PE2405 - SE02 - DIAGRAMA UNIFILAR - R0-Model
PE2405 - SE02 - DIAGRAMA UNIFILAR - R0-Model
PE2405 - SE02 - DIAGRAMA UNIFILAR - R0-Model
DA CONCESSIONÁRIA
13,8kV
CHAVE SECCIONADORA
MONOPOLAR PADRÃO
EDP ESCELSA
GAM2 375mm GBC-I 750mm GBM 375mm DM1-A 750mm IM 375mm QM 375mm QM 375mm QM 375mm
ALIMENTADOR TRAFO 01 ALIMENTADOR TRAFO 02 ALIMENTADOR TRAFO 03
ENTRADA PRINCIPAL 13,8KV - 630A MEDIÇÃO DE FATURAMENTO TRANSIÇÃO SAÍDA GERAL ENTRADA 500KVA - 127/220V 750KVA - 127/220V 500KVA - 220/380V
3x1/c #95mm2 - - 3x1/c #95mm² 3x1/c #95mm² 3x1/c #25mm² 3x1/c #25mm² 3x1/c #25mm²
WL5A
COLUNA 4 13.8/R3-0.115/R3kV Q3
QC2 630A 630A 630A
2 500VA
FF2,3,4 0.6P75 iC60N-2P
0,5A 4A 630A
1 2
13.8/R3-0.115/R3 kV
0.6P75
500VA
(**)
TP1,2,3
K K K
FF1,2,3 FF4,5,6 FF4,5,6
80A 80A 80A
(**)
TC1,2,3
X-5A
E
INTERT. WL8A
COLUNA 2
C1,2,3 PR1,2,3 C4,5,6
3
AJUSTE DA PROTEÇÃO GERAL - D1
3
CARGA TOTAL: 1.75 MVA
DEMANDA A SER CONTRATADA: 850kW
NEG.
NEG.
NEG.
NEG.
POS.
POS.
POS.
POS.
CÁLCULO DA CORRENTE DE CARGA: 35,56A
3
GRUPO GERADOR 1*
CÁLCULO DA CORRENTE DE INRUSH: 425A
625 kVA - 127/220V QTA
TIPO DE PROTEÇÃO: SECUNDÁRIA QGBT-3
RELÉ DE PROTEÇÃO:
*O GRUPO GERADOR NÃO FUNCIONA EM PARALELISMO COM A CONCESSIONÁRIA
MODELO: SF1
FABRICANTE: SCHNEIDER
FUNÇÕES: ANSI 50/51, 50/51N
TRANSFORMADOR DE CORRENTE (TC):
MEIO ISOLANTE: SECO
NEG.
NEG.
NEG.
NEG.
POS.
POS.
POS.
POS.
DIAGRAMA UNIFILAR MT
DIAL DE TEMPO: 0,1s
AJUSTE DA UNIDADE INSTATÂNEA DE NEUTRO (50N):
3
CORRENTE DE PICKUP PRIMÁRIA: 180A
QGBT-2 QGBT-1 VILA VELHA - ESPIRITO SANTO - TEL.: (27) 9 8115-5322 / (27) 9 9776-6142