2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
Adaptive Mho Type Distance Relaying Scheme
with Fault Resistance Compensation
Muhd Hafizi Idris, Member, IEEE, Mohd Saufi Ahmad, Ahmad Zaidi Abdullah, Surya Hardi
School of Electrical System Engineering
Universiti Malaysia Perlis,
Arau, Perlis, Malaysia.
Abstract-- This paper describes an adaptive distance relaying
scheme which can eliminate the effect of fault resistance on
distance relay zone reach. Distance relay is commonly used as
main protection to protect transmission line from any type of
fault. For a stand-alone distance relay, fault resistance can make
Mho type distance relay to be under reached and thus the fault
will be isolated at a longer time. In this scheme, the relay detects
the fault location using a two-terminal algorithm. By knowing
fault location, fault voltage at the fault point can be calculated by
using equivalent sequence network connection as seen from local
terminal. Then, fault resistance is calculated by using simple
equation considering contribution from remote terminal current.
Finally, the compensation of fault resistance is done onto
calculated apparent resistance as seen at relaying point. The
modeling and simulation was carried out using Matlab/Simulink
software. Several cases were carried out and the results show the
validity of the scheme.
Index Terms—Distance relay, Fault location, Fault resistance,
Matlab/Simulink, Mho type, Single line to ground
I. INTRODUCTION
T
ransmission line is one of the main components in High
Voltage (HV) and Extra High Voltage (EHV) power
system. The protection of transmission line from any type of
fault is very important because any mis-operation or maloperation of protection relays can give a great effect on the
stability of power system entirely. One of the main protection
used to protect transmission line is distance or impedance
relay. It uses the impedance measurement technique to
measure the apparent impedance as seen by the relay at the
relaying point. The inputs for distance relay are three phase
current and voltage phasors during fault occurrence.
Transmission line is segregated into several zones of
protection normally zone 1, zone 2 and zone 3 as shown in
Fig. 1 for relay at substation A [1]. Distance relay acts as main
protection for faults within zone 1 while for zone 2 and zone
3, it acts as backup protection for adjacent line.
Zone 1 reach is normally set only up to 80% - 90% of the
protected line. It is not set 100% of the protected line to avoid
relay from under reached or over reached due to current and
voltage measurement errors, transient effect and inaccuracy in
transmission line parameters. If a fault occurred within this
zone where distance relay acts as main protection, the relay
will instantaneously send trip signal to open the circuit
breaker.
To ensure full coverage of the protected line by considering
errors and other effects, zone 2 is set at minimum 120% of the
protected line. It is a common practice to set zone 2 reach
equal to 100% of the protected line plus 50% of the shortest
adjacent line. For faults within zone 2 reach, tripping signal
will be sent at a delayed time where the relay acts as backup
for main protection at adjacent line. The tripping time for zone
2 normally set at several hundred miliseconds.
Backup protection for entire adjacent line is covered by
zone 3 reach. It is normally set at least 1.2 times the
impedance of protected adjacent line. The set tripping time for
zone 3 reach is typically several seconds.
An accurate apparent impedance measurement during fault
occurrence by distance relay is very important because false
measurement might result in delayed tripping signal sent by
distance relay. There are several factors which can lead to
inaccurate apparent impedance measurement such as high
fault resistance, mutual inductance of parallel line, line
charging capacitance and transient effects due to switching of
Flexible Alternating Current Transmission System (FACTS)
devices [2]-[6].
In this paper, focus is given to compensate the effect of
fault resistance on the accuracy of Mho type distance relay.
Fault resistance can be high or low depending on the nature of
fault. Even a small fault resistance value can make the relay to
be under reached when it is used to protect short transmission
line. The relay also might be under reached when the fault is
near to remote substation terminal. Delayed tripping of circuit
breaker due to under reached of distance relay will make the
power system in stress for a longer time.
II. THEORIES OF THE PROPOSED SCHEME
Fig. 1. Zones of protection for distance relay
978-1-4673-5074-7/13/$31.00 ©2013 IEEE
This section presents the methodologies used to
compensate the effect of fault resistance on the accuracy of
apparent impedance measurement. The process began with
determining the fault location during the occurrence of fault.
There are many techniques currently and previously used to
208
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
locate the fault point. The most and commonly used technique
to locate fault at transmission line is impedance based
technique [7]. It measures the impedance by dividing the
fundamental frequency of voltage and current phasors at the
relaying point. It is widely used because of its simplicity and
easy to be adapted to electronic devices. However, this
technique is severely affected by fault resistance value where
the inaccuracy of fault location estimation increases with the
increase in fault resistance.
Available impedance based techniques also can be
classified into one-terminal and two-terminal algorithms.
Because of limitation in gaining measurement parameters,
one-terminal algorithm uses many assumptions in fault
location estimation which may lead to inaccurate result. Twoterminal algorithm is more accurate than one terminal
algorithm because it uses the voltage and current
measurements from both substation terminals. The data are
sent using low speed communication channel available at the
substation. This algorithm is expected to replace one-terminal
algorithm in the future because of the increasing use of
intelligent electronic devices (IED).
Two-terminal algorithm as was proposed by the author from
the previous research is used to estimate the fault location [8].
The algorithm does not need source impedance parameters
and estimated fault location is not influenced by fault
resistance value. Equation (1) represents the algorithm for
fault location calculation for Single Line to Ground (SLG)
fault while Fig. 2 shows the SLG fault condition at a phase
line.
m
(1)
the fault point can be calculated using (2). The value of fault
resistance, RF then directly calculated using (3). During fault
condition, current from both substations will flow into fault
point and return back to their sources. Hence, the contribution
of current from remote substation must be included into fault
resistance calculation.
Fig. 3. Sequence network connection as seen from local substation terminal
Where;
m
(2)
IA0 = Zero sequence component of phase current from local
substation.
RF
(3)
Where;
RF = Fault resistance
VF = Fault voltage between fault point and ground
IA = Phase current from local substation
IB = Phase current from remote substation
After the relay calculated the fault resistance, next step is to
compensate the effect of fault resistance on Mho type distance
relay. This is done first by measuring the apparent impedance
at the relaying point. The measurement of apparent impedance
is done by using (4) [9]. The apparent resistance, R and
reactance, X are the real and imaginary values of (4)
respectively.
Where;
m = fault location estimation (in per unit)
Z1 = Positive sequence impedance
Z2 = Negative sequence impedance
Z0 = Zero sequence impedance
VA = Phase to ground voltage for local substation
VB = Phase to ground voltage for remote substation
IA = Phase current from local substation
IB = Phase current from remote substation
(4)
Where;
k0 = residual compensation factor and k0 = (Z0-Z1)/kZ1.
I0 = Zero sequence component of neutral current.
After that, the apparent resistance will be subtracted with
fault resistance as shown in (5).
Rcompensated = R – RF
Fig. 2. Single line to ground fault
Fig. 3 shows the equivalent sequence network connection
for SLG fault as seen from local substation terminal. From the
result of fault location calculated using (1), fault voltage, VF at
Where;
Rcompensated = Compensated apparent resistance
R = Measured apparent resistance.
209
(5)
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
The proposed scheme was modeled using Matlab/Simulink
software. Table I lists the parameters used for transmission
line model. Fig. 5 shows the overall model for distance relay
with fault resistance compensation. The function of Analog
Low Pass Filter block is to filter any harmonic components
which may add to the fundamental frequency component of
voltage and current phasors. Next, the filtered voltage and
current phasors are transferred to Fourier Analysis block. The
function of this block is to extract the magnitude and phase
angle of every voltage and current phasors. Then, the
magnitudes and phase angles are used inside Fault Location
Calculation block. The output of this block is fault location in
kilometer. After that, from the value of fault location, it is
used inside Fault Resistance Calculation block to calculate
fault voltage and fault resistance.
Apparent impedance seen by the relay is calculated inside
Apparent Impedance Measurement block. The outputs of this
block are apparent resistance and apparent reactance at the
relaying point. Finally, the compensation is done by
subtracting the fault resistance from apparent resistance inside
Compensated Apparent Resistance block.
Start
V & I phasors from both substation terminals
Calculate fault location, m
Calculate fault voltage, VF
Calculate fault resistance, RF
Calculate apparent resistance, R and reactance, X
Subtract fault resistance, RF from apparent
resistance, R
Plot apparent reactance, X versus compensated
apparent resistance, Rcompensated
End
TABLE I
TRANSMISSION LINE PARAMETERS
Fig. 4. Proposed fault resistance compensation scheme
Fig. 4 shows the overall steps for the proposed fault
resistance compensation scheme. The final step is to plot the
apparent reactance versus the compensated apparent resistance
on R-X diagram.
III. MODELING THE PROPOSED SCHEME
Line Parameters
Line length
Nominal frequency
Phase to phase voltage
Positive sequence resistance
Zero sequence resistance
Positive sequence resistance
Zero sequence resistance
thetaIa
Out3
Ia
Out4
Va
Out1
Value
47
50
132,000
0.045531917
0.151489359
0.000617657
0.001533983
Unit
km
Hz
Volt
Ω / km
Ω / km
H / km
H / km
magnitude Z
angle Z
R
Apparent resistance
Out2
thetaVa
(pi /180 )*u
Continuous
Apparent Impedance
Measurement
radian 1
powergui
X
Apparent reactance
R
Out1
Va
fcn
In1
Out2
Rcompensated
Rf
thetaVa
Rcompensated
(pi /180 )*u
Iabc Local
In1
Out1
Vabc local
In2
Out4
Compensated apparent resistance
Out7
radian 2
Ia
Rcompensated
In4
thetaIa
Out8
Iabc remote
In3
Out7
In4
Out10
To Workspace1
fcn Fl _km
SLG Fault
Vb
Out13
Vabc remote
Out14
Transmission Line
Fault Location (km)
thetaVb
(pi /180 )*u
In7
radian 3
Ib
Analog Low Pass Filter
Out19
thetaIb
In10
Fault initiation
RF
Out20
Fourier Analysis
(pi /180 )*u
Fault Location Calculation
Va
radian 4
thetaVa
Ia
thetaIa
fcn
Rf
Ib
thetaIb
m
Fault Resistance Calculation
Fig. 5. Overall model of distance relay with fault resistance compensation.
210
Fault Resistance (ohm )
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
IV. SIMULATION RESULTS
This section presents the simulation results of Mho type
distance relay when subjected to fault with a resistive value.
The effectiveness and adaptability of the proposed scheme is
discussed. There are four cases simulated with different fault
locations and fault resistances. Below is the fault data for each
case.
Fig. 7 shows the result of apparent impedance locus for case
2 during fault occurrence with the same fault location as in
case 1 but with different fault resistance. It can be seen that for
uncompensated apparent impedance locus, fault resistance of
2 Ω has deviated away the final point of locus from zone 1. By
using the proposed scheme, the locus of apparent impedance
stop within the correct zone thus prevent distance relay from
under reached zone 1. The calculated fault location and fault
resistance are 34.55 km and 1.971 Ω respectively.
Case 1
1. Actual fault location = 35 km
2. Actual fault resistance = 0.01 Ω
Uncompensated
Compensated
Case 2
1. Actual Fault location = 35 km
2. Actual fault resistance = 2 Ω
Case 3
1. Actual Fault location = 45 km
2. Actual fault resistance = 0.01 Ω
Fig. 7. Apparent impedance locus for case 2
Case 4
1. Actual Fault location = 45 km
2. Actual fault resistance = 2 Ω
The selected zone reach settings for Mho type distance
relay at the local substation except Zone 3 are as follow;
Zone 1 = 80 % of the transmission line (equal to 37.6 km)
Zone 2 = 100 % + 20 % of the adjacent line (equal to 56.4 km)
Fig. 8 shows the result of apparent impedance locus for case
3 during fault occurrence at 45 km. It can be seen that both
locus for compensated and uncompensated apparent
impedance stop within the same zone and location. This is
because the fault resistance is very small compared to line
resistance and the effect is hardly seen. The calculated fault
location and fault resistance are 44.31 km and 0.1968 Ω
respectively.
Fig. 6 shows the result of apparent impedance locus for case
1 during fault occurrence at 35 km which is near the reach
setting of zone 1. It can be seen that both locus for
compensated and uncompensated apparent impedance stop
within zone 1 at the same location. This is because the fault
resistance is very small compared to line resistance. The
calculated fault location and fault resistance are 34.65 km and
0.06976 Ω respectively.
Compensated
Uncompensated
Compensated
Fig. 8. Apparent impedance locus for case 3
Uncompensated
Fig. 6. Apparent impedance locus for case 1
Fig. 9 shows the result of apparent impedance locus for case
4 during fault occurrence with the same fault location as in
case 3 but with different fault resistance. It can be seen that for
uncompensated apparent impedance locus, fault resistance of
2 Ω has deviated away the final point of locus from zone 2. By
using the proposed scheme, the locus of apparent impedance
stop within the correct zone thus prevent distance relay from
under reached zone 2. The calculated fault location and fault
resistance are 44.17 km and 1.933 Ω respectively.
211
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
VI. REFERENCES
Compensated
[1]
[2]
Uncompensated
[3]
[4]
[5]
Fig. 9. Apparent impedance locus for case 4
[6]
V. CONCLUSION
[7]
The results from the previous part show the adaptability of
the proposed scheme in compensating the effect of fault
resistance from making the Mho type distance relay under
reached. The scheme started with calculating the fault location
using two-terminal algorithm as in (1). Then, the fault voltage
and fault resistance is calculated directly using (2) and (3)
which consider the contribution of current from remote
substation. Then, apparent resistance and apparent reactance
are calculated using (4). Finally, calculated fault resistance
will be subtracted from calculated apparent resistance as
shown by (5).
[8]
[9]
212
B. Ram and D. N. Vishwakarma, “Power System Protection and
Switchgear”, Tata McGraw Hill, 1995.
M. E. Erezzaghi and P. A. Crossley, “The Effect Of High Resistance
Faults On A Distance Relay”, Power Engineering Society General
Meeting, IEEE, vol. 4, July 2003.
J. Upendar, C. P. Gupta and G. K. Singh , “Comprehensive Adaptive
Distance Relaying Scheme for Parallel Transmission Lines”, IEEE
Transactions on Power Delivery, vol. 26, no. 2, April 2011.
T. Kase, Y. Kurosawa and H. Amo, ‘‘Charging Current Compensation
for Distance Protection’’, Power Engineering Society General Meeting,
IEEE, vol. 3, pp. 2683 - 2688, June 2005.
K. Satyanarayana, B. K. V. Prasad and K. Saikrishna, “Effect of Series
FACTS Devices on Distance Protection”, International Conference on
Sustainable Energy and Intelligent Systems, pp. 36 – 41, July 2011.
T. S. Sidhu, R. K. Varma, P. K. Gangadharan, F. A. Albasri, and G. R.
Ortiz,“Performance of Distance Relays on Shunt – FACTS
Compensated Transmission Lines”, IEEE Transactions on Power
Delivery, vol. 20, no. 3, July 2005.
M. M. I. Hashim, H. W. Ping and V. K. Ramachandaramurthy,
“Impedance-Based Fault Location Techniques for Transmission Lines”,
TENCON, pp. 1-6, Jan 2009.
M. H. Idris, M. W. Mustafa and Y. Yatim, “Effective two-terminal
single line to ground fault location algorithm”, IEEE International
Power Engineering and Optimization Conference, pp. 246 – 251, June
2012.
M. H. Idris, S. Hardi and M. Z. Hassan, “Teaching Distance Relay
Using Matlab/Simulink Graphical User Interface”, Malaysian
Technical Universities Conference on Engineering and Technology,
November 2012.