IS : 2026 (Part I) - 1977
(Reaffirmed 2006)
Edition 2.3
(1985-10)
Indian Standard
SPECIFICATION FOR
POWER TRANSFORMERS
PART I
GENERAL
( First Revision )
(Incorporating Amendment Nos. 1, 2 & 3)
UDC
621.314.222.6
© BIS 2007
BUREAU
OF
INDIAN
STANDARDS
MANAK BHAVAN , 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI 110002
Price Group 8
IS : 2026 (Part I) - 1977
Indian Standard
SPECIFICATION FOR
POWER TRANSFORMERS
PART I
GENERAL
( First Revision )
Transformers Sectional Committee, ETDC 16
Chairman
SHRI U. K. PATWARDHAN
Prayog Electricals Pvt Ltd, Bombay
Members
Representing
Bharat Heavy Electricals Ltd (R & D Unit)
SHRI S. AMMEERJAN
SHRI N. S. S. AROKIASWAMY
Tamil Nadu Electricity Board, Madras
SHRI M. K. SUNDARARAJAN ( Alternate )
Kirloskar Electric Co Ltd, Bangalore
SHRI B. G. BHAKEY
DR B. N. JAYARAM ( Alternate )
SHRI A. V. BHEEMARAU
Gujarat Electricity Board, Vadodara
SHRI J. S. IYER ( Alternate )
SHRI S. D. CHOTRANEY
Bombay Electric Supply and Transport Undertaking,
Bombay
SHRI Y. K. PALVANKAR ( Alternate )
Central Electricity Authority, New Delhi
DIRECTOR (TRANSMISSION)
DEPUTY DIRECTOR (TRANSMISSION) ( Alternate )
SHRI T. K. GHOSE
Calcutta Electric Supply Corporation Ltd, Calcutta
SHRI P. K. BHATTACHARJEE ( Alternate )
JOINT DIRECTOR (SUB-STATION) Research, Designs and Standards Organization
(Ministry of Railways), Lucknow
DEPUTY DIRECTOR STANDARDS (ELECTRICAL) ( Alternate )
Directorate General of Supplies and Disposals
SHRI J. K. KHANNA
(Inspection Wing), New Delhi
SHRI K. L. GARG ( Alternate )
SHRI B. S. KOCHAR
Rural Electrification Corporation Ltd, New Delhi
SHRI R. D. JAIN ( Alternate )
SHRI J. R. MAHAJAN
Indian Electrical Manufacturer’s Association, Bombay
SHRI P. K. PHILIP ( Alternate )
SHRI D. B. MEHTA
Tata Hydro-Electric Power Supply Co Ltd, Bombay
SHRI R. CHANDRAMOULI ( Alternate )
( Continued on page 2 )
© BIS 2007
BUREAU OF INDIAN STANDARDS
This publication is protected under the Indian Copyright Act (XIV of 1957) and
reproduction in whole or in part by any means except with written permission of the
publisher shall be deemed to be an infringement of copyright under the said Act.
IS : 2026 (Part I) - 1977
( Continued from page 1 )
Members
Representing
SHRI D. V. NARKE
Bharat Heavy Electricals Ltd
SHRI ISHWAR CHANDRA ( Alternate I )
SHRI PREM CHAND ( Alternate II )
SHRI I. S. PATEL
Hindustan Brown Boveri Ltd, Bombay
SHRI V. N. PRAHLAD
National Electrical Industries Ltd, Bhopal
SHRI A. G. GURJAR ( Alternate )
SHRI K. N. RAMASWAMY
Directorate General of Technical Development, New
Delhi
SHRI S. K. PALHAN ( Alternate )
SHRI CHANDRA K. ROHATGI
Pradip Lamp Works, Patna
SHRI D. P. SAHGAL
Siemens India Ltd, Bombay
SHRI A. R. SALVI ( Alternate )
SHRI I. C. SANGAR
Delhi Electric Supply Undertaking, New Delhi
SHRI R. C. KHANNA ( Alternate )
SHRI K. G. SHANMUKHAPPA
NGEF Ltd, Bangalore
SHRI P. S. RAMAN ( Alternate )
SHRI M. A, SHARIFF
Karnataka Electricity Board, Bangalore
SHRI B. C. ALVA ( Alternate )
SUPERINTENDING E N G I N E E R Andhra Pradesh State Electricity Department
(OPERATION)
(Electricity Projects and Board), Hyderabad
SUPERINTENDING ENGINEER
TECHNICAL
(PROJECTS)
( Alternate )
Crompton Greaves Ltd, Bombay
SHRI C. R. VARIER
SHRI S. V. MANERIKAR ( Alternate )
SHRI S. P. SACHDEV,
Director General, BIS ( Ex-officio Member )
Director (Elec tech)
Secretary
SHRI VIJAI
Deputy Director (Elec tech), BIS
Panel for Revision of IS : 2026 Specification for Power Transformers,
ETDC 16 : P6
SHRI S. V. MANERIKAR
Crompton Greaves Ltd, Bombay
SHRI D. V. NARKE
Bharat Heavy Electricals Ltd
SHRI ISHWAR CHANDRA ( Alternate I )
SHRI PREM CHAND ( Alternate II )
SHRI S. SRINIVASAN ( Alternate III )
2
IS : 2026 (Part I) - 1977
Indian Standard
SPECIFICATION FOR
POWER TRANSFORMERS
PART I
GENERAL
( First Revision )
0. F O R E W O R D
0.1 This Indian Standard (Part I) (First Revision) was adopted by the
Indian Standards Institution on 24 February 1977, after the draft
finalized by the Transformers Sectional Committee had been approved
by the Electrotechnical Division Council.
0.2 This standard was first published in 1962 and covered naturallycooled oil-immersed transformers. By subsequent amendments forcedcooled transformers were included, use of synthetic liquids as cooling
medium was permitted and requirements for aluminium windings
were incorporated.
0.3 The revision has been undertaken with a view to bringing it in line
with the revision of IEC Pub 76-1967 ‘Power transformers’.
0.4 The salient features of this revision are as follows:
a) The kVA ratings have been extended to an unlimited range in
the same series,
b) The requirements with regard to ability to withstand short
circuit have been revised and a special test for assessing the
dynamic ability of the transformer to withstand short circuit has
been included,
c) Dry-type transformers have been covered,
d) Identification of transformers according to cooling methods has
been lined up with the international practice, and
e) The phase marking ABC have been replaced by UVW following
the international practice.
0.5 In this revision the requirements for power transformers are
covered in four parts as follows:
Part I General
Part II Temperature-rise
Part III Insulation levels and dielectric tests
Part IV Terminal markings, tappings and connections
3
IS : 2026 (Part I) - 1977
0.6 This standard (Part I) has been based on IEC Pub 76-1 (1976)
Power transformers, Part I : General, issued by the International
Electrotechnical Commission.
0.7 This part shall be read in conjunction with IS : 2026 (Part II)-1977*,
IS : 2026 (Part III)-1977† and IS : 2026 (Part IV)-1977‡.
0.8 This edition 2.3 incorporates Amendment No. 1 (January 1981),
Amendment No. 2 (January 1983) and Amendment No. 3
(October 1985). Side bar indicates modification of the text as the result
of incorporation of the amendments.
0.9 For the purpose of deciding whether a particular requirement of
this standard is complied with, the final value, observed or calculated,
expressing the result of a test or analysis, shall be rounded off in
accordance with IS : 2-1960§. The number of significant places
retained in the rounded off value should be the same as that of the
specified value in this standard.
1. SCOPE
1.1 This standard covers power transformers (including auto
transformers).
1.2 This standard does not cover the following small and special
purpose transformers:
a) Single-phase transformers rated at less than 1 kVA and
polyphase transformers rated at less than 5 kVA;
b) Outdoor type three-phase distribution transformers up to and
including 100 kVA, 11 kV (covered by IS : 1180-1964||);
c) Instrument transformers (covered by IS : 2705¶ and IS : 3156**);
d) Transformers for static convertors;
e) Starting transformers;
f) Testing transformers;
g) Traction transformers mounted on rolling stock;
h) Welding transformers [covered by IS : 1851-1966†† and IS : 4804
(Part I)-1968‡‡];
*Specification for power transformers: Part II Temperature-rise ( first revision ).
†Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
‡Specification for power transformers: Part IV Terminal markings, tappings and
connections ( first revision ).
§Rules for rounding off numerical values ( revised ).
||Specification for outdoor type three-phase distribution transformers up to and
including 100 kVA 11 kV ( revised ).
¶Specification for current transformers.
**Specification for voltage transformers.
††Specification for single operator type arc welding transformers ( first revision ).
‡‡Specification for resistance welding equipment: Part I Single-phase transformers.
4
IS : 2026 (Part I) - 1977
j) Mining transformers [covered by IS : 2772 (Part I)-1964*];
k) Earthing transformers (covered by IS : 3151-1965†);
m) X-ray transformers;
n) Reactors (covered by IS : 5553‡); and
p) Furnace type transformers.
NOTE — Where Indian Standards do not exist for the transformers mentioned above,
or for other special transformers, this standard may be applicable either as a whole
or in part.* †
2. TERMINOLOGY‡
2.0 For the purpose of this standard, the definitions given in IS : 1885
(Part XXXVIII)-1977§ shall apply.
3. SERVICE CONDITIONS
3.1 Reference Ambient Temperatures — The reference ambient
temperatures assumed for the purpose of this specification are as
follows:
a) Maximum ambient air temperature
50°C
b) Maximum daily average ambient air temperature
40°C
c) Maximum yearly weighted average ambient temperature 32°C
d) Minimum ambient air temperature
– 5°C
e) Water — When the cooling medium is water, it is assumed that a
temperature of 30°C will not be exceeded and that the average
cooling water temperature will not exceed 25°C in any day.
3.1.1 Transformers complying with this specification are suitable for
operation continuously, at their ratings provided the temperature of
the cooling air or water does not exceed any of the reference ambient
temperatures specified under 3.1.
It is also recognized that operation of a transformer at its rated kVA
provides normal life expectancy, if the hot spot temperature based on
maximum yearly weighted average ambient temperature is 98°C.
3.1.2 For service conditions differing from standard, it is recommended that a transformer having a standard temperature rise be used and
loaded in accordance with IS : 6600-1972|| .
*Specification for non-flameproof mining transformers for use below ground : Part I
Oil-immersed type.
†Specification for earthing transformers.
‡Specification for reactors.
§Electrotechnical vocabulary : Part XXXVIII Transformers ( first revision ).
||Guide for loading of oil-immersed transformers.
5
IS : 2026 (Part I) - 1977
3.2 Altitude
3.2.1 Transformers conforming to this standard are suitable for operation at an altitude not exceeding 1 000 metres above mean sea level.
3.2.2 For altitudes exceeding 1 000 metres above mean sea level, an
adjustment of the temperature-rise shall be necessary in accordance
with IS : 2026 (Part II)-1977*.
4. RATING
4.0 General — The manufacturer shall ascribe ratings to the
transformer, which shall be marked on the rating plate ( see 15 ).
These ratings shall be such that the transformer can deliver its rated
current under steady loading conditions without exceeding the limits
of temperature-rise specified in IS : 2026 (Part II)-1977* assuming
that the applied voltage is equal to the rated voltage and that the
supply is at rated frequency.
4.1 Rated kVA — The rated kVA assigned shall take into account
service conditions corresponding to those specified in 3 and shall be
related to the product of rated voltage, rated current and the
appropriate phase factor given in Table 1.
TABLE 1
NUMBER OF PHASES
(1)
1
3
PHASE FACTORS
PHASE FACTOR
(2)
1
1.73
NOTE 1 — The rated kVA assigned, corresponds to continuous duty; nevertheless
oil-immersed transformers complying with this standard may be overloaded and
guidance on overloads is given in IS : 6600-1972†.
Within the conditions defined in IS : 6600-1972†. occasional overloads‡ up to 1.5
times the rated value may be allowed on transformers with rated powers up to 100
MVA§. Under these conditions no limitations by bushings, tap-changers, or other
auxiliary equipment shall apply. Regular daily overloads or emergency overloads in
excess of this may be restricted by consideration of auxiliary equipment and in these
cases reference shall be made to the manufacturer.
NOTE 2 — With rated voltage applied to one of the windings, the apparent power
(kVA) that can really be delivered by (one of) the other winding(s) loaded with its
rated current will deviate from its rated kVA by an amount depending on the
corresponding voltage drop (or rise). This apparent power is equal to the product of
the actual voltage on load of the latter winding, the rated current related to that
winding and the appropriate phase factor ( see Table 1 ).
*Specification for power transformers: Part II Temperature rise ( first revision ).
†Guide for loading of oil immersed transformers.
‡Occasional overload implies:
a) operation at 1.5 times the rated current of the transformer for 3 percent of its life
without making tap-changes, and
b) tap-changing on the basis of 3 percent of the operations being at currents of 1.5
times the rated current of the transformer.
§Special purpose transformers, for example, generator transformers, are not
considered normally to require overload capacities.
6
IS : 2026 (Part I) - 1977
4.2 kVA Ratings — kVA ratings for three-phase transformers are
given in Table 2.
TABLE 2
kVA
kVA RATINGS FOR THREE-PHASE TRANSFORMERS
kVA
kVA
5
31.5
200
6.3
40
250
8
50
315
10
63
400
12.5
80
500
16
100
630
20
125
25
160
800
1 000 et al
NOTE — Underlined values are preferred ratings.
For single-phase transformers intended for use in three-phase
banks, the kVA ratings are one-third of the values in Table 2; for
single-phase transformers not intended for such use, they are the same
as for three-phase transformers.
4.3 Operation at Other than Rated Voltage and Frequency
4.3.1 A transformer built in accordance with this specification may be
operated at its rated kVA at any voltage within ± 10 percent of the
rated voltage of that particular tap.
4.3.2 The transformer shall be capable of delivering rated current at a
voltage equal to 105 percent of the rated voltage.
NOTE — The slight temperature-rise increase which would correspond to the 5
percent overvoltage, due to high no-load loss, is disregarded.
4.3.3 A transformer for two or more limits of voltage or frequency or
both shall give its rated kVA under all the rated conditions of voltage
or frequency or both; provided an increase in voltage is not
accompanied by a decrease in frequency.
NOTE — Operation of a transformer at rated kVA at reduced voltage may give rise to
excessive losses and temperature-rise.
4.4 Rated Frequency — The frequency for the purpose of this
standard shall be 50 Hz with tolerance of ± 3 percent.
7
IS : 2026 (Part I) - 1977
5. TEMPERATURE-RISE
5.1 The transformer shall conform to the requirements
temperature-rise specified in IS : 2026 (Part II)-1977*.
of
6. INSULATION LEVELS
6.1 The insulation levels shall be in accordance with IS : 2026
(Part III)-1977†.
7. TERMINAL MARKINGS, TAPPINGS AND CONNECTIONS
7.1 The terminal markings, tappings and connections shall be in
accordance with IS : 2026 (Part IV)-1977‡.
8. REQUIREMENTS WITH REGARD TO ABILITY TO
WITHSTAND SHORT CIRCUIT
8.0 General — Transformers shall be designed and constructed to
withstand without damage the thermal and dynamic effects of
external short circuit under the conditions specified in 8.1.
NOTE — External short circuits are not restricted to three-phase short circuits, they
include line-to-line, double line-to-earth and line-to-earth faults. The currents resulting
from these conditions in the windings are designated as overcurrents in this standard.
8.1 Overcurrent Conditions
8.1.1 Transformers with Two Separate Windings
8.1.1.1 The following three categories for the rated kVA of three-phase
transformers or three-phase banks shall be recognized:
Category 1 Up to 3 150 kVA
Category 2 3151 to 40 000 kVA
Category 3 Above 40 000 kVA
8.1.1.2 The symmetrical short-circuit current (rms value) ( see 9.1.2 )
shall be calculated using the short-circuit impedance of the transformer
plus the system impedance for transformers of categories 2 and 3 and
also for transformers of category 1 if the system impedance is greater
than 5 percent of the short-circuit impedance of the transformer.
For transformers of category 1 the system impedance shall be
neglected in the calculation if this impedance is equal to or less than 5
percent of the short-circuit impedance of the transformer.
*Specification for power transformers: Part II Temperature-rise ( first revision ).
†Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
‡Specification for power transformers: Part IV Terminal markings, tappings and
connections ( first revision ).
8
IS : 2026 (Part I) - 1977
The peak value of the short-circuit current shall be calculated in
accordance with 16.11.2.
8.1.1.3 Typical values for the short-circuit impedance of transformers
expressed as the impedance voltage at rated current (principal
tapping) are given in Table 3. If lower values are required, the ability
of the transformer to withstand a short circuit shall be subject to
agreement between the manufacturer and the purchaser.
TABLE 3 TYPICAL VALUES OF IMPEDANCE VOLTAGE FOR
TRANSFORMERS WITH TWO SEPARATE WINDINGS (AT
RATED CURRENT, GIVEN AS A PERCENTAGE OF THE
RATED VOLTAGE OF THE WINDING TO WHICH THE
VOLTAGE IS APPLIED)
IMPEDANCE VOLTAGE
RATED POWER
(1)
(2)
kVA
Percent
Up to
630
4.5
631 to
1 250
5.0
1 251 ,,
3 150
6.25
3 151 ,,
6 300
7.15
6 301 ,, 12 500
8.35
12 501 ,, 25 000
10.0
25 001 ,, 200 000
12.5
NOTE 1 — Values for rated powers greater than 200 000 kVA shall be subject to
agreement between the manufacturer and the purchaser.
NOTE 2 — In the case of single-phase transformers connected to form a three-phase
bank, the value for rated power applies to the three-phase bank.
8.1.1.4 The short-circuit apparent power of the system at the transformer location shall be specified by the purchaser in his enquiry in
order to obtain the value for the symmetrical short-circuit current to
be used for the design and the tests. If the short-circuit level is not
specified the value given in Table 4 shall be used.
8.1.2 Transformers with More Than Two Windings and
Auto-Transformers
8.1.2.1 The overcurrents in the windings including stabilizing windings
and auxiliary windings, shall be determined from the impedances of the
transformer and the system(s). Account shall be taken of the effect of
possible feedback from rotating machinery or from other transformers as
well as of the different forms of system faults that can arise in service,
such as line-to-earth faults and line-to-line faults associated with the
relevant system and transformer earthing conditions. The
characteristics of each system (at least the short-circuit level and the
range of the ratio between the zero-sequence impedance and the positive
sequence impedance) shall be specified by the purchaser in his enquiry.
9
IS : 2026 (Part I) - 1977
TABLE 4
SHORT-CIRCUIT APPARENT POWER OF THE SYSTEM
( Clauses 8.1.1.4 and 9.1.2 )
HIGHEST SYSTEM VOLTAGE
SHORT-CIRCUIT APPARENT POWER
(1)
kV
7.2, 12, 17.5 and 24
36
52 and 72.5
100 and 123
145
245
300
420
(2)
MVA
500
1 000
3 000
6 000
10 000
20 000
30 000
40 000
8.1.2.2 When the combined impedance of the transformer and the
system(s) results in excessive overcurrent, the manufacturer shall
advise the purchaser of the maximum overcurrent that the
transformer can withstand. In this case, provision shall be made by
the purchaser to limit the short-circuit current to the overcurrent
indicated by the manufacturer.
8.1.2.3 Stabilizing windings of three-phase transformers shall be
capable of withstanding the overcurrents resulting from different
forms of system faults that can arise in service associated with
relevant system earthing conditions.
8.1.2.4 It may not be economical to design auxiliary windings to
withstand short circuits on their terminals. In such a case the effect of
the overcurrents has to be limited by appropriate means, such as
series reactors, or in some instances suitable fuses. Care has to be
taken to guard against faults in the zone between the transformer and
the protective apparatus.
8.1.2.5 In the case of single-phase transformers connected to form a
three-phase bank the stabilizing windings shall be capable of
withstanding a short circuit on their terminals, unless the purchaser
specifies that special precautions shall be taken to avoid short circuits
between phases.
8.1.3 Booster-Transformers
8.1.3.1 The impedances of booster-transformers may be very low and
therefore the overcurrents in the windings are determined mainly by
the characteristics of the system at the location of the transformer.
These characteristics shall be specified by the purchaser in his enquiry.
10
IS : 2026 (Part I) - 1977
8.1.3.2 When the combined impedance of the transformer and the
system results in excessive overcurrent, the manufacturer shall advise
the purchaser of the maximum overcurrent that the transformer can
withstand. In this case, provision shall be made by the purchaser to
limit the short-circuit current to the overcurrent indicated by the
manufacturer.
8.1.4 Transformers Directly Associated with Other Apparatus
8.1.4.1 Where a transformer is directly associated with other
apparatus, the impedance of which would limit the short-circuit
current, the sum of the impedance of the transformer, the system and
the directly associated apparatus shall, by agreement between
manufacturer and purchaser be taken into account.
This applies, for example, to generator transformers if the
connection between generator and transformer is constructed in such a
way that the possibility of line-to-line or double line-to-earth faults in
this region is negligible.
NOTE — The most severe short-circuit conditions may occur, in the case of a stardelta connected generator transformer with earthed neutral, when a line-to-earth
fault occurs on the system connected to the star-connected winding.
8.1.5 Special Transformers — The ability of a transformer to
withstand frequent overcurrents arising from the method of operation
or the particular application (for example, furnace transformers,
rectifier transformer and traction feeding transformers), shall be
subject to special agreement between the manufacturer and the
purchaser.
8.1.6 Tap-Changing
fitted,
tap-changing
Equipment — Where
equipment shall be capable of carrying the same overcurrents due to
short circuits as the windings.
8.1.7 Neutral Terminals — The neutral terminal of windings with star
or zigzag connection shall be designed for the highest overcurrent that
can flow through this terminal.
9. DEMONSTRATION OF ABILITY TO WITHSTAND
SHORT CIRCUIT
9.1 Thermal Ability to Withstand Short Circuit
9.1.1 General — The thermal ability to withstand short circuit shall be
demonstrated by calculation.
11
IS : 2026 (Part I) - 1977
9.1.2 Value of the Symmetrical Short-Circuit Current I for
Transformers with Two Windings — The rms value of the symmetrical
short-circuit current I is calculated for three-phase transformers as
follows:
U
I = ---------------------------------------- kA
( Z t + Zs ) 3
where
Zs is the short-circuit impedance of the system U 2 s in ohms per
---------phase:
S
Us is the rated voltage of the system in kV and S is the
short-circuit apparent power of the system in MVA;
U and Z t are defined as follows:
a) for the principal tapping:
U is the rated voltage UN of the winding under consideration, in kV;
Zt is the short-circuit impedance of the transformer
referred to the winding under consideration, and is
calculated as follows:
u Z U 2N
Z t = ------------------- , in ohms per phase,
100 S N
where uz is the impedance voltage at rated current
and at the reference temperature, as a percentage, and
SN is the rated power of the transformer, in MVA; and
b) for tappings other than the principal tapping:
U is, unless otherwise specified, the tapping voltage of
the tapping and the winding under consideration, in
kV; and
Zt is the short-circuit impedance of the transformer
referred to the winding and the tapping under
consideration, in ohms per phase.
For transformers of category 1 the impedance of the system is
neglected in the calculations if it is equal to or less than 5 percent of
the short-circuit impedance of the transformer ( see also 8.1.1.2 ).
If the short-circuit power of the system is not specified by the
purchaser in the enquiry, its value may be taken from Table 4.
12
IS : 2026 (Part I) - 1977
9.1.3 Duration of the Symmetrical Short-Circuit Current I — The
duration of the current I to be used far the calculation of the thermal
ability to withstand short circuit shall be 2 seconds, unless otherwise
specified by the purchaser.
NOTE — For auto-transformers and for transformers with a short-circuit current
exceeding 25 times the rated current a short-circuit current duration below 2 seconds
may be adopted after agreement between the manufacturer and the purchaser.
9.1.4 Maximum Permissible Value of the Highest Average Temperature
θ1 — On the basis of an initial winding temperature θ0, derived from the
sum of the maximum permissible ambient temperature and the relevant
temperature rise at rated conditions measured by resistance (or, if this
temperature-rise is not available, the temperature-rise for the relevant
class of temperature of the winding) the highest average temperature θ1
of the winding, after loading with a symmetrical short-circuit current I
of a value and duration as described in 9.1.2 and 9.1.3 shall not exceed
the value stated for θ2 in Table 5 in any tapping position.
TABLE 5 MAXIMUM PERMISSIBLE VALUES OF AVERAGE
TEMPERATURES θ2 OF THE WINDING AFTER SHORT CIRCUIT
( Clauses 9.1.4, 9.1.5 and 9.1.6 )
TRANSFORMER TYPE
CLASS OF TEMPERATURE
VALUE OF θ2
(1)
Oil-immersed
Dry
(2)
A
A
E
B
F and H
Copper
(3)
°C
250
180
250
350
350
Aluminium
(4)
°C
200
180
200
200
—
9.1.5 Calculation of the Temperature θ1 — The highest average
temperature θ1 attained by the winding after short circuit shall be
calculated by the following formula:
θ1 = θ 0 + a.J 2 .t. 10 –3 °C,
where
θ0 is the initial temperature in degrees Celsius;
J is the short-circuit current density in amperes per square
millimetre;
t is the duration in seconds;
a is a function of 1/2 ( θ2 + θ0 ), in accordance with Table 6; and
θ2 is the maximum permissible average winding temperature,
in degrees Celsius, as specified in Table 5.
13
IS : 2026 (Part I) - 1977
TABLE 6
1/2 ( θ2 + θ0 )
VALUES OF FACTOR ‘’a’
( Clause 9.1.5 )
a*
(1)
°C
140
160
180
200
220
240
260
*Function of 1/2 ( θ2 + θ0 ).
Copper Windings
(2)
Aluminium Windings
(3)
7.41
7.80
8.20
8.59
8.99
9.38
9.78
16.5
17.4
18.3
19.1
—
—
—
9.1.6 Value of the Symmetrical Short-Circuit Current I for
Transformers
with
More
Than
Two
Windings
and
Auto-Transformers — The overcurrent shall be calculated in
accordance with 8.1.2. The highest average temperature of each
winding shall be calculated in accordance with 9.1.3, 9.1.4 and 9.1.5
and shall not exceed the maximum permissible values given in Table 5.
9.2 The Dynamic Ability to Withstand Short Circuit
9.2.1 General — The dynamic ability to withstand short circuit shall
be demonstrated by tests or by reference to tests on similar
transformers.
Short-circuit tests are special tests carried out in accordance
with 16.11.
NOTE — Transformers of category 3 can normally not be tested in accordance with
this standard. The conditions of tests on transformers with more than two windings
and auto-transformers shall always be subject to agreement between the
manufacturer and the purchaser.
10. MISCELLANEOUS REQUIREMENTS
10.1 Dimensions of Neutral Connection — The neutral conductor
and terminal of transformers (for example, distribution transformers)
intended to carry a load between phase and neutral shall be
dimensioned for the appropriate load current and earth fault current.
The neutral conductor and terminal of transformers not intended to
carry load between phase and neutral shall be dimensioned for earth
fault current.
10.2 Load Rejection on Generator Transformers — Transformers
intended to be connected directly to generators in such a way that they
may be subjected to load rejection conditions shall be able to withstand
1.4 times the rated voltage for 5 seconds at the transformer terminals
to which the generator is to be connected.
14
IS : 2026 (Part I) - 1977
10.3 Insulation Liquids — Mineral oil, if used, shall comply with
IS : 335-1972*.
10.4 Bushings — The bushings used on power transformers shall
comply with IS : 2099-1973†.‡ §
10.4.1 The dimensions of bushings of the following voltage classes
shall conform to Indian Standards mentioned against them:
Voltage Class
Indian Standard
For Porcelain Parts
Up to 1.1 kV IS : 3347 (Part I/Sec 1)1965‡
3.6 kV IS : 3347 (Part II/Sec 1)1965||
12 and 17.5 kV IS : 3347 (Part III/Sec 1)1972**
24 kV
IS : 3347 (Part IV/Sec 1)1973‡‡
36 kV
IS : 3347 (Part V/Sec 1)1973||||
For Metal Parts
IS : 3347 (Part I/Sec 2)1967§
IS : 3347 (Part II/Sec 2)1967¶
IS : 3347 (Part III/Sec 2)1967††
IS : 3347 (Part IV/Sec 2)1967§§
IS : 3347 (Part V/Sec 2)1967¶¶
10.5 Cable Sealing boxes — Cable sealing boxes for oil immersed
transformers suitable for paper-insulated lead-sheathed cables for
voltage class from 12 kV up to and including 36 kV shall comply with
IS : 9147-1979***.
*Specification for new insulating oils for transformers and switchgear ( second revision ).
†Specification for bushing for alternating voltage above 1 000 volts ( first revision ).
‡Dimensions for porcelain transformer bushings: Part I Up to 1.1 kV bushings,
Section 1 Porcelain parts.
§Dimensions for porcelain transformer bushings: Part I Up to 1.1 kV bushings,
Section 2 Metal parts.
||Dimensions for porcelain transformer bushings: Part II 3.6 kV bushings, Section 1
Porcelain parts.
¶Dimensions for porcelain transformer bushings: Part II 3.6 kV bushings, Section 2
Metal parts.
**Dimensions for porcelain transformer bushings: Part III 12 and 17.5 kV bushings,
Section 1 Porcelain parts ( first revision ).
††Dimensions for porcelain transformer bushings: Part III 12 and 17.5 kV bushings,
Section 2 Metal parts.
‡‡Dimensions for porcelain transformer bushings: Part IV 24 kV bushings, Section 1
Porcelain parts ( first revision ).
§§Dimensions for porcelain transformer bushings: Part IV 24 kV bushings, Section 2
Metal parts.
||||Dimensions for porcelain transformer bushings: Part 36 kV bushings, Section 1
Porcelain parts ( first revision ).
¶¶Dimensions for porcelain transformer bushings: Part V 36 kV bushings, Section 2
Metal parts.
***Specification for cable sealing boxes for oil-immersed transformers suitable for
paper-insulated lead-sheathed cables for highest system voltages from 12 kV up to and
including 36 kV.
15
IS : 2026 (Part I) - 1977
11. TOLERANCES
11.1 Because of inevitable differences in basic materials and
variations in manufacture, as well as measurement errors, the values
obtained on test may differ from the calculated values and tolerances
on guaranteed values are necessary.
Table 7 gives tolerances to be applied to certain rated quantities and
to other quantities when they are the subject of manufacturers guarantees referring to this standard. Where a tolerance in one direction is
omitted there is no restriction on the value in that direction.
A transformer is considered as complying with this standard when
the quantities subject to tolerances are not outside the tolerances
given in Table 7.
12. INFORMATION REQUIRED WITH ENQUIRY AND ORDER
12.1 The technical information that the purchaser is required to
supply with the enquiry and order is given in Appendix A.
13. TECHNICAL PARTICULARS TO BE FURNISHED BY THE
MANUFACTURER
13.1 The manufacturer shall furnish technical particulars in accordance with Appendix B wherever required with the enquiry.
14. FITTINGS
14.1Fittings as listed in Appendix C shall be provided.
15. RATING PLATES
15.1 Each transformer shall be provided with a rating plate of
weather-proof material, fitted in a visible position, showing the
appropriate items given in 15.2. The entries on the rating plate shall
be indelibly marked (for example, by etching, engraving or stamping).
15.2 Information to be Given in all Cases
a) Kind of transformer (for example, transformer, auto-transformer,
booster transformer, etc);
b) Number of this standard, Ref IS : 2026;
c) Manufacturer’s name;
d) Manufacturer’s serial number;
e) Year of manufacture;
f) Number of phases;
16
IS : 2026 (Part I) - 1977
g) Rated kVA (for multi-winding transformers the rated kVA of
each winding shall be given. The loading combinations shall also
be indicated unless the rated power of one of the windings is the
sum of the rated powers of the other windings);
h) Rated frequency;
j) Rated voltages;
k) Rated currents;
m) Connection symbol;
n) Percent impedance voltage at rated current (measured value
corrected to 75°C) and, if necessary, the reference power. The
reference power should always be given for multi-winding
transformers;
p) Type of cooling (if the transformer has several methods of
cooling, outputs that differ from the rated power may be shown
as percentages of the rated power, for example, ONAN/ONAF
70/100 percent);
q) Total mass; and
r) Mass and volume of insulating oil.
15.2.1 If the transformer has more than one rating, depending upon
different connections of windings which have been specifically allowed
for in the design, the additional ratings shall all be given on the rating
plate.
15.3 Additional Information to be Given in Certain Cases
a) Temperature class of insulation (for dry-type transformers);
b) Temperature-rise (if other than that specified);
c) Connection diagram (in cases where the connection symbol will
not give complete information regarding the internal connections). If the connections can be changed inside the transformer,
the connection fitted at the works shall be indicated;
d) Insulation levels (applicable to windings rated for voltages of 3.6
kV and above and to the neutral end of windings with nonuniform insulation);
e) Transportation mass (for transformers exceeding 5 tonnes total
mass);
f) Untanking mass (for transformers exceeding 5 tonnes total
mass);
g) Insulating liquid, if not mineral oil;
NOTE — In the case of transformers immersed in synthetic insulating liquid containing polychlorinated biphenyls, for example Askarel, it is recommended that a
distinctive plate be fitted with wording drawing attention to the need to take care
because of environmental considerations.
17
IS : 2026 (Part I) - 1977
h) Indication of the winding which is fitted with tappings;
j) Table giving the tapping voltage, the tapping current and the
tapping power of each windings, for each tapping ( see Note 1 );
k) Values of short-circuit impedance on the extreme tappings and
on the principal tapping and indication of the winding to which
the impedance is related ( see Note 1 ); and
m) Information on the ability of the transformer to operate at a
voltage exceeding 105 percent of the tapping voltage or, for the
principal tapping, 105 percent of the rated voltage [ see IS : 2026
(Part IV)-1977* and 4.3 ].
NOTE 1 — For separate winding transformers of rated power up to 3 150 kVA and
tapping range up to ± 5 percent the table may be limited to the tapping voltages [it is
then implied that tapping currents and tapping power vary as indicated in 3.2.3 of
IS : 2026 (Part IV)-1977*] and the values of impedance may be limited to the value on
the principal tapping.
NOTE 2 — More detailed information may be given on the rating plate or on a special
plate, by agreement between the manufacturer and the purchaser. If necessary, a list
of all characteristics should be given on a special plate, preferably in tabular form.
15.4 The power transformer may also be marked with the Standard
Mark.
NOTE — The use of the Standard Mark is governed by the provisions of the Bureau of
Indian Standards Act, 1986 and the Rules and Regulations made thereunder. The
Standard Mark on products covered by an Indian Standard conveys the assurance that
they have been produced to comply with the requirements of that standard under a
well defined system of inspection, testing and quality which is devised and supervised
by BIS and operated by the producer. Standard marked products are also continuously
checked by BIS for conformity to that standard as a further safeguard. Details of
conditions under which a licence for the use of the Standard Mark may be granted to
manufacturers or producers may be obtained from the Bureau of Indian Standards.
16. TESTS
16.1 General Requirements for Type, Routine and Special
Tests — Tests shall be made at any ambient air temperature below
50°C and with cooling water (if required) at any temperature not
exceeding 30°C.
Tests shall be made at the manufacturers’ works, unless otherwise
agreed between the manufacturer and the purchaser.
All external components and fittings that are likely to affect the
performance of the transformer during the test shall be in place.
Tapped windings shall be connected on their principal tapping,
unless the relevant test clause requires otherwise or unless the
manufacturer and the purchaser agree otherwise.
*Specification for power transformers : Part IV Terminal markings, tappings and
connections ( first revision ).
18
IS : 2026 (Part I) - 1977
TABLE 7
TOLERANCES
( Clause 11.1 )
SL
ITEM
NO.
i) a) Total losses
b) Component losses
ii)
Voltage ratio at no load on the
principal
tapping
(rated
voltage ratio) ( see Note 2 )
iii)
Impedance voltage at rated
current (principal tapping):
a) If the principal tapping
corresponds with the mean
tapping position or with one
of the two middle tapping
positions:
1) two-winding t r a n sformers
2) multi-winding t r a n sformers
iv)
TOLERANCE
+ 10 percent of the total losses
+ 15 percent of each component loss,
provided that the tolerance for total
losses is not exceeded
The lower of the following values:
a) ± 0.5 percent of the declared ratio
b) A percentage of the declared ratio
equal to 1/10 of the actual
percentage impedance voltage at
rated current ( see Note 3 )
± 10 percent of the declared impedance
voltage for that tapping
± 10 percent of the declared impedance
voltage for one specified pair of
windings
± 15 percent of the declared impedance
for a second specified pair of
windings
Tolerance to be agreed and started for
further pairs of windings
See IS : 2026 (Part IV)-1977*
b) For tappings other than the
principal tapping
Short-circuit impedance for any
tapping
No-load current
Not less than as indicated in [(iii)a]
[ see also IS : 2026 (Part IV)-1977* ]
v)
+ 30 percent of the declared no-load
current
NOTE 1 — For Item (i) the loss tolerances of multi-winding transformers apply to
every pair of windings unless the guarantee states that they apply to a given loading
condition.
NOTE 2 — Tolerances on other tappings shall be subject to agreement between the
manufacturer and the purchaser.
NOTE 3 — Alternative [(ii)b] does not apply in the case of auto-transformers and
booster transformers, where the smallness of the impedance would result in an
exceptionally small tolerance.
*Specification for power transformers: Part IV Terminal markings, tappings and
connections ( first revision ).
19
IS : 2026 (Part I) - 1977
The test basis for all characteristics, other than insulation, is the
rated condition, unless the test clause states otherwise.
Where it is required, test results shall be corrected to a reference
temperature of 75°C.
16.1.1 Type Tests — The following shall constitute the type tests:
a) Measurement of winding resistance (16.2);
b) Measurement of voltage ratio and check of voltage vector
relationship (16.3);
c) Measurement of impedance voltage/short-circuit impedance
(principal tapping) and load loss (16.4);
d) Measurement of no-load loss and current (16.5);
e) Measurement of insulation resistance (16.6);
f) Dielectric tests (16.7);
g) Temperature-rise (16.8); and
h) Tests on on-load tap-changers, where appropriate (16.9).
16.1.2 Routine Tests — The following shall constitute the routine tests:
a) Measurement of winding resistance (16.2);
b) Measurement of voltage ratio and check of voltage vector
relationship (16.3);
c) Measurement of impedance voltage/short-circuit impedance
(principal tapping) and load loss (16.4);
d) Measurement of no-load loss and current (16.5);
e) Measurement of insulation resistance (16.6);
f) Dielectric tests (16.7); and
g) Tests on on-load tap-changers, where appropriate (16.9).
16.1.3 Special Tests — The following tests shall be carried out by
mutual agreement between the purchaser and the supplier:
a) Dielectric tests (16.7);
b) Measurement of zero-sequence impedance of three-phase
transformers (16.10);
c) Short-circuit test (16.11);
d) Measurement of acoustic noise level (16.12);
e) Measurement of the harmonics of the no-load current (16.13); and
f) Measurement of the power taken by the fans and oil pumps
(16.14).
20
IS : 2026 (Part I) - 1977
16.1.3.1 If special tests other than those listed in 16.1.3 are required,
the test method shall be subject to agreement between the
manufacturer and the purchaser.
16.2 Measurement of Winding Resistance
16.2.1 General — The resistance of each winding, the terminals
between which it is measured and the temperature of the windings
shall be recorded. Direct current shall be used for the measurement.
In all resistance measurements care shall be taken that
self-inductive effects are minimized.
During these cold-resistance measurements, the time for the
measuring current to become steady should be noted and used for
guidance when making hot-resistance measurements following a
temperature-rise type test.
16.2.2 Dry-Type Transformers — The temperature recorded shall be
the average reading of several (at least three) thermometers placed on
the winding surface.
Winding resistance and temperature shall be measured
simultaneously, and the temperature of the winding, as measured by
thermometer, should approximately equal the temperature of the
surrounding medium.
16.2.3 Oil-Immersed Type Transformers — After the transformer has
been under oil without excitation for at least 3 hours, the average oil
temperature shall be determined and the temperature of the winding
shall be deemed to be the same as the average oil temperature. The
average oil temperature is taken as the mean of the top and bottom oil
temperatures.
In measuring the cold resistance for pusposes of the
temperature-rise test, special efforts shall be made to determine the
average winding temperature accurately. Thus the difference in
temperature between the top and bottom oil shall be small. To obtain
this result more rapidly, the oil may be circulated by a pump.
16.3 Measurement of Voltage Ratio and Check of Voltage
Vector Relationship — The voltage ratio shall be measured on each
tapping. The polarity of single-phase transformers and vector symbol
of three-phase transformers shall be checked.
16.4 Measurement
of
Impedance
Voltage/Short-Circuit
Impedance (Principal Tapping) and Load Loss — The impedance
voltage/short-circuit impedance (principal tapping) and load loss shall
be measured at rated frequency by applying an approximately
sinusoidal supply to one winding, with the other winding short
circuited, with the windings connected on the relevant tapping. The
measurements may be made at any current between 25 percent and
21
IS : 2026 (Part I) - 1977
100 percent, but preferably not less than 50 percent, of the rated
current (principal tapping) or tapping current. Each measurement
shall be performed quickly and the intervals between them shall be
long enough to ensure that temperature-rises do not cause significant
errors. The difference in temperature between the top oil and the
bottom oil shall be small enough to enable the average temperature to
be determined with the required accuracy. If necessary the oil may be
circulated by a pump.
The measured values of the load loss shall be corrected by multiplying them by the square of the ratio of rated current (principal tapping)
or tapping current to test current. The value so derived shall be
corrected to the reference temperature given in 16.1 taking the I2 R
loss ( R = dc resistance ) as varying directly with resistance and all
other losses as varying inversely with resistance. The resistance shall
be determined as specified in 16.2.
The measured value of the impedance voltage (principal tapping)
shall be corrected by increasing it in the ratio of rated current to test
current. The value of impedance voltage so derived shall be corrected
to the reference temperature given in 16.1.
The measured value of short-circuit impedance when given in ohms
per phase, shall also be corrected to the reference temperature given
in 16.1.
On three-winding transformers the impedance voltage/short-circuit
impedances (principal tapping) and the load losses shall be measured
between windings taken in pairs as shown below:
a) Between winding 1 and winding 2
b) Between winding 2 and winding 3 the other winding being
open-circuited.
c) Between winding 3 and winding 1
For transformers with more than three windings, the windings shall
be taken in pairs and the principle of the method specified for threewinding transformers shall be followed.
NOTE — The resistance of the test connections should be sufficiently low not to affect
the measurement. If it is impracticable to employ connections in which the loss may
be neglected in relation to the load loss of the transformer; allowance should be made
for such losses.
16.5 Measurement of No-Load Loss and Current — The no-load
loss and the no-load current shall be measured at rated frequency at a
voltage equal to rated voltage if the test is performed on the principal
tapping or equal to the appropriate tapping voltage if the test is performed on another tapping. Other winding(s) shall be left open-circuited
and any windings which may be connected in open-delta shall have the
delta closed.
22
IS : 2026 (Part I) - 1977
For all transformers, the voltage shall be measured with a voltmeter
responsive to the mean value of voltage but scaled to read the rms value
of a sinusoidal wave having the same mean value. The voltage U'
indicated by this voltmeter shall be taken as the required value of lineto-line voltage and the no-load loss Pm shall be measured at this voltage.
At the same time, a voltmeter responsive to the rms value of voltage
shall be connected in parallel with the mean-value voltmeter and its
indicated voltage U shall be recorded.
If the voltages U' and U are not the same, the measured value of
no-load loss is corrected according to the formula:
Pm
P = ------------------------P1 + kP2
where
P = corrected value,
P1 = ratio of hysteresis losses to total iron losses,
U- 2 , and
k = ---- U′
P2 = ratio of eddy current losses to total iron loss.
NOTE — For flux densities normally used at 50 or 60 Hz the following values should
be taken:
P1
P2
Oriented steel
0.5
0.5
Non-oriented steel
0.7
0.3
The no-load current of all the phases shall be measured by rms
ammeters, and the mean of their readings shall be taken as the
no-load current.
16.6 Measurement of Insulation Resistance — The oil/air
temperatures shall be measured and recorded immediately prior to the
test. The insulation resistance of each winding, in turn, to all the other
windings, core and frame or tank connected together, and to earth
shall be measured and recorded.
16.7 Dielectric Tests — The transformer shall pass the appropriate
dielectric tests specified in IS : 2026 (Part III)-1977*. The dielectric
tests may be type tests, routine tests or special tests in accordance
with IS : 2026 (Part III)-1977*.
16.8 Temperature-Rise — The
transformer
shall
pass
the
temperature-rise test specified in IS : 2026 (Part II)-1977†.
*Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
†Specification for power transformers: Part II Temperature-rise ( first revision ).
23
IS : 2026 (Part I) - 1977
16.9 Tests on On-Load Tap-Changers
16.9.1 Operation Test — After the tap-changer is fully assembled on the
transformer, the transformer manufacturer shall perform the following
tests [with the exception of (b)] at 100 percent of the rated auxiliary
supply voltage. These tests shall be performed without failure.
a) Eight complete operating cycle with the transformer not
energized;
b) One complete operating cycle with the transformer not
energized, with 85 percent of the rated auxiliary supply voltage;
c) One complete operating cycle with the transformer energized at
rated voltage and frequency at no load; and
d) Ten tap-change operations with ± 2 steps on either side of the
principal tapping with as far as possible the rated current of the
transformer with one winding short-circuited.
16.9.2 Auxiliary Circuits Insulation Test — After the tap-changer is
assembled on the transformer, a power frequency test shall be applied
to the auxiliary circuits as specified in IS : 2026 (Part III)-1977*.
16.10 Measurement of Zero-Sequence Impedance(s) of Three
Phase Transformers — The zero-sequence impedance is measured
at rated frequency between the line terminals of a star-connected or
zigzag-connected winding connected together and its neutral terminal.
It is expressed in ohms per phase and is given by 3 U/I where U is the
test voltage and I is the test current.
The phase test current I/3 shall be stated.
It shall be ensured that the current in the neutral connection is
compatible with its current carrying capability.
In the case of a transformer with an additional delta-connected
winding, the value of the test current shall be such that the current in
the delta-connected winding is not excessive, taking into account the
time of application.
If balancing ampere-turns are missing in the zero-sequence system,
for example, in a star-star-connected transformer without delta
winding, the applied voltage shall not exceed the line-to-neutral
voltage at normal operation.
The current in the neutral and the time of application however may
be limited to avoid excessive temperatures of metallic constructional
parts.
*Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
24
IS : 2026 (Part I) - 1977
In the case of transformers with more than one star-connected
winding and neutral terminals, the zero-sequence impedance
[ see 2.7.5 of IS : 1885 (Part XXXVIII)-1977* ] is dependent upon the
connections and the tests to be made shall be subject to agreement
between the manufacturer and the purchaser.
Measurements on windings with tappings shall be made on the
principal tapping. Measurements on other tappings may be made if
agreed between the manufacturer and the purchaser.
Auto-transformers with a neutral terminal intended to be permanently connected to earth shall be treated as normal transformers
with two star-connected windings. Thereby the series winding and the
common winding together form one measuring circuit, and the
common winding alone the other. The measurements shall be carried
out with a current not exceeding the difference between the rated
currents on the low-voltage side and the high-voltage side.
NOTE 1 — In conditions where the balancing ampere-turns are missing the relation
between voltage and current is generally not linear.
NOTE 2 — The zero-sequence impedance is dependent upon the physical disposition
of the windings and magnetic parts and measurements on different windings may
not therefore agree.
16.11 Short-Circuit Test
16.11.1 Condition of the Transformers Before the Short-Circuit Tests
16.11.1.1 Unless otherwise agreed, the tests shall be carried out on
new transformer ready for service. The mounting of accessories having
no influence on the behaviour during short circuit (for example,
detach- able cooling equipment) is not required.
16.11.1.2 Prior to the short-circuit tests the transformer shall be
subjected to the routine tests specified in 16.1.2.
If the windings are provided with tappings the reactance and, if
required, the resistance shall also be measured for the tapping
positions at which short-circuit tests shall be carried out.
All the reactance measurements shall be to a reproducibility of at
least ± 0.2 percent.
A report containing the results of the routine tests shall be available
at the beginning of the short-circuit tests.
16.11.1.3 At the beginning of the short-circuit test the average
temperature of the winding shall be between 0°C and 50°C.
*Electrotechnical vocabulary : Part XXXVIII Transformers ( first revision ).
25
IS : 2026 (Part I) - 1977
16.11.2 Peak Value î for Two-Winding Transformers — The amplitude
î of the first peak of the asymmetrical test current is calculated as
follows:
î = lk 2
where the symmetrical short-circuit current I is determind in accordance with 8.1.1.2 and 9.1.2.
The factor k 2 depends on the ratio X/R
where
X is the sum of the reactances of the transformer and the system
( Xt + Xs ), in ohm; and
R is the sum of the resistances of the transformer and the system
( Rt + Rs ), in ohms.
Unless otherwise specified the factor k 2 is limited to
1.8 2 = 2.55.
The following values of factor k 2 shall be used for different values
of X/R:
1.5 2
3
4
5
6
8
10
14
X/R 1
2.55
k 2 1.15 1.64 1.76 1.95 2.09 2.19 2.27 2.38 2.46
NOTE — For other values of X/R between 1 and 14, the factor k
determined by linear interpolation.
2 may be
For transformers of category 1 and Zs
0.05 Zt ( see 8.1.1.2 and
9.1.2 ) X and R are related to the transformer only ( Xt and Rt ). For
Zs > 0.05 Zt, on the other hand, X and R are related to the
transformer and the system ( Xt + Xs and Rt + Rs ).
0.05 Zt, instead of Xt and Rt (in ohms) ux and ur may be used
NOTE — When Zs
for the principal tapping, where
ux is the reactive component of uz, in percent;
ur is the resistance component, at reference temperature, of uz, in percent;
and
uz is the impedance voltage of the transformer, at reference temperature, in
percent.
16.11.3 Value and Duration of the Short-Circuit Test Current for
Two-Winding Transformers — The asymmetrical current having a
first peak of amplitude î (16.11.2) will change (if the duration of the
test current is sufficiently long) into the symmetrical current I (9.1.2).
The peak value of the current obtained in testing shall not deviate
by more than 5 percent and the symmetrical current by more than 10
percent from the specified value. The duration of the current for
shortcircuit tests is specified in 16.11.4.4.
26
IS : 2026 (Part I) - 1977
16.11.4 Short-Circuit Testing Procedure for Transformers with Two
Windings
16.11.4.1 In order to obtain a test current according to 16.11.3 the
no-load voltage of the source may be higher than the rated voltage of
the winding supplied. The short-circuiting of the winding may either
follow or precede (pre-set short-circuit) the application of the voltage to
the other winding of the transformer.
In the first case the voltage shall not exceed 1.15 times the rated
voltage of the winding.
If the pre-set short circuit is used for transformers with single
concentric windings, the supply should be connected to the winding
farther from the core, the winding nearer to the core being
short-circuited in order to avoid saturation of the magnetic core, which
could result in an excessive flow of magnetizing current being
superimposed on the short-circuit current during the first few cycles.
For transformers with sandwich windings or transformers with
double concentric windings the pre-set short-circuit method shall only
be used after agreement between the manufacturer and the purchaser.
16.11.4.2 To obtain the initial peak value of the current (16.11.2) in
the phase winding under test the moment of switching-on shall be
adjustable by a synchronous switch.
In order to check the value of the test currents î and I these currents
shall always be recorded by an oscillogragh. In order to obtain the
maximum asymmetry of the current in one of the phase windings the
switching-on shall occur at the moment the voltage of this winding
passes through zero.
NOTE 1 — For star-connected windings the maximum asymmetry is obtained by
switching-on when the phase voltage passes through zero. The factor k of the peak
value î can be determined from the oscillograms of the line currents. For there-phase
tests on delta-connected windings this condition is obtained by switching-on when
the line-to-line voltage passes through zero. One of the methods of determining the
factor k is by switching-on during the preliminary adjustment tests at a maximum of
the line-to-line voltage. In this case the factor k is found from the oscillograms of the
line currents.
Another method for determining the phase currents in a delta connected winding is
by suitably interconnecting the secondary windings of the current transformers
measuring the line currents. The oscillograph can be made to record the phase currents.
NOTE 2 — For transformers with star-zigzag connection belonging to category 1 and
with constant flux voltage variation, having a value for ux/ur < 3 ( see 16.11.2 ), the
three phases are switched-on simultaneoualy without the use of a synchronous
switch. For other transformers with star-zigzag connection the method of switching
on is subject to agreement between the manufacturer and the purchaser.
27
IS : 2026 (Part I) - 1977
16.11.4.3 For three-phase transformers, a three-phase supply should be
used, as long as the requirements given in 16.11.3 can be met. If this is
not the case a single-phase supply, as described below, may be used. For
delta-connected windings the single-phase supply is provided between
two corners of the delta and the voltage during the test has to be the
same as the voltage between phases during a three-phase test. For
star-connected windings the single-phase voltage is supplied between
one phase terminal and the other two phase terminals connected
together. The single-phase voltage during the test has to be equal to
3 ⁄ 2 times the voltage between phases during a three-phase test.
NOTE 1 — The use of the tests with single-phase supply applies mainly to
transformers of category 2 or 3 and is seldom of interest for category 1 transformers.
NOTE 2 — For star-connected windings with non-uniform insulation it is necessary to
check whether or not the insulation of the neutral is sufficient for single-phase testing.
NOTE 3 — If for star-connected windings the power supply is insufficient for the
single-phase testing described above and the neutral is available, the manufacturer
and the purchaser may agree upon the use of single-phase tests between a line
terminal and the neutral.
16.11.4.4 In the absence of any particular specification the number of
tests on three-phase and single-phase transformers is determined as
follows, not including preliminary adjustment tests carried out at less
than 70 percent of the specified current to check the proper functioning
of the test set-up with regard to the moment of switching-on, the
current setting, the damping and the duration.
For category 1 single-phase transformers the number of tests shall
be three, the duration of each test being 0.5 second with a tolerance of
± 10 percent. Unless otherwise specified each of the three tests on a
single-phase transformer with tappings is made in a different position
of the tap-changer, that is, one test in the position corresponding to the
highest voltage ratio, one test on the principal tapping and one test in
the position corresponding to the lowest voltage ratio.
For category 1 three-phase transformers the total number of tests
shall be nine, that is three tests on each limb, the duration of each test
being 0.5 second with a tolerance of ± 10 percent. Unless otherwise
specified the tests on each limb of a transformer with tappings are
made in different positions of the tap-changer, that is, three tests in
the position corresponding to the highest voltage ratio on one of the
outer limbs, three tests on the principal tapping on the middle limb
and three tests in the position corresponding to the lowest voltage
ratio on the other outer limb.
For transformers of categories 2 and 3, an agreement between the
manufacturer and the purchaser is always needed with regard to the
number of tests, their duration and the position of the tap-changer.
28
IS : 2026 (Part I) - 1977
16.11.4.5 In addition to the test of 16.11.4.4, when agreed between the
purchaser and the supplier, a test may be carried out at specified value
of short-circuit current in accordance with 8.1.1.2 and 9.1.2, for a
duration of two seconds. This test shall be carried out after performing
the test for dynamic ability to withstand short-circuit of 16.11.4.4. The
asymmetry of the test current shall be as minimum as possible. The
criteria for evaluation of test results shall be the same as that for the
test to determine the dynamic ability to withstand short-circuit.
16.11.5 Detection of Faults and the Evaluation of the Results of the
Short-Circuit Test
16.11.5.1 Before the short-circuit testing, measurements and tests
shall be carried out according to 16.11.1 and the gas relay (if any)
inspected. These measurements and tests serve as references for the
detection of faults.
16.11.5.2 During each test (including preliminary tests) oscillographic recording shall be made of the following:
a) The applied voltage (between line terminals), and
b) The currents ( see Notes 1 and 2 under 16.11.4.2 ).
Furthermore, the transformer under test shall be visually inspected.
NOTE — Additional means of detection may be used, such as oscillographic recording
of the radial stray flux by means of supplementary coils, information obtained from the
noise and, particularly, recording of the current between the tank (insulated) and earth.
16.11.5.3 After each test the oscillograms made during the test are
inspected, and also the gas relay. It is necessary to measure the shortcircuit reactance after each test.
NOTE 1 — Additional means of detection may be used, such as resistance
measurements, oscillograms of impulse voltages for comparison with oscillograms
obtained in the original state (recurrent surge oscillograph method) and a no-load
measurement (for detection of a short circuit between turns).
NOTE 2 — Any differences between the results of the measurements made before and
after the test may be a criterion for determining possible defects. It is of particular
importance to observe during successive tests possible changes in the reactance
measured after each test, which may be progressive or tending to a stable value.
16.11.5.4 After completion of the tests, the transformer and the gas
detection relay, if any, shall be inspected. The results of the shortcircuit reactance measurements and the oscillograms taken during the
different stages of the tests shall be examined for any indication of
possible anomaly during the tests, especially any indications of change
in the short-circuit reactance.
Different procedures are followed at this stage for transformers of
category 1 and categery 2 or 3 as under:
a) Transformers of category 1 — All the routine tests shall be
repeated. The dielectric routine tests shall be at 75 percent of the
29
IS : 2026 (Part I) - 1977
original test value unless a higher value has been agreed between
the manufacturer and the purchaser.
The transformer shall then be untanked for inspection of the core
and windings, in order to reveal possible apparent defects, such as
changes in lead position which, in spite of successful routine tests,
might endanger the safe operation of the transformer.
The transformer is deemed to have passed the short-circuit
tests if, firstly, the routine tests have been successfully repeated,
secondly, the results of the short-circuit tests, measurements
during short-circuit tests and out of tank inspection do not reveal
any defects (displacements, deformations of windings,
connections or supporting structures, or traces of discharge), and
thirdly, the short-circuit reactance measured after the tests
differs from that measured in the original state by not more than:
two percent for transformers with circular concentric coils.
However, for transformers having metal foil as a conductor
in the low-voltage winding, higher values, not exceeding 4
percent for transformers with an impedance voltage of 3
percent or more, may be agreed between the manufacturer
and the purchaser, or
7.5 percent for transformers with non-circular concentric
coils having an impedance voltage of 3 percent or more. The
value of 7.5 percent may be reduced by agreement between
the manufacturer and the purchaser, but not below 4 percent.
NOTE — For transformers with non-circular concentric coils having an
impedance voltage below 3 percent the maximum variation in reactance
cannot be specified in a general manner; practical knowledge of certain types
of construction leads to the acceptance for such transformers a variation
equal to (22.5 – 5Uz) percent, Uz being the impedance voltage in percent.
If the three conditions for passing the short-circuit tests have
been met, the transformer is restored to its original state and any
further routine tests necessary to prove fitness for service are
repeated before dispatch. If any of the three conditions have not
been met, it may be necessary to dismantle the unit as far as is
required to establish the cause of the change of the conditions.
b) Transformers of category 2 and 3 — By agreement between the
manufacturer and purchaser, a repeat of the routine tests,
normally carried out at this point, may be postponed until after
the inspection. The repeat of the dielectric routine tests shall be
at 75 percent of the original test value unless a higher value has
been agreed between the manufacturer and the purchaser.
30
IS : 2026 (Part I) - 1977
NOTE — If the transformer was originally subjected to dielectric tests in
accordance with Method 2 of IS : 2026 (Part III)-1981*, the voltage to be applied
for the induced power-frequency overvoltage test should be subject to agreement
between the manufacturer and the purchaser.
The transformer shall be untanked for inspection of the core
and windings and is deemed to have passed the short-circuit tests
if, firstly, the results of the short-circuit tests, measurements
during short-circuit tests, measurement of short-circuit reactance
and out of. tank inspection do not reveal any apparent defects
(displacements, deformations of windings, connections or
supporting structures, or traces of discharge) and, secondly, the
routine tests have been successfully repeated. Agreement between
the manufacturer and the purchaser is necessary concerning the
interpretation of any differences in the reactance measurements.
If either of the two conditions for passing the tests has not been
met, a more detailed examination may be required including, if
necessary, a partial or complete dismantling of the unit.
16.11.6 Clause deleted
16.12 Measurement of Acoustic Noise Level — The method of test
and criteria for conformity shall be agreed between the manufacturer
and the purchaser.
16.13 Measurement of the Harmonics of the No-Load Current
— The harmonics of the no-load current in all the phases are measured
by means of harmonic analyser and the magnitude of the harmonics is
expressed as a percentage of the fundamental component.
16.14 Measurement of Power Taken by the Fans and OilPumps — The method of test shall be agreed between the manufacturer
and the purchaser [ see also 4.7 of IS : 2026 (Part II)-1977†.
*Specification for power transformers: Part III Insulation levels and dielectric tests
( second revision ).
†Specification for power transformers: Part II Temperature-rise ( first revision ).
31
IS : 2026 (Part I) - 1977
APPENDIX A
( Clause 12.1 )
INFORMATION REQUIRED WITH ENQUIRY AND ORDER
A-1. RATING AND GENERAL DATA*
A-1.1 Two-Winding Transformers†
A-1.1.1 Normal — The following information should be given in all
cases:
a) Particulars of the specification to be complied with;
b) Type of transformer, for example, separate winding transformer;
auto-transformer or booster transformer;
c) Single or polyphase unit;
d) Number of phases in system;
e) Frequency;
f) Dry-type or oil-immersed type. If oil-immersed, whether mineral
oil or synthetic insulating liquid;
g) Indoor or outdoor type;
h) Type of cooling;
j) Rated power (in kVA) and, for tapping ranges exceeding ± 5
percent required power on extreme tappings;
If the transformer is to have different values of rated power for
different types of cooling, these should be stated.
k) Rated voltage (for each winding);
m) State if tappings are required and if no-load or off-circuit tapchangers, or links are required. Give the information required as
detailed in IS : 2026 (Part IV)-1977*;
n) Highest voltage for equipment (for each winding) [ see also
Appendix C of IS : 2026 (Part III)-1977† ];
p) Method of system earthing (for each winding);
q) Insulation level (for each winding), power frequency test level/
impulse level [ see IS : 2026 (Part III)-1977† ];
r) Connection symbol;
s) Neutral terminals, if required (for each winding) and their
insulation level to earth;
t) Special requirement of installation, assembly, transport and
handling;
u) Details of auxiliary supply voltage (for fans, tap-changer,
alarms, etc);
w) Fittings required and an indication of the side from which
meters, rating plates, oil-level indicator, etc, may be readable.
*Specification for power transformers: Part IV Terminal markings, tappings and
connections ( first revision ).
†Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
32
IS : 2026 (Part I) - 1977
A-1.1.2 Special — The following additional information may be
required to be given:*
a) If a lightning impulse voltage test is required, whether or not the
test is to include chopped waves [ see IS : 2026 (Part III)-1977* ];
b) Whether a stabilizing winding is required and, if so, the method
of earthing;
c) Impedance voltage at rated current, if specific value is required;
d) Whether transformer is to be connected to a generator directly or
through switchgear and whether it may be subjected to load
rejection conditions;
e) Altitude above mean sea-level, if in excess of 1 000 m;
f) Special cooling conditions, for example, temperature of cooling
medium if above or below values given in 3, or restrictions to
circulation of cooling air;
g) Whether unbalanced loading is anticipated, and if so details;
h) Whether transformers will be subjected to frequent overcurrents,
for example, furnace transformers and traction feeding transformers ( see 8 );
j) Details of intended regular cyclic overloading other than covered
by 4.1 (to enable the ratings of the transformer auxiliary equipment to be established);
k) Any other exceptional service conditions;
m) Connections required, ex-works, in the case of the transformer
having alternative winding connections;
n) Values of load and no-load losses, if specific values are required;
p) Short-circuit characteristics of the system ( see 8 and 9 );
q) Whether noise level measurement is to be carried out;
r) Vacuum withstand of the transformer tank, if a specific value is
required;
s) Type of tap-changer controls required;
t) Water analysis in case of OFWF cooled transformers; and
u) Any other appropriate information, including reference to any
special tests not referred to above which may be required.
A-1.2 Multi-Winding Transformers — Generally as in A-1.1, but
information in respect of the additional windings is required, and also:
a) required loading combinations, stating, when necessary, the
active and reactive outputs separately, especially in the case of
multi-winding auto-transformer; and
b) any impedance voltage that are specified for particular pairs of
windings.
*Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
33
IS : 2026 (Part I) - 1977
A-2. PARALLEL OPERATION
A-2.1 If parallel operation with existing transformers is required, this
should be stated and the following information given:
a) Rated kVA of existing transformers,
b) Rated voltage ratio,
c) Voltage ratios corresponding to tappings other than the principal
tapping,
d) Load loss at rated current and rated voltage on the principal
tapping corrected to the appropriate reference temperature,
e) Impedance voltage at rated current (on the principal tapping),
f) Short-circuit impedances at least on the extreme tappings if the
tapping range of the tapped winding exceeds ± 5 percent, and
g) Diagram of connections and connection symbol.
APPENDIX B
( Clause 13.1 )
SCHEDULE OF TECHNICAL PARTICULARS TO BE
FURNISHED BY THE MANUFACTURER
B-1. STANDARD FORM OF TECHNICAL PARTICULARS
1. Name of the manufacturer
2. Service
3. kVA rating:
a) HV winding
kVA
b) IV winding
kVA
c) LV winding
kVA
4. Rated voltage:
a) HV winding
kV
b) IV winding
kV
c) LV winding
kV
5. Rated frequency
Hz
6. Number of phases
7. Connections:
a) HV winding
b) IV winding
c) LV winding
34
IS : 2026 (Part I) - 1977
8. Connection symbol [ see IS : 2026 (Part IV)-1977* ]:
a) HV-IV
b) HV-LV
9. Tappings:
a) Range
b) Number of steps
c) For high voltage variation/For intermediate
voltage variation /For low voltage variation
10. Reference ambient temperatures:
a) Maximum ambient air temperature
b) Maximum daily average ambient air
temperature
c) Maximum yearly weighted average ambient
temperature
d) Minimum ambient air temperature
e) Maximum cooling water temperature
11. Type of cooling [ see IS : 2026 (Part II)-1977† ]
12. Temperature-rise [ see IS : 2026 (Part II)-1977† ]:
a) Top oil
b) Windings
13. Total loss at rated voltage at principal tapping
and rated frequency
14. Component losses:
a) No load loss at rated voltage on principal
tapping and at rated frequency
b) Load loss at rated current at principal tapping
at 75°C
15. Impedance voltage at rated current for the
principal tapping:
a) HV - IV
b) HV - LV
c) IV - LV
°C
°C
°C
°C
°C
°C
°C
kW
kW
kW
percent
percent
percent
NOTE — Item 11 to 15 are guaranteed particulars and are subject to tolerances as
specified in Table 7.* †
*Specification for power transformers: Part IV Terminal markings, tappings and
connections ( first revision ).
†Specification for power transformers: Part II Temperature rise ( first revision ).
35
IS : 2026 (Part I) - 1977
16. Reactance at rated current and rated frequency:*
a) HV - IV
b) HV - LV
c) IV - LV
17. No load current at rated voltage and rated
frequency
18. Input to cooling plant
19. Insulation level [ see IS : 2026 (Part III)-1977* ]:
a) Separate source power-frequency voltage
withstand:
i) HV winding
ii) IV winding
iii) LV winding
b) Induced overvoltage withstand:
i) HV winding
ii) IV winding
iii) LV winding
c) Full wave lightning impulse withstand voltage:
i) HV winding
ii) IV winding
iii) LV winding
d) Switching impulse withstand voltage:
i) HV winding
ii) IV winding
iii) LV winding
20. Stabilizing/Tertiary winding:
a) Rated voltage
b) Normal rating
c) Normal rating (expressed as percent of
main winding rating in the case of
stabilizing winding)
d) Delta closed inside/outside (In the case of
stabilizing winding)
percent
percent
percent
percent
kW
kV rms
kV rms
kV rms
kV rms
kV rms
kV rms
kV peak
kV peak
kV peak
kV peak
kV peak
kV peak
kV
kVA
percent
*Specification for power transformers: Part III Insulation levels and dielectric tests
( first revision ).
36
IS : 2026 (Part I) - 1977
21. Efficiencies at 75°C at unity power factor:
a) At full load
b) At 3/4 full load
c) At 1/2 full load
22. Regulation at full load at 75°C
a) At unity power factor
b) At 0.8 power factor lagging
23. Equipment for ONAN or ONAF/ONAN Cooling:
a) State:
i) Radiators on main tank
ii) Separate cooler bank
b) State ONAN rating in case of mixed cooling
24. Equipment for OFAF/ODAF cooling:
a) State:
i) Radiator bank
ii) Separate enclosed type coolers
b) State OFAN/ODAN, ONAF, ONAN rating (kVA)
whichever is/are applicable in case of mixed cooling:
i) OFAN/ODAN
ii) ONAF
iii) ONAN
25. Number of coolers or cooler banks per transformer.
26. Rating of each cooler or cooler bank
27. In case of OFF circuit voltage variation, state (a) or (b):
a) Off circuit tap switch
b) Off circuit links
28. Details of no-load tap-changer:
a) Make
b) Type
c) Rating:
i) Rated voltage
ii) Rated current
iii) Step voltage
iv) Number of steps
37
percent
percent
percent
percent
percent
IS : 2026 (Part I) - 1977
d) Control
e) Auxiliary supply details
f) Voltage control
g) Parallel operation
h) Protective devices
j) Approximate overall weight
k) Approximate overall dimensions
m) Approximate overall quantity of oil
kg
mm
litre
NOTE — The information against (j), (k) and (m) is required in case of separately
mounted and handled tap-changers.
29. Terminal arrangement:
a) High voltage
b) Intermediate voltage
c) Low voltage
d) Neutral
30. Approximate masses:
a) Core and windings
b) Tank, fittings and accessories
c) Oil
d) Total mass
31. Approximate quantity of oil required for
first filling
32. Approximate overall dimensions:
a) Length
b) Breadth
c) Height
33. Despatch details:
a) Approximate mass of heaviest package
b) Approximate dimensions of largest package:
i) Length
ii) Breadth
iii) Height
34. Untanking height
35. Reference standards
38
kg
kg
kg
kg
litres
mm
mm
mm
kg
mm
mm
mm
mm
IS : 2026 (Part I) - 1977
APPENDIX C
( Clause 14.1 )
FITTINGS
C-1. The fittings as given below shall be provided:
Sl No.
Item
Transformers to Which Fitted
1.
Inspection cover
Above 1 600 kVA
2.
Rating plate
All
3.
Terminal-marking plate
All
4.
Two earthing terminals
All
5.
Lifting lugs
All
6.
Drain valve with plug or cover plate 25 kVA and above
7.
Dehydrating breather
8.
Oil-level indicator with minimum
9.
Marking
All
10.
Thermometer pocket
All
11.
Oil-filling hole with cover
All
12.
Conservator
50 kVA and above for rated
voltage 11 kV and below,
and all ratings above 11 kV
13.
Air release device
All transformers fitted with
conservators
14.
Jacking lugs
Above 1 600 kVA
15.
Filter valve
Above 1 600 kVA
25 kVA and above for rated
voltage 11 kV and below,
and all ratings above 11 kV
NOTE — When filter valves are required, the drain valve should be used as one of
these.
39
IS : 2026 (Part I) - 1977
C-2. The additional fittings as given below may be provided, if ordered:
Sl No.
Item
Remarks
1.
Filter valves
1 600 kVA and below
2.
Rollers
Details of rollers to be stated
with enquiry or order
3.
Thermometer
Type to be stated
enquiry or order
4.
Additional thermometer pockets
To be stated with enquiry or
order
5.
Winding temperature indicator
Details of requirments to be
stated with enquiry or order
6.
Explosion vent
Details to be stated
7.
Gas- and oil-actuated relay
Type to be stated
8.
Skids
9.
Inspection cover
with
1 600 kVA and below
NOTE — The fittings listed in C-1 and C-2 shall conform to relevant Indian
Standards wherever they exist.
40
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 1986 to promote
harmonious development of the activities of standardization, marking and quality certification of
goods and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any
form without the prior permission in writing of BIS. This does not preclude the free use, in the course
of implementing the standard, of necessary details, such as symbols and sizes, type or grade
designations. Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Review of Indian Standards
Amendments are issued to standards as the need arises on the basis of comments. Standards are also
reviewed periodically; a standard along with amendments is reaffirmed when such review indicates
that no changes are needed; if the review indicates that changes are needed, it is taken up for
revision. Users of Indian Standards should ascertain that they are in possession of the latest
amendments or edition by referring to the latest issue of ‘BIS Catalogue’ and ‘Standards : Monthly
Additions’.
This Indian Standard has been developed by Technical Committee : ETDC 16
Amendments Issued Since Publication
Amend No.
Amd. No. 1
Amd. No. 2
Amd. No. 3
Date of Issue
January 1981
January 1983
October 1985
BUREAU OF INDIAN STANDARDS
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002.
Telephones: 323 01 31, 323 33 75, 323 94 02
Regional Offices:
Central
: Manak Bhavan, 9 Bahadur Shah Zafar Marg
NEW DELHI 110002
Eastern
: 1/14 C. I. T. Scheme VII M, V. I. P. Road, Kankurgachi
KOLKATA 700054
Telegrams: Manaksanstha
(Common to all offices)
Telephone
323 76 17
323 38 41
337 84 99, 337 85 61
337 86 26, 337 91 20
Northern : SCO 335-336, Sector 34-A, CHANDIGARH 160022
60 38 43
60 20 25
Southern : C. I. T. Campus, IV Cross Road, CHENNAI 600113
235 02 16, 235 04 42
235 15 19, 235 23 15
Western : Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093
832 92 95, 832 78 58
832 78 91, 832 78 92
BANGALORE.
BHOPAL.
BHUBANESHWAR.
COIMBATORE.
Branches : AHMEDABAD.
FARIDABAD. GHAZIABAD. GUWAHATI. HYDERABAD. JAIPUR. KANPUR. LUCKNOW.
NAGPUR. NALAGARH. PATNA. PUNE. RAJKOT. THIRUVANANTHAPURAM.
VISHAKHAPATNAM