to page 22
Attention:
Check the motional sequence of the door leaf:
The rods must not touch. If the glider (C) makes screeching noises, it needs
to be lubricated wih a little WD40.
G
E
F
1,5 Nm
B D
400
A B C D E FC G
52,5 / 76,5
27
65,5 / 89,5
D F
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 26 of 77
FD 20 Mounting and operating instructions
Procedure:
1. Mark out and drill the fastening holes on the lintel and the door leaf.
Note:
The illustration shows the 14 mm sliding bolt. Depending on the situation,
this bolt can be replaced by the version 38 mm. This will change the respec-
tive dimensions by plus 24 mm.
standard
* variable 10...18 mm
21*
76
M6
** adjust the dimensions
317 accordingly
524 Chassis profile
750
Lintel depth
Sliding bolt +150/-30
14 mm
100 830
Clamping piece
standard
26
66
161
8**
106**
95
689
60
120
380 Options
0548-124 clamping piece -13 mm
0548-125 clamping piece +20 mm
0548-126 clamping piece +50 mm
adjust the dimensions accordingly
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 27 of 77
FD 20 Mounting and operating instructions
5. Screw down the lever arm (B) parallel to the drive unit.
6. Push the guide profile (G) over the glider (C) and hook it into the mounting profile (E).
7. On both sides insert and screw down (with 1,5 Nm) the expansion element (F).
Attention:
Check the motional sequence of the door leaf:
The rods must not touch. If the glider (C) makes screeching noises, it needs
to be lubricated wih a little WD40.
G
E
F
1,5 Nm
D
500
A B C D E FC G
52,5 / 76,5
27
65,5 / 89,5
D F
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 28 of 77
FD 20 Mounting and operating instructions
Note:
The correct pre-stressing of the closing spring must imperatively be adjusted
before carrying out the automatic setting-up procedure! The setting values are
only mandatory for fire-protection and/or escape way doors. As a general rule,
the closing spring force can be reduced when setting the standard drive unit.
A possibly existing door lock must be correctly engaged to lock the leaf.
Otherwise: adapt the pre-stressing of the closing spring accordingly.
Attention:
The setting screw needs to be shortened by 10 mm if it butts against the side
cover's protection against accidental contact (with program selector key).
Procedure:
2. Using the setting screw, adjust the measure X* in function of the respective situation.
3. Open the door leaf by at least 60° and then let it be closed.
Program selector
further away from the door hinges
Closing spring
Adjusting screw
X*
* Measure X is an approximated value for a lintel depth of 0 mm. The force necessary for manually opening a
door must not exceed 150 N. This effort shall be measured as a static force on the main closing edge (per-
pendicularly to the door leaf), at a height of 1'000 mm ±10 mm.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 29 of 77
FD 20 Mounting and operating instructions
Inverse application
EN class EN 3 EN 4 EN 5 EN 6 EN 7
Width of door leaf 950 mm 1'100 mm 1'250 mm 1'400 mm 1'600 mm
Normal rods
Measure X * 40 mm 36 mm 31 mm 27 mm 23 mm
Sliding rods pulling function
Measure X * 38 mm 34 mm 29 mm 23 mm 20 mm
Sliding rods pushing function
Measure X * 36 mm 33 mm 27 mm 20 mm 17 mm
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 30 of 77
FD 20 Mounting and operating instructions
While an installation is in the state “without mains power” or in the operating mode MAN-
UAL, the motor acts as an attenuator, thus guaranteeing a constant closing speed until
the Closed position is reached.
To make sure that, when switched to the de-energized state or in the operating mode
MANUAL, the door leaf is reliably engaged by the door lock, the drive unit is equipped
with a door slam function (acceleration causing a forceful closing). By means of the
potentiometer, the motor attenuation (shortly before the door leaf reaches the closed posi-
tion) can be adjusted so that the pressure spring will have sufficient power for pushing the
door leaf safely into the door lock.
Procedure:
2. Should the door leaf fail to engage in the lock, adjust the door slam cushioning by
means of the potentiometer (provided on the control unit).
Warning:
In de-energized state or in the operating mode MANUAL, the closing pro-
cedure must last at least 3 seconds (from the open position 90° up to the
closed position 0°).
Adjusting trimmer
Forceful closing
max. min.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 31 of 77
FD 20 Mounting and operating instructions
Upon delivery from the factory, the activation of the accelerating function (forceful closing)
is pre-set (i.e. it intervenes approx. 5° before reaching the closed position). Under normal
conditions, it will not be necessary to change the default setting! However, in cases where
in the de-energized state or in the operating mode MANUAL the door leaf fails to be
reliably engaged in the door lock, the activation point of the accelerating function (forceful
closing) can be shifted (by means of a continuously adjustable cam disk).
Note:
The setting range is between 5 and 15° of the door opening angle.
Procedure:
1. Using a screwdriver, carefully prize the service cover (C) out of the gearbox housing.
2. By means of a socket wrench 1,5 mm, slightly loosen the locking screw (B), then
carefully turn the cam disk (A) to the left or to the right.
4. Open the door leaf by about 45° and then let it be closed. Check whether the door
leaf is correctly pushed into the door lock.
A B C
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 32 of 77
FD 20 Mounting and operating instructions
5 ELECTRICAL CONNECTIONS
5.1 Power supply
Warning:
Before working on the drive unit, make sure that the mains cable is voltage-
free! The mains supply line including mains plug (with respective protection)
has to be provided by customers.
The mains supply cable 230 VAC must imperatively be routed below the
chassis profile, whereas the cables of the control and safety elements can
be routed within the drive unit.
Procedure:
2. Connect the mains supply cable as illustrated (see also wiring diagram E4-0141-713
in the appendix).
Program selector
closer to the door hinges.
PE
L'
N'
L
Strain relief
0548-128
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 33 of 77
FD 20 Mounting and operating instructions
Cable layout
PE L' N'
Mains cable
Chassis profile 3 x 1,5 mm2
Program selector
further away from the door hinges
N
L
PE N'
L' L'
N'
PE
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 34 of 77
FD 20 Mounting and operating instructions
670
28 (614) 28
22
47
22
5.2.2 Leaf mounting
Socket by customers
Option
Flexible power supply system
0548-209
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 35 of 77
FD 20 Mounting and operating instructions
Attention:
For flexibly conducted cables, the drive-internal strain relief feature 0548-128
and a bushing socket must be installed in the side cover cutout!
0548-128
M4 x 6
0548-399
Cable clamp
2. Lead the cables of the elements up to the drive unit (by customers).
3. Connect the cables according to the diagram E4-0141-713 (in the appendix).
Note:
If an electric lock is provided, its connection rating is 24 VDC and max. 0,8 A
(or 24 VAC/1,5 A by customers). It should be designed for a duty cycle of
100 %. The electric lock locks the door leaf in the desired operating modes
and is configurable.
Attention:
For the Inverse application we advise to use an electric lock which maintains
the door leaf in the closed position. Without this electric lock, the drive unit
needs to apply a continuous closing pressure and push the leaf against the
spring power (at the cost of increased power consumption). An initial load is
acting on the electric load (spring power of the drive unit). For this reason (in
contrast to the fire protection application), the electric lock to be used must
be suitable for escape way applications (opening without mains power). The
starting delay TDelay must be > 0 s and the relieving force during unlocking
FDelay must be adjusted in accordance.
Attention:
If nothing but an impulse command is used for triggering the Inverse func-
tion, a maintained command is required (e.g. fire protection PCB FD 20-F).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 36 of 77
FD 20 Mounting and operating instructions
6 COMMISSIONING
Warning:
During the setting-up procedure (which must only be carried out by experts),
the safety devices (radar, sensors, ...) are switched off!
Before initiating the setting-up procedure, it is important to make sure that
neither persons nor objects remain within the danger area of the moving
door leaf, in order to avoid injuries or damages!
Attention:
Make sure that the motor connector plug has been correctly plugged into the
control unit (see chapter 4.1 and 4.2).
Joystick
Procedure:
2. Using the joystick, adjust the display direction: Move the joy-
stick downward once the display direction is switched to a
Press
readable position. Down
3. Programming the type of rod assembly Rod:
Move the joystick to the left/to the right (see parameter chapter Rod
7.4). STD-PH
Validate the correct type of rod assembly by means of OK: In
the rest position, shortly push in the joystick.
dAxis dAxis
+ – + –
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 37 of 77
FD 20 Mounting and operating instructions
Note:
A renewed setting-up procedure (Teach) is required if:
• the spring tension has been changed
• the leaf weight has been changed
• the type of rod assembly has been changed
• the opening angle Ao has been changed
• the Teach has been obstructed before reaching an opening angle of 20°
• the distance between axles (dAxis) has been changed
• the parameter Invers has been changed.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 38 of 77
FD 20 Mounting and operating instructions
Attention:
If nothing but an impulse command is used for triggering the Inverse func-
tion, a maintained command is required (e.g. fire protection PCB FD 20-F).
Software configuration:
• Activate the parameter Inverse.
Attention: the motor connector must not be plugged in the same manner as for the stan-
dard drive unit.
• The electric lock must be unlocked without mains power or powered by an external
source.
• For installations without an electric lock, the interlocking force Fch must be program-
med.
• If there is no electric lock and the interlocking force Fch is not adjusted, error 14/02 will
be displayed as a warning after the teach-in procedure. This means that the door leaf
will endlessly re-open.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 39 of 77
FD 20 Mounting and operating instructions
Drive mechanism 1
Master
Drive mechanism 2
Slave
Connections:
Opening elements (KE, OEO and OEI) connected to Master only act upon the Master
(single leaf operation). Opening elements connected to Slave act upon the Master as well
as on the Slave (bi-parting operation).
The safety elements SER and SES are connected to the respective drive unit.
An active EMCY element connected to the Master carries out the EMY-IN action configu-
red on the Master (for both door leaves). An active EMCY element connected to the Slave
switches the latter to the spring-powered operation.
An electric lock, which locks the Master leaf, is connected to the Master. Accordingly, an
electric lock, which locks the Slave leaf, is connected on the Slave.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 40 of 77
FD 20 Mounting and operating instructions
Function:
The first door leaf to be put in motion for the opening procedure is the Master; by means
of DubleD, this leaf is configured as MastrA. Its partner is the Slave, which is configured
as SlaveA by means of DubleD.
In the event of an existing CAN connection, the Master is identified by a small black (m)
and the Slave by a small black (s). If however there is no connection, this is indicated by
a small white (m) respectively a small white (s).
The parameter settings for the Master and the Slaves are entirely independent from each
other. It is thus possible to select a Vo = 4 for the Master and a Vo = 5 for the Slave.
In order to guarantee a collision-free opening of both door leaves, the Slave leaf lets the
Master leaf go ahead and initiate the opening. This time lag can be defined on the Slave
by means of AoSeq. The default value of AoSeq is 20°, which is sufficient for most of the
bi-parting installations. This means that the Slave only starts to open after the Master has
exceeded an opening angle of 20°.
From then on, it is admissible for the Slave to catch up with and pass the Master if this
should be required. This is done by configuring a higher Vo value for the Slave than the
one for the Master.
In cases where (due to an electric lock connected to the Master) TDelay of the Master is
configured with a higher value than 0,0 s, then the angle between the Slave and the Mas-
ter is accordingly increased. To compensate this, AoSeq can be reduced in accordance.
An AoSeq value of 0° means that both door leaves will be simultaneously opened, i.e.
that no opening delay is active.
The default value of AcSeq is 20° and thus sufficient for the majority of bi-parting installa-
tions. In cases where a mechanical closing sequence regulator is used with a mechanical
closing delay of e.g. 90°, AcSeq must be programmed with a value of 90° or more.
AcSeq 20° means: The Master only starts closing as soon as the Slave has gained a lead
of 20°. This advance guarantees that the Master will be closed in one go (without intermit-
tence), which results in an optically pleasing closing motion.
The Master is allowed to overtake the Slave. 20° (value AcSeq) before reaching the
closed position, the Master checks whether the Slave is already closed. If not, the Master
will perform an intermediate stop in order to prevent a collision.
An active SES signal on a door leaf causes a safety stop of both door leaves. The same
applies for the SER signal. An active SER signal causes both door leaves to reverse their
motion.
A bi-parting installation can be operated in the single-leaf mode. An active EMCY signal
on the Slave programs the closing sequence as a single-leaf configuration.
If only the EMCY signal on the Master is active, then this EMCY signal is applicable for
both door leaves. In accordance with the action configured on the Master by means of
EMY-IN, both door leaves carry out a CL-SPR (Close Spring), STOP, OPEN or CL-MOT
(Close Motor).
If only the EMCY signal on the Slave is active, then the Slave carries out a CL-SPR,
regardless of the action configured on the Slave by means of EMY-IN.
If both EMCY signals are active, then the Master performs its configured EMY-IN action
and the Slave performs a CL-SPR. One exception of this rule is the Master in the EMY-IN
configuration OPEN. In this case, both door leaves will be opened.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 41 of 77
FD 20 Mounting and operating instructions
Procedure:
1. Connect both control units by means of the CAN cable 0383-194/07 (by plugging it
into the socket X117).
Note:
The respective control and safety elements are connected to the corre-
sponding drive unit.
2. Take the Master drive unit into operation (see chapter 6).
3. For the Master drive unit: Select the operating mode OPEN.
4. Take the Slave drive unit into operation (see chapter 6).
Note:
In cases where a mechanical closing sequence regulator is used, start with a
AcSeq of 90°; afterwards AcSeq can be reduced.
Control:
1. Check the display of the Master control unit to see if a small black (m) is visible on
the first level (connection existing). On the display of the Slave control unit, a small
black (s) must be visible.
Note:
A small white (m) resp. (s) indicates: missing connection.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 42 of 77
FD 20 Mounting and operating instructions
Note:
Both installations must be Exterior side
plugged into resp. out of the
same power supply. Side A
Control:
1. Check the display of the Master control unit to see if a small black (w) is visible on
the first level (connection existing).
Note:
A small white (w) indicates: Missing connection.
Note:
The parameters ILAuto, ILExit and ILNigt enable you to configure the opera-
ting modes in which the interlock system shall be active.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 43 of 77
FD 20 Mounting and operating instructions
2 3 4
9 10
.......
30
2. Stick the monthly sticker onto the ser- Monthly
60
vice sticker, turning the monthly sticker
8
sticker 6 7
5
until the checking date matches the 0632-453
arrow. nŠchster Service 0632-453a
next Service
45-0460-816
3. Using a water-proof felt tip pen, enter prochain service
Zulässige Längenmass (mm)
prossimo Winkel
servizio
Koordinaten- Kanten-
Merkmals-
the year of the next checkup on the
Toleranzen nicht Kürzerer Schenkel masse bruch
0,5 >6 >30 >120 >400 >1000 >2000
–2000 proximo servicio klassifizierung
tolerierten Masse
–6,0 –30 –120 –400 –1000 ≤50 >50 45°
monthly sticker.
mittel ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 ±1,2 ±2 ±1° ±30' ±0,15 0,3±0,2
(k) = kritisch
grob ±0,3 ±0,5 ±0,8 ±1 ±1,5 ±2 ±3 ±1°30' ±1° ±0,25 entgratet
Sondertol. (w) = wichtig
3
–6,0 –30 –120 –400 –1000 –2000 ≤50 >50 45°
R
mittel ±0,1 ±0,2 ±0,3 ±0,5 ±0,8 ±1,2 ±2 ±1° ±30' ±0,15 0,3±0,2
(k) = kritisc
grob ±0,3 ±0,5 ±0,8 ±1 ±1,5 ±2 ±3 ±1°30' ±1° ±0,25 entgratet
(w) = wichti
1. For transparent door leaves or door leaf
Material: PVC-Folie Sondertol.
Farbe Schrift:
Farbe Untergrund: schwarz
weiss
Lieferform:
Farbe Schrift: einzeln
schwarz
80 mm
Träger/Abziehbarkeit:
Lieferform: gestanzt,
einzeln geschlitzt
6.4.3 Glass sticker Besonderes:
Material:
Träger/Abziehbarkeit: Haftgrund:
PVC-Folie
gestanzt, geschlitzt
Glas
Klebstoff: permanent
Oberfläche: glänzend
Farbe Untergrund: Pantone 115 C
1. Attach the glass sticker onto the degre- Farbe Schrift: weiss (Standard)
Farbe Pfeile: Pantone 425 C
ased surface of the
1 door 1 leaves (outside Lieferform: einzeln
Träger/Abziehbarkeit: gestanzt, geschlitzt 34 mm
at the bottom, near the closing edge).
Pos. Menge1 Einh. Sachnummer
1 Besonderes: beidseitig bedruckt
Benennung
Steinhof PrintMedia AG, Burgdorf (SPM)
© Gilgen Door Systems AG, Schwarzenburg
I Änd.-Nr.
Pos. Mengegeprüft F I
Einh. Sachnummer Änd.-Nr. geprüft
Benennung F Ursprung:
Erstellt: Ursprun
© Gilgen Door Systems AG, Schwarzenburg
Erstellt: Massstab
24.08.95 PG
I Änd.-Nr. Geändert F I Änd.-Nr. Geändert F
05.05.11 SPM
a 11783
I Änd.-Nr. geprüft kcdb
28.04.11
a 5624
8230
e0460-787
F 14.12.04
I mmcÄnd.-Nr.
f
e
geprüft Geprüft: FErsatz für:Erstellt: 1:1 Urspru
Anz. Geprüft:
c 9881 14.08.08 hdg g
05.05.11 kcd B4-4436-337 c
18.04.13 PG Ersatz f
b a f e Freigegeben: Blatt: Blatt-Nr.
d 11777 19.04.11 kcd
Ohne sep. Stückliste Nr. 1
h
Anlage
05.05.11 kea 1
Geprüft:
Auftrags-Nr.
17.06.11
1
B-Kl.
kcd Ersatz
c b g f
Sep. Stückliste gleicher Nr. 2
1 U
Sep. Stückliste anderer Nr. 3 Freigegeben: 29.04.13 tj Anz. Bl
Benennung Zeichnungs-Nr.
d c h g
Glaskleber mit Pfeilen Freigegeben:
B4-4436-337 d
17.06.11 kea Anz.1 B
Ohne
d sep. Stückliste 1 © Gilgen Door Systems h
Anlage
129 x 54
SLP - Redundant 1
29.04.13 kea Auftrag
1
AG, CH-3150 Schwarzenburg
Sep.Ohne
Stückliste gleicher Nr. 2 1
sep. Stückliste Anlage Auftrag
Sep.Sep.
Stückliste anderer
Stückliste Nr.Nr.32
gleicher
Sep. Stückliste anderer Nr. 3 Benennung
1 Zeichnu
material: pVC-Folie
Benennung Zeichn
Haftgrund: Glas
Klebstoff: Monats-Kleber
permanent B4-0
Oberfläche: glänzend Service-Kleber B4-0
Farbe Untergrund: transparent
Farbe schrift: weiss
Lieferform: einzeln
Träger/Abziehbarkeit: gestanzt, geschlitzt
Besonderes: steinhof printmedia AG, Burgdorf (spm)
Page 44 of 77
Ohne sep. Stückliste Nr. 1 Anlage Auftrags-Nr. B-Kl.
Sep. Stückliste gleicher Nr. 2
Sep. Stückliste anderer Nr. 3
1 U
Benennung Zeichnungs-Nr.
FD 20 Mounting and operating instructions
Procedure:
1. After cleaning and degreasing the gluing surface, attach the diagram sticker (in the
respective language) to the inside of the covering.
0548-364 Alu
0548-374 Inox
0548-366 Alu
0548-119 Alu
0548-120 Inox
0548-510
0548-365 Alu
0548-375 Inox
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 45 of 77
FD 20 Mounting and operating instructions
7 CONTROL
7.1 Main switch
The drive mechanism is supplied with a built-in A
main switch (A). This main installation switch
enables you to disconnect the power supply
from the drive unit. The door leaf then is closed
from any position by means of spring power
(Invers = spring opening, unless the door leaf
has not been locked). The motor attenuation B
ensures a controlled closing (Invers = opening).
Note:
In the event of a pending fatal error, alle the keys shortly flash up.
AUTOMATIC
Automatic opening via the opening elements inside/outside + Key.
Automatic closing upon expiration of the adjustable hold-open time.
NIGHT
The door leaf can only be opened via the opening element Key (key-operated
siwtch outside).
OPEN
The door leaf is automatically opened and remains in the OPEN position.
MANUAL
The drive mechanism and the control elements are switched off.
The door leaf can be manually opened.
The door leaf is closed by spring power from any position (Invers = spring ope-
ning, unless the door leaf has not been locked).
EXIT
The door leaf can only be opened via the opening elements inside and Key.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 46 of 77
FD 20 Mounting and operating instructions
7.4 Adjustings
Joystick
The parameters can be changed on the Display
control unit by means of the display and scroll
the joystick.
The movements of the joystick have the change
following effects:
• Vertical joystick movement (upward/downward) Scroll through the displayed information.
• Horizontal joystick movement (to the left/to the right) Change the settings.
• Shortly press in the joystick in the rest position Validation OK.
* Note:
A renewed setting-up procedure
Mounting plate (option) (Teach) is required.
dAxis dAxis
+ – + –
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 47 of 77
FD 20 Mounting and operating instructions
1) open 2) open
ASES SES
ive
inact
ASER
SER ina
ctive
closed closed
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 48 of 77
FD 20 Mounting and operating instructions
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 49 of 77
FD 20 Mounting and operating instructions
* Password protected
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 50 of 77
FD 20 Mounting and operating instructions
By means of OK you can switch over from the first to the second level.
For all the menus of the following list, exiting is possible by remaining on the OK key, or
by means of the menu item ESC.
PARAMETER
Setting the motional parameters
• A changed parameter value is shown by a flashing display.
Press OK in order to validate the change.
CONFIG
Setting the functionalities
• A changed parameter value is shown by a flashing display.
Press OK in order to validate the change.
DOUBLE DOOR
Setting the closing sequence and interlock function
• A changed parameter value is indicated by a flashing display.
In order to validate the change, OK must be pressed.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 51 of 77
FD 20 Mounting and operating instructions
DIAGNOSTICS
Diagnostic tools
• K-I-O-R-S-E shows the inputs KEY (K), OEI (I), OEO (O), SER (R), SES (S), EMY (E).
(+) stands for active, (-) for inactive.
• 5.1A 95° shows the motor current and the door opening angle.
• 37°C 25 65 indicates the presently measured temperature in the power electronics,
completed by the minimum and the maximum values. OK causes the minimum and the
maximum values to be reset.
• Simulate Key: OK triggers a Key command.
• E-Lock: L- shows the status of Lock (L). FB- shows the input El-Fb. OK actuates the
electric lock.
L+ resp. FB+ means locked. L- resp. FB- means unlocked.
• HW Version: Version of the Logic PCB.
• SW Version: Version of the Software.
• Cycles: Total number of openings (this value is memorized).
Optional PCBs see chapter 13.8.
ERROR ACTIVE
Pending active errors
• The pending active errors are displayed in a list. This list is updated at the end and the
latest additions appear during the next passage.
A0 indicates the latest error that has occurred.
• Exit the list by pressing OK.
HISTOR ERROR
Formerly active errors
• H0 indicates the latest error that has occurred.
REINIT
Carry out a re-initialization
• PARAM Reset sets all the motional parameters back to the default values (inclusive
opening angle, rod assemblies, Invers and dAxis).
• CONFIG Reset sets all the configuration settings back to the default values.
• DOUBLE Reset sets all the closing sequence and interlock settings back to the default
values.
• FACTOR Reset
The control unit is reset to the delivery configuration programmed by the manufacturer.
This means that all the motional parameters, configurations, closing sequence and
interlock settings are reinitialized with the default settings.
• Reset OK? is validated by means of OK and aborted by any other joystick movement.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 52 of 77
FD 20 Mounting and operating instructions
BLOCK/UNBLOC
Lock/unlock the joystick
• BLOCK
Lock the joystick. For a temporary unlocking, press OK for more than 1 second.
60 seconds after the last joystick actuation, the joystick is automatically relocked.
• UNBLOC
Permanent unlocking of the joystick.
TEACH
Completely close the door leaf. Initiate a setting-up procedure (during the setting-up pro-
cedure the drive unit continues to beep).
• Teach OK? is validated by means of OK and aborted by any other joystick movement.
• The setting-up procedure can be canceled by means of the D-BEDIX (C-key).
Setting of the opening angle (Ao): During the first setting-up run, the drive unit moves to
the open position (Ao) or up to the recommended open position stop piece, whichever
event happens first, and the obtained result is memorized as opening angle. In the event
of an excessively big difference between the actual opening angle and the displayed
angle (in the diagnostic menu), this angle can be corrected (by means of dAxis). If the
difference persists, the installation precision should be checked.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 53 of 77
FD 20 Mounting and operating instructions
8 SERVICE
A regular service (maintenance/checking) is absolutely indispensable in order to gua-
rantee a safe operation and long lifetime of the installation. The service must be carried
out by a expert, at least once a year, according to the following checklist.
This checkup work basically refers to visual and functional checking destined to evalu-
ate the integrality, the condition and the efficiency of the components and safety devices
(checking of the different elements as far as these are included in the installation).
Warning:
To avoid jeopardizing the safety of persons, any defective safety elements
may not be disonnected in order to continue the operation of the installation!
Attention:
In order to guarantee the availability of the installation, any elements show-
ing signs of wear must be replaced as a preventive measure!
Note:
• Every service which has been carried out shall be entered into the control
booklet!
• The following service description refers to the basic components. The opti-
ons are described in detail in chapter "Options".
Attention:
If the fastening screw (A) of
the lever arm is released, this
screw must be secured upon
tightening by means of Locti-
te 243, or else a new original
screw needs to be inserted (see
chapter: Spare parts).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 54 of 77
FD 20 Mounting and operating instructions
Grease
Check
Adjust
Clean
Installation
General condition x
Free door movement (manually) x x
Door guides/guideway rails x x x
Door sealing joints x x x
Side panels/protection leaves x x
Coverings/hinge-type covers x x
Check tight fitting of the screws and nuts x
Clean the installation2 x x
Drive mechanism
Drive mechanism x x x
Holding power in Closed position x
Transmission elements such as:
toothed belt, flat belt, cables, rods or chains x x x
Carrying rollers/counter-pressure rollers/running carriages x x x
Carrier rails x x x
Open/Closed position x x
Control
Electrical connections x
Control functions x x
Program switch (BEDIS, BEDiX, etc.) check all the positions x
Emergency battery x
Emergency opening (pull out both power plugs of the ANTE's)1 x
Control elements
All the existing control elements such as:
sensor, radar, key-operated switch, contact carpet, etc. x x x
Safety elements
Reversing/stopping mechanism x x x
Door locking/manual unlocking mechanism x x x x
Mechanical emergency opening x x
Monitoring switch x x x
Light barrier/Presence detector x x
Existing additional safety elements x x x
Minimum escape way width1 x x
Miscellaneous
Stickers/rating plates x x
1
Only for redundant drive mechanisms.
2
Gilgen Door Systems cleans all the elements of the installation provided this is necessary for the function of
the installation. A general cleaning of the installation is not planned.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 55 of 77
FD 20 Mounting and operating instructions
6. Normal rods:
Connect the rod arm (B) and the rotating arm (A): Snap in the spherical joint (C).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 56 of 77
FD 20 Mounting and operating instructions
9 TROUBLESHOOTING
Warning:
Electrocution hazard! Before working on any live elements, pull out the
mains plug respectively switch off the main installation switch!
If a malfunction occurs which might be detrimental to the safety of the users,
and which cannot be eliminated without delay, the operator must be informed
and if required the installation shall be taken out of operation. The installation
must be repaired as soon as possible.
Note:
Every troubleshooting procedure which is carried out must be entered into
the control booklet!
ror-no.
X109
X112 X104 X102 X116
X106
X114
X101
The error is indicated on the display of X115 X117 5V
the control unit.
X113
Display 30 V
Definition of the column "Reaction".
X105
on.
F Fatal error SE
X103
X110 X108
H Manual operating mode with re-starting attempt
W Warning
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 57 of 77
FD 20 Mounting and operating instructions
9.1.2 Operating
No. Description Cause Elimination Checking time Reaction
E10 01 Fullteach Parameter Ao, Rod, Invers or Carry out a teach. Upon changing the drive H
required dAxis changed. unit configuration.
02 Minimum opening angle has Check the locking/electric lock During Teach H
not been reached.
E11 01 Halfteach requi- Parameter Vo changed. Carry out a complete and unhindered Upon changing the motio- W
red (Opening) opening cycle. nal parameters.
02 Halfteach requi- Parameter Vc or FSlam Carry out a complete and unhindered
red (Closing) changed. closing cycle.
E14 01 Locking/electric The door leaf got caught in the Check the function of the locking/elec- When opening from a H
lock locking/electric lock. tric lock. closed position.
02 The inverted operation has no Program/increase the interlocking force At the end of the teach-in W
locking, or the interlocking force Fch. procedure.
Fch has not been programmed.
E15 01 Obstacle in ope- Too many successive obstac- Examine the installation. H, A
ning direction. les have occured. Remove the obstacle. Permanent. Restart after
Move the door leaf to the target position. 60 s.
02 Obstacle in clo-
sing direction.
E16 01 Temperature Temperature on output level Respect the applicaiton limits. A Drive unit
has reached 81 °C. Permanent. functions with
reduced power.
02 Temperature on output level A Drive unit
has reached 91 °C. has stopped.
9.1.4 Feeding
No. Description Cause Elimination Checking time Reaction
E30 01 30 V Error 30 V too low. Mains failure, overload motor. Check Permanent. A
02 30 V too high. the feed-in. Replace the hardware.
E32 01 24 V Safety Over- resp. under-voltage. Overload, short-circuit safety Elements.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 58 of 77
FD 20 Mounting and operating instructions
9.1.5 System
No. Description Cause Elimination Checking time Reaction
E50 01...99 System error Unexpected hardware or Switch the drive unit off/on. Permanent. W or H or F
E51 01...99 software event. Carry out a Factory Reset, carry out a
Software Update, inform the manufac-
E52 01...99 turer.
9.1.6 Options
No. Description Cause Elimination Checking time Reaction
60 00 Relay PCB 0 Option PCB has been remo- Check if the option is provided. Permanent. W
ved, its address changed or If defective: Replace or remove from the
10 Relay PCB 1 become defective. configuration. Permanent. W
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 59 of 77
FD 20 Mounting and operating instructions
Drive unit fails to react • The program selection keys in Power supply voltage is • Switch on the main installation
• No automatic open- the side cover are not lighted. missing. switch in the side cover.
ing. • LED 5 V (green) on the control • Measure the mains supply voltage,
• No reaction on the is not lighted. check its cabling and eliminate any
control elements detected deficiencies.
(side cover/ • Should the two above-mentioned
D-Bedix). measures not be successful, the
control unit needs to be replaced.
Drive unit fails to • LED SE (safety element, yellow) One or more safety • Remove the obstacle.
open. is lit. elements are active or • Check the cabling between the
• Determine the active safety incorrectly cabled. safety element and the control unit,
element via the diagnostic level. and eliminate any detected deficien-
cies.
• Replace the safety element.
• LED SE (safety element, yellow) Depending on the • Change the operating mode.
is not lighted. enabled operating mode, • Correct the cabling of the opening
• LED OE (opening command, the opening commands elements.
blue) reacts to the opening (inside/outside, etc.) are
element. ignored.
• Determine the opening element
via the diagnostic level.
• LED SE (safety element, yellow) The opening ocmmand is • Check the cabling between the
is not lighted. not evaluated. opening element and the control unit
• LED OE (opening command, and eliminate any detected deficien-
blue) is not lighted despite the cies.
active opening element. • Replace the opening element.
Drive unit fails to • LED SE (safety element, yellow) One or more safety • Remove the obstacle.
close. is lit. elements are active or • Check the cabling between the safety
incorrectly cabled. element and the control unit and
eliminate any detected deficiencies.
• Replace the safety element.
• LED SE (safety element, yellow) An opening command is • Check the cabling between the open-
is not lighted. pending. ing element and the control unit and
• LED OE (opening command, eliminate any detected deficiencies.
blue) is lit. • Replace the opening element.
• Check the operating mode. The operating mode • Change the operating mode.
OPEN is active.
The operating mode • The program selection keys in The ribbon cable is not • Check the ribbon cable and elimi-
cannot be changed. the side cover are not lighted. plugged in correctly, or nate any detected deficiencies.
not plugged in at all.
• The operating mode symbol on The operating mode is • Change the operating mode by means
the display is underlined. overridden via connection of the external program selector switch.
terminal X110. • Correct the cabling of the external
program selector switch.
Prior to commission- The motor connector plug • Plug the motor connector plug into
ing: During manual is not correctly connected. the correct socket, in accordance
opening, the door leaf with the application (pulling/pushing
encounters an impor- function) (see chapter 4.1; Default
tant resistance and setting = pushing function).
closes at high speed.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 60 of 77
FD 20 Mounting and operating instructions
Note:
Not all the USB memory sticks can be used. We thus recommend a previous
testing of their function together with the FD 20.
9.3.1 Preparation
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 61 of 77
FD 20 Mounting and operating instructions
9.3.2 Procedure
X109
X112 X104 X102 X116 X106
X114
X101
X115 X117 5V
switch on the FD 20.
X113
30 V
2. Plug the USB stick into the con-
X105
trol unit socket X118. X118 SOK
OE
X107
SE
X103
3. Switch on the main installations X110 X108
The display of the functions is ensured via three LEDs on the control PCB:
SOK Green USB-Loader started
OE Blue Activity in progress (delete/write memory)
SOK + OE Green/Blue Download completed remove the stick
SE Yellow Error
• Invalid file
Not encrypted, damaged, FD20 missing in the file name, gds missing in the file
extension.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 62 of 77
FD 20 Mounting and operating instructions
10 SHUT-DOWN
No particular measures need to be taken for de-commissioning the installation.
If the swing door drive mechanism will not be used during at least 1 month, it is recom-
mended to pull out the mains plug.
For taking the installation back into operation, all you have to do is to plug in the mains
cable and select the operating mode.
Attention:
If the installation is re-commissioned at low temperatures, it must be swit-
ched on 1...2 hours prior to the actual setting-up procedure (so that the
operating temperature can be reached).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 63 of 77
FD 20 Mounting and operating instructions
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 64 of 77
FD 20 Mounting and operating instructions
12 SPARE PARTS
Article No. Designation Remark
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 65 of 77
FD 20 Mounting and operating instructions
13 OPTIONS
13.1 D-BEDIX
The different operating modes can be
directly enabled by means of the D-BEDIX.
In addition, it provides easy programming of
the most important door settings.
The operating modes, menu settings as well
as possible errors are displayed in a clearly
arranged synopsis.
The D-BEDIX is connected to the control
unit FD 20 via a screened two-core connec-
tion cable (e.g. U72M or EIB-Y(St)Y, max.
length 50 m).
Only one D-BEDIX can be connected per
door installation.
13.1.1 Keys
C-key (Cancel)
• Exit the menu
• Invalidate entry.
OK-key
• Confirm the selection
• Confirm the entry.
Arrow keys
• Navigate within the menus
• Short simultaneous actuation of both keys = acces to the menu level.
13.1.2 Symbols
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 66 of 77
FD 20 Mounting and operating instructions
With the D-BEDIX, the following operating modes can be selected by means of the corre-
sponding symbols:
AUTOMATIC
Automatic operation. The installation can be locked.
NIGHT
The installation is locked1. As opening commands, only the key-operated impul-
se switch is accepted.
The delayed switchover to the operating mode NIGHT can be activated by
means of parameter TdNigt. Function: If the program selector switch is changed
to the operating mode NIGHT from any random operating mode, the internal
radar will still remain active during the programmed time TdNigt (EXIT).
OPEN
The installation is opened and remains in the open position.
MANUAL
The installation stops. The swing door leaf is released and can be manually ope-
ned and closed.
EXIT
One-way traffic from inside towards the outside.
The installation is locked2 (shop closing switching mode).
1
Provided that the locking mechanism (optional) is installed.
2
Each operating mode can be locked (this is configurable).
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 67 of 77
FD 20 Mounting and operating instructions
Short and simultaneous actuation of both arrow keys (=access to the menu level).
Select the desired menu item bymeans of the arrow key.
Confirm by means of the OK key.
Display Description
PARAMETER Setting the motional parameters *
CONFIG Setting the functionalities *
DOUBLE DOOR Setting the closing sequence and interlock function *
DIAGNOSTICS Diagnostic tool
ERROR ACTIVE Active pending errors
ERROR HISTORY Formerly active errors
REINIT Carry out a re-initialization *
BLOCK/UNBLOC Lock/unlock keys
TEACH Initiate a setting-up procedure
make sure that the door leaf is completely closed.
* password protected
Note:
The detailed settings are described in chapter 7.4.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 68 of 77
FD 20 Mounting and operating instructions
BLOCK?
Temporarily disabling the keylock (60 s)
Short simultaneous actuation of the C-key and the right-hand arrow key.
UBLOC?
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 69 of 77
FD 20 Mounting and operating instructions
TOEx 7
Teach
Completely close the door leaf.
Short simultaneous actuation of the arrow keys (= access to the menu level).
By means of the arrow key, select Teach.
Confirm with the OK key.
TEACH?
In the event of an error, the display shows (alternating with the door position status) the
presently active error number (e.g. E20/01).
Error list: see chapter Troubleshooting.
This sequence will be repeated until the error has been eliminated.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 70 of 77
FD 20 Mounting and operating instructions
13.2 KOMBI-D-BEDIX
In addition to the functions of the D-BEDIX,
the KOMBI-D-BEDIX contains a key-opera-
ted switch (round or profile cylinder) with the
following function:
Free Locked
0635-148/04 0635-148/02
KABA 1514 KESO 21.214.040
SEA 1.043.0 Adjustable beard E200
DOM 2222H ix5
Driver with 8 adjus. DOM 333 ix-5
possibilities Driver with 8 adjusting
possibilities
KESO 11.014.045
KESO 21.014.045
KESO 31.014.045 BKS 8900 N BL 31
Adjustable beard E201 BKS 3101 N BL 31
BKS 3301 N BL 31
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 71 of 77
FD 20 Mounting and operating instructions
0548-106
Set 0547-232 95
1 Plate 0547-391 25 45 (25)
5 Screws 4083-359 10 15 22,5 22,5 15 (10)
black
14
cataphoretic painting
45
21
(10)
R
2
Ø10 Ø5,5
4,1
3
M6 Ø10,4 x 90°
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 72 of 77
FD 20 Mounting and operating instructions
Attention:
The mounting measures according to chapter 4 must be verified and com-
plied with!
R6
(90 ±0,5 )
76 ±0,3
3 28
20
48
48
28 3
20
20
10 20
20
21
21
7
256
463
325
345
207
550
570
640
30
0
414
120
100
670 ±0,5
Attention:
The mounting measures according to chapter 4 must be verified and com-
plied with!
670 ±0,5
256
207
640
463
414
30
90 90 90 90
80 80
70 70 70 70
3 28 60 60 60 60 28 3
76 ±0,3
50 50 50 50
(100 )
48
48
R6 40 40 40 40 R6
30 30 30 30
20 20
26
26
10 10 10 10
12
524
544
435
75
95
204
415
184
Ø12,4 x 90°
Thickness 10 mm M6
Ø7
90
80 80
70 70
60 60
50 50
40 40
30 30
20 20
10
575
235
555
215
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 73 of 77
FD 20 Mounting and operating instructions
Note:
A fire alarm is displayed by the red LED in the side cover.
This LED must be visible on one of the two drive units!
,5
±0
690 X = .......... ±0,5 690
.
...
...
X = A - (2 x 690)
...
=
X
FD 20 FD 20
91
22
0548-414/60
5
0,
680 Y = .......... ±0,5 680
0548-414/60
.±
*
...
11
...
10 Y = A - (2 x 680)
11* 11* 10
...
=
Y
*
11
91
11* 11* *
11
10
*
11
* remove
120 130
min. 4 x min. 4 x
95
95
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 74 of 77
FD 20 Mounting and operating instructions
Attention:
All the four optional PCBs must only be plugged into/removed from the
control unit after the dive unit has been disconnected from the power supply
source!
Commissioning:
2. Switch-on the main installation swtich on the drive unit the relay PCB is automati-
cally identified.
The identified relay PCB is displayed as follows in the diagnostic menu:
R0 Addr0
R1 Addr1
Joystick
FP Fire protection PCB R0+R1-
RP Radio PCB
+ identified and ready for operation FP-RP-
- neither identified nor registered Display
e defective or error
x removed
3. Enabling of the desired function per relay: under Settings Configuration RC0.1 up
to RC0.4 (for Addr 0) and RC1.1 up to RC1.4 (for Addr 1).
5. In the rest position, press in the joystick: Reset OK? The relay PCB is deleted from
the configuration.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 75 of 77
FD 20 Mounting and operating instructions
A radio control PCB can be plugged into the control of the drive unit. Using a hand-held
radio transmitter, this PCB can be programmed with a code, upon which the drive unit can
be controlled via the hand-held radio transmitter.
In cases where several hand-held radio transmitters shall be used for controlling the
same drive unit, all the transmitters need to be programmed with the same code (which is
transmitted from the standard transmitter to all the additional transmitters).
On the other hand, several drive units can be simultaneously controlled by one single
button.
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 76 of 77
FD 20 Mounting and operating instructions
14 APPENDIX
The following document is added as an appendix to this instructions:
0548-990-01---10e_2014.12.indd 0548-990/02e
Page 77 of 77