NEC

"NATIONAL ELECTRICAL CODE." RULES AND REQUIREMENTS OF THlll lationsl Board of Fire Underwriters FOR THE INSTALLATION OF WIRING AND AP.PARATUS li'OR ELECTRIC LIGHT, HEAT AND POWER As Recommended by the UNDERWRITERS' NATIONAL ELECTRIC ASSOCIATION EDITION OF 1897. The National Electrical Code, as it is here presented, is the result of the united efforts of the various Electrical, Insurance, Architectural and allied interests which have, through the National Conference on Stand. ard Electrical Rules, composed of delegates from the following Associations, unanimously voted to recommend them to their respective Associations for approval or adoption: A-nc:an Institute of Atchit.Kts. AmeriCIIll Institute of Electrictal Engineers. Americtan Society of Mec:hanbl Engineers. Allleric:an Street Railway Association. factory Mutoal fire Insurance Companlos. Natloaal As&odation of fire Engineers. National Board of Fire Underwriters. National Electric light Association. Underwriters• National Electric Aendation. And as soon as meetings of these Associations are held, and action taken, the fact will be noted. GENER AL PLAN GOVERNING THE ARRANGEMENT OF RULES. CLASS A.-Central Stations, Dynamo, Motor and Storage-Battery Rooms, Transformer Sub-stations, etc. Rules I to II. CLASS B.-Outside Work, all systems and voltages. Rules 12 and 13. CLASS C.-Inside Work. Rules 14 to 39· Subdivided as follows ; Rules, applying to all systems and voltg・ョイセャ@ ages. Rules 14 to 17. Conatant·Current systems. Rules rS to 20. Constant·Poten!ial systems. All voltages. Rules 21 to 23. Voltage not over 300, Rules 24 to 31. Voltage between 300 and s,ooo, Rules 32 to 37• Voltage over 3,000. Rules 38 and 39· CLASS D.-Specifica tions for Wires and Fittings. Rules 40 to 55· s9. CLASS E.-Mlscel!an eous. Rules 56 to CLASS F.-Marine Wiring. Rules 6o to' 72, GENERAL SUOOESTIONS. In all electric work conductors, however well insulated, should always be treated as bare, to the end that under no conditions, existing or likely to exist, can a grounding or short circuit occur, and so that all leakage from conductor to conductor, or between conductor and ground, may be reduced to the minimum. In all wiring special attention must be paid to the mechanical execution of the work. Careful and neat running, connecting, soldering, taping of conductors and securing and attaching of fittings, are specially conducive to security and efficiency, and will be strongly insisted on. In laying out an installation, except for constantcurrent systems, the work should, if possible, be started from a center of distribution , and the switches and cut-outs, controlling and connected with the several branches, be grouped together in a safe and easily accessible place, where they can be readily got at for attention or repairs. The load should be divided as evenly as possible among the branches, and all complicated and unnecessary wiring avoided. The use of wire-ways for rendering concealed wiring permanently accessible is most heartily indorsed and recommend ed; and this method of accessible concealed construction is advised for genera.! use. Architects are urged, when drawing plans and specification s, to make provision for the channeling and pocketing of buildings for electric light or power wires, and in specification s for electric gas, lighting to require a'two-wire circuit, whether the building is to be wired for electric lighting or not, so that no part of the gas fixtures or gas piping be allowed to be used for the gas-lighting circuit, CLASS A. STATION S & DYNAMO ROOMS .. se.uo..a, Duft41111W, Mof.,. .. ,.,.. Bub-Btotions, Bte, .r-Bucleat oe ..eral 8torage Batteru Booms, TrGftlflj'o,.,_,. 1. Generatorsa. Must be located In a dry p'ace. セN@ Must never be placed in a room where any hazardous process is carried on, nor in places where they would be exposed to inflammable gases Ol' flyings of combustible materials. e. Must be insulated on floors or base framca, which must be kept filled to prevent absorption of moisture, and also kept clean and dry, Where frame insulation is .impracticable, the Inspection Department having jurisdiction may, in writing, permit its omission, in which case the frame must be permanently and effectively grounded. A high-potential machine which, I'D account of great weight or Cor other reasons, can not have its frame insulated from the I{I"OUnd, should be surrounded with an insulated platform. This may be made of wood, mounted on insulating supports, and so arranged that a man must always stand upon it In order to touch any (lart of the machine. In c:ase of a machme having an insulated frame, if there I• trouble from static electricity due to belt friction, it should be overcome by placing near the belt a meta!Uc comb connected with the earth, or by grounding the frame through a very bigh resistance of not less than aoo ohms per volt generated by the machine. tl. Every constant-potentia l generator must be protected from exceuive current by 111 safety fuse, or equivalent device, of approved design ln each lead wire, These devices should be placed on the machiM or ae near It aa_possible. Where the needs of the service make these devlcell lmpraeticable, tbe Inspection Department having jurisdiction ュ。ケLゥセF@ writing, modify the requirement&. 6 CLASS A.-STATIONS l. Generatere-Contlnued. e. Must each be provided with a waterproof cover. f. Must each be provided with. a name-plate, giving the maker's name, the capacity in volts and amperes, and normal speed in revolutions per minute. 2. ConductorsFrom generators to switchboards, rheostats or other instruments, and thence to outside lines. a. Must be in plain sight or readily accessible. 6. Must have an .approved insulating covering as called for by rules in Class "C" for similar work, except that in central stations, on exposed circuits, the wire which is used must have a heavy braided . non-combustible outer covering. Bus bars may be made of bare metal. &. Must be kept so rigidly in place that they c;an not come in contact. . d. Must in all other respects be. installed under the same precautions as required by rules in Class " C" for wires carrying a current of the same volume and potential. 8. Switchboards-a. Must be so placed as to reduce to a minimum the danger of communicating fire to adjacent combustible material. Si>ecial attention is called to the fact that switchboards should DOt be bullt down to the Boor, nor up to the ceiling, but a &!'Bee of at least ten or twelve inches should be left between tbe Boor and the board! and from· eighteen to twenty-four inches betWeen the cell ng and the 6oard in order to Jll:event fire from communicalinlil' from the switchboard to the Boor or ceiling, and also to prevent the formin.r of a panially concealed SI'&Ce very liable to be used for storage of rubbish and oily waste. 6. Must be made of non-c.ombustible material or of hardwood in skeleton form, filled to prevent absorption or moisture; AND DYNAMO ROOMS, ,. 8. Switchboards-Continued. c. Must be accessible from all. sides when the connections are on the back, but may be placed against a brick or stone wall when the wiring is entirely on the face. d. Must be kept free from moisture. e. Bus bars must be equipped in accordance ·with rules for pladng conductors. 4. Resistance Boxes and Equalizers( For constructitm rules, see No. ,52.) a. Must be placed on a switchboard or, if not thereon, at a distance of a foot from combustible material, or separated therefrom by a non-inflammable, non-absorptive, insulating material. 5. Lightning Arresters{Fflr constructWn rules, see No. ,5,5.) a. Must be attached to each side of every over. head circuit connected with the station. It is recomu11:nded to all electric light and power companies tbat arresters be connected .at interVllls over systems in such numbers and so located as to prevent ordinary discharge& entering (over the wires) buildings connected to tbe lines. IJ. Must be located in reacj.ily accessible places away from combustible materials, and as near as practicable to the point where the wires enter the building. Station arresters should generally be placed in plain sight on the switchboard. In all cases, kinks, coils and sharp bends in the wires between the arresters and the out-door lines must be avoided as far as possible. • c. Must be connected with a thoroughly good and permanent ground connection. by metallic strips or wires having a conductivity not less than that of a No. 6 B. & S. copper wire, which must be run as nearly in a straight line as.possible from the arrestera to the earth connection. · · 8 CLASS A.-STATIONS, 5. Lightning Arresters-Continued. Ground wires for lightning arresters must not be attached to gas pipes within the buildings. It is often desirable to introduce a choke coil in circuit between the arresters and the dynamo. In no case should the arrester be put into iron pipes, ground wire from a ャゥセィエョァ@ as these would tend to Impede the discharge. 6. Care and Attendancea. A competent man must be kept on duty where generators are operating. b. Oily waste must be kept in approved metal cans and removed daily. Approved waste cans shall be made of metal, with legs raising can three inches from the floor, and with self-closing covers. 7. Testing of Insulation Resistancea. All circuits must be provided with reliable ground detectors. Detectors which indicate continuously, and give an instant and permanent indication of a ground are preferable, Ground wires from detectors must not be attached to gas pipes within the building. b. Where continuously indicating detectors are not feasible, the circuits should be tested at least once per day, and preferably oftener. c. Data obtained from all tests must be preserved for examination by the Inspection Department · having jurisdiction. These rules on testing to be applied at such l_liaces as may be designated by the Inspection Department havmg jurisdiction. 8. Motorsa. Must be insulated on floors or base frames, which must be kept filled to prevent absorption of moisture; and must be kept clean and dry. Where frame insulation is impracticable the Inspection Department having jurisdiction may, in writing, permit its omission, in which case the frame must be permanently and effectively grounded. MOTORS. 9 8. Motors-Continued. A hla"h-potential machine which, on account of great weight or for other reasons, can not have its frame Insulated, shoUld be surrounded with an insulated platform. This may be made of wood, mounted on insulating supports, and so arranged that a man must stand upon it in order to touch any part of the machine. In case of a machine having an insulated frame, if there is trouble from static electricity due to belt friction, it should be overcome by placing near the belt a metall1c comb connected to the earth or by grounding the frame through a very high resistance of not less than 200 ohms per volt generated by the machine. · II. Must be wired under the same precautions as required by ndes in Class "C", for wires carrying a current of the same volume and potential. The leads or branch circuits should be designed to carry a current at least fifty per cent greater than that required by the rated capacity of the motor to provide for the inevitable overloading of the motor at times without over-fusing the wires. c. The motor and resistance box must be protected b:y a ·cut-out and controlled by a switch (see No. 17 a), said switch plainly indicating whether '' on " or '' off". Where one-quarter horse-power or less is used on low-tension c1rcuits a single-pole switch will be accepted. The switch and rheostat must be located within sight of the motor, except in such cases where special permission to locate them elsewhere is given, in writing, by the Inspection Department having jurisdiction. d. Must have their rheostats or starting boxes located sci as to conform to the require11;1ents of Rule 4· In connection with motors the nse of circuit breakers\ automatic starting boxes and automatic under-load switcnes is recommended, and they must be used when required. e. Must not be run in series-multiple or multi-pleseries. • f Must be'covered with a waterproof cover when not in use, and, if deemed necessary by the Inspection Department having jurisdiction, must be inclosed in an approved case. From the nature o( the question the decision as to what is an approved case must be left to the Inspection Department having jurisdiction to determine in each 1nstance. IO CLASS A.-STATIONS. 8. Motors-Continued. g. Must, when combined with· ceiling fans, be hung from insulated hooks, or else there must be an insulator interposed between the motor and its support. h. Must each be provided with a name-plate, giving the maker's name, the capacity in volts and amperes and the normal speed in revolutions per minute. 9. Railway Power Plantsa. Must be equipped in each feed wire before they leave the station with an approved' automatic circuit breaker (see No. 44) or other device, which will immediately cut off the current in case of a ground. This device must be mounted on a fireproof base, and in full view and reach of the attendant. 10. Storage or Primary Batteriesa. When current for light and power is taken from primary or secondary batteries, the same general regulations must be observed as applied セ@ similar apparatus fed from dynamo generators developing the same difference of potential. 6. Stotage battery rooms must be thoroughly ventilated. c. Special attention is directed to. the rules for rooms where acid fumes exist. (See No. 24, j and .k.) . d. All secondary batteries must be mounted on non-absorptive, non-combustible insulators, such as glass or thoroughly vitrified and glazed porcelain. e. The use of any metal liable to corrosion must be avoided in connections of secondary batteries. 11. Transformera(For construction rules, su No. 54.) a. In central or sub-stations the tra·nsformers must be so placed that smoke from the burning out of the coils or the boiling over of the oil (where oil filled cases are used) could do no harm. Cuss B. OUTSIDE WORK. セ@ s•• ,..... - · ,..••..,... 18. Wires. o. Service wires must have an approrllti rubber insulating covering. (.See No. 40 a.) Line wires, other than services, must have an appror;tt/ weatherproof, or rubber insulating covering. (See No. 40 a and b.) All tie wires must have an insulation equal to that of the conductors they con.tine. IJ. Must be so placed tbat moisture can not form a cross connection between them, not less than a foot apart, and not in contact with any substance other than their insulating supports. Service blocks must be covered over their entire surface with at least two coats of waterproof paint. &, Must be at least seven feet above the highest point of fiat roofs, and at least one foot above the ridge of pitched roofs over which they pass or to whit;h they are attached. d. Must be protected bf dead insulated guard, iron or wires from possibility of contact with other conducting wires or substances to which current may leak. Special precautions of this kind must be taken where sharp angles occur, or where any wires might possibly come in contact with electric · light or power wires. 1. Must be provided with petticoat insulators of glass or porcelain. Porcelain knobs or cleats and rubber boob will not be approved. f. Must be so spliced or joined as to be both mechanically and electrically secure without solder. to insure preserThe joints must then be ウッャ、セ・イL@ vation, and covered with an insulation equal to that on the conductors. CLASS B. 12 l2. Wires-Continued. All joints must be soldered, even ii made with some form of patent splicing device. This ruling applies to joints .and eplices in all classes of wiring covered by these rules. g-. Must, where they enter buildings, have drip loops outside, and the holes through which the con-dudors pass must be bushed with non-combustible, non-absorptive Insulating tubes slanting upward t.>ward the inside. A. Telegraph, telephone and similar wires must not be placed on the same cross-arm with electric light or power wires. i. The metallic sheathes to cables must be permanently and effect!vely connected to "earth". Tli.OLLEY WIRES, j. Mu1t not be smaller than No. o B. & S. copper or No. 4. '3. & S. silicon bronze, and must readily stand the strain put upon them when in use. 14. Must have a double insulation from the ground. In wooden pole construction, the pole will be considered as one insulation. I. Must be capable of being disconnected at the power plant, or of being divided into sections, so that, in case of fire on the railway route, the current may be shut off from the particular section and not interfere with the work of the firemen. This rule also applies to feeders. m. Must be safely protected against accidental contact where crossed by other conductors. Guard wires should be insulated from the ground and should be electrically disconnected in sections of not more than soo feet in length. GROUND RETURN WIRES, n. For the diminution of electrolytic corrosion of underground metal work, ground return wires must be so arranged that the difference oi potential between the grounded dynamo terminal and any point on the return circuit will not exceed twenty-five volts. OUTSIDE WORK. 13 12. Wir.u-Contlnued. It is suggested that the positive pole of the dynamo be Cl>Jl• nected to the trolley line, and that whenever pipes or other underground metal work are found to be electriCally positive to the raile or surrounding earth. that they be connected b-, conductore arralljfed so as to prevent as far as possible current Jlow from the pipes into the ground. 18. Tranaformera(For eonstruetion イセャ・ウL@ see No. 54.) a. Must not be placed inside of any building, excepting central stations, unless by special permission of the Inspection Department having jurisdiction. !J. Must not be attached to the outside walls of buildings, unless separated therefrom by substantial supportll, CLASS c. INSIDE WORK. GENERAL RULES-ALL SYSTEMS AND VOLTAGES. 14. Wirea(For special rules, set Nos• .18, 114, 32, .]8 and .1'1•) a. Must not be of smaller size than No. 14 B. & S., except as allowed under Rules 24 u and 4oe. 6. Tie wires must have an insulation equal to that of the conductors they confine. e. Must be so spliced or joined as to be both mechanically and electrically secure without solder ; they must then be soldered to insure preservation, and the joint covered with an insulation equal to that on the conductors. Stranded wires must be soldered before being fastened under clamps or binding screws, and, when they have a conductivity greater than No. Io · copper wire, they must be soldered into & · lugs. a. s. All joints muat be soldered, even if made with some form of patent spUclng device. ThiS rullnJr appUes to joints and spbc:es m all cl&sses of wiring covered by theBe rules. d. Must be separated from contact with walls, floors, timbers or partitions through which they may pass by non-combustible, non-absorptive insulating tubes, such as glass or porcelain. BPbiila-a must be long enough to bush the entire lenJtth of the bole in one continuop piece, or else the hole must first be bushed by a continuous .waterproof tube, wbich may be a conductor, such as iron p1pe; the tube then is to have a nonconducting bushing rushed in at each end so as to keep the wire absolutely out o contact with the conducting pipe. INSIDE WORK. IS 14. Wires-Continued. e. Must be kept free from contact with gas, water or other metallic piping, or any other conductors or conducting material which they may cross, by some continuous and firmly fixed non-conductor, creating a separation of at least one inch. Deviations from this rule may sometimes be allowed by special permission; f. Must be so placed in wet places that an air space will be left between conductors and pipes iu crossing, and the former must be run Ia such a way that they can not come in contact with the pipe accidentally. Wires shonld be run over, rather than under, pipes upon which moisture is likely to gather or which, by leaking, might cause trouble on a circuit, 11. Ulderground Conduotoraa. Must be protected, when brought into a building, against moiature and mechanical injury, and all comJ>ustible material must be kept removed from the immediate vicinity. IJ. Must not be so arranged as to shunt the current through a building around any catch-box. 18. Table of Carrylag Capaolty of WlreaBelow is a table showing the allowable carrying capacity of wires containing ninety-eight per cent pure copper. which must be followed in placing interior conductors: !6 GENERAL lWLES. 16. Table of Carrying Capacl!y of Wires-Continue d. TABLE B. TA.BLK A. Weatherproof Wires. Rubber Covered Wires. See No. 40 /J. See No. 40 ,., Amperes. Amperes. B. & S. G. AセZGN@ :. :::::: :· ::: t:::::::::::::.: :::::: i X.f••••• ••••••••••••• ... xoa ••••• .................. 8 .................. . .. 6 .......... . $ .................. . .. 54 ................. ... 77 9• 6s .................. ... 4 ................. .. 76 .................. .... no 90 .................. .... QSセ@ 3 .................. .. . 11 •••••••••• ••·•••••••• • •• 1 •••• ....... MセN@ •07 ................ ... •s6 "'7 .................. .... •Bs o ................... .. . ••••• セN@ 16 23 a4········· ............ 3• .······ 40 33··············•· 46 ................ .. 6s JO . . . . . . . . . . . . . •••••···· CJO 12••••••••••••··•• •••••• 17 .. •••• ................ • •••••••• 1 5 0 " " ' " ' " " " " " ' " " ' ROO 177 .................. ... •62 . ................... ... 31a エセクッ@ oao .•.. . ······ (lOOO . . . . . . . . . . . Circular Mills. . .. • .. • • .. • .. • """·.... •• .. • .. .. .. . • .. «10.000 • • • ]00,000 o 0 I 0 I I I I I I 0 I I I I I I I o I 2701 400,000 .................. ... ::·::::::: =:::.::·:·::::: )'OCI,oao ........ .......... セ[ZᄋN@ w........... 0 I I 0 I I I I 0 o I I 0 • o 0 o 0 I I I 300 400 500 セ@ soo .... ,.... 76o ll:>o,oao ........ · ......... •.. 550·.... .. ....... " • . .. • 840 セ@ ::::::::::: 1,::::::::::::: J,roo,ooo.... ••• • . . . • • • • ]ZセNL@ 6go ................ セ@ .... . 1.,o1Jo 1,15o 730· • .......•. t,aoo,ooo.... Y,220 1,300.000·... . . . . . . . . . . ' . . . 770· ··'·290 .... . 810... . . .. 1,400.000· ••..•. 8so ..• •o. • • • • • • • • • • • • • . r,36o t,soo,ooo o • • • • o. . •. . ••• .••••• 8QO ............... ...... 1,43o 1,6oo,ooo . ••••••••.. セᄋ@ o 0.. .. .... ..... I. • • J,,OO,OOOo 1 01 •• I •••••••••• 0 ••• I ... • • I..-...... I..... oo • ••••• • o • 1 •• ••••••••••••••••• • I o o ooo• Q30oo 11o10 oooo o oot o 0 o 1 o• ,1,4-qO l sso • 970 1:61o セZ@ o. I,t"xo ·': ·:. セZ@ セZ@ Zセ[@ ..•.• :a,ooo,ooo ... •• , ; .••• セ@ ......... ᄋセ@ x,oso •................... .... 1,670 コLqoッセMᄋ@ I,Soo.ooe» .• 0 •••• 1 •••••••• The lower limit is specified for rubber-cnvered wires to prevent rradual deterioration of the high insulations by tbe beat of tbe wires, but not from fear uf ignltlnl!' tbe insulation. Tbe question of drop is not taken anto consideration in tbe above tables. Tbe carrying capacity of sixteen and eil!'bteen wire is セイゥカ・ョL@ but no smaller than fourteen is to be used, u:cept u allowed under Rules 114 ,. and 40 e. INSIDE WORK. 17. Switches, Cut-outs, Circuit bイ・。ォNョセL@ Eto.- (For construction rules, see Nos. 43, 44 and 45.) a. Must, whenever called for, unless otherwise provided (for exceptions see No.8& and No. 22&), be. so arranged that the cut-outs will protect, a.nd the opening of the switch or circuit breaker will disconnec t, all of the wires; that is, in a two-wire system the two wire11, and in a three-wire system the three wires, .must be protected by the cut-out and disconnec ted by the operation of the switch or circuit breaker. IJ. Must not be placed in the immediate viduity of easily ignitible 11tuff or where exposed to inflammable gases or dust or to flyings of combustib le material. c. Must, when exposed to dampness , either be inclosed in a waterproo f box or mounted on porce· lain knobs.' CONSTANT-CURRENT SYSTEMS. Pt'i.. 」ゥーセFャヲ@ 18. Wirea- Berie• .f.2'c LighH'Ag. (See also Nos. r4, I5 aml r6.) a. Must have an approved rubber insulating covering. (See No. 40 a.) 6. Must be arranged to enter and leave the builddouble-co ntact service ing through an 。ーイッカセ、@ switch (see No. 43), mounted in a non-combu stible case, kept free fronl moisture, and easy of access to police or firemen. So-called "snap switches " must not be used on high-poten tial circuits.• e. Must always be in plain sight, and never incased, except when reqreirt'd by the Inspeclion Departme nt having jurisdictio n. d. Must be supported on glass or porcelain inwhich separate the wire at least one inch セ[オャ。エッイウLN@ from the surface wired over, and must be kept 18 CONSTANT CURRENT. 18. Wires-Continued. rigidly at least eight inches from each other, except within the structure of lamps, on hanger-boards, in cut-out boxes, or like places, where a less distance is necessary. '· Must, on side walls, be protected from mechanical injury by a substaatial boxing, retaining an air space of one inch around the conductors, closed at the top (the wires passing through bushed holes), and extending not less than seven feet from the door. When crossing floor timbers in cellars or in rooms, where they might be exposed to injury, wires must be attached by their insulating supports to the under side of a wooden strip not less than one-half an inch in thickness. 19. Aro Lampe(For t:IJtlltru&tion ,.ules, ue No. 19·) a. Must be carefully isolated from inflammable material. II. Must be provided at all times with a glass globe surrounding the arc, securely fastened upon a closed base. No broken or cracked globes to be used. ' t:. Must be provided with a wire netting (havin{ a mesh not exceeding one and one-quarter inches) around the globe, and an app,.o11etl spark arrester (see No. so), when readily inflammable material is in the vicinity of the lamps, to prevent escape of sparks, melted copper or carbon. It is recommended that plain carbons, not copper-plated, be used for lamps in such places. to Arc lamps, when used in places where thev are セウ・、@ lly!vgs of easily intlammable material, should have the carbons inclosed completely in a globe in such manner as to avoid the necessity for spark arresters. For the present, globes and spark arresters will not be required on so-called " inverted arc " lamps, but thia tTP.e of lam!' must not be used where a posed to llyings of easily uula.mmable material$. INSIDE WORK. 19. Arc Lamps-Continued. d. Where hanger-boards(see No. 48)are not used, lamps must be hung from insulating supports other than their conductors. 2U. Incandescent Lamps In Series Circuitsa. Must have the conductors installed as provided in Rule No. IS, and each lamp must be provided with an automatic cut-out. 6. Must have each lamp suspended from a hangerboard by means of rigid tube. c. No electro-magnetic device for switches and no system of multiple-series or series-multiple lighting will be approved. d. Under no circumstances can they be attached to gas fixtures. CONSTANT-POTENTIAL SYSTEMS. GENERAL RULES--ALL voltageセ@ 21. Automatic Cut-outs (Fum and Circuit Breakrz.) (See No . .r7, a11d for construction, Nos. 44 and 45·) a. Must be placed on all service wires, either overhead or underground, as near as possible to the point where they enter the building and inside the walls, and arranged to cut off the entire current from the building. · Where the switch required by rule No. '"' is inside tho build· iog, the 」オエセ@ required by thas section must be placed so as to protect it. 6. Must be placed at every _point where a change is made in the size of wire Lunless the cu.t-out in the larger w.ire will protect the smaller. (See No. 16)]. c. Must be in plain sight, or Inclosed in an approZJed box (see No. 46), and readily accessible. They must not be placed in the canopies or shells of fixtures. 20 CONS TANT POTE NTIA L. :.ll. Auto111atlc Cut-outs-Continued. desce nt tl. Must be so place d that no set of incan re .or sever al lamp s, whet her grou ped on- one fixtu nt of more fil'tu res or pend ants, requi ring a curre t upon one cutthan six ampe res shall be depe nden in writi ng out. Spec ial perm issio n may be given juris dicti on by the Inspe ction Depa rtme nt havinofg large chan for depa rture from this rule in case delie rs. rated capac e. Must be provi ded with fuses , theable carry ing ity of whic h does not excee d the allow break ers are capac ity of tbe wire, and, when ctrcu it abou t thirty used, they must not be set more than ing capac ity of per cent abov e the allow able carry insta lled in the wire, unles s a. fusible cut-o ut is also the circu it (see No. 16). 22. Switobas- (su No. I7, and for cpnstrudi.Dn, No. 4!1•) ce wires, eithe r a. Must be place d on all servi ly acces sible _overhead or unde rgrou nd, in a readi wher e the place, _as near as possible to the point to cut off wires enter the build ing, and arran ged the entir e curre nt. sible place1, IJ. Must alwa ys be place d in dry, acces switc hes and be grou ped as far as possible. Knife to open must be so place d that grav ity will tend rathe r than close the switc h. the circ. Must not be singl e-pol e, excep t whenthan six cuits whic h they contr ol supp ly not more alent . 16 cand le-po wer lamp s or their equivhes are used , d. Whe re gang s of flush switc the switc he1 whet her with cond uit syste ms or not, ed of or lined must be inclo sed in boxe s cons truct two or more with fire resis ting mate rial. Whe re, the box must switc hes are place d unde r one plate switc h. No have a separ ate comp artm ent for each its or the push butto ns for bells, gas light ing circuplate with Uke shall be place d in the aame orwall powe r wirin g. switc het contr ollin g elect ric light INSIDE WORK. 21 28. Eleotrlo Heatersa. Must, if stationary, be placed in a safe situation, isolated from inflammable materials and be treated as sources of, heat. IJ. Must each have a c.ut-out and indicating switch lsee No. 17 a). · c. Must have the attachments of feed wires to the heaters in plain sight, easily accessible and protected from interference, accidental or otherwise. d. The flexible conductors for portable. apparatus, such as irons, etc., must have an appr11ved insulating covering (see No. 40 c, 3). e. Must each be provided with name plate, giving the maker's name and the normal capacity in volts and amperes. LOW-POTENTIAL 6VSTEMS. 300 VoLTS 011. LEss. Any "circuit at/acned to a11y nzacMne, or &111Nfli-ti,,. of macnines, wAi,·A deve/qps a difference ef polnltwo 'Wires, 11f wer tell vo/11 and titll, Oj・ャキセョ。ケ@ kss tnan .JOO flo/is, sna/1 /Je considered IJS 1J loft•potentia/ ciuuil, and as cominr und"r tile class, un/us a11 approved transforminr deviu is エセウ・ゥL@ 'lunicn cuts tne difference ofpotential tiO'Wn to tm w1ts or less. The primary .-in:uit not to exceed a potmtial of .J,ooo volts. 24. WiresGENERAL RULES, (See al.r11 Nos. I</. I5 and r6.) a. Must not be laid in plaster, cement or elmilar finish. b. Must never be fastened with staples. distance, c Must not be fished for any セイ・。エ@ aud only in places where the Inspector can satisfy him11elf that the rules have been complied with. 32 LOW CONSTANT-POTENTIAl., 24. Wires-Continued. tl. Twin wires must never be used, except in conduits, or where flexible conductors are necessary. e. Must be protected on side walls from mechanical injury. When crossing ftoor timbers in ceilars or in rooms, where they might be exposed to injury, wires must be attached by their insulating suppprts to the under side of a wooden strip, not less than one-half Inch in thickness, and not less than three inches in width. Suitable protection on side walls may be secured by a eubstantial boxing, retaining an airspace of one inch around the conductor, closed at the top (the wires passing through bU8hed holes) 1 and extending not less than five feet fi'OID the floor; or by an Jron-armored or metal-sheathed insulating conduit aufliclently atrong to withstand the strain it will be subjected to; or plain. metal J)ipe, lined with insulating エオ「ゥョセイL@ which must extend one-half inch beyond the end of tne metal tube. The pipe must extend not less than ·five feet above the floor, and may extend through the ftoor in place of a floor bushing. U iron pipes are used wlth alternating currents, the two or more wires of a circnit ,.,..., be placed in the same conduit. In this case the inwlation of each wire must be re-inforced by a tough conduit tubing projecting beyond the ends of the iron pipe at least two inches. f. When run immediately under roofs, or in proximity to water tanks or pipes, will be considered as exposed to moisture. SPECIAL RULES, For open work : In Dry Plaus: g. Must have an approved rubber or weatherproof insulation. (See No. 40 a and 6.) A. Must be rigidly supported on non-combustible, non-absorptive insulators, which separate the wire at least one-half inch from the surface wired over, and they must be kept apart at least two and onehalf inches. ; Rigid supporting requires under ordinary conditions, where wiring along fiat surfaces, supports at least every four and one-half feet. If the wires are liable to be disturbed, the distance between wpports ebould be shortened. In building• of INSIDE WORK 24. Wires-Continued. mill construction, mains of No. 8 B. & 5. wire or over, where not liable to be disturbed, may be separated about four- inches, and run from timber to timber, not breaking around, and may be supported at each timl>er only. This rule will not be interpreted to forbid the Jllacing of the neutral of a three-WJre system ill the center ot a three-wire 」ャ・。セ@ proYided the outside wires are separated two and onehalf niches. It1 damp places, suck as B,.ewerils, Paclti"C Houses, Sla/Jies, Dye Houus, Pape,. w Pulp Mills, o,. !Juildi"Cs specially /ia!Jie to ュッゥウエオセ・@ w aeid w olke,- .funus /ia!Jie to in;u,.e Ike wi,.u o,. tkei,. insulation, except wke,.e used.fw pu;uia•ls: i. Must .have an app,.oved rubber insulating covering (see No. 40a). j. Must be rigidly supported on non-combustible, non-absorptive insulators, which separate the wire at least one inch from the surface wired ov¢r, and they must be kept apart at least two and one-half inches. · Rigid ウオセッイエャョァ@ requires under ordinary condltloiiS, where wiring over llat surfaces, supports at least every four and onehalf feet. If the wires are liable to be disturbed, the distance between supports should be. shortened. In buildings of mill construction, mams of No. 8 B. & 5. wire or over, where not liable to be disturbed, may be separated about four inches and run from timber to timber, not breaking around, and may be supported at each timber only. k. Must have no joints or splices. For moulding work: I. Must have o.pprD'IIed rubber insulating cov11:ring (see No. 40a}. m. Must never be placed in moulding In concealed or damp places. For conduit work: "· Must have an app,.D'IIed rubber insulatklg covering(see No. 40e). The use of concentric, wire (see No. 40 e) is recommended in preference to twin conductors. o. Must not be drawn in until all mechanical work: on the building bas been, as far as possible, completed. LOW CONSTANT-l'OTENTIAL, セTN@ Wires- -::ontlnued. p. Must not have wires of different circuits drawn in the same conduit. q. Must; for alternating systems, have the two or more wires of a circuit drawn in the same conduit. It is advised that this be done for direct-current 。ケウセ・ュ@ also, so that ther, may be changed to alternating systems at any time, tnduct on troubles preventing such a chalige unless thi8 construction is followed. For SO•,cilled Concealed work : ""· Must have an approvi!tl rubber insulating covering (see No. 40a). s. Must be rigidly supported on non-combustible, non-absorptive insulators which separate the wire at least one inch from the surface wired over, and must be kept at least ten inches apart, and, when possible, should be run singly on separate timbers or studding. Rigid supporting requires under ordinary conditions, where wiri • JC along flat surfaces, supportll ·at least every four and ッョセィ。ャヲ@ feet •. If the wires are !!•Ale to be disturbed, the distance between supports should セ@ sbonened. t. When from the nature of the case it is imposc;ible to place concealed wiring on non-combustible insulating supports of glass or porcelain, the wires, if not exposed to moisture, may be fished on the loop system if incased throughout in approved continuous flexible tubing or conduit. (See page 45.) For fixture work: u. Must have an approvi!tl rubber insulating covering (see No. 40 d), and shall not be less in size than No, xB, B. & S. · v. Supply conductors, and especially the splices to fixture wires, must be kept clear of the grounded part of gas pipes, and, where shells are used, the latter must be constructed in a· manner affording sufficient area tn aJiow this requirement. w. Must, when fixtures are wired outside, be so secured as not to be cut or abraded by the pressure of the fastenings or motion of the fixture. INSIDE WORK.. 25. Interior Conduits_(&e also Nos. 24- n t11 tJ, and 4r.) The object of a tube or conduit is to facilitate the Insertion or extractiOn of the ·conductors to protect them from mechanical mtury and, as far as possible. from moisture. Tulles or condwts are to be considered merely as raceways, and are not f.O be relied upon for insulation between w1re and wire, or between the mre and tlie ground. a. Must be continuous from one junction box to another or to fixtures, and the conduit tube must properly enter all fittings. 6. Must be first instal1ed as a complete conduit system, without the conductors. e. Conduits must extend at least one-half inch beyond the finished surface of walls or ceilings, except that, if the end is threaiied and a coupling screwed on, the conduit may be left flush with the surface, and the coupling may be removed when work on building is completed. d. Must, after conductors are introduced, have all outlets plugged with special wood or fibrous plugs, made in parts, and the. outlet then sealed with approved compound. Joints must be made airtight and moisture proof. e. Mu11t have the metal of the conduit perma-· nently and effectually grounded. 00. Fixturea(See also No. 24" tow.] a. mオセエL@ when supported from the gas piping of a building, be insulated from the gas-pipe system by means of approved insulating joints (see No. 51) placed as close as possible to the ceiling. · It is recommended that the gas outlet pipe be protected above the insulating joint by a non·combustible, non-absorptive insulating tube, having a tlange at the lower elid where it comes in contact with the insulating joint; and that, where outlet tubes are used, they be of sufficient length to extend below the insulating joint, and that they be so secured, that they will not be pushed back when the canopy is put in place. Where iron ceilings are used, care must be tali:en to see that the canopy is thoroughly and permanently insulated from the ceiling. 26 LOW CONSTANT-POTENTIAL. 26. Fixtures-Continued. IJ. Must have all bur;S, or fins, removed before the conductors are drawn into the fixture. e. The tendency to condensation within the pipes upper should be guarded against by sealing セィ・@ . end ofthe fixture. tl. No combination fixture in which the conductors are concealed in a space less than one-fourth inch between the inside pipe and the outside casing will be approved. e. Must be tested for "contacts" between conductors and fixtures, for "short circuits" and for ground connections before it is connected to its supply conductors. f. Ceiling blocks of fixtures should be made of insulating material ; if not, the wires in passing through the plate must be surrounded with noncombustible, non.-absQcptive, insulating material, such as glass or porcelain. 27. Sookets(For t:onstrw:tion ,.ules, see No. 47.) a. In rooms where inflammable gases may exist the incandescent lamp and socket must be inclosed in a vapor-tight globe, and supported on a piJ?ehanger, wired with approved rubber-covered w1re (See No. 40 a) soldered directly to the circuit. IJ. In damp or wet places, or over specially inflammable stuff. waterproof sockets must be used. When waterproof sockets are used, they should be hung stranded rubber-covered wires, not smaller than '!IY 。セイエ・@ No. •4 B. & S., which should preferably_ be twisted together when the drop is over three feet. These wires shoUld be soldered direct to the circlut wires; but supported illdepend- ently of them. 28. Flexible Corda. Must have an apprll'lml insulation and covering. (See No. iJOt:.) IJ. Must not be used as a support for clusters. e. Must not be used except for pendants, wirins of fixtures and portable lamps or motors. INSIDE, WORK. 27 .28. Flexible Cord-Continued. d. Must not be used in show windows. e. Must be protected by insulating bushings where the cord enters the socket. /. Must be so suspended that the entire weight of the socket and lamp will be borne by knots under the bushing in the socket, and above the point where the cord comes through the ceiling block or rosette, in order that the strain may be taken from the joints and binding screws. 29. Arc Lights on Low-Potential Circuitsa. Must have a cut-out (see No r7a) for each lamp or each series of lamps. The branch conductors should have a carrying i:apaclty about fifty per cent in excess of the normal current required by the lamp to ·provide for heavy current required when lamp is started or when carbons become stuck without over-fusing the wires. b. Must only be furnished with such resistances or regulators· as are inclosed in non-combustible material, such resistances being treated as sources of heat. Incandescent lamps must not be used for resistance devices. c. Must be supplied with globes and protected by spark arresters and. wire netting around globe, as in the case of arc lights on high-potential circuits. (See Nos. 19 and so.) 30. Economy Coilsa. Economy and compensator coils for arc lamps must be mounted on non-combustible, non-absorptive insulating supports, such as glass or porcelain, allowing an air space of at least one inch between frame and support, and in general to be treated like sources of heat. 81. Deoorat·ive Serie• Lampsa. Incandescent lamps run in series shall not be used for decorative purposes inside of buildinflS, f'xcept by special permission in writing from the Inspection Department having jnrisdiction, HIGH CONSTANT-POTENTIAl•• HIGH·POTENTIAL SYSJEMS. 300 TO 3,000 VOLTS, A11y tircuit attaclml to any mar:ki11e,-.or com!Ji11ation of maellines, wllir:k dwelops· a di.lferenu of potn.tial, 6etween any two wires, of tl'QI!I' 300 flolts alld tess tkan .f,OOO flolts, skaJ/6e r:otuidered as a flick potential circuit, alld as coming under tkat class, unless an apjlrO'lJed traiiSforming deviu is used, wkiek euts tke di.lfermee of potential down to 300 fl()/ts or less. 82. Wlres(See also Nqs. I<f., .l.J and ,16,) ·Must have an apjlrO'lJed rubber insulating covering'. (See No. 404.) . , 6. Must be always in plain sight and never incased, except where required by the Inspection Department having jurisdiction. e. Must be rigidly supported on glass or porcelain insulators, which· raise the wire at least one inch from the surface wired over. and must ·be kepl apart at least four inches 'for voltages up to 750 and at least eight ゥョ」セ・ウ@ for voltag'es over 750. 11. Rigid supporting requires under ordinary conditions, where wiring' along llat surfaces, supports at least about every four and one-half. feet. If the wires are unusually liable to be disturbed, the distance between supports should be shortened. · lp buildings of mill constrnction1 mains of No. 8 B. & S. wtre • or over, where not liable to be alsturbed, may be separated about six inches for voltages up to 750 and about ten inches for voltages above 750; and run from timber to.timber, not breaking around, and may be supported at each Umber only, d. Must be protected on side walls from .mechanical injury by a substantial boxing, retaining an air space of one inch around the conductors, closed at the top (the wires passing through bushed holes) and extending not less than seven feet from the floor. •Wben cros&ins floor timbers, in ccll•rs or in セ@ II I! INSIDE WORK. 32. Wires-.. 。ョャオセ、N@ rooms, where •·they might be exposed to injury, wires must be attached by their insulating supports to tbe under side of a wooden strip not less than one-half an inch in thickness. 33. TJIIln&formers (When permitted inside buildings, see No. I3)(For construction rules, see No. 54.) a. Must be located at a point as near as possible to that at which the primary wires enter the building. 6. Must be placed in an inclosure constructed of or lined with tire-resisting material ; the inclosure to be used only for this purpose, and to be kept securely locked and access to the same セッャキ・、@ only to responsible persons. e. Must be e.ffectf!ally insulated from the ground and the inclosure in which they are placed must be practically air tight, e.x:cept that it shall be thoroughly ventilated to the outdoor air, if possible, through a chimney or flue. There should be at least six inches air space on all sides of the transformer. 84. Ca,r. Wiringa. Must be always run out of reach ofthe passengers, and must have an apprwed rubber insulating covering. (See No. 40 a.} 35. Car HQuseaa. Must have the trolley wires securely supported on insulating hangers. II. Must ha_ve the -trolley hangers placed at such a distance apart that, in case of a brea'k in the contact i:an not be made with the floor. trolley キゥイセ[@ e. Must have cut-out switch located at a proper place outside of the building, . so that all trolley circuits in the building can be cut out at one point, be inet;t.lled, so that and line circuit breaker,. ュャゥセ@ 30 HIGH CONSTANT-POTENTIAL. 85. Car Houses-Continued. when this cut-out switch is open the trolley wire will be dead at all points within 100 feet of the building. The current must be cut out of the building whenever the same is not in use or the road not in operation. tl. Must have all lamps and stationary motors installed in such a way that one main switch can control tne whole of each installation-lighting or power-independently of main feeder-switch. No portable incandescent lamps or twin wire allowed, except that portable incandescent lamps may be used in the pits, connections to be made by two approved rubber-covered flexible wires (see No. 40a), pbperly protected against mechanical injury; the circuit to be controlled by a switch placed outside of the pit. e. Must ·have all wiring and apparatus installed in accordance with rules under Class "C" for constant potential systems. f. Must not have any system of feeder distribution centering in the building. g. Must have the rails bonded at each joint with not less than No.2 B. & S. annealed copper wire; also a supplementary wire to be run for each track. 11. Must not have cars left with trolley in electrical connection with the trollev wire. 86. Lighting and Power from Railway Wlre8a. Must not be permitted, uodet" any pretense, in the same circuit with. trolley wires with a ground return, except in electric: railway cars, electric: car bouse.. , and their power 11tations, nor 11haJI the same dynamo be used for both purpose11. 87. Series lampsa. No system of multiple-series or series-multiple for light or power will be approved. 6. Under no circumstances can lamps be attached to sas fixtures, INSIDE WORK. 3l EXTRA HIGH-POTENTIAL SYSTEMS. OVER s,ooo VoLTS. Any dreuit attached to any machine or com/Jination of maehind, which develops a difference of putential, !Jetwun any huo wires, of over .!J,ooo volts, high potential eirshall be considered as an セクエイ。@ cuit, and as toming under that dass, unless an approved transforming device is used, which cuts the difference of potential down tu ,s,ooo volts or less. 88. Primary WiresMust not be brought into or over buildings, except power and sub-stations. 39. Secondl!ry Wiresa. Must be installed under Rules for high-potential systems, when their immediate primary wires carry a current at a potential of over g,ooo volts. The high line insulation req:uired for extra high-potential current tends to make the msulat1on reSistance between primary and secondary coils of transformers a comparatively weak pomt, and lightning discharges would be apt to take th1s path to the eanb. Wtth the present means of protection against transformer break downs and the consequent liability of secondary wiring being subjected to the strain of the primary current, it is not deemed advisable to penn1t a primary current with a potential of over 3.ooo volts without an inter· mediate step-down transformer. The presence of wirescarryinll" a current at a potential of over 3,000 volts m the streets of cities and townsls also considered as increasing the fire hazard. CLASS D FITTINGS, MATERIALS AND DETAILS OF CONSTRUCTION. 40. Wire Insulationa. Rubber Covered- The insulating covering must be solid, at least three-sixty-fourths of an inch in thickness and covered with a substantial braid. It must not readily carry fire, must show an insulating resistance of one megohm per mile after two weeks' submetsion in water at seventy degrees Fahrenheit and three days' submersion in lime water, and after three minutes' electrification with 550 volts. (See page 44.) b. Weatherproof-The insulating covering must not support combustion, must resist abrasion, must be at least one-sixteenth of an inch in thickness, and thoroughly impregnated with a· moisture repellent. c. Flexible Cord-Must be made of two stranded conductors, each having a carrying capacity equivalent to not less than a No. 16 B. & S. wire, and each covered by an approved insulation, and protected by a slow-burning, tough-braided outer cove:dng. I. Insulation for pendants under this rule must be moisture and flame proof. 2. Insulation for cords u.rtdfor all other purposes, including portable lamps and motors, must be solid, at least one-thirty-second of an FlT'l'lNGS , MATERIA LS, ETC, 33 Wire ·Insulation-Continued. inch in thicknes s, and must show an insulatio n resistan ce between conduct ors, and between either conduct or and the ground, of at least one megohm per mile after one week's submersion in water at seventy degrees Fahrenh eit, and after three miimtes ' electrific ation, with 550 volts. 3· The flexible conduct ors for portable luating apparatus, such as irons, etc., must bave an insulatio n that will not be injured by heat, such as asbestos , which must be protecte d from mechan ical ·injury by an outer, substant ial, braided covering , and so arrange d that me. chanica l strain will not be borne by the electrical connecti on. d. fixture Wire-M ust have a solid insulatio n, with a sl,ow-bu rning, tough, outer covering , the whole to be at least one-thir ty-secon d of an inch in thicknes s, ·and show an insulatio n resistan ce between conduct ors, and between either conduct or and the ground, of at least one megohm per mile, after one week's submers ion in water at seventy degrees l'"ahrenheit, and after three minutes ' electri· fication, with 550 volts. e. Conduit Wire-M ust comply with the following specifica tions : 1. Fot' insulate d metal eonduits single wires and twin conduct ors must comply with section (a) of this rule. Conceni ric wire must have a braided covering between the outer conduct or and the insulation of the inner conduct or, and, tn•addit ion, must comply with section (a) of this rule. 2. For ,.o11-insulated 'llutal eo11dut'ts single wires and twin conduct ors must comply with section (a) of this rule, and, in addition , h:ave a second outer fibrous covering , at least 40. 34 CLASS D. 40. Wire Insulation-Continued. one-thirty-second of an inch in thickness, and sufficiently tenacious to withstand the abrasion of being hauled through the metal conduit. Concentric conductors must have a braided covering between the outer conductor and the insulation of the inner conductor, and comply with section (a) of this rule, and, in addition, must have a second outer fibrous covering at least one-thirty-second of an inch in thickness, and sufficiently tenacious to withstand the abrasion of being hauled through the セ・エ。ャ@ conduit. 41. Interior Condulta(Fw 'Uiiring rules, su Nos. 24 and 25.) a. Each length of conduit, whether insulated or uninsulated, must have the maker's name or initials stamped in the metal or attached thereto in a satisfactory manner, so that the inspectors can readily see the same. Insulated Metal Conduits: !J. The metal covering, or pipe, must be at least equal in thickness or of equal strength to resist penetration by nails, etc., as the ordinary commercial form of gas pipe of same size. e. Must not be seriously affected externally by burning out a wire inside the tube when the iron pipe is connected to one side of the circuit. d. Must have the insulating lining firmly secured to the pipe. セN@ The insulating lining must not crack or break when a length of the conduit is uniformly bent at temperature of 212 degrees }i'ahrenheit to an angle of ninety degrees, with a curve having a radius of fifteen inches, for pipes of one inch and less, and lifteen times the diameter of pipe for larger pipes. FITTINGS, MATERIALS, ETC, 35 41. Interior Condulls-Contlnued. f. The insulating lining must not soften injur.ously at a temperature below 212 degrees Fahrenheit and must leave water in which it is boiled practi· cally neutral. g. The insulating lining must be at least onethirty-second of an inch in thickness, and the materials of which it is composed must be of such a nature as will not have a deteriorating effect on the insulation. of the conductor, and be su11iciently tough and tenacious to withstand the abrasion test of drawing in and out of same long lengths of conductors. k. The insulating lining must not be mechanically weak after three days' submersion in water, and, when removed from the pipe entire, must not absorb more than ten per cent of its weight of water during Ioo hours of submersion. i. All elbows must be made for the .Purpose, and not bent from lengths of pipe. The radtus of the curve of the inner edge of any elbow not to be less than three and one-half inches. Must have· not more than the equivalent of four quarter bends from outlet to outlet, the bends at the outlets not being counted. Unln1ulatecl Metal Conduits: of equal thickness, ·or j. Plain iro11 ot' ウエセGャーゥ・@ of equal strength, to resist penetration of nails, etc., as the ordinary commercial form of gas pipe of the same size, may be used as'conduita, provided their interior surfaces are smooth and free from burs ; pipe to be galvanized, or the interior surfaces coated or enameled to prevent oxidization with some substance which will not soften so as to become sticky and prevent wire from being with. drawn from the pipe. k. All elbows must be made for the· purpose, and n·ot bent fro!D ·lengths of pipe. The radius of the curve of the iaaer edge of any elbow not to be less ᄋセ@ CLASS n. 41. Interior Conduit-Continued. than three and one-half inches. Must have not more than the equiv&lent of four quarter bends from outlet to outlet, the bends at the outlets not being counted. 4!. Wooden Mouldlaaa(For wiring rules, su No: 14.) a. Must have, both outside and inside, at least two coats of waterproof paint, or be impregnated with a moisture repellent. IJ. Must be made of two pieces, a backing and capping so constructed as to thoroughly incase the wire, and provide a one-half inch tongue between the conductors, and a solid backing, which, under grooves, shall not be less than three-eighths of an inch in thickness, and must afford suitable protection from abrasion. It is recommended tha.t only hardwood moulding be used. "· Swltcllee- (Se• Nos. I7 attrl1.a.) -· Must be mounted on non-combustible, nonabsorptive, insulating bases, such as slate or porcelain. IJ, Must have carrying capacity sufficient to prevent undue heating. &. Must, when used for service switches, indicate. on inspection, whether the current be "on" or "off". d. Must be plainly marked where it will always be visible, with the name of the maker and the current and voltage for which the switch is designed. '· Must. for constant potential systems, operate successfully at fifty per cent overload in amperes, with twenty-five per cent excess voltage under the most severe conditions they are liable to meet with in practice. FITTINGS, MATERIALS, ETC. 37 43. Switches-Continued. f. Must, for constant potential systems, have a firm and secure contact ; must make and break readily, and not stop when motion has once been imparted by the handle. g. Must, for constant current systems, close the main circuit and disconnect the branch wires when turned .. off"; must be so constructed that they shall be automatic in action, not stopping between points when started, and must prevent an arc between the points under all circumstances . They must indicate, upon inspection, whether the current be "on"or"off" . 44. Cut-outa and Circuit Breakera(For iNtallalio" rlllu, .111 No.r. I1 a1111 41I.) a. Must be supported on bases of non-combustible, non-a.bsorptive insulating material. 6. Cut-outs f11USt be provided with covert, wheo not arranged in approved cabinets, so as 'to obviate any danger of the melted fuse metal coming In contact with any substance which might be ignited thereby. e. Cut-outs must operate successfully, under the most severe conditions they are liable to meet with in practice, on short circuits with fuses rated a.t so per cent above and with a voltage 25 per cent above the current and voltage for which they are designed. tl. Circuit-breake r• musi. operate successfully, under the most 1evere conditions they are liable to meet with in practice, on short circuits when set at fifty per cent above the current, and with avoltage twenty-five· per eeoc above that·for which they are · designed. 1. Must be plainly marked where it will always be Tisible, with the name of the maker, and curthe device is designed. rent and voltage for キセゥ」ィ@ CLASS D. 45. Fases- (For insta//ati01t rules, see Nos. I'/ and JII.) a. Must have contact surfaces or tips of harder metal having perfect electrical connection wJth the fusible part of the strip. · 6, Must be stamped with about eighty per cent of the maximum current they can carry indefinitely, thus allowing about twenty-five per cent overload before fuse melts. With naked open fuses, of ordinary shapes and not over soo amperes capacity, the maximum current which will melt them in about five minutes may be safely taken as the melting point, as the fuse practically reaches lis max, mum temperature m this time. With larger fuses a longer time is necessary. Inclosed fuses where the fuse is often in contact with substances having good conductivity to heat, and often of considerable volume, require a much longer time to reach a maximum temperature on account of the surrounding material which heats up slowly. This data is given to facilitate testing. , e. Fuse terminals must be stamped with the maker's name, initials, or some known trademark. 46. Cut-out (!abfnets"· Must be so constructed, and cut-outs so arranged, as to obviate any danger of'the melted fuse metal coming in contact with any substance wbich mijtht be ignited thereby. A suitable bolt can be made of marble, &late or wood, strongly put tojl'ether1 the dooc to cio•e ajj·ainst a rabbet so as to be perfectly du•t tlght, and It should be hUll&" on strong hinges and held clu•ed by a strong hook or CJ.tch. セiヲ@ the box is wood the inside should be lined with sheets ot asbestos board about onesixteenth of an inch in thickness, neatly put on and firmly secured in place by shellac and tacks. The キゥイセウ@ should enter through holes bushed with porcelain bushiniJII ; the bushings tightly fitting the holes in the box, ;md the Wlreatightly fitting the bushings (using tape to build up the wire, if necessary) ao as to keep out the dust. FITTINGS, MATERIALS, ETC. 39 47. Sockets(See No. 27.) a. No portion of the lamp socket, or lamp base, exposed to contact with outside objects, must be allowed to come into electrical contact with either conductor. 11. Must, when provided with keys, comply with the requirements for switches. (See No. 43.) 48. Hanger-boarde"· Hanger-boards must be so constructed that all wires and current carrying devices thereon shall be exposed to view and thoroughly insulated by being mounted on a non-combustible, non-absorptive insulating substance. All switches attached to the same must be so constructed that they shall be automatic in their action, cutting off both poles to the lamp, not stopping between points when started and preventing an arc between points under all circumstances. 49. Aro Lampe(For installation rwks, su No. r9.) a. Must be provided with reliable stops to prevent carbons from falling out in case the clamps become. loose. IJ. Must be carefully insulated from the circuit in all their exposed parts. c. Must, for constant current systems, be provided with an apprwetl hand switch, also an automatic switch that will shunt the current around the carbons, should they faU to feed properly. The hand switch to be approved, if placed anywhere except on the lamp itself, mu1t comply with requirements for switches on hanger-boards as laid down ia Rule 48. I CLASS D. 50. Spark Arrester&- I9 e.) (See NlvZセ@ a. Spark arrester s must so close the upper orifice of the globe that h will be impossi ble for any sparks, thrown off by the carbons , to escape. lil. lnsulatlag Jolnta- (See N(). a6 a.) a. Must be entirely made of materia l that will resist the action of illumina ting gases, and will not give way or soften under the heat of an ordinary gas tlame or leak under a moderat e pressure . They shall be fO arrange d that a deposit of moistur e will not destroy the insulati ng effect, and shall have an ohms insulati ng resistan ce of at least ZRセッL@ between the gas-pipe attachm ents, and be suffi. ciently strong to resist the strain they will be liable to be subjecte d to in being installed , fl. Insulati ng joints having soft rubber in their construc tion will not be approve d. 52. Reelstanoe Boxes and Equalizera- +-> (F()r i'llltai/Qti()n rules, see ND. a. Must be equippe d with metal, or with other non-com bustible frames. entire case The word '• frame" in this section relates to the to the uphold- and surroundings of the rheostat, and not alone ing supports. 53. Reactive Coils and Condensera- a. Reactive coils must be made of non-com bustible material , mounted on non-com bustible bases and treated, in general, like sources of heat. fl.· Conden sers must be treated like apparatu s operatin g with equivale nt voltage and currents . They must have non-com bustible cases and supports, and must be isolated from all combust ible material s and, in geoeral, treated like sources of beat. FITTINGS, MATERIALS, ETC, 4I 64. Tranformers(F,,. in.rlllllotitm rules, see Nqs, I I anti.J.J.) a. Must not be placed in any but metallic or other non-combustible cases. 55. Ugbtalng Arresters(Fw in.rtallatitJn rules, ue No, 5.) a. Must be mounted on non-combustible bases, and must be so constructed as not to maintain an arc after the discharge has passed. and must have no moving parts. CLASS E. MISCELLANEOUS. 56. lnaulatlon RealatanoeThe wiring in any building must test free from grounds, i. セ@ .• the complete installation must have an insulation between conductors and between all conductors and the ground (not including attachments, sockets, receptacles, etc.) of not less than the following: Up to '' u s amperes ........................... 4,ooo,ooo to •s so ... " • • • • • . . . • . ................. a,ooo.ooo ........................ soo,ooo .. .• . . .. .. .. . . . . .. ... .. •.. 400.000 • • • • ••••• - • • • • • • • • • • .. • 1100,000 t()() • • • • aoo • •• • • • • • • ••• • • • <400 ............................ so.ooo • • • • • • • • • . . . • • • • • •• . .. • • • • • • tz,S,ooo Boo z,6oo " • . , . . • • • • • too,ooo and over.... . .. . . . .. .. .. • .. . . • 12,500 All cut-outs and safety devices in place in the above. Where lamp sockets, receptacles and electroliers, etc., are connected, one-half of the above will be required. 1:17......ectlon agafnat Forelga Cllrrente. a. Where telephone, telegraph or other wires, connected ...-ith outside circuits, are bunched together within any building, or where inside wires are laid in conduits or ducts with electric light or power wires, the covering: of such wires must be fireresisting, or else the wires must be inclosed in an air-tight tube or duct. IJ. AU aerial conductors and underground conductors, which are directly connected to aerial wires, connecting with telephone, telegraph, district messenger, burglar-alarm, watch-clock, ·electric-time and· other similar instruments must be provided near the point of entrance to the building with some approved protective device which will operate to shunt the instruments in case of a dangerous rise of potential, and will open the cir. cult and arrest any abnormal current flow. Any conductor normally forming an innocuous circuit may MISCELLANEOUS, 43 , 57, Protection against Foreign cオョ・エウMッャ、セ@ become a source of fire hazard if crossed with another conductor charged with a relatively high pressure. Protectors must have a non-combustible, Insulating base, and the cover to be provided with a lock similar to the lock now placed on telephone apparatus or !lome equally secure fastening, and to be installed under the following requirement& : •· The protector to be located at the point where the wires enter the building, either immediately inside or outside of the same. If outside, the p.-otector to be enclosed in a metallic, watel1lf0of case. "· If the pJ"Otector is placed inside of building, the wires of the circuit from tile support outside to the binding posts of the protector to be of sucli insulation as is approved for service wires of electric light and power (See No, 4b •) and the holes through the outer wall to be protected by bushmg the same as required for electric light and power service wires. 3• The wire from the point of entrance to the protector to be run in accordance with i'ules for high-potential wires, i. e., free of contact with building and supponed on non·combustible iosulators. + The ground wiresball beinsulated,notsmallerthan No.16 B. & S. gaug;e copper wire. This ground wire shall be kept at least three mches from all conductors, and shall never be secured by uninsulated, double-pointed tacks, and must be run in as •tra.Jght a line as possible to the ground connection. s. The ground wire shall be attached to a water pipe, if セウゥ「ャ・L@ otherwise may be attached to a gas pipe. The,ground wire shall be carried to, and attached to, the pipe outside of the first Joint or coupling inside the foundation walls_, and the connectaon shall be made by soldering, if possible. an the absence of other good ground, tbe ground shall be made by means of a metallic plate or a bunch of wires buried in a permanently moist earth. 58. Electric Gu Lighting- Where electric gas lighting is to be used oo the same fixture with the electric light: a. No part o.f the gas piping or fixture sball be Jn electric connection with the gas lighting circuit. 6. The wires used with the fixtures must have a non-iufiammable insulation, or, where concealed between the pipe and shell of the fixt11re, the ineula.. lion must be such as required for fixture wiring for the electric light. CLASS E. M. Electric Gas Lighting-Continu ed. c. The whole installation must test free from "grounds". tl. The two installations must test perfectly free from-connecti on with each other. li9. Soldering Fluid- a. The following formula for soldering fluid is suggested: Saturated solution of l'.inc chloride.................. 5 parts. セON[Z@ ::::.::. :.:·.:::::::::::::::: ·.::: セZ@ :·'.:·: Zセᆳ APPROVED MATERIALS. WI rea- The following Is a list of wires constructed to comply with the standard given in Rule 40 a. Result of recent tests on these and on other wires can be seen at inspection offices: Manufacturer. Name of W1re. Amerlcanite .............. American Electrical Workll. Percha Co, .Gutta Bishop.................. .. Bishop Clark:..... .. .. . . .. .. .. .. Eastern Electric Cable Co. Co. Electric Climax. . . . . . . • . . • . ..•• Simolex " " \• Shoplez (caoutchouc).... Co. Electrical Acme ................. .. Simplex C. C. , .•• , .••...• , .• ; ••••. Canadian General Electric Co. Crescent . . . . , ... , ....... John A. Roebling's Sons Co. Crown.................. .. Washburn & Moen. " " Globe.......... .......... Crefeld ...... : ... ........ Crefeld Electrical Workll. · Grimshaw (White core) .. N. Y. Insulated Wire Co. " " " Raven (Black core).. .. • " " " " core)...... " Raven Hwィゥセ・@ !le9.ua (White core) ..... Safety Insulated Wire and Cable Co. " " " " Safety (Black core)....... • " Habirshaw (White core), .Ind. Rubber & Gutta Percba Ins. Co. u " " •• " (Blue core}... " " ., n t• u .. (Red core)... u " Co, Wire Insulated Paranlte ................. Indiana Rubber & Liberty, .. ., ............. Atlas Covering Works. Kerite ........... , ....... W. R. Brixey. Oltonite ............ , ..... Okonite Co., Limited, Paracore. , •••••••.••• , ; .. Nat. Ind1a Rubber Co. N.. I.R . ........ セᄋ@ '' '' '' ., Double Rubber Core... General Electric Co. " " Double Rubber (Red core) " Uode[.ground c。Lセi・@ Sterling ............... sエ。セイ、@ TleTop.••..•....•..•.... Pli&llipa,,,, ••••••• •••••, .Phillip& Insulated Wire Co. C:?· MISCELLANEOUS, 45 Approved Materials-Continued, MaterialsThe following are given as BUSTIBLE, NON-ABSOlt.PflVE1 a list of NON-coMl.NSULA.TING materials and are listed here for the benefit of those who might c:om1ider hard rubber, fiber, wood and the like as fulfilling the above requirements. Any other substance, which it is claimed should be accepted, must be forwarded for testing before being put on the market : -1. Glass. s. Marble (filled). 3· Slate without metal veins. 4· Porcelain, thoroughly glazed and vitrified. 5· Pure Sheet Mica. 6. Lava (certain kinds of), 7· Alberene Stone. lro11-Armor8d 111811Jat8d ConduitsThe Iron and steel-armored conduits manufactured by the Interior Conduit and Insulation Company, the Armorite Company, the Clifton Manufacturing Company, and the Consolidated Tube Company have been tested and, in general, have given good results in practice. Flexible Tublng(&e No• .:14 1.) American Circular Loom tubing is approved for use under rule 24, section /, CLASS F. MAR INE WOR K. 60. Generatol'8- . a. Must be located in a dry place. !J. Must have their frames insulated from their bed-plates . c. Must each be provided with a waterproo f cover. d. Must each be provided with a name plate, giving the maker's name, the capacity in voltage and amperes and normal speed in revolution s per minute. 61. Wires. a. Must have an apprvved insulating covering. The insulation for all conductors, except for portables, to be approved, must be at least one-eighth inch in thickness and be covered with a substantial waterproof and llameproof braid. The physical characteristi cs shall not be affected by any change In temperature up to 2oodegrees Fahrenheit. Aftertwo weeks' show submersion in salt water atlodegrees Fahrenheit it must three an insulation resistance o one megohm per mile after volts. sso minutes' electrificatio n, with 6. Must have no single wire larger than No. 12 B. & S. Wires to be stranded when greater carrying capacity Is required. No single solid wire smaller than No. 14 B. & S., except in fixture wiring, to be used. Stranded wires must be soldered before being fastened under clamps or binding screws, and when they have a conductivity greater than No. xo B. & S. copper wire they must be soldered into lugs. t:. Must be supported in approved molding, except at switchboa rds and portables. Special permission may be given for deviation from this rule in dynamo rooms, d. Must be bushed with hard rubber tubing oneeighth inch in thickness when passing through beams and non-water -tight bulkheads . MARINE WORK, 47 61. Wires-Continued. t. Must have when passing through water-tight bulkheads and through all decks, a metal.ic stuffing tube lined with hard rubber. In case of deck tubes they shall be boxed near deck to prevent mechanical injury, f. Splices or taps iti conductors must be avoided as far as possible, Where it is necessary to make them they must be so spliced or joined a.s to be both mechanically and electrically secure without solder. They must then be soldered, to insure preservation, covered with an insulating compound equal to the insulation of the wire, and further protected by a waterproof tape. The joint must then be coated or painted with a waterproof compound. 62. Portable Conductorsa. Must be made of two stranded conductors, each having a carrying capacity equivalent to not less than No, 14 B. & S. wire, and each covered with an approved insulation and covering. Where not exposed to moisture or severe mechanical injury, each stranded conductor must have a solid insulation at least one-thirty-second of an inch in thickness, and must show an insulation resistance between conductors, and between either conductor and the ground, of at least one megohm per mile after one week's submersion in water at seventy degrees. Fahrenheit and after three minutes' electrification, with Soe> volts, and be protected by a slow-burning, tough-braided outer covering. Where exposed to moisture and mechanical injury-as for we on decks, b<>lds and fire rooms-each stranded conductor ,., soltd insulation, to be appr'lved, of at least oneshall ィセカ・@ thirty-second of an inch in thickness and protected by a tough braid. The two conductors shall then be stranded together, using a jute filling. The whole shall then be covered with 11. layer of flax 1 either woven or braided,at least one-thirty-second of an inch 1n thickness, and treated with a non-inflammable, waterproof compound. After one week's submersion in water at seventy degrees l"ahrenheit, with :;so volts and a three minutes' electrification, must show an msulation between the two conductors, or between either conductor and the ground, of one megohm permil!l· CLASS F. 63. Bell or Other. Wlreaa. Shall never be run i• &&me duct with lighting or power wires. 64. Table of Capacity of Wires.; i.:!;:;i ci ui old ) Ul !u Ill 11 z0 < セ」ゥ@ .; cilul ... 1lold NAZi。セ@ f !. a < Ul QLセX@ 1,62.. 2,0.8 •,s83 3.•57 6 4·'"7 6,530 q,o16. U,368 14,336 z8,o8z 7 7 7 7 38,gi2 '9 [セZ@ セZ@ WセLV@ 99,o64 "'4 928 ウセNVS@ >g8,677 •so.s•7 •¢.387 373·737 4'3,11J9 Nセ@ [セ@ 37 6I 6z 61 61 6x gr 17 16 ;3 セ@ 17 17 IS •1 •6 '4 •s . IS 14 ••1 •s When greater conducting area than that of u Qt rs I00 120 145 r 7o 200 "35 •1o 320 340 B. & S G. is required, the conductor shall he stranded m a aertes of 7, xg; ;!71 6t, 91 or 127 wires, as may be required; the strand CODSI&t• mg of one central Wire, the remainder la1d around it concentrically, each layer to be tw,sted m the opposite d1rect1on :from the precedmg. 65. Switchboardsa. Must be made Qf non-combustible, non-absorptive, insulating material, such as marble or slate. MARINE WORK. 49 65. Swltchboardt-Contlnued. fl. Must be kept free from moisture, and must be located so as to be accessible from all sides. c. Must have a main switch, main cut-out and ammeter for each generator. Must also have a voltmeter and ground detector. d. Must have a cut-out and 1witch for each side of each circuit leading from board. 68. Resistance Boxesa. Must be made of non-combustible material. fl. Must be located on switchhoard or away from combustible material. When not placed on switchboard they must be mounted on non-infiammable, non-absorptive insulating material. c. Must be so constructed as to allow sufficient Tentilation for the uses to which they are put. 67. SwltohestJ, Must· have non-combustible, non-absorptive, insulating bases. II. Must operate 1uccessfully at fifty per cent overload in amperes with. twenty.five per cent excess voltage under the most severe conditions they are liable to meet with in practice, and must be plainly marked where it will always be visible, with the name of the maker and the current and voltage for which the switch is designed. e. Must be double.pole when circuits which they control supply more than six 16-candle-power lamps or their equivalent. , d. When exposed to dampness, they must be enclosed in a water-tight case. 68. Cat-outsa. Must bave non-combustible, non-absorptive, insulating bases. II. Must operate successfully, under the most severe conditions they are liable to meet with in practice, on short circuit with fuse rated at fifty per cent above, and with a voltage twenty-five per cent 50 CLASS F, Gil. Cut-outa-Contlnued. above the current and · voltage they are designed for, and must be plainly marked where they will always be visible with the name of the maker and current and voltage for which the device is designed. セN@ Must be placed at every point where a change :is made in the size of the wire (unless the cut-out in the larger wire will protect the smaller). tl. In places such as upper decks, holds, cargo spaces and fire rooms a water-tight and fireproof cut-out may be used, connecting directly to mains· when such cut-out supplies not more than sbt z6-candle-power lamps or their equivalent. 1. When placed anywhere except on switchboards and certain places, as cargo spaces, holds, 'fire-rooms, etc., where it is impossible to run from center of distribution, they shall be in a cabinet lined with fire-resisting material. f. Except for motors, search-lights and diving· lamps shall be so placed that no group of lamps, イ・セオゥョァ@ a current of more than six amperes, shall ultimately be dependent upon one cut-out. A lliqle-pole covered cut-out may be placed in the mouldlntr when aame contains conductors auwlying curreDr for not more than two •6-i:a.Ddle-power lamps or their equivalent. 69. Fixturesa. Shall be mounted on blocks made from well seasoned lumber treated with two coats of white lead or shellac, 6. Where exposed to dampness, the lamp must be surrounded by a vapor-proof globe. セN@ Where exposed to mechanical injury, the lamp must be surrounded by a globe protected by a stout wire guard.· tl. Shall. be wired with same grade of insulation as portable conductors which are not e:c:posed to moasture or mechanical injury. MARINE WORK. SI 70. Sockataa. No portion of the lamp socket or lamp base exposed to contact with outside objects shall be allowed to come into electrical contact with either of the conductors. 'i'L Wooden Mouldingsa. Must be made o( well seasoned lumber, and be treated inside and out with at least t.wo coats of white lead or shellac:. 6. Must be made of two pieces, a backing and a capping, so constructed as to thoroughly incase the wire and provide a one-half-inch tongue between the conductors, and a solid backing which, under grooves, shall not be less than three-eighths inch in thickness. c. Where moulding is run over rivets, beame, etc., a backing strip must first be put up and the moulding secured to this. tl. Capping must be secured by brass screws. 72. Motol'8a. Must be wired under the same precautions as with a current of same volume and potential for lighting. Tlie motor and resistrnce box must be protected by a double-pole cut-out and controlled by a double-pole switch, except in cases where ッセZ・ᆳ quarter horse-power or less is used, The leads or branch circuits should be designed to earry a rurrent at least fifty per cent greater than that required by the rated capacity of the motor to provide for the inevllable overloading oi the motor at tunes. !J. Must be thoroughly insulated. Where possible, should ·be set on base frames made from filled, hard, dry wood and raised above surrounding deck. On hoists and winches they shall be insulated from bed-plates by hard rubber, fiber or similar insulating material. 52 MARINE WORK. '1'2. Motors-Continued. c. Shall be covered with a waterproof cover when not in use. d. Must each be provided with a name plate giving maker's name, the capacity in volts and amperes and the normal speed in revolutions per minute. INDEX. RULE AND S.ECI'ION.· Acidfumes................ .. . • ....... . .•. to (c), 24 (j).& (k) Arc lamps, Construction of.. • .............................. 49 Arc lamps, Installation of.. .. .. .. .. . ........................ •9 Arc lamps, On low-potential circuits ... , .............. , ..... 29 Base frames, Generators and motors ................. ({), 8 (a) ,Batteries, Storage or primary.... . .. . . . .. .. .. . .. .. . • ....... to Binding screws, not to bear strain ..................... aVJ Bonds, rails and car houses................. . : .. .. .. 35 (C) Boxmgt where necessary............... • • . •8 (e), "4 (/) 32 Id) Brewenes.... . .. .. • .. . ..................... , ..... ·•4 (t) to (k) Burglar alarms........ . .............................. oi7 (6) Burrs and fins. Fixture work. .. • .. • .. • .. • .. .. .. .. .. .. .'o6 (6} Bushings, For wires . .. • . .. .. • .. .. . .. . .. .. .. • • .. • .. • •4 (d) Bushings, Lamp sockets .................................. 28 (e) Bus bars ......................... ,. ................ ·• (6), 3 (e) Cabinets for cut-outs ......................................... 46 Care and atte)\dance ...... ,..... .. .. • .. .. • .. .. .. .. • • ......... 6 Car houses...........·.................... • ............... .. 35 c。イケゥセ@ capacity table .................................... x6 Car winng ........................................... ........ 34 Central stations.... .. .. . .. . . .. • .. .. .. ................ • tn 7 Circuit breakers, Construction of.............. .. .. .. , .. ..14 C1rcuit breakers, Installatton of.•••.••••••....••..•••• r7, 21 (tt) Compensator coils........ .. .. .. .. .. .. . . .. .. . . .. .. • .. . .. 30 Concealed wiring ..................... 24 (a) to(/}& (r) to (I) Condensers........... . ............................. ·53 (6) Conductors. (See Wires) ................................ .. Conduits, Installation of .......................... , ......... セ@ Conduits, Insulated approved list, page.................. '"45 Conduits, Insulated metal .........................p (6} to (i) Conduits, To be marked ........... , ...................... 41 (4) Conduits, Uninsulated metal............ .. .. .. .. . 4< (j) l!l (k) Condurt work ................. ·•· ............ :.24 (m) t.:> (9) Constant-current syS' ems .. .. ......................... xS to 20 ConStant-potential s_ystems, General Rules ...••••.•••• 21 to 23 Converters. (See Transformers)"'""'" ................... 46 Cut-out cabinets........ ..· ................................. .. Cut-outs, Construction of ................................... 44 Cut-outs, Installation of. . . . .. ............... ' .......... 17 tn 21 Cut-outs, Marine work.. .. . .. .. .. .. •.. • . .. .. .. .. .. • • .. . . .. 68 Cut-outs, Tobedoublepole....... ........ .. ......... 17 (a} Decorative series lamps ..................... ,"... : ........... 31 Distance between conductors, im!lde •••• 18 H、ILᄋセ@ (k), tj) l!l HセI@ ,. ' YNDE"· RULli: AN!l SI!CTION. Distance between c.;nductors, outside ..••••••• , • • • • • • • . •• (6) Drip loops at service entrances ............. ,... . ....... 12 (!{) Dynamo rooms ......................... · ................. , to 7 Economy co!Js ............................. .................. 30 Electric gaslighling............................. ......... ·... 511 Electric heaters.......... .. ............................. ... Rセ@ Efectro-magnetic 、・カゥ」セ@ for SWitches ••........••...••.•. .., (c) ᄋセオ。ャゥコ・イウN@ (See resistance boxes) ............ , .............. . Extra high-potential systems..... .. . .. . . .. .. .. . ........ 38 & 39 Feeders, Railway ............................. .......... 35 Ul Fished wires ............. : . ....................... 24 (c) & (t) Fittings and materials ....... ' ......................... ·40 to 55 Fixtures ..................... ; ............................. ... 6 Fixtures, Marine work..... . . . . .. . .. .. . .. . .. .. . .. . • .. .. .. Mセ@ Fixtu:e wire........................ ................ .. .40 ( Fixture wiring ............................. ....... •4 (,.)to (w Flellible cord, Construction of ........................... 40 (<) Flexible cord, Construction oi, Hesters ........... 40 (c-l_) Flexible cord, Construction of, :Pendants............ ; .. 40 (""•) Flexible cord, Construction of, Porrables .•.....••••. • 40 (c-..) Flexible cord, Use of ............................. ............a fャ・クゥ「エオョセイL@ page ........................... .......... 45 Foreign currents, protection against ••.•••.••••••••••••••.... 57 Formula for soldering i!uid .............................. .... 59 Fuses, Construction of ............................. .......... 25 Fuses, Installation of.......... .. .. .. .. .. .. .. • .. .. .. ........ mx Gas lighting, Electric ............................. .......... 58 General plan .of rules, page.. .. .. .. .. • .. . • .................... 3 General suggestions, page...... .. . . • .. . .. . . . .. . ............. 4 Generators ............................. ....................... x Generators, Marine work ............................. ...... 6o Grounded circuits ............. !".... . ..................... 36 Grounding of dynamo and motor frames; ............. (e-ll) (a) Grounds, Testing for .. .. .. . • • .. .. . .. • .. .. • .. ... . .. . .. • .. .. 7 Ground wire for lightning arresters ................ S-<", 57 (6-s) Hanger-boards, Construction of .. .. ........................ 48 Hanger-boards, When not used ............................ rg-d Heaters, Electric...... .. .. . .. .. . .. .. .. .. • . .. .. • .. .. .. ....... 23 f{lgh, constant-potential systems .•.••....•••.•.••...• • · 3• to 37 Incandescent lamps as resistances..........••.•• , ... , ••.• •orr-6 Inside work ..... セN@ . . ......................... x4 to 39 llllllulating joints, Construction of .................... ....... sx Insulating joints, When required ............ · ............ !16-a Insulation of trolley wires .............................. .... 12-k Insulation resistance .............................. ............ 56 Interior conduits. (See condUits) ............................. . JNDEX, 55 Rt'LB AND SBCTlON. ••-c Joints, in conductors ................... ; .............. zst-f, Joints, in interk>r conduits ........................... .... zs-d Joints, Inaulatmg. (See lmulating Joints) .................. .. l。ューセL@ Arc. (See Arc LaJDpa) ..... · .. . . .. .. . . .. .• · · ... • .... • Lamps, IJU:alldescent senes ............. • .................... zo Llghtnlllg arresters, Conatruction of ••••••••••••••••••••••••• ss !-i&'htnil!g arresters, Installation of ........................... s Lights from trolley circuits .................................. 36 LOw-potential systems ................................. セエッ@ 31 Marine work. .................. ·.. ,, .................... 6o to 72 Materls!s, MBセカ・、L@ ー。ァセ@ ....• .-_. . . • . . . . . . . . • • . # & 45 セ@ ..... 32-d MechamcaJ IRJury, PrOtecuonagamst ....... .- .. セXMQL@ Motors .....................................................8 Motors, Manne work ...................................... Mセ@ Moulding, Construction of........ .. .. • ..................,. Moulding, Manne 1• Moulding work ................................ セ@ .... tof, I, & m work................................. . Oily waste.... .. . .. .. .. • .................................. thf oーセ@ WJnng .. _. ............................... , ...... セ@ .... to .t Outside work ............... ,; .......................... xa & '3 Portable conductors ..................... セ@ ...............o (<"-o) Portable conductors for marme work . . . . . . . . . . . . . . . . . . . . . . 6o Protective devices, ••Jnal circuits.......................... 57·6 Power from trolley CU'cuits ................................. 36 Railway power plants............... .. .. .................... •9 Reacuve coils ............................................ ..53..,. Resistance boxes, Conatruction of ...... ....... • .............. 5" Resistance boxes, Installation of ........·.......... .. ......... 4 Resistance boxes, Manne work!'............................ 66 Re&lltances for arc lamps, Low-potenuaJ._. • .. • • .. . .. .. . .. JZ9-11 セエ。ZァォNᄋLG@ Sockets, Construction of .................................... ·.47 Sockets, InstallaUon of...................................... •"7 Sockets, Marine work.. . .. .. .. .. .. • .. .. .. • .. .. .. .. .. .. .. .. • 10 Soldering fluid. formula... .. ; ........................ •.. .. 59 Spark arresters, Construction or.......... .. .. .. .... .. .. .. • . . so Spark arresters, When required •.•.••.•..••••..•••.••• •9-<"· 2Q-C Storaa-e battery room& ......................... : .............. to SWitchboards ................................................ 8 Switchboards, Marble work........................ .. .... .. 6s Switches, Construction or ........ : ............. , .......... o Switches, Electro-magnetic ................ : ............... :ao-e SWitches, Installation of .................... , .......... 17 & a INDEX, RULK AND SECTIONQ Switches, Marine work ........................... ........ 67 Switches, To be double pole ............................ .. •7-a pole. . . . . . . . . . • .. ...•. 8-c, zo-e Switches, When may be ウュァャセ@ . .. ...................... x8 to 20 Systems, cッョウエ。M」オイ・セN@ ......... : .................. 21 to 39 Systems, cッョウエ。セMー・ュャ@ Systems, E'!'tra htgh, constant-J?Otenual. . . . • • • . . . . . . . . 38 & 3q Systems, H•gh, constant-potential . . . . . ..••.•....... , .. 32 to 37 Systems, Low, constant-potential ....................... 21 to 3 , .............. 57 Tei"JJ''lph, telephone, and other signal 」セイオゥャND@ Testmg ........................... ; ........................... 7 Transformers in central stations ....................... , ..... u Transformers, Construction of ............. , . . .. ............ s 4 Transformers, Inside ............ · ...... · · .. . . . . .......... 33 ............................ ........ 1 3 oオセsエ、・@ tイ。ョウヲ\Iュ・セ@ Tubing, Flexible, page ............................ ......... 45 Wire, Wire, Wire, Wire, W1re, Wire, W1re, Wire, Concentrjc ......................... , .............. , . 40-e Fixtures ............................. ............... 4o-d Insulatedconduit ............................. . .... {o-e,l Insulationof............................. .............. 4o Netting required on arc lamps ................. x9-c, zcrc Rubber covered............................. ........ 40-a Uninsulated conduit........ :...... .. .. .. ...... 40 (e-2} Weatherproof ............................ ...... .... 4o-il Wires, Carrying capacity table.... . . . . ..................... t6 Wires, Carrymg capaCity table, Marine work ................ 64 Wires, Central statiOns............... .. . .. . . . . • . . • • . • .. . . 2 Wires, Concealed work ............................. .. ·24-f" tot Wires,-Conduit work............................ ..... 24-n to q Wires, Distance between, inside '. • .... • ..... rB-d, 24-k,.f & s Wires, Distance between, outside .......................... •;z-6 Wires, Extra high-potential. . ; .. .. . .. .. .. . .. . .. .. .. • .. . 38 & 39 Wires, Fished ..................... ;.; .................. o4·c& t '•Vires, General rules, ·Jow-potenttal. , ..••••••........• 24-a to f QRセコ@ セ@ セ@ Wires, Ground return. ..... , ..... W.res, High-potential.. .. , ... , ............................. .. 32 Wires, Inside, constant-current ............................. . 18 Wires, InSide, general rules.... . .. .. . .. .. . .. .. .. • .. .. • .. .. . '4 Wires, Underground ............................ ....... .... 15 Wires, Marme work.; ............................ ......... 61 W1res, Moulding work . .. . . .. .. .. .. . .. ............. 24-l & "' Wires, Openwork, damp places •• , .................... 24-ito k Open work, dry places ......................... 24-g & k wセイ・ウL@ Wires, Outside, overhead.. .. .. .. . .. . .. • .. .. .. .. .. .. . . . .... 12 Wires, Rubber covered, approved hst, page ••.•.•••••.•..... 44 jセ@ Wires, Trolley •• , •... セᄋqLi。Mjエッ@ v •• •••••••••••••• ••• イ・」セエ@ tf!SI" ll>do udM lh ャセ・@カ &t (1.-; o tor ,._.t-r.., -lith...!>, conduit._ ,..;,..,.. tti'C.IIlt ltnauu., ヲ。セMN@ O(C., U'l ft ᄋセ\Ai@ et m$pectioo orne.... ••II sh.,.ld " COJl,...tted Ia ;oft fAIM!II セエ・@ dD¥bt .e•l.u u lo tile ability of •"Y partk.lllf' H-•ice to tile R'....,.,. of '"l)edfluclo..- ••r IMR:CeA....,. -• recaun-.-r.. ui"""· Copies CJf A・セイmッケ@ """'"U on all . .lu•-S obutlned セ@ llfdlittlcls. buillflllg Mセᄋ@ ..lid GBセ@ .,. NMセ@ th ll«lrk•l 8urNt1 ッヲセ@ ffolltloNl het4l .of .In IJAdt-r· writwll tiC UNr セᄋ@ olt'n:c. #it.. 157 t.SIIIN SUftl.te "kll セ@ ョNエキuォ・Mセ^イ@ ft.•ir:u "" ....wdt tQftl ilre セN@ altould .,.. CoOII 1M; ••t.