Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Chapter A General rules of electrical installation design A1 Contents 3 4 Methodology A2 Rules and statutory regulations A4 2.1 Definition of voltage ranges 2.2 Regulations 2.3 Standards 2.4 Quality and safety of an electrical installation 2.5 Initial testing of an installation 2.6 Periodic check-testing of an installation 2.7 Conformity (with standards and specifications) of equipment used in the installation 2.8 Environment A4 A5 A5 A6 A6 A7 Installed power loads - Characteristics A10 3.1 Induction motors 3.2 Resistive-type heating appliances and incandescent lamps (conventional or halogen) A10 Power loading of an installation A15 4.1 4.2 4.3 4.4 4.5 4.6 4.7 A15 A15 A16 A17 A18 A19 A20 Installed power (kW) Installed apparent power (kVA) Estimation of actual maximum kVA demand Example of application of factors ku and ks Diversity factor Choice of transformer rating Choice of power-supply sources A7 A8 A12 © Schneider Electric - all rights reserved 1 2 Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 1 Methodology A2 For the best results in electrical installation design it is recommended to read all the chapters of this guide in the order in which they are presented. Listing of power demands A - General rules of electrical installation design The study of a proposed electrical installation requires an adequate understanding of all governing rules and regulations. The total power demand can be calculated from the data relative to the location and power of each load, together with the knowledge of the operating modes (steady state demand, starting conditions, non simultaneous operation, etc.) From these data, the power required from the supply source and (where appropriate) the number of sources necessary for an adequate supply to the installation are readily obtained. Local information regarding tariff structures is also required to allow the best choice of connection arrangement to the power-supply network, e.g. at medium voltage or low voltage level. Service connection B – Connection to the MV utility distribution network C - Connection to the LV utility distribution network D - MV & LV architecture selection guide E - LV Distribution F - Protection against electric shocks This connection can be made at: b Medium Voltage level A consumer-type substation will then have to be studied, built and equipped. This substation may be an outdoor or indoor installation conforming to relevant standards and regulations (the low-voltage section may be studied separately if necessary). Metering at medium-voltage or low-voltage is possible in this case. b Low Voltage level The installation will be connected to the local power network and will (necessarily) be metered according to LV tariffs. Electrical Distribution architecture The whole installation distribution network is studied as a complete system. A selection guide is proposed for determination of the most suitable architecture. MV/LV main distribution and LV power distribution levels are covered. Neutral earthing arrangements are chosen according to local regulations, constraints related to the power-supply, and to the type of loads. The distribution equipment (panelboards, switchgears, circuit connections, ...) are determined from building plans and from the location and grouping of loads. The type of premises and allocation can influence their immunity to external disturbances. Protection against electric shocks The earthing system (TT, IT or TN) having been previously determined, then the appropriate protective devices must be implemented in order to achieve protection against hazards of direct or indirect contact. G - Sizing and protection of conductors Circuits and switchgear © Schneider Electric - all rights reserved Each circuit is then studied in detail. From the rated currents of the loads, the level of short-circuit current, and the type of protective device, the cross-sectional area of circuit conductors can be determined, taking into account the nature of the cableways and their influence on the current rating of conductors. Before adopting the conductor size indicated above, the following requirements must be satisfied: b The voltage drop complies with the relevant standard b Motor starting is satisfactory b Protection against electric shock is assured H - LV switchgear: functions & selection The short-circuit current Isc is then determined, and the thermal and electrodynamic withstand capability of the circuit is checked. These calculations may indicate that it is necessary to use a conductor size larger than the size originally chosen. The performance required by the switchgear will determine its type and characteristics. The use of cascading techniques and the discriminative operation of fuses and tripping of circuit breakers are examined. Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 1 Methodology A3 Protection against overvoltages J – Protection against voltage surges in LV Direct or indirect lightning strokes can damage electrical equipment at a distance of several kilometers. Operating voltage surges, transient and industrial frequency over-voltage can also produce the same consequences.The effects are examined and solutions are proposed. K – Energy efficiency in electrical distribution Energy efficiency in electrial distribution Implementation of measuring devices with an adequate communication system within the electrical installation can produce high benefits for the user or owner: reduced power consumption, reduced cost of energy, better use of electrical equipment. L - Power factor correction and harmonic filtering Reactive energy The power factor correction within electrical installations is carried out locally, globally or as a combination of both methods. Harmonics M - Harmonic management Harmonics in the network affect the quality of energy and are at the origin of many disturbances as overloads, vibrations, ageing of equipment, trouble of sensitive equipment, of local area networks, telephone networks. This chapter deals with the origins and the effects of harmonics and explain how to measure them and present the solutions. N - Characteristics of particular sources and loads Particular supply sources and loads P - Residential and other special locations Generic applications Particular items or equipment are studied: b Specific sources such as alternators or inverters b Specific loads with special characteristics, such as induction motors, lighting circuits or LV/LV transformers b Specific systems, such as direct-current networks Certain premises and locations are subject to particularly strict regulations: the most common example being residential dwellings. EMC Guidelines Q - EMC guideline Some basic rules must be followed in order to ensure Electromagnetic Compatibility. Non observance of these rules may have serious consequences in the operation of the electrical installation: disturbance of communication systems, nuisance tripping of protection devices, and even destruction of sensitive devices. Ecodial software Ecodial software(1) provides a complete design package for LV installations, in accordance with IEC standards and recommendations. (1) Ecodial is a Merlin Gerin product and is available in French and English versions. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved The following features are included: b Construction of one-line diagrams b Calculation of short-circuit currents b Calculation of voltage drops b Optimization of cable sizes b Required ratings of switchgear and fusegear b Discrimination of protective devices b Recommendations for cascading schemes b Verification of the protection of people b Comprehensive print-out of the foregoing calculated design data A - General rules of electrical installation design 2 Rules and statutory regulations A4 Low-voltage installations are governed by a number of regulatory and advisory texts, which may be classified as follows: b Statutory regulations (decrees, factory acts,etc.) b Codes of practice, regulations issued by professional institutions, job specifications b National and international standards for installations b National and international standards for products 2.1 Definition of voltage ranges IEC voltage standards and recommendations Three-phase four-wire or three-wire systems Nominal voltage (V) 50 Hz 60 Hz – 120/208 – 240 230/400(1) 277/480 400/690(1) 480 – 347/600 1000 600 Single-phase three-wire systems Nominal voltage (V) 60 Hz 120/240 – – – – – (1) The nominal voltage of existing 220/380 V and 240/415 V systems shall evolve toward the recommended value of 230/400 V. The transition period should be as short as possible and should not exceed the year 2003. During this period, as a first step, the electricity supply authorities of countries having 220/380 V systems should bring the voltage within the range 230/400 V +6 %, -10 % and those of countries having 240/415 V systems should bring the voltage within the range 230/400 V +10 %, -6 %. At the end of this transition period, the tolerance of 230/400 V ± 10 % should have been achieved; after this the reduction of this range will be considered. All the above considerations apply also to the present 380/660 V value with respect to the recommended value 400/690 V. Fig. A1 : Standard voltages between 100 V and 1000 V (IEC 60038 Edition 6.2 2002-07) © Schneider Electric - all rights reserved Series I Highest voltage for equipment (kV) 3.6(1) 7.2(1) 12 – – – (17.5) 24 – 36(3) – 40.5(3) Nominal system voltage (kV) 3.3(1) 3(1) 6.6(1) 6(1) 11 10 – – – – – – – (15) 22 20 – – 33(3) – – – – 35(3) Series II Highest voltage for equipment (kV) 4.40(1) – – 13.2(2) 13.97(2) 14.52(1) – – 26.4(2) – 36.5 – Nominal system voltage (kV) 4.16(1) – – 12.47(2) 13.2(2) 13.8(1) – – 24.94(2) – 34.5 – These systems are generally three-wire systems unless otherwise indicated. The values indicated are voltages between phases. The values indicated in parentheses should be considered as non-preferred values. It is recommended that these values should not be used for new systems to be constructed in future. Note 1: It is recommended that in any one country the ratio between two adjacent nominal voltages should be not less than two. Note 2: In a normal system of Series I, the highest voltage and the lowest voltage do not differ by more than approximately ±10 % from the nominal voltage of the system. In a normal system of Series II, the highest voltage does not differ by more then +5 % and the lowest voltage by more than -10 % from the nominal voltage of the system. (1) These values should not be used for public distribution systems. (2) These systems are generally four-wire systems. (3) The unification of these values is under consideration. Fig. A2 : Standard voltages above 1 kV and not exceeding 35 kV (IEC 60038 Edition 6.2 2002-07) Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 2 Rules and statutory regulations A5 2.2 Regulations In most countries, electrical installations shall comply with more than one set of regulations, issued by National Authorities or by recognized private bodies. It is essential to take into account these local constraints before starting the design. 2.3 Standards IEC 60038 IEC 60076-2 IEC 60076-3 IEC 60076-5 IEC 60076-10 IEC 60146 IEC 60255 IEC 60265-1 IEC 60269-1 IEC 60269-2 IEC 60282-1 IEC 60287-1-1 IEC 60364 IEC 60364-1 IEC 60364-4-41 IEC 60364-4-42 IEC 60364-4-43 IEC 60364-4-44 IEC 60364-5-51 IEC 60364-5-52 IEC 60364-5-53 IEC 60364-5-54 IEC 60364-5-55 IEC 60364-6-61 IEC 60364-7-701 IEC 60364-7-702 IEC 60364-7-703 IEC 60364-7-704 IEC 60364-7-705 IEC 60364-7-706 IEC 60364-7-707 IEC 60364-7-708 IEC 60364-7-709 IEC 60364-7-710 IEC 60364-7-711 IEC 60364-7-712 IEC 60364-7-713 IEC 60364-7-714 IEC 60364-7-715 IEC 60364-7-717 IEC 60364-7-740 IEC 60427 IEC 60439-1 IEC 60439-2 IEC 60439-3 IEC 60439-4 IEC 60446 IEC 60439-5 IEC 60479-1 IEC 60479-2 IEC 60479-3 Standard voltages Power transformers - Temperature rise Power transformers - Insulation levels, dielectric tests and external clearances in air Power transformers - Ability to withstand short-circuit Power transformers - Determination of sound levels Semiconductor convertors - General requirements and line commutated convertors Electrical relays High-voltage switches - High-voltage switches for rated voltages above 1 kV and less than 52 kV Low-voltage fuses - General requirements Low-voltage fuses - Supplementary requirements for fuses for use by unskilled persons (fuses mainly for household and similar applications) High-voltage fuses - Current-limiting fuses Electric cables - Calculation of the current rating - Current rating equations (100% load factor) and calculation of losses - General Electrical installations of buildings Electrical installations of buildings - Fundamental principles Electrical installations of buildings - Protection for safety - Protection against electric shock Electrical installations of buildings - Protection for safety - Protection against thermal effects Electrical installations of buildings - Protection for safety - Protection against overcurrent Electrical installations of buildings - Protection for safety - Protection against electromagnetic and voltage disrurbance Electrical installations of buildings - Selection and erection of electrical equipment - Common rules Electrical installations of buildings - Selection and erection of electrical equipment - Wiring systems Electrical installations of buildings - Selection and erection of electrical equipment - Isolation, switching and control Electrical installations of buildings - Selection and erection of electrical equipment - Earthing arrangements Electrical installations of buildings - Selection and erection of electrical equipment - Other equipments Electrical installations of buildings - Verification and testing - Initial verification Electrical installations of buildings - Requirements for special installations or locations - Locations containing a bath tub or shower basin Electrical installations of buildings - Requirements for special installations or locations - Swimming pools and other basins Electrical installations of buildings - Requirements for special installations or locations - Locations containing sauna heaters Electrical installations of buildings - Requirements for special installations or locations - Construction and demolition site installations Electrical installations of buildings - Requirements for special installations or locations - Electrical installations of agricultural and horticultural premises Electrical installations of buildings - Requirements for special installations or locations - Restrictive conducting locations Electrical installations of buildings - Requirements for special installations or locations - Earthing requirements for the installation of data processing equipment Electrical installations of buildings - Requirements for special installations or locations - Electrical installations in caravan parks and caravans Electrical installations of buildings - Requirements for special installations or locations - Marinas and pleasure craft Electrical installations of buildings - Requirements for special installations or locations - Medical locations Electrical installations of buildings - Requirements for special installations or locations - Exhibitions, shows and stands Electrical installations of buildings - Requirements for special installations or locations - Solar photovoltaic (PV) power supply systems Electrical installations of buildings - Requirements for special installations or locations - Furniture Electrical installations of buildings - Requirements for special installations or locations - External lighting installations Electrical installations of buildings - Requirements for special installations or locations - Extra-low-voltage lighting installations Electrical installations of buildings - Requirements for special installations or locations - Mobile or transportable units Electrical installations of buildings - Requirements for special installations or locations - Temporary electrical installations for structures, amusement devices and booths at fairgrounds, amusement parks and circuses High-voltage alternating current circuit-breakers Low-voltage switchgear and controlgear assemblies - Type-tested and partially type-tested assemblies Low-voltage switchgear and controlgear assemblies - Particular requirements for busbar trunking systems (busways) Low-voltage switchgear and controlgear assemblies - Particular requirements for low-voltage switchgear and controlgear assemblies intended to be installed in places where unskilled persons have access for their use - Distribution boards Low-voltage switchgear and controlgear assemblies - Particular requirements for assemblies for construction sites (ACS) Basic and safety principles for man-machine interface, marking and identification - Identification of conductors by colours or numerals Low-voltage switchgear and controlgear assemblies - Particular requirements for assemblies intended to be installed outdoors in public places - Cable distribution cabinets (CDCs) Effects of current on human beings and livestock - General aspects Effects of current on human beings and livestock - Special aspects Effects of current on human beings and livestock - Effects of currents passing through the body of livestock (Continued on next page) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved This Guide is based on relevant IEC standards, in particular IEC 60364. IEC 60364 has been established by medical and engineering experts of all countries in the world comparing their experience at an international level. Currently, the safety principles of IEC 60364 and 60479-1 are the fundamentals of most electrical standards in the world (see table below and next page). A - General rules of electrical installation design 2 Rules and statutory regulations A6 IEC 60529 IEC 60644 IEC 60664 IEC 60715 IEC 60724 IEC 60755 IEC 60787 IEC 60831 IEC 60947-1 IEC 60947-2 IEC 60947-3 IEC 60947-4-1 IEC 60947-6-1 IEC 61000 IEC 61140 IEC 61557-1 IEC 61557-8 IEC 61557-9 IEC 61557-12 IEC 61558-2-6 IEC 62271-1 IEC 62271-100 IEC 62271-102 IEC 62271-105 IEC 62271-200 IEC 62271-202 Degrees of protection provided by enclosures (IP code) Spécification for high-voltage fuse-links for motor circuit applications Insulation coordination for equipment within low-voltage systems Dimensions of low-voltage switchgear and controlgear. Standardized mounting on rails for mechanical support of electrical devices in switchgear and controlgear installations. Short-circuit temperature limits of electric cables with rated voltages of 1 kV (Um = 1.2 kV) and 3 kV (Um = 3.6 kV) General requirements for residual current operated protective devices Application guide for the selection of fuse-links of high-voltage fuses for transformer circuit application Shunt power capacitors of the self-healing type for AC systems having a rated voltage up to and including 1000 V - General - Performance, testing and rating - Safety requirements - Guide for installation and operation Low-voltage switchgear and controlgear - General rules Low-voltage switchgear and controlgear - Circuit-breakers Low-voltage switchgear and controlgear - Switches, disconnectors, switch-disconnectors and fuse-combination units Low-voltage switchgear and controlgear - Contactors and motor-starters - Electromechanical contactors and motor-starters Low-voltage switchgear and controlgear - Multiple function equipment - Automatic transfer switching equipment Electromagnetic compatibility (EMC) Protection against electric shocks - common aspects for installation and equipment Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring of protective measures - General requirements Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring of protective measures Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for insulation fault location in IT systems Electrical safety in low-voltage distribution systems up to 1000 V AC and 1500 V DC - Equipment for testing, measuring or monitoring of protective measures. Performance measuring and monitoring devices (PMD) Safety of power transformers, power supply units and similar - Particular requirements for safety isolating transformers for general use Common specifications for high-voltage switchgear and controlgear standards High-voltage switchgear and controlgear - High-voltage alternating-current circuit-breakers High-voltage switchgear and controlgear - Alternating current disconnectors and earthing switches High-voltage switchgear and controlgear - Alternating current switch-fuse combinations High-voltage switchgear and controlgear - Alternating current metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV High-voltage/low voltage prefabricated substations (Concluded) 2.4 Quality and safety of an electrical installation In so far as control procedures are respected, quality and safety will be assured only if: b The initial checking of conformity of the electrical installation with the standard and regulation has been achieved b The electrical equipment comply with standards b The periodic checking of the installation recommended by the equipment manufacturer is respected. 2.5 Initial testing of an installation Before a utility will connect an installation to its supply network, strict precommissioning electrical tests and visual inspections by the authority, or by its appointed agent, must be satisfied. These tests are made according to local (governmental and/or institutional) regulations, which may differ slightly from one country to another. The principles of all such regulations however, are common, and are based on the observance of rigorous safety rules in the design and realization of the installation. © Schneider Electric - all rights reserved IEC 60364-6-61 and related standards included in this guide are based on an international consensus for such tests, intended to cover all the safety measures and approved installation practices normally required for residential, commercial and (the majority of) industrial buildings. Many industries however have additional regulations related to a particular product (petroleum, coal, natural gas, etc.). Such additional requirements are beyond the scope of this guide. The pre-commissioning electrical tests and visual-inspection checks for installations in buildings include, typically, all of the following: b Insulation tests of all cable and wiring conductors of the fixed installation, between phases and between phases and earth b Continuity and conductivity tests of protective, equipotential and earth-bonding conductors b Resistance tests of earthing electrodes with respect to remote earth b Verification of the proper operation of the interlocks, if any b Check of allowable number of socket-outlets per circuit Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 2 Rules and statutory regulations A7 b Cross-sectional-area check of all conductors for adequacy at the short-circuit levels prevailing, taking account of the associated protective devices, materials and installation conditions (in air, conduit, etc.) b Verification that all exposed- and extraneous metallic parts are properly earthed (where appropriate) b Check of clearance distances in bathrooms, etc. These tests and checks are basic (but not exhaustive) to the majority of installations, while numerous other tests and rules are included in the regulations to cover particular cases, for example: TN-, TT- or IT-earthed installations, installations based on class 2 insulation, SELV circuits, and special locations, etc. The aim of this guide is to draw attention to the particular features of different types of installation, and to indicate the essential rules to be observed in order to achieve a satisfactory level of quality, which will ensure safe and trouble-free performance. The methods recommended in this guide, modified if necessary to comply with any possible variation imposed by a utility, are intended to satisfy all precommissioning test and inspection requirements. 2.6 Periodic check-testing of an installation In many countries, all industrial and commercial-building installations, together with installations in buildings used for public gatherings, must be re-tested periodically by authorized agents. Figure A3 shows the frequency of testing commonly prescribed according to the kind of installation concerned. Type of installation Installations which require the protection of employees Installations in buildings used for public gatherings, where protection against the risks of fire and panic are required Residential b Locations at which a risk of degradation, fire or explosion exists b Temporary installations at worksites b Locations at which MV installations exist b Restrictive conducting locations where mobile equipment is used Other cases According to the type of establishment and its capacity for receiving the public Testing frequency Annually Every 3 years From one to three years According to local regulations Fig A3 : Frequency of check-tests commonly recommended for an electrical installation 2.7 Conformity (with standards and specifications) of equipment used in the installation Attestation of conformity The conformity of equipment with the relevant standards can be attested: b By an official mark of conformity granted by the certification body concerned, or b By a certificate of conformity issued by a certification body, or b By a declaration of conformity from the manufacturer The first two solutions are generally not available for high voltage equipment. Declaration of conformity Where the equipment is to be used by skilled or instructed persons, the manufacturer’s declaration of conformity (included in the technical documentation), is generally recognized as a valid attestation. Where the competence of the manufacturer is in doubt, a certificate of conformity can reinforce the manufacturer’s declaration. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Conformity of equipment with the relevant standards can be attested in several ways A - General rules of electrical installation design 2 Rules and statutory regulations A8 Note: CE marking In Europe, the European directives require the manufacturer or his authorized representative to affix the CE marking on his own responsibility. It means that: b The product meets the legal requirements b It is presumed to be marketable in Europe The CE marking is neither a mark of origin nor a mark of conformity. Mark of conformity Marks of conformity are affixed on appliances and equipment generally used by ordinary non instructed people (e.g in the field of domestic appliances). A mark of conformity is delivered by certification body if the equipment meet the requirements from an applicable standard and after verification of the manufacturer’s quality management system. Certification of Quality The standards define several methods of quality assurance which correspond to different situations rather than to different levels of quality. Assurance A laboratory for testing samples cannot certify the conformity of an entire production run: these tests are called type tests. In some tests for conformity to standards, the samples are destroyed (tests on fuses, for example). Only the manufacturer can certify that the fabricated products have, in fact, the characteristics stated. Quality assurance certification is intended to complete the initial declaration or certification of conformity. As proof that all the necessary measures have been taken for assuring the quality of production, the manufacturer obtains certification of the quality control system which monitors the fabrication of the product concerned. These certificates are issued by organizations specializing in quality control, and are based on the international standard ISO 9001: 2000. These standards define three model systems of quality assurance control corresponding to different situations rather than to different levels of quality: b Model 3 defines assurance of quality by inspection and checking of final products. b Model 2 includes, in addition to checking of the final product, verification of the manufacturing process. For example, this method is applied, to the manufacturer of fuses where performance characteristics cannot be checked without destroying the fuse. b Model 1 corresponds to model 2, but with the additional requirement that the quality of the design process must be rigorously scrutinized; for example, where it is not intended to fabricate and test a prototype (case of a custom-built product made to specification). 2.8 Environment Environmental management systems can be certified by an independent body if they meet requirements given in ISO 14001. This type of certification mainly concerns industrial settings but can also be granted to places where products are designed. © Schneider Electric - all rights reserved A product environmental design sometimes called “eco-design” is an approach of sustainable development with the objective of designing products/services best meeting the customers’ requirements while reducing their environmental impact over their whole life cycle. The methodologies used for this purpose lead to choose equipment’s architecture together with components and materials taking into account the influence of a product on the environment along its life cycle (from extraction of raw materials to scrap) i.e. production, transport, distribution, end of life etc. In Europe two Directives have been published, they are called: b RoHS Directive (Restriction of Hazardous Substances) coming into force on July 2006 (the coming into force was on February 13th, 2003, and the application date is July 1st, 2006) aims to eliminate from products six hazardous substances: lead, mercury, cadmium, hexavalent chromium, polybrominated biphenyls (PBB) or polybrominated diphenyl ethers (PBDE). Schneider Electric - Electrical installation guide 2009 2 Rules and statutory regulations A9 b WEEE Directive (Waste of Electrical and Electronic Equipment) coming into force in August 2005 (the coming into force was on February 13th, 2003, and the application date is August 13th, 2005) in order to master the end of life and treatments for household and non household equipment. In other parts of the world some new legislation will follow the same objectives. In addition to manufacturers action in favour of products eco-design, the contribution of the whole electrical installation to sustainable development can be significantly improved through the design of the installation. Actually, it has been shown that an optimised design of the installation, taking into account operation conditions, MV/LV substations location and distribution structure (switchboards, busways, cables), can reduce substantially environmental impacts (raw material depletion, energy depletion, end of life) See chapter D about location of the substation and the main LV switchboard. © Schneider Electric - all rights reserved A - General rules of electrical installation design Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 3 Installed power loads Characteristics A10 The examination of actual values of apparent-power required by each load enables the establishment of: An examination of the actual apparentpower demands of different loads: a necessary preliminary step in the design of a LV installation b A declared power demand which determines the contract for the supply of energy b The rating of the MV/LV transformer, where applicable (allowing for expected increased load) b Levels of load current at each distribution board The nominal power in kW (Pn) of a motor indicates its rated equivalent mechanical power output. The apparent power in kVA (Pa) supplied to the motor is a function of the output, the motor efficiency and the power factor. Pn Pa = ηcosϕ 3.1 Induction motors Current demand The full-load current Ia supplied to the motor is given by the following formulae: b 3-phase motor: Ia = Pn x 1,000 / (√3 x U x η x cos ϕ) b 1-phase motor: Ia = Pn x 1,000 / (U x η x cos ϕ) where Ia: current demand (in amps) Pn: nominal power (in kW) U: voltage between phases for 3-phase motors and voltage between the terminals for single-phase motors (in volts). A single-phase motor may be connected phase-toneutral or phase-to-phase. η: per-unit efficiency, i.e. output kW / input kW cos ϕ: power factor, i.e. kW input / kVA input Subtransient current and protection setting b Subtransient current peak value can be very high ; typical value is about 12 to 15 times the rms rated value Inm. Sometimes this value can reach 25 times Inm. b Merlin Gerin circuit-breakers, Telemecanique contactors and thermal relays are designed to withstand motor starts with very high subtransient current (subtransient peak value can be up to 19 times the rms rated value Inm). b If unexpected tripping of the overcurrent protection occurs during starting, this means the starting current exceeds the normal limits. As a result, some maximum switchgear withstands can be reached, life time can be reduced and even some devices can be destroyed. In order to avoid such a situation, oversizing of the switchgear must be considered. b Merlin Gerin and Telemecanique switchgears are designed to ensure the protection of motor starters against short-circuits. According to the risk, tables show the combination of circuit-breaker, contactor and thermal relay to obtain type 1 or type 2 coordination (see chapter N). Motor starting current Although high efficiency motors can be found on the market, in practice their starting currents are roughly the same as some of standard motors. The use of start-delta starter, static soft start unit or variable speed drive allows to reduce the value of the starting current (Example : 4 Ia instead of 7.5 Ia). Compensation of reactive-power (kvar) supplied to induction motors © Schneider Electric - all rights reserved It is generally advantageous for technical and financial reasons to reduce the current supplied to induction motors. This can be achieved by using capacitors without affecting the power output of the motors. The application of this principle to the operation of induction motors is generally referred to as “power-factor improvement” or “power-factor correction”. As discussed in chapter L, the apparent power (kVA) supplied to an induction motor can be significantly reduced by the use of shunt-connected capacitors. Reduction of input kVA means a corresponding reduction of input current (since the voltage remains constant). Compensation of reactive-power is particularly advised for motors that operate for long periods at reduced power. kW input so kVA input will sothat thataakVA kVA input input reduction reduction in will increase kVA input (i.e. improve) the value of cos ϕ . increase (i.e. improve) the value of cos As noted above cos = Schneider Electric - Electrical installation guide 2009 3 Installed power loads Characteristics A11 The current supplied to the motor, after power-factor correction, is given by: cos I=Ia cos ' where cos ϕ is the power factor before compensation and cos ϕ’ is the power factor after compensation, Ia being the original current. Figure A4 below shows, in function of motor rated power, standard motor current values for several voltage supplies. kW hp 230 V 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3.0 3.7 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 150 160 185 200 220 250 280 300 1/2 3/4 1 1-1/2 2 3 7-1/2 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 - A 1.0 1.5 1.9 2.6 3.3 4.7 6.3 8.5 11.3 15 20 27 38.0 51 61 72 96 115 140 169 230 278 340 400 487 609 748 - 380 415 V A 1.3 1.8 2.3 3.3 4.3 6.1 9.7 14.0 18.0 27.0 34.0 44 51 66 83 103 128 165 208 240 320 403 482 560 636 - 400 V A 0.6 0.85 1.1 1.5 1.9 2.7 3.6 4.9 6.5 8.5 11.5 15.5 22.0 29 35 41 55 66 80 97 132 160 195 230 280 350 430 - 440 480 V A 1.1 1.6 2.1 3.0 3.4 4.8 7.6 11.0 14.0 21.0 27.0 34 40 52 65 77 96 124 156 180 240 302 361 414 474 - Fig. A4 : Rated operational power and currents (continued on next page) Schneider Electric - Electrical installation guide 2009 500 V 690 V A 0.48 0.68 0.88 1.2 1.5 2.2 2.9 3.9 5.2 6.8 9.2 12.4 17.6 23 28 33 44 53 64 78 106 128 156 184 224 280 344 - A 0.35 0.49 0.64 0.87 1.1 1.6 2.1 2.8 3.8 4.9 6.7 8.9 12.8 17 21 24 32 39 47 57 77 93 113 134 162 203 250 - © Schneider Electric - all rights reserved A - General rules of electrical installation design A - General rules of electrical installation design 3 Installed power loads Characteristics A12 kW hp 230 V 315 335 355 375 400 425 450 475 500 530 560 600 630 670 710 750 800 850 900 950 1000 540 500 - A 940 1061 1200 1478 1652 1844 2070 2340 2640 2910 380 415 V A 786 - 400 V 440 480 V A 515 590 - A 540 610 690 850 950 1060 1190 1346 1518 1673 500 V 690 V A 432 488 552 680 760 848 952 1076 1214 1339 A 313 354 400 493 551 615 690 780 880 970 Fig. A4 : Rated operational power and currents (concluded) 3.2 Resistive-type heating appliances and incandescent lamps (conventional or halogen) The current demand of a heating appliance or an incandescent lamp is easily obtained from the nominal power Pn quoted by the manufacturer (i.e. cos ϕ = 1) (see Fig. A5). © Schneider Electric - all rights reserved Nominal power (kW) 0.1 0.2 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 6 7 8 9 10 Current demand (A) 1-phase 1-phase 127 V 230 V 0.79 0.43 1.58 0.87 3.94 2.17 7.9 4.35 11.8 6.52 15.8 8.70 19.7 10.9 23.6 13 27.6 15.2 31.5 17.4 35.4 19.6 39.4 21.7 47.2 26.1 55.1 30.4 63 34.8 71 39.1 79 43.5 3-phase 230 V 0.25 0.50 1.26 2.51 3.77 5.02 6.28 7.53 8.72 10 11.3 12.6 15.1 17.6 20.1 22.6 25.1 3-phase 400 V 0.14 0.29 0.72 1.44 2.17 2.89 3.61 4.33 5.05 5.77 6.5 7.22 8.66 10.1 11.5 13 14.4 Fig. A5 : Current demands of resistive heating and incandescent lighting (conventional or halogen) appliances Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 3 Installed power loads Characteristics A13 The currents are given by: b 3-phase case: case: I a = Pn (1) 3U Pn b 1-phase case: case: I a = (1) U where U is the voltage between the terminals of the equipment. For an incandescent lamp, the use of halogen gas allows a more concentrated light source. The light output is increased and the lifetime of the lamp is doubled. Note: At the instant of switching on, the cold filament gives rise to a very brief but intense peak of current. Fluorescent lamps and related equipment The power Pn (watts) indicated on the tube of a fluorescent lamp does not include the power dissipated in the ballast. The current is given by: Ia = Pballast + Pn U cos Where U = the voltage applied to the lamp, complete with its related equipment. If no power-loss value is indicated for the ballast, a figure of 25% of Pn may be used. Standard tubular fluorescent lamps With (unless otherwise indicated): b cos ϕ = 0.6 with no power factor (PF) correction(2) capacitor b cos ϕ = 0.86 with PF correction(2) (single or twin tubes) b cos ϕ = 0.96 for electronic ballast. If no power-loss value is indicated for the ballast, a figure of 25% of Pn may be used. Figure A6 gives these values for different arrangements of ballast. Arrangement Tube power of lamps, starters (W) (3) and ballasts Single tube 18 36 58 Twin tubes 2 x 18 2 x 36 2 x 58 (3) Power in watts marked on tube Current (A) at 230 V Magnetic ballast Without PF correction capacitor 0.20 0.33 0.50 With PF correction capacitor 0.14 0.23 0.36 0.28 0.46 0.72 Electronic ballast Tube length (cm) 0.10 0.18 0.28 0.18 0.35 0.52 60 120 150 60 120 150 Fig. A6 : Current demands and power consumption of commonly-dimensioned fluorescent lighting tubes (at 230 V-50 Hz) Compact fluorescent lamps (1) Ia in amps; U in volts. Pn is in watts. If Pn is in kW, then multiply the equation by 1,000 (2) “Power-factor correction” is often referred to as “compensation” in discharge-lighting-tube terminology. Cos ϕ is approximately 0.95 (the zero values of V and I are almost in phase) but the power factor is 0.5 due to the impulsive form of the current, the peak of which occurs “late” in each half cycle Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Compact fluorescent lamps have the same characteristics of economy and long life as classical tubes. They are commonly used in public places which are permanently illuminated (for example: corridors, hallways, bars, etc.) and can be mounted in situations otherwise illuminated by incandescent lamps (see Fig. A7 next page). A - General rules of electrical installation design 3 Installed power loads Characteristics A14 Type of lamp Separated ballast lamp Integrated ballast lamp Lamp power (W) 10 18 26 8 11 16 21 Current at 230 V (A) 0.080 0.110 0.150 0.075 0.095 0.125 0.170 Fig. A7 : Current demands and power consumption of compact fluorescent lamps (at 230 V - 50 Hz) Discharge lamps The power in watts indicated on the tube of a discharge lamp does not include the power dissipated in the ballast. Figure A8 gives the current taken by a complete unit, including all associated ancillary equipment. These lamps depend on the luminous electrical discharge through a gas or vapour of a metallic compound, which is contained in a hermetically-sealed transparent envelope at a pre-determined pressure. These lamps have a long start-up time, during which the current Ia is greater than the nominal current In. Power and current demands are given for different types of lamp (typical average values which may differ slightly from one manufacturer to another). Type of lamp (W) Power demand (W) at 230 V 400 V Current In(A) Starting PF not PF Ia/In corrected corrected 230 V 400 V 230 V 400 V © Schneider Electric - all rights reserved High-pressure sodium vapour lamps 50 60 0.76 70 80 1 100 115 1.2 150 168 1.8 250 274 3 400 431 4.4 1000 1055 10.45 Low-pressure sodium vapour lamps 26 34.5 0.45 36 46.5 66 80.5 91 105.5 131 154 Period (mins) Luminous efficiency (lumens per watt) Average timelife of lamp (h) Utilization 0.3 0.45 0.65 0.85 1.4 2.2 4.9 1.4 to 1.6 4 to 6 80 to 120 9000 b Lighting of large halls b Outdoor spaces b Public lighting 0.17 0.22 0.39 0.49 0.69 1.1 to 1.3 7 to 15 100 to 200 8000 to 12000 b Lighting of autoroutes b Security lighting, station b Platform, storage areas Mercury vapour + metal halide (also called metal-iodide) 70 80.5 1 0.40 1.7 3 to 5 70 to 90 6000 b Lighting of very 150 172 1.80 0.88 6000 large areas by 250 276 2.10 1.35 6000 projectors (for 400 425 3.40 2.15 6000 example: sports 1000 1046 8.25 5.30 6000 stadiums, etc.) 2000 2092 2052 16.50 8.60 10.50 6 2000 Mercury vapour + fluorescent substance (fluorescent bulb) 50 57 0.6 0.30 1.7 to 2 3 to 6 40 to 60 8000 b Workshops 80 90 0.8 0.45 to 12000 with very high 125 141 1.15 0.70 ceilings (halls, 250 268 2.15 1.35 hangars) 400 421 3.25 2.15 b Outdoor lighting 700 731 5.4 3.85 b Low light output(1) 1000 1046 8.25 5.30 2000 2140 2080 15 11 6.1 (1) Replaced by sodium vapour lamps. Note: these lamps are sensitive to voltage dips. They extinguish if the voltage falls to less than 50% of their nominal voltage, and will not re-ignite before cooling for approximately 4 minutes. Note: Sodium vapour low-pressure lamps have a light-output efficiency which is superior to that of all other sources. However, use of these lamps is restricted by the fact that the yellow-orange colour emitted makes colour recognition practically impossible. Fig. A8 : Current demands of discharge lamps Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 4 Power loading of an installation A15 In order to design an installation, the actual maximum load demand likely to be imposed on the power-supply system must be assessed. To base the design simply on the arithmetic sum of all the loads existing in the installation would be extravagantly uneconomical, and bad engineering practice. The aim of this chapter is to show how some factors taking into account the diversity (non simultaneous operation of all appliances of a given group) and utilization (e.g. an electric motor is not generally operated at its full-load capability, etc.) of all existing and projected loads can be assessed. The values given are based on experience and on records taken from actual installations. In addition to providing basic installation-design data on individual circuits, the results will provide a global value for the installation, from which the requirements of a supply system (distribution network, MV/LV transformer, or generating set) can be specified. 4.1 Installed power (kW) The installed power is the sum of the nominal powers of all power consuming devices in the installation. This is not the power to be actually supplied in practice. Most electrical appliances and equipments are marked to indicate their nominal power rating (Pn). The installed power is the sum of the nominal powers of all power-consuming devices in the installation. This is not the power to be actually supplied in practice. This is the case for electric motors, where the power rating refers to the output power at its driving shaft. The input power consumption will evidently be greater Fluorescent and discharge lamps associated with stabilizing ballasts, are other cases in which the nominal power indicated on the lamp is less than the power consumed by the lamp and its ballast. Methods of assessing the actual power consumption of motors and lighting appliances are given in Section 3 of this Chapter. The power demand (kW) is necessary to choose the rated power of a generating set or battery, and where the requirements of a prime mover have to be considered. For a power supply from a LV public-supply network, or through a MV/LV transformer, the significant quantity is the apparent power in kVA. 4.2 Installed apparent power (kVA) The installed apparent power is commonly assumed to be the arithmetical sum of the kVA of individual loads. The maximum estimated kVA to be supplied however is not equal to the total installed kVA. The installed apparent power is commonly assumed to be the arithmetical sum of the kVA of individual loads. The maximum estimated kVA to be supplied however is not equal to the total installed kVA. The apparent-power demand of a load (which might be a single appliance) is obtained from its nominal power rating (corrected if necessary, as noted above for motors, etc.) and the application of the following coefficients: η = the per-unit efficiency = output kW / input kW cos ϕ = the power factor = kW / kVA The apparent-power kVA demand of the load Pa = Pn /(η x cos ϕ) From this value, the full-load current Ia (A)(1) taken by the load will be: Pa x 103 V for single phase-to-neutral for single phase-to-neutral connected load c b Ia = Pa x 103 3xU for single phase-to-neutral for three-phase balanced load where: (1) For greater precision, account must be taken of the factor of maximum utilization as explained below in 4.3 V = phase-to-neutral voltage (volts) U = phase-to-phase voltage (volts) It may be noted that, strictly speaking, the total kVA of apparent power is not the arithmetical sum of the calculated kVA ratings of individual loads (unless all loads are at the same power factor). It is common practice however, to make a simple arithmetical summation, the result of which will give a kVA value that exceeds the true value by an acceptable “design margin”. When some or all of the load characteristics are not known, the values shown in Figure A9 next page may be used to give a very approximate estimate of VA demands (individual loads are generally too small to be expressed in kVA or kW). The estimates for lighting loads are based on floor areas of 500 m2. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved c b Ia = A - General rules of electrical installation design 4 Power loading of an installation A16 Fluorescent lighting (corrected to cos ϕ = 0.86) Type of application Estimated (VA/m2) Average lighting fluorescent tube level (lux = lm/m2) with industrial reflector(1) Roads and highways 7 150 storage areas, intermittent work Heavy-duty works: fabrication and 14 300 assembly of very large work pieces Day-to-day work: office work 24 500 Fine work: drawing offices 41 800 high-precision assembly workshops Power circuits Type of application Estimated (VA/m2) Pumping station compressed air 3 to 6 Ventilation of premises 23 Electrical convection heaters: private houses 115 to 146 flats and apartments 90 Offices 25 Dispatching workshop 50 Assembly workshop 70 Machine shop 300 Painting workshop 350 Heat-treatment plant 700 (1) example: 65 W tube (ballast not included), flux 5,100 lumens (Im), luminous efficiency of the tube = 78.5 Im / W. Fig. A9 : Estimation of installed apparent power 4.3 Estimation of actual maximum kVA demand All individual loads are not necessarily operating at full rated nominal power nor necessarily at the same time. Factors ku and ks allow the determination of the maximum power and apparent-power demands actually required to dimension the installation. Factor of maximum utilization (ku) In normal operating conditions the power consumption of a load is sometimes less than that indicated as its nominal power rating, a fairly common occurrence that justifies the application of an utilization factor (ku) in the estimation of realistic values. This factor must be applied to each individual load, with particular attention to electric motors, which are very rarely operated at full load. In an industrial installation this factor may be estimated on an average at 0.75 for motors. For incandescent-lighting loads, the factor always equals 1. For socket-outlet circuits, the factors depend entirely on the type of appliances being supplied from the sockets concerned. © Schneider Electric - all rights reserved Factor of simultaneity (ks) It is a matter of common experience that the simultaneous operation of all installed loads of a given installation never occurs in practice, i.e. there is always some degree of diversity and this fact is taken into account for estimating purposes by the use of a simultaneity factor (ks). The factor ks is applied to each group of loads (e.g. being supplied from a distribution or sub-distribution board). The determination of these factors is the responsibility of the designer, since it requires a detailed knowledge of the installation and the conditions in which the individual circuits are to be exploited. For this reason, it is not possible to give precise values for general application. Factor of simultaneity for an apartment block Some typical values for this case are given in Figure A10 opposite page, and are applicable to domestic consumers supplied at 230/400 V (3-phase 4-wires). In the case of consumers using electrical heat-storage units for space heating, a factor of 0.8 is recommended, regardless of the number of consumers. Schneider Electric - Electrical installation guide 2009 4 Power loading of an installation A17 Number of downstream consumers 2 to 4 5 to 9 10 to 14 15 to 19 20 to 24 25 to 29 30 to 34 35 to 39 40 to 49 50 and more Factor of simultaneity (ks) 1 0.78 0.63 0.53 0.49 0.46 0.44 0.42 0.41 0.40 Fig. A10 : Simultaneity factors in an apartment block Example (see Fig. A11): 5 storeys apartment building with 25 consumers, each having 6 kVA of installed load. The total installed load for the building is: 36 + 24 + 30 + 36 + 24 = 150 kVA The apparent-power supply required for the building is: 150 x 0.46 = 69 kVA From Figure A10, it is possible to determine the magnitude of currents in different sections of the common main feeder supplying all floors. For vertical rising mains fed at ground level, the cross-sectional area of the conductors can evidently be progressively reduced from the lower floors towards the upper floors. These changes of conductor size are conventionally spaced by at least 3-floor intervals. In the example, the current entering the rising main at ground level is: 150 x 0.46 x 103 400 3 = 100 A the current entering the third floor is: (36 + 24) x 0.63 x 103 400 3 = 55 A 4th floor 6 consumers 36 kVA 3 rd floor 4 consumers 24 kVA 2 nd floor 5 consumers 30 kVA 1st floor 6 consumers 36 kVA ground floor 4 consumers 24 kVA 0.78 0.63 0.53 0.49 0.46 Fig. A11 : Application of the factor of simultaneity (ks) to an apartment block of 5 storeys Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved A - General rules of electrical installation design A - General rules of electrical installation design 4 Power loading of an installation A18 Factor of simultaneity for distribution boards Figure A12 shows hypothetical values of ks for a distribution board supplying a number of circuits for which there is no indication of the manner in which the total load divides between them. If the circuits are mainly for lighting loads, it is prudent to adopt ks values close to unity. Number of circuits Assemblies entirely tested 2 and 3 4 and 5 6 to 9 10 and more Assemblies partially tested in every case choose Factor of simultaneity (ks) 0.9 0.8 0.7 0.6 1.0 Fig. A12 : Factor of simultaneity for distribution boards (IEC 60439) Factor of simultaneity according to circuit function ks factors which may be used for circuits supplying commonly-occurring loads, are shown in Figure A13. Circuit function Factor of simultaneity (ks) Lighting 1 Heating and air conditioning 1 Socket-outlets 0.1 to 0.2 (1) Lifts and catering hoist (2) b For the most powerful motor 1 b For the second most powerful motor 0.75 b For all motors 0.60 (1) In certain cases, notably in industrial installations, this factor can be higher. (2) The current to take into consideration is equal to the nominal current of the motor, increased by a third of its starting current. Fig. A13 : Factor of simultaneity according to circuit function 4.4 Example of application of factors ku and ks An example in the estimation of actual maximum kVA demands at all levels of an installation, from each load position to the point of supply is given Fig. A14 (opposite page). In this example, the total installed apparent power is 126.6 kVA, which corresponds to an actual (estimated) maximum value at the LV terminals of the MV/LV transformer of 65 kVA only. Note: in order to select cable sizes for the distribution circuits of an installation, the current I (in amps) through a circuit is determined from the equation: kVA x 103 I= U 3 © Schneider Electric - all rights reserved where kVA is the actual maximum 3-phase apparent-power value shown on the diagram for the circuit concerned, and U is the phase to- phase voltage (in volts). 4.5 Diversity factor The term diversity factor, as defined in IEC standards, is identical to the factor of simultaneity (ks) used in this guide, as described in 4.3. In some English-speaking countries however (at the time of writing) diversity factor is the inverse of ks i.e. it is always u 1. Schneider Electric - Electrical installation guide 2009 A - General rules of electrical installation design 4 Power loading of an installation A19 Level 2 Level 1 Utilization Level 3 Apparent Utilization Apparent Simultaneity Apparent Simultaneity Apparent Simultaneity Apparent power factor power factor power factor power factor power (Pa) max. demand demand demand demand kVA max. kVA kVA kVA kVA Workshop A Lathe no. 1 5 0.8 4 no. 2 5 0.8 4 no. 3 5 0.8 4 no. 4 5 0.8 4 2 0.8 1.6 2 0.8 1.6 18 1 18 0.2 3.6 3 1 3 1 3 15 0.8 12 1 12 Socket- 10.6 1 10.6 0.4 4.3 1 1 1 1 1 Workshop C Ventilation no. 1 2.5 1 2.5 no. 2 2.5 1 2.5 Distribution box no. 1 15 1 15 no. 2 5 socketoutlets 10/16 A 15 1 15 18 1 18 0.28 5 2 1 2 1 2 Pedestalno. 1 drill no. 2 5 socketoutlets 10/16 A 30 fluorescent lamps Workshop B Compressor 3 socketoutlets 10/16 A 10 fluorescent lamps Oven 20 fluorescent lamps Distribution box 0.75 1 Power circuit 14.4 Workshop A distribution box 0.9 Socketoulets Lighting circuit Power circuit oulets Workshop B distribution box Lighting circuit 18.9 Main general distribution board MGDB LV / MV 15.6 65 0.9 0.9 Workshop C distribution 35 Powver box circuit 0.9 37.8 Socketoulets Lighting circuit Fig A14 : An example in estimating the maximum predicted loading of an installation (the factor values used are for demonstration purposes only) 4.6 Choice of transformer rating When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of the installation has been determined, a suitable rating for the transformer can be decided, taking into account the following considerations (see Fig. A15): b The possibility of improving the power factor of the installation (see chapter L) b Anticipated extensions to the installation b Installation constraints (e.g. temperature) Apparent power kVA 100 160 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 In (A) 237 V 244 390 609 767 974 1218 1535 1949 2436 3045 3898 4872 6090 7673 410 V 141 225 352 444 563 704 887 1127 1408 1760 2253 2816 3520 4436 Fig. A15 : Standard apparent powers for MV/LV transformers and related nominal output currents Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved b Standard transformer ratings A - General rules of electrical installation design 4 Power loading of an installation A20 The nominal full-load current In on the LV side of a 3-phase transformer is given by: In = Pa x 103 U 3 where b Pa = kVA rating of the transformer b U = phase-to-phase voltage at no-load in volts (237 V or 410 V) b In is in amperes. For a single-phase transformer: Pa x 103 V where where In = b V = voltage between LV terminals at no-load (in volts) Simplified equation for 400 V (3-phase load) b In = kVA x 1.4 The IEC standard for power transformers is IEC 60076. 4.7 Choice of power-supply sources The importance of maintaining a continuous supply raises the question of the use of standby-power plant. The choice and characteristics of these alternative sources are part of the architecture selection, as described in chapter D. For the main source of supply the choice is generally between a connection to the MV or the LV network of the power-supply utility. In practice, connection to a MV source may be necessary where the load exceeds (or is planned eventually to exceed) a certain level - generally of the order of 250 kVA, or if the quality of service required is greater than that normally available from a LV network. Moreover, if the installation is likely to cause disturbance to neighbouring consumers, when connected to a LV network, the supply authorities may propose a MV service. © Schneider Electric - all rights reserved Supplies at MV can have certain advantages: in fact, a MV consumer: b Is not disturbed by other consumers, which could be the case at LV b Is free to choose any type of LV earthing system b Has a wider choice of economic tariffs b Can accept very large increases in load It should be noted, however, that: b The consumer is the owner of the MV/LV substation and, in some countries, he must build and equip it at his own expense. The power utility can, in certain circumstances, participate in the investment, at the level of the MV line for example b A part of the connection costs can, for instance, often be recovered if a second consumer is connected to the MV line within a certain time following the original consumer’s own connection b The consumer has access only to the LV part of the installation, access to the MV part being reserved to the utility personnel (meter reading, operations, etc.). However, in certain countries, the MV protective circuit-breaker (or fused load-break switch) can be operated by the consumer b The type and location of the substation are agreed between the consumer and the utility Schneider Electric - Electrical installation guide 2009 Chapter B Connection to the MV utility distribution network B1 Contents Supply of power at medium voltage B2 1.1 Power supply characteristics of medium voltage utility distribution network 1.2 Different MV service connections 1.3 Some operational aspects of MV distribution networks B2 B11 B12 Procedure for the establishment of a new substation B14 2.1 Preliminary informations B14 2.2 Project studies 2.3 Implementation 2.4 Commissioning B15 B15 B15 3 Protection aspect B16 3.1 Protection against electric shocks 3.2 Protection of transformer and circuits 3.3 Interlocks and conditioned operations B16 B17 B19 4 The consumer substation with LV metering B22 4.1 4.2 4.3 4.4 B22 B22 B25 B25 1 2 General Choice of MV switchgear Choice of MV switchgear panel for a transformer circuit Choice of MV/LV transformer B29 5 The consumer substation with MV metering B32 5.1 General 5.2 Choice of panels 5.3 Parallel operation of transformers B32 B34 B35 6 Constitution of MV/LV distribution substations B37 6.1 Different types of substation 6.2 Indoor substation 6.3 Outdoor substation B37 B37 B39 © Schneider Electric - all rights reserved 4.5 Instructions for use of MV equipment Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 1 Supply of power at medium voltage B2 The term "medium voltage" is commonly used for distribution systems with voltages above 1 kV and generally applied up to and including 52 kV (see IEC 601-01-28 Standard). In this chapter, distribution networks which operate at voltages of 1,000 V or less are referred to as Low-Voltage systems, while systems of power distribution which require one stage of stepdown voltage transformation, in order to feed into low voltage networks, will be referred to as Medium- Voltage systems. For economic and technical reasons the nominal voltage of medium-voltage distribution systems, as defined above, seldom exceeds 35 kV. The main features which characterize a powersupply system include: b The nominal voltage and related insulation levels b The short-circuit current b The rated normal current of items of plant and equipment b The earthing system 1.1 Power supply characteristics of medium voltage utility distribution network Nominal voltage and related insulation levels The nominal voltage of a system or of an equipment is defined in IEC 60038 Standard as “the voltage by which a system or equipment is designated and to which certain operating characteristics are referred”. Closely related to the nominal voltage is the “highest voltage for equipment” which concerns the level of insulation at normal working frequency, and to which other characteristics may be referred in relevant equipment recommendations. The “highest voltage for equipment” is defined in IEC 60038 Standard as: “the maximum value of voltage for which equipment may be used, that occurs under normal operating conditions at any time and at any point on the system. It excludes voltage transients, such as those due to system switching, and temporary voltage variations”. Notes: 1- The highest voltage for equipment is indicated for nominal system voltages higher than 1,000 V only. It is understood that, particularly for some categories of equipment, normal operation cannot be ensured up to this "highest voltage for equipment", having regard to voltage sensitive characteristics such as losses of capacitors, magnetizing current of transformers, etc. In such cases, IEC standards specify the limit to which the normal operation of this equipment can be ensured. 2- It is understood that the equipment to be used in systems having nominal voltage not exceeding 1,000 V should be specified with reference to the nominal system voltage only, both for operation and for insulation. 3- The definition for “highest voltage for equipment” given in IEC 60038 Standard is identical to the definition given in IEC 62271-1 Standard for “rated voltage”. IEC 62271-1 Standard concerns switchgear for voltages exceeding 1,000 V. © Schneider Electric - all rights reserved The following values of Figure B1, taken from IEC 60038 Standard, list the most-commonly used standard levels of medium-voltage distribution, and relate the nominal voltages to corresponding standard values of “Highest Voltage for Equipment”. These systems are generally three-wire systems unless otherwise indicated. The values shown are voltages between phases. The values indicated in parentheses should be considered as non-preferred values. It is recommended that these values should not be used for new systems to be constructed in future. It is recommended that in any one country the ratio between two adjacent nominal voltages should be not less than two. Series I (for 50 Hz and 60 Hz networks) Nominal system voltage Highest voltage for equipement (kV) (kV) 3.3 (1) 3 (1) 3.6 (1) 6.6 (1) 6 (1) 7.2 (1) 11 10 12 15 17.5 22 20 24 33 (2) 36 (2) 35 (2) 40.5 (2) (1) These values should not be used for public distribution systems. (2) The unification of these values is under consideration. Fig. B1 : Relation between nominal system voltages and highest voltages for the equipment Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 1 Supply of power at medium voltage In order to ensure adequate protection of equipment against abnormally-medium short term power-frequency overvoltages, and transient overvoltages caused by lightning, switching, and system fault conditions, etc. all MV equipment must be specified to have appropriate rated insulation levels. B3 A "rated insulation level" is a set of specified dielectric withstand values covering various operating conditions. For MV equipment, in addition to the "highest voltage for equipment", it includes lightning impulse withstand and short-duration power frequency withstand. Switchgear Figure B2 shown below, lists normal values of “withstand” voltage requirements from IEC 62271-1 Standard. The choice between List 1 and List 2 values of table B2 depends on the degree of exposure to lightning and switching overvoltages(1), the type of neutral earthing, and the type of overvoltage protection devices, etc. (for further guidance reference should be made to IEC 60071). Rated voltage U (r.m.s. value) Rated lightning impulse withstand voltage (peak value) Rated short-duration power-frequency withstand voltage (r.m.s. value) List 1 List 2 To earth, Across the To earth, Across the To earth, Across the between isolating between isolating between isolating poles distance poles distance poles distance and across and across and across open open open switching switching switching device device device (kV) (kV) (kV) (kV) (kV) (kV) (kV) 3.6 20 23 40 46 10 12 7.2 40 46 60 70 20 23 12 60 70 75 85 28 32 17.5 75 85 95 110 38 45 24 95 110 125 145 50 60 36 145 165 170 195 70 80 52 250 290 95 110 72.5 325 375 140 160 Note: The withstand voltage values “across the isolating distance” are valid only for the switching devices where the clearance between open contacts is designed to meet requirements specified for disconnectors (isolators). Fig. B2 : Switchgear rated insulation levels It should be noted that, at the voltage levels in question, no switching overvoltage ratings are mentioned. This is because overvoltages due to switching transients are less severe at these voltage levels than those due to lightning. Transformers Figure B3 shown below have been extracted from IEC 60076-3. Highest voltage for equipment (r.m.s.) (kV) y 1.1 3.6 7.2 12 17.5 24 36 52 72.5 (1) This means basically that List 1 generally applies to switchgear to be used on underground-cable systems while List 2 is chosen for switchgear to be used on overhead-line systems. Rated short duration power frequency withstand voltage (r.m.s.) (kV) 3 10 20 28 38 50 70 95 140 Fig. B3 : Transformers rated insulation levels Schneider Electric - Electrical installation guide 2009 Rated lightning impulse withstand voltage (peak) List 1 List 2 (kV) (kV) 20 40 40 60 60 75 75 95 95 125 145 170 250 325 © Schneider Electric - all rights reserved The significance of list 1 and list 2 is the same as that for the switchgear table, i.e. the choice depends on the degree of exposure to lightning, etc. B - Connection to the MV public distribution network 1 Supply of power at medium voltage B4 Other components It is evident that the insulation performance of other MV components associated with these major items, e.g. porcelain or glass insulators, MV cables, instrument transformers, etc. must be compatible with that of the switchgear and transformers noted above. Test schedules for these items are given in appropriate IEC publications. The national standards of any particular country are normally rationalized to include one or two levels only of voltage, current, and fault-levels, etc. The national standards of any particular country are normally rationalized to include one or two levels only of voltage, current, and fault-levels, etc. General note: The IEC standards are intended for worldwide application and consequently embrace an extensive range of voltage and current levels. These reflect the diverse practices adopted in countries of different meteorologic, geographic and economic constraints. A circuit-breaker (or fuse switch, over a limited voltage range) is the only form of switchgear capable of safely breaking all kinds of fault currents occurring on a power system. Short-circuit current Standard values of circuit-breaker short-circuit current-breaking capability are normally given in kilo-amps. These values refer to a 3-phase short-circuit condition, and are expressed as the average of the r.m.s. values of the AC component of current in each of the three phases. For circuit-breakers in the rated voltage ranges being considered in this chapter, Figure B4 gives standard short-circuit current-breaking ratings. kV kA (rms) 3.6 8 10 16 25 40 7.2 8 12.5 16 25 40 12 8 12.5 16 25 40 50 17.5 8 12.5 16 25 40 24 8 12.5 16 25 40 36 8 12.5 16 25 40 52 8 12.5 20 Fig. B4 : Standard short-circuit current-breaking ratings Short-circuit current calculation The rules for calculating short-circuit currents in electrical installations are presented in IEC standard 60909. The calculation of short-circuit currents at various points in a power system can quickly turn into an arduous task when the installation is complicated. The use of specialized software accelerates calculations. This general standard, applicable for all radial and meshed power systems, 50 or 60 Hz and up to 550 kV, is extremely accurate and conservative. It may be used to handle the different types of solid short-circuit (symmetrical or dissymmetrical) that can occur in an electrical installation: b Three-phase short-circuit (all three phases), generally the type producing the highest currents b Two-phase short-circuit (between two phases), currents lower than three-phase faults b Two-phase-to-earth short-circuit (between two phases and earth) b Phase-to-earth short-circuit (between a phase and earth), the most frequent type (80% of all cases). Current (I) 22I''k When a fault occurs, the transient short-circuit current is a function of time and comprises two components (see Fig. B5). b An AC component, decreasing to its steady-state value, caused by the various rotating machines and a function of the combination of their time constants b A DC component, decreasing to zero, caused by the initiation of the current and a function of the circuit impedances 22Ib IDC 22Ik © Schneider Electric - all rights reserved Ip Time (t) tmin Fig. B5 : Graphic representation of short-circuit quantities as per IEC 60909 Practically speaking, one must define the short-circuit values that are useful in selecting system equipment and the protection system: b I’’k: rms value of the initial symmetrical current b Ib: rms value of the symmetrical current interrupted by the switching device when the first pole opens at tmin (minimum delay) b Ik: rms value of the steady-state symmetrical current b Ip: maximum instantaneous value of the current at the first peak b IDC: DC value of the current Schneider Electric - Electrical installation guide 2009 1 Supply of power at medium voltage These currents are identified by subscripts 3, 2, 2E, 1, depending on the type of short-circuit, respectively three-phase, two-phase clear of earth, two-phase-to-earth, phase-to-earth. B5 The method, based on the Thevenin superposition theorem and decomposition into symmetrical components, consists in applying to the short-circuit point an equivalent source of voltage in view of determining the current. The calculation takes place in three steps. b Define the equivalent source of voltage applied to the fault point. It represents the voltage existing just before the fault and is the rated voltage multiplied by a factor taking into account source variations, transformer on-load tap changers and the subtransient behavior of the machines. b Calculate the impedances, as seen from the fault point, of each branch arriving at this point. For positive and negative-sequence systems, the calculation does not take into account line capacitances and the admittances of parallel, non-rotating loads. b Once the voltage and impedance values are defined, calculate the characteristic minimum and maximum values of the short-circuit currents. The various current values at the fault point are calculated using: b The equations provided b A summing law for the currents flowing in the branches connected to the node: v I’’k (see Fig. B6 for I’’k calculation, where voltage factor c is defined by the standard; geometric or algebraic summing) v Ip = κ x 2 x I’’k, where κ is less than 2, depending on the R/X ratio of the positive sequence impedance for the given branch; peak summing v Ib = μ x q x I’’k, where μ and q are less than 1, depending on the generators and motors, and the minimum current interruption delay; algebraic summing v Ik = I’’k, when the fault is far from the generator v Ik = λ x Ir, for a generator, where Ir is the rated generator current and λ is a factor depending on its saturation inductance; algebraic summing. Type of short-circuit I’’k General situation Distant faults c Un 3 Z1 3-phase c Un 3 Z1 2-phase c Un Z1 + Z2 2-phase-to-earth c Un 3 Z2 Z1 Z2 + Z2 Z0 + Z1 Z0 c Un 3 Z1 + 2Z 0 c Un 3 Z1+Z2+Z0 c Un 3 2 Z1 + Z0 + Phase-to-earth + c Un 2Z1 Fig. B6 : Short-circuit currents as per IEC 60909 Characterization There are 2 types of system equipment, based on whether or not they react when a fault occurs. Passive equipment This category comprises all equipment which, due to its function, must have the capacity to transport both normal current and short-circuit current. This equipment includes cables, lines, busbars, disconnecting switches, switches, transformers, series reactances and capacitors, instrument transformers. For this equipment, the capacity to withstand a short-circuit without damage is defined in terms of: b Electrodynamic withstand (“peak withstand current”; value of the peak current expressed in kA), characterizing mechanical resistance to electrodynamic stress b Thermal withstand (“short time withstand current”; rms value expressed in kA for duration between 0,5 and 3 seconds, with a preferred value of 1 second), characterizing maximum permissible heat dissipation. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved B - Connection to the MV public distribution network B - Connection to the MV public distribution network 1 Supply of power at medium voltage B6 Active equipment This category comprises the equipment designed to clear short-circuit currents, i.e. circuit-breakers and fuses. This property is expressed by the breaking capacity and, if required, the making capacity when a fault occurs. b Breaking capacity (see Fig. B7) This basic characteristic of a fault interrupting device is the maximum current (rms value expressed in kA) it is capable of breaking under the specific conditions defined by the standards; in the IEC 62271-100 standard, it refers to the rms value of the AC component of the short-circuit current. In some other standards, the rms value of the sum of the 2 components (AC and DC) is specified, in which case, it is the “asymmetrical current”. The breaking capacity depends on other factors such as: v Voltage v R/X ratio of the interrupted circuit v Power system natural frequency v Number of breaking operations at maximum current, for example the cycle: O - C/O - C/O (O = opening, C = closing) The breaking capacity is a relatively complicated characteristic to define and it therefore comes as no surprise that the same device can be assigned different breaking capacities depending on the standard by which it is defined. b Short-circuit making capacity In general, this characteristic is implicitly defined by the breaking capacity because a device should be able to close for a current that it can break. Sometimes, the making capacity needs to be higher, for example for circuit-breakers protecting generators. The making capacity is defined in terms of peak value (expressed in kA) because the first asymmetric peak is the most demanding from an electrodynamic point of view. For example, according to standard IEC 62271-100, a circuit-breaker used in a 50 Hz power system must be able to handle a peak making current equal to 2.5 times the rms breaking current (2.6 times for 60 Hz systems). Making capacity is also required for switches, and sometimes for disconnectors, even if these devices are not able to clear the fault. b Prospective short-circuit breaking current Some devices have the capacity to limit the fault current to be interrupted. Their breaking capacity is defined as the maximum prospective breaking current that would develop during a solid short-circuit across the upstream terminals of the device. Specific device characteristics The functions provided by various interrupting devices and their main constraints are presented in Figure B8. Current (I) IAC Device Isolation of two active networks Disconnector Switch Yes No Current switching conditions Normal Fault No No Yes No Contactor No Yes No Circuit-breaker No Yes Yes Fuse No No Yes Time (t) © Schneider Electric - all rights reserved IDC IAC: Peak of the periodic component IDC: Aperiodic component Fig. B7 : Rated breaking current of a circuit-breaker subjected to a short-circuit as per IEC 60056 Fig. B8 : Functions provided by interrupting devices Schneider Electric - Electrical installation guide 2009 Main constrains Longitudinal input/output isolation Making and breaking of normal load current Short-circuit making capacity Rated making and breaking capacities Maximum making and breaking capacities Duty and endurance characteristics Short-circuit breaking capacity Short-circuit making capacity Minimum short-circuit breaking capacity Maximum short-circuit breaking capacity The most common normal current rating for general-purpose MV distribution switchgear is 400 A. 1 Supply of power at medium voltage Rated normal current The rated normal current is defined as “the r.m.s. value of the current which can be carried continuously at rated frequency with a temperature rise not exceeding that specified by the relevant product standard”. The rated normal current requirements for switchgear are decided at the substation design stage. The most common normal current rating for general-purpose MV distribution switchgear is 400 A. In industrial areas and medium-load-density urban districts, circuits rated at 630 A are sometimes required, while at bulk-supply substations which feed into MV networks, 800 A; 1,250 A; 1,600 A; 2,500 A and 4,000 A circuit-breakers are listed as standard ratings for incoming-transformer circuits, bus-section and bus-coupler CBs, etc. For MV/LV transformer with a normal primary current up to roughly 60 A, a MV switch-fuse combination can be used . For higher primary currents, switch-fuse combination usually does not have the required performances. There are no IEC-recommended rated current values for switch-fuse combinations. The actual rated current of a given combination, meaning a switchgear base and defined fuses, is provided by the manufacturer of the combination as a table "fuse reference / rated current". These values of the rated current are defined by considering parameters of the combination as: b Normal thermal current of the fuses b Necessary derating of the fuses, due to their usage within the enclosure. When combinations are used for protecting transformers, then further parameters are to be considered, as presented in Appendix A of the IEC 62271-105 and in the IEC 60787. They are mainly: b The normal MV current of the transformer b The possible need for overloading the transformer b The inrush magnetizing current b The MV short-circuit power b The tapping switch adjustment range. Manufacturers usually provide an application table "service voltage / transformer power / fuse reference" based on standard distribution network and transformer parameters, and such table should be used with care, if dealing with unusual installations. B7 In such a scheme, the load-break switch should be suitably fitted with a tripping device e.g. with a relay to be able to trip at low fault-current levels which must cover (by an appropriate margin) the rated minimum breaking current of the MV fuses. In this way, medium values of fault current which are beyond the breaking capability of the load-break switch will be cleared by the fuses, while low fault-current values, that cannot be correctly cleared by the fuses, will be cleared by the tripped load-break switch. Influence of the ambient temperature and altitude on the rated current Normal-current ratings are assigned to all current-carrying electrical appliances, and upper limits are decided by the acceptable temperature rise caused by the I2R (watts) dissipated in the conductors, (where I = r.m.s. current in amperes and R = the resistance of the conductor in ohms), together with the heat produced by magnetic-hysteresis and eddy-current losses in motors, transformers, steel enclosures, etc. and dielectric losses in cables and capacitors, where appropriate. The temperature rise above the ambient temperature will depend mainly on the rate at which the heat is removed. For example, large currents can be passed through electric motor windings without causing them to overheat, simply because a cooling fan fixed to the shaft of the motor removes the heat at the same rate as it is produced, and so the temperature reaches a stable value below that which could damage the insulation and result in a burnt-out motor. The normal-current values recommended by IEC are based on ambientair temperatures common to temperate climates at altitudes not exceeding 1,000 metres, so that items which depend on natural cooling by radiation and air-convection will overheat if operated at rated normal current in a tropical climate and/ or at altitudes exceeding 1,000 metres. In such cases, the equipment has to be derated, i.e. be assigned a lower value of normal current rating. The case of transformer is addressed in IEC 60076-2. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved B - Connection to the MV public distribution network B - Connection to the MV public distribution network 1 Supply of power at medium voltage B8 Earth faults on medium-voltage systems can produce dangerous voltage levels on LV installations. LV consumers (and substation operating personnel) can be safeguarded against this danger by: b Restricting the magnitude of MV earth-fault currents b Reducing the substation earthing resistance to the lowest possible value b Creating equipotential conditions at the substation and at the consumer’s installation Earthing systems Earthing and equipment-bonding earth connections require careful consideration, particularly regarding safety of the LV consumer during the occurrence of a shortcircuit to earth on the MV system. Earth electrodes In general, it is preferable, where physically possible, to separate the electrode provided for earthing exposed conductive parts of MV equipment from the electrode intended for earthing the LV neutral conductor. This is commonly practised in rural systems where the LV neutral-conductor earth electrode is installed at one or two spans of LV distribution line away from the substation. In most cases, the limited space available in urban substations precludes this practice, i.e. there is no possibility of separating a MV electrode sufficiently from a LV electrode to avoid the transference of (possibly dangerous) voltages to the LV system. Earth-fault current Earth-fault current levels at medium voltage are generally (unless deliberately restricted) comparable to those of a 3-phase short-circuit. Such currents passing through an earth electrode will raise its voltage to a medium value with respect to “remote earth” (the earth surrounding the electrode will be raised to a medium potential; “remote earth” is at zero potential). For example, 10,000 A of earth-fault current passing through an electrode with an (unusually low) resistance of 0.5 ohms will raise its voltage to 5,000 V. Providing that all exposed metal in the substation is “bonded” (connected together) and then connected to the earth electrode, and the electrode is in the form of (or is connected to) a grid of conductors under the floor of the substation, then there is no danger to personnel, since this arrangement forms an equipotential “cage” in which all conductive material, including personnel, is raised to the same potential. Transferred potential A danger exists however from the problem known as Transferred Potential. It will be seen in Figure B9 that the neutral point of the LV winding of the MV/LV transformer is also connected to the common substation earth electrode, so that the neutral conductor, the LV phase windings and all phase conductors are also raised to the electrode potential. Low-voltage distribution cables leaving the substation will transfer this potential to consumers installations. It may be noted that there will be no LV insulation failure between phases or from phase to neutral since they are all at the same potential. It is probable, however, that the insulation between phase and earth of a cable or some part of an installation would fail. HV Solutions A first step in minimizing the obvious dangers of transferred potentials is to reduce the magnitude of MV earth-fault currents. This is commonly achieved by earthing the MV system through resistors or reactors at the star points of selected transformers(1), located at bulk-supply substations. A relatively medium transferred potential cannot be entirely avoided by this means, however, and so the following strategy has been adopted in some countries. The equipotential earthing installation at a consumer’s premises represents a remote earth, i.e. at zero potential. However, if this earthing installation were to be connected by a low-impedance conductor to the earth electrode at the substation, then the equipotential conditions existing in the substation would also exist at the consumer’s installation. LV 1 2 3 N Fault If Consumer If Low-impedance interconnection This low-impedance interconnection is achieved simply by connecting the neutral conductor to the consumer’s equipotential installation, and the result is recognized as the TN earthing system (IEC 60364) as shown in diagram A of Figure B10 next page. The TN system is generally associated with a Protective Multiple Earthing (PME) scheme, in which the neutral conductor is earthed at intervals along its length (every 3rd or 4th pole on a LV overhead-line distributor) and at each consumer’s service position. It can be seen that the network of neutral conductors radiating from a substation, each of which is earthed at regular intervals, constitutes, together with the substation earthing, a very effective low-resistance earth electrode. V= IfRs © Schneider Electric - all rights reserved Rs Fig. B9 : Transferred potential (1) The others being unearthed. A particular case of earth-fault current limitation is by means of a Petersen coil. Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 1 Supply of power at medium voltage B9 Diagram A - TN-a MV Rs value B - IT-a LV MV Cases A and B LV 1 1 2 2 3 3 N N RS RS C - TT-a Cases C and D D - IT-b MV LV MV LV 1 1 2 2 3 3 N N RS F - IT-c RS LV RN Rs y Uw - Uo Im Where Uw = the rated normal-frequency withstand voltage for low-voltage equipment at consumer installations Uo = phase to neutral voltage at consumer's installations Im = maximum value of MV earth-fault current RS E - TT-b MV No particular resistance value for Rs is imposed in these cases Cases E and F MV LV 1 1 2 2 3 3 N N RS RN Rs y Uws - U Im Where Uws = the normal-frequency withstand voltage for low-voltage equipments in the substation (since the exposed conductive parts of these equipments are earthed via Rs) U = phase to neutral voltage at the substation for the TT(s) system, but the phase-tophase voltage for the IT(s) system Im = maximum value of MV earth-fault current In cases E and F the LV protective conductors (bonding exposed conductive parts) in the substation are earthed via the substation earth electrode, and it is therefore the substation LV equipment (only) that could be subjected to overvoltage. Notes: b For TN-a and IT-a, the MV and LV exposed conductive parts at the substation and those at the consumer’s installations, together with the LV neutral point of the transformer, are all earthed via the substation electrode system. b For TT-a and IT-b, the MV and LV exposed conductive parts at the substation, together with the LV neutral point of the transformer are earthed via the substation electrode system. b For TT-b and IT-c, the LV neutral point of the transformer is separately earthed outside of the area of influence of the substation earth electrode. Uw and Uws are commonly given the (IEC 60364-4-44) value Uo + 1200 V, where Uo is the nominal phase-to-neutral voltage of the LV system concerned. The combination of restricted earth-fault currents, equipotential installations and low resistance substation earthing, results in greatly reduced levels of overvoltage and limited stressing of phase-to-earth insulation during the type of MV earth-fault situation described above. Limitation of the MV earth-fault current and earth resistance of the substation Another widely-used earthing system is shown in diagram C of Figure B10. It will be seen that in the TT system, the consumer’s earthing installation (being isolated from that of the substation) constitutes a remote earth. This means that, although the transferred potential will not stress the phase-to-phase insulation of the consumer’s equipment, the phase-to-earth insulation of all three phases will be subjected to overvoltage. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. B10 : Maximum earthing resistance Rs at a MV/LV substation to ensure safety during a short-circuit to earth fault on the medium-voltage equipment for different earthing systems B - Connection to the MV public distribution network B10 1 Supply of power at medium voltage The strategy in this case, is to reduce the resistance of the substation earth electrode, such that the standard value of 5-second withstand-voltage-to-earth for LV equipment and appliances will not be exceeded. Practical values adopted by one national electrical power-supply authority, on its 20 kV distribution systems, are as follows: b Maximum earth-fault current in the neutral connection on overhead line distribution systems, or mixed (O/H line and U/G cable) systems, is 300 A b Maximum earth-fault current in the neutral connection on underground systems is 1,000 A The formula required to determine the maximum value of earthing resistance Rs at the substation, to ensure that the LV withstand voltage will not be exceeded, is: Uw Uo in ohms ohms (see (see cases cases C C and and D D in in Figure Figure B10). C10). in Rs = Im Where Uw = the lowest standard value (in volts) of short-term (5 s) withstand voltage for the consumer’s installation and appliances = Uo + 1200 V (IEC 60364-4-44) Uo = phase to neutral voltage (in volts) at the consumer’s LV service position Im = maximum earth-fault current on the MV system (in amps). This maximum earth fault current Im is the vectorial sum of maximum earth-fault current in the neutral connection and total unbalanced capacitive current of the network. A third form of system earthing referred to as the “IT” system in IEC 60364 is commonly used where continuity of supply is essential, e.g. in hospitals, continuousprocess manufacturing, etc. The principle depends on taking a supply from an unearthed source, usually a transformer, the secondary winding of which is unearthed, or earthed through a medium impedance (u1,000 ohms). In these cases, an insulation failure to earth in the low-voltage circuits supplied from the secondary windings will result in zero or negligible fault-current flow, which can be allowed to persist until it is convenient to shut-down the affected circuit to carry out repair work. Diagrams B, D and F (Figure B10) They show IT systems in which resistors (of approximately 1,000 ohms) are included in the neutral earthing lead. If however, these resistors were removed, so that the system is unearthed, the following notes apply. © Schneider Electric - all rights reserved Diagram B (Figure B10) All phase wires and the neutral conductor are “floating” with respect to earth, to which they are “connected” via the (normally very medium) insulation resistances and (very small) capacitances between the live conductors and earthed metal (conduits, etc.). Assuming perfect insulation, all LV phase and neutral conductors will be raised by electrostatic induction to a potential approaching that of the equipotential conductors. In practice, it is more likely, because of the numerous earth-leakage paths of all live conductors in a number of installations acting in parallel, that the system will behave similarly to the case where a neutral earthing resistor is present, i.e. all conductors will be raised to the potential of the substation earth. In these cases, the overvoltage stresses on the LV insulation are small or nonexistent. Diagrams D and F (Figure B10) In these cases, the medium potential of the substation (S/S) earthing system acts on the isolated LV phase and neutral conductors: b Through the capacitance between the LV windings of the transformer and the transformer tank b Through capacitance between the equipotential conductors in the S/S and the cores of LV distribution cables leaving the S/S b Through current leakage paths in the insulation, in each case. At positions outside the area of influence of the S/S earthing, system capacitances exist between the conductors and earth at zero potential (capacitances between cores are irrelevant - all cores being raised to the same potential). The result is essentially a capacitive voltage divider, where each “capacitor” is shunted by (leakage path) resistances. In general, LV cable and installation wiring capacitances to earth are much larger, and the insulation resistances to earth are much smaller than those of the corresponding parameters at the S/S, so that most of the voltage stresses appear at the substation between the transformer tank and the LV winding. The rise in potential at consumers’ installations is not likely therefore to be a problem where the MV earth-fault current level is restricted as previously mentioned. Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 1 Supply of power at medium voltage All IT-earthed transformers, whether the neutral point is isolated or earthed through a medium impedance, are routinely provided with an overvoltage limiting device which will automatically connect the neutral point directly to earth if an overvoltage condition approaches the insulation-withstand level of the LV system. In addition to the possibilities mentioned above, several other ways in which these overvoltages can occur are described in Clause 3.1. This kind of earth-fault is very rare, and when does occur is quickly detected and cleared by the automatic tripping of a circuit-breaker in a properly designed and constructed installation. Safety in situations of elevated potentials depends entirely on the provision of properly arranged equipotential areas, the basis of which is generally in the form of a widemeshed grid of interconnected bare copper conductors connected to verticallydriven copper-clad(1) steel rods. The equipotential criterion to be respected is that which is mentioned in Chapter F dealing with protection against electric shock by indirect contact, namely: that the potential between any two exposed metal parts which can be touched simultaneously by any parts the body must never, under any circumstances, exceed 50 V in dry conditions, or 25 V in wet conditions. Special care should be taken at the boundaries of equipotential areas to avoid steep potential gradients on the surface of the ground which give rise to dangerous “step potentials”. This question is closely related to the safe earthing of boundary fences and is further discussed in Sub-clause 3.1. Overhead line B11 1.2 Different MV service connections According to the type of medium-voltage network, the following supply arrangements are commonly adopted. Single-line service The substation is supplied by a single circuit tee-off from a MV distributor (cable or line). In general, the MV service is connected into a panel containing a load-break/ isolating switch-fuse combination and earthing switches, as shown in Figure B11. In some countries a pole-mounted transformer with no MV switchgear or fuses (at the pole) constitutes the “substation”. This type of MV service is very common in rural areas. Protection and switching devices are remote from the transformer, and generally control a main overhead line, from which a number of these elementary service lines are tapped. Fig. B11 : Single-line service Underground cable ring main Fig. B12 : Ring-main service (1) Copper is cathodic to most other metals and therefore resists corrosion. (2) A ring main is a continuous distributor in the form of a closed loop, which originates and terminates on one set of busbars. Each end of the loop is controlled by its own circuitbreaker. In order to improve operational flexibility the busbars are often divided into two sections by a normally closed bussection circuit-breaker, and each end of the ring is connected to a different section. An interconnector is a continuous untapped feeder connecting the busbars of two substations. Each end of the interconnector is usually controlled by a circuit beaker. An interconnector-distributor is an interconnector which supplies one or more distribution substations along its length. Ring-main units (RMU) are normally connected to form a MV ring main(2) or interconnector-distributor(2), such that the RMU busbars carry the full ring-main or interconnector current (see Fig. B12). The RMU consists of three units, integrated to form a single assembly, viz: b 2 incoming units, each containing a load break/isolating switch and a circuit earthing switch b 1 outgoing and general protection unit, containing a load-break switch and MV fuses, or a combined load-break/fuse switch, or a circuit-breaker and isolating switch, together with a circuit-earthing switch in each case. All load-break switches and earthing switches are fully rated for short-circuit currentmaking duty. This arrangement provides the user with a two-source supply, thereby reducing considerably any interruption of service due to system faults or operations by the supply authority, etc. The main application for RMUs is in utility supply MV underground-cable networks in urban areas. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Ring-main service B - Connection to the MV public distribution network B12 1 Supply of power at medium voltage Parallel feeders service Where a MV supply connection to two lines or cables originating from the same busbar of a substation is possible, a similar MV switchboard to that of a RMU is commonly used (see Fig. B13). The main operational difference between this arrangement and that of a RMU is that the two incoming panels are mutually interlocked, such that one incoming switch only can be closed at a time, i.e. its closure prevents the closure of the other. On the loss of power supply, the closed incoming switch must be opened and the (formerly open) switch can then be closed. The sequence may be carried out manually or automatically. This type of switchboard is used particularly in networks of medium-load density and in rapidly-expanding urban areas supplied by MV underground cable systems. 1.3 Some operational aspects of MV distribution networks Overhead lines © Schneider Electric - all rights reserved Paralleled underground cable distributors Fig. B13 : Parallel feeders service Medium winds, ice formation, etc., can cause the conductors of overhead lines to touch each other, thereby causing a momentary (i.e. not permanent) short-circuit fault. Insulation failure due to broken ceramic or glass insulators, caused by air-borne debris; careless use of shot-guns, etc., or again, heavily polluted insulator surfaces, can result in a short-circuit to earth. Many of these faults are self-clearing. For example, in dry conditions, broken insulators can very often remain in service undetected, but are likely to flashover to earth (e.g. to a metal supporting structure) during a rainstorm. Moreover, polluted surfaces generally cause a flashover to earth only in damp conditions. The passage of fault current almost invariably takes the form of an electric arc, the intense heat of which dries the current path, and to some extent, re-establishes its insulating properties. In the meantime, protective devices have usually operated to clear the fault, i.e. fuses have blown or a circuit-breaker has tripped. Experience has shown that in the large majority of cases, restoration of supply by replacing fuses or by re-closing a circuit-breaker will be successful. For this reason it has been possible to considerably improve the continuity of service on MV overhead-line distribution networks by the application of automatic circuitbreaker reclosing schemes at the origin of the circuits concerned. These automatic schemes permit a number of reclosing operations if a first attempt fails, with adjustable time delays between successive attempts (to allow de-ionization of the air at the fault) before a final lock-out of the circuit-breaker occurs, after all (generally three) attempts fail. Other improvements in service continuity are achieved by the use of remotelycontrolled section switches and by automatic isolating switches which operate in conjunction with an auto-reclosing circuit-breaker. This last scheme is exemplified by the final sequence shown in Figure B14 next page. The principle is as follows: if, after two reclosing attempts, the circuit-breaker trips, the fault is assumed to be permanent, then there are two possibilities: b The fault is on the section downstream the Automatic Line Switch, and while the feeder is dead the ALS opens to isolate this section of the network, before the third (and final) reclosing takes place, b The fault is on the section upstream the ALS and the circuit-breaker will make a third reclosing attempt and thus trip and lock out. While these measures have greatly improved the reliability of supplies from MV overhead line systems, the consumers must, where considered necessary, make their own arrangements to counter the effects of momentary interruptions to supply (between reclosures), for example: b Uninterruptible standby emergency power b Lighting that requires no cooling down before re-striking (“hot restrike”). Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 1 Supply of power at medium voltage B13 1- Cycle 1SR O1 If O2 In Io SR O3 15 to 30 s fault Permanent fault 0.3 s 0.4 s 2 - Cycle 2SR a - Fault on main feeder O1 If O2 In Io SR1 O3 15 to 30s SR2 O4 15 to 30 s fault 0.3 s 0.4 s Permanent fault 0.45 s 0.4 s b - Fault on section supplied through Automatic Line Switch O1 O2 SR1 O3 If In Io SR2 15 to 30 s 15 to 30 s Fault 0.3 s 0.4 s 0.4 s Opening of ALS Fig. B14 : Automatic reclosing cycles of a circuit-breaker controlling a radial MV feeder Underground cable networks Faults on underground cable networks are sometimes the result of careless workmanship by cable jointers or by cable laying contractors, etc., but are more commonly due to damage from tools such as pick-axes, pneumatic drills and trench excavating machines, and so on, used by other utilities. Insulation failures sometimes occur in cable terminating boxes due to overvoltage, particularly at points in a MV system where an overhead line is connected to an underground cable. The overvoltage in such a case is generally of atmospheric origin, and electromagnetic-wave reflection effects at the joint box (where the natural impedance of the circuit changes abruptly) can result in overstressing of the cablebox insulation to the point of failure. Overvoltage protection devices, such as lightning arresters, are frequently installed at these locations. Faults occurring in cable networks are less frequent than those on overhead (O/H) line systems, but are almost invariably permanent faults, which require more time for localization and repair than those on O/H lines. Where a cable fault occurs on a ring, supply can be quickly restored to all consumers when the faulty section of cable has been determined. If, however, the fault occurs on a radial feeder, the delay in locating the fault and carrying out repair work can amount to several hours, and will affect all consumers downstream of the fault position. In any case, if supply continuity is essential on all, or part of, an installation, a standby source must be provided. Remote control of MV networks Remote control on MV feeders is useful to reduce outage durations in case of cable fault by providing an efficient and fast mean for loop configuration. This is achieved by motor operated switches implemented in some of the substations along the loop associated with relevant remote telecontrol units. Remote controled substation will always be reenergized through telecontroled operation when the other ones could have to wait for further manual operation. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Centralized remote control, based on SCADA (Supervisory Control And Data Acquisition) systems and recent developments in IT (Information Technology) techniques, is becoming more and more common in countries in which the complexity of highly interconnected systems justifies the expenditure. B - Connection to the MV public distribution network 2 Procedure for the establishment of a new substation B14 Large consumers of electricity are invariably supplied at MV. On LV systems operating at 120/208 V (3-phase 4-wires), a load of 50 kVA might be considered to be “large”, while on a 240/415 V 3-phase system a “large” consumer could have a load in excess of 100 kVA. Both systems of LV distribution are common in many parts of the world. As a matter of interest, the IEC recommends a “world” standard of 230/400 V for 3-phase 4-wire systems. This is a compromise level and will allow existing systems which operate at 220/380 V and at 240/415 V, or close to these values, to comply with the proposed standard simply by adjusting the off-circuit tapping switches of standard distribution transformers. The distance over which the energy has to be transmitted is a further factor in considering an MV or LV service. Services to small but isolated rural consumers are obvious examples. The decision of a MV or LV supply will depend on local circumstances and considerations such as those mentioned above, and will generally be imposed by the utility for the district concerned. When a decision to supply power at MV has been made, there are two widelyfollowed methods of proceeding: 1 - The power-supplier constructs a standard substation close to the consumer’s premises, but the MV/LV transformer(s) is (are) located in transformer chamber(s) inside the premises, close to the load centre 2 - The consumer constructs and equips his own substation on his own premises, to which the power supplier makes the MV connection In method no. 1 the power supplier owns the substation, the cable(s) to the transformer(s), the transformer(s) and the transformer chamber(s), to which he has unrestricted access. The transformer chamber(s) is (are) constructed by the consumer (to plans and regulations provided by the supplier) and include plinths, oil drains, fire walls and ceilings, ventilation, lighting, and earthing systems, all to be approved by the supply authority. The tariff structure will cover an agreed part of the expenditure required to provide the service. Whichever procedure is followed, the same principles apply in the conception and realization of the project. The following notes refer to procedure no. 2. The consumer must provide certain data to the utility at the earliest stage of the project. 2.1 Preliminary information Before any negotiations or discussions can be initiated with the supply authorities, the following basic elements must be established: Maximum anticipated power (kVA) demand Determination of this parameter is described in Chapter A, and must take into account the possibility of future additional load requirements. Factors to evaluate at this stage are: b The utilization factor (ku) b The simultaneity factor (ks) © Schneider Electric - all rights reserved Layout plans and elevations showing location of proposed substation Plans should indicate clearly the means of access to the proposed substation, with dimensions of possible restrictions, e.g. entrances corridors and ceiling height, together with possible load (weight) bearing limits, and so on, keeping in mind that: b The power-supply personnel must have free and unrestricted access to the MV equipment in the substation at all times b Only qualified and authorized consumer’s personnel are allowed access to the substation b Some supply authorities or regulations require that the part of the installation operated by the authority is located in a separated room from the part operated by the customer. Degree of supply continuity required The consumer must estimate the consequences of a supply failure in terms of its duration: b Loss of production b Safety of personnel and equipment Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 2 Procedure for the establishment of a new substation The utility must give specific information to the prospective consumer. 2.2 Project studies B15 From the information provided by the consumer, the power-supplier must indicate: The type of power supply proposed, and define: b The kind of power-supply system: overheadline or underground-cable network b Service connection details: single-line service, ring-main installation, or parallel feeders, etc. b Power (kVA) limit and fault current level The nominal voltage and rated voltage (Highest voltage for equipment) Existing or future, depending on the development of the system. Metering details which define: b The cost of connection to the power network b Tariff details (consumption and standing charges) 2.3 Implementation The utility must give official approval of the equipment to be installed in the substation, and of proposed methods of installation. Before any installation work is started, the official agreement of the power-supplier must be obtained. The request for approval must include the following information, largely based on the preliminary exchanges noted above: b Location of the proposed substation b Single-line diagram of power circuits and connections, together with earthingcircuit proposals b Full details of electrical equipment to be installed, including performance characteristics b Layout of equipment and provision for metering components b Arrangements for power-factor improvement if required b Arrangements provided for emergency standby power plant (MV or LV) if eventually required After testing and checking of the installation by an independent test authority, a certificate is granted which permits the substation to be put into service. 2.4 Commissioning When required by the authority, commissioning tests must be successfully completed before authority is given to energize the installation from the power supply system. Even if no test is required by the authority it is better to do the following verification tests: b Measurement of earth-electrode resistances b Continuity of all equipotential earth-and safety bonding conductors b Inspection and functional testing of all MV components b Insulation checks of MV equipment b Dielectric strength test of transformer oil (and switchgear oil if appropriate), if applicable b Inspection and testing of the LV installation in the substation b Checks on all interlocks (mechanical key and electrical) and on all automatic sequences b Checks on correct protective-relay operation and settings When finally the substation is operational: b The substation and all equipment belongs to the consumer b The power-supply authority has operational control over all MV switchgear in the substation, e.g. the two incoming load-break switches and the transformer MV switch (or CB) in the case of a RingMainUnit, together with all associated MV earthing switches b The power-supply personnel has unrestricted access to the MV equipment b The consumer has independent control of the MV switch (or CB) of the transformer(s) only, the consumer is responsible for the maintenance of all substation equipment, and must request the power-supply authority to isolate and earth the switchgear to allow maintenance work to proceed. The power supplier must issue a signed permitto-work to the consumers maintenance personnel, together with keys of locked-off isolators, etc. at which the isolation has been carried out. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved It is also imperative to check that all equipment is provided, such that any properly executed operation can be carried out in complete safety. On receipt of the certificate of conformity (if required): b Personnel of the power-supply authority will energize the MV equipment and check for correct operation of the metering b The installation contractor is responsible for testing and connection of the LV installation B - Connection to the MV public distribution network B16 3 Protection aspect The subject of protection in the electrical power industry is vast: it covers all aspects of safety for personnel, and protection against damage or destruction of property, plant, and equipment. These different aspects of protection can be broadly classified according to the following objectives: b Protection of personnel and animals against the dangers of overvoltages and electric shock, fire, explosions, and toxic gases, etc. b Protection of the plant, equipment and components of a power system against the stresses of short-circuit faults, atmospheric surges (lightning) and power-system instability (loss of synchronism) etc. b Protection of personnel and plant from the dangers of incorrect power-system operation, by the use of electrical and mechanical interlocking. All classes of switchgear (including, for example, tap-position selector switches on transformers, and so on...) have well-defined operating limits. This means that the order in which the different kinds of switching device can be safely closed or opened is vitally important. Interlocking keys and analogous electrical control circuits are frequently used to ensure strict compliance with correct operating sequences. It is beyond the scope of a guide to describe in full technical detail the numerous schemes of protection available to power-systems engineers, but it is hoped that the following sections will prove to be useful through a discussion of general principles. While some of the protective devices mentioned are of universal application, descriptions generally will be confined to those in common use on MV and LV systems only, as defined in Sub-clause 1.1 of this Chapter. Protection against electric shocks and overvoltages is closely related to the achievement of efficient (low resistance) earthing and effective application of the principles of equipotential environments. 3.1 Protection against electric shocks Protective measures against electric shock are based on two common dangers: b Contact with an active conductor, i.e. which is live with respect to earth in normal circumstances. This is referred to as a “direct contact” hazard. b Contact with a conductive part of an apparatus which is normally dead, but which has become live due to insulation failure in the apparatus. This is referred to as an “indirect contact” hazard. It may be noted that a third type of shock hazard can exist in the proximity of MV or LV (or mixed) earth electrodes which are passing earth-fault currents. This hazard is due to potential gradients on the surface of the ground and is referred to as a “step-voltage” hazard; shock current enters one foot and leaves by the other foot, and is particular dangerous for four-legged animals. A variation of this danger, known as a “touch voltage” hazard can occur, for instance, when an earthed metallic part is situated in an area in which potential gradients exist. Touching the part would cause current to pass through the hand and both feet. Animals with a relatively long front-to-hind legs span are particularly sensitive to step-voltage hazards and cattle have been killed by the potential gradients caused by a low voltage (230/400 V) neutral earth electrode of insufficiently low resistance. Potential-gradient problems of the kind mentioned above are not normally encountered in electrical installations of buildings, providing that equipotential conductors properly bond all exposed metal parts of equipment and all extraneous metal (i.e. not part of an electrical apparatus or the installation - for example structural steelwork, etc.) to the protective-earthing conductor. Direct-contact protection or basic protection The main form of protection against direct contact hazards is to contain all live parts in housings of insulating material or in metallic earthed housings, by placing out of reach (behind insulated barriers or at the top of poles) or by means of obstacles. © Schneider Electric - all rights reserved Where insulated live parts are housed in a metal envelope, for example transformers, electric motors and many domestic appliances, the metal envelope is connected to the installation protective earthing system. For MV switchgear, the IEC standard 62271-200 (Prefabricated Metal Enclosed switchgear and controlgear for voltages up to 52 kV) specifies a minimum Protection Index (IP coding) of IP2X which ensures the direct-contact protection. Furthermore, the metallic enclosure has to demonstrate an electrical continuity, then establishing a good segregation between inside and ouside of the enclosure. Proper grounding of the enclosure further participates to the electrical protection of the operators under normal operating conditions. For LV appliances this is achieved through the third pin of a 3-pin plug and socket. Total or even partial failure of insulation to the metal, can raise the voltage of the envelope to a dangerous level (depending on the ratio of the resistance of the leakage path through the insulation, to the resistance from the metal envelope to earth). Schneider Electric - Electrical installation guide 2009 3 Protection aspect Indirect-contact protection or fault protection B17 A person touching the metal envelope of an apparatus with a faulty insulation, as described above, is said to be making an indirect contact. An indirect contact is characterized by the fact that a current path to earth exists (through the protective earthing (PE) conductor) in parallel with the shock current through the person concerned. Case of fault on L.V. system Extensive tests have shown that, providing the potential of the metal envelope is not greater than 50 V with respect to earth, or to any conductive material within reaching distance, no danger exists. Indirect-contact hazard in the case of a MV fault If the insulation failure in an apparatus is between a MV conductor and the metal envelope, it is not generally possible to limit the rise of voltage of the envelope to 50 V or less, simply by reducing the earthing resistance to a low value. The solution in this case is to create an equipotential situation, as described in Sub-clause 1.1 “Earthing systems”. 3.2 Protection of transformer and circuits General The electrical equipment and circuits in a substation must be protected in order to avoid or to control damage due to abnormal currents and/or voltages. All equipment normally used in power system installations have standardized short-time withstand ratings for overcurrent and overvoltage. The role of protective scheme is to ensure that this withstand limits can never be exceeded. In general, this means that fault conditions must be cleared as fast as possible without missing to ensure coordination between protective devices upstream and downstream the equipement to be protected. This means, when there is a fault in a network, generally several protective devices see the fault at the same time but only one must act. These devices may be: b Fuses which clear the faulty circuit directly or together with a mechanical tripping attachment, which opens an associated three-phase load-break switch b Relays which act indirectly on the circuit-breaker coil Transformer protection Stresses due to the supply network Some voltage surges can occur on the network such as : b Atmospheric voltage surges Atmospheric voltage surges are caused by a stroke of lightning falling on or near an overhead line. b Operating voltage surges A sudden change in the established operating conditions in an electrical network causes transient phenomena to occur. This is generally a high frequency or damped oscillation voltage surge wave. For both voltage surges, the overvoltage protection device generally used is a varistor (Zinc Oxide). In most cases, voltage surges protection has no action on switchgear. Stresses due to the load Overloading is frequently due to the coincidental demand of a number of small loads, or to an increase in the apparent power (kVA) demand of the installation, due to expansion in a factory, with consequent building extensions, and so on. Load increases raise the temperature of the wirings and of the insulation material. As a result, temperature increases involve a reduction of the equipment working life. Overload protection devices can be located on primary or secondary side of the transformer. The protection against overloading of a transformer is now provided by a digital relay which acts to trip the circuit-breaker on the secondary side of the transformer. Such relay, generally called thermal overload relay, artificially simulates the temperature, taking into account the time constant of the transformer. Some of them are able to take into account the effect of harmonic currents due to non linear loads (rectifiers, computer equipment, variable speed drives…).This type of relay is also able to predict the time before overload tripping and the waiting time after tripping. So, this information is very helpful to control load shedding operation. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved B - Connection to the MV public distribution network B - Connection to the MV public distribution network 3 Protection aspect B18 In addition, larger oil-immersed transformers frequently have thermostats with two settings, one for alarm purposes and the other for tripping. Dry-type transformers use heat sensors embedded in the hottest part of the windings insulation for alarm and tripping. Internal faults The protection of transformers by transformer-mounted devices, against the effects of internal faults, is provided on transformers which are fitted with airbreathing conservator tanks by the classical Buchholz mechanical relay (see Fig. B15). These relays can detect a slow accumulation of gases which results from the arcing of incipient faults in the winding insulation or from the ingress of air due to an oil leak. This first level of detection generally gives an alarm, but if the condition deteriorates further, a second level of detection will trip the upstream circuit-breaker. An oil-surge detection feature of the Buchholz relay will trip the upstream circuitbreaker “instantaneously” if a surge of oil occurs in the pipe connecting the main tank with the conservator tank. Such a surge can only occur due to the displacement of oil caused by a rapidly formed bubble of gas, generated by an arc of short-circuit current in the oil. By specially designing the cooling-oil radiator elements to perform a concerting action, “totally filled” types of transformer as large as 10 MVA are now currently available. Expansion of the oil is accommodated without an excessive rise in pressure by the “bellows” effect of the radiator elements. A full description of these transformers is given in Sub-clause 4.4 (see Fig. B16). Fig. B15 : Transformer with conservator tank Evidently the Buchholz devices mentioned above cannot be applied to this design; a modern counterpart has been developed however, which measures: b The accumulation of gas b Overpressure b Overtemperature The first two conditions trip the upstream circuit-breaker, and the third condition trips the downstream circuit-breaker of the transformer. Internal phase-to-phase short-circuit Internal phase-to-phase short-circuit must be detected and cleared by: b 3 fuses on the primary side of the tranformer or b An overcurrent relay that trips a circuit-breaker upstream of the transformer Internal phase-to-earth short-circuit This is the most common type of internal fault. It must be detected by an earth fault relay. Earth fault current can be calculated with the sum of the 3 primary phase currents (if 3 current transformers are used) or by a specific core current transformer. If a great sensitivity is needed, specific core current transformer will be prefered. In such a case, a two current transformers set is sufficient (see Fig. B17). Protection of circuits Fig. B16 : Totally filled transformer The protection of the circuits downstream of the transformer must comply with the IEC 60364 requirements. HV LV 1 1 2 2 3 3 N © Schneider Electric - all rights reserved Overcurrent relay E/F relay Fig. B17 : Protection against earth fault on the MV winding Discrimination between the protective devices upstream and downstream of the transformer The consumer-type substation with LV metering requires discriminative operation between the MV fuses or MV circuit-breaker and the LV circuit-breaker or fuses. The rating of the MV fuses will be chosen according to the characteristics of the transformer. The tripping characteristics of the LV circuit-breaker must be such that, for an overload or short-circuit condition downstream of its location, the breaker will trip sufficiently quickly to ensure that the MV fuses or the MV circuit-breaker will not be adversely affected by the passage of overcurrent through them. The tripping performance curves for MV fuses or MV circuit-breaker and LV circuitbreakers are given by graphs of time-to-operate against current passing through them. Both curves have the general inverse-time/current form (with an abrupt discontinuity in the CB curve at the current value above which “instantaneous” tripping occurs). These curves are shown typically in Figure B18. Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network b In order to achieve discrimination: All parts of the fuse or MV circuit-breaker curve must be above and to the right of the CB curve. Minimum pre-arcing time of MV fuse b In order to leave the fuses unaffected (i.e. undamaged): All parts of the minimum pre-arcing fuse curve must be located to the right of the CB curve by a factor of 1.35 or more (e.g. where, at time T, the CB curve passes through a point corresponding to 100 A, the fuse curve at the same time T must pass through a point corresponding to 135 A, or more, and so on...) and, all parts of the fuse curve must be above the CB curve by a factor of 2 or more (e.g. where, at a current level I the CB curve passes through a point corresponding to 1.5 seconds, the fuse curve at the same current level I must pass through a point corresponding to 3 seconds, or more, etc.). The factors 1.35 and 2 are based on standard maximum manufacturing tolerances for MV fuses and LV circuit-breakers. In order to compare the two curves, the MV currents must be converted to the equivalent LV currents, or vice-versa. Where a LV fuse-switch is used, similar separation of the characteristic curves of the MV and LV fuses must be respected. B/A u 1.35 at any moment in time D/C u 2 at any current value D Circuit breaker tripping characteristic C Current A B Fig. B18 : Discrimination between MV fuse operation and LV circuit-breaker tripping, for transformer protection U1 MV LV Fig. B19 : MV fuse and LV circuit-breaker configuration U2 B19 b In order to leave the MV circuit-breaker protection untripped: All parts of the minimum pre-arcing fuse curve must be located to the right of the CB curve by a factor of 1.35 or more (e.g. where, at time T, the LV CB curve passes through a point corresponding to 100 A, the MV CB curve at the same time T must pass through a point corresponding to 135 A, or more, and so on...) and, all parts of the MV CB curve must be above the LV CB curve (time of LV CB curve must be less or equal than MV CB curves minus 0.3 s) The factors 1.35 and 0.3 s are based on standard maximum manufacturing tolerances for MV current transformers, MV protection relay and LV circuit-breakers. In order to compare the two curves, the MV currents must be converted to the equivalent LV currents, or vice-versa. Choice of protective device on the primary side of the transformer As explained before, for low reference current, the protection may be by fuses or by circuit-breaker. When the reference current is high, the protection will be achieved by circuit-breaker. Protection by circuit-breaker provides a more sensitive transformer protection compared with fuses. The implementation of additional protections (earth fault protection, thermal overload protection) is easier with circuit-breakers. 3.3 Interlocks and conditioned operations Mechanical and electrical interlocks are included on mechanisms and in the control circuits of apparatus installed in substations, as a measure of protection against an incorrect sequence of manœuvres by operating personnel. Mechanical protection between functions located on separate equipment (e.g. switchboard and transformer) is provided by key-transfer interlocking. An interlocking scheme is intended to prevent any abnormal operational manœuvre. Some of such operations would expose operating personnel to danger, some others would only lead to an electrical incident. Basic interlocking Basic interlocking functions can be introduced in one given functionnal unit; some of these functions are made mandatory by the IEC 62271-200, for metal-enclosed MV switchgear, but some others are the result of a choice from the user. Considering access to a MV panel, it requires a certain number of operations which shall be carried out in a pre-determined order. It is necessary to carry out operations in the reverse order to restore the system to its former condition. Either proper procedures, or dedicated interlocks, can ensure that the required operations are performed in the right sequence. Then such accessible compartment will be classified as “accessible and interlocked” or “accessible by procedure”. Even for users with proper rigorous procedures, use of interlocks can provide a further help for safety of the operators. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Time 3 Protection aspect B - Connection to the MV public distribution network 3 Protection aspect B20 Key interlocking Beyond the interlocks available within a given functionnal unit (see also 4.2), the most widely-used form of locking/interlocking depends on the principle of key transfer. The principle is based on the possibility of freeing or trapping one or several keys, according to whether or not the required conditions are satisfied. These conditions can be combined in unique and obligatory sequences, thereby guaranteeing the safety of personnel and installation by the avoidance of an incorrect operational procedure. Non-observance of the correct sequence of operations in either case may have extremely serious consequences for the operating personnel, as well as for the equipment concerned. Note: It is important to provide for a scheme of interlocking in the basic design stage of planning a MV/LV substation. In this way, the apparatuses concerned will be equipped during manufacture in a coherent manner, with assured compatibility of keys and locking devices. Service continuity For a given MV switchboard, the definition of the accessible compartments as well as their access conditions provide the basis of the “Loss of Service Continuity” classification defined in the standard IEC 62271-200. Use of interlocks or only proper procedure does not have any influence on the service continuity. Only the request for accessing a given part of the switchboard, under normal operation conditions, results in limiting conditions which can be more or less severe regarding the continuity of the electrical distribution process. Interlocks in substations In a MV/LV distribution substation which includes: b A single incoming MV panel or two incoming panels (from parallel feeders) or two incoming/outgoing ring-main panels b A transformer switchgear-and-protection panel, which can include a load-break/ disconnecting switch with MV fuses and an earthing switch, or a circuit-breaker and line disconnecting switch together with an earthing switch b A transformer compartment Interlocks allow manœuvres and access to different panels in the following conditions: Basic interlocks, embedded in single functionnal units b Operation of the load-break/isolating switch v If the panel door is closed and the associated earthing switch is open b Operation of the line-disconnecting switch of the transformer switchgear - and - protection panel v If the door of the panel is closed, and v If the circuit-breaker is open, and the earthing switch(es) is (are) open b Closure of an earthing switch v If the associated isolating switch(es) is (are) open(1) b Access to an accessible compartment of each panel, if interlocks have been specified v If the isolating switch for the compartment is open and the earthing switch(es) for the compartment is (are) closed b Closure of the door of each accessible compartment, if interlocks have been specified v If the earthing switch(es) for the compartment is (are) closed © Schneider Electric - all rights reserved Functional interlocks involving several functional units or separate equipment b Access to the terminals of a MV/LV transformer v If the tee-off functional unit has its switch open and its earthing switch closed. According to the possibility of back-feed from the LV side, a condition on the LV main breaker can be necessary. Practical example In a consumer-type substation with LV metering, the interlocking scheme most commonly used is MV/LV/TR (high voltage/ low voltage/transformer). (1) If the earthing switch is on an incoming circuit, the associated isolating switches are those at both ends of the circuit, and these should be suitably interlocked. In such situation, the interlocking function becomes a multi-units key interlock. The aim of the interlocking is: b To prevent access to the transformer compartment if the earthing switch has not been previously closed b To prevent the closure of the earthing switch in a transformer switchgear-andprotection panel, if the LV circuit-breaker of the transformer has not been previously locked “open” or “withdrawn” Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 3 Protection aspect Access to the MV or LV terminals of a transformer, (protected upstream by a MV switchgear-and-protection panel, containing a MV load-break / isolating switch, MV fuses, and a MV earthing switch) must comply with the strict procedure described below, and is illustrated by the diagrams of Figure B20. B21 Note: The transformer in this example is provided with plug-in type MV terminal connectors which can only be removed by unlocking a retaining device common to all three phase connectors(1). The MV load-break / disconnecting switch is mechanically linked with the MV earthing switch such that only one of the switches can be closed, i.e. closure of one switch automatically locks the closure of the other. Procedure for the isolation and earthing of the power transformer, and removal of the MV plug-type shrouded terminal connections (or protective cover) S Initial conditions b MV load-break/disconnection switch and LV circuit-breaker are closed b MV earthing switch locked in the open position by key “O” b Key “O” is trapped in the LV circuit-breaker as long as that circuit-breaker is closed S Step 1 b Open LV CB and lock it open with key “O” b Key “O” is then released MV switch and LV CB closed Step 2 b Open the MV switch b Check that the “voltage presence” indicators extinguish when the MV switch is opened O S O Step 3 b Unlock the MV earthing switch with key “O” and close the earthing switch b Key “O” is now trapped Step 4 The access panel to the MV fuses can now be removed (i.e. is released by closure of the MV earthing switch). Key “S” is located in this panel, and is trapped when the MV switch is closed b Turn key “S” to lock the MV switch in the open position b Key “S” is now released S MV fuses accessible O The result of the foregoing procedure is that: b The MV switch is locked in the open position by key “S”. Key “S” is trapped at the transformer terminals interlock as long as the terminals are exposed. b The MV earthing switch is in the closed position but not locked, i.e. may be opened or closed. When carrying out maintenance work, a padlock is generally used to lock the earthing switch in the closed position, the key of the padlock being held by the engineer supervizing the work. b The LV CB is locked open by key “O”, which is trapped by the closed MV earthing switch. The transformer is therefore safely isolated and earthed. S O Transformer MV terminals accessible Legend Key absent Key free Key trapped Panel or door It may be noted that the upstream terminal of the load-break disconnecting switch may remain live in the procedure described as the terminals in question are located in a separate non accessible compartment in the particular switchgear under discussion. Any other technical solution with exposed terminals in the accessed compartment would need further de-energisation and interlocks. Fig. B20 : Example of MV/LV/TR interlocking (1) Or may be provided with a common protective cover over the three terminals. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved S Step 5 Key “S” allows removal of the common locking device of the plug-type MV terminal connectors on the transformer or of the common protective cover over the terminals, as the case may be. In either case, exposure of one or more terminals will trap key “S” in the interlock. B - Connection to the MV public distribution network B22 4 The consumer substation with LV metering 4.1 General A consumer substation with LV metering is an electrical installation connected to a utility supply system at a nominal voltage of 1 kV - 35 kV, and includes a single MV/LV transformer generally not exceeding 1,250 kVA. Functions The substation All component parts of the substation are located in one room, either in an existing building, or in the form of a prefabricated housing exterior to the building. Connection to the MV network Connection at MV can be: b Either by a single service cable or overhead line, or b Via two mechanically interlocked load-break switches with two service cables from duplicate supply feeders, or b Via two load-break switches of a ring-main unit The transformer Since the use of PCB(1)-filled transformers is prohibited in most countries, the preferred available technologies are: b Oil-immersed transformers for substations located outside premises b Dry-type, vacuum-cast-resin transformers for locations inside premises, e.g. multistoreyed buildings, buildings receiving the public, and so on... Metering Metering at low voltage allows the use of small metering transformers at modest cost. Most tariff structures take account of MV/LV transformer losses. LV installation circuits A low-voltage circuit-breaker, suitable for isolation duty and locking off facilities, to: b Supply a distribution board b Protect the transformer against overloading and the downstream circuits against short-circuit faults. One-line diagrams The diagrams on the following page (see Fig. B21) represent the different methods of MV service connection, which may be one of four types: b Single-line service b Single-line service (equipped for extension to form a ring main) b Duplicate supply service b Ring main service 4.2 Choice of MV switchgear Standards and specifications The switchgear and equipment described below are rated for 1 kV - 24 kV systems and comply with the following international standards: IEC 62271-1, 62271-200, 60265-1, 62271-102, 62271-100, 62271-105 Local regulations can also require compliance with national standards as: b France: UTE b United Kingdom: BS b Germany: VDE b United States of America: ANSI © Schneider Electric - all rights reserved Type of equipment In addition of Ring Main Units discussed in section 1.2, all kinds of switchgear arrangements are possible when using modular switchgear, and provisions for later extensions are easily realized. (1) Polychlorinated biphenyl Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 4 The consumer substation with LV metering B23 Power supply system Service connection MV protection and MV/LV transformation Supplier/consumer interface Single-line service LV metering and isolation Transformer LV terminals LV distribution and protection Downstream terminals of LV isolator Protection Protection Single-line service (equipped for extension to form a ring main) Permitted if only one transformer and rated power low enough to accomodate the limitations of fuses and combinations Protection Duplicatesupply service Ring main service Permitted if only one transformer and rated power low enough to accomodate the limitations of fuses and combinations Protection Protection + Auto-changeover switch Automatic LV standby source © Schneider Electric - all rights reserved Always permitted Fig. B21 : Consumer substation with LV metering Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 4 The consumer substation with LV metering B24 Operational safety of metal enclosed switchgear Description The following notes describe a “state-of-the art” load-break / disconnecting-switch panel (see Fig. B22) incorporating the most modern developments for ensuring: b Operational safety b Minimum space requirements b Extendibility and flexibility b Minimum maintenance requirements Each panel includes 3 compartments: b Switchgear: the load-break disconnecting switch is incorporated in an hermetically sealed (for life) molded epoxy-resin unit b Connections: by cable at terminals located on the molded switch unit b Busbars: modular, such that any number of panels may be assembled side-by-side to form a continuous switchboard, and for control and indication a low voltage cabinet which can accommodate automatic control and relaying equipment. An additional cabinet may be mounted above the existing one if further space is required. Cable connections are provided inside a cable-terminating compartment at the front of the unit, to which access is gained by removal of the front panel of the compartment. The units are connected electrically by means of prefabricated sections of busbars. Site erection is effected by following the assembly instructions. Operation of the switchgear is simplified by the grouping of all controls and indications on a control panel at the front of each unit. The technology of these switchgear units is essentially based on operational safety, ease of installation and low maintenance requirements. Switchgear internal safety measures b The load-break/disconnecting switch fully satisfies the requirement of “reliable position indicating device” as defined in IEC 62271-102 (disconnectors and earthing switches) b The functionnal unit incorporates the basic interlocks specified by the IEC 62271-200 (prefabricated metal enclosed switchgear and controlgear): v Closure of the switch is not possible unless the earth switch is open v Closure of the earthing switch is only possible if the load break/isolating switch is open b Access to the cable compartment, which is the only user-accessible compartment during operation, is secured by further interlocks: v Opening of the access panel to the cable terminations compartment(1) is only possible if the earthing switch is closed v The load-break/disconnecting switch is locked in the open position when the above-mentioned access panel is open. Opening of the earthing switch is then possible, for instance to allow a dielectric test on the cables. With such features, the switchboard can be operated with live busbars and cables, except for the unit where the access to cables is made. It complies then with the Loss of Service Continuity class LSB2A, as defined in the IEC 62271-200. Apart from the interlocks noted above, each switchgear panel includes: b Built-in padlocking facilities on the operation levers b 5 predrilled sets of fixing holes for possible future interlocking locks © Schneider Electric - all rights reserved Operations Fig. B22 : Metal enclosed MV load break disconnecting switch b Operating handles, levers, etc. required for switching operations are grouped together on a clearly illustrated panel b All closing-operation levers are identical on all units (except those containing a circuit-breaker) b Operation of a closing lever requires very little effort b Opening or closing of a load-break/disconnecting switch can be by lever or by push-button for automatic switches b Conditions of switches (Open, Closed, Spring-charged), are clearly indicated (1) Where MV fuses are used they are located in this compartment. Schneider Electric - Electrical installation guide 2009 4 The consumer substation with LV metering 4.3 Choice of MV switchgear panel for a transformer circuit B25 Three types of MV switchgear panel are generally available: b Load-break switch and separate MV fuses in the panel b Load-break switch/MV fuses combination b Circuit-breaker Seven parameters influence the optimum choice: b The primary current of the transformer b The insulating medium of the transformer b The position of the substation with respect to the load centre b The kVA rating of the transformer b The distance from switchgear to the transformer b The use of separate protection relays (as opposed to direct-acting trip coils). Note: The fuses used in the load-break/switch fuses combination have striker-pins which ensure tripping of the 3-pole switch on the operation of one (or more) fuse(s). 4.4 Choice of MV/LV transformer Characteristic parameters of a transformer A transformer is characterized in part by its electrical parameters, but also by its technology and its conditions of use. Electrical characteristics b Rated power (Pn): the conventional apparent-power in kVA on which other designparameter values and the construction of the transformer are based. Manufacturing tests and guarantees are referred to this rating b Frequency: for power distribution systems of the kind discussed in this guide, the frequency will be 50 Hz or 60 Hz b Rated primary and secondary voltages: For a primary winding capable of operating at more than one voltage level, a kVA rating corresponding to each level must be given. The secondary rated voltage is its open circuit value b Rated insulation levels are given by overvoltage-withstand test values at power frequency, and by high voltage impulse tests values which simulate lightning discharges. At the voltage levels discussed in this guide, overvoltages caused by MV switching operations are generally less severe than those due to lightning, so that no separate tests for switching-surge withstand capability are made b Off-circuit tap-selector switch generally allows a choice of up to ± 2.5% and ± 5% level about the rated voltage of the highest voltage winding. The transformer must be de-energized before this switch is operated b Winding configurations are indicated in diagrammatic form by standard symbols for star, delta and inter-connected-star windings; (and combinations of these for special duty, e.g. six-or twelve-phase rectifier transformers, etc.) and in an IEC-recommended alphanumeric code. This code is read from left-to-right, the first letter refers to the highest voltage winding, the second letter to the next highest, and so on: v Capital letters refer to the highest voltage winding D = delta Y = star Z = interconnected-star (or zigzag) N = neutral connection brought out to a terminal v Lower-case letters are used for tertiary and secondary windings d = delta y = star z = interconnected-star (or zigzag) n = neutral connection brought out to a terminal v A number from 0 to 11, corresponding to those, on a clock dial (“0” is used instead of “12”) follows any pair of letters to indicate the phase change (if any) which occurs during the transformation. A very common winding configuration used for distribution transformers is that of a Dyn 11 transformer, which has a delta MV winding with a star-connected secondary winding the neutral point of which is brought out to a terminal. The phase change through the transformer is +30 degrees, i.e. phase 1 secondary voltage is at “11 o’clock” when phase 1 of the primary voltage is at “12 o’clock”, as shown in Figure B31 page B34. All combinations of delta, star and zigzag windings produce a phase change which (if not zero) is either 30 degrees or a multiple of 30 degrees. IEC 60076-4 describes the “clock code” in detail. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved B - Connection to the MV public distribution network B - Connection to the MV public distribution network B26 4 The consumer substation with LV metering Characteristics related to the technology and utilization of the transformer This list is not exhaustive: b Choice of technology The insulating medium is: v Liquid (mineral oil) or v Solid (epoxy resin and air) b For indoor or outdoor installation b Altitude (<= 1,000 m is standard) b Temperature (IEC 60076-2) v Maximum ambient air: 40 °C v Daily maximum average ambient air: 30 °C v Annual maximum average ambient air: 20 °C For non-standard operating conditions, refer to “Influence of the Ambient temperature and altitude on the rated current” on page B7. Description of insulation techniques There are two basic classes of distribution transformer presently available: b Dry type (cast in resin) b Liquid filled (oil-immersed) Dry type transformers The windings of these transformers are insulated by resin between turns and by resin and air to other windings and to frame. The resin is usually cast under vacuum process (which is patented by major manufacturers). It is recommended that the transformer be chosen according to the IEC 60076-11, as follows: b Environment class E2 (frequent condensation and/or high level of pollution) b Climatic conditions class B2 (utilization, transport and stockage down to -25 °C) b Fire resistance (transformers exposed to fire risk with low flammability and self extinguishing in a given time) The following description refers to the process developed by a leading European manufacturer in this field. The encapsulation of a winding uses three components: b Epoxy-resin based on biphenol A with a viscosity that ensures complete impregnation of the windings b Anhydride hardener modified to introduce a degree of resilience in the moulding, essential to avoid the development of cracks during the temperature cycles occurring in normal operation b Pulverulent additive composed of trihydrated alumina Al (OH)3 and silica which enhances its mechanical and thermal properties, as well as giving exceptional intrinsic qualities to the insulation in the presence of heat. This three-component system of encapsulation gives Class F insulation (Δθ = 100 K) with excellent fire-resisting qualities and immediate self-extinction. These transformers are therefore classified as nonflammable. The mouldings of the windings contain no halogen compounds (chlorine, bromine, etc.) or other compounds capable of producing corrosive or toxic pollutants, thereby guaranteeing a high degree of safety to personnel in emergency situations, notably in the event of a fire. It also performs exceptionally well in hostile industrial atmospheres of dust, humidity, etc. (see Fig. B23). © Schneider Electric - all rights reserved Liquid-filled transformers The most common insulating/cooling liquid used in transformers is mineral oil. Mineral oils are specified in IEC 60296. Being flammable, safety measures are obligatory in many countries, especially for indoor substations. The DGPT unit (Detection of Gas, Pressure and Temperature) ensures the protection of oil-filled transformers. In the event of an anomaly, the DGPT causes the MV supply to the transformer to be cut off very rapidly, before the situation becomes dangerous. Mineral oil is bio-degradable and does not contain PCB (polychlorinated biphenyl), which was the reason for banning askerel, i.e. Pyralène, Pyrolio, Pyroline... On request, mineral oil can be replaced by an alternative insulating liquid, by adapting the transformer, as required, and taking appropriate additional precautions if necessary. Fig. B23 : Dry-type transformer The insulating fluid also acts as a cooling medium; it expands as the load and/or the ambient temperature increases, so that all liquid-filled transformers must be designed to accommodate the extra volume of liquid without the pressure in the tank becoming excessive. Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 4 The consumer substation with LV metering There are two ways in which this pressure limitation is commonly achieved: b Hermetically-sealed totally-filled tank (up to 10 MVA at the present time) Developed by a leading French manufacturer in 1963, this method was adopted by the national utility in 1972, and is now in world-wide service (see Fig. B24). Expansion of the liquid is compensated by the elastic deformation of the oil-cooling passages attached to the tank. The “total-fill” technique has many important advantages over other methods: v Oxydation of the dielectric liquid (with atmospheric oxygen) is entirely precluded v No need for an air-drying device, and so no consequent maintenance (inspection and changing of saturated dessicant) v No need for dielectric-strength test of the liquid for at least 10 years v Simplified protection against internal faults by means of a DGPT device is possible v Simplicity of installation: lighter and lower profile (than tanks with a conservator) and access to the MV and LV terminals is unobstructed v Immediate detection of (even small) oil leaks; water cannot enter the tank b Air-breathing conservator-type tank at atmospheric pressure Expansion of the insulating liquid is taken up by a change in the level of liquid in an expansion (conservator) tank, mounted above the transformer main tank, as shown in Figure B25. The space above the liquid in the conservator may be filled with air which is drawn in when the level of liquid falls, and is partially expelled when the level rises. When the air is drawn in from the surrounding atmosphere it is admitted through an oil seal, before passing through a dessicating device (generally containing silica-gel crystals) before entering the conservator. In some designs of larger transformers the space above the oil is occupied by an impermeable air bag so that the insulation liquid is never in contact with the atmosphere. The air enters and exits from the deformable bag through an oil seal and dessicator, as previously described. A conservator expansion tank is obligatory for transformers rated above 10 MVA (which is presently the upper limit for “total-fill” type transformers). B27 Choice of technology As discussed above, the choice of transformer is between liquid-filled or dry type. For ratings up to 10 MVA, totally-filled units are available as an alternative to conservator-type transformers. A choice depends on a number of considerations, including: b Safety of persons in proximity to the transformer. Local regulations and official recommendations may have to be respected b Economic considerations, taking account of the relative advantages of each technique The regulations affecting the choice are: b Dry-type transformer: v In some countries a dry-type transformer is obligatory in high apartment blocks v Dry-type transformers impose no constraints in other situations b Transformers with liquid insulation: v This type of transformer is generally forbidden in high apartment blocks v For different kinds of insulation liquids, installation restrictions, or minimum protection against fire risk, vary according to the class of insulation used v Some countries in which the use of liquid dielectrics is highly developed, classify the several categories of liquid according to their fire performance. This latter is assessed according to two criteria: the flash-point temperature, and the minimum calorific power. The principal categories are shown in Figure B26 in which a classification code is used for convenience. Fig. B24 : Hermetically-sealed totally-filled tank As an example, French standard defines the conditions for the installation of liquidfilled transformers. No equivalent IEC standard has yet been established. Fig. B25 : Air-breathing conservator-type tank at atmosphere pressure Code Dielectric fluid O1 K1 K2 K3 L3 Mineral oil High-density hydrocarbons Esters Silicones Insulating halogen liquids Fig. B26 : Categories of dielectric fluids Schneider Electric - Electrical installation guide 2009 Flash-point (°C) < 300 > 300 > 300 > 300 - Minimum calorific power (MJ/kg) 48 34 - 37 27 - 28 12 © Schneider Electric - all rights reserved The French standard is aimed at ensuring the safety of persons and property and recommends, notably, the minimum measures to be taken against the risk of fire. B - Connection to the MV public distribution network B28 4 The consumer substation with LV metering The main precautions to observe are indicated in Figure B27. b For liquid dielectrics of class L3 there are no special measures to be taken b For dielectrics of classes O1 and K1 the measures indicated are applicable only if there are more than 25 litres of dielectric liquid in the transformer b For dielectrics of classes K2 and K3 the measures indicated are applicable only if there are more than 50 litres of dielectric liquid in the transformer. Class of dielectric fluid O1 No. of litres above which measures must be taken 25 K1 K2 K3 L3 50 Locations Chamber or enclosed area reserved to qualified and authorized personnel, and separated from any other building by a distance D D>8m 4m<D<8m D < 4 m(1) in the direction of occupied areas No special Interposition of Fire-proof wall measures a fire-proof (2 hour rating) screen against adjoining (1 hour rating) building No special measures Interposition of a fire-proof screen (1 hour rating) No special measures Reserved to trained personnel and isolated from work areas by fire-proof walls (2 hours rating) No openings With opening(s) Other chambers or locations(2) Measures (1 + 2) or 3 or 4 No special measures Measures (1A + 2 + 4)(3) or 3 Measures (1 + 2 + 5) or 3 or (4 + 5) Measures 1A or 3 or 4 Measures 1 or 3 or 4 Measure 1: Arrangements such that if the dielectric escapes from the transformer, it will be completely contained (in a sump, by sills around the transformer, and by blocking of cable trenches, ducts and so on, during construction). Measure 1A: In addition to measure 1, arrange that, in the event of liquid ignition there is no possibility of the fire spreading (any combustible material must be moved to a distance of at least 4 metres from the transformer, or at least 2 metres from it if a fire-proof screen [of 1 hour rating] is interposed). Measure 2: Arrange that burning liquid will extinguish rapidly and naturally (by providing a pebble bed in the containment sump). Measure 3: An automatic device (gas, pressure & thermal relay, or Buchholz) for cutting off the primary power supply, and giving an alarm, if gas appears in the transformer tank. Measure 4: Automatic fire-detection devices in close proximity to the transformer, for cutting off primary power supply, and giving an alarm. Measure 5: Automatic closure by fire-proof panels (1/2 hour minimum rating) of all openings (ventilation louvres, etc.) in the walls and ceiling of the substation chamber. Notes: (1) A fire-proof door (rated at 2 hours) is not considered to be an opening. (2) Transformer chamber adjoining a workshop and separated from it by walls, the fire-proof characteristics of which are not rated for 2 hours. Areas situated in the middle of workshops the material being placed (or not) in a protective container. (3) It is indispensable that the equipment be enclosed in a chamber, the walls of which are solid, the only orifices being those necessary for ventilation purposes. Fig. B27 : Safety measures recommended in electrical installations using dielectric liquids of classes 01, K1, K2 or K3 The determination of optimal power Oversizing a transformer It results in: b Excessive investment and unecessarily high no-load losses, but b Lower on-load losses © Schneider Electric - all rights reserved Undersizing a transformer It causes: b A reduced efficiency when fully loaded, (the highest efficiency is attained in the range 50% - 70% full load) so that the optimum loading is not achieved b On long-term overload, serious consequences for v The transformer, owing to the premature ageing of the windings insulation, and in extreme cases, resulting in failure of insulation and loss of the transformer v The installation, if overheating of the transformer causes protective relays to trip the controlling circuit-breaker. Definition of optimal power In order to select an optimal power (kVA) rating for a transformer, the following factors must be taken into account: b List the power of installed power-consuming equipment as described in Chapter A b Decide the utilization (or demand) factor for each individual item of load b Determine the load cycle of the installation, noting the duration of loads and overloads b Arrange for power-factor correction, if justified, in order to: v Reduce cost penalties in tariffs based, in part, on maximum kVA demand v Reduce the value of declared load (P(kVA) = P (kW)/cos ϕ) b Select, among the range of standard transformer ratings available, taking into account all possible future extensions to the installation. It is important to ensure that cooling arrangements for the transformer are adequate. Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 4 The consumer substation with LV metering 4.5 Instructions for use of MV equipment B29 The purpose of this chapter is to provide general guidelines on how to avoid or greatly reduce MV equipment degradation on sites exposed to humidity and pollution. Normal service conditions for indoor MV equipment All MV equipments comply with specific standards and with the IEC 62271-1 standard “Common specifications for high-voltage switchgear and controlgear”, which defines the normal conditions for the installation and use of such equipment. For instance, regarding humidity, the standard mentions: The conditions of humidity are as follows: b The average value of the relative humidity, measured over a period of 24 h does not exceed 90%; b The average value of the water vapour pressure, over a period of 24 h does not exceed 2.2 kPa; b The average value of the relative humidity, over a period of one month does not exceed 90%; b The average value of water vapour pressure, over a period of one month does not exceed 1.8 kPa; Under these conditions, condensation may occasionally occur. NOTE 1: Condensation can be expected where sudden temperature changes occur in period of high humidity. NOTE 2: To withstand the effects of high humidity and condensation, such as a breakdown of insulation or corrosion of metallic parts, switchgear designed for such conditions and tested accordingly shoul be used. NOTE 3: Condensation may be prevented by special design of the building or housing, by suitable ventilation and heating of the station or by use of dehumifying equipment. As indicated in the standard, condensation may occasionally occur even under normal conditions. The standard goes on to indicate special measures concerning the substation premises that can be implemented to prevent condensation. Use under severe conditions Under certain severe conditions concerning humidity and pollution, largely beyond the normal conditions of use mentioned above, correctly designed electrical equipment can be subject to damage by rapid corrosion of metal parts and surface degradation of insulating parts. Remedial measures for condensation problems b Carefully design or adapt substation ventilation. b Avoid temperature variations. b Eliminate sources of humidity in the substation environment. b Install an air conditioning system. b Make sure cabling is in accordance with applicable rules. Remedial measures for pollution problems b Equip substation ventilation openings with chevron-type baffles to reduce entry of dust and pollution. b Keep substation ventilation to the minimum required for evacuation of transformer heat to reduce entry of pollution and dust. b Use MV cubicles with a sufficiently high degree of protection (IP). b Use air conditioning systems with filters to restrict entry of pollution and dust. b Regularly clean all traces of pollution from metal and insulating parts. Ventilation Substation ventilation is generally required to dissipate the heat produced by transformers and to allow drying after particularly wet or humid periods. However, a number of studies have shown that excessive ventilation can drastically increase condensation. Ventilation should therefore be kept to the minimum level required. Furthermore, ventilation should never generate sudden temperature variations that can cause the dew point to be reached. For this reason: Natural ventilation should be used whenever possible. If forced ventilation is necessary, the fans should operate continuously to avoid temperature fluctuations. Guidelines for sizing the air entry and exit openings of substations are presented hereafter. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. B28 : SM6 metal enclosed indoor MV eqpuipment B - Connection to the MV public distribution network 4 The consumer substation with LV metering B30 Calculation methods A number of calculation methods are available to estimate the required size of substation ventilation openings, either for the design of new substations or the adaptation of existing substations for which condensation problems have occurred. The basic method is based on transformer dissipation. The required ventilation opening surface areas S and S’ can be estimated using the following formulas: S ฀฀ S' H and S' 1.10 x S where: S = Lower (air entry) ventilation opening area [m²] (grid surface deducted) S’= Upper (air exit) ventilation opening area [m²] (grid surface deducted) P = Total dissipated power [W] P is the sum of the power dissipated by: b The transformer (dissipation at no load and due to load) b The LV switchgear b The MV switchgear H = Height between ventilation opening mid-points [m] See Fig. B29 Note: This formula is valid for a yearly average temperature of 20 °C and a maximum altitude of 1,000 m. 200 mm mini H S Fig. B29 : Natural ventilation 1.8 x 10-4 P It must be noted that these formulae are able to determine only one order of magnitude of the sections S and S', which are qualified as thermal section, i.e. fully open and just necessary to evacuate the thermal energy generated inside the MV/LV substation. The pratical sections are of course larger according ot the adopted technological solution. Indeed, the real air flow is strongly dependant: b on the openings shape and solutions adopted to ensure the cubicle protection index (IP): metal grid, stamped holes, chevron louvers,... b on internal components size and their position compared to the openings: transformer and/or retention oil box position and dimensions, flow channel between the components, ... b and on some physical and environmental parameters: outside ambient temperature, altitude, magnitude of the resulting temperature rise. The understanding and the optimization of the attached physical phenomena are subject to precise flow studies, based on the fluid dynamics laws, and realized with specific analytic software. Example: Transformer dissipation = 7,970 W LV switchgear dissipation = 750 W MV switchgear dissipation = 300 W The height between ventilation opening mid-points is 1.5 m. Calculation: Dissipated Power P = 7,970 + 750 + 300 = 9,020 W S 1.8 x 10-4 P 1.5 1.32 m2 and S' 1.1 x 1.32 1.46 m2 Ventilation opening locations © Schneider Electric - all rights reserved Fig. B30 : Ventilation opening locations To favour evacuation of the heat produced by the transformer via natural convection, ventilation openings should be located at the top and bottom of the wall near the transformer. The heat dissipated by the MV switchboard is negligible. To avoid condensation problems, the substation ventilation openings should be located as far as possible from the switchboard (see Fig. B 30). Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 4 The consumer substation with LV metering Type of ventilation openings B31 To reduce the entry of dust, pollution, mist, etc., the substation ventilation openings should be equipped with chevron-blade baffles. Always make sure the baffles are oriented in the right direction (see Fig. B31). Temperature variations inside cubicles Temperature variations inside the substation The following measures can be taken to reduce temperature variations inside the substation: b Improve the thermal insulation of the substation to reduce the effects of outdoor temperature variations on the temperature inside the substation. b Avoid substation heating if possible. If heating is required, make sure the regulation system and/or thermostat are sufficiently accurate and designed to avoid excessive temperature swings (e.g. no greater than 1 °C). If a sufficiently accurate temperature regulation system is not available, leave the heating on continuously, 24 hours a day all year long. b Eliminate cold air drafts from cable trenches under cubicles or from openings in the substation (under doors, roof joints, etc.). Substation environment and humidity Various factors outside the substation can affect the humidity inside. b Plants Avoid excessive plant growth around the substation. b Substation waterproofing The substation roof must not leak. Avoid flat roofs for which waterproofing is difficult to implement and maintain. b Humidity from cable trenches Make sure cable trenches are dry under all conditions. A partial solution is to add sand to the bottom of the cable trench. Pollution protection and cleaning Excessive pollution favours leakage current, tracking and flashover on insulators. To prevent MV equipment degradation by pollution, it is possible to either protect the equipment against pollution or regularly clean the resulting contamination. Protection Indoor MV switchgear can be protected by enclosures providing a sufficiently high degree of protection (IP). Cleaning If not fully protected, MV equipment must be cleaned regularly to prevent degradation by contamination from pollution. Cleaning is a critical process. The use of unsuitable products can irreversibly damage the equipment. For cleaning procedures, please contact your Schneider Electric correspondent. © Schneider Electric - all rights reserved Fig. B31 : Chevron-blade baffles To reduce temperature variations, always install anti-condensation heaters inside MV cubicles if the average relative humidity can remain high over a long period of time. The heaters must operate continuously, 24 hours a day all year long. Never connect them to a temperature control or regulation system as this could lead to temperature variations and condensation as well as a shorter service life for the heating elements. Make sure the heaters offer an adequate service life (standard versions are generally sufficient). Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network B32 A consumer substation with MV metering is an electrical installation connected to a utility supply system at a nominal voltage of 1 kV - 35 kV and generally includes a single MV/LV transformer which exceeds 1,250 kVA, or several smaller transformers. The rated current of the MV switchgear does not normally exceed 400 A. 5 The consumer substation with MV metering 5.1 General Functions The substation According to the complexity of the installation and the manner in which the load is divided, the substation: b Might include one room containing the MV switchboard and metering panel(s), together with the transformer(s) and low-voltage main distribution board(s), b Or might supply one or more transformer rooms, which include local LV distribution boards, supplied at MV from switchgear in a main substation, similar to that described above. These substations may be installed, either: b Inside a building, or b Outdoors in prefabricated housings. Connection to the MV network Connection at MV can be: b Either by a single service cable or overhead line, or b Via two mechanically interlocked load-break switches with two service cables from duplicate supply feeders, or b Via two load-break switches of a ring-main unit. Metering Before the installation project begins, the agreement of the power-supply utility regarding metering arrangements must be obtained. A metering panel will be incorporated in the MV switchboard. Voltage transformers and current transformers, having the necessary metering accuracy, may be included in the main incoming circuit-breaker panel or (in the case of the voltage transformer) may be installed separately in the metering panel. Transformer rooms If the installation includes a number of transformer rooms, MV supplies from the main substation may be by simple radial feeders connected directly to the transformers, or by duplicate feeders to each room, or again, by a ring-main, according to the degree of supply availability desired. In the two latter cases, 3-panel ring-main units will be required at each transformer room. Local emergency generators Emergency standby generators are intended to maintain a power supply to essential loads, in the event of failure of the power supply system. Capacitors Capacitors will be installed, according to requirements: b In stepped MV banks at the main substation, or b At LV in transformer rooms. Transformers For additional supply-security reasons, transformers may be arranged for automatic changeover operation, or for parallel operation. © Schneider Electric - all rights reserved One-line diagrams The diagrams shown in Figure B32 next page represent: b The different methods of MV service connection, which may be one of four types: v Single-line service v Single-line service (equipped for extension to form a ring main) v Duplicate supply service v Ring main service b General protection at MV, and MV metering functions b Protection of outgoing MV circuits b Protection of LV distribution circuits Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 5 The consumer substation with MV metering B33 Power supply system Service connection Supplier/consumer interface MV protection and metering MV distribution and protection of outgoing circuits Downstream terminals of MV isolator for the installation Single-line service LV distribution and protection LV terminals of transformer Protection LV Single-line service (equipped for extension to form a ring main) A single transformer Automatic LV/MV standby source Duplicatesupply service Protection + automatic changeover feature Protection Ring-main service Automatic LV standby source © Schneider Electric - all rights reserved Fig. B32 : Consumer substation with MV metering Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 5 The consumer substation with MV metering B34 5.2 Choice of panels A substation with MV metering includes, in addition to the panels described in 4.2, panels specifically designed for metering and, if required, for automatic or manual changeover from one source to another. Metering and general protection These two functions are achieved by the association of two panels: b One panel containing the VT b The main MV circuit-breaker panel containing the CTs for measurement and protection The general protection is usually against overcurrent (overload and short-circuit) and earth faults. Both schemes use protective relays which are sealed by the powersupply utility. Substation including generators MV distribution panels for which standby Automatic supply is changeover required panel Generator in stand alone operation If the installation needs great power supply availability, a MV standby generator set can be used. In such a case, the installation must include an automatic changeover. In order to avoid any posssibility of parallel operation of the generator with the power supply network, a specific panel with automatic changeover is needed (see Fig. B33). Busbar transition panel To remainder of the MV switchboard b Protection Specific protective devices are intended to protect the generator itself. It must be noted that, due to the very low short-circuit power of the generator comparing with the power supply network, a great attention must be paid to protection discrimination. b Control A voltage regulator controlling an alternator is generally arranged to respond to a reduction of voltage at its terminals by automatically increasing the excitation current of the alternator, until the voltage is restored to normal. When it is intended that the alternator should operate in parallel with others, the AVR (Automatic Voltage Regulator) is switched to “parallel operation” in which the AVR control circuit is slightly modified (compounded) to ensure satisfactory sharing of kvars with the other parallel machines. When a number of alternators are operating in parallel under AVR control, an increase in the excitation current of one of them (for example, carried out manually after switching its AVR to Manual control) will have practically no effect on the voltage level. In fact, the alternator in question will simply operate at a lower power factor (more kVA, and therefore more current) than before. From standby generator P y 20,000 kVA Fig. B33 : Section of MV switchboard including standby supply panel The power factor of all the other machines will automatically improve, such that the load power factor requirements are satisfied, as before. Generator operating in parallel with the utility supply network To connect a generator set on the network, the agreement of the power supply utility is usually required. Generally the equipement (panels, protection relays) must be approved by the utility. The following notes indicate some basic consideration to be taken into account for protection and control. © Schneider Electric - all rights reserved b Protection To study the connection of generator set, the power supply utility needs some data as follows : v Power injected on the network v Connection mode v Short-circuit current of the generator set v Voltage unbalance of the generator v etc. Depending on the connection mode, dedicated uncoupling protection functions are required : v Under-voltage and over-voltage protection v Under-frequency and over-frequency protection v Zero sequence overvoltage protection v Maximum time of coupling (for momentary coupling) v Reverse real power For safety reasons, the switchgear used for uncoupling must also be provided with the characteristics of a disconnector (i.e total isolation of all active conductors between the generator set and the power supply network). Schneider Electric - Electrical installation guide 2009 5 The consumer substation with MV metering b Control When generators at a consumer’s substation operate in parallel with all the generation of the utility power supply system, supposing the power system voltage is reduced for operational reasons (it is common to operate MV systems within a range of ± 5% of nominal voltage, or even more, where load-flow patterns require it), an AVR set to maintain the voltage within ± 3% (for example) will immediately attempt to raise the voltage by increasing the excitation current of the alternator. B35 Instead of raising the voltage, the alternator will simply operate at a lower power factor than before, thereby increasing its current output, and will continue to do so, until it is eventually tripped out by its overcurrent protective relays. This is a wellknown problem and is usually overcome by the provision of a “constant powerfactor” control switch on the AVR unit. By making this selection, the AVR will automatically adjust the excitation current to match whatever voltage exists on the power system, while at the same time maintaining the power factor of the alternator constant at the pre-set value (selected on the AVR control unit). In the event that the alternator becomes decoupled from the power system, the AVR must be automatically (rapidly) switched back to “constant-voltage” control. 5.3 Parallel operation of transformers The need for operation of two or more transformers in parallel often arises due to: b Load growth, which exceeds the capactiy of an existing transformer b Lack of space (height) for one large transformer b A measure of security (the probability of two transformers failing at the same time is very small) b The adoption of a standard size of transformer throughout an installation Total power (kVA) The total power (kVA) available when two or more transformers of the same kVA rating are connected in parallel, is equal to the sum of the individual ratings, providing that the percentage impedances are all equal and the voltage ratios are identical. Transformers of unequal kVA ratings will share a load practically (but not exactly) in proportion to their ratings, providing that the voltage ratios are identical and the percentage impedances (at their own kVA rating) are identical, or very nearly so. In these cases, a total of more than 90% of the sum of the two ratings is normally available. It is recommended that transformers, the kVA ratings of which differ by more than 2:1, should not be operated permanently in parallel. Conditions necessary for parallel operation All paralleled units must be supplied from the same network. The inevitable circulating currents exchanged between the secondary circuits of paralleled transformers will be negligibly small providing that: b Secondary cabling from the transformers to the point of paralleling have approximately equal lengths and characteristics b The transformer manufacturer is fully informed of the duty intended for the transformers, so that: v The winding configurations (star, delta, zigzag star) of the several transformers have the same phase change between primary and secondary voltages v The short-circuit impedances are equal, or differ by less than 10% v Voltage differences between corresponding phases must not exceed 0.4% v All possible information on the conditions of use, expected load cycles, etc. should be given to the manufacturer with a view to optimizing load and no-load losses © Schneider Electric - all rights reserved B - Connection to the MV public distribution network Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network B36 5 The consumer substation with MV metering Common winding arrangements As described in 4.4 “Electrical characteristics-winding configurations” the relationships between primary, secondary, and tertiary windings depend on: b Type of windings (delta, star, zigzag) b Connection of the phase windings Depending on which ends of the windings form the star point (for example), a star winding will produce voltages which are 180° displaced with respect to those produced if the opposite ends had been joined to form the star point. Similar 180° changes occur in the two possible ways of connecting phase-to-phase coils to form delta windings, while four different combinations of zigzag connections are possible. b The phase displacement of the secondary phase voltages with respect to the corresponding primary phase voltages. As previously noted, this displacement (if not zero) will always be a multiple of 30° and will depend on the two factors mentioned above, viz type of windings and connection (i.e. polarity) of the phase windings. By far the most common type of distribution transformer winding configuration is the Dyn 11 connection (see Fig. B34). Voltage vectors 1 1 V12 2 N 3 2 3 1 1 N 2 2 Windings correspondence 3 V12 on the primary winding produces V1N in the secondary winding and so on ... © Schneider Electric - all rights reserved Fig. B34 : Phase change through a Dyn 11 transformer Schneider Electric - Electrical installation guide 2009 3 6 Constitution of MV/LV distribution substations MV/LV substations are constructed according to the magnitude of the load and the kind of power system in question. B37 Substations may be built in public places, such as parks, residential districts, etc. or on private premises, in which case the power supply authority must have unrestricted access. This is normally assured by locating the substation, such that one of its walls, which includes an access door, coincides with the boundary of the consumers premises and the public way. 6.1 Different types of substation Substations may be classified according to metering arrangements (MV or LV) and type of supply (overhead line or underground cable). The substations may be installed: b Either indoors in room specially built for the purpose, within a building, or b An outdoor installation which could be : v Installed in a dedicated enclosure prefabricated or not, with indoor equipment (switchgear and transformer) v Ground mounted with outdoor equipment (switchgear and transformers) v Pole mounted with dedicated outdoor equipment (swithgear and transformers) Prefabricated substations provide a particularly simple, rapid and competitive choice. 6.2 Indoor substation Conception Figure B35 shows a typical equipment layout recommended for a LV metering substation. Remark: the use of a cast-resin dry-type transformer does not need a fireprotection oil sump. However, periodic cleaning is needed. LV connections from transformer MV connections to transformer (included in a panel or free-standing) LV switchgear 2 incoming MV panels MV switching and protection panel Current transformers provided by power-supply authority Connection to the powersupply network by single-core or three-core cables, with or without a cable trench Transformer Fig. B35 : Typical arrangment of switchgear panels for LV metering Schneider Electric - Electrical installation guide 2009 Oil sump LV cable trench © Schneider Electric - all rights reserved B - Connection to the MV public distribution network B - Connection to the MV public distribution network B38 6 Constitution of MV/LV distribution substations Service connections and equipment interconnections At high voltage b Connections to the MV system are made by, and are the responsibility of the utility b Connections between the MV switchgear and the transformers may be: v By short copper bars where the transformer is housed in a panel forming part of the MV switchboard v By single-core screened cables with synthetic insulation, with possible use of plugin type terminals at the transformer At low voltage b Connections between the LV terminals of the transformer and the LV switchgear may be: v Single-core cables v Solid copper bars (circular or rectangular section) with heat-shrinkable insulation Metering (see Fig. B36) b Metering current transformers are generally installed in the protective cover of the power transformer LV terminals, the cover being sealed by the supply utility b Alternatively, the current transformers are installed in a sealed compartment within the main LV distribution cabinet b The meters are mounted on a panel which is completely free from vibrations b Placed as close to the current transformers as possible, and b Are accessible only to the utility 100 MV supply LV distribution Common earth busbar for the substation 800 mini Safety accessories Meters Fig. B36 : Plan view of typical substation with LV metering Earthing circuits The substation must include: b An earth electrode for all exposed conductive parts of electrical equipment in the substation and exposed extraneous metal including: v Protective metal screens v Reinforcing rods in the concrete base of the substation Substation lighting Supply to the lighting circuits can be taken from a point upstream or downstream of the main incoming LV circuit-breaker. In either case, appropriate overcurrent protection must be provided. A separate automatic circuit (or circuits) is (are) recommended for emergency lighting purposes. © Schneider Electric - all rights reserved Operating switches, pushbuttons, etc. are normally located immediately adjacent to entrances. Lighting fittings are arranged such that: b Switchgear operating handles and position indication markings are adequately illuminated b All metering dials and instruction plaques and so on, can be easily read Schneider Electric - Electrical installation guide 2009 B - Connection to the MV public distribution network 6 Constitution of MV/LV distribution substations B39 Materials for operation and safety According to local safety rules, generally, the substation is provided with: b Materials for assuring safe exploitation of the equipment including: v Insulating stool and/or an insulating mat (rubber or synthetic) v A pair of insulated gloves stored in an envelope provided for the purpose v A voltage-detecting device for use on the MV equipment v Earthing attachments (according to type of switchgear) b Fire-extinguishing devices of the powder or CO2 type b Warning signs, notices and safety alarms: v On the external face of all access doors, a DANGER warning plaque and prohibition of entry notice, together with instructions for first-aid care for victims of electrical accidents. 6.3 Outdoor substations Outdoor substation with prefabricated enclosures A prefabricated MV/LV substation complying with IEC 62271-202 standard includes : b equipement in accordance with IEC standards b a type tested enclosure, which means during its design, it has undergone a battery of tests (see Fig. B37): v Degree of protection v Functional tests v Temperature class v Non-flammable materials v Mechanical resistance of the enclosure v Sound level v Insulation level v Internal arc withstand v Earthing circuit test v Oil retention,… Use of equipment conform to IEC standards: Mechanical resistance of the enclosure: b Degree of protection b Sound level b Electromagnetic compatibility b Insulation level b Functional tests LV MV b Internal arcing withstand b Temperature class b Non-flammable materials Earthing circuit test Oil retention Walk-in Non walk-in Half buried Underground a- b- Main benefits are : b Safety: v For public and operators thanks to a high reproducible quality level b Cost effective: v Manufactured, equipped and tested in the factory b Delivery time v Delivered ready to be connected. IEC 62271-202 standard includes four main designs (see Fig. B38) Fig. B38 : The four designs according to IEC 62271-202 standard and two pictures [a] walk-in type MV/LV substation; [b] half buried type MV/LV substation b Walk-in type substation : v Operation protected from bad weather conditions b Non walk-in substation v Ground space savings, and outdoors operations b Half buried substation v Limited visual impact b Underground substation v Blends completely into the environment. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. B37 : Type tested substation according to IEC 62271-202 standard B - Connection to the MV public distribution network B40 6 Constitution of MV/LV distribution substations Outdoor substations without enclosures (see Fig. B39) These kinds of outdoor substation are common in some countries, based on weatherproof equipment exposed to the elements. These substations comprise a fenced area in which three or more concrete plinths are installed for: b A ring-main unit, or one or more switch-fuse or circuit-breaker unit(s) b One or more transformer(s), and b One or more LV distribution panel(s). Pole mounted substations Field of application These substations are mainly used to supply isolated rural consumers from MV overhead line distribution systems. Constitution In this type of substation, most often, the MV transformer protection is provided by fuses. Lightning arresters are provided, however, to protect the transformer and consumers as shown in Figure B40. General arrangement of equipment As previously noted the location of the substation must allow easy access, not only for personnel but for equipment handling (raising the transformer, for example) and the manœuvring of heavy vehicles. Lightning arresters LV circuit breaker D1 Earthing conductor 25 mm2 copper Protective conductor cover © Schneider Electric - all rights reserved Safety earth mat Fig. B39 : Outdoor substations without enclosures Fig. B40 : Pole-mounted transformer substation Schneider Electric - Electrical installation guide 2009 Chapter C Connection to the LV utility distribution network Contents 1 Low-voltage utility distribution networks C2 1.1 1.2 1.3 1.4 C2 C1 C10 C11 C15 2 Tariffs and metering C16 © Schneider Electric - all rights reserved Low-voltage consumers Low-voltage distribution networks The consumer service connection Quality of supply voltage Schneider Electric - Electrical installation guide 2009 C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks The most-common LV supplies are within the range 120 V single phase to 240/415 V 3-phase 4-wires. C2 Loads up to 250 kVA can be supplied at LV, but power-supply organizations generally propose a MV service at load levels for which their LV networks are marginally adequate. An international voltage standard for 3-phase 4-wire LV systems is recommended by the IEC 60038 to be 230/400 V 1.1 Low-voltage consumers In Europe, the transition period on the voltage tolerance to “230V/400V + 10% / - 10%” has been extended for another 5 years up to the year 2008. Low-voltage consumers are, by definition, those consumers whose loads can be satisfactorily supplied from the low-voltage system in their locality. The voltage of the local LV network may be 120/208 V or 240/415 V, i.e. the lower or upper extremes of the most common 3-phase levels in general use, or at some intermediate level, as shown in Figure C1. An international voltage standard for 3-phase 4-wire LV systems is recommended by the IEC 60038 to be 230/400 V. Loads up to 250 kVA can be supplied at LV, but power-supply organizations generally propose a MV service at load levels for which their LV networks are marginally adequate. Country Algeria Frequency & tolerance (Hz & %) 50 220 (k) 50 ± 1.5 Angola 50 Antigua and Barbuda 60 Argentina 50 ± 2 Armenia 50 ± 5 Australia 50 ± 0.1 Austria 50 ± 0.1 230 (k) Azerbaijan 50 ± 0.1 Bahrain 50 ± 0.1 208/120 (a) 240/120 (k) 415/240 (a) 240 (k) Bangladesh 50 ± 2 Barbados 50 ± 6 Belarus 50 Belgium 50 ± 5 Bolivia 50 ± 0.5 230 (k) Botswana Brazil 50 ± 3 60 220 (k) 220 (k) 127 (k) 400/230 (a) 230 (k) 380/220 (a) 220/380 (a) 127/220 (a) Brunei 50 ± 2 230 230 Bulgaria 50 ± 0.1 220 220/240 © Schneider Electric - all rights reserved Afghanistan Domestic (V) Commercial (V) Industrial (V) 380/220 (a) 380/220 (a) 380/220 (a) 220/127 (e) 220 (k) 380/220 (a) 220/127 (a) 380/220 (a) 220 (k) 240 (k) 120 (k) 380/220 (a) 220 (k) 380/220 (a) 220 (k) 415/240 (a) 240 (k) 380/220 (a) 10,000 5,500 6,600 380/220 (a) 380/220 (a) 410/220 (a) 220 (k) 230/115 (j) 115 (k) 380/220 (a) 220 (k) 220/127 (a) 127 (k) 230 (k) 230 (a) 3N, 400 400/230 (a) 120/208 (a) 380/220 (a) 220 (k) 380/220 (a) 220 (k) 415/240 (a) 440/250 (a) 440 (m) 380/230 (a) (b) 230 (k) 208/120 (a) 240/120 (k) 415/240 (a) 240 (k) 410/220 (a) 230/115 (j) 200/115 (a) 220/115 (a) 380/220 (a) 220 (k) 230 (k) 230 (a) 3N, 400 Fig. C1 : Voltage of local LV network and their associated circuit diagrams (continued on next page) Schneider Electric - Electrical installation guide 2009 400/230 (a) 120/208 (a) 380/220 (a) 22,000 11,000 6,600 415/240 440/250 5,000 380/220 (a) 11,000 415/240 (a) 240 (k) 11,000 410/220 (a) 230/400 (g) 230/155 (j) 380/220 (a) 6,600 10,000 11,000 15,000 400/230 (a) 380/220 (a) 13,800 11,200 220/380 (a) 127/220 (a) 11,000 68,000 1,000 690 380 C - Connecion to the LV public distribution network Domestic (V) Commercial (V) Industrial (V) Cambodia Cameroon Canada Frequency & tolerance (Hz & %) 50 ± 1 50 ± 1 60 ± 0.02 220 (k) 220/260 (k) 120/240 (j) 220/300 220/260 (k) 347/600 (a) 480 (f) 240 (f) 120/240 (j) 120/208 (a) Cape Verde Chad Chile China 50 ± 1 50 ± 1 50 ± 0.5 220 220 (k) 220 (k) 220 (k) Colombia 60 ± 1 Congo 50 Croatia 50 Cyprus 50 ± 0.1 400/230 (a) 230 (k) 240 (k) 220 220 (k) 380/220 (a) 380/220 (a) 220 (k) 120/240 (g) 120 (k) 240/120 (j) 120 (k) 400/230 (a) 230 (k) 415/240 220/380 220/380 (a) 7,200/12,500 347/600 (a) 120/208 600 (f) 480 (f) 240 (f) 380/400 380/220 (a) 380/220 (a) 380/220 (a) 220 (k) 13,200 120/240 (g) 380/220 (a) Czech Republic 50 ± 1 230 500 230/400 Denmark Djibouti Dominica Egypt 50 ± 1 50 50 50 ± 0.5 400/230 (a) 230 (k) 380/220 (a) 220 (k) 400/230 (a) 400/230 (a) 400/230 (a) 380/220 (a) 220 (k) Estonia 50 ± 1 Ethiopia 50 ± 2.5 380/220 (a) 220 (k) 220 (k) 380/220 (a) 220 (k) 380/231 (a) Falkland Islands Fidji Islands 50 ± 3 50 ± 2 Finland 50 ± 0.1 230 (k) 415/240 (a) 240 (k) 230 (k) 415/230 (a) 415/240 (a) 240 (k) 400/230 (a) France 50 ± 1 400/230 (a) 230 (a) Gambia Georgia 50 50 ± 0.5 Germany 50 ± 0.3 220 (k) 380/220 (a) 220 (k) 400/230 (a) 230 (k) 400/230 690/400 590/100 220/380 380/220 (a) 220 (k) 400/230 (a) 230 (k) Ghana Gibraltar Greece 50 ± 5 50 ± 1 50 220/240 415/240 (a) 220 (k) 230 220/240 415/240 (a) 6,000 380/220 (a) Granada Hong Kong 50 50 ± 2 230 (k) 220 (k) Hungary Iceland 50 ± 5 50 ± 0.1 220 230 400/230 (a) 380/220 (a) 220 (k) 220 230/400 120/240 (g) 120 (k) 220 (k) Fig. C1 : Voltage of local LV network and their associated circuit diagrams (continued on next page) Schneider Electric - Electrical installation guide 2009 C3 400/230 (a) 11,000 415/240 400,000 220,000 110,000 35,000 22,000 10,000 6,000 3,000 400/230 (a) 400/230 (a) 400/230 (a) 66,000 33,000 20,000 11,000 6,600 380/220 (a) 380/220 (a) 15 000 380/231 (a) 415/230 (a) 11,000 415/240 (a) 690/400 (a) 400/230 (a) 20,000 10,000 230/400 380 380/220 (a) 20,000 10,000 6,000 690/400 400/230 415/240 (a) 415/240 (a) 22,000 20,000 15,000 6,600 400/230 (a) 11,000 386/220 (a) 220/380 230/400 © Schneider Electric - all rights reserved Country 1 Low-voltage utility distribution networks C - Connecion to the LV public distribution network © Schneider Electric - all rights reserved C4 1 Low-voltage utility distribution networks Country Frequency & tolerance (Hz & %) Domestic (V) Commercial (V) Industrial (V) India 50 ± 1.5 440/250 (a) 230 (k) 440/250 (a) 230 (k) Indonesia 50 ± 2 220 (k) 380/220 (a) Iran 50 ± 5 220 (k) 380/220 (a) Iraq 50 220 (k) 380/220 (a) Ireland 50 ± 2 230 (k) 400/230 (a) Israel 50 ± 0.2 400/230 (a) 230 (k) 400/230 (a) 230 (k) Italy 50 ± 0.4 400/230 (a) 230 (k) 400/230 (a) Jamaica 50 ± 1 220/110 (g) (j) 220/110 (g) (j) Japan (east) + 0.1 - 0.3 200/100 (h) 200/100 (h) (up to 50 kW) Jordan 50 380/220 (a) Kazakhstan 50 Kenya Kirghizia 50 50 Korea (North) 60 +0, -5 380/220 (a) 400/230 (k) 380/220 (a) 220 (k) 220/127 (a) 127 (k) 240 (k) 380/220 (a) 220 (k) 220/127 (a) 127 (k) 220 (k) 11,000 400/230 (a) 440/250 (a) 150,000 20,000 380/220 (a) 20,000 11,000 400/231 (a) 380/220 (a) 11,000 6,600 3,000 380/220 (a) 20,000 10,000 400/230 (a) 22,000 12,600 6,300 400/230 (a) 20,000 15,000 10,000 400/230 (a) 4,000 2,300 220/110 (g) 140,000 60,000 20,000 6,000 200/100 (h) 400 (a) Korea (South) Kuwait Laos Lesotho Latvia 60 50 ± 3 50 ± 8 50 ± 0.4 Lebanon Libya 50 50 100 (k) 240 (k) 380/220 (a) 220 (k) 380/220 (a) 220 (k) 220 (k) 230 (k) 127 (k) Lithuania 50 ± 0.5 Luxembourg 50 ± 0.5 380/220 (a) 220 (k) 380/220 (a) 100/200 (j) 415/240 (a) 380/220 (a) 380/220 (a) 380/220 (a) 220 (k) 380/220 (a) 400/230 (a) 220/127 (a) 230 (k) 127 (k) 380/220 (a) 220 (k) 380/220 (a) Macedonia 50 380/220 (a) 220 (k) 380/220 (a) 220 (k) Madagascar 50 220/110 (k) 380/220 (a) 380/220 (a) 220 (k) 380/220 (a) 415/240 (a) 380/220 (a) 220 (k) 415/240 (a) 380/220 (a) 220/380 (a) 13,600 6,800 Fig. C1 : Voltage of local LV network and their associated circuit diagrams (continued on next page) Schneider Electric - Electrical installation guide 2009 415/240 (a) 380/220 (a) 380/220 (a) 380/220 (a) 380/220 (a) 400/230 (a) 220/127 (a) 380/220 (a) 20,000 15,000 5,000 10,000 6,600 380/220 (a) 35,000 5,000 380/220 C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks Country Frequency & tolerance (Hz & %) Domestic (V) Commercial (V) Industrial (V) Malaysia 50 ± 1 415/240 (a) 415/240 (a) Malawi 50 ± 2.5 240 (k) 415 (a) 230 (k) 400 (a) Mali 50 220 (k) 127 (k) Malta Martinique 50 ± 2 50 240 (k) 127 (k) Mauritania Mexico 50 ± 1 60 ± 0.2 230 (k) 127/220 (a) 220 (k) 120 (l) 400 (a) 230 (k) 380/220 (a) 220/127 (a) 220 (k) 127 (k) 415/240 (a) 220/127 (a) 127 (k) 400/230 (a) 127/220 (a) 220 (k) 120 (l) Moldavia 50 380/220 (a) 220 (k) Morocco 50 ± 5 380/220 (a) 220 (k) 220/127 (a) 127 (k) 380/220 (a) 220/110 (a) Mozambique 50 380/220 (a) 380/220 (a) Nepal 50 ± 1 220 (k) Netherlands 50 ± 0.4 230/400 (a) 230 (k) 440/220 (a) 220 (k) 230/400 (a) New Zealand 50 ± 1.5 400/230 (e) (a) 230 (k) Niger 50 ± 1 400/230 (e) (a) 230 (k) 460/230 (e) 230 (k) Nigeria 50 ± 1 230 (k) 220 (k) 400/230 (a) 380/220 (a) Norway 50 ± 2 230/400 230/400 Oman 50 240 (k) Pakistan 50 230 (k) Papua New Guinea 50 ± 2 240 (k) 415/240 (a) 240 (k) 400/230 (a) 230 (k) 415/240 (a) 240 (k) Paraguay 50 ± 0.5 220 (k) Philippines (Rep of the) 60 ± 0.16 110/220 (j) 380/220 (a) 220 (k) 13,800 4,160 2,400 110/220 (h) Poland 50 ± 0.1 230 (k) 400/230 (a) Portugal 50 ± 1 380/220 (a) 220 (k) Qatar 50 ± 0.1 415/240 (k) 15,000 5,000 380/220 (a) 220 (k) 415/240 (a) 380/220 (a) Fig. C1 : Voltage of local LV network and their associated circuit diagrams (continued on next page) Schneider Electric - Electrical installation guide 2009 380/220 (a) 220/127 (a) 415/240 (a) 220/127 (a) 400/230 (a) 13,800 13,200 277/480 (a) 127/220 (b) 380/220 (a) 225,000 150,000 60,000 22,000 20,000 6,000 10,000 11,000 440/220 (a) 25,000 20,000 12,000 10,000 230/400 11,000 400/230 (a) 15,000 380/220 (a) 15,000 11,000 400/230 (a) 380/220 (a) 230/400 690 415/240 (a) 400/230 (a) 22,000 11,000 415/240 (a) 22,000 380/220 (a) 13,800 4,160 2,400 440 (b) 110/220 (h) 1,000 690/400 400/230 (a) 15,000 5,000 380/220 (a) 11,000 415/240 (a) © Schneider Electric - all rights reserved 380/220 (a) C5 C - Connecion to the LV public distribution network © Schneider Electric - all rights reserved C6 1 Low-voltage utility distribution networks Country Frequency & tolerance (Hz & %) Domestic (V) Commercial (V) Industrial (V) Romania 50 ± 0.5 220 (k) 220/380 (a) 220/380 (a) Russia 50 ± 0.2 Rwanda 50 ± 1 380/220 (a) 220 (k) 220 (k) 380/220 (a) 220 (k) 380/220 (a) 20,000 10,000 6,000 220/380 (a) 380/220 (a) Saint Lucia 50 ± 3 240 (k) 415/240 (a) Samoa San Marino 50 ± 1 400/230 230/220 380 Saudi Arabia 60 220/127 (a) 220/127 (a) 380/220 (a) The Solomon Islands Senegal 50 ± 2 50 ± 5 240 220 (a) 127 (k) 415/240 380/220 (a) 220/127 (k) Serbia and Montenegro 50 380/220 (a) 220 (k) 380/220 (a) 220 (k) Seychelles 50 ± 1 400/230 (a) 400/230 (a) Sierra Leone 50 ± 5 230 (k) Singapore 50 400/230 (a) 230 (k) 400/230 (a) 230 (k) 400/230 (a) Slovakia Slovenia 50 ± 0.5 50 ± 0.1 230 220 (k) 230 380/220 (a) Somalia 50 South Africa 50 ± 2.5 230 (k) 220 (k) 110 (k) 433/250 (a) 400/230 (a) 380/220 (a) 220 (k) Spain 50 ± 3 Sri Lanka 50 ± 2 380/220 (a) (e) 220 (k) 220/127 (a) 127 (k) 230 (k) 440/220 (j) 220/110 (j) 230 (k) 11,000 6,600 3,300 433/250 (a) 400/230 (a) 380/220 (a) 380/220 (a) 220/127 (a) (e) Sudan 50 240 (k) Swaziland 50 ± 2.5 230 (k) Sweden 50 ± 0.5 Switzerland 50 ± 2 400/230 (a) 230 (k) 400/230 (a) Syria 50 220 (k) 115 (k) Tadzhikistan 50 380/220 (a) 220 (k) 220/127 (a) 127 (k) 400/230 (a) 230 (k) 415/240 (a) 240 (k) 400/230 (a) 230 (k) 400/230 (a) 230 (k) 400/230 (a) 380/220 (a) 220 (k) 200/115 (a) 380/220 (a) 220 (k) Fig. C1 : Voltage of local LV network and their associated circuit diagrams (continued on next page) Schneider Electric - Electrical installation guide 2009 15,000 6,600 380/220 (a) 11,000 415/240 (a) 15,000 380 11,000 7,200 380/220 (a) 415/240 90,000 30,000 6,600 10,000 6,600 380/220 (a) 11,000 400/230 (a) 11,000 400 22,000 6,600 400/230 (a) 230/400 10,000 6,600 380/220 (a) 440/220 (g) 220/110 (g) 11,000 6,600 3,300 500 (b) 380/220 (a) 15,000 11,000 380/220 (a) 11,000 400/230 (a) 415/240 (a) 11,000 400/230 (a) 6,000 400/230 (a) 20,000 10,000 3,000 1,000 690/500 380/220 (a) 380/220 (a) C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks Country Frequency & tolerance (Hz & %) Domestic (V) Commercial (V) Industrial (V) Tanzania 50 400/230 (a) 400/230 (a) Thailand 50 220 (k) Togo 50 220 (k) 380/220 (a) 220 (k) 380/220 (a) 11,000 400/230 (a) 380/220 (a) Tunisia 50 ± 2 380/220 (a) 220 (k) 380/220 (a) 220 (k) Turkmenistan 50 380/220 (a) 220 (k) Turkey 50 ± 1 380/220 (a) 220 (k) 220/127 (a) 127 (k) 380/220 (a) Uganda + 0.1 240 (k) 415/240 (a) Ukraine + 0.2 / - 1.5 United Arab Emirates 50 ± 1 380/220 (a) 220 (k) 220 (k) United Kingdom (except Northern Ireland) 50 ± 1 230 (k) 380/220 (a) 220 (k) 415/240 (a) 380/220 (a) 220 (k) 400/230 (a) United Kingdom (Including Northern Ireland) United States of America Charlotte (North Carolina) 50 ± 0.4 230 (k) 220 (k) 400/230 (a) 380/220 (a) 60 ± 0.06 120/240 (j) 120/208 (a) 265/460 (a) 120/240 (j) 120/208 (a) United States of America Detroit (Michigan) 60 ± 0.2 120/240 (j) 120/208 (a) 480 (f) 120/240 (h) 120/208 (a) United States of America Los Angeles (California) United States of America Miami (Florida) 60 ± 0.2 120/240 (j) 4,800 120/240 (g) 60 ± 0.3 120/240 (j) 120/208 (a) 120/240 (j) 120/240 (h) 120/208 (a) United States of America New York (New York) 60 120/240 (j) 120/208 (a) 120/240 (j) 120/208 (a) 240 (f) United States of America Pittsburg (Pennsylvania) 60 ± 0.03 120/240 (j) 265/460 (a) 120/240 (j) 120/208 (a) 460 (f) 230 (f) Fig. C1 : Voltage of local LV network and their associated circuit diagrams (continued on next page) Schneider Electric - Electrical installation guide 2009 20,000 5,500 380/220 (a) 30,000 15,000 10,000 380/220 (a) 380/220 (a) 15,000 6,300 380/220 (a) 11,000 415/240 (a) 380/220 (a) 220 (k) 6,600 415/210 (a) 380/220 (a) 22,000 11,000 6,600 3,300 400/230 (a) 400/230 (a) 380/220 (a) 14,400 7,200 2,400 575 (f) 460 (f) 240 (f) 265/460 (a) 120/240 (j) 120/208 (a) 13,200 4,800 4,160 480 (f) 120/240 (h) 120/208 (a) 4,800 120/240 (g) 13,200 2,400 480/277 (a) 120/240 (h) 12,470 4,160 277/480 (a) 480 (f) 13,200 11,500 2,400 265/460 (a) 120/208 (a) 460 (f) 230 (f) © Schneider Electric - all rights reserved 380/220 (a) C7 C - Connecion to the LV public distribution network Country C8 1 Low-voltage utility distribution networks Frequency & tolerance (Hz & %) 60 Domestic (V) Commercial (V) Industrial (V) 120/240 (j) 227/480 (a) 120/240 (j) 120/208 (a) 480 (f) 240 (f) United States of America San Francisco (California) 60 ± 0.08 120/240 (j) 277/480 (a) 120/240 (j) United States of America Toledo (Ohio) 60 ± 0.08 120/240 (j) 120/208 (a) 277/480 (c) 120/240(h) 120/208 (j) Uruguay 50 ± 1 220 (b) (k) 220 (b) (k) Vietnam 50 ± 0.1 220 (k) 380/220 (a) Yemen Zambia Zimbabwe 50 50 ± 2.5 50 250 (k) 220 (k) 225 (k) 440/250 (a) 380/220 (a) 390/225 (a) 19,900 12,000 7,200 2,400 277/480 (a) 120/208 (a) 480 (f) 240 (f) 20,800 12,000 4,160 277/480 (a) 120/240 (g) 12,470 7,200 4,800 4,160 480 (f) 277/480 (a) 120/208 (a) 15,000 6,000 220 (b) 35,000 15,000 10,000 6,000 440/250 (a) 380 (a) 11,000 390/225 (a) United States of America Portland (Oregon) Circuit diagrams (a) Three-phase star; Four-wire: Earthed neutral (f) Three-phase delta: Three-wire (b) Three-phase star: Three-wire (c) Three-phase star; Three-wire: Earthed neutral (g) Three-phase delta; Four-wire: Earthed mid point of one phase (d) Three-phase star; (e) Two-phase star; Four-wire: Three-wire Non-earthed neutral Earthed neutral (h) Three-phase open delta; Four-wire: Earthed mid point of one phase © Schneider Electric - all rights reserved V (j) Single-phase; Three-wire: Earthed mid point (k) Single-phase; Two-wire: Earthed end of phase (l) Single-phase; Two-wire Unearthed Vk (m) Single-wire: Earthed return (swer) Fig. C1 : Voltage of local LV network and their associated circuit diagrams (concluded) Schneider Electric - Electrical installation guide 2009 (i) Three-phase open delta: Earthed junction of phases (n) DC: Three-wire: Unearthed C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks Residential and commercial consumers The function of a LV “mains” distributor is to provide service connections (underground cable or overhead line) to a number of consumers along its route. The current-rating requirements of distributors are estimated from the number of consumers to be connected and an average demand per consumer. C9 The two principal limiting parameters of a distributor are: b The maximum current which it is capable of carrying indefinitely, and b The maximum length of cable which, when carrying its maximum current, will not exceed the statutory voltage-drop limit These constraints mean that the magnitude of loads which utilities are willing to connect to their LV distribution mains, is necessarily restricted. For the range of LV systems mentioned in the second paragraph of this sub-clause (1.1) viz: 120 V single phase to 240/415 V 3-phase, typical maximum permitted loads connected to a LV distributor might(1) be (see Fig. C2): System 120 V 1-phase 2-wire 120/240 V 1-phase 3-wire 120/208 V 3-phase 4-wire 220/380 V 3-phase 4-wire 230/400 V 3-phase 4-wire 240/415 V 3-phase 4-wire Assumed max. permitted current per consumer service 60 A 60 A 60 A 120 A 120 A 120 A kVA 7.2 14.4 22 80 83 86 Fig. C2 : Typical maximum permitted loads connected to a LV distributor Practices vary considerably from one power supply organization to another, and no “standardized” values can be given. Factors to be considered include: b The size of an existing distribution network to which the new load is to be connected b The total load already connected to the distribution network b The location along the distribution network of the proposed new load, i.e. close to the substation, or near the remote end of the distribution network, etc In short, each case must be examined individually. The load levels listed above are adequate for all normal residential consumers, and will be sufficient for the installations of many administrative, commercial and similar buildings. Medium-size and small industrial consumers (with dedicated LV lines direct from a utility supply MV/LV substation) Medium and small industrial consumers can also be satisfactorily supplied at lowvoltage. For loads which exceed the maximum permitted limit for a service from a distributor, a dedicated cable can usually be provided from the LV distribution fuse- (or switch-) board, in the power utility substation. (1) The Figure C2 values shown are indicative only, being (arbitrarily) based on 60 A maximum service currents for the first three systems, since smaller voltage drops are allowed at these lower voltages, for a given percentage statutory limit. The second group of systems is (again, arbitrarily) based on a maximum permitted service current of 120 A. In practice, however: b Large loads (e.g. > 300 kVA) require correspondingly large cables, so that, unless the load centre is close to the substation, this method can be economically unfavourable b Many utilities prefer to supply loads exceeding 200 kVA (this figure varies with different suppliers) at medium voltage For these reasons, dedicated supply lines at LV are generally applied (at 220/380 V to 240/415 V) to a load range of 80 kVA to 250 kVA. Consumers normally supplied at low voltage include: b Residential dwellings b Shops and commercial buildings b Small factories, workshops and filling stations b Restaurants b Farms, etc Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Generaly, the upper load limit which can be supplied by this means is restricted only by the available spare transformer capacity in the substation. C - Connecion to the LV public distribution network In cities and large towns, standardized LV distribution cables form a network through link boxes. Some links are removed, so that C10 each (fused) distributor leaving a substation forms a branched open-ended radial system, as shown in Figure C3 1 Low-voltage utility distribution networks 1.2 LV distribution networks In European countries the standard 3-phase 4-wire distribution voltage level is 230/400 V. Many countries are currently converting their LV systems to the latest IEC standard of 230/400 V nominal (IEC 60038). Medium to large-sized towns and cities have underground cable distribution systems. MV/LV distribution substations, mutually spaced at approximately 500-600 metres, are typically equipped with: b A 3-or 4-way MV switchboard, often made up of incoming and outgoing loadbreak switches forming part of a ring main, and one or two MV circuit-breakers or combined fuse/ load-break switches for the transformer circuits b One or two 1,000 kVA MV/LV transformers b One or two (coupled) 6-or 8-way LV 3-phase 4-wire distribution fuse boards, or moulded-case circuit-breaker boards, control and protect outgoing 4-core distribution cables, generally referred to as “distributors” The output from a transformer is connected to the LV busbars via a load-break switch, or simply through isolating links. In densely-loaded areas, a standard size of distributor is laid to form a network, with (generally) one cable along each pavement and 4-way link boxes located in manholes at street corners, where two cables cross. Recent trends are towards weather-proof cabinets above ground level, either against a wall, or where possible, flush-mounted in the wall. Links are inserted in such a way that distributors form radial circuits from the substation with open-ended branches (see Fig. C3). Where a link box unites a distributor from one substation with that from a neighbouring substation, the phase links are omitted or replaced by fuses, but the neutral link remains in place. 4-way link box HV/LV substation Service cable © Schneider Electric - all rights reserved Phase links removed Fig. C3 : Showing one of several ways in which a LV distribution network may be arranged for radial branched-distributor operation, by removing (phase) links Schneider Electric - Electrical installation guide 2009 C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks This arrangement provides a very flexible system in which a complete substation can be taken out of service, while the area normally supplied from it is fed from link boxes of the surrounding substations. Moreover, short lengths of distributor (between two link boxes) can be isolated for fault-location and repair. In less-densely loaded urban areas a moreeconomic system of tapered radial distribution is commonly used, in which conductors of reduced size are installed as the distance from a substation increases C11 Where the load density requires it, the substations are more closely spaced, and transformers up to 1,500 kVA are sometimes necessary. Other forms of urban LV network, based on free-standing LV distribution pillars, placed above ground at strategic points in the network, are widely used in areas of lower load density. This scheme exploits the principle of tapered radial distributors in which the distribution cable conductor size is reduced as the number of consumers downstream diminish with distance from the substation. In this scheme a number of large-sectioned LV radial feeders from the distribution board in the substation supply the busbars of a distribution pillar, from which smaller distributors supply consumers immediately surrounding the pillar. Distribution in market towns, villages and rural areas generally has, for many years, been based on bare copper conductors supported on wooden, concrete or steel poles, and supplied from pole-mounted or ground-mounted transformers. Improved methods using insulated twisted conductors to form a pole mounted aerial cable are now standard practice in many countries In recent years, LV insulated conductors, twisted to form a two-core or 4-core self supporting cable for overhead use, have been developed, and are considered to be safer and visually more acceptable than bare copper lines. This is particularly so when the conductors are fixed to walls (e.g. under-eaves wiring) where they are hardly noticeable. As a matter of interest, similar principles have been applied at higher voltages, and self supporting “bundled” insulated conductors for MV overhead installations are now available for operation at 24 kV. Where more than one substation supplies a village, arrangements are made at poles on which the LV lines from different substations meet, to interconnect corresponding phases. In Europe, each utility-supply distribution substation is able to supply at LV an area corresponding to a radius of approximately 300 metres from the substation. North and Central American systems of distribution consist of a MV network from which numerous (small) MV/LV transformers each supply one or several consumers, by direct service cable (or line) from the transformer location North and Central American practice differs fundamentally from that in Europe, in that LV networks are practically nonexistent, and 3-phase supplies to premises in residential areas are rare. The distribution is effectively carried out at medium voltage in a way, which again differs from standard European practices. The MV system is, in fact, a 3-phase 4-wire system from which single-phase distribution networks (phase and neutral conductors) supply numerous single-phase transformers, the secondary windings of which are centre-tapped to produce 120/240 V single-phase 3-wire supplies. The central conductors provide the LV neutrals, which, together with the MV neutral conductors, are solidly earthed at intervals along their lengths. Each MV/LV transformer normally supplies one or several premises directly from the transformer position by radial service cable(s) or by overhead line(s). Many other systems exist in these countries, but the one described appears to be the most common. Figure C4 (next page) shows the main features of the two systems. 1.3 The consumer-service connection In the past, an underground cable service or the wall-mounted insulated conductors from an overhead line service, invariably terminated inside the consumer’s premises, where the cable-end sealing box, the utility fuses (inaccessible to the consumer) and meters were installed. A more recent trend is (as far as possible) to locate these service components in a weatherproof housing outside the building. The utility/consumer interface is often at the outgoing terminals of the meter(s) or, in some cases, at the outgoing terminals of the installation main circuit-breaker (depending on local practices) to which connection is made by utility staff, following a satisfactory test and inspection of the installation. A typical arrangement is shown in Figure C5 (next page). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Service components and metering equipment were formerly installed inside a consumer’s building. The modern tendency is to locate these items outside in a weatherproof cabinet C - Connecion to the LV public distribution network C12 1 Low-voltage utility distribution networks For primary voltages > 72.5 kV (see note) primary winding may be: - Delta - Earthed star - Earthed zigzag Depending on the country concerned 13.8 kV / 2.4-4.16 kV N 1 2 Each MV/LV transformer shown represents many similar units 3 Tertiary delta normally (not always) used if the primary winding is not delta 2 3 N 2.4 kV / 120-240 V 1 ph - 3 wire distribution transformer 1 ph MV / 230 V service transformer to isolated consumer(s) (rural supplies) } HV (1) Ph N 1 1 N MV (2) N Resistor replaced by a Petersen coil on O/H line systems in some countries N 2 2 N 3 ph MV / 230/400 V 4-wire distribution transformer 1 2 3 N N N 1 2 3 LV distribution network Main 3 ph and neutral MV distributor (1) 132 kV for example (2) 11 kV for example Note: At primary voltages greater than 72.5 kV in bulk-supply substations, it is common practice in some European countries to use an earthed-star primary winding and a delta secondary winding. The neutral point on the secondary side is then provided by a zigzag earthing reactor, the star point of which is connected to earth through a resistor. Frequently, the earthing reactor has a secondary winding to provide LV 3-phase supplies for the substation. It is then referred to as an “earthing transformer”. Fig. C4 : Widely-used American and European-type systems CB © Schneider Electric - all rights reserved M F A Fig. C5 : Typical service arrangement for TT-earthed systems Schneider Electric - Electrical installation guide 2009 C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks LV consumers are normally supplied according to the TN or TT system, as described in chapters F and G. The installation main circuitbreaker for a TT supply must include a residual current earth-leakage protective device. For a TN service, overcurrent protection by circuitbreaker or switch-fuse is required A MCCB -moulded case circuit-breaker- which incorporates a sensitive residualcurrent earth-fault protective feature is mandatory at the origin of any LV installation forming part of a TT earthing system. The reason for this feature and related leakage-current tripping levels are discussed in Clause 3 of Chapter G. A further reason for this MCCB is that the consumer cannot exceed his (contractual) declared maximum load, since the overload trip setting, which is sealed by the supply authority, will cut off supply above the declared value. Closing and tripping of the MCCB is freely available to the consumer, so that if the MCCB is inadvertently tripped on overload, or due to an appliance fault, supplies can be quickly restored following correction of the anomaly. C13 In view of the inconvenience to both the meter reader and consumer, the location of meters is nowadays generally outside the premises, either: b In a free-standing pillar-type housing as shown in Figures C6 and C7 b In a space inside a building, but with cable termination and supply authority’s fuses located in a flush-mounted weatherproof cabinet accessible from the public way, as shown in Figure C8 next page b For private residential consumers, the equipment shown in the cabinet in Figure C5 is installed in a weatherproof cabinet mounted vertically on a metal frame in the front garden, or flush-mounted in the boundary wall, and accessible to authorized personnel from the pavement. Figure C9 (next page) shows the general arrangement, in which removable fuse links provide the means of isolation M F CB A In this kind of installation it is often necessary to place the main installation circuitbreaker some distance from the point of utilization, e.g. saw-mills, pumping stations, etc. Fig. C6 : Typical rural-type installation CB M A The main installation CB is located in the consumer’s premises in cases where it is set to trip if the declared kVA load demand is exceeded. Fig. C7 : Semi-urban installations (shopping precincts, etc.) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved F C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks C14 M CB F A The service cable terminates in a flushmounted wall cabinet which contains the isolating fuse links, accessible from the public way. This method is preferred for esthetic reasons, when the consumer can provide a suitable metering and mainswitch location. Fig. C8 : Town centre installations Interface Utility Service cable Consumer Installation Isolation by fuse links Meter Meter cabinet Main circuit breaker © Schneider Electric - all rights reserved Fig. C9 : Typical LV service arrangement for residential consumers In the field of electronic metering, techniques have developed which make their use attractive by utilities either for electricity metering and for billing purposes, the liberalisation of the electricity market having increased the needs for more data collection to be returned from the meters. For example electronic metering can also help utilities to understand their customers’ consumption profiles. In the same way, they will be useful for more and more power line communication and radio-frequency applications as well. In this area, prepayment systems are also more and more employed when economically justified. They are based on the fact that for instance consumers having made their payment at vending stations, generate tokens to pass the information concerning this payment on to the meters. For these systems the key issues are security and inter-operability which seem to have been addressed successfully now. The attractiveness of these systems is due to the fact they not only replace the meters but also the billing systems, the reading of meters and the administration of the revenue collection. Schneider Electric - Electrical installation guide 2009 C - Connecion to the LV public distribution network 1 Low-voltage utility distribution networks An adequate level of voltage at the consumers supply-service terminals is essential for satisfactory operation of equipment and appliances. Practical values of current, and resulting voltage drops in a typical LV system, show the importance of maintaining a high Power Factor as a means of reducing voltage drop. 1.4 Quality of supply voltage The quality of the LV network supply voltage in its widest sense implies: b Compliance with statutory limits of magnitude and frequency b Freedom from continual fluctuation within those limits b Uninterrupted power supply, except for scheduled maintenance shutdowns, or as a result of system faults or other emergencies b Preservation of a near-sinusoidal wave form C15 In this Sub-clause the maintenance of voltage magnitude only will be discussed. In most countries, power-supply authorities have a statutory obligation to maintain the level of voltage at the service position of consumers within the limits of ± 5% (or in some cases ± 6% or more-see table C1) of the declared nominal value. Again, IEC and most national standards recommend that LV appliances be designed and tested to perform satisfactorily within the limits of ± 10% of nominal voltage. This leaves a margin, under the worst conditions (of minus 5% at the service position, for example) of 5% allowable voltage drop in the installation wiring. The voltage drops in a typical distribution system occur as follows: the voltage at the MV terminals of a MV/LV transformer is normally maintained within a ± 2% band by the action of automatic onload tapchangers of the transformers at bulk-supply substations, which feed the MV network from a higher-voltage subtransmission system. If the MV/LV transformer is in a location close to a bulk-supply substation, the ± 2% voltage band may be centered on a voltage level which is higher than the nominal MV value. For example, the voltage could be 20.5 kV ± 2% on a 20 kV system. In this case, the MV/LV distribution transformer should have its MV off-circuit tapping switch selected to the + 2.5% tap position. Conversely, at locations remote from bulk supply substations a value of 19.5 kV ± 2% is possible, in which case the off-circuit tapping switch should be selected to the - 5% position. The different levels of voltage in a system are normal, and depend on the system powerflow pattern. Moreover, these voltage differences are the reason for the term “nominal” when referring to the system voltage. Practical application With the MV/LV transformer correctly selected at its off-circuit tapping switch, an unloaded transformer output voltage will be held within a band of ± 2% of its no-load voltage output. To ensure that the transformer can maintain the necessary voltage level when fully loaded, the output voltage at no-load must be as high as possible without exceeding the upper + 5% limit (adopted for this example). In present-day practice, the winding ratios generally give an output voltage of about 104% at no-load(1), when nominal voltage is applied at MV, or is corrected by the tapping switch, as described above. This would result in a voltage band of 102% to 106% in the present case. A typical LV distribution transformer has a short-circuit reactance voltage of 5%. If it is assumed that its resistance voltage is one tenth of this value, then the voltage drop within the transformer when supplying full load at 0.8 power factor lagging, will be: V% drop = R% cos ϕ + X% sin ϕ = 0.5 x 0.8 + 5 x 0.6 = 0.4 + 3 = 3.4% The voltage band at the output terminals of the fully-loaded transformer will therefore be (102 - 3.4) = 98.6% to (106 - 3.4) = 102.6%. This means, in practical terms, that a medium-sized 230/400 V 3-phase 4-wire distribution cable of 240 mm2 copper conductors would be able to supply a total load of 292 kVA at 0.8 PF lagging, distributed evenly over 306 metres of the distributor. Alternatively, the same load at the premises of a single consumer could be supplied at a distance of 153 metres from the transformer, for the same volt-drop, and so on... As a matter of interest, the maximum rating of the cable, based on calculations derived from IEC 60287 (1982) is 290 kVA, and so the 3.6% voltage margin is not unduly restrictive, i.e. the cable can be fully loaded for distances normally required in LV distribution systems. (1) Transformers designed for the 230/400 V IEC standard will have a no-load output of 420 V, i.e. 105% of the nominal voltage Furthermore, 0.8 PF lagging is appropriate to industrial loads. In mixed semiindustrial areas 0.85 is a more common value, while 0.9 is generally used for calculations concerning residential areas, so that the volt-drop noted above may be considered as a “worst case” example. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved The maximum allowable voltage drop along a distributor is therefore 98.6 - 95 = 3.6%. C - Connecion to the LV public distribution network 2 Tariffs and metering No attempt will be made in this guide to discuss particular tariffs, since there appears to be as many different tariff structures around the world as there are utilities. Some tariffs are very complicated in detail but certain elements are basic to all of them and are aimed at encouraging consumers to manage their power consumption in a way which reduces the cost of generation, transmission and distribution. C16 The two predominant ways in which the cost of supplying power to consumers can be reduced, are: b Reduction of power losses in the generation, transmission and distribution of electrical energy. In principle the lowest losses in a power system are attained when all parts of the system operate at unity power factor b Reduction of the peak power demand, while increasing the demand at low-load periods, thereby exploiting the generating plant more fully, and minimizing plant redundancy Reduction of losses Although the ideal condition noted in the first possibility mentioned above cannot be realized in practice, many tariff structures are based partly on kVA demand, as well as on kWh consumed. Since, for a given kW loading, the minimum value of kVA occurs at unity power factor, the consumer can minimize billing costs by taking steps to improve the power factor of the load (as discussed in Chapter L). The kVA demand generally used for tariff purposes is the maximum average kVA demand occurring during each billing period, and is based on average kVA demands, over fixed periods (generally 10, 30 or 60 minute periods) and selecting the highest of these values. The principle is described below in “principle of kVA maximum-demand metering”. Reduction of peak power demand The second aim, i.e. that of reducing peak power demands, while increasing demand at low-load periods, has resulted in tariffs which offer substantial reduction in the cost of energy at: b Certain hours during the 24-hour day b Certain periods of the year The simplest example is that of a residential consumer with a storage-type water heater (or storage-type space heater, etc.). The meter has two digital registers, one of which operates during the day and the other (switched over by a timing device) operates during the night. A contactor, operated by the same timing device, closes the circuit of the water heater, the consumption of which is then indicated on the register to which the cheaper rate applies. The heater can be switched on and off at any time during the day if required, but will then be metered at the normal rate. Large industrial consumers may have 3 or 4 rates which apply at different periods during a 24-hour interval, and a similar number for different periods of the year. In such schemes the ratio of cost per kWh during a period of peak demand for the year, and that for the lowest-load period of the year, may be as much as 10: 1. Meters It will be appreciated that high-quality instruments and devices are necessary to implement this kind of metering, when using classical electro-mechanical equipment. Recent developments in electronic metering and micro-processors, together with remote ripple-control(1) from an utility control centre (to change peak-period timing throughout the year, etc.) are now operational, and facilitate considerably the application of the principles discussed. © Schneider Electric - all rights reserved In most countries, some tariffs, as noted above, are partly based on kVA demand, in addition to the kWh consumption, during the billing periods (often 3-monthly intervals). The maximum demand registered by the meter to be described, is, in fact, a maximum (i.e. the highest) average kVA demand registered for succeeding periods during the billing interval. (1) Ripple control is a system of signalling in which a voice frequency current (commonly at 175 Hz) is injected into the LV mains at appropriate substations. The signal is injected as coded impulses, and relays which are tuned to the signal frequency and which recognize the particular code will operate to initiate a required function. In this way, up to 960 discrete control signals are available. Schneider Electric - Electrical installation guide 2009 2 Tariffs and metering Figure C10 shows a typical kVA demand curve over a period of two hours divided into succeeding periods of 10 minutes. The meter measures the average value of kVA during each of these 10 minute periods. C17 kVA Maximum average value during the 2 hour interval Average values for 10 minute periods t 0 1 2 hrs Fig. C10 : Maximum average value of kVA over an interval of 2 hours Principle of kVA maximum demand metering A kVAh meter is similar in all essentials to a kWh meter but the current and voltage phase relationship has been modified so that it effectively measures kVAh (kilovolt-ampere-hours). Furthermore, instead of having a set of decade counter dials, as in the case of a conventional kWh meter, this instrument has a rotating pointer. When the pointer turns it is measuring kVAh and pushing a red indicator before it. At the end of 10 minutes the pointer will have moved part way round the dial (it is designed so that it can never complete one revolution in 10 minutes) and is then electrically reset to the zero position, to start another 10 minute period. The red indicator remains at the position reached by the measuring pointer, and that position, corresponds to the number of kVAh (kilo-volt-ampere-hours) taken by the load in 10 minutes. Instead of the dial being marked in kVAh at that point however it can be marked in units of average kVA. The following figures will clarify the matter. Supposing the point at which the red indicator reached corresponds to 5 kVAh. It is known that a varying amount of kVA of apparent power has been flowing for 10 minutes, i.e. 1/6 hour. If now, the 5 kVAh is divided by the number of hours, then the average kVA for the period is obtained. In this case the average kVA for the period will be: 1 5x = 5 x 6 = 30 kVA 1 6 Every point around the dial will be similarly marked i.e. the figure for average kVA will be 6 times greater than the kVAh value at any given point. Similar reasoning can be applied to any other reset-time interval. At the end of the billing period, the red indicator will be at the maximum of all the average values occurring in the billing period. The red indicator will be reset to zero at the beginning of each billing period. Electromechanical meters of the kind described are rapidly being replaced by electronic instruments. The basic measuring principles on which these electronic meters depend however, are the same as those described above. © Schneider Electric - all rights reserved C - Connecion to the LV public distribution network Schneider Electric - Electrical installation guide 2009 Chapter D MV & LV architecture selection guide Contents 1 2 3 D3 Simplified architecture design process D4 2.1 The architecture design 2.2 The whole process D4 D5 Electrical installation characteristics D7 3.1 Activity 3.2 Site topology 3.3 Layout latitude 3.4 Service reliability 3.5 Maintainability 3.6 Installation lexibility 3.7 Power demand 3.8 Load distribution 3.9 Power interruption sensitivity 3.10 Disturbance sensitivity 3.11 Disturbance capability of circuits 3.12 Other considerations or constraints D7 D7 D7 D8 D8 D8 D8 D9 D9 D9 D10 D10 4 Technological characteristics D11 4.1 Environment, atmosphere 4.2 Service Index 4.3 Other considerations D11 D11 D12 5 Architecture assessment criteria D13 5.1 On-site work time 5.2 Environmental impact 5.3 Preventive maintenance level 5.4 Availability of electrical power supply D13 D13 D13 D14 6 Choice of architecture fundamentals D15 6.1 Connection to the upstream network 6.2 MV circuit coniguration 6.3 Number and distribution of MV/LV transformation substations 6.4 Number of MV/LV transformers 6.5 MV back-up generator D15 D16 D17 D18 D18 7 Choice of architecture details D19 7.1 Layout 7.2 Centralized or distributed layout 7.3 Presence of an Uninterruptible Power Supply (UPS) 7.4 Coniguration of LV circuits D19 D20 D22 D22 8 Choice of equiment D24 D1 © Schneider Electric - all rights reserved Stakes for the user Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide Recommendations for architecture optimization D26 9.1 On-site work time 9.2 Environmental impact 9.3 Preventive maintenance volume 9.4 Electrical power availability D26 D26 D28 D28 10 11 12 Glossary D29 ID-Spec software D30 Example: electrical installation in a printworks D31 12.1 Brief description 12.2 Installation characteristics 12.3 Technological characteristics 12.4 Architecture assessment criteria 12.5 Choice of technogical solutions D31 D31 D31 D32 D34 © Schneider Electric - all rights reserved D2 9 Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 1 Stakes for the user Choice of distribution architecture The choice of distribution architecture has a decisive impact on installation performance throughout its lifecycle: b right from the construction phase, choices can greatly inluence the installation time, possibilities of work rate, required competencies of installation teams, etc. b there will also be an impact on performance during the operation phase in terms of quality and continuity of power supply to sensitive loads, power losses in power supply circuits, b and lastly, there will be an impact on the proportion of the installation that can be recycled in the end-of-life phase. D3 The Electrical Distribution architecture of an installation involves the spatial coniguration, the choice of power sources, the deinition of different distribution levels, the single-line diagram and the choice of equipment. The choice of the best architecture is often expressed in terms of seeking a compromise between the various performance criteria that interest the customer who will use the installation at different phases in its lifecycle. The earlier we search for solutions, the more optimization possibilities exist (see Fig. D1). Potential for optimization Ecodial Preliminary design ID-Spec Detailled design Installation Exploitation A successful search for an optimal solution is also strongly linked to the ability for exchange between the various players involved in designing the various sections of a project: b the architect who deines the organization of the building according to user requirements, b the designers of different technical sections (lighting, heating, air conditioning, luids, etc.), b the user’s representatives e.g. deining the process. The following paragraphs present the selection criteria as well as the architecture design process to meet the project performance criteria in the context of industrial and tertiary buildings (excluding large sites). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. D1 : Optimization potential D - MV & LV architecture selection guide 2 Simplified architecture design process 2.1 The architecture design The architecture design considered in this document is positioned at the Draft Design stage. It generally covers the levels of MV/LV main distribution, LV power distribution, and exceptionally the terminal distribution level. (see Fig. D2). D4 MV/LV main distribution LV power distribution LV terminal distribution M M M M Fig. D2 : Example of single-line diagram © Schneider Electric - all rights reserved The design of an electrical distribution architecture can be described by a 3-stage process, with iterative possibilities. This process is based on taking account of the installation characteristics and criteria to be satisied. Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 2 Simplified architecture design process 2.2 The whole process The whole process is described briely in the following paragraphs and illustrated on Figure D3. The process described in this document is not intended as the only solution. This document is a guide intended for the use of electrical installation designers. D5 Data See § 3 Step Installation characteristics Deliverable See § 6 Step 1 Choice of fundamentals Schematic diagram See § 7 Step 2 Choice of architecturedetails Detailed diagram See § 4 Technological characteristics See § 8 Step 3 Choice of equipment Techno. Solution See § 5 Assessment criteria See § 9 ASSESSMENT Optimisation recommendations Definitive solution Fig. D3 : Flow diagram for choosing the electrical distribution architecture This involves deining the general features of the electrical installation. It is based on taking account of macroscopic characteristics concerning the installation and its usage. These characteristics have an impact on the connection to the upstream network, MV circuits, the number of transformer substations, etc. At the end of this step, we have several distribution schematic diagram solutions, which are used as a starting point for the single-line diagram. The deinitive choice is conirmed at the end of the step 2. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Step 1: Choice of distribution architecture fundamentals D - MV & LV architecture selection guide 2 Simplified architecture design process Step 2: choice of architecture details This involves deining the electrical installation in more detail. It is based on the results of the previous step, as well as on satisfying criteria relative to implementation and operation of the installation. The process loops back into step1 if the criteria are not satisied. An iterative process allows several assessment criteria combinations to be analyzed. At the end of this step, we have a detailed single-line diagram. D6 Step 3: choice of equipment The choice of equipment to be implemented is carried out in this stage, and results from the choice of architecture. The choices are made from the manufacturer catalogues, in order to satisfy certain criteria. This stage is looped back into step 2 if the characteristics are not satisied. Assessment © Schneider Electric - all rights reserved This assessment step allows the Engineering Ofice to have igures as a basis for discussions with the customer and other players. According to the result of these discussions, it may be possible to loop back into step 1. Schneider Electric - Electrical installation guide 2009 3 Electrical installation characteristics These are the main installation characteristics enabling the deining of the fundamentals and details of the electrical distribution architecture. For each of these characteristics, we supply a deinition and the different categories or possible values. 3.1 Activity Definition: D7 Main economic activity carried out on the site. Indicative list of sectors considered for industrial buildings: b Manufacturing b Food & Beverage b Logistics Indicative list of sectors considered for tertiary buildings: b Ofices buildings b Hypermarkets b Shopping malls 3.2 Site topology Definition: Architectural characteristic of the building(s), taking account of the number of buildings, number of loors, and of the surface area of each loor. Different categories: b Single storey building, b Multi-storey building, b Multi-building site, b High-rise building. 3.3 Layout latitude Definition: Characteristic taking account of constraints in terms of the layout of the electrical equipment in the building: b aesthetics, b accessibility, b presence of dedicated locations, b use of technical corridors (per loor), b use of technical ducts (vertical). Different categories: b Low: the position of the electrical equipment is virtually imposed b Medium: the position of the electrical equipment is partially imposed, to the detriment of the criteria to be satisied b High: no constraints. The position of the electrical equipment can be deined to best satisfy the criteria. © Schneider Electric - all rights reserved D - MV & LV architecture selection guide Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 3 Electrical installation characteristics 3.4 Service reliability Definition: The ability of a power system to meet its supply function under stated conditions for a speciied period of time. Different categories: D8 b Minimum: this level of service reliability implies risk of interruptions related to constraints that are geographical (separate network, area distant from power production centers), technical (overhead line, poorly meshed system), or economic (insuficient maintenance, under-dimensioned generation). b Standard b Enhanced: this level of service reliability can be obtained by special measures taken to reduce the probability of interruption (underground network, strong meshing, etc.) 3.5 Maintainability Definition: Features input during design to limit the impact of maintenance actions on the operation of the whole or part of the installation. Different categories: b Minimum: the installation must be stopped to carry out maintenance operations. b Standard: maintenance operations can be carried out during installation operations, but with deteriorated performance. These operations must be preferably scheduled during periods of low activity. Example: several transformers with partial redundancy and load shedding. b Enhanced: special measures are taken to allow maintenance operations without disturbing the installation operations. Example: double-ended coniguration. 3.6 Installation flexibility Definition: Possibility of easily moving electricity delivery points within the installation, or to easily increase the power supplied at certain points. Flexibility is a criterion which also appears due to the uncertainty of the building during the pre-project summary stage. Different categories: © Schneider Electric - all rights reserved b No lexibility: the position of loads is ixed throughout the lifecycle, due to the high constraints related to the building construction or the high weight of the supplied process. E.g.: smelting works. b Flexibility of design: the number of delivery points, the power of loads or their location are not precisely known. b Implementation lexibility: the loads can be installed after the installation is commissioned. b Operating lexibility: the position of loads will luctuate, according to process reorganization. Examples: v industrial building: extension, splitting and changing usage v ofice building: splitting Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 3 Electrical installation characteristics 3.7 Power demand Definition: The sum of the apparent load power (in kVA), to which is applied a usage coeficient. This represents the maximum power which can be consumed at a given time for the installation, with the possibility of limited overloads that are of short duration. Signiicant power ranges correspond to the transformer power limits most commonly used: b < 630kVA b from 630 to 1250kVA b from 1250 to 2500kVA b > 2500kVA D9 3.8 Load distribution Definition: A characteristic related to the uniformity of load distribution (in kVA / m²) over an area or throughout the building. Different categories: b Uniform distribution: the loads are generally of an average or low unit power and spread throughout the surface area or over a large area of the building (uniform density). E.g.: lighting, individual workstations b intermediate distribution: the loads are generally of medium power, placed in groups over the whole building surface area E.g.: machines for assembly, conveying, workstations, modular logistics “sites” b localized loads: the loads are generally high power and localized in several areas of the building (non-uniform density). E.g.: HVAC 3.9 Power Interruption Sensitivity Definition: The aptitude of a circuit to accept a power interruption. Different categories: b “Sheddable” circuit: possible to shut down at any time for an indeinite duration b Long interruption acceptable: interruption time > 3 minutes * b Short interruption acceptable: interruption time < 3 minutes * b No interruption acceptable. This is expressed in terms of the criticality of supplying of loads or circuits. b Non-critical: The load or the circuit can be “shed” at any time. E.g.: sanitary water heating circuit. b Low criticality: A power interruption causes temporary discomfort for the occupants of a building, without any inancial consequences. Prolonging of the interruption beyond the critical time can cause a loss of production or lower productivity. E.g.: heating, ventilation and air conditioning circuits (HVAC). b Medium criticality A power interruption causes a short break in process or service. Prolonging of the interruption beyond a critical time can cause a deterioration of the production facilities or a cost of starting for starting back up. E.g.: refrigerated units, lifts. b High criticality Any power interruption causes mortal danger or unacceptable inancial losses. E.g.: operating theatre, IT department, security department. * indicative value, supplied by standard EN50160: “Characteristics of the voltage supplied by public distribution networks”. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved We can distinguish various levels of severity of an electrical power interruption, according to the possible consequences: b No notable consequence, b Loss of production, b Deterioration of the production facilities or loss of sensitive data, b Causing mortal danger. D - MV & LV architecture selection guide 3 Electrical installation characteristics 3.10 Disturbance sensitivity Definition The ability of a circuit to work correctly in presence of an electrical power disturbance. D10 A disturbance can lead to varying degrees of malfunctioning. E.g.: stopping working, incorrect working, accelerated ageing, increase of losses, etc Types of disturbances with an impact on circuit operations: b brown-outs, b overvoltages b voltage distortion, b voltage luctuation, b voltage imbalance. Different categories: b low sensitivity: disturbances in supply voltages have very little effect on operations. E.g.: heating device. b medium sensitivity: voltage disturbances cause a notable deterioration in operations. E.g.: motors, lighting. b high sensitivity: voltage disturbances can cause operation stoppages or even the deterioration of the supplied equipment. E.g.: IT equipment. The sensitivity of circuits to disturbances determines the design of shared or dedicated power circuits. Indeed it is better to separate “sensitive” loads from “disturbing” loads. E.g.: separating lighting circuits from motor supply circuits. This choice also depends on operating features. E.g.: separate power supply of lighting circuits to enable measurement of power consumption. 3.11 Disturbance capability of circuits Definition The ability of a circuit to disturb the operation of surrounding circuits due to phenomena such as: harmonics, in-rush current, imbalance, High Frequency currents, electromagnetic radiation, etc. Different categories b Non disturbing: no speciic precaution to take b moderate or occasional disturbance: separate power supply may be necessary in the presence of medium or high sensitivity circuits. E.g.: lighting circuit generating harmonic currents. b Very disturbing: a dedicated power circuit or ways of attenuating disturbances are essential for the correct functioning of the installation. E.g.: electrical motor with a strong start-up current, welding equipment with luctuating current. © Schneider Electric - all rights reserved 3.12 Other considerations or constraints b Environment E.g.: lightning classiication, sun exposure b Speciic rules E.g.: hospitals, high rise buildings, etc. b Rule of the Energy Distributor Example: limits of connection power for LV, access to MV substation, etc b Attachment loads Loads attached to 2 independent circuits for reasons of redundancy. b Designer experience Consistency with previous designs or partial usage of previous designs, standardization of sub-assemblies, existence of an installed equipment base. b Load power supply constraints Voltage level (230V, 400V, 690V), voltage system (single-phase, three-phase with or without neutral, etc) Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 4 Technological characteristics The technological solutions considered concern the various types of MV and LV equipment, as well as Busbar Trunking Systems . The choice of technological solutions is made following the choice of single-line diagram and according to characteristics given below. 4.1 Environment, atmosphere A notion taking account of all of the environmental constraints (average ambient temperature, altitude, humidity, corrosion, dust, impact, etc.) and bringing together protection indexes IP and IK. Different categories: b Standard: no particular environmental constraints b Enhanced: severe environment, several environmental parameters generate important constraints for the installed equipment b Speciic: atypical environment, requiring special enhancements D11 4.2 Service Index The service index (IS) is a value that allows us to characterize an LV switchboard according to user requirements in terms of operation, maintenance, and scalability. The different index values are indicated in the following table (Fig D4): Operation Maintenance Upgrade Level 1 IS = 1 • • Operation may lead to complete stoppage of the switchboard IS = • 1 • Operation may lead to complete stoppage of the switchboard IS = • • 1 Operation may lead to complete stoppage of the switchboard Level 2 IS = 2 • • Operation may lead to stoppage of only the functional unit IS = • 2 • Operation may lead to stoppage of only the functional unit, with work on connections IS = • • 2 Operation may lead to stoppage of only the functional unit, with functional units provided for back-up Level 3 IS = 3 • • Operation may lead to stoppage of the power of the functional unit only IS = • 3 • Operation may lead to stoppage of only the functional unit, without work on connections IS = • • 3 Operation may lead to stoppage of only the functional unit, with total freedom in terms of upgrade Fig. D4 : Different index values b Examples of an operation event: turning off a circuit-breaker, switching operation to energize/de-energize a machine b Example of a maintenance operation: tightening connections b Example of an upgrade operation: connecting an additional feeder IS Operation Maintenance Upgrade 111 Switching off the whole switchboard Working time > 1h, with total nonavailability Extension not planned Working time between 1/4h and 1h, with work on connections Possible adding of functional units without stopping the switchboard 211 223 232 Individually switching off the functional unit and re-commissioning < 1h Possible adding of functional units with stopping the switchboard 233 Working time between 1/4h and 1h, without work on connections 332 333 Individually switching off the functional unit and re-commissioning < 1/4h Fig. D5 : Relevant service indices (IS) Schneider Electric - Electrical installation guide 2009 Possible adding of functional units without stopping the switchboard Possible adding of functional units with stopping the switchboard Possible adding of functional units without stopping the switchboard © Schneider Electric - all rights reserved There are a limited number of relevant service indices (see Fig. D5) D - MV & LV architecture selection guide 4 Technological characteristics The types of electrical connections of functional units can be denoted by a threeletter code: b The irst letter denotes the type of electrical connection of the main incoming circuit, b The second letter denotes the type of electrical connection of the main outgoing circuit, b The third letter denotes the type of electrical connection of the auxiliary circuits. The following letters are used: b F for ixed connections, b D for disconnectable connections, b W for withdrawable connections. D12 Service ratings are related to other mechanical parameters, such as the Protection Index (IP), form of internal separations, the type of connection of functional units or switchgear (Fig. D6): Service rating Protection index IP Form Functional Unit Withdrawability 111 2XX 1 FFF 211 2XB 1 FFF 223 2XB 3b WFD 232 2XB 3b WFW 233 2XB 3b WWW 332 2XB 3b WWW 333 2XB 3b WWW Fig. D6 : Correspondence between service index and other mechanical parameters Technological examples are given in chapter E2. b Deinition of the protection index: see IEC 60529: “Degree of protection given by enclosures (IP code)”, b Deinitions of the form and withdrawability: see IEC 60439-1: “Low-voltage switchgear and controlgear assemblies; part 1: type-tested and partially type-tested assemblies”. 4.3 Other considerations Other considerations have an impact on the choice of technological solutions: b Designer experience, b Consistency with past designs or the partial use of past designs, b Standardization of sub-assemblies, b The existence of an installed equipment base, b Utilities requirements, b Technical criteria: target power factor, backed-up load power, presence of harmonic generators… © Schneider Electric - all rights reserved These considerations should be taken into account during the detailed electrical deinition phase following the draft design stage. Schneider Electric - Electrical installation guide 2009 5 Architecture assessment criteria Certain decisive criteria are assessed at the end of the 3 stages in deining architecture, in order to validate the architecture choice. These criteria are listed below with the different allocated levels of priority. 5.1 On-site work time Time for implementing the electrical equipment on the site. D13 Different levels of priority: b Secondary: the on-site work time can be extended, if this gives a reduction in overall installation costs, b Special: the on-site work time must be minimized, without generating any signiicant excess cost, b Critical: the on-site work time must be reduced as far as possible, imperatively, even if this generates a higher total installation cost, 5.2 Environmental impact Taking into consideration environmental constraints in the installation design. This takes account of: consumption of natural resources, Joule losses (related to CO2 emission), “recyclability” potential, throughout the installation’s lifecycle. Different levels of priority: b Non signiicant: environmental constraints are not given any special consideration, b Minimal: the installation is designed with minimum regulatory requirements, b Proactive: the installation is designed with a speciic concern for protecting the environment. Excess cost is allowed in this situation. E.g.: using low-loss transformers. The environmental impact of an installation will be determined according to the method carrying out an installation lifecycle analysis, in which we distinguish between the following 3 phases: b manufacture, b operation, b end of life (dismantling, recycling). In terms of environmental impact, 3 indicators (at least) can be taken into account and inluenced by the design of an electrical installation. Although each lifecycle phase contributes to the three indicators, each of these indicators is mainly related to one phase in particular: b consumption of natural resources mainly has an impact on the manufacturing phase, b consumption of energy has an impact on the operation phase, b “recycleability” potential has an impact on the end of life. The following table details the contributing factors to the 3 environmental indicators (Fig D7). Indicators Contributors Natural resources consumption Mass and type of materials used Power consumption Joule losses at full load and no load «Recyclability» potential Mass and type of material used Fig D7 : Contributing factors to the 3 environmental indicators © Schneider Electric - all rights reserved D - MV & LV architecture selection guide Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 5 Architecture assessment criteria 5.3 Preventive maintenance level Definition: Number of hours and sophistication of maintenance carried out during operations in conformity with manufacturer recommendations to ensure dependable operation of the installation and the maintaining of performance levels (avoiding failure: tripping, down time, etc). D14 Different categories: b Standard: according to manufacturer recommendations. b Enhanced: according to manufacturer recommendations, with a severe environment, b Speciic: speciic maintenance plan, meeting high requirements for continuity of service, and requiring a high level of maintenance staff competency. 5.4 Availability of electrical power supply Definition: This is the probability that an electrical installation be capable of supplying quality power in conformity with the speciications of the equipment it is supplying. This is expressed by an availability level: Availability (%) = (1 - MTTR/ MTBF) x 100 MTTR (Mean Time To Repair): the average time to make the electrical system once again operational following a failure (this includes detection of the reason for failure, its repair and re-commissioning), MTBF (Mean Time Between Failure): measurement of the average time for which the electrical system is operational and therefore enables correct operation of the application. The different availability categories can only be deined for a given type of installation. E.g.: hospitals, data centers. Example of classification used in data centers: © Schneider Electric - all rights reserved Tier 1: the power supply and air conditioning are provided by one single channel, without redundancy, which allows availability of 99.671%, Tier 2: the power supply and air conditioning are provided by one single channel, with redundancy, which allows availability of 99.741%, Tier 3: the power supply and air conditioning are provided by several channels, with one single redundant channel, which allows availability of 99.982%, Tier 4: the power supply and air conditioning are provided by several channels, with redundancy, which allows availability of 99.995%. Schneider Electric - Electrical installation guide 2009 6 Choice of architecture fundamentals The single-line diagram can be broken down into different key parts, which are determined throughout a process in 2 successive stages. During the irst stage we make the following choices: b connection to the utilities network, b coniguration of MV circuits, b number of power transformers, b number and distribution of transformation substations, b MV back-up generator D15 6.1 Connection to the upstream network The main conigurations for possible connection are as follows (see Fig. D8 for MV service): b LV service, b MV single-line service, b MV ring-main service, b MV duplicate supply service, b MV duplicate supply service with double busbar. Metering, protection, disconnection devices, located in the delivery substations are not represented on the following diagrams. They are often speciic to each utilities company and do not have an inluence on the choice of installation architecture. For each connection, one single transformer is shown for simpliication purposes, but in the practice, several transformers can be connected. (MLVS: Main Low Voltage Switchboard) a) Single-line: b) Ring-main: MV MV LV LV MLVS MLVS c) Duplicate supply: d) Double busbar with duplicate supply: MV MV MV LV LV LV MLVS Fig. D8 : MV connection to the utilities network Schneider Electric - Electrical installation guide 2009 MLVS1 MLVS2 © Schneider Electric - all rights reserved D - MV & LV architecture selection guide D - MV & LV architecture selection guide 6 Choice of architecture fundamentals For the different possible conigurations, the most probable and usual set of characteristics is given in the following table: Configuration LV D16 MV Characteristic to consider Simple-line Ring-main Duplicate supply Duplicate supply with double busbars Activity Any Any Any Hi-tech, sensitive ofice, health-care Any Site topology Single building Single building Single building Single building Several buildings Service reliability Minimal Minimal Standard Enhanced Enhanced Power demand < 630kVA ≤ 1250kVA ≤ 2500kVA > 2500kVA > 2500kVA Other connection constraints Any Isolated site Low density urban area High density urban area Urban area with utility constraint 6.2 MV circuit configuration The main possible connection conigurations are as follows (Fig. D9): b single feeder, one or several transformers b open ring, one MV incomer b open ring, 2 MV incomers The basic coniguration is a radial single-feeder architecture, with one single transformer. In the case of using several transformers, no ring is realised unless all of the transformers are located in a same substation. Closed-ring coniguration is not taken into account. a) Single feeder: b) Open ring, 1 MV substation: c) Open ring, 2 MV substations: MV MV MV MV MV MV MV MV LV LV LV LV LV LV LV LV MLVS 1 MLVS n MLVS 1 MLVS 2 MLVS n © Schneider Electric - all rights reserved Fig. D9 : MV circuit configuration Schneider Electric - Electrical installation guide 2009 MLVS 1 MLVS 2 MLVS n 6 Choice of architecture fundamentals For the different possible conigurations, the most probable and usual set of characteristics is given in the table on Fig D10. MV circuit configuration Characteristic to consider Single feeder Open ring 1 MV substation Open ring 2 MV substations Site topology Any < 25000m² Building with one level or several buildings ≤ 25000m² Several buildings ≥ 25000m² Maintainability Minimal or standard Enhanced Enhanced Power demand Any > 1250kVA > 2500kVA Disturbance sensitivity Long interruption acceptable Short interruption acceptable Short interruption acceptable D17 Fig. D10 : Typical values of the installation characteristics Another exceptional coniguration: power supply by 2 MV substations and connection of the transformers to each of these 2 substations (MV “double ended” connection). 6.3 Number and distribution of MV/LV transformation substations Main characteristics to consider to determine the transformation substations: b Surface area of building or site b Power demand, (to be compared with standardized transformer power), b Load distribution The preferred basic coniguration comprises one single substation. Certain factors contribute to increasing the number of substations (> 1): b A large surface area (> 25000m²), b The site coniguration: several buildings, b Total power > 2500kVA, b Sensitivity to interruption: need for redundancy in the case of a ire. Configuration Characteristic to consider 1 substation with N transformers N substations N transformers (identical substations) Building coniguration < 25000m² Power demand < 2500kVA ≥ 2500kVA ≥ 2500kVA Load distribution Localized loads Uniform distribution Medium density ≥ 25000m² 1 building with several loors N substations M transformers (different powers) ≥ 25000m² several buildings Fig. D11 : Typical characteristics of the different configurations © Schneider Electric - all rights reserved D - MV & LV architecture selection guide Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 6 Choice of architecture fundamentals 6.4 Number of MV/LV transformers D18 Main characteristics to consider to determine the number of transformers: b Surface of building or site b Total power of the installed loads b Sensitivity of circuits to power interruptions b Sensitivity of circuits to disturbances b Installation scalability The basic preferred coniguration comprises a single transformer supplying the total power of the installed loads. Certain factors contribute to increasing the number of transformers (> 1), preferably of equal power: b A high total installed power (> 1250kVA): practical limit of unit power (standardization, ease of replacement, space requirement, etc), b A large surface area (> 5000m²): the setting up of several transformers as close as possible to the distributed loads allows the length of LV trunking to be reduced b A need for partial redundancy (down-graded operation possible in the case of a transformer failure) or total redundancy (normal operation ensured in the case a transformer failure) b Separating of sensitive and disturbing loads (e.g.: IT, motors) 6.5 MV back-up generator Main characteristics to consider for the implementation of an MV back-up generator: b Site activity b Total power of the installed loads b Sensitivity of circuits to power interruptions b Availability of the public distribution network The preferred basic coniguration does not include an MV generator. Certain factors contribute to installing an MV generator: b Site activity: process with co-generation, optimizing the energy bill, b Low availability of the public distribution network. © Schneider Electric - all rights reserved Installation of a back-up generator can also be carried out at LV level. Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 7 Choice of architecture details This is the second stage in designing of the electrical installation. During this stage we carry out the following choices are carried out: b Layout, b Centralized or decentralized distribution, b Presence of back-up generators, b Presence of uninterruptible power supplies, b Coniguration of LV circuits, b Architecture combinations. D19 7.1 Layout Position of the main MV and LV equipment on the site or in the building. This layout choice is applied to the results of stage 1. Selection guide: b Place power sources as close as possible to the barycenter of power consumers, b Reduce atmospheric constraints: building dedicated premises if the layout in the workshop is too restrictive (temperature, vibrations, dust, etc.), b Placing heavy equipment (transformers, generators, etc) close to walls or main exists for ease of maintenance, A layout example is given in the following diagram (Fig. D12): Global current consumer Barycenter Finishing Panel shop Office Painting © Schneider Electric - all rights reserved Fig. D12 : The position of the global current consumer barycenter guides the positioning of power sources Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 7 Choice of architecture details 7.2 Centralized or distributed layout In centralized layout, current consumers are connected to the power sources by a star-connection. Cables are suitable for centralized layout, with point to point links between the MLVS and current consumers or sub-distribution boards (radial distribution, star- distribution) (Fig. D13): D20 Fig. D13: Example of centralized layout with point to point links In decentralized layout, current consumers are connected to sources via a busway. Busbar trunking systems are well suited to decentralized layout, to supply many loads that are spread out, making it easy to change, move or add connections (Fig D14): Fig. D14 : Example of decentralized layout, with busbar trunking links © Schneider Electric - all rights reserved Factors in favour of centralized layout (see summary table in Fig. D15): b Installation lexibility: no, b Load distribution: localized loads (high unit power loads). Factors in favor of decentralized layout: b Installation lexibility: "Implementation" lexibility (moving of workstations, etc…), b Load distribution: uniform distribution of low unit power loads Schneider Electric - Electrical installation guide 2009 7 Choice of architecture details Load distribution Flexibility Localized loads Intermediate distribution Uniform distributed No flexibility Centralized Design flexibility Implementation flexibility Decentralized Centralized Decentralized D21 Operation flexibility Fig. D15 : Recommendations for centralized or decentralized layout Power supply by cables gives greater independence of circuits (lighting, power sockets, HVAC, motors, auxiliaries, security, etc), reducing the consequences of a fault from the point of view of power availability. The use of busbar trunking systems allows load power circuits to be combined and saves on conductors by taking advantage of a clustering coeficient. The choice between cable and busbar trunking, according to the clustering coeficient, allows us to ind an economic optimum between investment costs, implementation costs and operating costs. These two distribution modes are often combined. Presence of back-up generators (Fig. D16) Here we only consider LV back-up generators. The electrical power supply supplied by a back-up generator is produced by an alternator, driven by a thermal engine. No power can be produced until the generator has reached its rated speed. This type of device is therefore not suitable for an uninterrupted power supply. According to the generator’s capacity to supply power to all or only part of the installation, there is either total or partial redundancy. A back-up generator functions generally disconnected from the network. A source switching system is therefore necessary. The generator can function permanently or intermittently. Its back-up time depends on the quantity of available fuel. G LV switchboard Fig. D16 : Connection of a back-up generator The main characteristics to consider for implementing LV back-up generator: b Sensitivity of loads to power interruption, b Availability of the public distribution network, b Other constraints (e.g.: generators compulsory in hospitals or high-vise buildings) The presence of generators can be decided to reduce the energy bill or due to the opportunity for co-generation. These two aspects are not taken into account in this guide. The presence of a back-up generator is essential if the loads cannot be shed for an indeinite duration (long interruption only acceptable) or if the utility network availability is low. Determining the number of back-up generator units is in line with the same criteria as determining the number of transformers, as well as taking account of economic and availability considerations (redundancy, start-up reliability, maintenance facility). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved D - MV & LV architecture selection guide D - MV & LV architecture selection guide 7 Choice of architecture details 7.3 Presence of an Uninterruptible Power Supply (UPS) The electrical power from a UPS is supplied from a storage unit: batteries or inertia wheel. This system allows us to avoid any power failure. The back-up time of the system is limited: from several minutes to several hours. The simultaneous presence of a back-up generator and a UPS unit is used for permanently supply loads for which no failure is acceptable (Fig. D17). The back-up time of the battery or the inertia wheel must be compatible with the maximum time for the generator to start up and be brought on-line. A UPS unit is also used for supply power to loads that are sensitive to disturbances (generating a “clean” voltage that is independent of the network). D22 Main characteristics to be considered for implementing a UPS: b Sensitivity of loads to power interruptions, b Sensitivity of loads to disturbances. The presence of a UPS unit is essential if and only if no failure is acceptable. G LV Switchboard Normal By-pass Non-critical circuit MLVS ASI Fig. D18 : Radial single feeder configuration Critical circuit Fig. D17 : Example of connection for a UPS 7.4 Configuration of LV circuits MLVS © Schneider Electric - all rights reserved Fig. D19 : Two-pole configuration MLVS NO Fig. D20 : Two-pole configuration with two ½ MLVS and NO link Main possible conigurations (see figures D18 to D25): b Radial single feeder configuration: This is the reference coniguration and the most simple. A load is connected to only one single source. This coniguration provides a minimum level of availability, since there is no redundancy in case of power source failure. b Two-pole configuration: The power supply is provided by 2 transformers, connected to the same MV line. When the transformers are close, they are generally connected in parallel to the same MLVS. b Variant: two-pole with two ½ MLVS: In order to increase the availability in case of failure of the busbars or authorize maintenance on one of the transformers, it is possible to split the MLVS into 2 parts, with a normally open link (NO). This coniguration generally requires an Automatic Transfer Switch, (ATS). b Shedable switchboard (simple disconnectable attachment): A series of shedable circuits can be connected to a dedicated switchboard. The connection to the MLVS is interrupted when needed (overload, generator operation, etc) b Interconnected switchboards: If transformers are physically distant from one another, they may be connected by a busbar trunking. A critical load can be supplied by one or other of the transformers. The availability of power is therefore improved, since the load can always be supplied in the case of failure of one of the sources. The redundancy can be: v Total: each transformer being capable of supplying all of the installation, v Partial: each transformer only being able to supply part of the installation. In this case, part of the loads must be disconnected (load-shedding) in the case of one of the transformers failing. Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide MLVS LV swichboard b Ring configuration: This coniguration can be considered as an extension of the coniguration with interconnection between switchboards. Typically, 4 transformers connected to the same MV line, supply a ring using busbar trunking. A given load is then supplied power by several clustered transformers. This coniguration is well suited to extended installations, with a high load density (in kVA/m²). If all of the loads can be supplied by 3 transformers, there is total redundancy in the case of failure of one of the transformers. In fact, each busbar can be fed power by one or other of its ends. Otherwise, downgraded operation must be considered (with partial load shedding). This coniguration requires special design of the protection plan in order to ensure discrimination in all of the fault circumstances. D23 b Double-ended power supply: This coniguration is implemented in cases where maximum availability is required. The principle involves having 2 independent power sources, e.g.: v 2 transformers supplied by different MV lines, v 1 transformer and 1 generator, v 1 transformer and 1 UPS. An automatic transfer switch (ATS) is used to avoid the sources being parallel connected. This coniguration allows preventive and curative maintenance to be carried out on all of the electrical distribution system upstream without interrupting the power supply. Fig. D21 : Shedable switchboard MLVS 7 Choice of architecture details MLVS b Configuration combinations: An installation can be made up of several subasssemblies with different conigurations, according to requirements for the availability of the different types of load. E.g.: generator unit and UPS, choice by sectors (some sectors supplied by cables and others by busbar trunking). Busbar or G or UPS Fig. D22 : Interconnected switchboards MLVS MLVS Fig. D24 : Double-ended configuration with automatic transfer switch Busbar 1 Busbar 2 3 G Busbar Busbar MLVS MLVS Busbar Fig. D23 : Ring configuration MLVS Fig. D25 : Example of a configuration combination 1: Single feeder, 2: Switchboard interconnection, 3: Double-ended Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved MLVS D - MV & LV architecture selection guide 7 Choice of architecture details For the different possible conigurations, the most probable and usual set of characteristics is given in the following table: Coniguration Radial Two-pole Sheddable load Interconnected switchboards Ring Double-ended Site topology Any Any Any 1 level 5 to 25000m² 1 level 5 to 25000m² Any Location latitude Any Any Any Medium of high Medium or high Any Maintainability Minimal Standard Minimal Standard Standard Enhanced Power demand < 2500kVA Any Any ≥ 1250kVA > 2500kVA Any Load distribution Localized loads Localized loads Localized load Intermediate or uniforme distribution Uniform distribution Localized loads Interruptions sensitivity Long interruption acceptable Long interruption acceptable Sheddable Long interruption acceptable Long interruption acceptable Short or no interruption Disturbances sensitivity Low sensitivity High sensitivity Low sensitivity High sensitivity High sensitivity High sensitivity Other constraints / / / / / Double-ended loads © Schneider Electric - all rights reserved D24 Characteristic to be considered Schneider Electric - Electrical installation guide 2009 8 Choice of equipment The choice of equipment is step 3 in the design of an electrical installation. The aim of this step is to select equipment from the manufacturers’ catalogues. The choice of technological solutions results from the choice of architecture. List of equipment to consider: b MV/LV substation, b MV switchboards, b Transformers, b LV switchboards, b Busbar trunking, b UPS units, b Power factor correction and iltering equipment. D25 Criteria to consider: b Atmosphere, environment, b Service index, b Offer availability per country, b Utilities requirements, b Previous architecture choices. The choice of equipment is basically linked to the offer availability in the country. This criterion takes into account the availability of certain ranges of equipment or local technical support. The detailed selection of equipment is out of the scope of this document. © Schneider Electric - all rights reserved D - MV & LV architecture selection guide Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 9 Recommendations for architecture optimization These recommendations are intended to guide the designer towards architecture upgrades which allow him to improve assessment criteria. 9.1 On-site work D26 To be compatible with the “special” or “critical” work-site time, it is recommended to limit uncertainties by applying the following recommendations: b Use of proven solutions and equipment that has been validated and tested by manufacturers (“functional” switchboard or “manufacturer” switchboard according to the application criticality), b Prefer the implementation of equipment for which there is a reliable distribution network and for which it is possible to have local support (supplier well established), b Prefer the use of factory-built equipment (MV/LV substation, busbar trunking), allowing the volume of operations on site to be limited, b Limit the variety of equipment implemented (e.g. the power of transformers), b Avoid mixing equipment from different manufacturers. 9.2 Environmental impact The optimization of the environmental assessment of an installation will involve reducing: b Power losses at full load and no load during installation operation, b Overall, the mass of materials used to produce the installation. Taken separately and when looking at only one piece of equipment, these 2 objectives may seem contradictory. However, when applied to whole installation, it is possible to design the architecture to contribute to both objectives. The optimal installation will therefore not be the sum of the optimal equipment taken separately, but the result of an optimization of the overall installation. Figure D26 gives an example of the contribution per equipment category to the weight and energy dissipation for a 3500 kVA installation spread over 10000m². LV switchboard and switchgear LV switchboard and switchgear 5% 10 % LV cables and trunking LV cables and trunking 75 % 46 % Transformers Transformers 20 % 44 % Total loss for equipment considered: 414 MWh Total mass of equipment considered: 18,900 kg © Schneider Electric - all rights reserved Fig. D26 : Example of the spread of losses and the weight of material for each equipment category Generally speaking, LV cables and trunking as well as the MV/LV transformers are the main contributors to operating losses and the weight of equipment used. Environmental optimization of the installation by the architecture will therefore involve: b reducing the length of LV circuits in the installation, b clustering LV circuits wherever possible to take advantage of the factor of simultaneity ks (see chapter A: General rules of electrical installation design, Chapter – Power loading of an installation, 4.3 “Estimation of actual maximum kVA demand”) Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 9 Recommendations for architecture optimization Objectives Resources Reducing the length of LV circuits Placing MV/LV substations as close as possible to the barycenter of all of the LV loads to be supplied Clustering LV circuits When the simultaneity factor of a group of loads to be supplied is less than 0.7, the clustering of circuits allows us to limit the volume of conductors supplying power to these loads. In real terms this involves: b setting up sub-distribution switchboards as close as possible to the barycenter of the groups of loads if they are localized, b setting up busbar trunking systems as close as possible to the barycenter of the groups of loads if they are distributed. The search for an optimal solution may lead to consider several clustering scenarios. In all cases, reducing the distance between the barycenter of a group of loads and the equipment that supplies them power allows to reduce environmental impact. D27 Fig. D27 : Environmental optimization : Objectives and Ressources. As an example figure D28 shows the impact of clustering circuits on reducing the distance between the barycenter of the loads of an installation and that of the sources considered (MLVS whose position is imposed). This example concerns a mineral water bottling plant for which: b the position of electrical equipment (MLVS) is imposed in the premises outside of the process area for reasons of accessibility and atmosphere constraints, b the installed power is around 4 MVA. In solution No.1, the circuits are distributed for each workshop. In solution No. 2, the circuits are distributed by process functions (production lines). Solution Barycenter position Workshop 1 N°1 Workshop 2 Workshop 3 Storage MLVS area Workshop 1 Barycenter N°2 Workshop 2 Barycenter Workshop 1 Workshop 2 Workshop 3 Barycenter Workshop 3 Storage Barycenter line 1 Barycenter line 2 Barycenter line 3 Barycenter line 3 Fig. D28 : Example of barycenter positioning Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved MLVS area D - MV & LV architecture selection guide 9 Recommendations for architecture optimization Without changing the layout of electrical equipment, the second solution allows us to achieve gains of around 15% on the weight of LV cables to be installed (gain on lengths) and a better uniformity of transformer power. To supplement the optimizations carried out in terms of architecture, the following points also contribute to the optimization: D28 b the setting up of LV power factor correction to limit losses in the transformers and LV circuits if this compensation is distributed, b the use of low loss transformers, b the use of aluminum LV busbar trunking when possible, since natural resources of this metal are greater. 9.3 Preventive maintenance volume Recommendations for reducing the volume of preventive maintenance: b Use the same recommendations as for reducing the work site time, b Focus maintenance work on critical circuits, b Standardize the choice of equipment, b Use equipment designed for severe atmospheres (requires less maintenance). 9.4 Electrical power availability Recommendations for improving the electrical power availability: b Reduce the number of feeders per switchboard, in order to limit the effects of a possible failure of a switchboard, b Distributing circuits according to availability requirements, b Using equipment that is in line with requirements (see Service Index, 4.2), b Follow the selection guides proposed for steps 1 & 2 (see Fig. D3 page D5). © Schneider Electric - all rights reserved Recommendations to increase the level of availability: b Change from a radial single feeder coniguration to a two-pole coniguration, b Change from a two-pole coniguration to a double-ended coniguration, b Change from a double-ended coniguration to a uninterruptible coniguration with a UPS unit and a Static Transfer Switch b Increase the level of maintenance (reducing the MTTR, increasing the MTBF) Schneider Electric - Electrical installation guide 2009 10 Glossary Architecture: choice of a single-line diagram and technological solutions, from connection to the utility network through to load power supply circuits. Main MV/LV distribution: Level upstream of the architecture, from connection to the network utility through to LV distribution equipment on the site (MLVS – or equivalent). MLVS – Main Low Voltage Switchboard: Main switchboard downstream of the MV/LV transformer, starting point of power distribution circuits in the installation LV power distribution: intermediate level in the architecture, downstream of the main level through to the sub-distribution switchboards (spatial and functional distribution of electrical power in the circuits). D29 LV terminal distribution: Downstream level of the architecture, downstream of the sub-distribution switchboards through to the loads. This level of distribution is not dealt with in this guide. Single-line diagram: general electrical schematic diagram to represent the main electrical equipment and their interconnection. MV substation, transformation substation: Enclosures grouping together MV equipment and/or MV/LV transformers. These enclosures can be shared or separate, according to the site layout, or the equipment technology. In certain countries, the MV substation is assimilated with the delivery substation. Technological solution: Resulting from the choice of technology for an installation sub-assembly, from among the different products and equipment proposed by the manufacturer. Characteristics: Technical or environmental data relative to the installation, enabling the best-suited architecture to be selected. Criteria: Parameters for assessing the installation, enabling selection of the architecture that is the best-suited to the needs of the customer. © Schneider Electric - all rights reserved D - MV & LV architecture selection guide Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 11 ID-Spec software ID-Spec is a new software which aims at helping the designer to be more productive in draft design phase and argue easily his design decisions. It supports the designer in selecting the relevant single line diagram patterns for main distribution and sub distribution and in adapting these patterns to his project. It also supports the designer in equipment technology and rating selection. Its generates automatically the corresponding design speciication documentation including single line diagram and its argument, list and speciication of the corresponding equipment. © Schneider Electric - all rights reserved D30 Schneider Electric - Electrical installation guide 2009 12 Example: electrical installation in a printworks 12.1 Brief description Printing of personalized mailshots intended for mail order sales. 12.2 Installation characteristics Characteristic Category Activity Mechanical Site topology single storey building, 10000m² (8000m² dedicated to the process, 2000m² for ancillary areas) Layout latitude High Service reliability Standard Maintainability Standard Installation lexibility b No lexibility planned: v HVAC v Process utilities v Ofice power supply b Possible lexibility: v inishing, putting in envelopes v special machines, installed at a later date v rotary machines (uncertainty at the draft design stage) Power demand 3500kVA Load distribution Intermediate distribution Power interruptions sensitivity b Sheddable circuits: v ofices (apart from PC power sockets) v air conditioning, ofice heating v social premises v maintenance premises b long interruptions acceptable: v printing machines v workshop HVAC (hygrometric control) v Finishing, envelope illing v Process utilities (compressor, recycling of cooled water) b No interruptions acceptable: v servers, ofice PCs Disturbance sensitivity b Average sensitivity: v motors, lighting b High sensitivity: v IT D31 No special precaution to be taken due to the connection to the EdF network (low level of disturbance) Disturbance capability Non disturbing Other constraints b Building with lightning classiication: lightning surge arresters installed b Power supply by overhead single feeder line 12.3 Technological characteristics Criteria Category Atmosphere, environment b IP: standard (no dust, no water protection) b IK: standard (use of technical pits, dedicated premises) b °C: standard (temperature regulation) Service index 211 Offer availability by country No problem (project carried out in France) Other criteria Nothing particular Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved D - MV & LV architecture selection guide D - MV & LV architecture selection guide 12 Example: electrical installation in a printworks 12.4 Architecture assessment criteria D32 Criteria Category On-site work time Secondary Environmental impact Minimal: compliance with European standard regulations Preventive maintenance costs Standard Power supply availability Level I Step 1: Architecture fundamentals Choice Main criteria Solution Connection to upstream network Isolated site single branch circuit MV Circuits Layout + criticality single feeder Number of transformers Power > 2500kVA 2 x 2000kVA Number and distribution of substations Surface area and power distribution 2 possible solutions: 1 substation or 2 substations b if 1 substations: NO link between MLVS b if 2 substations: interconnected switchboards MV Generator Site activity No MV MV MV MV LV LV LV LV MLVS 1 MLVS 2 MLVS 1 MLVS 2 Trunking © Schneider Electric - all rights reserved Fig. D29 : Two possible single-line diagrams Schneider Electric - Electrical installation guide 2009 12 Example: electrical installation in a printworks Step 2: Architecture details “1 substation” solution Choice Main criteria Solution Layout Atmospheric constraint Dedicated premises Centralized or decentralized layout Uniform loads, distributed power, scalability possibilities b Decentralized with busbar trunking: v inishing sector, envelope illing b Centralized with cables: v special machines, rotary machines, HVAC, process utilities, ofices (2 switchboards), ofice air conditioning, social premises, maintenance Non-uniform loads, direct link from MLVS Presence of back-up generator Criticality ≤ low Network availability: standard Presence of UPS Criticality UPS unit for servers and ofice PCs LV circuit coniguration 2 transformers, possible partial redundancy b Two-pole, variant 2 ½ MLVS + NO link (reduction of the Isc by MLVS, no redundancy b process (≤ weak) b sheddable circuit for noncritical loads No back-up generator MV MV LV LV MLVS 1 D33 MLVS 2 Trunking ASI HVAC Sheddable Offices Machines Fig. D30 : Detailed single-line diagram (1 substation) © Schneider Electric - all rights reserved D - MV & LV architecture selection guide Schneider Electric - Electrical installation guide 2009 D - MV & LV architecture selection guide 12 Example: electrical installation in a printworks 12.5 Choice of technological solutions: D34 Choice Main criteria Solution MV/LV substation Atmosphere, environment indoor (dedicated premises) MV switchboard Offer availability by country SM6 (installation produced in France) Transformers Atmosphere, environment cast resin transfo (avoids constraints related to oil) LV switchboard Atmosphere, IS MLVS: Prisma + P Sub-distribution: Prisma + Busbar trunking Installed power to be supplied Canalis KS UPS units Installed power to be supplied, back-up time Galaxy PW Power factor correction Installed power, presence of harmonics LV, standard, automatic (Average Q, ease of installation) “2 substation” solution Ditto apart from: LV circuit: 2 remote MLVS connected via busbar trunking MV MV LV LV MLVS 1 MLVS 2 Trunking Trunking HVAC Sheddable ASI Offices © Schneider Electric - all rights reserved Fig. D31 : Detailed single-line diagram (2 substations) Schneider Electric - Electrical installation guide 2009 Machines Chapter E LV Distribution Contents 1 Earthing schemes E2 1.1 1.2 1.3 1.4 1.5 1.6 E2 E3 E6 E8 E10 E11 2 The installation system E15 2.1 Distribution boards 2.2 Cables and busways E15 E18 3 External influences (IEC 60364-5-51) E25 3.1 3.2 3.3 3.4 E25 E25 E25 E28 Earthing connections Definition of standardised earthing schemes Characteristics of TT, TN and IT systems Selection criteria for the TT, TN and IT systems Choice of earthing method - implementation Installation and measurements of earth electrodes © Schneider Electric - all rights reserved Definition and reference standards Classification List of external influences Protection provided for enclosed equipment: codes IP and IK E1 Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes In a building, the connection of all metal parts of the building and all exposed conductive parts of electrical equipment to an earth electrode prevents the appearance of dangerously high voltages between any two simultaneously accessible metal parts E2 Extraneous conductive parts 4 3 3 Main protective conductor Heating Definitions National and international standards (IEC 60364) clearly define the various elements of earthing connections. The following terms are commonly used in industry and in the literature. Bracketed numbers refer to Figure E1 : b Earth electrode (1): A conductor or group of conductors in intimate contact with, and providing an electrical connection with Earth (cf details in section 1.6 of Chapter E.) b Earth: The conductive mass of the Earth, whose electric potential at any point is conventionally taken as zero b Electrically independent earth electrodes: Earth electrodes located at such a distance from one another that the maximum current likely to flow through one of them does not significantly affect the potential of the other(s) b Earth electrode resistance: The contact resistance of an earth electrode with the Earth b Earthing conductor (2): A protective conductor connecting the main earthing terminal (6) of an installation to an earth electrode (1) or to other means of earthing (e.g. TN systems); b Exposed-conductive-part: A conductive part of equipment which can be touched and which is not a live part, but which may become live under fault conditions b Protective conductor (3): A conductor used for some measures of protection against electric shock and intended for connecting together any of the following parts: v Exposed-conductive-parts v Extraneous-conductive-parts v The main earthing terminal v Earth electrode(s) v The earthed point of the source or an artificial neutral b Extraneous-conductive-part: A conductive part liable to introduce a potential, generally earth potential, and not forming part of the electrical installation (4). For example: v Non-insulated floors or walls, metal framework of buildings v Metal conduits and pipework (not part of the electrical installation) for water, gas, heating, compressed-air, etc. and metal materials associated with them b Bonding conductor (5): A protective conductor providing equipotential bonding b Main earthing terminal (6): The terminal or bar provided for the connection of protective conductors, including equipotential bonding conductors, and conductors for functional earthing, if any, to the means of earthing. Connections 5 Water 4 3 Branched protective conductors to individual consumers 1.1 Earthing connections The main equipotential bonding system The bonding is carried out by protective conductors and the aim is to ensure that, in the event of an incoming extraneous conductor (such as a gas pipe, etc.) being raised to some potential due to a fault external to the building, no difference of potential can occur between extraneous-conductive-parts within the installation. The bonding must be effected as close as possible to the point(s) of entry into the building, and be connected to the main earthing terminal (6). However, connections to earth of metallic sheaths of communications cables require the authorisation of the owners of the cables. 5 Gas 5 6 7 Supplementary equipotential connections These connections are intended to connect all exposed-conductive-parts and all extraneous-conductive-parts simultaneously accessible, when correct conditions for protection have not been met, i.e. the original bonding conductors present an unacceptably high resistance. 2 1 Connection of exposed-conductive-parts to the earth electrode(s) The connection is made by protective conductors with the object of providing a lowresistance path for fault currents flowing to earth. © Schneider Electric - all rights reserved Fig. E1 : An example of a block of flats in which the main earthing terminal (6) provides the main equipotential connection; the removable link (7) allows an earth-electrode-resistance check Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes Components (see Fig. E2) Effective connection of all accessible metal fixtures and all exposed-conductive-parts of electrical appliances and equipment, is essential for effective protection against electric shocks. Component parts to consider: as exposed-conductive-parts Cableways b Conduits b Impregnated-paper-insulated lead-covered cable, armoured or unarmoured b Mineral insulated metal-sheathed cable (pyrotenax, etc.) Switchgear b cradle of withdrawable switchgear Appliances b Exposed metal parts of class 1 insulated appliances Non-electrical elements b metallic fittings associated with cableways (cable trays, cable ladders, etc.) b Metal objects: v Close to aerial conductors or to busbars v In contact with electrical equipment. Component parts not to be considered: as exposed-conductive-parts Diverse service channels, ducts, etc. b Conduits made of insulating material b Mouldings in wood or other insulating material b Conductors and cables without metallic sheaths Switchgear b Enclosures made of insulating material Appliances b All appliances having class II insulation regardless of the type of exterior envelope as extraneous-conductive-parts Elements used in building construction b Metal or reinforced concrete (RC): v Steel-framed structure v Reinforcement rods v Prefabricated RC panels b Surface finishes: v Floors and walls in reinforced concrete without further surface treatment v Tiled surface b Metallic covering: v Metallic wall covering E3 Building services elements other than electrical b Metal pipes, conduits, trunking, etc. for gas, water and heating systems, etc. b Related metal components (furnaces, tanks, reservoirs, radiators) b Metallic fittings in wash rooms, bathrooms, toilets, etc. b Metallised papers as extraneous-conductive-parts b Wooden-block floors b Rubber-covered or linoleum-covered floors b Dry plaster-block partition b Brick walls b Carpets and wall-to-wall carpeting Fig. E2 : List of exposed-conductive-parts and extraneous-conductive-parts 1.2 Definition of standardised earthing schemes The choice of these methods governs the measures necessary for protection against indirect-contact hazards. The earthing system qualifies three originally independent choices made by the designer of an electrical distribution system or installation: b The type of connection of the electrical system (that is generally of the neutral conductor) and of the exposed parts to earth electrode(s) b A separate protective conductor or protective conductor and neutral conductor being a single conductor b The use of earth fault protection of overcurrent protective switchgear which clear only relatively high fault currents or the use of additional relays able to detect and clear small insulation fault currents to earth In practice, these choices have been grouped and standardised as explained below. Each of these choices provides standardised earthing systems with three advantages and drawbacks: b Connection of the exposed conductive parts of the equipment and of the neutral conductor to the PE conductor results in equipotentiality and lower overvoltages but increases earth fault currents b A separate protective conductor is costly even if it has a small cross-sectional area but it is much more unlikely to be polluted by voltage drops and harmonics, etc. than a neutral conductor is. Leakage currents are also avoided in extraneous conductive parts b Installation of residual current protective relays or insulation monitoring devices are much more sensitive and permits in many circumstances to clear faults before heavy damage occurs (motors, fires, electrocution). The protection offered is in addition independent with respect to changes in an existing installation Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved The different earthing schemes (often referred to as the type of power system or system earthing arrangements) described characterise the method of earthing the installation downstream of the secondary winding of a MV/LV transformer and the means used for earthing the exposed conductive-parts of the LV installation supplied from it E - Distribution in low-voltage installations Neutral Exposed conductive parts Earth Earth 1 Earthing schemes TT system (earthed neutral) (see Fig. E3) L1 L2 L3 N PE One point at the supply source is connected directly to earth. All exposed- and extraneous-conductive-parts are connected to a separate earth electrode at the installation. This electrode may or may not be electrically independent of the source electrode. The two zones of influence may overlap without affecting the operation of protective devices. TN systems (exposed conductive parts connected to the neutral) The source is earthed as for the TT system (above). In the installation, all exposedand extraneous-conductive-parts are connected to the neutral conductor. The several versions of TN systems are shown below. Rn E4 Fig. E3 : TT System Neutral Exposed conductive parts Earth Neutral L1 L2 L3 PEN Rn Fig. E4 : TN-C system L1 L2 L3 N PE TN-C system (see Fig. E4) The neutral conductor is also used as a protective conductor and is referred to as a PEN (Protective Earth and Neutral) conductor. This system is not permitted for conductors of less than 10 mm2 or for portable equipment. The TN-C system requires an effective equipotential environment within the installation with dispersed earth electrodes spaced as regularly as possible since the PEN conductor is both the neutral conductor and at the same time carries phase unbalance currents as well as 3rd order harmonic currents (and their multiples). The PEN conductor must therefore be connected to a number of earth electrodes in the installation. Caution: In the TN-C system, the “protective conductor” function has priority over the “neutral function”. In particular, a PEN conductor must always be connected to the earthing terminal of a load and a jumper is used to connect this terminal to the neutral terminal. TN-S system (see Fig. E5) The TN-S system (5 wires) is obligatory for circuits with cross-sectional areas less than 10 mm2 for portable equipment. The protective conductor and the neutral conductor are separate. On underground cable systems where lead-sheathed cables exist, the protective conductor is generally the lead sheath. The use of separate PE and N conductors (5 wires) is obligatory for circuits with cross-sectional areas less than 10 mm2 for portable equipment. TN-C-S system (see Fig. E6 below and Fig. E7 next page) The TN-C and TN-S systems can be used in the same installation. In the TN-C-S system, the TN-C (4 wires) system must never be used downstream of the TN-S (5 wires) system, since any accidental interruption in the neutral on the upstream part would lead to an interruption in the protective conductor in the downstream part and therefore a danger. Rn Fig. E5 : TN-S system 5 x 50 mm2 L1 L2 L3 N PE PEN PE 16 mm2 6 mm2 16 mm2 16 mm2 PEN Bad Bad © Schneider Electric - all rights reserved TN-C scheme not permitted downstream of TN-S scheme Fig. E6 : TN-C-S system Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes 4 x 95 mm2 L1 L2 L3 PEN 16 mm2 10 mm2 6 mm2 6 mm2 PEN PEN N Correct Incorrect Correct PEN connected to the neutral terminal is prohibited Neutral Exposed conductive parts Isolated or impedance-earthed Earth IT system (isolated or impedance-earthed neutral) Fig. E8 : IT system (isolated neutral) MV/LV R1 C2 E5 Fig. E7 : Connection of the PEN conductor in the TN-C system L1 L2 L3 N PE C1 Incorrect S < 10 mm 2 TNC prohibited R2 R3 C3 IT system (isolated neutral) No intentional connection is made between the neutral point of the supply source and earth (see Fig. E8). Exposed- and extraneous-conductive-parts of the installation are connected to an earth electrode. In practice all circuits have a leakage impedance to earth, since no insulation is perfect. In parallel with this (distributed) resistive leakage path, there is the distributed capacitive current path, the two paths together constituting the normal leakage impedance to earth (see Fig. E9). Example (see Fig. E10) In a LV 3-phase 3-wire system, 1 km of cable will have a leakage impedance due to C1, C2, C3 and R1, R2 and R3 equivalent to a neutral earth impedance Zct of 3,000 to 4,000 Ω, without counting the filtering capacitances of electronic devices. IT system (impedance-earthed neutral) An impedance Zs (in the order of 1,000 to 2,000 Ω) is connected permanently between the neutral point of the transformer LV winding and earth (see Fig. E11). All exposed- and extraneous-conductive-parts are connected to an earth electrode. The reasons for this form of power-source earthing are to fix the potential of a small network with respect to earth (Zs is small compared to the leakage impedance) and to reduce the level of overvoltages, such as transmitted surges from the MV windings, static charges, etc. with respect to earth. It has, however, the effect of slightly increasing the first-fault current level. Fig. E9 : IT system (isolated neutral) MV/LV MV/LV Zct Fig. E10 : Impedance equivalent to leakage impedances in an IT system Fig. E11 : IT system (impedance-earthed neutral) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Zs E - Distribution in low-voltage installations 1 Earthing schemes 1.3 Characteristics of TT, TN and IT systems TT system (see Fig. E12) The TT system: b Technique for the protection of persons: the exposed conductive parts are earthed and residual current devices (RCDs) are used b Operating technique: interruption for the first insulation fault E6 Fig. E12 : TT system Note: If the exposed conductive parts are earthed at a number of points, an RCD must be installed for each set of circuits connected to a given earth electrode. Main characteristics b Simplest solution to design and install. Used in installations supplied directly by the public LV distribution network. b Does not require continuous monitoring during operation (a periodic check on the RCDs may be necessary). b Protection is ensured by special devices, the residual current devices (RCD), which also prevent the risk of fire when they are set to y 500 mA. b Each insulation fault results in an interruption in the supply of power, however the outage is limited to the faulty circuit by installing the RCDs in series (selective RCDs) or in parallel (circuit selection). b Loads or parts of the installation which, during normal operation, cause high leakage currents, require special measures to avoid nuisance tripping, i.e. supply the loads with a separation transformer or use specific RCDs (see section 5.1 in chapter F). The TN system: TN system (see Fig. E13 and Fig. E14 ) b Technique for the protection of persons: v Interconnection and earthing of exposed conductive parts and the neutral are mandatory v Interruption for the first fault using overcurrent protection (circuit-breakers or fuses) b Operating technique: interruption for the first insulation fault PEN © Schneider Electric - all rights reserved Fig. E13 : TN-C system N PE Fig. E14 : TN-S system Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes Main characteristics b Generally speaking, the TN system: v requires the installation of earth electrodes at regular intervals throughout the installation v Requires that the initial check on effective tripping for the first insulation fault be carried out by calculations during the design stage, followed by mandatory measurements to confirm tripping during commissioning v Requires that any modification or extension be designed and carried out by a qualified electrician v May result, in the case of insulation faults, in greater damage to the windings of rotating machines v May, on premises with a risk of fire, represent a greater danger due to the higher fault currents E7 b In addition, the TN-C system: v At first glance, would appear to be less expensive (elimination of a device pole and of a conductor) v Requires the use of fixed and rigid conductors v Is forbidden in certain cases: - Premises with a risk of fire - For computer equipment (presence of harmonic currents in the neutral) b In addition, the TN-S system: v May be used even with flexible conductors and small conduits v Due to the separation of the neutral and the protection conductor, provides a clean PE (computer systems and premises with special risks) IT system (see Fig. E15) IT system: b Protection technique: v Interconnection and earthing of exposed conductive parts v Indication of the first fault by an insulation monitoring device (IMD) v Interruption for the second fault using overcurrent protection (circuit-breakers or fuses) Cardew IMD Fig. E15 : IT system Main characteristics b Solution offering the best continuity of service during operation b Indication of the first insulation fault, followed by mandatory location and clearing, ensures systematic prevention of supply outages b Generally used in installations supplied by a private MV/LV or LV/LV transformer b Requires maintenance personnel for monitoring and operation b Requires a high level of insulation in the network (implies breaking up the network if it is very large and the use of circuit-separation transformers to supply loads with high leakage currents) b The check on effective tripping for two simultaneous faults must be carried out by calculations during the design stage, followed by mandatory measurements during commissioning on each group of interconnected exposed conductive parts b Protection of the neutral conductor must be ensured as indicated in section 7.2 of Chapter G © Schneider Electric - all rights reserved b Operating technique: v Monitoring of the first insulation fault v Mandatory location and clearing of the fault v Interruption for two simultaneous insulation faults Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes Selection does not depend on safety criteria. The three systems are equivalent in terms of protection of persons if all installation and operating rules are correctly followed. The selection criteria for the best system(s) depend on the regulatory requirements, the required continuity of service, operating conditions and the types of network and loads. E8 1.4 Selection criteria for the TT, TN and IT systems In terms of the protection of persons, the three system earthing arrangements (SEA) are equivalent if all installation and operating rules are correctly followed. Consequently, selection does not depend on safety criteria. It is by combining all requirements in terms of regulations, continuity of service, operating conditions and the types of network and loads that it is possible to determine the best system(s) (see Fig. E16). Selection is determined by the following factors: b Above all, the applicable regulations which in some cases impose certain types of SEA b Secondly, the decision of the owner if supply is via a private MV/LV transformer (MV subscription) or the owner has a private energy source (or a separate-winding transformer) If the owner effectively has a choice, the decision on the SEA is taken following discussions with the network designer (design office, contractor) The discussions must cover: b First of all, the operating requirements (the required level of continuity of service) and the operating conditions (maintenance ensured by electrical personnel or not, in-house personnel or outsourced, etc.) b Secondly, the particular characteristics of the network and the loads (see Fig. E17 next page) TT TN-S TN-C IT1 IT2 Comments Electrical characteristics Fault current Fault voltage - -- -- + + -- Touch voltage +/- - - - + - Only the IT system offers virtually negligible first-fault currents In the IT system, the touch voltage is very low for the first fault, but is considerable for the second In the TT system, the touch voltage is very low if system is equipotential, otherwise it is high Protection Protection of persons against indirect contact + + + + + + - - + - + + Not + allowed + + + + - + + - + + + + + - + + + + + + - + + + - - + - + - - + + + - Only the IT system avoids tripping for the first insulation fault The TN-S, TNC and IT (2nd fault) systems generate high fault currents which may cause phase voltage dips Installation Special devices - + + - - Number of earth electrodes - + + -/+ -/+ Number of cables - - + - - The TT system requires the use of RCDs. The IT system requires the use of IMDs The TT system requires two distinct earth electrodes. The IT system offers a choice between one or two earth electrodes Only the TN-C system offers, in certain cases, a reduction in the number of cables Maintenance Cost of repairs - -- -- - -- Installation damage + - - ++ - Protection of persons with emergency generating sets Protection against fire (with an RCD) Overvoltages Continuous overvoltage Transient overvoltage Overvoltage if transformer breakdown (primary/secondary) Electromagnetic compatibility Immunity to nearby lightning strikes © Schneider Electric - all rights reserved Immunity to lightning strikes on MV lines Continuous emission of an electromagnetic field Transient non-equipotentiality of the PE Continuity of service Interruption for first fault Voltage dip during insulation fault All SEAs (system earthing arrangement) are equivalent, if the rules are followed Systems where protection is ensured by RCDs are not sensitive to a change in the internal impedance of the source All SEAs in which RCDs can be used are equivalent. The TN-C system is forbidden on premises where there is a risk of fire A phase-to-earth overvoltage is continuous in the IT system if there is a first insulation fault Systems with high fault currents may cause transient overvoltages In the TT system, there is a voltage imbalance between the different earth electrodes. The other systems are interconnected to a single earth electrode In the TT system, there may be voltage imbalances between the earth electrodes. In the TT system, there is a significant current loop between the two separate earth electrodes All SEAs are equivalent when a MV line takes a direct lightning strike Connection of the PEN to the metal structures of the building is conducive to the continuous generation of electromagnetic fields The PE is no longer equipotential if there is a high fault current The cost of repairs depends on the damage caused by the amplitude of the fault currents Systems causing high fault currents require a check on the installation after clearing the fault Fig. E16 : Comparison of system earthing arrangements Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes Type of network Very large network with high-quality earth electrodes for exposed conductive parts (10 Ω max.) Very large network with low-quality earth electrodes for exposed conductive parts (> 30 Ω) Disturbed area (storms) (e.g. television or radio transmitter) Network with high leakage currents (> 500 mA) Network with outdoor overhead lines Emergency standby generator set Advised TN Possible TT, TN, IT (1) or mixed TN-S Not advised TN TT IT (1) TN-C IT (2) TN (4) TT (5) IT (4) TT (3) (4) TN (5) (6) IT (6) IT TT TN (7) E9 Type of loads Loads sensitive to high fault currents (motors, etc.) IT TT TN (8) Loads with a low insulation level (electric furnaces, welding machines, heating elements, immersion heaters, equipment in large kitchens) Numerous phase-neutral single-phase loads (mobile, semi-fixed, portable) Loads with sizeable risks (hoists, conveyers, etc.) TN (9) TT (9) IT TT (11) IT (10) TN-C (10) IT (11) Numerous auxiliaries (machine tools) TN-S TN-C IT (12 bis) TT (12) Miscellaneous Supply via star-star connected power transformer (13) TT Premises with risk of fire IT (15) IT without neutral TN-S (15) TT (15) IT (13) with neutral TN-C (14) LV TT (16) MV/LV TT (17) Installation where the continuity of earth circuits is uncertain (work sites, old installations) Electronic equipment (computers, PLCs) Machine control-monitoring network, PLC sensors and actuators TT (19) TN-S TN-S IT (20) TT TN-S, TT TN (18) IT (18) TN-C IT (19) TN-C (1) When the SEA is not imposed by regulations, it is selected according to the level of operating characteristics (continuity of service that is mandatory for safety reasons or desired to enhance productivity, etc.) Whatever the SEA, the probability of an insulation failure increases with the length of the network. It may be a good idea to break up the network, which facilitates fault location and makes it possible to implement the system advised above for each type of application. (2) The risk of flashover on the surge limiter turns the isolated neutral into an earthed neutral. These risks are high for regions with frequent thunder storms or installations supplied by overhead lines. If the IT system is selected to ensure a higher level of continuity of service, the system designer must precisely calculate the tripping conditions for a second fault. (3) Risk of RCD nuisance tripping. (4) Whatever the SEA, the ideal solution is to isolate the disturbing section if it can be easily identified. (5) Risks of phase-to-earth faults affecting equipotentiality. (6) Insulation is uncertain due to humidity and conducting dust. (7) The TN system is not advised due to the risk of damage to the generator in the case of an internal fault. What is more, when generator sets supply safety equipment, the system must not trip for the first fault. (8) The phase-to-earth current may be several times higher than In, with the risk of damaging or accelerating the ageing of motor windings, or of destroying magnetic circuits. (9) To combine continuity of service and safety, it is necessary and highly advised, whatever the SEA, to separate these loads from the rest of the installation (transformers with local neutral connection). (10) When load equipment quality is not a design priority, there is a risk that the insulation resistance will fall rapidly. The TT system with RCDs is the best means to avoid problems. (11) The mobility of this type of load causes frequent faults (sliding contact for bonding of exposed conductive parts) that must be countered. Whatever the SEA, it is advised to supply these circuits using transformers with a local neutral connection. (12) Requires the use of transformers with a local TN system to avoid operating risks and nuisance tripping at the first fault (TT) or a double fault (IT). (12 bis) With a double break in the control circuit. (13) Excessive limitation of the phase-to-neutral current due to the high value of the zero-phase impedance (at least 4 to 5 times the direct impedance). This system must be replaced by a star-delta arrangement. (14) The high fault currents make the TN system dangerous. The TN-C system is forbidden. (15) Whatever the system, the RCD must be set to Δn y 500 mA. (16) An installation supplied with LV energy must use the TT system. Maintaining this SEA means the least amount of modifications on the existing network (no cables to be run, no protection devices to be modified). (17) Possible without highly competent maintenance personnel. (18) This type of installation requires particular attention in maintaining safety. The absence of preventive measures in the TN system means highly qualified personnel are required to ensure safety over time. (19) The risks of breaks in conductors (supply, protection) may cause the loss of equipotentiality for exposed conductive parts. A TT system or a TN-S system with 30 mA RCDs is advised and is often mandatory. The IT system may be used in very specific cases. (20) This solution avoids nuisance tripping for unexpected earth leakage. Fig. E17 : Influence of networks and loads on the selection of system earthing arrangements Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Increase in power level of LV utility subscription, requiring a private substation Installation with frequent modifications TT (10) TN-S TN (11) E - Distribution in low-voltage installations 1 Earthing schemes 1.5 Choice of earthing method - implementation After consulting applicable regulations, Figures E16 and E17 can be used as an aid in deciding on divisions and possible galvanic isolation of appropriate sections of a proposed installation. Division of source E10 This technique concerns the use of several transformers instead of employing one high-rated unit. In this way, a load that is a source of network disturbances (large motors, furnaces, etc.) can be supplied by its own transformer. The quality and continuity of supply to the whole installation are thereby improved. The cost of switchgear is reduced (short-circuit current level is lower). The cost-effectiveness of separate transformers must be determined on a case by case basis. Network islands The creation of galvanically-separated “islands” by means of LV/LV transformers makes it possible to optimise the choice of earthing methods to meet specific requirements (see Fig. E18 and Fig. E19 ). MV/LV IMD IT system LV/LV TN-S system Fig. E18 : TN-S island within an IT system MV/LV TN-S LV/LV LV/LV IMD IT TN-S system Hospital IMD IT Operating room Fig. E19 : IT islands within a TN-S system Conclusion © Schneider Electric - all rights reserved The optimisation of the performance of the whole installation governs the choice of earthing system. Including: b Initial investments, and b Future operational expenditures, hard to assess, that can arise from insufficient reliability, quality of equipment, safety, continuity of service, etc. An ideal structure would comprise normal power supply sources, local reserve power supply sources (see section 1.4 of Chapter E) and the appropriate earthing arrangements. Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 1 Earthing schemes A very effective method of obtaining a lowresistance earth connection is to bury a conductor in the form of a closed loop in the soil at the bottom of the excavation for building foundations. The resistance R of such an electrode (in homogeneous soil) is given (approximately) in ohms by: R = 2 L where where 1.6 Installation and measurements of earth electrodes The quality of an earth electrode (resistance as low as possible) depends essentially on two factors: b Installation method b Type of soil Installation methods L = length of the buried conductor in metres ρ = soil resistivity in ohm-metres Three common types of installation will be discussed: Buried ring (see Fig. E20) This solution is strongly recommended, particularly in the case of a new building. The electrode should be buried around the perimeter of the excavation made for the foundations. It is important that the bare conductor be in intimate contact with the soil (and not placed in the gravel or aggregate hard-core, often forming a base for concrete). At least four (widely-spaced) vertically arranged conductors from the electrode should be provided for the installation connections and, where possible, any reinforcing rods in concrete work should be connected to the electrode. The conductor forming the earth electrode, particularly when it is laid in an excavation for foundations, must be in the earth, at least 50 cm below the hard-core or aggregate base for the concrete foundation. Neither the electrode nor the vertical rising conductors to the ground floor, should ever be in contact with the foundation concrete. For existing buildings, the electrode conductor should be buried around the outside wall of the premises to a depth of at least 1 metre. As a general rule, all vertical connections from an electrode to above-ground level should be insulated for the nominal LV voltage (600-1,000 V). E11 The conductors may be: b Copper: Bare cable (u 25 mm2) or multiple-strip (u 25 mm2 and u 2 mm thick) b Aluminium with lead jacket: Cable (u 35 mm2) b Galvanised-steel cable: Bare cable (u 95 mm2) or multiple-strip (u 100 mm2 and u 3 mm thick) The approximate resistance R of the electrode in ohms: 2 where R= L where L = length of conductor in metres ρ = resistivity of the soil in ohm-metres (see “Influence of the type of soil” next page) Earthing rods (see Fig. E21) Vertically driven earthing rods are often used for existing buildings, and for improving (i.e. reducing the resistance of) existing earth electrodes. For n rods: R = 1 nL where The rods may be: b Copper or (more commonly) copper-clad steel. The latter are generally 1 or 2 metres long and provided with screwed ends and sockets in order to reach considerable depths, if necessary (for instance, the water-table level in areas of high soil resistivity) b Galvanised (see note (1) next page) steel pipe u 25 mm diameter or rod u 15 mm diameter, u 2 metres long in each case. Rods connected in parallel Fig. E20 : Conductor buried below the level of the foundations, i.e. not in the concrete Fig. E21 : Earthing rods Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Lu3m E - Distribution in low-voltage installations 1 Earthing schemes It is often necessary to use more than one rod, in which case the spacing between them should exceed the depth to which they are driven, by a factor of 2 to 3. The total resistance (in homogeneous soil) is then equal to the resistance of one rod, divided by the number of rods in question. The approximate resistance R obtained is: 1 R= if the distance separating the rods > 4L nL where where L = the length of the rod in metres ρ = resistivity of the soil in ohm-metres (see “Influence of the type of soil” below) n = the number of rods E12 Vertical plates (see Fig. E22) Rectangular plates, each side of which must be u 0.5 metres, are commonly used as earth electrodes, being buried in a vertical plane such that the centre of the plate is at least 1 metre below the surface of the soil. For a vertical plate electrode: R = 0.8 L The plates may be: b Copper of 2 mm thickness b Galvanised (1) steel of 3 mm thickness The resistance R in ohms is given (approximately), by: 0.8 R= L L = the perimeter of the plate in metres ρ = resistivity of the soil in ohm-metres (see “Influence of the type of soil” below) Influence of the type of soil Measurements on earth electrodes in similar soils are useful to determine the resistivity value to be applied for the design of an earthelectrode system Type of soil Swampy soil, bogs Silt alluvium Humus, leaf mould Peat, turf Soft clay Marl and compacted clay Jurassic marl Clayey sand Siliceous sand Stoney ground Grass-covered-stoney sub-soil Chalky soil Limestone Fissured limestone Schist, shale Mica schist Granite and sandstone Modified granite and sandstone Mean value of resistivity in Ωm 1 - 30 20 - 100 10 - 150 5 - 100 50 100 - 200 30 - 40 50 - 500 200 - 300 1,500 - 3,000 300 - 500 100 - 300 1,000 - 5,000 500 - 1,000 50 - 300 800 1,500 - 10,000 100 - 600 Fig. E23 : Resistivity (Ωm) for different types of soil Type of soil © Schneider Electric - all rights reserved 2 mm thickness (Cu) Fertile soil, compacted damp fill Arid soil, gravel, uncompacted non-uniform fill Stoney soil, bare, dry sand, fissured rocks Average value of resistivity in Ωm 50 500 3,000 Fig. E24 : Average resistivity (Ωm) values for approximate earth-elect Fig. E22 : Vertical plate (1) Where galvanised conducting materials are used for earth electrodes, sacrificial cathodic protection anodes may be necessary to avoid rapid corrosion of the electrodes where the soil is aggressive. Specially prepared magnesium anodes (in a porous sack filled with a suitable “soil”) are available for direct connection to the electrodes. In such circumstances, a specialist should be consulted Schneider Electric - Electrical installation guide 2009 1 Earthing schemes Measurement and constancy of the resistance between an earth electrode and the earth The resistance of the electrode/earth interface rarely remains constant Among the principal factors affecting this resistance are the following: b Humidity of the soil The seasonal changes in the moisture content of the soil can be significant at depths of up to 2 meters. At a depth of 1 metre the resistivity and therefore the resistance can vary by a ratio of 1 to 3 between a wet winter and a dry summer in temperate regions b Frost Frozen earth can increase the resistivity of the soil by several orders of magnitude. This is one reason for recommending the installation of deep electrodes, in particular in cold climates E13 b Ageing The materials used for electrodes will generally deteriorate to some extent for various reasons, for example: v Chemical reactions (in acidic or alkaline soils) v Galvanic: due to stray DC currents in the earth, for example from electric railways, etc. or due to dissimilar metals forming primary cells. Different soils acting on sections of the same conductor can also form cathodic and anodic areas with consequent loss of surface metal from the latter areas. Unfortunately, the most favourable conditions for low earth-electrode resistance (i.e. low soil resistivity) are also those in which galvanic currents can most easily flow. b Oxidation Brazed and welded joints and connections are the points most sensitive to oxidation. Thorough cleaning of a newly made joint or connection and wrapping with a suitable greased-tape binding is a commonly used preventive measure. Measurement of the earth-electrode resistance There must always be one or more removable links to isolate an earth electrode so that it can be tested. There must always be removable links which allow the earth electrode to be isolated from the installation, so that periodic tests of the earthing resistance can be carried out. To make such tests, two auxiliary electrodes are required, each consisting of a vertically driven rod. b Ammeter method (see Fig. E25) U t1 A T t2 Fig. E25 : Measurement of the resistance to earth of the earth electrode of an installation by means of an ammeter A = RT + Rt1 = UTt1 i1 B = Rt1 + Rt 2 = Ut1t 2 i2 C = Rt 2 + RT = Ut 2T i3 When the source voltage U is constant (adjusted to be the same value for each test) then: RT = U 1 1 + 2 i1 i3 1 i2 Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved E - Distribution in low-voltage installations E - Distribution in low-voltage installations 1 Earthing schemes In order to avoid errors due to stray earth currents (galvanic -DC- or leakage currents from power and communication networks and so on) the test current should be AC, but at a different frequency to that of the power system or any of its harmonics. Instruments using hand-driven generators to make these measurements usually produce an AC voltage at a frequency of between 85 Hz and 135 Hz. The distances between the electrodes are not critical and may be in different directions from the electrode being tested, according to site conditions. A number of tests at different spacings and directions are generally made to cross-check the test results. E14 b Use of a direct-reading earthing-resistance ohmmeter These instruments use a hand-driven or electronic-type AC generator, together with two auxiliary electrodes, the spacing of which must be such that the zone of influence of the electrode being tested should not overlap that of the test electrode (C). The test electrode (C) furthest from the electrode (X) under test, passes a current through the earth and the electrode under test, while the second test electrode (P) picks up a voltage. This voltage, measured between (X) and (P), is due to the test current and is a measure of the contact resistance (of the electrode under test) with earth. It is clear that the distance (X) to (P) must be carefully chosen to give accurate results. If the distance (X) to (C) is increased, however, the zones of resistance of electrodes (X) and (C) become more remote, one from the other, and the curve of potential (voltage) becomes more nearly horizontal about the point (O). In practical tests, therefore, the distance (X) to (C) is increased until readings taken with electrode (P) at three different points, i.e. at (P) and at approximately 5 metres on either side of (P), give similar values. The distance (X) to (P) is generally about 0.68 of the distance (X) to (C). VG G I V X P C voltage-drop due to the resistance of electrode (X) O VG voltage-drop due to the resistance of electrode (C) a) the principle of measurement is based on assumed homogeneous soil conditions. Where the zones of influence of electrodes C and X overlap, the location of test electrode P is difficult to determine for satisfactory results. X P C © Schneider Electric - all rights reserved O b) showing the effect on the potential gradient when (X) and (C) are widely spaced. The location of test electrode P is not critical and can be easily determined. Fig. E26 : Measurement of the resistance to the mass of earth of electrode (X) using an earthelectrode-testing ohmmeter. Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 2 The installation system Distribution switchboards, including the main LV switchboard (MLVS), are critical to the dependability of an electrical installation. They must comply with well-defined standards governing the design and construction of LV switchgear assemblies 2.1 Distribution switchboards A distribution switchboard is the point at which an incoming-power supply divides into separate circuits, each of which is controlled and protected by the fuses or switchgear of the switchboard. A distribution switchboard is divided into a number of functional units, each comprising all the electrical and mechanical elements that contribute to the fulfilment of a given function. It represents a key link in the dependability chain. Consequently, the type of distribution switchboard must be perfectly adapted to its application. Its design and construction must comply with applicable standards and working practises. The distribution switchboard enclosure provides dual protection: b Protection of switchgear, indicating instruments, relays, fusegear, etc. against mechanical impacts, vibrations and other external influences likely to interfere with operational integrity (EMI, dust, moisture, vermin, etc.) b The protection of human life against the possibility of direct and indirect electric shock (see degree of protection IP and the IK index in section 3.3 of Chapter E). E15 Types of distribution switchboards Distribution switchboards may differ according to the kind of application and the design principle adopted (notably in the arrangement of the busbars). The load requirements dictate the type of distribution switchboard to be installed Distribution switchboards according to specific applications The principal types of distribution switchboards are: b The main LV switchboard - MLVS - (see Fig. E27a) b Motor control centres - MCC - (see Fig. E27b) b Sub-distribution switchboards (see Fig. E28) b Final distribution switchboards (see Fig. E29) Distribution switchboards for specific applications (e.g. heating, lifts, industrial processes) can be located: b Adjacent to the main LV switchboard, or b Near the application concerned Sub-distribution and final distribution switchboards are generally distributed throughout the site. a b Fig. E27 : [a] A main LV switchboard - MLVS - (Prisma Plus P) with incoming circuits in the form of busways - [b] A LV motor control centre - MCC - (Okken) Fig. E28 : A sub-distribution switchboard (Prisma Plus G) b c Fig. E29 : Final distribution switchboards [a] Prisma Plus G Pack; [b] Kaedra; [c] mini-Pragma Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved a E - Distribution in low-voltage installations 2 The installation system A distinction is made between: b Traditional distribution switchboards in which switchgear and fusegear, etc. are fixed to a chassis at the rear of an enclosure b Functional distribution switchboards for specific applications, based on modular and standardised design. Traditional distribution switchboards Switchgear and fusegear, etc. are normally located on a chassis at the rear of the enclosure. Indications and control devices (meters, lamps, pushbuttons, etc.) are mounted on the front face of the switchboard. The placement of the components within the enclosure requires very careful study, taking into account the dimensions of each item, the connections to be made to it, and the clearances necessary to ensure safe and trouble-free operation. . Functional distribution switchboards Generally dedicated to specific applications, these distribution switchboards are made up of functional modules that include switchgear devices together with standardised accessories for mounting and connections, ensuring a high level of reliability and a great capacity for last-minute and future changes. b Many advantages The use of functional distribution switchboards has spread to all levels of LV electrical distribution, from the main LV switchboard (MLVS) to final distribution switchboards, due to their many advantages: v System modularity that makes it possible to integrate numerous functions in a single distribution switchboard, including protection, control, technical management and monitoring of electrical installations. Modular design also enhances distribution switchboard maintenance, operation and upgrades v Distribution switchboard design is fast because it simply involves adding functional modules v Prefabricated components can be mounted faster v Finally, these distribution switchboards are subjected to type tests that ensure a high degree of dependability. E16 Fig. E30 : Assembly of a final distribution switchboard with fixed functional units (Prisma Plus G) The new Prisma Plus G and P ranges of functional distribution switchboards from Schneider Electric cover needs up to 3200 A and offer: v Flexibility and ease in building distribution switchboards v Certification of a distribution switchboard complying with standard IEC 60439 and the assurance of servicing under safe conditions v Time savings at all stages, from design to installation, operation and modifications or upgrades v Easy adaptation, for example to meet the specific work habits and standards in different countries Figures E27a, E28 and E29 show examples of functional distribution switchboards ranging for all power ratings and figure E27b shows a high-power industrial functional distribution switchboard. b Main types of functional units Three basic technologies are used in functional distribution switchboards. v Fixed functional units (see Fig. E30) These units cannot be isolated from the supply so that any intervention for maintenance, modifications and so on, requires the shutdown of the entire distribution switchboard. Plug-in or withdrawable devices can however be used to minimise shutdown times and improve the availability of the rest of the installation. v Disconnectable functional units (see Fig. E31) Each functional unit is mounted on a removable mounting plate and provided with a means of isolation on the upstream side (busbars) and disconnecting facilities on the downstream (outgoing circuit) side. The complete unit can therefore be removed for servicing, without requiring a general shutdown. v Drawer-type withdrawable functional units (see Fig. E32) The switchgear and associated accessories for a complete function are mounted on a drawer-type horizontally withdrawable chassis. The function is generally complex and often concerns motor control. Isolation is possible on both the upstream and downstream sides by the complete withdrawal of the drawer, allowing fast replacement of a faulty unit without deenergising the rest of the distribution switchboard. Fig. E31 : Distribution switchboard with disconnectable functional units © Schneider Electric - all rights reserved Two technologies of distribution switchboards Fig. E32 : Distribution switchboard with withdrawable functional units in drawers Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 2 The installation system Standards Different standards Certain types of distribution switchboards (in particular, functional distribution switchboards) must comply with specific standards according to the application or environment involved. The reference international standard is IEC 60439-1 type-tested and partially typetested assemblies Three elements of standard IEC 60439-1 contribute significantly to dependability: b Clear definition of functional units b Forms of separation between adjacent functional units in accordance with user requirements b Clearly defined routine tests and type tests Form 1 Standard IEC 60439-1 b Categories of assemblies Standard IEC 60439-1 distinguishes between two categories of assemblies: v Type-tested LV switchgear and controlgear assemblies (TTA), which do not diverge significantly from an established type or system for which conformity is ensured by the type tests provided in the standard v Partially type-tested LV switchgear and controlgear assemblies (PTTA), which may contain non-type-tested arrangements provided that the latter are derived from typetested arrangements When implemented in compliance with professional work standards and manufacturer instructions by qualified personnel, they offer the same level of safety and quality. b Functional units The same standard defines functional units: v Part of an assembly comprising all the electrical and mechanical elements that contribute to the fulfilment of the same function v The distribution switchboard includes an incoming functional unit and one or more functional units for outgoing circuits, depending on the operating requirements of the installation What is more, distribution switchboard technologies use functional units that may be fixed, disconnectable or withdrawable (see section 3.1 of Chapter E). b Forms (see Fig. E33) Separation of functional units within the assembly is provided by forms that are specified for different types of operation. The various forms are numbered from 1 to 4 with variations labelled “a” or “b”. Each step up (from 1 to 4) is cumulative, i.e. a form with a higher number includes the characteristics of forms with lower numbers. The standard distinguishes: v Form 1: No separation v Form 2: Separation of busbars from the functional units v Form 3: Separation of busbars from the functional units and separation of all functional units, one from another, except at their output terminals v Form 4: As for Form 3, but including separation of the outgoing terminals of all functional units, one from another The decision on which form to implement results from an agreement between the manufacturer and the user. The Prima Plus functional range offers solutions for forms 1, 2b, 3b, 4a, 4b. Form 2a Form 2b Form 3a Busbar Separation Form 3b Form 4a Form 4b Fig. E33 : Representation of different forms of LV functional distribution switchboards Schneider Electric - Electrical installation guide 2009 E17 © Schneider Electric - all rights reserved Compliance with applicable standards is essential in order to ensure an adequate degree of dependability E - Distribution in low-voltage installations 2 The installation system b Type tests and routine tests They ensure compliance of each distribution switchboard with the standard. The availability of test documents certified by independent organisations is a guarantee for users. Total accessibility of electrical information and intelligent distribution switchboards are now a reality E18 Remote monitoring and control of the electrical installation Remote monitoring and control are no longer limited to large installations. These functions are increasingly used and provide considerable cost savings. The main potential advantages are: b Reductions in energy bills b Reductions in structural costs to maintain the installation in running order b Better use of the investment, notably concerning optimisation of the installation life cycle b Greater satisfaction for energy users (in a building or in process industries) due to improved power availability and/or quality The above possibilities are all the more an option given the current deregulation of the electrical-energy sector. Modbus is increasingly used as the open standard for communication within the distribution switchboard and between the distribution switchboard and customer power monitoring and control applications. Modbus exists in two forms, twisted pair (RS 485) and Ethernet-TCP/IP (IEEE 802.3). The www.modbus.org site presents all bus specifications and constantly updates the list of products and companies using the open industrial standard. The use of web technologies has largely contributed to wider use by drastically reducing the cost of accessing these functions through the use of an interface that is now universal (web pages) and a degree of openness and upgradeability that simply did not exist just a few years ago. 2.2 Cables and busway trunking Two types of distribution are possible: b By insulated wires and cables b By busbar trunking (busways) Distribution by insulated conductors and cables Definitions b Conductor A conductor comprises a single metallic core with or without an insulating envelope. b Cable A cable is made up of a number of conductors, electrically separated, but joined mechanically, generally enclosed in a protective flexible sheath. b Cableway © Schneider Electric - all rights reserved The term cableway refers to conductors and/or cables together with the means of support and protection, etc. for example : cable trays, ladders, ducts, trenches, and so on… are all “cableways”. Conductor marking Conductor identification must always respect the following three rules: b Rule 1 The double colour green and yellow is strictly reserved for the PE and PEN protection conductors. b Rule 2 v When a circuit comprises a neutral conductor, it must be light blue or marked “1” for cables with more than five conductors v When a circuit does not have a neutral conductor, the light blue conductor may be used as a phase conductor if it is part of a cable with more than one conductor b Rule 3 Phase conductors may be any colour except: v Green and yellow v Green v Yellow v Light blue (see rule 2) Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 2 The installation system Conductors in a cable are identified either by their colour or by numbers (see Fig. E34). Number of Circuit conductors in circuit 1 2 3 4 5 >5 Fixed cableways Insulated conductors Protection or earth Single-phase between phases Single-phase between phase and neutral Single-phase between phase and neutral + protection conductor Three-phase without neutral 2 phases + neutral 2 phases + protection conductor Single-phase between phase and neutral + protection conductor Three-phase with neutral Three-phase with neutral + protection conductor 2 phases + neutral + protection conductor Three-phase with PEN conductor Three-phase + neutral + protection conductor G/Y: Green and yellow BL: Black b : As indicated in rule 3 Ph Ph b b b b b b b b b b b Pn N PE G/Y LB G/Y b LB LB G/Y G/Y Rigid and flexible multiconductor cables Ph Ph Ph N BL BL BL LB BL BL BL BL B B LB PE LB G/Y E19 LB LB LB G/Y G/Y b b b LB BL B BL LB b b b G/Y BL B LB G/Y b b LB G/Y BL B LB G/Y b b b G/Y BL B LB G/Y b b b LB G/Y BL B BL LB G/Y Protection conductor: G/Y - Other conductors: BL: with numbering The number “1” is reserved for the neutral conductor if it exists LB: Light blue B: Brown Fig. E34 : Conductor identification according to the type of circuit Note: If the circuit includes a protection conductor and if the available cable does not have a green and yellow conductor, the protection conductor may be: b A separate green and yellow conductor b The blue conductor if the circuit does not have a neutral conductor b A black conductor if the circuit has a neutral conductor In the last two cases, the conductor used must be marked by green and yellow bands or markings at the ends and on all visible lengths of the conductor. Equipment power cords are marked similar to multi-conductor cables (see Fig. E35). Distribution and installation methods (see Fig. E36) Distribution takes place via cableways that carry single insulated conductors or cables and include a fixing system and mechanical protection. Final distribution swichboard Floor subdistribution swichboard Main LV switchboard (MLVS) Black conductor Heating, etc. Light blue conductor Building utilities sub-distribution swichboard Fig. E35 : Conductor identification on a circuit-breaker with a phase and a neutral Fig. E36 : Radial distribution using cables in a hotel Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved N E - Distribution in low-voltage installations 2 The installation system Busways, also referred to as busbar trunking systems, stand out for their ease of installation, flexibility and number of possible connection points Busbar trunking (busways) Busbar trunking is intended to distribute power (from 20 A to 5000 A) and lighting (in this application, the busbar trunking may play a dual role of supplying electrical power and physically holding the lights). Busbar trunking system components A busbar trunking system comprises a set of conductors protected by an enclosure (see Fig. E37). Used for the transmission and distribution of electrical power, busbar trunking systems have all the necessary features for fitting: connectors, straights, angles, fixings, etc. The tap-off points placed at regular intervals make power available at every point in the installation. E20 Straight trunking Power Unit Tap-off points to distribute current Fixing system for ceilings, walls or raised floor, etc. Range of clip-on tap-off units to connect a load (e.g.: a machine) to the busbar trunking End piece Angle Fig. E37 : Busbar trunking system design for distribution of currents from 25 to 4000 A. The various types of busbar trunking: © Schneider Electric - all rights reserved Busbar trunking systems are present at every level in electrical distribution: from the link between the transformer and the low voltage switch switchboard (MLVS) to the distribution of power sockets and lighting to offices, or power distribution to workshops. Fig. E38 : Radial distribution using busways We talk about a distributed network architecture. Schneider Electric - Electrical installation guide 2009 2 The installation system There are essentially three categories of busways. b Transformer to MLVS busbar trunking Installation of the busway may be considered as permanent and will most likely never be modified. There are no tap-off points. Frequently used for short runs, it is almost always used for ratings above 1,600 / 2,000 A, i.e. when the use of parallel cables makes installation impossible. Busways are also used between the MLVS and downstream distribution switchboards. The characteristics of main-distribution busways authorize operational currents from 1,000 to 5,000 A and short-circuit withstands up to 150 kA. b Sub-distribution busbar trunking with low or high tap-off densities Downstream of main-distribution busbar trunking , two types of applications must be supplied: v Mid-sized premises (industrial workshops with injection presses and metalwork machines or large supermarkets with heavy loads). The short-circuit and current levels can be fairly high (respectively 20 to 70 kA and 100 to 1,000 A) v Small sites (workshops with machine-tools, textile factories with small machines, supermarkets with small loads). The short-circuit and current levels are lower (respectively 10 to 40 kA and 40 to 400 A) Sub-distribution using busbar trunking meets user needs in terms of: v Modifications and upgrades given the high number of tap-off points v Dependability and continuity of service because tap-off units can be connected under energized conditions in complete safety The sub-distribution concept is also valid for vertical distribution in the form of 100 to 5,000 A risers in tall buildings. E21 b Lighting distribution busbar trunking Lighting circuits can be distributed using two types of busbar trunking according to whether the lighting fixtures are suspended from the busbar trunking or not. v busbar trunking designed for the suspension of lighting fixtures These busways supply and support light fixtures (industrial reflectors, discharge lamps, etc.). They are used in industrial buildings, supermarkets, department stores and warehouses. The busbar trunkings are very rigid and are designed for one or two 25 A or 40 A circuits. They have tap-off outlets every 0.5 to 1 m. v busbar trunking not designed for the suspension of lighting fixtures Similar to prefabricated cable systems, these busways are used to supply all types of lighting fixtures secured to the building structure. They are used in commercial buildings (offices, shops, restaurants, hotels, etc.), especially in false ceilings. The busbar trunking is flexible and designed for one 20 A circuit. It has tap-off outlets every 1.2 m to 3 m. Busbar trunking systems are suited to the requirements of a large number of buildings. b Industrial buildings: garages, workshops, farm buildings, logistic centers, etc. b Commercial areas: stores, shopping malls, supermarkets, hotels, etc. b Tertiary buildings: offices, schools, hospitals, sports rooms, cruise liners, etc. Standards Busbar trunking systems must meet all rules stated in IEC 439-2. This defines the manufacturing arrangements to be complied with in the design of busbar trunking systems (e.g.: temperature rise characteristics, short-circuit withstand, mechanical strength, etc.) as well as test methods to check them. Standard IEC 439-2 defines 13 compulsory type-tests on configurations or system components.. By assembling the system components on the site according to the assembly instructions, the contractor benefits from conformity with the standard. The advantages of busbar trunking systems Flexibility b Easy to change configuration (on-site modification to change production line configuration or extend production areas). b Reusing components (components are kept intact): when an installation is subject to major modifications, the busbar trunking is easy to dismantle and reuse. b Power availability throughout the installation (possibility of having a tap-off point every meter). b Wide choice of tap-off units. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved E - Distribution in low-voltage installations E - Distribution in low-voltage installations 2 The installation system Simplicity b Design can be carried out independently from the distribution and layout of current consumers. b Performances are independent of implementation: the use of cables requires a lot of derating coefficients. b Clear distribution layout b Reduction of fitting time: the trunking system allows fitting times to be reduced by up to 50% compared with a traditional cable installation. b Manufacturer’s guarantee. b Controlled execution times: the trunking system concept guarantees that there are no unexpected surprises when fitting. The fitting time is clearly known in advance and a quick solution can be provided to any problems on site with this adaptable and scalable equipment. b Easy to implement: modular components that are easy to handle, simple and quick to connect. E22 Dependability b Reliability guaranteed by being factory-built b Fool-proof units b Sequential assembly of straight components and tap-off units making it impossible to make any mistakes Continuity of service b The large number of tap-off points makes it easy to supply power to any new current consumer. Connecting and disconnecting is quick and can be carried out in complete safety even when energized. These two operations (adding or modifying) take place without having to stop operations. b Quick and easy fault location since current consumers are near to the line b Maintenance is non existent or greatly reduced Major contribution to sustainable development b Busbar trunking systems allow circuits to be combined. Compared with a traditional cable distribution system, consumption of copper raw materials and insulators is divided by 3 due to the busbar trunking distributed network concept (see Fig. E39). Distribution type Conductors Insulators Consumption Branched ΣIxks I1 R I2 I3 R R I4 R I5 R I6 R I7 R ks: clustering coefficient= 0.6 Alu: 128 mm² 4 kg Copper equivalent: 86 mm² 1 000 Joules Copper: 250 mm² 1 600 Joules Centralized ΣIxks I1 R I2 R I3 R I4 R I5 R I6 R I7 12 kg R ks: clustering coefficient= 0.6 Fig. E39 : Example: 30 m of Canalis KS 250A equipped with 10 25 A, four-pole feeders b Reusable device and all of its components are fully recyclable. b Does not contain PVC and does not generate toxic gases or waste. b Reduction of risks due to exposure to electromagnetic fields. © Schneider Electric - all rights reserved New functional features for Canalis Busbar trunking systems are getting even better. Among the new features we can mention: b Increased performance with a IP55 protection index and new ratings of 160 A through to 1000 A (Ks). b New lighting offers with pre-cabled lights and new light ducts. b New fixing accessories. Quick fixing system, cable ducts, shared support with “VDI” (voice, data, images) circuits. Schneider Electric - Electrical installation guide 2009 2 The installation system Busbar trunking systems are perfectly integrated with the environment: b white color to enhance the working environment, naturally integrated in a range of electrical distribution products. b conformity with European regulations on reducing hazardous materials (RoHS). Examples of Canalis busbar trunking systems E23 Fig. E40 : Flexible busbar trunking not capable of supporting light fittings : Canalis KDP (20 A) Fig. E41 : Rigid busbar trunking able to support light fittings : Canalis KBA or KBB (25 and 40 A) Fig. E42 : Lighting duct : Canalis KBX (25 A) Fig. E43 : A busway for medium power distribution : Canalis KN (40 up to 160 A) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved E - Distribution in low-voltage installations E - Distribution in low-voltage installations 2 The installation system Fig. E44 : A busway for medium power distribution : Canalis KS (100 up to 1000 A) E24 © Schneider Electric - all rights reserved Fig. E45 : A busway for high power distribution : Canalis KT (800 up to 1000 A) Schneider Electric - Electrical installation guide 2009 E - Distribution in low-voltage installations 3 External influences (IEC 60364-5-51) External influences shall be taken into account when choosing: b The appropriate measures to ensure the safety of persons (in particular in special locations or electrical installations) b The characteristics of electrical equipment, such as degree of protection (IP), mechanical withstand (IK), etc. 3.1 Definition and reference standards Every electrical installation occupies an environment that presents a variable degree of risk: b For people b For the equipment constituting the installation Consequently, environmental conditions influence the definition and choice of appropriate installation equipment and the choice of protective measures for the safety of persons. The environmental conditions are referred to collectively as “external influences”. Many national standards concerned with external influences include a classification scheme which is based on, or which closely resembles, that of international standard IEC 60364-5-51. If several external influences appear at the same time, they can have independent or mutual effects and the degree of protection must be chosen accordingly E25 3.2 Classification Each condition of external influence is designated by a code comprising a group of two capital letters and a number as follows: First letter (A, B or C) The first letter relates to the general category of external influence : b A = environment b B = utilisation b C = construction of buildings Second letter The second letter relates to the nature of the external influence. Number The number relates to the class within each external influence. Additional letter (optional) Used only if the effective protection of persons is greater than that indicated by the first IP digit. When only the protection of persons is to be specified, the two digits of the IP code are replaced by the X’s. Example: IP XXB. Example For example the code AC2 signifies: A = environment AC = environment-altitude AC2 = environment-altitude > 2,000 m 3.3 List of external influences Figure E46 below is from IEC 60364-5-51, which should be referred to if further details are required. Characteristics required for equipment Specially designed equipment or appropriate arrangements Normal (special precautions in certain cases) Normal Specially designed equipment or appropriate arrangements Fig. E46 : List of external influences (taken from Appendix A of IEC 60364-5-51) (continued on next page) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Code External influences A - Environment AA Ambient temperature (°C) Low High AA1 - 60 °C + 5 °C AA2 - 40 °C + 5 °C AA3 - 25 °C + 5 °C AA4 - 5° C + 40 °C AA5 + 5 °C + 40 °C AA6 + 5 °C + 60 °C AA7 - 25 °C + 55 °C AA8 - 50 °C + 40 °C E - Distribution in low-voltage installations E26 Code External influences A - Environment AB Atmospheric humidity Air temperature °C Low High AB1 - 60 °C + 5 °C AB2 - 40 °C + 5 °C AB3 - 25 °C + 5 °C AB4 - 5° C + 40 °C AB5 + 5 °C + 40 °C AB6 + 5 °C + 60 °C AB7 - 25 °C + 55 °C AB8 - 50 °C + 40 °C AC Altitude AC1 y 2000 m AC2 > 2000 m AD Presence of water AD1 Negligible AD2 Free-falling drops AD3 Sprays AD4 Splashes AD5 Jets AD6 Waves AD7 Immersion © Schneider Electric - all rights reserved AD8 AE AE1 AE2 AE3 AE4 AE5 AE6 AF AF1 AF2 AF3 AF4 AG AG1 AG2 AG3 AH AH1 AH2 AH3 AJ AK AH1 AH2 AL AH1 AH2 AM AM1 AM2 AM3 AM4 AM5 AM6 AM7 AM8 AM9 AM21 3 External influences (IEC 60364-5-51) Characteristics required for equipment Relative humidity % Low High 3 100 10 100 10 100 5 95 5 85 10 100 10 100 15 100 Absolute humidity g/m3 Low High 0.003 7 0.1 7 0.5 7 1 29 1 25 1 35 0.5 29 0.04 36 Appropriate arrangements shall be made Normal Normal Appropriate arrangements shall be made Normal May necessitate precaution (derating factors) Outdoor or non-weather protected locations IPX0 IPX1 or IPX2 IPX3 IPX4 IPX5 IPX6 IPX7 Locations where hose water is used regularly Seashore locations (piers, beaches, quays…) Water 150 mm above the highest point and equipment not more than 1m below the surface Submersion Equipment is permanently and totally covered IPX8 Presence of foreign solid bodies Smallest dimension Example Negligible IP0X Small objects 2.5 mm Tools IP3X Very small objects 1 mm Wire IP4X Light dust IP5X if dust penetration is not harmful to functioning Moderate dust IP6X if dust should not penetrate Heavy dust IP6X Presence of corrosive or polluting substances Negligible Normal Atmospheric According to the nature of the substance Intermittent, accidental Protection against corrosion Continuous Equipment specially designed Mechanical stress impact Low severity Normal Medium severity Standard where applicable or reinforced material High severity Reinforced protection Vibrations Low severity Household or similar Normal Medium severity Usual industrial conditions Specially designed equipment or special arrangements High severity Severe industrial conditions Other mechanical stresses Presence of flora and/or mould growth No hazard Normal Hazard Presence of fauna No hazard Normal Hazard Electromagnetic, electrostatic or ionising influences / Low frequency electromagnetic phenomena / Harmonics Harmonics, interharmonics Refer to applicable IEC standards Signalling voltage Voltage amplitude variations Voltage unbalance Power frequency variations Induced low-frequency voltages Direct current in a.c. networks Radiated magnetic fields Electric field Induced oscillatory voltages or currents Fig. E46 : List of external influences (taken from Appendix A of IEC 60364-5-51) (continued on next page) Schneider Electric - Electrical installation guide 2009 3 External influences (IEC 60364-5-51) Code External influences A - Environment AM22 Conducted unidirectional transients of the nanosecond time scale AM23 Conducted unidirectional transients of the microsecond to the millisecond time scale AM24 Conducted oscillatory transients AM25 Radiated high frequency phenomena AM31 Electrostatic discharges AM41 Ionisation AN Solar radiation AN1 Low AN2 Medium AN3 High AP Seismic effect AP1 Negligible AP2 Low severity AP3 Medium severity AP4 High severity AQ Lightning AQ1 Negligible AQ2 Indirect exposure AQ3 Direct exposure AR Movement of air AQ1 Low AQ2 Medium AQ3 High AS Wind AQ1 Low AQ2 Medium AQ3 High B - Utilization BA Capability of persons BA1 Ordinary BA2 Children BA3 Handicapped BA4 Instructed BA5 Skilled BB Electrical resistance of human body BC Contact of persons with earth potential BC1 None BC2 Low BC3 Frequent BC4 Continuous BD Condition of evacuation in case of emergency BD1 Low density / easy exit BD2 Low density / difficult exit BD3 High density / easy exit BD4 High density / difficult exit BE Nature of processed or stored materials BE1 No significant risks BE2 Fire risks BE3 Explosion risks BE4 Contamination risks C - Construction of building CA Construction materials CA1 Non combustible CA2 Combustible CB Building design CB1 Negligible risks CB2 Propagation of fire CB3 Movement CB4 lexible or unstable Characteristics required for equipment Refer to applicable IEC standards Normal E27 Normal Normal Normal Normal Normal Class of equipment according to IEC61140 Normal Normal Normal Normal Fig. E46 : List of external influences (taken from Appendix A of IEC 60364-5-51) (concluded) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved E - Distribution in low-voltage installations E - Distribution in low-voltage installations 3 External influences (IEC 60364-5-51) 3.4 Protection provided for enclosed equipment: codes IP and IK IP code definition (see Fig. E47) The degree of protection provided by an enclosure is indicated in the IP code, recommended in IEC 60529. Protection is afforded against the following external influences: b Penetration by solid bodies b Protection of persons against access to live parts b Protection against the ingress of dust b Protection against the ingress of liquids E28 Note: the IP code applies to electrical equipment for voltages up to and including 72.5 kV. Elements of the IP Code and their meanings A brief description of the IP Code elements is given in the following chart (see Fig. E48). Element Code letters First characteristic numeral Second characteristic numeral IP 2 3 C H Code letters (International Protection) First characteristic numeral (numerals 0 to 6, or letter X) Additional letter (optional) Second characteristic numeral (numerals 0 to 6, or letter X) Additional letter (optional) (letters A, B, C, D) © Schneider Electric - all rights reserved Supplementary letter (optional) (letters H, M, S, W) Where a characteristic numeral is not required to be specified, it shall be replaced by the letter "X" ("XX" if both numerals are omitted). Additional letters and/or supplementary letters may be omitted without replacement. Fig. E47 : IP Code arrangement Supplementary letter (optional) Numerals or letters Meaning for the protection of equipment Meaning for the protection of persons Against ingress of solid foreign objects Against access to hazardous parts with (non-protected) u 50 mm diameter u 12.5 mm diameter u 2.5 mm diameter u 1.0 mm diameter Dust-protected Dust-tight (non-protected) Back of hand Finger Too l Wire Wire Wire IP 0 1 2 3 4 5 6 Against ingress of water with harmful effects 0 1 2 3 4 5 6 7 8 (non-protected) Vertically dripping Dripping (15° tilted) Spraying Splashing Jetting Powerful jetting Temporary immersion Continuous immersion Against access to hazardous parts with A B C D H M S W back of hand Finger Too l Wire Supplementary information specific to: High-voltage apparatus Motion during water test Stationary during water test Weather conditions Fig. E48 : Elements of the IP Code Schneider Electric - Electrical installation guide 2009 3 External influences (IEC 60364-5-51) IK Code definition Standard IEC 62262 defines an IK code that characterises the aptitude of equipment to resist mechanical impacts on all sides (see Fig. E49). IK code 00 01 02 03 04 05 06 07 08 09 10 Impact energy (in Joules) 0 y 0.14 y 0.20 y 0.35 y 0.50 y 0.70 y1 y2 y5 y 10 y 20 AG code AG1 E29 AG2 AG3 AG4 Fig. E49 : Elements of the IK Code IP and IK code specifications for distribution switchboards The degrees of protection IP and IK of an enclosure must be specified as a function of the different external influences defined by standard IEC 60364-5-51, in particular: b Presence of solid bodies (code AE) b Presence of water (code AD) b Mechanical stresses (no code) b Capability of persons (code BA) b… Prisma Plus switchboards are designed for indoor installation. Unless the rules, standards and regulations of a specific country stipulate otherwise, Schneider Electric recommends the following IP and IK values (see Fig. E50 and Fig. E51 ) IP recommendations IP codes according to conditions Normal without risk of vertically falling water Normal with risk of vertically falling water Very severe with risk of splashing water from all directions Technical rooms Hallways Workshops 30 31 54/55 Technical rooms Hallways 07 08 (enclosure with door) 10 Fig. E50 : IP recommendations IK recommendations IK codes according to conditions No risk of major impact Significant risk of major impact that could damage devices Maximum risk of impact that could damage the enclosure Fig. E51 : IK recommendations Schneider Electric - Electrical installation guide 2009 Workshops © Schneider Electric - all rights reserved E - Distribution in low-voltage installations Chapter F Protection against electric shocks Contents 2 3 4 5 6 7 8 General F2 1.1 Electric shock F2 1.2 Protection against electric shock F3 1.3 Direct and indirect contact F3 Protection against direct contact F4 2.1 Measures of protection against direct contact F4 2.2 Additional measure of protection against direct contact F6 Protection against indirect contact F6 3.1 Measures of protection: two levels F6 3.2 Automatic disconnection for TT system F7 3.3 Automatic disconnection for TN systems F8 3.4 Automatic disconnection on a second fault in an IT system F10 3.5 Measures of protection against direct or indirect contact without automatic disconnection of supply F13 Protection of goods in case of insulation fault F17 4.1 Measures of protection against fire risk with RCDs F17 4.2 Ground Fault Protection (GFP) F17 Implementation of the TT system F19 5.1 Protective measures F19 5.2 Coordination of residual current protective devices F20 Implementation of the TN system F23 6.1 Preliminary conditions F23 6.2 Protection against indirect contact F23 6.3 High-sensitivity RCDs F27 6.4 Protection in high fire-risk locations F28 6.5 When the fault current-loop impedance is particularly high F28 Implementation of the IT system F29 7.1 Preliminary conditions F29 7.2 Protection against indirect contact F30 7.3 High-sensitivity RCDs F34 7.4 Protection in high fire-risk locations F35 7.5 When the fault current-loop impedance is particularly high F35 Residual current differential devices (RCDs) F36 8.1 Types of RCDs F36 8.2 Description F36 8.3 Sensitivity of RDCs to disturbances F39 F1 © Schneider Electric - all rights reserved 1 Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 1 General 1.1 Electric shock When a current exceeding 30 mA passes through a part of a human body, the person concerned is in serious danger if the current is not interrupted in a very short time. The protection of persons against electric shock in LV installations must be provided in conformity with appropriate national standards statutory regulations, codes of practice, official guides and circulars etc. Relevant IEC standards include: IEC 60364, IEC 60479 series, IEC 61008, IEC 61009 and IEC 60947-2. An electric shock is the pathophysiological effect of an electric current through the human body. Its passage affects essentially the muscular, circulatory and respiratory functions and sometimes results in serious burns. The degree of danger for the victim is a function of the magnitude of the current, the parts of the body through which the current passes, and the duration of current flow. IEC publication 60479-1 updated in 2005 defines four zones of current-magnitude/ time-duration, in each of which the pathophysiological effects are described (see Fig F1). Any person coming into contact with live metal risks an electric shock. Curve C1 shows that when a current greater than 30 mA passes through a human being from one hand to feet, the person concerned is likely to be killed, unless the current is interrupted in a relatively short time. The point 500 ms/100 mA close to the curve C1 corresponds to a probability of heart fibrillation of the order of 0.14%. F2 The protection of persons against electric shock in LV installations must be provided in conformity with appropriate national standards and statutory regulations, codes of practice, official guides and circulars, etc. Relevant IEC standards include: IEC 60364 series, IEC 60479 series, IEC 60755, IEC 61008 series, IEC 61009 series and IEC 60947-2. Duration of current flow I (ms) A 10,000 C1 C2 C3 B 5,000 AC-4.1 AC-4.2 2,000 AC-4.3 1,000 500 AC-1 AC-2 AC-3 AC-4 200 100 50 20 Body current Is (mA) 10 0.1 0.2 0.5 1 2 5 10 20 50 100 200 500 2,000 10,000 1,000 5,000 AC-1 zone: Imperceptible AC-2 zone: Perceptible A curve: Threshold of perception of current B curve: Threshold of muscular reactions AC-3 zone : Reversible effects: muscular contraction AC-4 zone: Possibility of irreversible effects C1 curve: Threshold of 0% probability of ventricular fibrillation C2 curve: Threshold of 5% probability of ventricular fibrillation C3 curve: Threshold of 50% probability of ventricular fibrillation AC-4-1 zone: Up to 5%probability of heart fibrillation AC-4-2 zone: Up to 50% probability of heart fibrillation AC-4-3 zone: More than 50% probability of heart fibrillation © Schneider Electric - all rights reserved Fig. F1 : Zones time/current of effects of AC current on human body when passing from left hand to feet Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 1 General 1.2 Protection against electric shock The fundamental rule of protection against electric shock is provided by the document IEC 61140 which covers both electrical installations and electrical equipment. Hazardous-live-parts shall not be accessible and accessible conductive parts shall not be hazardous. This requirement needs to apply under: b Normal conditions, and b Under a single fault condition Various measures are adopted to protect against this hazard, and include: b Automatic disconnection of the power supply to the connected electrical equipment b Special arrangements such as: v The use of class II insulation materials, or an equivalent level of insulation v Non-conducting location, out of arm’s reach or interposition of barriers v Equipotential bonding F3 v Electrical separation by means of isolating transformers 1.3 Direct and indirect contact Two measures of protection against direct contact hazards are often required, since, in practice, the first measure may not be infallible Direct contact A direct contact refers to a person coming into contact with a conductor which is live in normal circumstances (see Fig. F2). IEC 61140 standard has renamed “protection against direct contact” with the term “basic protection”. The former name is at least kept for information. Standards and regulations distinguish two kinds of dangerous contact, b Direct contact b Indirect contact and corresponding protective measures Indirect contact An indirect contact refers to a person coming into contact with an exposedconductive-part which is not normally alive, but has become alive accidentally (due to insulation failure or some other cause). The fault current raise the exposed-conductive-part to a voltage liable to be hazardous which could be at the origin of a touch current through a person coming into contact with this exposed-conductive-part (see Fig. F3). IEC 61140 standard has renamed “protection against indirect contact” with the term “fault protection”. The former name is at least kept for information. 1 1 2 3 2 3 PE N Id Busbars Insulation failure Is Is Fig. F2 : Direct contact Fig F3 : Indirect contact Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Id: Insulation fault current Is: Touch current F - Protection against electric shock 2 Protection against direct contact Two complementary measures are commonly used as protection against the dangers of direct contact: b The physical prevention of contact with live parts by barriers, insulation, inaccessibility, etc. b Additional protection in the event that a direct contact occurs, despite or due to failure of the above measures. This protection is based on residual-current operating device with a high sensitivity (IΔn y 30 mA) and a low operating time. These devices are highly effective in the majority of case of direct contact. IEC and national standards frequently distinguish two protections: b Complete (insulation, enclosures) b Partial or particular 2.1 Measures of protection against direct contact Protection by the insulation of live parts This protection consists of an insulation which complies with the relevant standards (see Fig. F4). Paints, lacquers and varnishes do not provide an adequate protection. F4 Fig. F4 : Inherent protection against direct contact by insulation of a 3-phase cable with outer sheath Protection by means of barriers or enclosures This measure is in widespread use, since many components and materials are installed in cabinets, assemblies, control panels and distribution boards (see Fig. F5). To be considered as providing effective protection against direct contact hazards, these equipment must possess a degree of protection equal to at least IP 2X or IP XXB (see chapter E sub-clause 3.4). Moreover, an opening in an enclosure (door, front panel, drawer, etc.) must only be removable, open or withdrawn: b By means of a key or tool provided for this purpose, or b After complete isolation of the live parts in the enclosure, or b With the automatic interposition of another screen removable only with a key or a tool. The metal enclosure and all metal removable screen must be bonded to the protective earthing conductor of the installation. Partial measures of protection b Protection by means of obstacles, or by placing out of arm’s reach This protection is reserved only to locations to which skilled or instructed persons only have access. The erection of this protective measure is detailed in IEC 60364-4-41. Particular measures of protection © Schneider Electric - all rights reserved Fig. F5 : Example of isolation by envelope b Protection by use of extra-low voltage SELV (Safety Extra-Low Voltage) or by limitation of the energy of discharge. These measures are used only in low-power circuits, and in particular circumstances, as described in section 3.5. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 2 Protection against direct contact An additional measure of protection against the hazards of direct contact is provided by the use of residual current operating device, which operate at 30 mA or less, and are referred to as RCDs of high sensitivity 2.2 Additional measure of protection against direct contact All the preceding protective measures are preventive, but experience has shown that for various reasons they cannot be regarded as being infallible. Among these reasons may be cited: b Lack of proper maintenance b Imprudence, carelessness b Normal (or abnormal) wear and tear of insulation; for instance flexure and abrasion of connecting leads b Accidental contact b Immersion in water, etc. A situation in which insulation is no longer effective In order to protect users in such circumstances, highly sensitive fast tripping devices, based on the detection of residual currents to earth (which may or may not be through a human being or animal) are used to disconnect the power supply automatically, and with sufficient rapidity to prevent injury to, or death by electrocution, of a normally healthy human being (see Fig. F6). F5 These devices operate on the principle of differential current measurement, in which any difference between the current entering a circuit and that leaving it (on a system supplied from an earthed source) be flowing to earth, either through faulty insulation or through contact of an earthed part, such as a person, with a live conductor. Standardised residual-current devices, referred to as RCDs, sufficiently sensitive for protection against direct contact are rated at 30 mA of differential current. According to IEC 60364-4-41, additional protection by means of high sensitivity RCDs (I∆n y 30 mA) must be provided for circuits supplying socket-outlets with a rated current y 20 A in all locations, and for circuits supplying mobile equipment with a rated current y 32 A for use outdoors. This additional protection is required in certain countries for circuits supplying socketoutlets rated up to 32 A, and even higher if the location is wet and/or temporary (such as work sites for instance). It is also recommended to limit the number of socket-outlets protected by a RCD (e.g. 10 socket-outlets for one RCD). Chapter P section 3 itemises various common locations in which RCDs of high sensitivity are obligatory (in some countries), but in any case, are highly recommended as an effective protection against both direct and indirect contact hazards. © Schneider Electric - all rights reserved Fig. F6 : High sensitivity RCD Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 3 Protection against indirect contact Exposed-conductive-parts used in the manufacturing process of an electrical equipment is separated from the live parts of the equipment by the “basic insulation”. Failure of the basic insulation will result in the exposed-conductive-parts being alive. Touching a normally dead part of an electrical equipment which has become live due to the failure of its insulation, is referred to as an indirect contact. 3.1 Measures of protection: two levels Protection against indirect contact hazards can be achieved by automatic disconnection of the supply if the exposed-conductive-parts of equipment are properly earthed F6 Two levels of protective measures exist: b 1st level: The earthing of all exposed-conductive-parts of electrical equipment in the installation and the constitution of an equipotential bonding network (see chapter G section 6). b 2sd level: Automatic disconnection of the supply of the section of the installation concerned, in such a way that the touch-voltage/time safety requirements are respected for any level of touch voltage Uc(1) (see Fig. F7). Earth connection Uc Fig. F7 : Illustration of the dangerous touch voltage Uc The greater the value of Uc, the greater the rapidity of supply disconnection required to provide protection (see Fig. F8). The highest value of Uc that can be tolerated indefinitely without danger to human beings is 50 V a.c. Reminder of the theoretical disconnecting-time limits Uo (V) 50 < Uo y 120 System TN or IT 0.8 TT 0.3 120 < Uo y 230 0.4 0.2 230 < Uo y 400 0.2 0.07 Uo > 400 0.1 0.04 © Schneider Electric - all rights reserved Fig. F8 : Maximum safe duration of the assumed values of AC touch voltage (in seconds) (1) Touch voltage Uc is the voltage existing (as the result of insulation failure) between an exposed-conductive-part and any conductive element within reach which is at a different (generally earth) potential. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 3 Protection against indirect contact 3.2 Automatic disconnection for TT system Automatic disconnection for TT system is achieved by RCD having a sensitivity of 50 I ni where RA is the resistance of the RA installation earth electrode Principle In this system all exposed-conductive-parts and extraneous-conductive-parts of the installation must be connected to a common earth electrode. The neutral point of the supply system is normally earthed at a pint outside the influence area of the installation earth electrode, but need not be so. The impedance of the earth-fault loop therefore consists mainly in the two earth electrodes (i.e. the source and installation electrodes) in series, so that the magnitude of the earth fault current is generally too small to operate overcurrent relay or fuses, and the use of a residual current operated device is essential. This principle of protection is also valid if one common earth electrode only is used, notably in the case of a consumer-type substation within the installation area, where space limitation may impose the adoption of a TN system earthing, but where all other conditions required by the TN system cannot be fulfilled. Protection by automatic disconnection of the supply used in TT system is by RCD of sensitivity: I ni 50 where R RA F7 where RA is the resistance of the earth electrode for the installation IΔn is the rated residual operating current of the RCD For temporary supplies (to work sites, …) and agricultural and horticultural premises, the value of 50 V is replaced by 25 V. Example (see Fig. F9) b The resistance of the earth electrode of substation neutral Rn is 10 Ω. b The resistance of the earth electrode of the installation RA is 20 Ω. b The earth-fault loop current Id = 7.7 A. b The fault voltage Uf = Id x RA = 154 V and therefore dangerous, but IΔn = 50/20 = 2.5 A so that a standard 300 mA RCD will operate in about 30 ms without intentional time delay and will clear the fault where a fault voltage exceeding appears on an exposed-conductive-part. Uo(1) (V) T (s) 50 < Uo y 120 0.3 120 < Uo y 230 0.2 230 < Uo y 400 0.07 Uo > 400 0.04 (1) Uo is the nominal phase to earth voltage Fig. F10 : Maximum disconnecting time for AC final circuits not exceeding 32 A Rn = 10 Ω RA = 20 Ω Uf Substation earth electrode Installation earth electrode Fig. F9 : Automatic disconnection of supply for TT system Specified maximum disconnection time The tripping times of RCDs are generally lower than those required in the majority of national standards; this feature facilitates their use and allows the adoption of an effective discriminative protection. The IEC 60364-4-41 specifies the maximum operating time of protective devices used in TT system for the protection against indirect contact: b For all final circuits with a rated current not exceeding 32 A, the maximum disconnecting time will not exceed the values indicated in Figure F10 b For all other circuits, the maximum disconnecting time is fixed to 1s. This limit enables discrimination between RCDs when installed on distribution circuits. RCD is a general term for all devices operating on the residual-current principle. RCCB (Residual Current Circuit-Breaker) as defined in IEC 61008 series is a specific class of RCD. Type G (general) and type S (Selective) of IEC 61008 have a tripping time/current characteristics as shown in Figure F11 next page. These characteristics allow a certain degree of selective tripping between the several combination of ratings and types, as shown later in sub-clause 4.3. Industrial type RCD according to IEC 60947-2 provide more possibilities of discrimination due to their flexibility of time-delaying. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 1 2 3 N PE F - Protection against electric shock 3 Protection against indirect contact x IΔn Domestic Industrial Instantaneous Type S Instantaneous Time-delay (0.06) Time-delay (other) 1 2 5 0.3 0.15 0.04 0.5 0.2 0.15 0.3 0.15 0.04 0.5 0.2 0.15 According to manufacturer >5 0.04 0.15 0.04 0.15 Fig. F11 : Maximum operating time of RCD’s (in seconds) 3.3 Automatic disconnection for TN systems F8 The automatic disconnection for TN system is achieved by overcurrent protective devices or RCD’s Principle In this system all exposed and extraneous-conductive-parts of the installation are connected directly to the earthed point of the power supply by protective conductors. As noted in Chapter E Sub-clause 1.2, the way in which this direct connection is carried out depends on whether the TN-C, TN-S, or TN-C-S method of implementing the TN principle is used. In figure F12 the method TN-C is shown, in which the neutral conductor acts as both the Protective-Earth and Neutral (PEN) conductor. In all TN systems, any insulation fault to earth results in a phase to neutral short-circuit. High fault current levels allow to use overcurrent protection but can give rise to touch voltages exceeding 50% of the phase to neutral voltage at the fault position during the short disconnection time. In practice for utility distribution network, earth electrodes are normally installed at regular intervals along the protective conductor (PE or PEN) of the network, while the consumer is often required to install an earth electrode at the service entrance. On large installations additional earth electrodes dispersed around the premises are often provided, in order to reduce the touch voltage as much as possible. In high-rise apartment blocks, all extraneous conductive parts are connected to the protective conductor at each level. In order to ensure adequate protection, the earth-fault current Uo Uo must be higher or equal to Ia, where: or 0.8 I Zc Zs b Uo = nominal phase to neutral voltage b Id = the fault current b Ia = current equal to the value required to operate the protective device in the time specified b Zs = earth-fault current loop impedance, equal to the sum of the impedances of the source, the live phase conductors to the fault position, the protective conductors from the fault position back to the source b Zc = the faulty-circuit loop impedance (see “conventional method” Sub-clause 6.2) Id = Note: The path through earth electrodes back to the source will have (generally) much higher impedance values than those listed above, and need not be considered. B A 1 2 3 PEN F E N NSX160 35 mm2 © Schneider Electric - all rights reserved 50 m 35 mm2 D C Uf Example (see Fig. F12) 230 = 115 V and is hazardous; The fault voltage Uf = 2 The fault loop impedance Zs=ZAB + ZBC + ZDE + ZEN + ZNA. If ZBC and ZDE are predominant, then: L sothat that = 64.3 m , ,so S 230 = 3,576 A ((≈ 22 In based on a NSX160 circuit-breaker). I d= 64.3 x10 -3 The “instantaneous” magnetic trip unit adjustment of the circuit-breaker is many time less than this short-circuit value, so that positive operation in the shortest possible time is assured. Zs = 2 Note: Some authorities base such calculations on the assumption that a voltage drop of 20% occurs in the part of the impedance loop BANE. This method, which is recommended, is explained in chapter F sub-clause 6.2 Fig. F12 : Automatic disconnection in TN system “conventional method” and in this example will give an estimated fault current of 230 x 0.8 x 103 = 2,816 A ((≈ 18 In). 64.3 Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 3 Protection against indirect contact Specified maximum disconnection time The IEC 60364-4-41 specifies the maximum operating time of protective devices used in TN system for the protection against indirect contact: b For all final circuits with a rated current not exceeding 32 A, the maximum disconnecting time will not exceed the values indicated in Figure F13 b For all other circuits, the maximum disconnecting time is fixed to 5s. This limit enables discrimination between protective devices installed on distribution circuits Note: The use of RCDs may be necessary on TN-earthed systems. Use of RCDs on TN-C-S systems means that the protective conductor and the neutral conductor must (evidently) be separated upstream of the RCD. This separation is commonly made at the service entrance. Uo(1) (V) T (s) 50 < Uo y 120 0.8 120 < Uo y 230 0.4 230 < Uo y 400 0.2 Uo > 400 0.1 (1) Uo is the nominal phase to earth voltage F9 Fig. F13 : Maximum disconnecting time for AC final circuits not exceeding 32 A Protection by means of circuit-breaker (see Fig. F14) If the protection is to be provided by a circuitbreaker, it is sufficient to verify that the fault current will always exceed the current-setting level of the instantaneous or short-time delay tripping unit (Im) The instantaneous trip unit of a circuit-breaker will eliminate a short-circuit to earth in less than 0.1 second. In consequence, automatic disconnection within the maximum allowable time will always be assured, since all types of trip unit, magnetic or electronic, instantaneous or slightly retarded, are suitable: Ia = Im. The maximum tolerance authorised by the relevant standard, however, must always be taken into consideration. It is Uo Uo determined calculation sufficient therefore that the fault current determined byby calculation (or estimated or 0.8 Zs Zc (or estimated on site) be greater than the instantaneous trip-setting current, or than the very short-time tripping threshold level, to be sure of tripping within the permitted time limit. Protection by means of fuses (see Fig. F15) Ia can be determined from the fuse performance curve. In any case, protection The value of current which assures the correct operation of a fuse can be ascertained from a current/time performance graph for the fuse concerned. cannot be achieved if the loop impedance Zs Uo Uo or Zc exceeds a certain value therefore thatThe the fault current determined by calculation estimated or 0.8 as determined above, must(or largely exceed that Zs Zc necessary to ensure positive operation of the fuse. The condition to observe Uo Uo therefore as as indicated in Figure F15. or 0.8 therefore is that I a < indicated in Figure F15. Zs Zc t t 1: Short-time delayed trip 2: Instantaneous trip 2 Im Uo/Zs Fig. F14 : Disconnection by circuit-breaker for a TN system I Ia Uo/Zs Fig. F15 : Disconnection by fuses for a TN system Schneider Electric - Electrical installation guide 2009 I © Schneider Electric - all rights reserved tc = 0.4 s 1 F - Protection against electric shock 3 Protection against indirect contact Example: The nominal phase to neutral voltage of the network is 230 V and the maximum disconnection time given by the graph in Figure F15 is 0.4 s. The corresponding value of Ia can be read from the graph. Using the voltage (230 V) and the current IIa, the complete loop impedance or the circuit loop impedance can 230 230 . This impedance value must never be be calculated from Zs = or Zc = 0.8 Ia Ia exceeded and should preferably be substantially less to ensure satisfactory fuse operation. Protection by means of Residual Current Devices for TN-S circuits Residual Current Devices must be used where: b The loop impedance cannot be determined precisely (lengths difficult to estimate, presence of metallic material close to the wiring) b The fault current is so low that the disconnecting time cannot be met by using overcurrent protective devices The rated tripping current of RCDs being in the order of a few amps, it is well below the fault current level. RCDs are consequently well adapted to this situation. F10 In practice, they are often installed in the LV sub distribution and in many countries, the automatic disconnection of final circuits shall be achieved by Residual Current Devices. 3.4 Automatic disconnection on a second fault in an IT system In this type of system: b The installation is isolated from earth, or the neutral point of its power-supply source is connected to earth through a high impedance b All exposed and extraneous-conductive-parts are earthed via an installation earth electrode. First fault situation In IT system the first fault to earth should not cause any disconnection On the occurrence of a true fault to earth, referred to as a “first fault”, the fault current is very low, such that the rule Id x RA y 50 V (see F3.2) is fulfilled and no dangerous fault voltages can occur. In practice the current Id is low, a condition that is neither dangerous to personnel, nor harmful to the installation. However, in this system: b A permanent monitoring of the insulation to earth must be provided, coupled with an alarm signal (audio and/or flashing lights, etc.) operating in the event of a first earth fault (see Fig. F16) b The rapid location and repair of a first fault is imperative if the full benefits of the IT system are to be realised. Continuity of service is the great advantage afforded by the system. © Schneider Electric - all rights reserved For a network formed from 1 km of new conductors, the leakage (capacitive) impedance to earth Zf is of the order of 3,500 Ω per phase. In normal operation, the capacitive current(1) to earth is therefore: Uo 230 = = 66 mA per phase. Zf 3,500 During a phase to earth fault, as indicated in Figure F17 opposite page, the current passing through the electrode resistance RnA is the vector sum of the capacitive currents in the two healthy phases. The voltages of the healthy phases have (because of the fault) increased to 3 the normal phase voltage, so that the capacitive currents increase by the same amount. These currents are displaced, one from the other by 60°, so that when added vectorially, this amounts to 3 x 66 mA = 198 mA, in the present example. The fault voltage Uf is therefore equal to 198 x 5 x 10-3 = 0.99 V, which is obviously harmless. The current through the short-circuit to earth is given by the vector sum of the neutral-resistor current Id1 (=153 mA) and the capacitive current Id2 (198 mA). Since the exposed-conductive-parts of the installation are connected directly to earth, the neutral impedance Zct plays practically no part in the production of touch voltages to earth. Fig. F16 : Phases to earth insulation monitoring device obligatory in IT system (1) Resistive leakage current to earth through the insulation is assumed to be negligibly small in the example. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 3 Protection against indirect contact Id1 + Id2 Id1 1 2 3 N PE B Zf Zct = 1,500 Ω Ω RnA = 5 Ω Id2 Uf F11 Fig. F17 : Fault current path for a first fault in IT system Second fault situation On the appearance of a second fault, on a different phase, or on a neutral conductor, a rapid disconnection becomes imperative. Fault clearance is carried out differently in each of the following cases: The simultaneous existence of two earth faults (if not both on the same phase) is dangerous, and rapid clearance by fuses or automatic circuit-breaker tripping depends on the type of earth-bonding scheme, and whether separate earthing electrodes are used or not, in the installation concerned 1st case It concerns an installation in which all exposed conductive parts are bonded to a common PE conductor, as shown in Figure F18. In this case no earth electrodes are included in the fault current path, so that a high level of fault current is assured, and conventional overcurrent protective devices are used, i.e. circuit-breakers and fuses. The first fault could occur at the end of a circuit in a remote part of the installation, while the second fault could feasibly be located at the opposite end of the installation. For this reason, it is conventional to double the loop impedance of a circuit, when calculating the anticipated fault setting level for its overcurrent protective device(s). Where the system includes a neutral conductor in addition to the 3 phase conductors, the lowest short-circuit fault currents will occur if one of the (two) faults is from the neutral conductor to earth (all four conductors are insulated from earth in an IT scheme). In four-wire IT installations, therefore, the phase-to-neutral voltage must Uo (1) where u I a (1) be used to calculate short-circuit protective levels i.e. i.e. 0.8 2 Zc Uo = phase to neutral voltage Zc = impedance of the circuit fault-current loop (see F3.3) Ia = current level for trip setting If no neutral conductor is distributed, then the voltage to use for the fault-current 3 Uo (1) calculationisisthe thephase-to-phase phase-to-phasevalue, value, i.e. i.e. 0.8 calculation u I a (1) 2 Zc b Maximum tripping times Disconnecting times for IT system depends on how the different installation and substation earth electrodes are interconnected. For final circuits supplying electrical equipment with a rated current not exceeding 32 A and having their exposed-conductive-parts connected to an independent earth electrode electrically separated from the substation earth electrode, the maximum tripping time is given in Figure F13. For the other circuits within the same group of non interconnected exposed-conductive-parts, the maximum disconnecting time is 1s. This is due to the fact that any double fault situation resulting from one insulation fault within this group and another insulation fault from another group will generate a fault current limited by the different earth electrode resistances as in TT system. (1) Based on the “conventional method” noted in the first example of Sub-clause 3.3. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved For final circuits supplying electrical equipment with a rated current not exceeding 32 A and having their exposed-conductive-parts bonded with the substation earth electrode, the maximum tripping time is given in table F8. For the other circuits within the same group of interconnected exposed-conductive-parts, the maximum disconnecting time is 5 s. This is due to the fact that any double fault situation within this group will result in a short-circuit current as in TN system. F - Protection against electric shock 3 Protection against indirect contact Id K A B J F NSX160 160 A 50 m 35 mm2 G 1 2 3 N PE E 50 m 35 mm2 H D C RA F12 Fig. F18 : Circuit-breaker tripping on double fault situation when exposed-conductive-parts are connected to a common protective conductor b Protection by circuit-breaker In the case shown in Figure F18, the adjustments of instantaneous and short-time delay overcurrent trip unit must be decided. The times recommended here above can be readily complied with. The short-circuit protection provided by the NSX160 circuitbreaker is suitable to clear a phase to phase short-circuit occurring at the load ends of the circuits concerned. Reminder: In an IT system, the two circuits involved in a phase to phase short-circuit are assumed to be of equal length, with the same cross sectional area conductors, the PE conductors being the same cross sectional area as the phase conductors. In such a case, the impedance of the circuit loop when using the “conventional method” (sub clause 6.2) will be twice that calculated for one of the circuits in the TN case, shown in Chapter F sub clause 3.3. L in m where: The resistance of circuit loop FGHJ == 2RJH = 2 where: a ρ = resistance of copper rod 1 meter long of cross sectional area 1 mm2, in mΩ L = length of the circuit in meters a = cross sectional area of the conductor in mm2 FGHJ = 2 x 22.5 x 50/35 = 64.3 mΩ and the loop resistance B, C, D, E, F, G, H, J will be 2 x 64.3 = 129 mΩ. The fault current will therefore be 0.8 x 3 x 230 x 103/129 = 2,470 A. b Protection by fuses The current Ia for which fuse operation must be assured in a time specified according to here above can be found from fuse operating curves, as described in figure F15. The current indicated should be significantly lower than the fault currents calculated for the circuit concerned. b Protection by Residual current circuit-breakers (RCCBs) For low values of short-circuit current, RCCBs are necessary. Protection against indirect contact hazards can be achieved then by using one RCCB for each circuit. 2nd case b It concerns exposed conductive parts which are earthed either individually (each part having its own earth electrode) or in separate groups (one electrode for each group). © Schneider Electric - all rights reserved If all exposed conductive parts are not bonded to a common electrode system, then it is possible for the second earth fault to occur in a different group or in a separately earthed individual apparatus. Additional protection to that described above for case 1, is required, and consists of a RCD placed at the circuit-breaker controlling each group and each individually-earthed apparatus. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 3 Protection against indirect contact The reason for this requirement is that the separate-group electrodes are “bonded” through the earth so that the phase to phase short-circuit current will generally be limited when passing through the earth bond by the electrode contact resistances with the earth, thereby making protection by overcurrent devices unreliable. The more sensitive RCDs are therefore necessary, but the operating current of the RCDs must evidently exceed that which occurs for a first fault (see Fig. F19). Leakage capacitance (µF) 1 5 30 First fault current (A) 0.07 0.36 2.17 Note: 1 µF is the 1 km typical leakage capacitance for 4-conductor cable. F13 Fig. F19 : Correspondence between the earth leakage capacitance and the first fault current For a second fault occurring within a group having a common earth-electrode system, the overcurrent protection operates, as described above for case 1. Note 1: See also Chapter G Sub-clause 7.2, protection of the neutral conductor. Note 2: In 3-phase 4-wire installations, protection against overcurrent in the neutral conductor is sometimes more conveniently achieved by using a ring-type current transformer over the single-core neutral conductor (see Fig. F20). Case 1 Case 2 RCD N RCD N Ω PIM RCD RCD Ω PIM Group earth 1 Group earth RA Rn Rn RA1 Group earth 2 RA2 Fig. F20 : Application of RCDs when exposed-conductive-parts are earthed individually or by group on IT system 3.5 Measures of protection against direct or indirect contact without automatic disconnection of supply The use of SELV (Safety Extra-Low Voltage) Safety by extra low voltage SELV is used in situations where the operation of electrical equipment presents a serious hazard (swimming pools, amusement parks, etc.). This measure depends on supplying power at extra-low voltage from the secondary windings of isolating transformers especially designed according to national or to international (IEC 60742) standard. The impulse withstand level of insulation between the primary and secondary windings is very high, and/or an earthed metal screen is sometimes incorporated between the windings. The secondary voltage never exceeds 50 V rms. Three conditions of exploitation must be respected in order to provide satisfactory protection against indirect contact: b No live conductor at SELV must be connected to earth b Exposed-conductive-parts of SELV supplied equipment must not be connected to earth, to other exposed conductive parts, or to extraneous-conductive-parts b All live parts of SELV circuits and of other circuits of higher voltage must be separated by a distance at least equal to that between the primary and secondary windings of a safety isolating transformer. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Extra-low voltage is used where the risks are great: swimming pools, wandering-lead hand lamps, and other portable appliances for outdoor use, etc. F - Protection against electric shock 3 Protection against indirect contact These measures require that: b SELV circuits must use conduits exclusively provided for them, unless cables which are insulated for the highest voltage of the other circuits are used for the SELV circuits b Socket outlets for the SELV system must not have an earth-pin contact. The SELV circuit plugs and sockets must be special, so that inadvertent connection to a different voltage level is not possible. Note: In normal conditions, when the SELV voltage is less than 25 V, there is no need to provide protection against direct contact hazards. Particular requirements are indicated in Chapter P, Clause 3: “special locations”. The use of PELV (Protection by Extra Low Voltage) (see Fig. F21) This system is for general use where low voltage is required, or preferred for safety reasons, other than in the high-risk locations noted above. The conception is similar to that of the SELV system, but the secondary circuit is earthed at one point. IEC 60364-4-41 defines precisely the significance of the reference PELV. Protection against direct contact hazards is generally necessary, except when the equipment is in the zone of equipotential bonding, and the nominal voltage does not exceed 25 V rms, and the equipment is used in normally dry locations only, and large-area contact with the human body is not expected. In all other cases, 6 V rms is the maximum permitted voltage, where no direct contact protection is provided. F14 230 V / 24 V Fig. F21 : Low-voltage supplies from a safety isolating transformer FELV system (Functional Extra-Low Voltage) Where, for functional reasons, a voltage of 50 V or less is used, but not all of the requirements relating to SELV or PELV are fulfilled, appropriate measures described in IEC 60364-4-41 must be taken to ensure protection against both direct and indirect contact hazards, according to the location and use of these circuits. Note: Such conditions may, for example, be encountered when the circuit contains equipment (such as transformers, relays, remote-control switches, contactors) insufficiently insulated with respect to circuits at higher voltages. The electrical separation of circuits is suitable for relatively short cable lengths and high levels of insulation resistance. It is preferably used for an individual appliance The electrical separation of circuits (see Fig. F22) The principle of the electrical separation of circuits (generally single-phase circuits) for safety purposes is based on the following rationale. The two conductors from the unearthed single-phase secondary winding of a separation transformer are insulated from earth. If a direct contact is made with one conductor, a very small current only will flow into the person making contact, through the earth and back to the other conductor, via the inherent capacitance of that conductor with respect to earth. Since the conductor capacitance to earth is very small, the current is generally below the level of perception. As the length of circuit cable increases, the direct contact current will progressively increase to a point where a dangerous electric shock will be experienced. © Schneider Electric - all rights reserved 230 V/230 V Fig. F22 : Safety supply from a class II separation transformer Even if a short length of cable precludes any danger from capacitive current, a low value of insulation resistance with respect to earth can result in danger, since the current path is then via the person making contact, through the earth and back to the other conductor through the low conductor-to-earth insulation resistance. For these reasons, relatively short lengths of well insulated cables are essential in separation systems. Transformers are specially designed for this duty, with a high degree of insulation between primary and secondary windings, or with equivalent protection, such as an earthed metal screen between the windings. Construction of the transformer is to class II insulation standards. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 3 Protection against indirect contact As indicated before, successful exploitation of the principle requires that: b No conductor or exposed conductive part of the secondary circuit must be connected to earth, b The length of secondary cabling must be limited to avoid large capacitance values(1), b A high insulation-resistance value must be maintained for the cabling and appliances. These conditions generally limit the application of this safety measure to an individual appliance. In the case where several appliances are supplied from a separation transformer, it is necessary to observe the following requirements: b The exposed conductive parts of all appliances must be connected together by an insulated protective conductor, but not connected to earth, b The socket outlets must be provided with an earth-pin connection. The earth-pin connection is used in this case only to ensure the interconnection (bonding) of all exposed conductive parts. In the case of a second fault, overcurrent protection must provide automatic disconnection in the same conditions as those required for an IT system of power system earthing. F15 Class II equipment Class II equipment symbol: These appliances are also referred to as having “double insulation” since in class II appliances a supplementary insulation is added to the basic insulation (see Fig. F23). No conductive parts of a class II appliance must be connected to a protective conductor: b Most portable or semi-fixed equipment, certain lamps, and some types of transformer are designed to have double insulation. It is important to take particular care in the exploitation of class II equipment and to verify regularly and often that the class II standard is maintained (no broken outer envelope, etc.). Electronic devices, radio and television sets have safety levels equivalent to class II, but are not formally class II appliances b Supplementary insulation in an electrical installation: IEC 60364-4-41(Sub-clause 413-2) and some national standards such as NF C 15-100 (France) describe in more detail the necessary measures to achieve the supplementary insulation during installation work. Active part Basic insulation Supplementary insulation Fig. F23 : Principle of class II insulation level A simple example is that of drawing a cable into a PVC conduit. Methods are also described for distribution switchboards. b For distribution switchboards and similar equipment, IEC 60439-1 describes a set of requirements, for what is referred to as “total insulation”, equivalent to class II b Some cables are recognised as being equivalent to class II by many national standards Out-of-arm’s reach or interposition of obstacles By these means, the probability of touching a live exposed-conductive-part, while at the same time touching an extraneous-conductive-part at earth potential, is extremely low (see Fig. F24 next page). In practice, this measure can only be applied in a dry location, and is implemented according to the following conditions: b The floor and the wall of the chamber must be non-conducting, i.e. the resistance to earth at any point must be: v > 50 kΩ (installation voltage y 500 V) v > 100 kΩ (500 V < installation voltage y 1000 V) Resistance is measured by means of “MEGGER” type instruments (hand-operated generator or battery-operated electronic model) between an electrode placed on the floor or against the wall, and earth (i.e. the nearest protective earth conductor). The electrode contact area pressure must be evidently be the same for all tests. (1) It is recommended in IEC 364-4-41 that the product of the nominal voltage of the circuit in volts and length in metres of the wiring system should not exceed 100,000, and that the length of the wiring system should not exceed 500 m. Different instruments suppliers provide electrodes specific to their own product, so that care should be taken to ensure that the electrodes used are those supplied with the instrument. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved In principle, safety by placing simultaneouslyaccessible conductive parts out-of-reach, or by interposing obstacles, requires also a nonconducting floor, and so is not an easily applied principle F - Protection against electric shock 3 Protection against indirect contact b The placing of equipment and obstacles must be such that simultaneous contact with two exposed-conductive-parts or with an exposed conductive-part and an extraneous-conductive-part by an individual person is not possible. b No exposed protective conductor must be introduced into the chamber concerned. b Entrances to the chamber must be arranged so that persons entering are not at risk, e.g. a person standing on a conducting floor outside the chamber must not be able to reach through the doorway to touch an exposed-conductive-part, such as a lighting switch mounted in an industrial-type cast-iron conduit box, for example. Insulated walls Insulated obstacles F16 2.5 m Electrical apparatus Electrical apparatus Electrical apparatus Insulated floor >2m <2m Fig. F24 : Protection by out-of arm’s reach arrangements and the interposition of non-conducting obstacles Earth-free equipotential chambers are associated with particular installations (laboratories, etc.) and give rise to a number of practical installation difficulties Earth-free equipotential chambers In this scheme, all exposed-conductive-parts, including the floor (1) are bonded by suitably large conductors, such that no significant difference of potential can exist between any two points. A failure of insulation between a live conductor and the metal envelope of an appliance will result in the whole “cage” being raised to phaseto-earth voltage, but no fault current will flow. In such conditions, a person entering the chamber would be at risk (since he/she would be stepping on to a live floor). Suitable precautions must be taken to protect personnel from this danger (e.g. nonconducting floor at entrances, etc.). Special protective devices are also necessary to detect insulation failure, in the absence of significant fault current. M © Schneider Electric - all rights reserved Conductive floor Insulating material Fig. F25 : Equipotential bonding of all exposed-conductive-parts simultaneously accessible (1) Extraneous conductive parts entering (or leaving) the equipotential space (such as water pipes, etc.) must be encased in suitable insulating material and excluded from the equipotential network, since such parts are likely to be bonded to protective (earthed) conductors elsewhere in the installation. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 4 Protection of goods in case of insulation fault The standards consider the damage (mainly fire) of goods due to insulation faults to be high. Therefore, for location with high risk of fire, 300 mA Residual Current Devices must be used. For the other locations, some standards relies on technique called « Ground Fault Protection » (GFP). 4.1 Measures of protection against fire risk with RCDs RCDs are very effective devices to provide protection against fire risk due to insulation fault because they can detect leakage current (ex : 300 mA) wich are too low for the other protections, but sufficient to cause a fire RCDs are very effective devices to provide protection against fire risk due to insulation fault. This type of fault current is actually too low to be detected by the other protection (overcurrent, reverse time). For TT, IT TN-S systems in which leakage current can appear, the use of 300 mA sensitivity RCDs provides a good protection against fire risk due to this type of fault. An investigation has shown that the cost of the fires in industrial and tertiary buildings can be very great. F17 The analysis of the phenomena shows that fire risk due to electicity is linked to overheating due to a bad coordination between the maximum rated current of the cable (or isolated conductor) and the overcurrent protection setting. Overheating can also be due to the modification of the initial method of installation (addition of cables on the same support). This overheating can be the origin of electrical arc in humid environment. These electrical arcs evolve when the fault current-loop impedance is greater than 0.6 Ω and exist only when an insulation fault occurs. Some tests have shown that a 300 mA fault current can induce a real risk of fire (see Fig. F26). 4.2 Ground Fault Protection (GFP) Beginning of fire Different type of ground fault protections (see Fig. F27) Three types of GFP are possible dependind on the measuring device installed : b “Residual Sensing” RS The “insulation fault” current is calculated using the vectorial sum of currents of current transformers secondaries. The current transformer on the neutral conductor is often outside the circuit-breaker. Id << 300 mA Humid dust Some tests have shown that a very low leakage current (a few mA) can evolve and, from 300 mA, induce a fire in humid and dusty environment. b “Source Ground Return” SGR The « insulation fault current » is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker. b “Zero Sequence” ZS The « insulation fault » is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values. Fig. F26 : Origin of fires in buildings RS system SGR system ZS system R R L1 L1 L2 L3 N L2 L3 L1 L2 L3 N N PE Fig. F27 : Different types of ground fault protections Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved R F - Protection against electric shock 4 Protection of goods in case of insulation fault Positioning GFP devices in the installation Type / installation level Source Ground Return (SGR) Main-distribution v Sub-distribution Comments Used Residual Sensing (RS) (SGR) v b Often used Zero Sequence (SGR) v b Rarely used v Possible b Recommended or required © Schneider Electric - all rights reserved F18 Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 5 Implementation of the TT system 5.1 Protective measures Protection against indirect contact General case Protection against indirect contact is assured by RCDs, the sensitivity IΔn of which 50 V (1)(1) complies with the condition I n i RA The choice of sensitivity of the residual current device is a function of the resistance RA of the earth electrode for the installation, and is given in Figure F28. IΔn 3A 1A 500 mA 300 mA 30 mA Maximum resistance of the earth electrode (50 V) (25 V) 16 Ω 8Ω 50 Ω 25 Ω 100 Ω 50 Ω 166 Ω 83 Ω 1666 Ω 833 Ω F19 Fig. F28 : The upper limit of resistance for an installation earthing electrode which must not be exceeded, for given sensitivity levels of RCDs at UL voltage limits of 50 V and 25 V Case of distribution circuits (see Fig. F29) IEC 60364-4-41 and a number of national standards recognize a maximum tripping time of 1 second in installation distribution circuits (as opposed to final circuits). This allows a degree of selective discrimination to be achieved: b At level A: RCD time-delayed, e.g. “S” type b At level B: RCD instantaneous Case where the exposed conductive parts of an appliance, or group of appliances, are connected to a separate earth electrode (see Fig. F30) Protection against indirect contact by a RCD at the circuit-breaker level protecting each group or separately-earthed individual appliance. A RCD In each case, the sensitivity must be compatible with the resistance of the earth electrode concerned. High-sensitivity RCDs (see Fig. F31) RCD Fig. F29 : Distribution circuits RA1 RA2 Distant location Fig. F30 : Separate earth electrode Fig. F31 : Circuit supplying socket-outlets (1) 25 V for work-site installations, agricultural establishments, etc. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for protection of socket outlets with rated current y 20 A in all locations. The use of such RCDs is also recommended in the following cases: b Socket-outlet circuits in wet locations at all current ratings b Socket-outlet circuits in temporary installations b Circuits supplying laundry rooms and swimming pools b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs See 2.2 and chapter P, section 3 B RCD F - Protection against electric shock 5 Implementation of the TT system In high fire risk locations (see Fig. F32) RCD protection at the circuit-breaker controlling all supplies to the area at risk is necessary in some locations, and mandatory in many countries. The sensitivity of the RCD must be y 500 mA, but a 300 mA sensitivity is recommended. Protection when exposed conductive parts are not connected to earth (see Fig. F33) (In the case of an existing installation where the location is dry and provision of an earthing connection is not possible, or in the event that a protective earth wire becomes broken). RCDs of high sensitivity (y 30 mA) will afford both protection against indirect-contact hazards, and the additional protection against the dangers of direct-contact. F20 Fire-risk location Fig. F32 : Fire-risk location Fig. F33 : Unearthed exposed conductive parts (A) 5.2 Coordination of residual current protective devices Discriminative-tripping coordination is achieved either by time-delay or by subdivision of circuits, which are then protected individually or by groups, or by a combination of both methods. Such discrimination avoids the tripping of any RCD, other than that immediately upstream of a fault position: b With equipment currently available, discrimination is possible at three or four different levels of distribution : v At the main general distribution board v At local general distribution boards v At sub-distribution boards v At socket outlets for individual appliance protection b In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards. Discrimination between RCDs © Schneider Electric - all rights reserved The general specification for achieving total discrimination between two RCDs is as follow: b The ratio between the rated residual operating currents must be > 2 b Time delaying the upstream RCD Discrimination is achieved by exploiting the several levels of standardized sensitivity: 30 mA, 100 mA, 300 mA and 1 A and the corresponding tripping times, as shown opposite page in Figure F34. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 5 Implementation of the TT system t (ms) 10,000 1,000 500 300 250 200 150 130 100 II I 60 40 selective RCDs domestic S F21 and industrial (settings I and II) RCD 30 mA general domestic and industrial setting 0 Current (mA) 1,000 500 600 60 300 30 150 15 100 10 1 1.5 10 100 500 1,000 (A) Fig. F34 : Total discrimination at 2 levels Discrimination at 2 levels (see Fig. F35) A b Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic device) for protection against indirect contacts b Level B: RCD instantaneous, with high sensitivity on circuits supplying socketoutlets or appliances at high risk (washing machines, etc.) See also Chapter P Clause 3 Protection RCD 300 mA type S RCD 30 mA B Schneider Electric solutions b Level A: Compact or Multi 9 circuit-breaker with adaptable RCD module (Vigi NSX160 or Vigi NC100), setting I or S type b Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable RCD module (e.g. Vigi C60 or Vigi NC100) or Vigicompact Fig. F35 : Total discrimination at 2 levels Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents. Relay with separate toroidal CT 3 A delay time 500 ms B Discrimination at 3 or 4 levels (see Fig. F36) Protection b Level A: RCD time-delayed (setting III) b Level B: RCD time-delayed (setting II) b Level C: RCD time-delayed (setting I) or type S b Level D: RCD instantaneous RCCB 1 A delay time 250 ms C RCCB 300 A delay time 50 ms or type S D Fig. F36 : Total discrimination at 3 or 4 levels RCCB 30 mA Schneider Electric solutions b Level A: Circuit-breaker associated with RCD and separate toroidal transformer (Vigirex RH328AP) b Level B: Vigicompact or Vigirex b Level C: Vigirex, Vigicompact or Vigi NC100 or Vigi C60 b Level D: v Vigicompact or v Vigirex or v Multi 9 with integrated or adaptable RCD module : Vigi C60 or DPN Vigi Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved A F - Protection against electric shock 5 Implementation of the TT system Discriminative protection at three levels (see Fig. F37) Withdrawable Masterpact or Visucompact MV/LV F22 NSX400 NSX100 MA Discont. Vigicompact NSX100 Setting 1 300 mA NC100L MA instantaneous 300 mA NC100 diff. 300 mA selective S © Schneider Electric - all rights reserved Leakage current of the filter: 20 mA Terminal board Leakage current equal to 3.5 mA per socket outlet (Information technology equipement): max 4 sockets outlets. Fig. F37 : Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 6 Implementation of the TN system 6.1 Preliminary conditions At the design stage, the maximum permitted lengths of cable downstream of a protective circuit-breaker (or set of fuses) must be calculated, while during the installation work certain rules must be fully respected. Certain conditions must be observed, as listed below and illustrated in Figure F38. 1. PE conductor must be regularly connected to earth as much as possible. 2. The PE conductor must not pass through ferro-magnetic conduit, ducts, etc. or be mounted on steel work, since inductive and/or proximity effects can increase the effective impedance of the conductor. 3. In the case of a PEN conductor (a neutral conductor which is also used as a protective conductor), connection must be made directly to the earth terminal of an appliance (see 3 in Figure F38) before being looped to the neutral terminal of the same appliance. 4. Where the conductor y 6 mm2 for copper or 10 mm2 for aluminium, or where a cable is movable, the neutral and protective conductors should be separated (i.e. a TN-S system should be adopted within the installation). 5. Earth faults may be cleared by overcurrent-protection devices, i.e. by fuses and circuit-breakers. The foregoing list indicates the conditions to be respected in the implementation of a TN scheme for the protection against indirect contacts. F23 5 2 2 5 1 5 PE N 4 PEN 3 TN-C system TN-C-S system RpnA Notes: b The TN scheme requires that the LV neutral of the MV/LV transformer, the exposed conductive parts of the substation and of the installation, and the extraneous conductive parts in the substation and installation, all be earthed to a common earthing system. b For a substation in which the metering is at low-voltage, a means of isolation is required at the origin of the LV installation, and the isolation must be clearly visible. b A PEN conductor must never be interrupted under any circumstances. Control and protective switchgear for the several TN arrangements will be: v 3-pole when the circuit includes a PEN conductor, v Preferably 4-pole (3 phases + neutral) when the circuit includes a neutral with a separate PE conductor. Fig. F38 : Implementation of the TN system of earthing 6.2 Protection against indirect contact Methods of determining levels of short-circuit current In TN-earthed systems, a short-circuit to earth will, in principle, always provide sufficient current to operate an overcurrent device. The source and supply mains impedances are much lower than those of the installation circuits, so that any restriction in the magnitude of earth-fault currents will be mainly caused by the installation conductors (long flexible leads to appliances greatly increase the “fault-loop” impedance, with a corresponding reduction of shortcircuit current). The most recent IEC recommendations for indirect-contact protection on TN earthing systems only relates maximum allowable tripping times to the nominal system voltage (see Figure F12 in Sub-clause 3.3). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Three methods of calculation are commonly used: b The method of impedances, based on the trigonometric addition of the system resistances and inductive reactances b The method of composition b The conventional method, based on an assumed voltage drop and the use of prepared tables F - Protection against electric shock 6 Implementation of the TN system The reasoning behind these recommendations is that, for TN systems, the current which must flow in order to raise the potential of an exposed conductive part to 50 V or more is so high that one of two possibilities will occur: b Either the fault path will blow itself clear, practically instantaneously, or b The conductor will weld itself into a solid fault and provide adequate current to operate overcurrent devices To ensure correct operation of overcurrent devices in the latter case, a reasonably accurate assessment of short-circuit earth-fault current levels must be determined at the design stage of a project. A rigorous analysis requires the use of phase-sequence-component techniques applied to every circuit in turn. The principle is straightforward, but the amount of computation is not considered justifiable, especially since the zero-phase-sequence impedances are extremely difficult to determine with any reasonable degree of accuracy in an average LV installation. Other simpler methods of adequate accuracy are preferred. Three practical methods are: F24 b The “method of impedances”, based on the summation of all the impedances (positive-phase-sequence only) around the fault loop, for each circuit b The “method of composition”, which is an estimation of short-circuit current at the remote end of a loop, when the short-circuit current level at the near end of the loop is known b The “conventional method” of calculating the minimum levels of earth-fault currents, together with the use of tables of values for obtaining rapid results These methods are only reliable for the case in which the cables that make up the earth-fault-current loop are in close proximity (to each other) and not separated by ferro-magnetic materials. For calculations, modern practice is to use software agreed by National Authorities, and based on the method of impedances, such as Ecodial 3. National Authorities generally also publish Guides, which include typical values, conductor lengths, etc. Method of impedances This method summates the positive-sequence impedances of each item (cable, PE conductor, transformer, etc.) included in the earth-fault loop circuit from which the short-circuit earth-fault current is calculated, using the formula: U I= 2 2 R + X ( ) ( ) where (ΣR) 2 = (the sum of all resistances in the loop)2 at the design stage of a project. and (ΣX) 2 = (the sum of all inductive reactances in the loop) 2 and U = nominal system phase-to-neutral voltage. The application of the method is not always easy, because it supposes a knowledge of all parameter values and characteristics of the elements in the loop. In many cases, a national guide can supply typical values for estimation purposes. Method of composition This method permits the determination of the short-circuit current at the end of a loop from the known value of short-circuit at the sending end, by means of the approximate formula: U I = Isc U+ Zs. I sc where Isc = upstream short-circuit current I = end-of-loop short-circuit current U = nominal system phase voltage Zs = impedance of loop © Schneider Electric - all rights reserved Note: in this method the individual impedances are added arithmetically(1) as opposed to the previous “method of impedances” procedure. Conventional method This method is generally considered to be sufficiently accurate to fix the upper limit of cable lengths. Principle (1) This results in a calculated current value which is less than that it would actually flow. If the overcurrent settings are based on this calculated value, then operation of the relay, or fuse, is assured. The principle bases the short-circuit current calculation on the assumption that the voltage at the origin of the circuit concerned (i.e. at the point at which the circuit protective device is located) remains at 80% or more of the nominal phase to neutral voltage. The 80% value is used, together with the circuit loop impedance, to compute the short-circuit current. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 6 Implementation of the TN system This coefficient takes account of all voltage drops upstream of the point considered. In LV cables, when all conductors of a 3-phase 4-wire circuit are in close proximity (which is the normal case), the inductive reactance internal to and between conductors is negligibly small compared to the cable resistance. This approximation is considered to be valid for cable sizes up to 120 mm2. Above that size, the resistance value R is increased as follows: The maximum length of any circuit of a TN-earthed installation is:= 0.8 Uo Sph (1+ m) I a Core size (mm2) S = 150 mm2 S = 185 mm2 S = 240 mm2 Value of resistance R+15% R+20% R+25% The maximum length of a circuit in a TN-earthed installation is given by the formula: 0.8 Uo Sph Lmax = (1+ m) I a where: Lmax = maximum length in metres Uo = phase volts = 230 V for a 230/400 V system ρ = resistivity at normal working temperature in ohm-mm2/metre (= 22.5 10-3 for copper; = 36 10-3 for aluminium) Ia = trip current setting for the instantaneous operation of a circuit-breaker, or Ia = the current which assures operation of the protective fuse concerned, in the specified time. Sph m= SPE F25 Sph = cross-sectional area of the phase conductors of the circuit concerned in mm2 SPE = cross-sectional area of the protective conductor concerned in mm2. (see Fig. F39) The following tables give the length of circuit which must not be exceeded, in order that persons be protected against indirect contact hazards by protective devices Tables The following tables, applicable to TN systems, have been established according to the “conventional method” described above. The tables give maximum circuit lengths, beyond which the ohmic resistance of the conductors will limit the magnitude of the short-circuit current to a level below that required to trip the circuit-breaker (or to blow the fuse) protecting the circuit, with sufficient rapidity to ensure safety against indirect contact. Correction factor m Figure F40 indicates the correction factor to apply to the values given in Figures F41 to F44 next pages, according to the ratio Sph/SPE, the type of circuit, and the conductor materials. A The tables take into account: b The type of protection: circuit-breakers or fuses b Operating-current settings b Cross-sectional area of phase conductors and protective conductors b Type of system earthing (see Fig. F45 page F27) b Type of circuit-breaker (i.e. B, C or D)(1) B PE Imagn The tables may be used for 230/400 V systems. Id Equivalent tables for protection by Compact and Multi 9 circuit-breakers (Merlin Gerin) are included in the relevant catalogues. L Sph Circuit C 3P + N or P + N Fig. F39 : Calculation of L max. for a TN-earthed system, using the conventional method Conductor material Copper Aluminium m = Sph/SPE (or PEN) m=1 m=2 m=3 1 0.67 0.50 0.62 0.42 0.31 Fig. F40 : Correction factor to apply to the lengths given in tables F40 to F43 for TN systems (1) For the definition of type B, C, D circuit-breakers, refer to chapter H, clause 4.2 Schneider Electric - Electrical installation guide 2009 m=4 0.40 0.25 © Schneider Electric - all rights reserved SPE F - Protection against electric shock 6 Implementation of the TN system Circuits protected by general purpose circuit-breakers (Fig. F41) F26 Nominal crosssectional area of conductors mm2 50 63 1.5 100 79 2.5 167 133 4 267 212 6 400 317 10 16 25 35 50 70 95 120 150 185 240 Instantaneous or short-time-delayed tripping current Im (amperes) 80 63 104 167 250 417 100 50 83 133 200 333 125 40 67 107 160 267 427 160 31 52 83 125 208 333 200 25 42 67 100 167 267 417 250 20 33 53 80 133 213 333 467 320 16 26 42 63 104 167 260 365 495 400 13 21 33 50 83 133 208 292 396 500 10 17 27 40 67 107 167 233 317 560 9 15 24 36 60 95 149 208 283 417 630 8 13 21 32 53 85 132 185 251 370 700 7 12 19 29 48 76 119 167 226 333 452 800 6 10 17 25 42 67 104 146 198 292 396 875 6 10 15 23 38 61 95 133 181 267 362 457 1000 5 8 13 20 33 53 83 117 158 233 317 400 435 1120 4 7 12 18 30 48 74 104 141 208 283 357 388 459 1250 4 7 11 16 27 43 67 93 127 187 263 320 348 411 1600 2000 2500 3200 4000 5000 6300 8000 10000 12500 5 8 13 21 33 52 73 99 146 198 250 272 321 400 4 7 10 17 27 42 58 79 117 158 200 217 257 320 5 8 13 21 33 47 63 93 127 160 174 206 256 4 6 10 17 26 36 49 73 99 125 136 161 200 5 8 13 21 29 40 58 79 100 109 128 160 4 7 11 17 23 32 47 63 80 87 103 128 5 8 13 19 25 37 50 63 69 82 102 4 7 10 15 20 29 40 50 54 64 80 5 8 12 16 23 32 40 43 51 64 4 7 9 13 19 25 32 35 41 51 Fig. F41 : Maximum circuit lengths (in metres) for different sizes of copper conductor and instantaneous-tripping-current settings for general-purpose circuit-breakers in 230/240 V TN system with m = 1 Circuits protected by Compact or Multi 9 circuit-breakers for industrial or domestic use (Fig. F42 to Fig. F44) Sph mm2 1.5 2.5 4 6 10 16 25 35 50 Rated current (A) 1 2 3 1200 600 400 1000 666 1066 4 300 500 800 1200 6 200 333 533 800 10 120 200 320 480 800 16 75 125 200 300 500 800 20 60 100 160 240 400 640 25 48 80 128 192 320 512 800 32 37 62 100 150 250 400 625 875 40 30 50 80 120 200 320 500 700 50 24 40 64 96 160 256 400 560 760 63 19 32 51 76 127 203 317 444 603 80 15 25 40 60 100 160 250 350 475 100 12 20 32 48 80 128 200 280 380 125 10 16 26 38 64 102 160 224 304 © Schneider Electric - all rights reserved Fig. F42 : Maximum circuit lengths (in meters) for different sizes of copper conductor and rated currents for type B (1) circuit-breakers in a 230/240 V single-phase or three-phase TN system with m = 1 Sph mm2 1.5 2.5 4 6 10 16 25 35 50 Rated current (A) 1 2 3 600 300 200 500 333 533 4 150 250 400 600 6 100 167 267 400 667 10 60 100 160 240 400 640 16 37 62 100 150 250 400 625 875 20 30 50 80 120 200 320 500 700 25 24 40 64 96 160 256 400 560 760 32 18 31 50 75 125 200 312 437 594 40 15 25 40 60 100 160 250 350 475 50 12 20 32 48 80 128 200 280 380 63 9 16 25 38 63 101 159 222 301 80 7 12 20 30 50 80 125 175 237 100 6 10 16 24 40 64 100 140 190 125 5 8 13 19 32 51 80 112 152 Fig. F43 : Maximum circuit lengths (in metres) for different sizes of copper conductor and rated currents for type C (1) circuit-breakers in a 230/240 V single-phase or three-phase TN system with m = 1 (1) For the definition of type B and C circuit-breakers refer to chapter H clause 4.2. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock Sph mm2 1.5 2.5 4 6 10 16 25 35 50 Rated current (A) 1 2 3 429 214 143 714 357 238 571 381 857 571 952 6 Implementation of the TN system 4 107 179 286 429 714 6 71 119 190 286 476 762 10 43 71 114 171 286 457 714 16 27 45 71 107 179 286 446 625 20 21 36 80 120 200 320 500 700 848 25 17 29 46 69 114 183 286 400 543 32 13 22 36 54 89 143 223 313 424 40 11 18 29 43 71 114 179 250 339 50 9 14 23 34 57 91 143 200 271 63 7 11 18 27 45 73 113 159 215 80 5 9 14 21 36 57 89 125 170 100 4 7 11 17 29 46 71 80 136 125 3 6 9 14 23 37 57 100 109 Fig. F44 : Maximum circuit lengths (in metres) for different sizes of copper conductor and rated currents for type D (1) circuit-breakers in a 230/240 V single-phase or three-phase TN system with m = 1 F27 Example A 3-phase 4-wire (230/400 V) installation is TN-C earthed. A circuit is protected by a type B circuit-breaker rated at 63 A, and consists of an aluminium cored cable with 50 mm2 phase conductors and a neutral conductor (PEN) of 25 mm2. What is the maximum length of circuit, below which protection of persons against indirect-contact hazards is assured by the instantaneous magnetic tripping relay of the circuit-breaker? Figure F42 gives, for 50 mm2 and a 63 A type B circuit-breaker, 603 metres, to which Sph must be applied a factor of 0.42 (Figure F40 for m = = 2).. SPE The maximum length of circuit is therefore: 603 x 0.42 = 253 metres. RA1 RA2 Distant location Particular case where one or more exposed conductive part(s) is (are) earthed to a separate earth electrode Protection must be provided against indirect contact by a RCD at the origin of any circuit supplying an appliance or group of appliances, the exposed conductive parts of which are connected to an independent earth electrode. Fig. F45 : Separate earth electrode The sensitivity of the RCD must be adapted to the earth electrode resistance (RA2 in Figure F45). See specifications applicable to TT system. 6.3 High-sensitivity RCDs (see Fig. F31) Fig. F46 : Circuit supplying socket-outlets (1) For the definition of type D circuit-breaker refer to chapter H Sub-clause 4.2. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for protection of socket outlets with rated current y 20 A in all locations. The use of such RCDs is also recommended in the following cases: b Socket-outlet circuits in wet locations at all current ratings b Socket-outlet circuits in temporary installations b Circuits supplying laundry rooms and swimming pools b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs See 2.2 and chapter P, al section 3. F - Protection against electric shock 6 Implementation of the TN system 6.4 Protection in high fire-risk location According to IEC 60364-422-3.10, circuits in high fire-risk locations must be protected by RCDs of sensitivity y 500 mA. This excludes the TN-C arrangement and TN-S must be adopted. A preferred sensitivity of 300 mA is mandatory in some countries (see Fig. F47). 6.5 When the fault current-loop impedance is particularly high When the earth-fault current is limited due to an inevitably high fault-loop impedance, so that the overcurrent protection cannot be relied upon to trip the circuit within the prescribed time, the following possibilities should be considered: Suggestion 1 (see Fig. F48) b Install a circuit-breaker which has a lower instantaneous magnetic tripping level, for example: F28 2In y Irm y 4In This affords protection for persons on circuits which are abnormally long. It must be checked, however, that high transient currents such as the starting currents of motors will not cause nuisance trip-outs. b Schneider Electric solutions v Type G Compact (2Im y Irm y 4Im) v Type B Multi 9 circuit-breaker Fire-risk location Suggestion 2 (see Fig. F49) b Install a RCD on the circuit. The device does not need to be highly-sensitive (HS) (several amps to a few tens of amps). Where socket-outlets are involved, the particular circuits must, in any case, be protected by HS (y 30 mA) RCDs; generally one RCD for a number of socket outlets on a common circuit. b Schneider Electric solutions v RCD Multi 9 NG125 : IΔn = 1 or 3 A v Vigicompact REH or REM: IΔn = 3 to 30 A v Type B Multi 9 circuit-breaker Fig. F47 : Fire-risk location Suggestion 3 Increase the size of the PE or PEN conductors and/or the phase conductors, to reduce the loop impedance. PE or PEN 2 y Irm y 4In Suggestion 4 Add supplementary equipotential conductors. This will have a similar effect to that of suggestion 3, i.e. a reduction in the earth-fault-loop resistance, while at the same time improving the existing touch-voltage protection measures. The effectiveness of this improvement may be checked by a resistance test between each exposed conductive part and the local main protective conductor. Great length of cable Fig. F48 : Circuit-breaker with low-set instantaneous magnetic tripping For TN-C installations, bonding as shown in Figure F50 is not allowed, and suggestion 3 should be adopted. Phases © Schneider Electric - all rights reserved Neutral PE Fig. F49 : RCD protection on TN systems with high earth-faultloop impedance Fig. F50 : Improved equipotential bonding Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 7 Implementation of the IT system The basic feature of the IT earthing system is that, in the event of a short-circuit to earth fault, the system can continue to operate without interruption. Such a fault is referred to as a “first fault”. In this system, all exposed conductive parts of an installation are connected via PE conductors to an earth electrode at the installation, while the neutral point of the supply transformer is: b Either isolated from earth b Or connected to earth through a high resistance (commonly 1,000 ohms or more) This means that the current through an earth fault will be measured in milli-amps, which will not cause serious damage at the fault position, or give rise to dangerous touch voltages, or present a fire hazard. The system may therefore be allowed to operate normally until it is convenient to isolate the faulty section for repair work. This enhances continuity of service. In practice, the system earthing requires certain specific measures for its satisfactory exploitation: b Permanent monitoring of the insulation with respect to earth, which must signal (audibly or visually) the occurrence of the first fault b A device for limiting the voltage which the neutral point of the supply transformer can reach with respect to earth b A “first-fault” location routine by an efficient maintenance staff. Fault location is greatly facilitated by automatic devices which are currently available b Automatic high-speed tripping of appropriate circuit-breakers must take place in the event of a “second fault” occurring before the first fault is repaired. The second fault (by definition) is an earth fault affecting a different live conductor than that of the first fault (can be a phase or neutral conductor)(1). F29 The second fault results in a short-circuit through the earth and/or through PE bonding conductors. 7.1 Preliminary conditions (see Fig. F51 and Fig. F52) Minimum functions required Protection against overvoltages at power frequency Neutral earthing resistor (for impedance earthing variation) Components and devices (1) Voltage limiter Examples Cardew C (2) Resistor Impedance Zx Overall earth-fault monitor with alarm for first fault condition Automatic fault clearance on second fault and protection of the neutral conductor against overcurrent Location of first fault (3) Permanent insulation monitor PIM with alarm feature (4) Four-pole circuit-breakers (if the neutral is distributed) all 4 poles trip Vigilohm TR22A or XM 200 Compact circuit-breaker or RCD-MS (5) With device for fault-location on live system, or by successive opening of circuits Vigilohm system Fig. F51 : Essential functions in IT schemes and examples with Merlin Gerin products 4 L1 L2 L3 N 4 4 2 1 3 5 Fig. F52 : Positions of essential functions in 3-phase 3-wire IT-earthed system (1) On systems where the neutral is distributed, as shown in Figure F56. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved HV/LV F - Protection against electric shock 7 Implementation of the IT system 7.2 Protection against indirect contact Modern monitoring systems greatly facilitate first-fault location and repair First-fault condition The earth-fault current which flows under a first-fault condition is measured in milliamps. The fault voltage with respect to earth is the product of this current and the resistance of the installation earth electrode and PE conductor (from the faulted component to the electrode). This value of voltage is clearly harmless and could amount to several volts only in the worst case (1,000 Ω earthing resistor will pass 230 mA(1) and a poor installation earth-electrode of 50 ohms, would give 11.5 V, for example). An alarm is given by the permanent insulation monitoring device. Principle of earth-fault monitoring A generator of very low frequency a.c. current, or of d.c. current, (to reduce the effects of cable capacitance to negligible levels) applies a voltage between the neutral point of the supply transformer and earth. This voltage causes a small current to flow according to the insulation resistance to earth of the whole installation, plus that of any connected appliance. F30 Low-frequency instruments can be used on a.c. systems which generate transient d.c. components under fault conditions. Certain versions can distinguish between resistive and capacitive components of the leakage current. Modern equipment allow the measurement of leakage-current evolution, so that prevention of a first fault can be achieved. Fault-location systems comply with IEC 61157-9 standard Examples of equipment b Manual fault-location (see Fig. F53) The generator may be fixed (example: XM100) or portable (example: GR10X permitting the checking of dead circuits) and the receiver, together with the magnetic clamp-type pick-up sensor, are portable. M ERLIN GERIN XM100 XM100 P12 P50 P100 ON/O FF GR10X RM10N © Schneider Electric - all rights reserved Fig. F53 : Non-automatic (manual) fault location b Fixed automatic fault location (see Fig. F54 next page) The monitoring relay XM100, together with the fixed detectors XD1 or XD12 (each connected to a toroidal CT embracing the conductors of the circuit concerned) provide a system of automatic fault location on a live installation. Moreover, the level of insulation is indicated for each monitored circuit, and two levels are checked: the first level warns of unusually low insulation resistance so that preventive measures may be taken, while the second level indicates a fault condition and gives an alarm. (1) On a 230/400 V 3-phase system. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 7 Implementation of the IT system M ERLIN GERIN XM100 Toroidal CTs XM100 1 to 12 circuits F31 XD1 XD1 XD1 XD12 Fig. F54 : Fixed automatic fault location b Automatic monitoring, logging, and fault location (see Fig. F55) The Vigilohm System also allows access to a printer and/or a PC which provides a global review of the insulation level of an entire installation, and records the chronological evolution of the insulation level of each circuit. The central monitor XM100, together with the localization detectors XD08 and XD16, associated with toroidal CTs from several circuits, as shown below in Figure F55, provide the means for this automatic exploitation. M ERLIN GERIN XM100 XM100 M ERLIN GERIN M ERLIN GERIN XL08 XL16 897 678 Fig. F55 : Automatic fault location and insulation-resistance data logging Schneider Electric - Electrical installation guide 2009 XD16 © Schneider Electric - all rights reserved XD08 F - Protection against electric shock 7 Implementation of the IT system Implementation of permanent insulation-monitoring (PIM) devices b Connection The PIM device is normally connected between the neutral (or articificial neutral) point of the power-supply transformer and its earth electrode. b Supply Power supply to the PIM device should be taken from a highly reliable source. In practice, this is generally directly from the installation being monitored, through overcurrent protective devices of suitable short-circuit current rating. b Level settings Certain national standards recommend a first setting at 20% below the insulation level of the new installation. This value allows the detection of a reduction of the insulation quality, necessitating preventive maintenance measures in a situation of incipient failure. The detection level for earth-fault alarm will be set at a much lower level. By way of an example, the two levels might be: v New installation insulation level: 100 kΩ v Leakage current without danger: 500 mA (fire risk at > 500 mA) v Indication levels set by the consumer: - Threshold for preventive maintenance: 0.8 x 100 = 80 kΩ - Threshold for short-circuit alarm: 500 Ω F32 Notes: v Following a long period of shutdown, during which the whole, or part of the installation remains de-energized, humidity can reduce the general level of insulation resistance. This situation, which is mainly due to leakage current over the damp surface of healthy insulation, does not constitute a fault condition, and will improve rapidly as the normal temperature rise of current-carrying conductors reduces the surface humidity. v The PIM device (XM) can measure separately the resistive and the capacitive current components of the leakage current to earth, thereby deriving the true insulation resistance from the total permanent leakage current. The case of a second fault A second earth fault on an IT system (unless occurring on the same conductor as the first fault) constitutes a phase-phase or phase-to-neutral fault, and whether occurring on the same circuit as the first fault, or on a different circuit, overcurrent protective devices (fuses or circuit-breakers) would normally operate an automatic fault clearance. The settings of overcurrent tripping relays and the ratings of fuses are the basic parameters that decide the maximum practical length of circuit that can be satisfactorily protected, as discussed in Sub-clause 6.2. Note: In normal circumstances, the fault current path is through common PE conductors, bonding all exposed conductive parts of an installation, and so the fault loop impedance is sufficiently low to ensure an adequate level of fault current. Where circuit lengths are unavoidably long, and especially if the appliances of a circuit are earthed separately (so that the fault current passes through two earth electrodes), reliable tripping on overcurrent may not be possible. In this case, an RCD is recommended on each circuit of the installation. © Schneider Electric - all rights reserved Where an IT system is resistance earthed, however, care must be taken to ensure that the RCD is not too sensitive, or a first fault may cause an unwanted trip-out. Tripping of residual current devices which satisfy IEC standards may occur at values of 0.5 IΔn to IΔn, where IΔn is the nominal residual-current setting level. Three methods of calculation are commonly used: b The method of impedances, based on the trigonometric addition of the system resistances and inductive reactances b The method of composition b The conventional method, based on an assumed voltage drop and the use of prepared tables Methods of determining levels of short-circuit current A reasonably accurate assessment of short-circuit current levels must be carried out at the design stage of a project. A rigorous analysis is not necessary, since current magnitudes only are important for the protective devices concerned (i.e. phase angles need not be determined) so that simplified conservatively approximate methods are normally used. Three practical methods are: b The method of impedances, based on the vectorial summation of all the (positivephase-sequence) impedances around a fault-current loop b The method of composition, which is an approximate estimation of short-circuit current at the remote end of a loop, when the level of short-circuit current at the near end of the loop is known. Complex impedances are combined arithmetically in this method b The conventional method, in which the minimum value of voltage at the origin of a faulty circuit is assumed to be 80% of the nominal circuit voltage, and tables are used based on this assumption, to give direct readings of circuit lengths. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 7 Implementation of the IT system These methods are reliable only for the cases in which wiring and cables which make up the fault-current loop are in close proximity (to each other) and are not separated by ferro-magnetic materials. Methods of impedances This method as described in Sub-clause 6.2, is identical for both the IT and TN systems of earthing. The software Ecodial is based on the “method of impedance” Methods of composition This method as described in Sub-clause 6.2, is identical for both the IT and TN systems of earthing. Conventional method (see Fig. F56) The principle is the same for an IT system as that described in Sub-clause 6.2 for a TN system : the calculation of maximum circuit lengths which should not be exceeded downstream of a circuit-breaker or fuses, to ensure protection by overcurrent devices. The maximum length of an IT earthed circuit is: b For a 3-phase 3-wire scheme Lmax = 0.8 Uo 3 Sph 2 I a(1+ m) It is clearly impossible to check circuit lengths for every feasible combination of two concurrent faults. b For a 3-phase 4-wire scheme Lmax = All cases are covered, however, if the overcurrent trip setting is based on the assumption that a first fault occurs at the remote end of the circuit concerned, while the second fault occurs at the remote end of an identical circuit, as already mentioned in Sub-clause 3.4. This may result, in general, in one trip-out only occurring (on the circuit with the lower trip-setting level), thereby leaving the system in a first-fault situation, but with one faulty circuit switched out of service. 0.8 Uo S1 2 I a(1+ m) F33 b For the case of a 3-phase 3-wire installation the second fault can only cause a phase/phase short-circuit, so that the voltage to use in the formula for maximum circuit length is 3 Uo. The maximum circuit length is given by: Lmax = 0.8 Uo 3 Sph metres 2 I a(1+ m) b For the case of a 3-phase 4-wire installation the lowest value of fault current will occur if one of the faults is on a neutral conductor. In this case, Uo is the value to use for computing the maximum cable length, and Lmax = 0.8 Uo S1 metres 2 I a(1+ m) i.e. 50% only of the length permitted for a TN scheme (1) N N B D A C Id PE Id Id Non distributed neutral Fig. F56 : Calculation of Lmax. for an IT-earthed system, showing fault-current path for a double-fault condition (1) Reminder: There is no length limit for earth-fault protection on a TT scheme, since protection is provided by RCDs of high sensitivity. Schneider Electric - Electrical installation guide 2009 Id Distributed neutral © Schneider Electric - all rights reserved PE F - Protection against electric shock 7 Implementation of the IT system In the preceding formulae: Lmax = longest circuit in metres Uo = phase-to-neutral voltage (230 V on a 230/400 V system) ρ = resistivity at normal operating temperature (22.5 x 10-3 ohms-mm2/m for copper, 36 x 10-3 ohms-mm2/m for aluminium) Ia = overcurrent trip-setting level in amps, or Ia = current in amps required to clear the fuse in the specified time m= Sph SPE SPE = cross-sectional area of PE conductor in mm2 S1 = S neutral if the circuit includes a neutral conductor S1 = Sph if the circuit does not include a neutral conductor The following tables(1) give the length of circuit which must not be exceeded, in order that F34 persons be protected against indirect contact hazards by protective devices Tables The following tables have been established according to the “conventional method” described above. The tables give maximum circuit lengths, beyond which the ohmic resistance of the conductors will limit the magnitude of the short-circuit current to a level below that required to trip the circuit-breaker (or to blow the fuse) protecting the circuit, with sufficient rapidity to ensure safety against indirect contact. The tables take into account: b The type of protection: circuit-breakers or fuses, operating-current settings b Cross-sectional area of phase conductors and protective conductors b Type of earthing scheme b Correction factor: Figure F57 indicates the correction factor to apply to the lengths given in tables F40 to F43, when considering an IT system Circuit 3 phases 3ph + N or 1ph + N Conductor material Copper Aluminium Copper Aluminium m = Sph/SPE (or PEN) m=1 m=2 m=3 0.86 0.57 0.43 0.54 0.36 0.27 0.50 0.33 0.25 0.31 0.21 0.16 m=4 0.34 0.21 0.20 0.12 Fig. F57 : Correction factor to apply to the lengths given in tables F41 to F44 for TN systems Example A 3-phase 3-wire 230/400 V installation is IT-earthed. One of its circuits is protected by a circuit-breaker rated at 63 A, and consists of an aluminium-cored cable with 50 mm2 phase conductors. The 25 mm2 PE conductor is also aluminum. What is the maximum length of circuit, below which protection of persons against indirect-contact hazards is assured by the instantaneous magnetic tripping relay of the circuit-breaker? Figure F42 indicates 603 metres, to which must be applied a correction factor of 0.36 (m = 2 for aluminium cable). The maximum length is therefore 217 metres. © Schneider Electric - all rights reserved 7.3 High-sensitivity RCDs According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for protection of socket outlets with rated current y 20 A in all locations. The use of such RCDs is also recommended in the following cases: b Socket-outlet circuits in wet locations at all current ratings b Socket-outlet circuits in temporary installations b Circuits supplying laundry rooms and swimming pools b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs See 2.2 and chapter P, al section 3 Fig. F62 : Circuit supplying socket-outlets (1) The tables are those shown in Sub-clause 6.2 (Figures F41 to F44). However, the table of correction factors (Figure F57) which takes into account the ratio Sph/SPE, and of the type of circuit (3-ph 3-wire; 3-ph 4-wire; 1-ph 2-wire) as well as conductor material, is specific to the IT system, and differs from that for TN. Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 7 Implementation of the IT system 7.4 Protection in high fire-risk locations Protection by a RCD of sensitivity y 500 mA at the origin of the circuit supplying the fire-risk locations is mandatory in some countries (see Fig. F59). A preferred sensitivity of 300 mA may be adopted. 7.5 When the fault current-loop impedance is particularly high When the earth-fault current is restricted due to an inevitably high fault-loop impedance, so that the overcurrent protection cannot be relied upon to trip the circuit within the prescribed time, the following possibilities should be considered: Suggestion 1 (see Fig. F60) b Install a circuit-breaker which has an instantaneous magnetic tripping element with an operation level which is lower than the usual setting, for example: F35 2In y Irm y 4In This affords protection for persons on circuits which are abnormally long. It must be checked, however, that high transient currents such as the starting currents of motors will not cause nuisance trip-outs. Fire-risk location b Schneider Electric solutions v Compact NSX with G trip unit or Micrologic trip unit (2Im y Irm y 4Im) v Type B Multi 9 circuit-breaker Suggestion 2 (see Fig. F61) Install a RCD on the circuit. The device does not need to be highly-sensitive (HS) (several amps to a few tens of amps). Where socket-outlets are involved, the particular circuits must, in any case, be protected by HS (y 30 mA) RCDs; generally one RCD for a number of socket outlets on a common circuit. Fig. F59 : Fire-risk location b Schneider Electric solutions v RCD Multi 9 NG125 : IΔn = 1 or 3 A v Vigicompact MH or ME: IΔn = 3 to 30 A PE Suggestion 3 Increase the size of the PE conductors and/or the phase conductors, to reduce the loop impedance. 2 y Irm y 4In Great length of cable Fig. F60 : A circuit-breaker with low-set instantaneous magnetic trip Suggestion 4 (see Fig. F62) Add supplementary equipotential conductors. This will have a similar effect to that of suggestion 3, i.e. a reduction in the earth-fault-loop resistance, while at the same time improving the existing touch-voltage protection measures. The effectiveness of this improvement may be checked by a resistance test between each exposed conductive part and the local main protective conductor. Phases Fig. F61 : RCD protection Fig. F62 : Improved equipotential bonding Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Neutral PE F - Protection against electric shock 8 Residual current devices (RCDs) 8.1 Types of RCDs Residual current devices (RCD) are commonly incorporated in or associated with the following components: b Industrial-type moulded-case circuit-breakers (MCCB) and air circuit-breakers (ACB) conforming to IEC 60947-2 and its appendix B and M b Industrial type miniature circuit-breakers (MCB) conforming to IEC 60947-2 and its appendix B and M b Household and similar miniature circuit-breakers (MCB) complying with IEC 60898, IEC 61008, IEC 61009 b Residual load switch conforming to particular national standards b Relays with separate toroidal (ring-type) current transformers, conforming to IEC 60947-2 Appendix M RCDs are mandatorily used at the origin of TT-earthed installations, where their ability to discriminate with other RCDs allows selective tripping, thereby ensuring the level of service continuity required. F36 Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B Industrial type circuit-breakers with integrated or adaptable RCD module (see Fig. F63) Industrial type circuit-breaker Vigi Compact Multi 9 DIN-rail industrial Circuit-breaker with adaptable Vigi RCD module Fig. F63 : Industrial-type CB with RCD module Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Multi 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi). The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault. © Schneider Electric - all rights reserved Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009 Household and similar miniature circuit-breakers with RCD (see Fig. F64) The incoming-supply circuitbreaker can also have timedelayed characteristics and integrate a RCD (type S). “Monobloc” Déclic Vigi residual current circuit-breakers intended for protection of terminal socket-outlet circuits in domestic and tertiary sector applications. Fig. F64 : Domestic residual current circuit-breakers (RCCBs) for earth leakage protection Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 8 Residual current devices (RCDs) Residual current load break switches are covered by particular national standards. RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M Residual current circuit-breakers and RCDs with separate toroidal current transformer (see Fig. F65) RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors. F37 Fig. F65 : RCDs with separate toroidal current transformers (Vigirex) 8.2 Description Principle The essential features are shown schematically in Figure F66 below. I1 A magnetic core encompasses all the current-carrying conductors of an electric circuit and the magnetic flux generated in the core will depend at every instant on the arithmetical sum of the currents; the currents passing in one direction being considered as positive (I1), while those passing in the opposite direction will be negative (I2). I2 In a normally healthy circuit I1 + I2 = 0 and there will be no flux in the magnetic core, and zero e.m.f. in its coil. I3 An earth-fault current Id will pass through the core to the fault, but will return to the source via the earth, or via protective conductors in a TN-earthed system. The current balance in the conductors passing through the magnetic core therefore no longer exists, and the difference gives rise to a magnetic flux in the core. The difference current is known as the “residual” current and the principle is referred to as the “residual current” principle. The resultant alternating flux in the core induces an e.m.f. in its coil, so that a current I3 flows in the tripping-device operating coil. If the residual current exceeds the value required to operate the tripping device either directly or via an electronic relay, then the associated circuit-breaker will trip. 8.3 Sensitivity of RDCs to disturbances In certain cases, aspects of the environment can disturb the correct operation of RCDs: b “nuisance” tripping: Break in power supply without the situation being really hazardous. This type of tripping is often repetitive, causing major inconvenience and detrimental to the quality of the user's electrical power supply. b non-tripping, in the event of a hazard. Less perceptible than nuisance tripping, these malfunctions must still be examined carefully since they undermine user safety. This is why international standards define 3 categories of RCDs according to their immunity to this type of disturbance (see below). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. F66 : The principle of RCD operation F - Protection against electric shock 8 Residual current devices (RCDs) Main disturbance types I Permanent earth leakage currents Every LV installation has a permanent leakage current to earth, which is either due to: b Unbalance of the intrinsic capacitance between live conductors and earth for threephase circuits or b Capacitance between live conductors and earth for single-phase circuits The larger the installation the greater its capacitance with consequently increased leakage current. 100% 90% 10 s (f = 100 kHz) The capacitive current to earth is sometimes increased significantly by filtering capacitors associated with electronic equipment (automation, IT and computerbased systems, etc.). 10% t In the absence of more precise data, permanent leakage current in a given installation can be estimated from the following values, measured at 230 V 50 Hz: ca.0.5 s Single-phase or three-phase line: 1.5 mA /100m b Heating floor: 1mA / kW b Fax terminal, printer: 1 mA b Microcomputer, workstation: 2 mA b Copy machine: 1.5 mA F38 60% Fig. F67 : Standardized 0.5 µs/100 kHz current transient wave Since RCDs complying with IEC and many national standards may operate under, the limitation of permanent leakage current to 0.25 I∆n, by sub-division of circuits will, in practice, eliminate any unwanted tripping. For very particular cases, such as the extension, or partial renovation of extended IT-earthed installations, the manufacturers must be consulted. U High frequency components (harmonics, transients, etc.), are generated by computer equipment power supplies, converters, motors with speed regulators, fluorescent lighting systems and in the vicinity of high power switching devices and reactive energy compensation banks. Part of these high frequency currents may flow to earth through parasitic capacitances. Although not hazardous for the user, these currents can still cause the tripping of differential devices. Umax 0.5U t 1.2 s 50 s Fig. F68 : Standardized 1.2/50 µs voltage transient wave Common mode overvoltages Electrical networks are subjected to overvoltages due to lightning strikes or to abrupt changes of system operating conditions (faults, fuse operation, switching, etc.). These sudden changes often cause large transient voltages and currents in inductive and capacitive circuits. Records have established that, on LV systems, overvoltages remain generally below 6 kV, and that they can be adequately represented by the conventional 1.2/50 µs impulse wave (see Fig. F68). I 1 0.9 These overvoltages give rise to transient currents represented by a current impulse wave of the conventional 8/20 µs form, having a peak value of several tens of amperes (see Fig. F69). The transient currents flow to earth via the capacitances of the installation. 0.5 Non-sinusoidal fault currents 0.1 © Schneider Electric - all rights reserved t Fig. F69 : Standardized current-impulse wave 8/20 µs Energization The initial energization of the capacitances mentioned above gives rise to high frequency transient currents of very short duration, similar to that shown in Figure F67. The sudden occurrence of a first-fault on an IT-earthed system also causes transient earth-leakage currents at high frequency, due to the sudden rise of the two healthy phases to phase/phase voltage above earth. Type AC, A, B Standard IEC 60755 (General requirements for residual current operated protective devices) defines three types of RCD depending on the characteristics of the fault current: b Type AC RCD for which tripping is ensured for residual sinusoidal alternating currents. b Type A RCD for which tripping is ensured: v for residual sinusoidal alternating currents, v for residual pulsating direct currents, Schneider Electric - Electrical installation guide 2009 8 Residual current devices (RCDs) b Type B RCD for which tripping is ensured: v as for type A, v for pure direct residual currents which may result from three-phase rectifying circuits. Cold: in the cases of temperatures under - 5 °C, very high sensitivity electromechanical relays in the RCD may be “welded” by the condensation – freezing action. Type “Si” devices can operate under temperatures down to - 25 °C. Atmospheres with high concentrations of chemicals or dust: the special alloys used to make the RCDs can be notably damaged by corrosion. Dust can also block the movement of mechanical parts. See the measures to be taken according to the levels of severity defined by standards in Fig. F70. Regulations define the choice of earth leakage protection and its implementation. The main reference texts are as follows: b Standard IEC 60364-3: v This gives a classification (AFx) for external influences in the presence of corrosive or polluting substances. v It defines the choice of materials to be used according to extreme influences. Disturbed network Influence of the electrical network Clean network Superimmunized residual current protections Type A if: k SiE k residual current protections Standard immunized residual current protections Type AC SiE k SiE k residual current residual current protections protections + + Appropriate additional protection (sealed cabinet or unit) Appropriate additional protection (sealed cabinet or unit + overpressure) AF1 AF2 AF3 AF4 b External influences: negligible, b External influences: presence of corrosive or polluting atmospheric agents, b External influences: intermittent or accidental action of certain common chemicals, b External influences: permanent action of corrosive or polluting chemicals b Equipment characteristics: normal. b Equipment characteristics: e.g. conformity with salt mist or atmospheric pollution tests. b Equipment characteristics: corrosion protection. b Equipment characteristics: specifically studied according to the type of products. Examples of exposed sites External influences Iron and steel works. Presence of sulfur, sulfur vapor, hydrogen sulfide. Marinas, trading ports, boats, sea edges, naval shipyards. Salt atmospheres, humid outside, low temperatures. Swimming pools, hospitals, food & beverage. Chlorinated compounds. Petrochemicals. Hydrogen, combustion gases, nitrogen oxides. Breeding facilities, tips. Hydrogen sulfide. Fig. F70 : External influence classification according to IEC 60364-3 standard Schneider Electric - Electrical installation guide 2009 F39 © Schneider Electric - all rights reserved F - Protection against electric shock F - Protection against electric shock 8 Residual current devices (RCDs) Immunity level for Merlin Gerin residual current devices The Merlin Gerin range comprises various types of RCDs allowing earth leakage protection to be adapted to each application. The table below indicates the choices to be made according to the type of probable disturbances at the point of installation. Device type Nuisance trippings High frequency leakage current Fault current Rectified alternating Pure direct Low Corrosion temperatures Dust (down to - 25 °C) b AC F40 Non-trippings A b b b SI b b b b b SiE b b b b b B b b b b b b b Fig. F71 : Immunity level of Merlin Gerin RCDs Immunity to nuisance tripping Type Si/SiE RCDs have been designed to avoid nuisance tripping or non-tripping in case of polluted network , lightning effect, high frequency currents, RF waves, etc. Figure F72 below indicates the levels of tests undergone by this type of RCDs. Disturbance type Rated test wave Immunity Multi9 : ID-RCCB, DPN Vigi, Vigi C60, Vigi C120, Vigi NG125 SI / SiE type Continuous disturbances Harmonics 1 kHz Earth leakage current = 8 x I∆n Lightning induced overvoltage 1.2 / 50 µs pulse (IEC/EN 61000-4-5) 4.5 kV between conductors 5.5 kV / earth Lightning induced current 8 / 20 µs pulse (IEC/EN 61008) 5 kA peak Switching transient, indirect lightning currents 0.5 µs / 100 kHz “ ring wave ” (IEC/EN 61008) 400 A peak Downstream surge arrester operation, capacitance loading 10 ms pulse 500 A Inductive load switchings fluorescent lights, motors, etc.) Repeated bursts (IEC 61000-4-4) 4 kV / 400 kHz Fluorescent lights, thyristor controlled circuits, etc. RF conducted waves (IEC 61000-4-6) 66 mA (15 kHz to 150 kHz) 30 V (150 kHz to 230 MHz) RF waves (TV& radio, broadcact, telecommunications,etc.) RF radiated waves 80 MHz to 1 GHz (IEC 61000-4-3) 30 V / m Transient disturbances © Schneider Electric - all rights reserved Electromagnetic compatibility Fig. F72 : Immunity to nuisance tripping tests undergone by Merlin Gerin RCDs Schneider Electric - Electrical installation guide 2009 8 Residual current devices (RCDs) Recommendations concerning the installation of RCDs with separate toroidal current transformers The detector of residual current is a closed magnetic circuit (usually circular) of very high magnetic permeability, on which is wound a coil of wire, the ensemble constituting a toroidal (or ring-type) current transformer. Because of its high permeability, any small deviation from perfect symmetry of the conductors encompassed by the core, and the proximity of ferrous material (steel enclosure, chassis members, etc.) can affect the balance of magnetic forces sufficiently, at times of large load currents (motor-starting current, transformer energizing current surge, etc.) to cause unwanted tripping of the RCD. Unless particular measures are taken, the ratio of operating current IΔn to maximum phase current Iph (max.) is generally less than 1/1,000. This limit can be increased substantially (i.e. the response can be desensitized) by adopting the measures shown in Figure F73, and summarized in Figure F74. F41 L L = twice the diameter of the magnetic ring core Fig. F73 : Three measures to reduce the ratio IΔn/Iph (max.) Measures Diameter (mm) Sensitivity diminution factor Careful centralizing of cables through the ring core Oversizing of the ring core ø 50 → ø 100 ø 80 → ø 200 ø 120 → ø 300 ø 50 3 2 2 6 4 Use of a steel or soft-iron shielding sleeve b Of wall thickness 0.5 mm b Of length 2 x inside diameter of ring core b Completely surrounding the conductors and ø 80 3 ø 120 3 ø 200 2 overlapping the circular core equally at both ends These measures can be combined. By carefully centralizing the cables in a ring core of 200 mm diameter, where a 50 mm core would be large enough, and using a sleeve, the ratio 1/1,000 could become 1/30,000. Fig. F74 : Means of reducing the ratio I∆n/Iph (max.) © Schneider Electric - all rights reserved F - Protection against electric shock Schneider Electric - Electrical installation guide 2009 F - Protection against electric shock 8 Residual current devices (RCDs) Choice of characteristics of a residual-current circuit-breaker (RCCB - IEC 61008) a Rated current The rated current of a RCCB is chosen according to the maximum sustained load current it will carry. b b If the RCCB is connected in series with, and downstream of a circuit-breaker, the rated current of both items will be the same, i.e. In u In1 (see Fig. F75a) b If the RCCB is located upstream of a group of circuits, protected by circuitbreakers, as shown in Figure F75b, then the RCCB rated current will be given by: In1 In u ku x ks (In1 + In2 + In3 + In4) In In F42 In1 In2 In3 In4 Electrodynamic withstand requirements Protection against short-circuits must be provided by an upstream SCPD (ShortCircuit Protective Device) but it is considered that where the RCCB is located in the same distribution box (complying with the appropriate standards) as the downstream circuit-breakers (or fuses), the short-circuit protection afforded by these (outgoingcircuit) SCPDs is an adequate alternative. Coordination between the RCCB and the SCPDs is necessary, and manufacturers generally provide tables associating RCCBs and circuit-breakers or fuses (see Fig. F76). Fig. F75 : Residual current circuit-breakers (RCCBs) Circuit-breaker and RCCB association – maxi Isc (r.m.s) value in kA Upstream circuit-breaker Downstream 2P I 20A RCCB 230V IN-A 40A IN-A 63A I 100A 4P I 20A 400V IN-A 40A IN-A 63A NG 125NA DT40 6.5 6 6 DT40N 6.5 10 10 C60N 6.5 20 20 C60H 6.5 30 30 C60L 6.5 30 30 4.5 6 6 4.5 10 10 4.5 10 10 4.5 15 15 4.5 15 15 gG upstream fuse Downstream 2P RCCB 230V 20A 8 Fuses and RCCB association – maxi Isc (r.m.s) value in kA 4P 400V I 20A IN-A 40A IN-A 63A I 100A I 20A IN-A 40A IN-A 63A NG 125NA 63A 100A 30 30 20 20 6 30 30 20 20 C120N 3 10 10 15 2 7 7 10 125A 8 50 © Schneider Electric - all rights reserved Fig. F76 : Typical manufacturers coordination table for RCCBs, circuit-breakers, and fuses (Merlin Gerin products) Schneider Electric - Electrical installation guide 2009 C120H 4.5 10 10 15 3 7 7 16 NG125N 4.5 15 15 15 3 15 15 25 NG125H 4.5 15 15 15 3 15 15 50 Chapter G Sizing and protection of conductors Contents 1 General G2 1.1 1.2 1.3 1.4 1.5 G2 G4 G4 G6 G6 2 Practical method for determining the smallest allowable cross-sectional area of circuit conductors G7 2.1 2.2 2.3 2.4 G7 G7 G16 G18 3 4 Determination of voltage drop G20 3.1 Maximum voltage drop limit 3.2 Calculation of voltage drop in steady load conditions G20 G21 G1 Short-circuit current G24 4.1 Short-circuit current at the secondary terminals of a MV/LV distribution transformer 4.2 3-phase short-circuit current (Isc) at any point within a LV installation 4.3 Isc at the receiving end of a feeder in terms of the Isc at its sending end 4.4 Short-circuit current supplied by an alternator or an inverter G24 Methodology and definition Overcurrent protection principles Practical values for a protective scheme Location of protective devices Conductors in parallel General General method for cables Recommended simplified approach for cables Busbar trunking systems G25 G28 G29 5 Particular cases of short-circuit current G30 5.1 Calculation of minimum levels of short-circuit current 5.2 Verification of the withstand capabilities of cables under short-circuit conditions G30 G35 6 Protective earthing conductor G37 6.1 Connection and choice 6.2 Conductor sizing 6.3 Protective conductor between MV/LV transformer and the main general distribution board (MGDB) 6.4 Equipotential conductor G37 G38 G40 G41 7 The neutral conductor G42 7.1 7.2 7.3 7.4 G42 G42 G44 G44 8 Worked example of cable calculation G46 © Schneider Electric - all rights reserved Sizing the neutral conductor Protection of the neutral conductor Breaking of the neutral conductor Isolation of the neutral conductor Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 1 General 1.1 Methodology and definition Component parts of an electric circuit and its protection are determined such that all normal and abnormal operating conditions are satisfied Methodology (see Fig. G1 ) Following a preliminary analysis of the power requirements of the installation, as described in Chapter B Clause 4, a study of cabling(1) and its electrical protection is undertaken, starting at the origin of the installation, through the intermediate stages to the final circuits. The cabling and its protection at each level must satisfy several conditions at the same time, in order to ensure a safe and reliable installation, e.g. it must: b Carry the permanent full load current, and normal short-time overcurrents b Not cause voltage drops likely to result in an inferior performance of certain loads, for example: an excessively long acceleration period when starting a motor, etc. Moreover, the protective devices (circuit-breakers or fuses) must: b Protect the cabling and busbars for all levels of overcurrent, up to and including short-circuit currents b Ensure protection of persons against indirect contact hazards, particularly in TN- and IT- earthed systems, where the length of circuits may limit the magnitude of short-circuit currents, thereby delaying automatic disconnection (it may be remembered that TT- earthed installations are necessarily protected at the origin by a RCD, generally rated at 300 mA). G2 The cross-sectional areas of conductors are determined by the general method described in Sub-clause 2 of this Chapter. Apart from this method some national standards may prescribe a minimum cross-sectional area to be observed for reasons of mechanical endurance. Particular loads (as noted in Chapter N) require that the cable supplying them be oversized, and that the protection of the circuit be likewise modified. Power demand: - kVA to be supplied - Maximum load current IB Conductor sizing: - Selection of conductor type and insulation - Selection of method of installation - Taking account of correction factors for different environment conditions - Determination of cross-sectional areas using tables giving the current carrying capability Verification of the maximum voltage drop: - Steady state conditions - Motor starting conditions © Schneider Electric - all rights reserved Calculation of short-circuit currents: - Upstream short-circuit power - Maximum values - Minimum values at conductor end Selection of protective devices: - Rated current - Breaking capability - Implementation of cascading - Check of discrimination Fig. G1 : Flow-chart for the selection of cable size and protective device rating for a given circuit (1) The term “cabling” in this chapter, covers all insulated conductors, including multi-core and single-core cables and insulated wires drawn into conduits, etc. Schneider Electric - Electrical installation guide 2009 1 General Definitions Maximum load current: IB b At the final circuits level, this current corresponds to the rated kVA of the load. In the case of motor-starting, or other loads which take a high in-rush current, particularly where frequent starting is concerned (e.g. lift motors, resistance-type spot welding, and so on) the cumulative thermal effects of the overcurrents must be taken into account. Both cables and thermal type relays are affected. b At all upstream circuit levels this current corresponds to the kVA to be supplied, which takes account of the factors of simultaneity (diversity) and utilization, ks and ku respectively, as shown in Figure G2. Main distribution board Combined factors of simultaneity (or diversity) and utilization: ks x ku = 0.69 IB = (80+60+100+50) x 0.69 = 200 A G3 Sub-distribution board 80 A 60 A 100 A 50 A M Normal load motor current 50 A Fig. G2 : Calculation of maximum load current IB Maximum permissible current: Iz This is the maximum value of current that the cabling for the circuit can carry indefinitely, without reducing its normal life expectancy. The current depends, for a given cross sectional area of conductors, on several parameters: b Constitution of the cable and cable-way (Cu or Alu conductors; PVC or EPR etc. insulation; number of active conductors) b Ambient temperature b Method of installation b Influence of neighbouring circuits Overcurrents An overcurrent occurs each time the value of current exceeds the maximum load current IB for the load concerned. This current must be cut off with a rapidity that depends upon its magnitude, if permanent damage to the cabling (and appliance if the overcurrent is due to a defective load component) is to be avoided. Overcurrents of relatively short duration can however, occur in normal operation; two types of overcurrent are distinguished: b Overloads These overcurrents can occur in healthy electric circuits, for example, due to a number of small short-duration loads which occasionally occur co-incidentally: motor starting loads, and so on. If either of these conditions persists however beyond a given period (depending on protective-relay settings or fuse ratings) the circuit will be automatically cut off. b Short-circuit currents These currents result from the failure of insulation between live conductors or/and between live conductors and earth (on systems having low-impedance-earthed neutrals) in any combination, viz: v 3 phases short-circuited (and to neutral and/or earth, or not) v 2 phases short-circuited (and to neutral and/or earth, or not) v 1 phase short-circuited to neutral (and/or to earth) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved G - Sizing and protection of conductors G - Sizing and protection of conductors 1 General 1.2 Overcurrent protection principles A protective device is provided at the origin of the circuit concerned (see Fig. G3 and Fig. G4). b Acting to cut-off the current in a time shorter than that given by the I2t characteristic of the circuit cabling b But allowing the maximum load current IB to flow indefinitely The characteristics of insulated conductors when carrying short-circuit currents can, for periods up to 5 seconds following short-circuit initiation, be determined approximately by the formula: I2t = k2 S2 which shows that the allowable heat generated is proportional to the squared cross-sectional-area of the condutor. where t: Duration of short-circuit current (seconds) S: Cross sectional area of insulated conductor (mm2) I: Short-circuit current (A r.m.s.) k: Insulated conductor constant (values of k2 are given in Figure G52 ) For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 > θa2), Iz1 is less than Iz2 (see Fig. G5). θ means “temperature”. G4 Note: v ISC: 3-phase short-circuit current v ISCB: rated 3-ph. short-circuit breaking current of the circuit-breaker v Ir (or Irth)(1): regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker can be regulated to have a protective range, i.e. a conventional overcurrent tripping level (see Fig. G6 opposite page) similar to that of a 30 A circuit-breaker. t Maximum load current I2t cable characteristic 1.3 Practical values for a protective scheme Temporary overload The following methods are based on rules laid down in the IEC standards, and are representative of the practices in many countries. Circuit-breaker tripping curve General rules IB Ir Iz ISCB ICU I Fig. G3 : Circuit protection by circuit-breaker A protective device (circuit-breaker or fuse) functions correctly if: b Its nominal current or its setting current In is greater than the maximum load current IB but less than the maximum permissible current Iz for the circuit, i.e. IB y In y Iz corresponding to zone “a” in Figure G6 b Its tripping current I2 “conventional” setting is less than 1.45 Iz which corresponds to zone “b” in Figure G6 The “conventional” setting tripping time may be 1 hour or 2 hours according to local standards and the actual value selected for I2. For fuses, I2 is the current (denoted If) which will operate the fuse in the conventional time. t I2t cable characteristic t 1 2 θa1 > θa2 Fuse curve © Schneider Electric - all rights reserved Temporary overload IB 5s Ir cIz Iz I2t = k2S2 I Fig. G4 : Circuit protection by fuses Iz1 < Iz2 I Fig. G5 : I2t characteristic of an insulated conductor at two different ambient temperatures (1) Both designations are commonly used in different standards. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 1 General Circuit cabling Iz 45 1. B I nt rre cu M ax im um ad lo lo ad um im ax M cu rre nt Iz Loads IB 1.45 Iz Iz Isc 0 In I2 ISCB zone a zone c Protective device g 3 fa -ph ul s t-c ho ur r t re -ci nt rc br uit ea ki ng ra tin re ur rc C tri onv p e cu nt rre ion nt al I 2 ov e N its om re ina gu l c la ur te re d n cu t I rre n o nt r Ir nt zone b G5 IB y In y Iz zone a I2 y 1.45 Iz zone b ISCB u ISC zone c Fig. G6 : Current levels for determining circuir breaker or fuse characteristics b Its 3-phase short-circuit fault-current breaking rating is greater than the 3-phase short-circuit current existing at its point of installation. This corresponds to zone “c” in Figure G6. Applications Criteria for fuses: IB y In y Iz/k3 and ISCF u ISC. b Protection by fuses The condition I2 y 1.45 Iz must be taken into account, where I2 is the fusing (melting level) current, equal to k2 x In (k2 ranges from 1.6 to 1.9) depending on the particular fuse concerned. k2 A further factor k3 has been introduced ( k3 = ) such that I2 y 1.45 Iz 1.45 will be valid if In y Iz/k3. For fuses type gG: In < 16 A → k3 = 1.31 In u 16 A → k3 = 1.10 Moreover, the short-circuit current breaking capacity of the fuse ISCF must exceed the level of 3-phase short-circuit current at the point of installation of the fuse(s). b Association of different protective devices The use of protective devices which have fault-current ratings lower than the fault level existing at their point of installation are permitted by IEC and many national standards in the following conditions: v There exists upstream, another protective device which has the necessary shortcircuit rating, and v The amount of energy allowed to pass through the upstream device is less than that which can be withstood without damage by the downstream device and all associated cabling and appliances. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Criteria for circuit-breakers: IB y In y Iz and ISCB u ISC. b Protection by circuit-breaker By virtue of its high level of precision the current I2 is always less than 1.45 In (or 1.45 Ir) so that the condition I2 y 1.45 Iz (as noted in the “general rules” above) will always be respected. v Particular case If the circuit-breaker itself does not protect against overloads, it is necessary to ensure that, at a time of lowest value of short-circuit current, the overcurrent device protecting the circuit will operate correctly. This particular case is examined in Subclause 5.1. G - Sizing and protection of conductors 1 General In pratice this arrangement is generally exploited in: v The association of circuit-breakers/fuses v The technique known as “cascading” or “series rating” in which the strong current-limiting performance of certain circuit-breakers effectively reduces the severity of downstream short-circuits Possible combinations which have been tested in laboratories are indicated in certain manufacturers catalogues. 1.4 Location of protective devices A protective device is, in general, required at the origin of each circuit General rule (see Fig. G7a) A protective device is necessary at the origin of each circuit where a reduction of permissible maximum current level occurs. Possible alternative locations in certain circumstances (see Fig. G7b) The protective device may be placed part way along the circuit: b If AB is not in proximity to combustible material, and b If no socket-outlets or branch connections are taken from AB G6 a P P2 P3 50 mm2 P4 10 mm2 25 mm2 b Three cases may be useful in practice: b Consider case (1) in the diagram v AB y 3 metres, and v AB has been installed to reduce to a practical minimum the risk of a short-circuit (wires in heavy steel conduit for example) b Consider case (2) v The upstream device P1 protects the length AB against short-circuits in accordance with Sub-clause 5.1 b Consider case (3) v The overload device (S) is located adjacent to the load. This arrangement is convenient for motor circuits. The device (S) constitutes the control (start/stop) and overload protection of the motor while (SC) is: either a circuit-breaker (designed for motor protection) or fuses type aM v The short-circuit protection (SC) located at the origin of the circuit conforms with the principles of Sub-clause 5.1 Circuits with no protection (see Fig. G7c) P1 Either b The protective device P1 is calibrated to protect the cable S2 against overloads and short-circuits A <3m sc B B P2 B P3 Case (1) Case (2) Short-circuit protective device s Overload protective device Or b Where the breaking of a circuit constitutes a risk, e.g. v Excitation circuits of rotating machines v circuits of large lifting electromagnets v the secondary circuits of current transformers No circuit interruption can be tolerated, and the protection of the cabling is of secondary importance. Case (3) 1.5 Conductors in parallel Conductors of the same cross-sectional-area, the same length, and of the same material, can be connected in parallel. c The maximum permissible current is the sum of the individual-core maximum currents, taking into account the mutual heating effects, method of installation, etc. Protection against overload and short-circuits is identical to that for a single-cable circuit. © Schneider Electric - all rights reserved P1: C60 rated 15 A 2.5 mm2 S2: 1.5 mm2 Fig. G7 : Location of protective devices The following precautions should be taken to avoid the risk of short-circuits on the paralleled cables: b Additional protection against mechanical damage and against humidity, by the introduction of supplementary protection b The cable route should be chosen so as to avoid close proximity to combustible materials Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors 2.1 General The reference international standard for the study of cabling is IEC 60364-5-52: “Electrical installation of buildings - Part 5-52: Selection and erection of electrical equipment - Wiring system”. A summary of this standard is presented here, with examples of the most commonly used methods of installation. The current-carrying capacities of conductors in all different situations are given in annex A of the standard. A simplified method for use of the tables of annex A is proposed in informative annex B of the standard. 2.2 General method for cables Possible methods of installation for different types of conductors or cables The different admissible methods of installation are listed in Figure G8, in conjonction with the different types of conductors and cables. G7 Conductors and cables Method of installation Without Clipped Conduit Cable trunking fixings direct (including skirting trunking, flush floor trunking) – – – – – – + + + + + + Bare conductors Insulated conductors Sheathed Multi-core cables (including armoured Single-core 0 + and mineral insulated) + Permitted. – Not permitted. 0 Not applicable, or not normally used in practice. + + Cable Cable ladder ducting Cable tray Cable brackets On Support insulators wire – + + – – + + + 0 – – + + + 0 + © Schneider Electric - all rights reserved Fig. G8 : Selection of wiring systems (table 52-1 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors Possible methods of installation for different situations: Different methods of installation can be implemented in different situations. The possible combinations are presented in Figure G9. The number given in this table refer to the different wiring systems considered. (see also Fig. G10) Situations Building voids G8 Method of installation Without With Conduit fixings fixings Cable channel 40, 46, 15, 16 56 0 15, 16, 41, 42 54, 55 56 Buried in ground Embedded in structure 72, 73 57, 58 0 3 Surface mounted – 20, 21 70, 71 1, 2, 59, 60 4, 5 Overhead – – Immersed 80 80 – Not permitted. 0 Not applicable, or not normally used in practice. Cable trunking Cable (including ducting skirting trunking, flush floor trunking) – 43 0 44, 45 – 50, 51, 52, 53 44, 45 0 6, 7, 8, 9, 12, 13, 14 22, 23 10, 11 6, 7, 8, 9 – 0 – 0 © Schneider Electric - all rights reserved Fig. G9 : Erection of wiring systems (table 52-2 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 Cable ladder cable tray, cable brackets On Support insulators wire 30, 31, 32, 33, 34 30, 31, 32, 33, 34 70, 71 0 – – – – 0 – – – 36 – 36 35 – – 30, 31, 32, 33, 34 30, 31, 32 33, 34 0 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors Examples of wiring systems and reference methods of installations An illustration of some of the many different wiring systems and methods of installation is provided in Figure G10. Several reference methods are defined (with code letters A to G), grouping installation methods having the same characteristics relative to the current-carrying capacities of the wiring systems. Item No. Methods of installation 1 Description Reference method of installation to be used to obtain current-carrying capacity Insulated conductors or single-core cables in conduit in a thermally insulated wall A1 Room G9 2 Multi-core cables in conduit in a thermally insulated wall A2 4 Insulated conductors or single-core cables in conduit on a wooden, or masonry wall or spaced less than 0,3 x conduit diameter from it B1 5 Multi-core cable in conduit on a wooden, or mansonry wall or spaced less than 0,3 x conduit diameter from it B2 20 Single-core or multi-core cables: - fixed on, or sapced less than 0.3 x cable diameter from a wooden wall C On unperforated tray C Room 30 0.3 D e Fig. G10 : Examples of methods of installation (part of table 52-3 of IEC 60364-5-52) (continued on next page) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 0.3 D e G - Sizing and protection of conductors Item No. 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors Description Reference method of installation to be used to obtain current-carrying capacity On perforated tray E or F 36 Bare or insulated conductors on insulators G 70 Multi-core cables in conduit or in cable ducting in the ground D 71 Single-core cable in conduit or in cable ducting in the ground D 31 Methods of installation 0.3 D e 0.3 D e G10 Fig. G10 : Examples of methods of installation (part of table 52-3 of IEC 60364-5-52) Maximum operating temperature: The current-carrying capacities given in the subsequent tables have been determined so that the maximum insulation temperature is not exceeded for sustained periods of time. For different type of insulation material, the maximum admissible temperature is given in Figure G11. Type of insulation Polyvinyl-chloride (PVC) Cross-linked polyethylene (XLPE) and ethylene propylene rubber (EPR) Mineral (PVC covered or bare exposed to touch) Mineral (bare not exposed to touch and not in contact with combustible material) Temperature limit °C 70 at the conductor 90 at the conductor 70 at the sheath 105 at the seath © Schneider Electric - all rights reserved Fig. G11 : Maximum operating temperatures for types of insulation (table 52-4 of IEC 60364-5-52) Correction factors: In order to take environnement or special conditions of installation into account, correction factors have been introduced. The cross sectional area of cables is determined using the rated load current IB divided by different correction factors, k1, k2, ...: I' B = IB k1 ⋅ k 2 ... I’B is the corrected load current, to be compared to the current-carrying capacity of the considered cable. Schneider Electric - Electrical installation guide 2009 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors b Ambient temperature The current-carrying capacities of cables in the air are based on an average air temperature equal to 30 °C. For other temperatures, the correction factor is given in Figure G12 for PVC, EPR and XLPE insulation material. The related correction factor is here noted k1. Ambient temperature °C 10 15 20 25 35 40 45 50 55 60 65 70 75 80 Insulation PVC 1.22 1.17 1.12 1.06 0.94 0.87 0.79 0.71 0.61 0.50 - XLPE and EPR 1.15 1.12 1.08 1.04 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.41 G11 Fig. G12 : Correction factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air (from table A.52-14 of IEC 60364-5-52) The current-carrying capacities of cables in the ground are based on an average ground temperature equal to 20 °C. For other temperatures, the correction factor is given in Figure G13 for PVC, EPR and XLPE insulation material. The related correction factor is here noted k2. Ground temperature °C 10 15 25 30 35 40 45 50 55 60 65 70 75 80 Insulation PVC 1.10 1.05 0.95 0.89 0.84 0.77 0.71 0.63 0.55 0.45 - XLPE and EPR 1.07 1.04 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.46 0.38 Fig. G13 : Correction factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying capacities for cables in ducts in the ground (from table A.52-15 of IEC 60364-5-52) © Schneider Electric - all rights reserved G - Sizing and protection of conductors Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors b Soil thermal resistivity The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5 K.m/W. For other values, the correction factor is given in Figure G14. The related correction factor is here noted k3. Thermal resistivity, K.m/W Correction factor 1 1.18 1.5 1.1 2 1.05 2.5 1 3 0.96 Fig. G14 : Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied to the current-carrying capacities for reference method D (table A52.16 of IEC 60364-5-52) Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric values of correction factors k3 are proposed in Figure G15, depending on the nature of soil. G12 Nature of soil Very wet soil (saturated) Wet soil Damp soil Dry soil Very dry soil (sunbaked) k3 1.21 1.13 1.05 1.00 0.86 Fig. G15 : Correction factor k3 depending on the nature of soil b Grouping of conductors or cables The current-carrying capacities given in the subsequent tables relate to single circuits consisting of the following numbers of loaded conductors: v Two insulated conductors or two single-core cables, or one twin-core cable (applicable to single-phase circuits); v Three insulated conductors or three single-core cables, or one three-core cable (applicable to three-phase circuits). Where more insulated conductors or cables are installed in the same group, a group reduction factor (here noted k4) shall be applied. Examples are given in Figures G16 to G18 for different configurations (installation methods, in free air or in the ground). © Schneider Electric - all rights reserved Figure G16 gives the values of correction factor k4 for different configurations of unburied cables or conductors, grouping of more than one circuit or multi-core cables. Arrangement (cables touching) Bunched in air, on a surface, embedded or enclosed Single layer on wall, floor or unperforated tray Single layer fixed directly under a wooden ceiling Single layer on a perforated horizontal or vertical tray Single layer on ladder support or cleats etc. Number of circuits or multi-core cables 1 2 3 4 5 6 1.00 0.80 0.70 0.65 0.60 0.57 7 0.54 8 0.52 9 0.50 12 0.45 Reference methods 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61 No further reduction factor for more than nine circuits or multi-core cables 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78 16 0.41 20 0.38 Fig. G16 : Reduction factors for groups of more than one circuit or of more than one multi-core cable (table A.52-17 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 Methods A to F Method C Methods E and F G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors Figure G17 gives the values of correction factor k4 for different configurations of unburied cables or conductors, for groups of more than one circuit of single-core cables in free air. Method of installation Perforated trays Vertical perforated trays Number of tray 1 2 3 1 0.98 0.91 0.87 2 0.96 0.87 0.81 20 mm 3 0.95 0.85 0.78 Touching 1 0.96 0.86 2 0.95 0.84 Touching 31 31 Number of three-phase circuits Use as a multiplier to rating for Three cables in horizontal formation Three cables in vertical formation 225 mm G13 Ladder supports, cleats, etc... 32 1 1.00 0.97 0.96 2 0.98 0.93 0.89 3 0.97 0.90 0.86 1 1.00 0.98 0.96 2 0.97 0.93 0.89 3 0.96 0.92 0.86 1 1.00 0.91 0.89 2 1.00 0.90 0.86 1 1.00 1.00 1.00 2 0.97 0.95 0.93 3 0.96 0.94 0.90 Touching 33 34 Three cables in horizontal formation 20 mm Perforated trays 31 2D e De 20 mm Vertical perforated trays 31 De Spaced 225 mm Three cables in trefoil formation 2D e Ladder supports, cleats, etc... 32 2D e De 33 34 20 mm © Schneider Electric - all rights reserved Fig. G17 : Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating for one circuit of single-core cables in free air - Method of installation F. (table A.52.21 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors Figure G18 gives the values of correction factor k4 for different configurations of cables or conductors laid directly in the ground. Number of circuits 2 3 4 5 6 a G14 a Cable to cable clearance (a)a Nil (cables One cable 0.125 m touching) diameter 0.75 0.80 0.85 0.65 0.70 0.75 0.60 0.60 0.70 0.55 0.55 0.65 0.50 0.55 0.60 0.25 m 0.5 m 0.90 0.80 0.75 0.70 0.70 0.90 0.85 0.80 0.80 0.80 Multi-core cables a a a a Single-core cables Fig. G18 : Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground. Installation method D. (table 52-18 of IEC 60364-5-52) b Harmonic current The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption that only 3 conductors are fully loaded. However, when harmonic currents are circulating, the neutral current can be significant, and even higher than the phase currents. This is due to the fact that the 3rd harmonic currents of the three phases do not cancel each other, and sum up in the neutral conductor. This of course affects the current-carrying capacity of the cable, and a correction factor noted here k5 shall be applied. In addition, if the 3rd harmonic percentage h3 is greater than 33%, the neutral current is greater than the phase current and the cable size selection is based on the neutral current. The heating effect of harmonic currents in the phase conductors has also to be taken into account. The values of k5 depending on the 3rd harmonic content are given in Figure G19. Third harmonic content of phase current % © Schneider Electric - all rights reserved 0 - 15 15 - 33 33 - 45 > 45 Correction factor Size selection is based on phase current 1.0 0.86 Size selection is based on neutral current 0.86 1.0 Fig. G19 : Correction factors for harmonic currents in four-core and five-core cables (table D.52.1 of IEC 60364-5-52) Admissible current as a function of nominal cross-sectional area of conductors IEC standard 60364-5-52 proposes extensive information in the form of tables giving the admissible currents as a function of cross-sectional area of cables. Many parameters are taken into account, such as the method of installation, type of insulation material, type of conductor material, number of loaded conductors. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors As an example, Figure G20 gives the current-carrying capacities for different methods of installation of PVC insulation, three loaded copper or aluminium conductors, free air or in ground. Nominal cross-sectional area of conductors (mm2) 1 Copper 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Aluminium 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Installation methods A1 A2 B1 B2 C D 2 3 4 5 6 7 13.5 18 24 31 42 56 73 89 108 136 164 188 216 245 286 328 13 17.5 23 29 39 52 68 83 99 125 150 172 196 223 261 298 15.5 21 28 36 50 68 89 110 134 171 207 239 - 15 20 27 34 46 62 80 99 118 149 179 206 - 17.5 24 32 41 57 76 96 119 144 184 223 259 299 341 403 464 18 24 31 39 52 67 86 103 122 151 179 203 230 258 297 336 14 18.5 24 32 43 57 70 84 107 129 149 170 194 227 261 13.5 17.5 23 31 41 53 65 78 98 118 135 155 176 207 237 16.5 22 28 39 53 70 86 104 133 161 186 - 15.5 21 27 36 48 62 77 92 116 139 160 - 18.5 25 32 44 59 73 90 110 140 170 197 227 259 305 351 18.5 24 30 40 52 66 80 94 117 138 157 178 200 230 260 G15 © Schneider Electric - all rights reserved Fig. G20 : Current-carrying capacities in amperes for different methods of installation, PVC insulation, three loaded conductors, copper or aluminium, conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground (table A.52.4 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors 2.3 Recommended simplified approach for cables In order to facilitate the selection of cables, 2 simplified tables are proposed, for unburied and buried cables. These tables summarize the most commonly used configurations and give easier access to the information. b Unburied cables: G16 Reference methods A1 A2 B1 B2 C E F 1 Size (mm2) Copper 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 Aluminium 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 Number of loaded conductors and type of insulation 2 3 4 3 XLPE 2 XLPE 3 XLPE 2 XLPE 3 PVC 2 PVC 3 XLPE 2 PVC 3 XLPE 2 XLPE 3 PVC 2 PVC 3 XLPE 3 PVC 2 PVC 3 PVC 5 6 7 8 9 13 17.5 23 29 39 52 68 - 13.5 18 24 31 42 56 73 - 14.5 19.5 26 34 46 61 80 - 15.5 21 28 36 50 68 89 110 134 171 207 239 - 17 23 31 40 54 73 95 117 141 179 216 249 285 324 380 18.5 25 34 43 60 80 101 126 153 196 238 276 318 362 424 19.5 27 36 46 63 85 110 137 167 213 258 299 344 392 461 22 30 40 51 70 94 119 147 179 229 278 322 371 424 500 23 31 42 54 75 100 127 158 192 246 298 346 395 450 538 24 33 45 58 80 107 135 169 207 268 328 382 441 506 599 26 36 49 63 86 115 149 185 225 289 352 410 473 542 641 161 200 242 310 377 437 504 575 679 13.5 17.5 23 31 41 53 - 14 18.5 24 32 43 57 - 15 20 26 36 48 63 - 16.5 22 28 39 53 70 86 104 133 161 186 - 18.5 25 32 44 58 73 90 110 140 170 197 226 256 300 19.5 26 33 46 61 78 96 117 150 183 212 245 280 330 21 28 36 49 66 83 103 125 160 195 226 261 298 352 23 31 39 54 73 90 112 136 174 211 245 283 323 382 24 32 42 58 77 97 120 146 187 227 263 304 347 409 26 35 45 62 84 101 126 154 198 241 280 324 371 439 28 38 49 67 91 108 135 164 211 257 300 346 397 470 121 150 184 237 289 337 389 447 530 3 PVC 2 PVC 2 PVC 3 PVC 3 PVC © Schneider Electric - all rights reserved Fig. G21a : Current-carrying capacity in amperes (table B.52-1 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 2 XLPE 2 XLPE 3 XLPE 2 XLPE 2 PVC 3 XLPE 2 XLPE 10 11 12 13 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors Correction factors are given in Figure G21b for groups of several circuits or multicore cables: Arrangement Number of circuits or multi-core cables 1 2 3 4 6 9 12 16 20 1.00 0.80 0.70 0.70 0.55 0.50 0.45 0.40 0.40 Embedded or enclosed Single layer on walls, floors or on unperforatedtrays Single layer fixed directly under a ceiling Single layer on perforated horizontal trays or on vertical trays Single layer on cable ladder supports or cleats, etc... 1.00 0.85 0.80 0.75 0.70 0.70 - - - 0.95 0.80 0.70 0.70 0.65 0.60 - - - 1.00 0.90 0.80 0.75 0.75 0.70 - - - 1.00 0.85 0.80 0.80 0.80 0.80 - - - Fig. G21b : Reduction factors for groups of several circuits or of several multi-core cables (table B.52-3 of IEC 60364-5-52) G17 b Buried cables: Installation Size method mm2 D Copper 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 D Aluminium 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Number of loaded conductors and type of insulation Two PVC Three PVC Two XLPE Three XLPE 22 29 38 47 63 81 104 125 148 183 216 246 278 312 361 408 18 24 31 39 52 67 86 103 122 151 179 203 230 258 297 336 26 34 44 56 73 95 121 146 173 213 252 287 324 363 419 474 22 29 37 46 61 79 101 122 144 178 211 240 271 304 351 396 22 29 36 48 62 80 96 113 140 166 189 213 240 277 313 18.5 24 30 40 52 66 80 94 117 138 157 178 200 230 260 26 34 42 56 73 93 112 132 163 193 220 249 279 322 364 22 29 36 47 61 78 94 112 138 164 186 210 236 272 308 Fig. G22 : Current-carrying capacity in amperes (table B.52-1 of IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved G - Sizing and protection of conductors G - Sizing and protection of conductors 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors 2.4 Busbar trunking systems The selection of busbar trunking systems is very straightforward, using the data provided by the manufacturer. Methods of installation, insulation materials, correction factors for grouping are not relevant parameters for this technology. The cross section area of any given model has been determined by the manufacturer based on: b The rated current, b An ambient air temperature equal to 35 °C, b 3 loaded conductors. Rated current The rated current can be calculated taking account of: b The layout, b The current absorbed by the different loads connected along the trunking system. Ambient temperature G18 A correction factor has to be applied for temperature higher than 35 °C. The correction factor applicable to medium and high power range (up to 4,000 A) is given in Figure G23a. °C Correction factor 35 1 40 0.97 45 0.93 50 0.90 55 0.86 Fig. G23a : Correction factor for air temperature higher than 35 °C Neutral current Where 3rd harmonic currents are circulating, the neutral conductor may be carrying a significant current and the corresponding additional power losses must be taken into account. Figure G23b represents the maximum admissible phase and neutral currents (per unit) in a high power busbar trunking system as functions of 3rd harmonic level. Maximum admissible current (p.u) 1.4 Neutral conductor 1.2 1 0.8 0.6 Phase conductor 0.4 0.2 0 0 10 20 30 40 50 60 70 80 90 © Schneider Electric - all rights reserved 3rd harmonic current level (%) Fig. G23b : Maximum admissible currents (p.u.) in a busbar trunking system as functions of the 3rd harmonic level. Schneider Electric - Electrical installation guide 2009 2 Practical method for determining the smallest allowable crosssectional area of circuit conductors The layout of the trunking system depends on the position of the current consumers, the location of the power source and the possibilities for fixing the system. v One single distribution line serves a 4 to 6 meter area v Protection devices for current consumers are placed in tap-off units, connected directly to usage points. v One single feeder supplies all current consumers of different powers. Once the trunking system layout is established, it is possible to calculate the absorbed current In on the distribution line. In is equal to the sum of absorbed currents by the current In consumers: In = Σ IB. The current consumers do not all work at the same time and are not permanently on full load, so we have to use a clustering coefficient kS : In = Σ (IB . kS). Application Number of current consumers Lighting, Heating Distribution (engineering workshop) Ks Coefficient 1 2...3 4...5 6...9 10...40 40 and over 0.9 0.8 0.7 0.6 0.5 G19 Note : for industrial installations, remember to take account of upgrading of the machine equipment base. As for a switchboard, a 20 % margin is recommended: In ≤ IB x ks x 1.2. Fig G24 : Clustering coefficient according to the number of current consumers © Schneider Electric - all rights reserved G - Sizing and protection of conductors Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 3 Determination of voltage drop The impedance of circuit conductors is low but not negligible: when carrying load current there is a voltage drop between the origin of the circuit and the load terminals. The correct operation of a load (a motor, lighting circuit, etc.) depends on the voltage at its terminals being maintained at a value close to its rated value. It is necessary therefore to determine the circuit conductors such that at full-load current, the load terminal voltage is maintained within the limits required for correct performance. This section deals with methods of determining voltage drops, in order to check that: b They comply with the particular standards and regulations in force b They can be tolerated by the load b They satisfy the essential operational requirements 3.1 Maximum voltage drop Maximum allowable voltage-drop vary from one country to another. Typical values for LV installations are given below in Figure G25. G20 Type of installations A low-voltage service connection from a LV public power distribution network Consumers MV/LV substation supplied from a public distribution MV system Lighting circuits 3% Other uses (heating and power) 5% 6% 8% Fig. G25 : Maximum voltage-drop between the service-connection point and the point of utilization These voltage-drop limits refer to normal steady-state operating conditions and do not apply at times of motor starting, simultaneous switching (by chance) of several loads, etc. as mentioned in Chapter A Sub-clause 4.3 (factor of simultaneity, etc.). When voltage drops exceed the values shown in Figure G25, larger cables (wires) must be used to correct the condition. The value of 8%, while permitted, can lead to problems for motor loads; for example: b In general, satisfactory motor performance requires a voltage within ± 5% of its rated nominal value in steady-state operation, b Starting current of a motor can be 5 to 7 times its full-load value (or even higher). If an 8% voltage drop occurs at full-load current, then a drop of 40% or more will occur during start-up. In such conditions the motor will either: v Stall (i.e. remain stationary due to insufficient torque to overcome the load torque) with consequent over-heating and eventual trip-out v Or accelerate very slowly, so that the heavy current loading (with possibly undesirable low-voltage effects on other equipment) will continue beyond the normal start-up period b Finally an 8% voltage drop represents a continuous power loss, which, for continuous loads will be a significant waste of (metered) energy. For these reasons it is recommended that the maximum value of 8% in steady operating conditions should not be reached on circuits which are sensitive to under-voltage problems (see Fig. G26). © Schneider Electric - all rights reserved MV consumer LV consumer 8% (1) 5% (1) Load Fig. G26 : Maximum voltage drop Schneider Electric - Electrical installation guide 2009 (1) Between the LV supply point and the load 3 Determination of voltage drop 3.2 Calculation of voltage drop in steady load conditions Use of formulae Figure G27 below gives formulae commonly used to calculate voltage drop in a given circuit per kilometre of length. If: b IB: The full load current in amps b L: Length of the cable in kilometres b R: Resistance of the cable conductor in Ω/km R= R= 22.5 Ω mm2 / km ( ) for copper ) for aluminium S c.s.a. in mm2 36 Ω mm2 / km ( S c.s.a. in mm2 Note: R is negligible above a c.s.a. of 500 mm2 b X: inductive reactance of a conductor in Ω/km Note: X is negligible for conductors of c.s.a. less than 50 mm2. In the absence of any other information, take X as being equal to 0.08 Ω/km. b ϕ: phase angle between voltage and current in the circuit considered, generally: v Incandescent lighting: cos ϕ = 1 v Motor power: - At start-up: cos ϕ = 0.35 - In normal service: cos ϕ = 0.8 b Un: phase-to-phase voltage b Vn: phase-to-neutral voltage G21 For prefabricated pre-wired ducts and bustrunking, resistance and inductive reactance values are given by the manufacturer. Circuit Voltage drop (ΔU) in volts in % Single phase: phase/phase ∆U = 2 I B(R cos ϕ + X sin ϕ) L 100 ∆U Un Single phase: phase/neutral ∆U = 2 I B(R cos ϕ + X sin ϕ) L 100 ∆U Vn Balanced 3-phase: 3 phases ∆U = 3 I B(R cos ϕ + X sin ϕ) L 100 ∆U Un (with or without neutral) Fig. G27 : Voltage-drop formulae Simplified table Calculations may be avoided by using Figure G28 next page, which gives, with an adequate approximation, the phase-to-phase voltage drop per km of cable per ampere, in terms of: b Kinds of circuit use: motor circuits with cos ϕ close to 0.8, or lighting with a cos ϕ close to 1. b Type of cable; single-phase or 3-phase Voltage drop in a cable is then given by: K x IB x L K is given by the table, IB is the full-load current in amps, L is the length of cable in km. The column motor power “cos ϕ = 0.35” of Figure G28 may be used to compute the voltage drop occurring during the start-up period of a motor (see example no. 1 after the Figure G28). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved G - Sizing and protection of conductors G - Sizing and protection of conductors c.s.a. in mm2 G22 Cu 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 Al 10 16 25 35 50 70 120 150 185 240 300 400 500 3 Determination of voltage drop Single-phase circuit Motor power Normal service Start-up cos ϕ = 0.8 24 14.4 9.1 6.1 3.7 2.36 1.5 1.15 0.86 0.64 0.48 0.39 0.33 0.29 0.24 0.21 Lighting cos ϕ = 0.35 10.6 6.4 4.1 2.9 1.7 1.15 0.75 0.6 0.47 0.37 0.30 0.26 0.24 0.22 0.2 0.19 cos ϕ = 1 30 18 11.2 7.5 4.5 2.8 1.8 1.29 0.95 0.64 0.47 0.37 0.30 0.24 0.19 0.15 Balanced three-phase circuit Motor power Normal service Start-up cos ϕ = 0.8 20 12 8 5.3 3.2 2.05 1.3 1 0.75 0.56 0.42 0.34 0.29 0.25 0.21 0.18 cos ϕ = 0.35 9.4 5.7 3.6 2.5 1.5 1 0.65 0.52 0.41 0.32 0.26 0.23 0.21 0.19 0.17 0.16 Lighting cos ϕ = 1 25 15 9.5 6.2 3.6 2.4 1.5 1.1 0.77 0.55 0.4 0.31 0.27 0.2 0.16 0.13 Fig. G28 : Phase-to-phase voltage drop ΔU for a circuit, in volts per ampere per km Examples Example 1 (see Fig. G29) A three-phase 35 mm2 copper cable 50 metres long supplies a 400 V motor taking: b 100 A at a cos ϕ = 0.8 on normal permanent load b 500 A (5 In) at a cos ϕ = 0.35 during start-up The voltage drop at the origin of the motor cable in normal circumstances (i.e. with the distribution board of Figure G29 distributing a total of 1,000 A) is 10 V phase-tophase. What is the voltage drop at the motor terminals: b In normal service? b During start-up? Solution: b Voltage drop in normal service conditions: ∆U ∆U% = 100 1,000 A Un Table G28 shows 1 V/A/km so that: ΔU for the cable = 1 x 100 x 0.05 = 5 V ΔU total = 10 + 5 = 15 V = i.e. 400 V 15 x 100 = 3.75% 400 This value is less than that authorized (8%) and is satisfactory. b Voltage drop during motor start-up: ΔUcable = 0.52 x 500 x 0.05 = 13 V 50 m / 35 mm2 Cu IB = 100 A © Schneider Electric - all rights reserved (500 A du ring start-up) Owing to the additional current taken by the motor when starting, the voltage drop at the distribution board will exceed 10 Volts. Supposing that the infeed to the distribution board during motor starting is 900 + 500 = 1,400 A then the voltage drop at the distribution board will increase approximately pro rata, i.e. 10 x 1,400 = 14 V 1,000 ΔU distribution board = 14 V ΔU for the motor cable = 13 V ΔU total = 13 + 14 = 27 V i.e. 27 x 100 = 6.75% 400 Fig. G29 : Example 1 a value which is satisfactory during motor starting. Schneider Electric - Electrical installation guide 2009 3 Determination of voltage drop Example 2 (see Fig. G30) A 3-phase 4-wire copper line of 70 mm2 c.s.a. and a length of 50 m passes a current of 150 A. The line supplies, among other loads, 3 single-phase lighting circuits, each of 2.5 mm2 c.s.a. copper 20 m long, and each passing 20 A. It is assumed that the currents in the 70 mm2 line are balanced and that the three lighting circuits are all connected to it at the same point. What is the voltage drop at the end of the lighting circuits? Solution: b Voltage drop in the 4-wire line: ∆U ∆U% = 100 Un ΔU line = 0.55 x 150 x 0.05 = 4.125 V phase-to-phase Figure G28 shows 0.55 V/A/km which gives: 4 . 125 phase to to neutral. neutral. = 2.38 V phase 3 b Voltage drop in any one of the lighting single-phase circuits: ΔU for a single-phase circuit = 18 x 20 x 0.02 = 7.2 V The total voltage drop is therefore 7.2 + 2.38 = 9.6 V G23 9.6 V x 100 = 4.2% 230 V This value is satisfactory, being less than the maximum permitted voltage drop of 6%. 50 m / 70 mm2 Cu IB = 150 A 20 m / 2.5 mm2 Cu IB = 20 A Fig. G30 : Example 2 © Schneider Electric - all rights reserved G - Sizing and protection of conductors Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 4 Short-circuit current A knowledge of 3-phase symmetrical short-circuit current values (Isc) at strategic points of an installation is necessary in order to determine switchgear (fault current rating), cables (thermal withstand rating), protective devices (discriminative trip settings) and so on... In the following notes a 3-phase short-circuit of zero impedance (the so-called bolted short-circuit) fed through a typical MV/LV distribution transformer will be examined. Except in very unusual circumstances, this type of fault is the most severe, and is certainly the simplest to calculate. Short-circuit currents occurring in a network supplied from a generator and also in DC systems are dealt with in Chapter N. The simplified calculations and practical rules which follow give conservative results of sufficient accuracy, in the large majority of cases, for installation design purposes. Knowing the levels of 3-phase symmetrical short-circuit currents (Isc) at different points in an installation is an essential feature of its design 4.1 Short-circuit current at the secondary terminals of a MV/LV distribution transformer The case of one transformer b In a simplified approach, the impedance of the MV system is assumed to be G24 negligibly small, so that: I sc = I n x 100 Usc where I n = P x 103 and : U20 3 P = kVA rating of the transformer U20 = phase-to-phase secondary volts on open circuit In = nominal current in amps Isc = short-circuit fault current in amps Usc = short-circuit impedance voltage of the transformer in %. Typical values of Usc for distribution transformers are given in Figure G31. Transformer rating (kVA) Usc in % Oil-immersed 50 to 750 800 to 3,200 4 6 Cast-resin dry type 6 6 Fig. G31 : Typical values of Usc for different kVA ratings of transformers with MV windings y 20 kV b Example 400 kVA transformer, 420 V at no load Usc = 4% In = 400 x 103 = 550 A 420 x 3 I sc = 550 x 100 = 13.7 kA 4 The case of several transformers in parallel feeding a busbar The value of fault current on an outgoing circuit immediately downstream of the busbars (see Fig. G32) can be estimated as the sum of the Isc from each transformer calculated separately. Isc1 Isc2 Isc3 © Schneider Electric - all rights reserved Isc1 + Isc2 + Isc3 Fig. G32 : Case of several transformers in parallel It is assumed that all transformers are supplied from the same MV network, in which case the values obtained from Figure G31 when added together will give a slightly higher fault-level value than would actually occur. Other factors which have not been taken into account are the impedance of the busbars and of the circuit-breakers. The conservative fault-current value obtained however, is sufficiently accurate for basic installation design purposes. The choice of circuit-breakers and incorporated protective devices against short-circuit fault currents is described in Chapter H Subclause 4.4. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 4 Short-circuit current 4.2 3-phase short-circuit current (Isc) at any point within a LV installation In a 3-phase installation Isc at any point is given by: I sc = U20 3 ZT where U20 = phase-to-phase voltage of the open circuited secondary windings of the power supply transformer(s). ZT = total impedance per phase of the installation upstream of the fault location (in Ω) Method of calculating ZT Each component of an installation (MV network, transformer, cable, circuit-breaker, busbar, and so on...) is characterized by its impedance Z, comprising an element of resistance (R) and an inductive reactance (X). It may be noted that capacitive reactances are not important in short-circuit current calculations. The parameters R, X and Z are expressed in ohms, and are related by the sides of a right angled triangle, as shown in the impedance diagram of Figure G33. Z The method consists in dividing the network into convenient sections, and to calculate the R and X values for each. X Where sections are connected in series in the network, all the resistive elements in the section are added arithmetically; likewise for the reactances, to give RT and XT. The impedance (ZT) for the combined sections concerned is then calculated from R G25 Z T = RT 2 + X T 2 Fig. G33 : Impedance diagram Any two sections of the network which are connected in parallel, can, if predominantly both resistive (or both inductive) be combined to give a single equivalent resistance (or reactance) as follows: Let R1 and R2 be the two resistances connected in parallel, then the equivalent resistance R3 will be given by: R3 = R1 x R2 R1 + R2 or for reactances X 3 = X1 x X2 X1 + X2 It should be noted that the calculation of X3 concerns only separated circuit without mutual inductance. If the circuits in parallel are close togother the value of X3 will be notably higher. Determination of the impedance of each component b Network upstream of the MV/LV transformer (see Fig. G34) The 3-phase short-circuit fault level PSC, in kA or in MVA(1) is given by the power supply authority concerned, from which an equivalent impedance can be deduced. Psc 250 MVA 500 MVA Uo (V) 420 420 Ra (mΩ) 0.07 0.035 Xa (mΩ) 0.7 0.351 Fig. G34 : The impedance of the MV network referred to the LV side of the MV/LV transformer where Zs = impedance of the MV voltage network, expessed in milli-ohms Uo = phase-to-phase no-load LV voltage, expressed in volts Psc = MV 3-phase short-circuit fault level, expressed in kVA The upstream (MV) resistance Ra is generally found to be negligible compared with the corresponding Xa, the latter then being taken as the ohmic value for Za. If more accurate calculations are necessary, Xa may be taken to be equal to 0.995 Za and Ra equal to 0.1 Xa. (1) Short-circuit MVA: 3 EL Isc where: b EL = phase-to-phase nominal system voltage expressed in kV (r.m.s.) b Isc = 3-phase short-circuit current expressed in kA (r.m.s.) (2) up to 36 kV Figure G36 gives values for Ra and Xa corresponding to the most common MV(2) short-circuit levels in utility power-supply networks, namely, 250 MVA and 500 MVA. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved A formula which makes this deduction and at the same time converts the impedance to an equivalent value at LV is given, as follows: U 2 Zs = 0 Psc G - Sizing and protection of conductors 4 Short-circuit current b Transformers (see Fig. G35) The impedance Ztr of a transformer, viewed from the LV terminals, is given by the formula: U 2 Usc Ztr = 20 x Pn 100 where: U20 = open-circuit secondary phase-to-phase voltage expressed in volts Pn = rating of the transformer (in kVA) Usc = the short-circuit impedance voltage of the transformer expressed in % The transformer windings resistance Rtr can be derived from the total losses as follows: Pcu = 3 I n2 x Rtr so that Rtr = Pcu x 103 in milli-ohms 3 I n2 where Pcu = total losses in watts In = nominal full-load current in amps Rtr = resistance of one phase of the transformer in milli-ohms (the LV and corresponding MV winding for one LV phase are included in this resistance value). Xtr = Ztr 2 − Rtr 2 For an approximate calculation Rtr may be ignored since X ≈ Z in standard distribution type transformers. G26 Rated Oil-immersed Usc (%) Rtr (mΩ) Xtr (mΩ) Ztr (mΩ) Cast-resin Power (kVA) 100 160 200 250 315 400 500 630 800 1,000 1,250 1,600 2,000 Usc (%) Rtr (mΩ) Xtr (mΩ) Ztr (mΩ) 4 4 4 4 4 4 4 4 6 6 6 6 6 37.9 16.2 11.9 9.2 6.2 5.1 3.8 2.9 2.9 2.3 1.8 1.4 1.1 59.5 41.0 33.2 26.7 21.5 16.9 13.6 10.8 12.9 10.3 8.3 6.5 5.2 70.6 44.1 35.3 28.2 22.4 17.6 14.1 11.2 13.2 10.6 8.5 6.6 5.3 6 6 6 6 6 6 6 6 6 6 6 6 6 37.0 18.6 14.1 10.7 8.0 6.1 4.6 3.5 2.6 1.9 1.5 1.1 0.9 99.1 63.5 51.0 41.0 32.6 25.8 20.7 16.4 13.0 10.4 8.3 6.5 5.2 105.8 66.2 52.9 42.3 33.6 26.5 21.2 16.8 13.2 10.6 8.5 6.6 5.3 Fig. G35 : Resistance, reactance and impedance values for typical distribution 400 V transformers with MV windings y 20 kV b Circuit-breakers In LV circuits, the impedance of circuit-breakers upstream of the fault location must be taken into account. The reactance value conventionally assumed is 0.15 mΩ per CB, while the resistance is neglected. © Schneider Electric - all rights reserved b Busbars The resistance of busbars is generally negligible, so that the impedance is practically all reactive, and amounts to approximately 0.15 mΩ/metre(1) length for LV busbars (doubling the spacing between the bars increases the reactance by about 10% only). b Circuit conductors L The resistance of a conductor is given by the formula: Rc = ρ S where ρ = the resistivity constant of the conductor material at the normal operating temperature being: v 22.5 mΩ.mm2/m for copper v 36 mΩ.mm2/m for aluminium L = length of the conductor in m S = c.s.a. of conductor in mm2 (1) For 50 Hz systems, but 0.18 mΩ/m length at 60 Hz Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 4 Short-circuit current Cable reactance values can be obtained from the manufacturers. For c.s.a. of less than 50 mm2 reactance may be ignored. In the absence of other information, a value of 0.08 mΩ/metre may be used (for 50 Hz systems) or 0.096 mΩ/metre (for 60 Hz systems). For prefabricated bus-trunking and similar pre-wired ducting systems, the manufacturer should be consulted. b Motors At the instant of short-circuit, a running motor will act (for a brief period) as a generator, and feed current into the fault. In general, this fault-current contribution may be ignored. However, if the total power of motors running simultaneously is higher than 25% of the total power of transformers, the influence of motors must be taken into account. Their total contribution can be estimated from the formula: Iscm = 3.5 In from each motor i.e. 3.5mIn for m similar motors operating concurrently. The motors concerned will be the 3-phase motors only; single-phase-motor contribution being insignificant. b Fault-arc resistance Short-circuit faults generally form an arc which has the properties of a resistance. The resistance is not stable and its average value is low, but at low voltage this resistance is sufficient to reduce the fault-current to some extent. Experience has shown that a reduction of the order of 20% may be expected. This phenomenon will effectively ease the current-breaking duty of a CB, but affords no relief for its faultcurrent making duty. G27 b Recapitulation table (see Fig. G36) Parts of power-supply system Supply network Figure G34 Transformer Figure G35 R (mΩ) X (mΩ) Ra = 0.1 Xa Xa = 0.995 Za; Za = Rtr = Circuit-breaker Rtr is often negligible compared to Xtr for transformers > 100 kVA Negligible Busbars Negligible for S > 200 mm2 in the formula: L S L R=ρ S R=ρ Circuit conductors(2) M Pcu x 103 3 I n2 Motors (1) U202 Psc Ztr 2 − Rtr 2 with Ztr = U202 Usc x Pn 100 XD = 0.15 mΩ/pole XB = 0.15 mΩ/m Cables: Xc = 0.08 mΩ/m (1) See Sub-clause 4.2 Motors (often negligible at LV) Three-phase short circuit current in kA U20 I sc = 3 RT 2 + XT 2 U20: Phase-to-phase no-load secondary voltage of MV/LV transformer (in volts). Psc: 3-phase short-circuit power at MV terminals of the MV/LV transformers (in kVA). Pcu: 3-phase total losses of the MV/LV transformer (in watts). Pn: Rating of the MV/LV transformer (in kVA). Usc: Short-circuit impedance voltage of the MV/LV transfomer (in %). RT : Total resistance. XT: Total reactance (1) ρ = resistivity at normal temperature of conductors in service b ρ = 22.5 mΩ x mm2/m for copper b ρ = 36 mΩ x mm2/m for aluminium (2) If there are several conductors in parallel per phase, then divide the resistance of one conductor by the number of conductors. The reactance remains practically unchanged. © Schneider Electric - all rights reserved Fig. G36 : Recapitulation table of impedances for different parts of a power-supply system Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 4 Short-circuit current b Example of short-circuit calculations (see Fig. G37) LV installation G28 MV network Psc = 500 MVA Transformer 20 kV/420 V Pn = 1000 kVA Usc = 5% Pcu = 13.3 x 103 watts Single-core cables 5 m copper 4 x 240 mm2/phase Main circuit-breaker Busbars 10 m Three-core cable 100 m 95 mm2 copper Three-core cable 20 m 10 mm2 copper final circuits R (mΩ) X (mΩ) 0.035 0.351 2.24 8.10 Rc = 22.5 5 x = 0.12 4 240 Xc = 0.08 x 5 = 0.40 RT (mΩ) XT (mΩ) I sc = 2.41 8.85 Isc1 = 26 kA 420 3 RT 2 + XT 2 RD = 0 XD = 0.15 RB = 0 XB = 1.5 2.41 10.5 Isc2 = 22 kA Xc = 100 x 0.08 = 8 26.1 18.5 Isc3 = 7.4 kA Xc = 20 x 0.08 = 1.6 71.1 20.1 Isc4 = 3.2 kA Rc = 22.5 x Rc = 22.5 x 100 = 23.68 95 20 = 45 10 Fig. G37 : Example of short-circuit current calculations for a LV installation supplied at 400 V (nominal) from a 1,000 kVA MV/LV transformer 4.3 Isc at the receiving end of a feeder as a function of the Isc at its sending end The network shown in Figure G38 typifies a case for the application of Figure G39 next page, derived by the «method of composition» (mentioned in Chapter F Subclause 6.2). These tables give a rapid and sufficiently accurate value of short-circuit current at a point in a network, knowing: b The value of short-circuit current upstream of the point considered b The length and composition of the circuit between the point at which the shortcircuit current level is known, and the point at which the level is to be determined It is then sufficient to select a circuit-breaker with an appropriate short-circuit fault rating immediately above that indicated in the tables. If more precise values are required, it is possible to make a detailled calculation (see Sub-Clause 4.2) or to use a software package, such as Ecodial. In such a case, moreover, the possibility of using the cascading technique should be considered, in which the use of a current limiting circuit-breaker at the upstream position would allow all circuit-breakers downstream of the limiter to have a short-circuit current rating much lower than would otherwise be necessary (See chapter H Sub-Clause 4.5). Method Select the c.s.a. of the conductor in the column for copper conductors (in this example the c.s.a. is 47.5 mm2). Search along the row corresponding to 47.5 mm2 for the length of conductor equal to that of the circuit concerned (or the nearest possible on the low side). Descend vertically the column in which the length is located, and stop at a row in the middle section (of the 3 sections of the Figure) corresponding to the known fault-current level (or the nearest to it on the high side). 400 V © Schneider Electric - all rights reserved Isc = 28 kA 47,5 mm2, Cu 20 m In this case 30 kA is the nearest to 28 kA on the high side. The value of short-circuit current at the downstream end of the 20 metre circuit is given at the intersection of the vertical column in which the length is located, and the horizontal row corresponding to the upstream Isc (or nearest to it on the high side). Isc = ? This value in the example is seen to be 14.7 kA. IB = 55 A The procedure for aluminium conductors is similar, but the vertical column must be ascended into the middle section of the table. IB = 160 A Fig. G38 : Determination of downstream short-circuit current level Isc using Figure G39 In consequence, a DIN-rail-mounted circuit-breaker rated at 63 A and Isc of 25 kA (such as a NG 125N unit) can be used for the 55 A circuit in Figure G38. A Compact rated at 160 A with an Isc capacity of 25 kA (such as a NS160 unit) can be used to protect the 160 A circuit. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 4 Short-circuit current Copper 230 V / 400 V c.s.a. of phase conductors (mm2) 1.5 2.5 4 6 10 16 25 35 47.5 70 95 120 150 185 240 300 2x120 2x150 2x185 553x120 3x150 3x185 Isc upstream (in kA) 100 90 80 70 60 50 40 35 30 25 20 15 10 7 5 4 3 2 1 Length of circuit (in metres) 1.6 2.3 1.2 1.8 2.5 1.5 2.1 2.9 1.8 2.6 3.7 2.2 3.1 4.4 2.3 3.2 4.6 2.5 3.5 5.0 2.9 4.2 5.9 3.4 4.9 6.9 3.7 5.3 7.5 4.4 6.2 8.8 Isc downstream (in kA) 93 90 87 84 82 79 75 74 71 66 65 63 57 56 55 48 47 46 39 38 38 34 34 33 29 29 29 25 24 24 20 20 19.4 14.8 14.8 14.7 9.9 9.9 9.8 7.0 6.9 6.9 5.0 5.0 5.0 4.0 4.0 4.0 3.0 3.0 3.0 2.0 2.0 2.0 1.0 1.0 1.0 1.1 1.2 1.7 1.8 2.6 2.2 3.0 4.3 1.7 2.4 3.4 4.9 6.9 1.3 1.9 2.7 3.8 5.4 7.6 10.8 1.9 2.7 3.8 5.3 7.5 10.6 15.1 1.8 2.6 3.6 5.1 7.2 10.2 14.4 20 2.7 3.8 5.3 7.5 10.7 15.1 21 30 2.6 3.6 5.1 7.2 10.2 14.5 20 29 41 3.2 4.6 6.5 9.1 12.9 18.3 26 37 52 3.5 5.0 7.0 9.9 14.0 19.8 28 40 56 4.2 5.9 8.3 11.7 16.6 23 33 47 66 5.2 7.3 10.3 14.6 21 29 41 58 83 6.2 8.8 12.4 17.6 25 35 50 70 99 6.5 9.1 12.9 18.3 26 37 52 73 103 7.0 9.9 14.0 20 28 40 56 79 112 8.3 11.7 16.6 23 33 47 66 94 133 9.7 13.7 19.4 27 39 55 77 110 155 10.5 14.9 21 30 42 60 84 119 168 12.5 17.6 25 35 50 70 100 141 199 1.5 2.4 3.6 6.1 9.7 15.2 21 29 43 58 73 79 94 117 140 146 159 187 219 238 281 1.3 2.1 3.4 5.2 8.6 13.8 21 30 41 60 82 103 112 133 165 198 206 224 265 309 336 398 1.8 3.0 4.9 7.3 12.2 19.4 30 43 58 85 115 146 159 187 233 280 292 317 375 438 476 562 2.6 4.3 6.9 10.3 17.2 27 43 60 82 120 163 206 224 265 330 396 412 448 530 619 672 82 75 68 61 53 45 37 33 28 24 19.2 14.5 9.8 6.9 4.9 4.0 3.0 2.0 1.0 22 22 21 20 20 18.3 16.8 15.8 14.7 13.4 11.8 9.9 7.4 5.6 4.3 3.5 2.7 1.9 1.0 17.0 16.7 16.3 15.8 15.2 14.5 13.5 12.9 12.2 11.2 10.1 8.7 6.7 5.2 4.0 3.3 2.6 1.8 1.0 12.6 12.5 12.2 12.0 11.6 11.2 10.6 10.2 9.8 9.2 8.4 7.4 5.9 4.7 3.7 3.1 2.5 1.8 0.9 9.3 9.2 9.1 8.9 8.7 8.5 8.1 7.9 7.6 7.3 6.8 6.1 5.1 4.2 3.4 2.9 2.3 1.7 0.9 6.7 6.7 6.6 6.6 6.5 6.3 6.1 6.0 5.8 5.6 5.3 4.9 4.2 3.6 3.0 2.6 2.1 1.6 0.9 4.9 4.8 4.8 4.8 4.7 4.6 4.5 4.5 4.4 4.2 4.1 3.8 3.4 3.0 2.5 2.2 1.9 1.4 0.8 3.5 3.5 3.5 3.4 3.4 3.4 3.3 3.3 3.2 3.2 3.1 2.9 2.7 2.4 2.1 1.9 1.6 1.3 0.8 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.4 2.4 2.3 2.3 2.2 2.0 1.9 1.7 1.6 1.4 1.1 0.7 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.3 1.2 1.1 1.0 0.6 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.0 1.0 0.9 0.8 0.6 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.8 0.8 0.8 0.7 0.7 0.6 0.5 1.1 1.6 1.9 2.7 2.2 3.1 4.3 1.7 2.4 3.4 4.8 6.8 1.7 2.4 3.4 4.7 6.7 9.5 1.6 2.3 3.2 4.6 6.4 9.1 12.9 2.4 3.4 4.7 6.7 9.5 13.4 19.0 2.3 3.2 4.6 6.4 9.1 12.9 18.2 26 2.9 4.1 5.8 8.1 11.5 16.3 23 32 3.1 4.4 6.3 8.8 12.5 17.7 25 35 3.7 5.2 7.4 10.4 14.8 21 30 42 4.6 6.5 9.2 13.0 18.4 26 37 52 5.5 7.8 11.1 15.6 22 31 44 62 5.8 8.1 11.5 16.3 23 33 46 65 6.3 8.8 12.5 17.7 25 35 50 71 7.4 10.5 14.8 21 30 42 59 83 9.2 13.0 18.4 26 37 52 74 104 8.6 12.2 17.3 24 34 49 69 97 9.4 13.3 18.8 27 37 53 75 106 11.1 15.7 22 31 44 63 89 125 13.8 19.5 28 39 55 78 110 156 1.5 2.3 3.8 6.1 9.6 13.4 18.2 27 36 46 50 59 73 88 92 100 118 147 138 150 177 220 1.4 2.2 3.2 5.4 8.7 13.5 18.9 26 38 51 65 71 83 104 125 130 141 167 208 195 212 250 312 1.9 3.1 4.6 7.7 12.2 19.1 27 36 54 73 92 100 118 147 177 184 200 236 294 275 299 354 441 2.7 4.3 6.5 10.8 17.3 27 38 51 76 103 130 141 167 208 250 260 282 334 415 389 423 500 623 3.8 6.1 9.2 15.3 24 38 54 73 107 145 184 199 236 294 353 367 399 472 587 551 598 707 5.4 8.6 13.0 22 35 54 76 103 151 205 259 282 333 415 499 519 7.6 12.2 18.3 31 49 76 107 145 214 290 367 399 471 10.8 17.3 26 43 69 108 151 205 303 411 15.3 24 37 61 98 153 214 290 428 22 35 52 86 138 216 302 410 77 71 64 58 51 43 36 32 27 23 18.8 14.3 9.7 6.9 4.9 4.0 3.0 2.0 1.0 70 65 59 54 48 41 34 30 27 23 18.4 14.1 9.6 6.8 4.9 3.9 3.0 2.0 1.0 62 58 54 49 44 38 32 29 25 22 17.8 13.7 9.4 6.7 4.9 3.9 2.9 2.0 1.0 54 51 47 44 39 35 30 27 24 21 17.0 13.3 9.2 6.6 4.8 3.9 2.9 2.0 1.0 45 43 40 38 35 31 27 24 22 19.1 16.1 12.7 8.9 6.4 4.7 3.8 2.9 2.0 1.0 37 35 34 32 29 27 24 22 20 17.4 14.9 11.9 8.5 6.2 4.6 3.7 2.9 1.9 1.0 29 28 27 26 24 22 20 18.8 17.3 15.5 13.4 11.0 8.0 6.0 4.5 3.6 2.8 1.9 1.0 3.6 6.1 9.7 14.6 24 39 61 85 115 170 231 291 317 374 466 561 583 634 749 5.2 8.6 13.7 21 34 55 86 120 163 240 326 412 448 529 659 7.3 12.1 19.4 29 49 78 121 170 231 340 461 10.3 17.2 27 41 69 110 172 240 326 14.6 24 39 58 97 155 243 340 461 21 34 55 82 137 220 343 480 G29 Aluminium 230 V / 400 V Length of circuit (in metres) 1.2 1.4 1.4 1.6 1.9 2.3 2.2 2.3 2.8 3.5 1.6 2.0 2.0 2.2 2.6 3.3 3.1 3.3 3.9 4.9 2.3 2.8 2.9 3.1 3.7 4.6 4.3 4.7 5.5 6.9 2.6 3.3 3.9 4.1 4.4 5.2 6.5 6.1 6.6 7.8 9.8 Note: for a 3-phase system having 230 V between phases, divide the above lengths by 3 Fig. G39 : Isc at a point downstream, as a function of a known upstream fault-current value and the length and c.s.a. of the intervening conductors, in a 230/400 V 3-phase system 4.4 Short-circuit current supplied by a generator or an inverter: Please refer to Chapter N Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved c.s.a. of phase conductors (mm2) 2.5 4 6 10 16 25 35 47.5 70 95 120 150 185 240 300 2x120 2x150 2x185 2x240 3x120 3x150 3x185 3x240 G - Sizing and protection of conductors 5 Particular cases of short-circuit current 5.1 Calculation of minimum levels of short-circuit current If a protective device in a circuit is intended only to protect against short-circuit faults, it is essential that it will operate with certainty at the lowest possible level of short-circuit current that can occur on the circuit In general, on LV circuits, a single protective device protects against all levels of current, from the overload threshold through the maximum rated short-circuit currentbreaking capability of the device. In certain cases, however, overload protective devices and separate short-circuit protective devices are used. Examples of such arrangements Figures G40 to G42 show some common arrangements where overload and short-circuit protections are achieved by separate devices. aM fuses (no protection against overload) G30 Load breaking contactor with thermal overload relay Circuit breaker with instantaneous magnetic short-circuit protective relay only Fig. G40 : Circuit protected by aM fuses As shown in Figures G40 and G41, the most common circuits using separate devices control and protect motors. Figure G42a constitutes a derogation in the basic protection rules, and is generally used on circuits of prefabricated bustrunking, lighting rails, etc. Load breaking contactor with thermal overload relay Fig. G41 : Circuit protected by circuit-breaker without thermal overload relay Variable speed drive Figure G42b shows the functions provided by the variable speed drive, and if necessary some additional functions provided by devices such as circuit-breaker, thermal relay, RCD. Protection to be provided Circuit breaker D Cable overload Motor overload Downstream short-circuit Variable speed drive overload Overvoltage Undervoltage Loss of phase Upstream short-circuit S1 Protection generally provided by the variable speed drive Yes = (1) Yes = (2) Yes Yes Yes Yes Yes © Schneider Electric - all rights reserved Internal fault Load with incorporated overload protection S2 < S1 Downstream earth fault (indirect contact) Direct contact fault Fig. G42a : Circuit-breaker D provides protection against shortcircuit faults as far as and including the load (self protection) Additional protection Not necessary if (1) Not necessary if (2) Circuit-breaker (short-circuit tripping) Circuit-breaker (short-circuit and overload tripping) RCD u 300 mA RCD y 30 mA Figure G42b : Protection to be provided for variable speeed drive applications Schneider Electric - Electrical installation guide 2009 The protective device must fulfill: b instantaneous trip setting Im < Iscmin for a circuit-breaker b fusion current Ia < Iscmin for a fuse 5 Particular cases of short-circuit current Conditions to be fulfilled The protective device must therefore satisfy the two following conditions: b Its fault-current breaking rating must be greater than Isc, the 3-phase short-circuit current at its point of installation b Elimination of the minimum short-circuit current possible in the circuit, in a time tc compatible with the thermal constraints of the circuit conductors, where: (valid for tc < 5 seconds) K 2S 2 tc i I scmin2 Comparison of the tripping or fusing performance curve of protective devices, with the limit curves of thermal constraint for a conductor shows that this condition is satisfied if: b Isc (min) > Im (instantaneous or short timedelay circuit-breaker trip setting current level), (see Fig. G45) b Isc (min) > Ia for protection by fuses. The value of the current Ia corresponds to the crossing point of the fuse curve and the cable thermal withstand curve (see Fig. G44 and G45) G31 t t= k2 S2 I2 I Im Fig. G45 : Protection by circuit-breaker t t= k2 S2 I2 I Ia Fig. G46 : Protection by aM-type fuses t t= Ia Fig. G47 : Protection by gl-type fuses Schneider Electric - Electrical installation guide 2009 k2 S2 I2 I © Schneider Electric - all rights reserved G - Sizing and protection of conductors G - Sizing and protection of conductors 5 Particular cases of short-circuit current In practice this means that the length of circuit downstream of the protective device must not exceed a calculated maximum length: 0.8 U Sph Lmax = 2ρI m Practical method of calculating Lmax The limiting effect of the impedance of long circuit conductors on the value of short-circuit currents must be checked and the length of a circuit must be restricted accordingly. The method of calculating the maximum permitted length has already been demonstrated in TN- and IT- earthed schemes for single and double earth faults, respectively (see Chapter F Sub-clauses 6.2 and 7.2). Two cases are considered below: 1 - Calculation of Lmax for a 3-phase 3-wire circuit The minimum short-circuit current will occur when two phase wires are shortcircuited at the remote end of the circuit (see Fig. G46). P 0.8 U G32 Load L Fig G46 : Definition of L for a 3-phase 3-wire circuit Using the “conventional method”, the voltage at the point of protection P is assumed to be 80% of the nominal voltage during a short-circuit fault, so that 0.8 U = Isc Zd, where: Zd = impedance of the fault loop Isc = short-circuit current (ph/ph) U = phase-to-phase nominal voltage For cables y 120 mm2, reactance may be neglected, so that 2L Zd = ρ (1) Sph where: ρ = resistivity of conductor material at the average temperature during a short-circuit, Sph = c.s.a. of a phase conductor in mm2 L = length in metres The condition for the cable protection is Im y Isc with Im = magnetic trip current setting of the CB. This leads to Im y 0.8 U which gives L y= 0.8 U Sph Zd with U = 400 V ρ = 1.25 x 0.018 = 0.023 Ω.mm2/m(2) (Cu) Lmax = maximum circuit length in metres Lmax = 2ρI m k Sph Im 2 - Calculation of Lmax for a 3-phase 4-wire 230/400 V circuit The minimum Isc will occur when the short-circuit is between a phase conductor and the neutral. A calculation similar to that of example 1 above is required, but using the following formulae (for cable y 120 mm2 (1)). b Where Sn for the neutral conductor = Sph for the phase conductor Lmax = 3,333 Sph Im b If Sn for the neutral conductor < Sph, then © Schneider Electric - all rights reserved Lmax = 6,666 (1) For larger c.s.a.’s, the resistance calculated for the conductors must be increased to account for the non-uniform current density in the conductor (due to “skin” and “proximity” effects) Suitable values are as follows: 150 mm2: R + 15% 185 mm2: R + 20% 240 mm2: R + 25% 300 mm2: R + 30% (2) The high value for resistivity is due to the elevated temperature of the conductor when passing short-circuit current Sph 1 Sph where m = I m 1+ m Sn For larger c.s.a.’s than those listed, reactance values must be combined with those of resistance to give an impedance. Reactance may be taken as 0.08 mΩ/m for cables (at 50 Hz). At 60 Hz the value is 0.096 mΩ/m. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 5 Particular cases of short-circuit current Tabulated values for Lmax Figure G47 below gives maximum circuit lengths (Lmax) in metres, for: b 3-phase 4-wire 400 V circuits (i.e. with neutral) and b 1-phase 2-wire 230 V circuits protected by general-purpose circuit-breakers. In other cases, apply correction factors (given in Figure G53) to the lengths obtained. The calculations are based on the above methods, and a short-circuit trip level within ± 20% of the adjusted value Im. For the 50 mm2 c.s.a., calculation are based on a 47.5 mm2 real c.s.a. Operating current level Im of the instantaneous magnetic tripping element (in A) 50 63 80 100 125 160 200 250 320 400 500 560 630 700 800 875 1000 1120 1250 1600 2000 2500 3200 4000 5000 6300 8000 10000 12500 c.s.a. (nominal cross-sectional-area) of conductors (in mm2) 1.5 100 79 63 50 40 31 25 20 16 13 10 9 8 7 6 6 5 4 4 2.5 167 133 104 83 67 52 42 33 26 21 17 15 13 12 10 10 8 7 7 5 4 4 267 212 167 133 107 83 67 53 42 33 27 24 21 19 17 15 13 12 11 8 7 5 4 6 400 317 250 200 160 125 100 80 63 50 40 36 32 29 25 23 20 18 16 13 10 8 6 5 4 10 417 333 267 208 167 133 104 83 67 60 63 48 42 38 33 30 27 21 17 13 10 8 7 5 4 16 25 35 50 70 95 120 150 185 240 G33 427 333 267 213 167 133 107 95 85 76 67 61 53 48 43 33 27 21 17 13 11 8 7 5 4 417 333 260 208 167 149 132 119 104 95 83 74 67 52 42 33 26 21 17 13 10 8 7 467 365 292 233 208 185 167 146 133 117 104 93 73 58 47 36 29 23 19 15 12 9 495 396 317 283 251 226 198 181 158 141 127 99 79 63 49 40 32 25 20 16 13 417 370 333 292 267 233 208 187 146 117 93 73 58 47 37 29 23 19 452 396 362 317 283 253 198 158 127 99 79 63 50 40 32 25 457 400 357 320 250 200 160 125 100 80 63 50 40 32 435 388 348 272 217 174 136 109 87 69 54 43 35 459 411 321 257 206 161 128 103 82 64 51 41 400 320 256 200 160 128 102 80 64 51 Fig. G47 : Maximum circuit lengths in metres for copper conductors (for aluminium, the lengths must be multiplied by 0.62) Figures G48 to G50 next page give maximum circuit length (Lmax) in metres for: b 3-phase 4-wire 400 V circuits (i.e. with neutral) and b 1-phase 2-wire 230 V circuits protected in both cases by domestic-type circuit-breakers or with circuit-breakers having similar tripping/current characteristics. © Schneider Electric - all rights reserved In other cases, apply correction factors to the lengths indicated. These factors are given in Figure G51 next page. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors Rated current of circuit-breakers (in A) 6 10 16 20 25 32 40 50 63 80 100 125 5 Particular cases of short-circuit current c.s.a. (nominal cross-sectional-area) of conductors (in mm2) 1.5 2.5 4 6 10 16 25 35 200 333 533 800 120 200 320 480 800 75 125 200 300 500 800 60 100 160 240 400 640 48 80 128 192 320 512 800 37 62 100 150 250 400 625 875 30 50 80 120 200 320 500 700 24 40 64 96 160 256 400 560 19 32 51 76 127 203 317 444 15 25 40 60 100 160 250 350 12 20 32 48 80 128 200 280 10 16 26 38 64 102 160 224 50 760 603 475 380 304 Fig. G48 : Maximum length of copper-conductor circuits in metres protected by B-type circuit-breakers G34 Rated current of circuit-breakers (in A) 6 10 16 20 25 32 40 50 63 80 100 125 c.s.a. (nominal cross-sectional-area) of conductors (in mm2) 1.5 2.5 4 6 10 16 25 35 100 167 267 400 667 60 100 160 240 400 640 37 62 100 150 250 400 625 875 30 50 80 120 200 320 500 700 24 40 64 96 160 256 400 560 18.0 31 50 75 125 200 313 438 15.0 25 40 60 100 160 250 350 12.0 20 32 48 80 128 200 280 9.5 16.0 26 38 64 102 159 222 7.5 12.5 20 30 50 80 125 175 6.0 10.0 16.0 24 40 64 100 140 5.0 8.0 13.0 19.0 32 51 80 112 50 760 594 475 380 302 238 190 152 Fig. G49 : Maximum length of copper-conductor circuits in metres protected by C-type circuit-breakers Rated current of circuit-breakers (in A) 1 2 3 4 6 10 16 20 25 32 40 50 63 80 100 125 c.s.a. (nominal cross-sectional-area) of conductors (in mm2) 1.5 2.5 4 6 10 16 25 35 429 714 214 357 571 857 143 238 381 571 952 107 179 286 429 714 71 119 190 286 476 762 43 71 114 171 286 457 714 27 45 71 107 179 286 446 625 21 36 57 86 143 229 357 500 17.0 29 46 69 114 183 286 400 13.0 22 36 54 89 143 223 313 11.0 18.0 29 43 71 114 179 250 9.0 14.0 23 34 57 91 143 200 7.0 11.0 18.0 27 45 73 113 159 5.0 9.0 14.0 21 36 57 89 125 4.0 7.0 11.0 17.0 29 46 71 100 3.0 6.0 9.0 14.0 23 37 57 80 50 848 679 543 424 339 271 215 170 136 109 © Schneider Electric - all rights reserved Fig. G50 : Maximum length of copper-conductor circuits in metres protected by D-type circuit-breakers Circuit detail 3-phase 3-wire 400 V circuit or 1-phase 2-wire 400 V circuit (no neutral) 1-phase 2-wire (phase and neutral) 230 V circuit 3-phase 4-wire 230/400 V circuit or 2-phase 3-wire 230/400 V circuit (i.e with neutral) Sph / S neutral = 1 Sph / S neutral = 2 1.73 1 1 0.67 Fig. G51 : Correction factor to apply to lengths obtained from Figures G47 to G50 Note: IEC 60898 accepts an upper short-circuit-current tripping range of 10-50 In for type D circuit-breakers. European standards, and Figure G50 however, are based on a range of 10-20 In, a range which covers the vast majority of domestic and similar installations. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 5 Particular cases of short-circuit current Examples Example 1 In a 1-phase 2-wire installation the protection is provided by a 50 A circuit-breaker type NSX80HMA, the instantaneous short-circuit current trip, is set at 500 A (accuracy of ± 20%), i.e. in the worst case would require 500 x 1,2 = 600 A to trip. The cable c.s.a. = 10 mm2 and the conductor material is copper. In Figure G47, the row Im = 500 A crosses the column c.s.a. = 10 mm2 at the value for Lmax of 67 m. The circuit-breaker protects the cable against short-circuit faults, therefore, provided that its length does not exceed 67 metres. Example 2 In a 3-phase 3-wire 400 V circuit (without neutral), the protection is provided by a 220 A circuit-breaker type NSX250N with an instantaneous short-circuit current trip unit type MA set at 2,000 A (± 20%), i.e. a worst case of 2,400 A to be certain of tripping. The cable c.s.a. = 120 mm2 and the conductor material is copper. In Figure G47 the row Im = 2,000 A crosses the column c.s.a. = 120 mm2 at the value for Lmax of 200 m. Being a 3-phase 3-wire 400 V circuit (without neutral), a correction factor from Figure G51 must be applied. This factor is seen to be 1.73. The circuit-breaker will therefore protect the cable against short-circuit current, provided that its length does not exceed 200 x 1.73= 346 metres. G35 5.2 Verification of the withstand capabilities of cables under short-circuit conditions In general, verification of the thermal-withstand capability of a cable is not necessary, except in cases where cables of small c.s.a. are installed close to, or feeding directly from, the main general distribution board Thermal constraints When the duration of short-circuit current is brief (several tenths of a second up to five seconds maximum) all of the heat produced is assumed to remain in the conductor, causing its temperature to rise. The heating process is said to be adiabatic, an assumption that simplifies the calculation and gives a pessimistic result, i.e. a higher conductor temperature than that which would actually occur, since in practice, some heat would leave the conductor and pass into the insulation. For a period of 5 seconds or less, the relationship I2t = k2S2 characterizes the time in seconds during which a conductor of c.s.a. S (in mm2) can be allowed to carry a current I, before its temperature reaches a level which would damage the surrounding insulation. The factor k2 is given in Figure G52 below. Insulation PVC XLPE Conductor copper (Cu) 13,225 20,449 Conductor aluminium (Al) 5,776 8,836 Fig. G52 : Value of the constant k2 S (mm2) 1.5 2.5 4 6 10 16 25 35 50 PVC Copper 0.0297 0.0826 0.2116 0.4761 1.3225 3.3856 8.2656 16.2006 29.839 Aluminium 0.0130 0.0361 0.0924 0.2079 0.5776 1.4786 3.6100 7.0756 13.032 XLPE Copper 0.0460 0.1278 0.3272 0.7362 2.0450 5.2350 12.7806 25.0500 46.133 Aluminium 0.0199 0.0552 0.1414 0.3181 0.8836 2.2620 5.5225 10.8241 19.936 Fig. G53 : Maximum allowable thermal stress for cables I2t (expressed in ampere2 x second x 106) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved The method of verification consists in checking that the thermal energy I2t per ohm of conductor material, allowed to pass by the protecting circuit-breaker (from manufacturers catalogues) is less than that permitted for the particular conductor (as given in Figure G53 below). G - Sizing and protection of conductors 5 Particular cases of short-circuit current Example Is a copper-cored XLPE cable of 4 mm2 c.s.a. adequately protected by a C60N circuit-breaker? Figure G53 shows that the I2t value for the cable is 0.3272 x 106, while the maximum “let-through” value by the circuit-breaker, as given in the manufacturer’s catalogue, is considerably less (< 0.1.106 A2s). The cable is therefore adequately protected by the circuit-breaker up to its full rated breaking capability. Electrodynamic constraints For all type of circuit (conductors or bus-trunking), it is necessary to take electrodynamic effects into account. To withstand the electrodynamic constraints, the conductors must be solidly fixed and the connection must be strongly tightened. For bus-trunking, rails, etc. it is also necessary to verify that the electrodynamic withstand performance is satisfactory when carrying short-circuit currents. The peak value of current, limited by the circuit-breaker or fuse, must be less than the busbar system rating. Tables of coordination ensuring adequate protection of their products are generally published by the manufacturers and provide a major advantage of such systems. © Schneider Electric - all rights reserved G36 Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 6 Protective earthing conductor (PE) 6.1 Connection and choice Protective (PE) conductors provide the bonding connection between all exposed and extraneous conductive parts of an installation, to create the main equipotential bonding system. These conductors conduct fault current due to insulation failure (between a phase conductor and an exposed conductive part) to the earthed neutral of the source. PE conductors are connected to the main earthing terminal of the installation. The main earthing terminal is connected to the earthing electrode (see Chapter E) by the earthing conductor (grounding electrode conductor in the USA). PE conductors must be: b Insulated and coloured yellow and green (stripes) b Protected against mechanical and chemical damage In IT and TN-earthed schemes it is strongly recommended that PE conductors should be installed in close proximity (i.e. in the same conduits, on the same cable tray, etc.) as the live cables of the related circuit. This arrangement ensures the minimum possible inductive reactance in the earth-fault current carrying circuits. It should be noted that this arrangement is originally provided by bus-trunking. Connection PE conductors must: b Not include any means of breaking the continuity of the circuit (such as a switch, removable links, etc.) b Connect exposed conductive parts individually to the main PE conductor, i.e. in parallel, not in series, as shown in Figure G54 b Have an individual terminal on common earthing bars in distribution boards. PE G37 TT scheme The PE conductor need not necessarily be installed in close proximity to the live conductors of the corresponding circuit, since high values of earth-fault current are not needed to operate the RCD-type of protection used in TT installations. Correct PE Incorrect Fig. G54 : A poor connection in a series arrangement will leave all downstream appliances unprotected PEN IT and TN schemes The PE or PEN conductor, as previously noted, must be installed as close as possible to the corresponding live conductors of the circuit and no ferro-magnetic material must be interposed between them. A PEN conductor must always be connected directly to the earth terminal of an appliance, with a looped connection from the earth terminal to the neutral terminal of the appliance (see Fig. G55). b TN-C scheme (the neutral and PE conductor are one and the same, referred to as a PEN conductor) The protective function of a PEN conductor has priority, so that all rules governing PE conductors apply strictly to PEN conductors b TN-C to TN-S transition The PE conductor for the installation is connected to the PEN terminal or bar (see Fig. G56) generally at the origin of the installation. Downstream of the point of separation, no PE conductor can be connected to the neutral conductor. PEN PE N Fig. G56 : The TN-C-S scheme © Schneider Electric - all rights reserved Fig. G55 : Direct connection of the PEN conductor to the earth terminal of an appliance Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 6 Protective earthing conductor (PE) Types of materials Materials of the kinds mentioned below in Figure G57 can be used for PE conductors, provided that the conditions mentioned in the last column are satisfied. G38 Type of protective earthing conductor (PE) IT scheme TN scheme TT scheme Conditions to be respected Supplementary In the same cable Strongly Strongly recommended Correct The PE conductor must conductor as the phases, or in recommended be insulated to the same the same cable run level as the phases Independent of the Possible (1) Possible (1) (2) Correct b The PE conductor may phase conductors be bare or insulated (2) b The electrical continuity Metallic housing of bus-trunking or of other Possible (3) PE possible (3) Correct prefabricated prewired ducting (5) PEN possible (8) must be assured by protection against deterioration by External sheath of extruded, mineral- insulated Possible (3) PE possible (3) Possible mechanical, chemical and conductors (e.g. «pyrotenax» type systems) PEN not recommended (2)(3) electrochemical hazards Certain extraneous conductive elements (6) Possible (4) PE possible (4) Possible such as: PEN forbidden b Their conductance b Steel building structures must be adequate b Machine frames b Water pipes (7) Metallic cable ways, such as, conduits (9), Possible (4) PE possible (4) Possible ducts, trunking, trays, ladders, and so on… PEN not recommended (2)(4) Forbidden for use as PE conductors, are: metal conduits (9), gas pipes, hot-water pipes, cable-armouring tapes (9) or wires (9) (1) In TN and IT schemes, fault clearance is generally achieved by overcurrent devices (fuses or circuit-breakers) so that the impedance of the fault-current loop must be sufficiently low to assure positive protective device operation. The surest means of achieving a low loop impedance is to use a supplementary core in the same cable as the circuit conductors (or taking the same route as the circuit conductors). This solution minimizes the inductive reactance and therefore the impedance of the loop. (2) The PEN conductor is a neutral conductor that is also used as a protective earth conductor. This means that a current may be flowing through it at any time (in the absence of an earth fault). For this reason an insulated conductor is recommended for PEN operation. (3) The manufacturer provides the necessary values of R and X components of the impedances (phase/PE, phase/PEN) to include in the calculation of the earth-fault loop impedance. (4) Possible, but not recomended, since the impedance of the earth-fault loop cannot be known at the design stage. Measurements on the completed installation are the only practical means of assuring adequate protection for persons. (5) It must allow the connection of other PE conductors. Note: these elements must carry an indivual green/yellow striped visual indication, 15 to 100 mm long (or the letters PE at less than 15 cm from each extremity). (6) These elements must be demountable only if other means have been provided to ensure uninterrupted continuity of protection. (7) With the agreement of the appropriate water authorities. (8) In the prefabricated pre-wired trunking and similar elements, the metallic housing may be used as a PEN conductor, in parallel with the corresponding bar, or other PE conductor in the housing. (9) Forbidden in some countries only. Universally allowed to be used for supplementary equipotential conductors. Fig. G57 : Choice of protective conductors (PE) 6.2 Conductor sizing Figure G58 below is based on IEC 60364-5-54. This table provides two methods of determining the appropriate c.s.a. for both PE or PEN conductors. © Schneider Electric - all rights reserved Simplified method (1) Adiabatic method c.s.a. of phase conductors Sph (mm2) Minimum c.s.a. of PE conductor (mm2) Sph y 16 16 < Sph y 25 25 < Sph y 35 35 < Sph y 50 Sph > 50 Sph (2) 16 Any size Sph /2 SPE/PEN = I2 ⋅ t Minimum c.s.a. of PEN conductor (mm2) Cu Al Sph (3) Sph (3) 16 25 Sph /2 Sph /2 (3)(4) (4) (3) k (1) Data valid if the prospective conductor is of the same material as the line conductor. Otherwise, a correction factor must be applied. (2) When the PE conductor is separated from the circuit phase conductors, the following minimum values must be respected: b 2.5 mm2 if the PE is mechanically protected b 4 mm2 if the PE is not mechanically protected (3) For mechanical reasons, a PEN conductor, shall have a cross-sectional area not less than 10 mm2 in copper or 16 mm2 in aluminium. (4) Refer to table G53 for the application of this formula. Fig. G58 : Minimum cross section area of protective conductors Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 6 Protective earthing conductor (PE) The two methods are: b Adiabatic (which corresponds with that described in IEC 60724) This method, while being economical and assuring protection of the conductor against overheating, leads to small c.s.a.’s compared to those of the corresponding circuit phase conductors. The result is sometimes incompatible with the necessity in IT and TN schemes to minimize the impedance of the circuit earth-fault loop, to ensure positive operation by instantaneous overcurrent tripping devices. This method is used in practice, therefore, for TT installations, and for dimensioning an earthing conductor (1). b Simplified This method is based on PE conductor sizes being related to those of the corresponding circuit phase conductors, assuming that the same conductor material is used in each case. Thus, in Figure G58 for: Sph y 16 mm2 SPE = Sph 16 < Sph y 35 mm2 SPE = 16 mm2 Sph Sph Sph>>35 35 mm mm22 SPE = 2 : when, in a TT scheme, the installation earth electrode is beyond the zone of Note: when, in a TT scheme, the installation earth electrode is beyond the zone of influence of the source earthing electrode, the c.s.a. of the PE conductor can be limited to 25 mm2 (for copper) or 35 mm2 (for aluminium). G39 The neutral cannot be used as a PEN conductor unless its c.s.a. is equal to or larger than 10 mm2 (copper) or 16 mm2 (aluminium). Moreover, a PEN conductor is not allowed in a flexible cable. Since a PEN conductor functions also as a neutral conductor, its c.s.a. cannot, in any case, be less than that necessary for the neutral, as discussed in Subclause 7.1 of this Chapter. This c.s.a. cannot be less than that of the phase conductors unless: b The kVA rating of single-phase loads is less than 10% of the total kVA load, and b Imax likely to pass through the neutral in normal circumstances, is less than the current permitted for the selected cable size. Furthermore, protection of the neutral conductor must be assured by the protective devices provided for phase-conductor protection (described in Sub-clause 7.2 of this Chapter). k values Final temperature (°C) Initial temperature (°C) Insulated conductors not incoporated in cables or bare conductors in contact with cable jackets Conductors of a multi-core-cable Nature of insulation Polyvinylchloride (PVC) Copper Aluminium Steel 160 30 143 95 52 Cross-linked-polyethylene (XLPE) Ethylene-propylene-rubber (EPR) 250 30 176 116 64 Copper Aluminium 115 76 143 94 Fig. G59 : k factor values for LV PE conductors, commonly used in national standards and complying with IEC 60724 (1) Grounding electrode conductor Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Values of factor k to be used in the formulae These values are identical in several national standards, and the temperature rise ranges, together with factor k values and the upper temperature limits for the different classes of insulation, correspond with those published in IEC 60724 (1984). The data presented in Figure G59 are those most commonly needed for LV installation design. G - Sizing and protection of conductors 6 Protective earthing conductor (PE) 6.3 Protective conductor between MV/LV transformer and the main general distribution board (MGDB) These conductors must be sized according to national practices All phase and neutral conductors upstream of the main incoming circuit-breaker controlling and protecting the MGDB are protected by devices at the MV side of the transformer. The conductors in question, together with the PE conductor, must be dimensioned accordingly. Dimensioning of the phase and neutral conductors from the transformer is exemplified in Sub-clause 7.5 of this chapter (for circuit C1 of the system illustrated in Fig. G65). Recommended conductor sizes for bare and insulated PE conductors from the transformer neutral point, shown in Figure G60, are indicated below in Figure G61. The kVA rating to consider is the sum of all (if more than one) transformers connected to the MGDB. G40 PE MGDB Main earth bar for the LV installation Fig. G60 : PE conductor to the main earth bar in the MGDB The table indicates the c.s.a. of the conductors in mm2 according to: b The nominal rating of the MV/LV transformer(s) in kVA b The fault-current clearance time by the MV protective devices, in seconds b The kinds of insulation and conductor materials If the MV protection is by fuses, then use the 0.2 seconds columns. In IT schemes, if an overvoltage protection device is installed (between the transformer neutral point and earth) the conductors for connection of the device should also be dimensioned in the same way as that described above for PE conductors. Transformer Conductor rating in kVA material (230/400 V Copper t(s) output) Aluminium t(s) Bare conductors 0.2 0.5 0.2 y100 25 25 25 25 35 50 50 70 70 95 95 © Schneider Electric - all rights reserved 160 200 250 315 400 500 630 800 1,000 1,250 c.s.a. of PE conductors SPE (mm2) 25 25 35 35 50 70 70 95 120 120 150 0.5 PVC-insulated conductors 0.2 0.5 0.2 0.5 XLPE-insulated conductors 0.2 0.5 0.2 0.5 25 35 50 70 70 95 120 150 150 185 185 25 25 25 35 35 50 70 70 95 95 120 25 25 25 25 35 35 50 70 70 70 95 25 25 35 50 50 70 95 95 120 120 150 25 50 50 70 95 95 120 150 185 185 240 25 25 25 35 50 50 70 95 95 120 120 25 35 50 50 70 95 95 120 150 150 185 Fig. G61 : Recommended c.s.a. of PE conductor between the MV/LV transformer and the MGDB, as a function of transformer ratings and fault-clearance times. Schneider Electric - Electrical installation guide 2009 6 Protective earthing conductor (PE) 6.4 Equipotential conductor The main equipotential conductor This conductor must, in general, have a c.s.a. at least equal to half of that of the largest PE conductor, but in no case need exceed 25 mm2 (copper) or 35 mm2 (aluminium) while its minimum c.s.a. is 6 mm2 (copper) or 10 mm2 (aluminium). Supplementary equipotential conductor This conductor allows an exposed conductive part which is remote from the nearest main equipotential conductor (PE conductor) to be connected to a local protective conductor. Its c.s.a. must be at least half of that of the protective conductor to which it is connected. If it connects two exposed conductive parts (M1 and M2 in Figure G62) its c.s.a. must be at least equal to that of the smaller of the two PE conductors (for M1 and M2). Equipotential conductors which are not incorporated in a cable, should be protected mechanically by conduits, ducting, etc. wherever possible. Other important uses for supplementary equipotential conductors concern the reduction of the earth-fault loop impedance, particulary for indirect-contact protection schemes in TN- or IT-earthed installations, and in special locations with increased electrical risk (refer to IEC 60364-4-41). Between two exposed conductive parts if SPE1 y SPE2 then S LS = SPE1 Between an exposed conductive part and a metallic structure SPE SLS = 2 SPE2 SPE1 SPE1 SLS M1 G41 SLS M2 Metal structures (conduits, girders…) M1 Fig. G62 : Supplementary equipotential conductors © Schneider Electric - all rights reserved G - Sizing and protection of conductors Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 7 The neutral conductor The c.s.a. and the protection of the neutral conductor, apart from its current-carrying requirement, depend on several factors, namely: b The type of earthing system, TT, TN, etc. b The harmonic currents b The method of protection against indirect contact hazards according to the methods described below The color of the neutral conductor is statutorily blue. PEN conductor, when insulated, shall be marked by one of the following methods : b Green-and-yellow throughout its length with, in addition, light blue markings at the terminations, or b Light blue throughout its length with, in addition, green-and-yellow markings at the terminations 7.1 Sizing the neutral conductor Influence of the type of earthing system TT and TN-S schemes b Single-phase circuits or those of c.s.a. y 16 mm2 (copper) 25 mm2 (aluminium): the c.s.a. of the neutral conductor must be equal to that of the phases b Three-phase circuits of c.s.a. > 16 mm2 copper or 25 mm2 aluminium: the c.s.a. of the neutral may be chosen to be: v Equal to that of the phase conductors, or v Smaller, on condition that: - The current likely to flow through the neutral in normal conditions is less than the permitted value Iz. The influence of triplen(1) harmonics must be given particular consideration or - The neutral conductor is protected against short-circuit, in accordance with the following Sub-clause G-7.2 - The size of the neutral conductor is at least equal to 16 mm2 in copper or 25 mm2 in aluminium G42 TN-C scheme The same conditions apply in theory as those mentioned above, but in practice, the neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor (see Figure G58 “c.s.a. of PEN conductor” column). IT scheme In general, it is not recommended to distribute the neutral conductor, i.e. a 3-phase 3-wire scheme is preferred. When a 3-phase 4-wire installation is necessary, however, the conditions described above for TT and TN-S schemes are applicable. Influence of harmonic currents Effects of triplen harmonics Harmonics are generated by the non-linear loads of the installation (computers, fluorescent lighting, rectifiers, power electronic choppers) and can produce high currents in the Neutral. In particular triplen harmonics of the three Phases have a tendency to cumulate in the Neutral as: b Fundamental currents are out-of-phase by 2π/3 so that their sum is zero b On the other hand, triplen harmonics of the three Phases are always positioned in the same manner with respect to their own fundamental, and are in phase with each other (see Fig. G63a). © Schneider Electric - all rights reserved (1) Harmonics of order 3 and multiple of 3 I1 H1 + I1 H3 I2 H1 + I2 H3 I3 H1 + I3 H3 3 3 IN = Ik H1 + Ik H3 1 1 0 + 3 IH3 Fig. G63a : Triplen harmonics are in phase and cumulate in the Neutral Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 7 The neutral conductor Figure G63b shows the load factor of the neutral conductor as a function of the percentage of 3rd harmonic. In practice, this maximum load factor cannot exceed 3. INeutral IPhase 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 0.2 0 i 3 (%) 0 20 40 60 80 G43 100 Fig. G63b : Load factor of the neutral conductor vs the percentage of 3rd harmonic Reduction factors for harmonic currents in four-core and five-core cables with four cores carrying current The basic calculation of a cable concerns only cables with three loaded conductors i.e there is no current in the neutral conductor. Because of the third harmonic current, there is a current in the neutral. As a result, this neutral current creates an hot environment for the 3 phase conductors and for this reason, a reduction factor for phase conductors is necessary (see Fig. G63). Reduction factors, applied to the current-carrying capacity of a cable with three loaded conductors, give the current-carrying capacity of a cable with four loaded conductors, where the current in the fourth conductor is due to harmonics. The reduction factors also take the heating effect of the harmonic current in the phase conductors into account. b Where the neutral current is expected to be higher than the phase current, then the cable size should be selected on the basis of the neutral current b Where the cable size selection is based on a neutral current which is not significantly higher than the phase current, it is necessary to reduce the tabulated current carrying capacity for three loaded conductors b If the neutral current is more than 135% of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction factor to the current carrying capacity for three loaded conductors. b In order to protect cables, the fuse or circuit-breaker has to be sized taking into account the greatest of the values of the line currents (phase or neutral). However, there are special devices (for example the Compact NSX circuit breaker equipped with the OSN tripping unit), that allow the use of a c.s.a. of the phase conductors smaller than the c.s.a. of the neutral conductor. A big economic gain can thus be made. Third harmonic content of phase current (%) 0 - 15 15 - 33 33 - 45 > 45 Reduction factor Size selection is based on phase current 1.0 0.86 - Size selection is based on neutral current 0.86 1.0 Fig. G63 : Reduction factors for harmonic currents in four-core and five-core cables (according to IEC 60364-5-52) Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Compact NSX100 circuit breaker G - Sizing and protection of conductors 7 The neutral conductor Examples Consider a three-phase circuit with a design load of 37 A to be installed using fourcore PVC insulated cable clipped to a wall, installation method C. From Figure G24, a 6 mm2 cable with copper conductors has a current-carrying capacity of 40 A and hence is suitable if harmonics are not present in the circuit. b If 20 % third harmonic is present, then a reduction factor of 0,86 is applied and the design load becomes: 37/0.86 = 43 A. For this load a 10 mm2 cable is necessary. In this case, the use of a special protective device (Compact NSX equipped with the OSN trip unit for instance) would allow the use of a 6 mm2 cable for the phases and of 10 mm2 for the neutral. b If 40 % third harmonic is present, the cable size selection is based on the neutral current which is: 37 x 0,4 x 3 = 44,4 A and a reduction factor of 0,86 is applied, leading to a design load of: 44.4/0.86 = 51.6 A. For this load a 10 mm2 cable is suitable. G44 b If 50 % third harmonic is present, the cable size is again selected on the basis of the neutral current, which is: 37 x 0,5 x 3 = 55,5 A .In this case the rating factor is 1 and a 16 mm2 cable is required. In this case, the use of a special protective device (Compact NSX equipped with the OSN trip for instance) would allow the use of a 6 mm2 cable for the phases and of 10 mm2 for the neutral. 7.2 Protection of the neutral conductor (see Fig. G64 next page) Protection against overload If the neutral conductor is correctly sized (including harmonics), no specific protection of the neutral conductor is required because it is protected by the phase protection. However, in practice, if the c.s.a. of the neutral conductor is lower than the phase c.s.a, a neutral overload protection must be installed. Protection against short-circuit If the c.s.a. of the neutral conductor is lower than the c.s.a. of the phase conductor, the neutral conductor must be protected against short-circuit. If the c.s.a. of the neutral conductor is equal or greater than the c.s.a. of the phase conductor, no specific protection of the neutral conductor is required because it is protected by the phase protection. 7.3 Breaking of the neutral conductor (see Fig. G64 next page) The need to break or not the neutral conductor is related to the protection against indirect contact. In TN-C scheme The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor. © Schneider Electric - all rights reserved In TT, TN-S and IT schemes In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar. The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch. 7.4 Isolation of the neutral conductor (see Fig. G64 next page) It is considered to be the good practice that every circuit be provided with the means for its isolation. Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 7 The neutral conductor TT TN-C TN-S IT Single-phase (Phase-Neutral) N N N or N (B) or N N Single-phase (Phase-Phase) (A) (A) or or Three-phase four wires Sn u Sph G45 N N N (B) N or N Three-phase four wires Sn < Sph N N (B) N or N (A) Authorized for TT or TN-S systems if a RCD is installed at the origin of the circuit or upstream of it, and if no artificial neutral is distributed downstream of its location (B) The neutral overcurrent protection is not necessary: b If the neutral conductor is protected against short-circuits by a device placed upstream, or, b If the circuit is protected by a RCD which sensitivity is less than 15% of the neutral admissible current. © Schneider Electric - all rights reserved Fig. G64 : The various situations in which the neutral conductor may appear Schneider Electric - Electrical installation guide 2009 G - Sizing and protection of conductors 8 Worked example of cable calculation Worked example of cable calculation (see Fig. G65) The installation is supplied through a 1,000 kVA transformer. The process requires a high degree of supply continuity and this is provided by the installation of a 500 kVA 400 V standby generator and the adoption of a 3-phase 3-wire IT system at the main general distribution board. The remainder of the installation is isolated by a 400 kVA 400/400 V transformer. The downstream network is a TT-earthed 3-phase 4-wire system. Following the single-line diagram shown in Figure G65 below, a reproduction of the results of a computer study for the circuit C1, the circuit-breaker Q1, the circuit C6 and the circuit-breaker Q6. These studies were carried out with ECODIAL 3.3 software (a Merlin Gerin product). This is followed by the same calculations carried out by the method described in this guide. T1 1000 kVA 400 V 50 Hz G46 Circuit 1 C1 G5 G P = 500 kVA U = 400 V Q1 Switchboard 2 Ks = 1.00 ib = 826.8 A B2 Q6 Circuit 5 C5 Q5 Q3 Switchboard 4 Ks = 1.00 ib = 250.0 A B4 Q12 Circuit 6 C6 T6 P = 400 kVA U = 400 V Circuit 12 C12 Q7 L12 ku = 1.0 ib = 250.00 A P = 147.22 kW C7 Circuit 7 x1 Switchboard 8 Ks = 1.00 ib = 490.0 A B8 Q9 Q10 Circuit 9 © Schneider Electric - all rights reserved C9 Q11 Circuit 10 C10 L9 L10 L11 ku = 1.0 ib = 250.00 A P = 147.22 kW x1 Circuit 11 C11 ku = 1.0 ib = 160.00 A P = 94.22 kW x1 Fig. G65 : Example of single-line diagram Schneider Electric - Electrical installation guide 2009 ku = 1.0 ib = 80.00 A P = 47.11 kW x1 G - Sizing and protection of conductors 8 Worked example of cable calculation Calculation using software Ecodial 3.3 General network characteristics Earthing system Neutral distributed Voltage (V) Frequency (Hz) Transformer T1 Number of transformers Upstream fault level (MVA) Rating (kVA) Short-circuit impedance voltage (%) Busbars B2 Maximum load current (A) Type IT No 400 50 Ambient temperature (°C) Dimensions (m and mm) 1 500 1,000 6 Resistance of MV network (mΩ) Reactance of MV network (mΩ) 0.0351 Transformer resistance RT (mΩ) 0.351 3-phase short-circuit current Ik3 (kA) Cable C1 Maximum load current (A) Type of insulation Conductor material Ambient temperature (°C) Single-core or multi-core cable Installation method Number of circuits in close proximity (table G21b) Other coefficient Selected cross-sectional area (mm2) Protective conductor Length (m) 10.333 Transformer reactance XT (mΩ) Voltage drop ΔU (%) Voltage drop ΔU total (%) 2.293 23.3 1,374 PVC Copper 30 Single F 1 1 6 x 95 1 x 120 5 .122 3-phase short-circuit current Ik3 (kA) .122 1-phase-to-earth fault current Id (kA) Circuit-breaker Q1 17 3-ph short-circuit current Ik3 upstream of the circuit-breaker (kA) Maximum load current (A) Number of poles and protected poles Circuit-breaker Type Tripping unit type Rated current (A) 23 23 1,374 3P3D NT 16 H 1 – 42 kA Micrologic 5 A 1,600 3-ph short-circuit current Ik3 (kA) Material 3-ph peak value of short-circuit current Ik (kA) Resistance of busbar R (mΩ) Reactance of busbar X (mΩ) Circuit-breaker Q6 3-ph short-circuit current upstream of the circuit-breaker Ik3 (kA) Maximum load current (A) Number of poles and protected poles Circuit-breaker Type Tripping unit type Rated current (A) Limit of discrimination (kA) Cable C6 Maximum load current (A) Type of insulation Conductor material Ambient temperature (°C) Single-core or multi-core cable Installation method Number of circuits in close proximity (table G20) Other coefficient Selected cross-sectional area (mm2) Protective conductor Length (m) Voltage drop ΔU (%) Voltage drop ΔU total (%) 3-phase short-circuit current Ik3 (kA) 1-phase-to-earth fault current Id (kA) Specific sizing constraint 1,374 Standard on edge 30 1m 2x5 mm x 63 mm Copper 23 48 2.52 10.8 23 560 3P3D NS800 N – 50 kA Micrologic 2.0 800 Total G47 560 PVC Copper 30 Single F 1 1 1 x 300 1 x 150 15 .38 .54 20 13.7 Overloads Fig. G66 : Partial results of calculation carried out with Ecodial software (Merlin Gerin) The same calculation using the simplified method recommended in this guide Six single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F. The “k” correction factors are as follows: k1 = 1 (see table G12, temperature = 30 °C) k4 = 0.87 (see table G17, touching cables, 1 tray, u 3 circuits) Other correction factors are not relevant in this example. The corrected load current is: IB 1,374 I' B = = = 1,579 A k1⋅ k4 0.87 Each conductor will therefore carry 263 A. Figure G21a indicates that the c.s.a. is 95 mm2. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Dimensioning circuit C1 The MV/LV 1,000 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of 1,000 x 103 IB = = 1,374 A per phase 3 x 420 G - Sizing and protection of conductors 8 Worked example of cable calculation The resistances and the inductive reactances for the six conductors in parallel are, for a length of 5 metres: R= 22.5 x 5 = 0.20 mΩ (cab (cable resistance: 22.5 mΩ.mm2/m) 95 x 6 X = 0.08 x 5 = 0.40 mΩ (cable reactance: 0.08 mΩ/m) Ω Dimensioning circuit C6 Circuit C6 supplies a 400 kVA 3-phase 400/400 V isolating transformer Primary current = 400.103 = 550 A 420. 3 A single-core cable laid on a cable tray (without any other cable) in an ambient air temperature of 30 °C is proposed. The circuit-breaker is set at 560 A The method of installation is characterized by the reference letter F, and the “k” correcting factors are all equal to 1. A c.s.a. of 240 mm2 is appropriate. The resistance and inductive reactance are respectively: 22.5 x 15 = 1.4 mΩ 240 X = 0.08 x 15 = 1.2 mΩ R= G48 Calculation of short-circuit currents for the selection of circuit-breakers Q 1 and Q 6 (see Fig. G67) Circuits components parts 500 MVA at the MV source network 1 MVA transformer Cable C1 Sub-total for Q1 Busbar B2 Cable C6 Sub-total for Q6 R (mΩ) X (mΩ) 0.04 0.36 2.2 0.20 2.44 3.6 1.4 4.0 9.8 0.4 10.6 7.2 1.2 8.4 Z (mΩ) Ikmax (kA) 10.0 23 10.9 23 9.3 20 Fig. G67 : Example of short-circuit current evaluation The protective conductor Thermal requirements: Figures G58 and G59 show that, when using the adiabatic method the c.s.a. for the protective earth (PE) conductor for circuit C1 will be: 34,800 x 0.2 = 108 mm2 143 A single 120 mm2 conductor dimensioned for other reasons mentioned later is therefore largely sufficient, provided that it also satisfies the requirements for indirectcontact protection (i.e. that its impedance is sufficiently low). © Schneider Electric - all rights reserved For the circuit C6, the c.s.a. of its PE conductor should be: 29,300 x 0.2 = 92 mm2 143 In this case a 95 mm2 conductor may be adequate if the indirect-contact protection conditions are also satisfied. Schneider Electric - Electrical installation guide 2009 8 Worked example of cable calculation Protection against indirect-contact hazards For circuit C6 of Figure G65, Figures F45 and F61, or the formula given page F27 may be used for a 3-phase 3-wire circuit. The maximum permitted length of the circuit is given by : Lmax = 0.8 x 240 x 230 3 x 1,000 = 70 m  240  x 630 x 11 2 x 22.5 1+  95  (The value in the denominator 630 x 11 = Im i.e. the current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker operates). The length of 15 metres is therefore fully protected by “instantaneous” overcurrent devices. Voltage drop From Figure G28 it can be seen that: b For the cable C1 (6 x 95mm2 per phase) 0.42 (V A-1 km-1) x 1,374 (A) x 0.008 ∆U = = 1.54 V 3 100 x 1.54 = 0.38% ∆U% = 400 G49 b For the circuit C6 0.21 (V A-1 km-1) x 433 (A) x 0.015 ∆U = = 1.36 V 3 100 ∆U% = x 1.36 = 0.34% 400 ΔU% = 0.72% At the circuit terminals of the LV/LV transformer the percentage volt-drop © Schneider Electric - all rights reserved G - Sizing and protection of conductors Schneider Electric - Electrical installation guide 2009 Chapter H LV switchgear: functions & selection Contents 1 The basic functions of LV switchgear H2 1.1 Electrical protection 1.2 Isolation 1.3 Switchgear control H2 H3 H4 2 The switchgear H5 2.1 Elementary switching devices 2.2 Combined switchgear elements H5 H9 3 Choice of switchgear H10 3.1 Tabulated functional capabilities 3.2 Switchgear selection H10 H10 4 Circuit-breaker H11 4.1 4.2 4.3 4.4 4.5 4.6 H11 H13 H15 H18 H1 H22 H28 © Schneider Electric - all rights reserved Standards and description Fundamental characteristics of a circuit-breaker Other characteristics of a circuit-breaker Selection of a circuit-breaker Coordination between circuit-breakers Discrimination MV/LV in a consumer’s substation Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 1 The basic functions of LV switchgear National and international standards define the manner in which electric circuits of LV installations must be realized, and the capabilities and limitations of the various switching devices which are collectively referred to as switchgear. The role of switchgear is: b Electrical protection b Safe isolation from live parts b Local or remote switching The main functions of switchgear are: b Electrical protection b Electrical isolation of sections of an installation b Local or remote switching These functions are summarized below in Figure H1. Electrical protection at low voltage is (apart from fuses) normally incorporated in circuit-breakers, in the form of thermal-magnetic devices and/or residual-currentoperated tripping devices (less-commonly, residual voltage- operated devices - acceptable to, but not recommended by IEC). In addition to those functions shown in Figure H1, other functions, namely: b Over-voltage protection b Under-voltage protection are provided by specific devices (lightning and various other types of voltage-surge arrester, relays associated with contactors, remotely controlled circuit-breakers, and with combined circuit-breaker/isolators… and so on) Electrical protection against b Overload currents b Short-circuit currents b Insulation failure H2 Isolation Control b Isolation clearly indicated by an authorized fail-proof mechanical indicator b A gap or interposed insulating barrier between the open contacts, clearly visible b Functional switching b Emergency switching b Emergency stopping b Switching off for mechanical maintenance Fig. H1 : Basic functions of LV switchgear 1.1 Electrical protection © Schneider Electric - all rights reserved Electrical protection assures: b Protection of circuit elements against the thermal and mechanical stresses of short-circuit currents b Protection of persons in the event of insulation failure b Protection of appliances and apparatus being supplied (e.g. motors, etc.) The aim is to avoid or to limit the destructive or dangerous consequences of excessive (short-circuit) currents, or those due to overloading and insulation failure, and to separate the defective circuit from the rest of the installation. A distinction is made between the protection of: b The elements of the installation (cables, wires, switchgear…) b Persons and animals b Equipment and appliances supplied from the installation The protection of circuits v Against overload; a condition of excessive current being drawn from a healthy (unfaulted) installation v Against short-circuit currents due to complete failure of insulation between conductors of different phases or (in TN systems) between a phase and neutral (or PE) conductor Protection in these cases is provided either by fuses or circuit-breaker, in the distribution board at the origin of the final circuit (i.e. the circuit to which the load is connected). Certain derogations to this rule are authorized in some national standards, as noted in chapter H1 sub-clause 1.4. The protection of persons v Against insulation failures. According to the system of earthing for the installation (TN, TT or IT) the protection will be provided by fuses or circuit-breakers, residual current devices, and/or permanent monitoring of the insulation resistance of the installation to earth The protection of electric motors v Against overheating, due, for example, to long term overloading, stalled rotor, single-phasing, etc. Thermal relays, specially designed to match the particular characteristics of motors are used. Such relays may, if required, also protect the motor-circuit cable against overload. Short-circuit protection is provided either by type aM fuses or by a circuit-breaker from which the thermal (overload) protective element has been removed, or otherwise made inoperative. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 1 The basic functions of LV switchgear A state of isolation clearly indicated by an approved “fail-proof” indicator, or the visible separation of contacts, are both deemed to satisfy the national standards of many countries 1.2 Isolation The aim of isolation is to separate a circuit or apparatus (such as a motor, etc.) from the remainder of a system which is energized, in order that personnel may carry out work on the isolated part in perfect safety. In principle, all circuits of an LV installation shall have means to be isolated. In practice, in order to maintain an optimum continuity of service, it is preferred to provide a means of isolation at the origin of each circuit. An isolating device must fulfil the following requirements: b All poles of a circuit, including the neutral (except where the neutral is a PEN conductor) must open(1) b It must be provided with a locking system in open position with a key (e.g. by means of a padlock) in order to avoid an unauthorized reclosure by inadvertence b It must comply with a recognized national or international standard (e.g. IEC 60947-3) concerning clearance between contacts, creepage distances, overvoltage withstand capability, etc.: Other requirements apply: v Verification that the contacts of the isolating device are, in fact, open. The verification may be: - Either visual, where the device is suitably designed to allow the contacts to be seen (some national standards impose this condition for an isolating device located at the origin of a LV installation supplied directly from a MV/LV transformer) - Or mechanical, by means of an indicator solidly welded to the operating shaft of the device. In this case the construction of the device must be such that, in the eventuality that the contacts become welded together in the closed position, the indicator cannot possibly indicate that it is in the open position v Leakage currents. With the isolating device open, leakage currents between the open contacts of each phase must not exceed: - 0.5 mA for a new device - 6.0 mA at the end of its useful life v Voltage-surge withstand capability, across open contacts. The isolating device, when open must withstand a 1.2/50 μs impulse, having a peak value of 6, 8 or 12 kV according to its service voltage, as shown in Figure H2. The device must satisfy these conditions for altitudes up to 2,000 metres. Correction factors are given in IEC 60664-1 for altitudes greater than 2,000 metres. H3 Consequently, if tests are carried out at sea level, the test values must be increased by 23% to take into account the effect of altitude. See standard IEC 60947. Service (nominal voltage (V) 230/400 400/690 690/1,000 Impulse withstand peak voltage category (for 2,000 metres) (kV) III IV 4 6 6 8 8 12 (1) the concurrent opening of all live conductors, while not always obligatory, is however, strongly recommended (for reasons of greater safety and facility of operation). The neutral contact opens after the phase contacts, and closes before them (IEC 60947-1). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. H2 : Peak value of impulse voltage according to normal service voltage of test specimen. The degrees III and IV are degrees of pollution defined in IEC 60664-1 H - LV switchgear: functions & selection 1 The basic functions of LV switchgear Switchgear-control functions allow system operating personnel to modify a loaded system at any moment, according to requirements, and include: b Functional control (routine switching, etc.) b Emergency switching b Maintenance operations on the power system 1.3 Switchgear control In broad terms “control” signifies any facility for safely modifying a load-carrying power system at all levels of an installation. The operation of switchgear is an important part of power-system control. Functional control This control relates to all switching operations in normal service conditions for energizing or de-energizing a part of a system or installation, or an individual piece of equipment, item of plant, etc. Switchgear intended for such duty must be installed at least: b At the origin of any installation b At the final load circuit or circuits (one switch may control several loads) Marking (of the circuits being controlled) must be clear and unambiguous. In order to provide the maximum flexibility and continuity of operation, particularly where the switching device also constitutes the protection (e.g. a circuit-breaker or switch-fuse) it is preferable to include a switch at each level of distribution, i.e. on each outgoing way of all distribution and subdistribution boards. The manœuvre may be: b Either manual (by means of an operating lever on the switch) or b Electric, by push-button on the switch or at a remote location (load-shedding and reconnection, for example) These switches operate instantaneously (i.e. with no deliberate delay), and those that provide protection are invariably omni-polar(1). H4 The main circuit-breaker for the entire installation, as well as any circuit-breakers used for change-over (from one source to another) must be omni-polar units. Emergency switching - emergency stop An emergency switching is intended to de-energize a live circuit which is, or could become, dangerous (electric shock or fire). An emergency stop is intended to halt a movement which has become dangerous. In the two cases: b The emergency control device or its means of operation (local or at remote location(s)) such as a large red mushroom-headed emergency-stop pushbutton must be recognizable and readily accessible, in proximity to any position at which danger could arise or be seen b A single action must result in a complete switching-off of all live conductors (2) (3) b A “break glass” emergency switching initiation device is authorized, but in unmanned installations the re-energizing of the circuit can only be achieved by means of a key held by an authorized person It should be noted that in certain cases, an emergency system of braking, may require that the auxiliary supply to the braking-system circuits be maintained until final stoppage of the machinery. Switching-off for mechanical maintenance work © Schneider Electric - all rights reserved This operation assures the stopping of a machine and its impossibility to be inadvertently restarted while mechanical maintenance work is being carried out on the driven machinery. The shutdown is generally carried out at the functional switching device, with the use of a suitable safety lock and warning notice at the switch mechanism. (1) One break in each phase and (where appropriate) one break in the neutral. (2) Taking into account stalled motors. (3) In a TN schema the PEN conductor must never be opened, since it functions as a protective earthing wire as well as the system neutral conductor. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 2 The switchgear 2.1 Elementary switching devices Disconnector (or isolator) (see Fig. H5) This switch is a manually-operated, lockable, two-position device (open/closed) which provides safe isolation of a circuit when locked in the open position. Its characteristics are defined in IEC 60947-3. A disconnector is not designed to make or to break current(1) and no rated values for these functions are given in standards. It must, however, be capable of withstanding the passage of short-circuit currents and is assigned a rated short-time withstand capability, generally for 1 second, unless otherwise agreed between user and manufacturer. This capability is normally more than adequate for longer periods of (lower-valued) operational overcurrents, such as those of motor-starting. Standardized mechanical-endurance, overvoltage, and leakage-current tests, must also be satisfied. Load-breaking switch (see Fig. H6) This control switch is generally operated manually (but is sometimes provided with electrical tripping for operator convenience) and is a non-automatic two-position device (open/closed). It is used to close and open loaded circuits under normal unfaulted circuit conditions. It does not consequently, provide any protection for the circuit it controls. IEC standard 60947-3 defines: b The frequency of switch operation (600 close/open cycles per hour maximum) b Mechanical and electrical endurance (generally less than that of a contactor) b Current making and breaking ratings for normal and infrequent situations When closing a switch to energize a circuit there is always the possibility that an unsuspected short-circuit exists on the circuit. For this reason, load-break switches are assigned a fault-current making rating, i.e. successful closure against the electrodynamic forces of short-circuit current is assured. Such switches are commonly referred to as “fault-make load-break” switches. Upstream protective devices are relied upon to clear the short-circuit fault H5 Category AC-23 includes occasional switching of individual motors. The switching of capacitors or of tungsten filament lamps shall be subject to agreement between manufacturer and user. Fig. H5 : Symbol for a disconnector (or isolator) The utilization categories referred to in Figure H7 do not apply to an equipment normally used to start, accelerate and/or stop individual motors. Example A 100 A load-break switch of category AC-23 (inductive load) must be able: b To make a current of 10 In (= 1,000 A) at a power factor of 0.35 lagging b To break a current of 8 In (= 800 A) at a power factor of 0.45 lagging b To withstand short duration short-circuit currents when closed Fig. H6 : Symbol for a load-break switch AC-21A AC-21B AC-22A AC-22B AC-23A AC-23B Typical applications Cos ϕ Making current x In Breaking current x In Connecting and disconnecting under no-load conditions Switching of resistive loads including moderate overloads Switching of mixed resistive and inductive loads, including moderate overloads - - - 0.95 1.5 1.5 0.65 3 3 Switching of motor loads or other highly inductive loads 0.45 for I y 100 A 10 0.35 for I > 100 A Fig. H7 : Utilization categories of LV AC switches according to IEC 60947-3 (1) i.e. a LV disconnector is essentially a dead system switching device to be operated with no voltage on either side of it, particularly when closing, because of the possibility of an unsuspected short-circuit on the downstream side. Interlocking with an upstream switch or circuit-breaker is frequently used. Schneider Electric - Electrical installation guide 2009 8 © Schneider Electric - all rights reserved Utilization category Frequent Infrequent operations operations AC-20A AC-20B H - LV switchgear: functions & selection 2 The switchgear Remote control switch (see Fig. H8) This device is extensively used in the control of lighting circuits where the depression of a pushbutton (at a remote control position) will open an already-closed switch or close an opened switch in a bistable sequence. Typical applications are: b Two-way switching on stairways of large buildings b Stage-lighting schemes b Factory illumination, etc. Auxiliary devices are available to provide: b Remote indication of its state at any instant b Time-delay functions b Maintained-contact features Contactor (see Fig. H9) The contactor is a solenoid-operated switching device which is generally held closed by (a reduced) current through the closing solenoid (although various mechanically-latched types exist for specific duties). Contactors are designed to carry out numerous close/open cycles and are commonly controlled remotely by on-off pushbuttons. The large number of repetitive operating cycles is standardized in table VIII of IEC 60947-4-1 by: b The operating duration: 8 hours; uninterrupted; intermittent; temporary of 3, 10, 30, 60 and 90 minutes b Utilization category: for example, a contactor of category AC3 can be used for the starting and stopping of a cage motor b The start-stop cycles (1 to 1,200 cyles per hour) b Mechanical endurance (number of off-load manœuvres) b Electrical endurance (number of on-load manœuvres) b A rated current making and breaking performance according to the category of utilization concerned H6 Example: A 150 A contactor of category AC3 must have a minimum current-breaking capability of 8 In (= 1,200 A) and a minimum current-making rating of 10 In (= 1,500 A) at a power factor (lagging) of 0.35. Fig. H8 : Symbol for a bistable remote control switch Discontactor(1) Control circuit A contactor equipped with a thermal-type relay for protection against overloading defines a “discontactor”. Discontactors are used extensively for remote push-button control of lighting circuits, etc., and may also be considered as an essential element in a motor controller, as noted in sub-clause 2.2. “combined switchgear elements”. The discontactor is not the equivalent of a circuit-breaker, since its short-circuit current breaking capability is limited to 8 or 10 In. For short-circuit protection therefore, it is necessary to include either fuses or a circuit-breaker in series with, and upstream of, the discontactor contacts. Power circuit Fig. H9 : Symbol for a contactor Two classes of LV cartridge fuse are very widely used: b For domestic and similar installations type gG b For industrial installations type gG, gM or aM Fuses (see Fig. H10) The first letter indicates the breaking range: b “g” fuse-links (full-range breaking-capacity fuse-link) b “a” fuse-links (partial-range breaking-capacity fuse-link) The second letter indicates the utilization category; this letter defines with accuracy the time-current characteristics, conventional times and currents, gates. © Schneider Electric - all rights reserved For example b “gG” indicates fuse-links with a full-range breaking capacity for general application b “gM” indicates fuse-links with a full-range breaking capacity for the protection of motor circuits b “aM” indicates fuse-links with a partial range breaking capacity for the protection of motor circuits Fuses exist with and without “fuse-blown” mechanical indicators. Fuses break a circuit by controlled melting of the fuse element when a current exceeds a given value for a corresponding period of time; the current/time relationship being presented in the form of a performance curve for each type of fuse. Standards define two classes of fuse: b Those intended for domestic installations, manufactured in the form of a cartridge for rated currents up to 100 A and designated type gG in IEC 60269-1 and 3 b Those for industrial use, with cartridge types designated gG (general use); and gM and aM (for motor-circuits) in IEC 60269-1 and 2 Fig. H10 : Symbol for fuses (1) This term is not defined in IEC publications but is commonly used in some countries. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 2 The switchgear The main differences between domestic and industrial fuses are the nominal voltage and current levels (which require much larger physical dimensions) and their fault-current breaking capabilities. Type gG fuse-links are often used for the protection of motor circuits, which is possible when their characteristics are capable of withstanding the motor-starting current without deterioration. A more recent development has been the adoption by the IEC of a fuse-type gM for motor protection, designed to cover starting, and short-circuit conditions. This type of fuse is more popular in some countries than in others, but at the present time the aM fuse in combination with a thermal overload relay is more-widely used. A gM fuse-link, which has a dual rating is characterized by two current values. The first value In denotes both the rated current of the fuse-link and the rated current of the fuseholder; the second value Ich denotes the time-current characteristic of the fuse-link as defined by the gates in Tables II, III and VI of IEC 60269-1. These two ratings are separated by a letter which defines the applications. For example: In M Ich denotes a fuse intended to be used for protection of motor circuits and having the characteristic G. The first value In corresponds to the maximum continuous current for the whole fuse and the second value Ich corresponds to the G characteristic of the fuse link. For further details see note at the end of sub-clause 2.1. An aM fuse-link is characterized by one current value In and time-current characteristic as shown in Figure H14 next page. Important: Some national standards use a gI (industrial) type fuse, similar in all main essentails to type gG fuses. Type gI fuses should never be used, however, in domestic and similar installations. gM fuses require a separate overload relay, as described in the note at the end of sub-clause 2.1. H7 Fusing zones - conventional currents The conditions of fusing (melting) of a fuse are defined by standards, according to their class. Class gG fuses These fuses provide protection against overloads and short-circuits. Conventional non-fusing and fusing currents are standardized, as shown in Figure H12 and in Figure H13. b The conventional non-fusing current Inf is the value of current that the fusible element can carry for a specified time without melting. Example: A 32 A fuse carrying a current of 1.25 In (i.e. 40 A) must not melt in less than one hour (table H13) b The conventional fusing current If (= I2 in Fig. H12) is the value of current which will cause melting of the fusible element before the expiration of the specified time. Example: A 32 A fuse carrying a current of 1.6 In (i.e. 52.1 A) must melt in one hour or less IEC 60269-1 standardized tests require that a fuse-operating characteristic lies between the two limiting curves (shown in Figure H12) for the particular fuse under test. This means that two fuses which satisfy the test can have significantly different operating times at low levels of overloading. Minimum pre-arcing time curve 1 hour Rated current(1) In (A) In y 4 A 4 < In < 16 A 16 < In y 63 A 63 < In y 160 A 160 < In y 400 A 400 < In Fuse-blow curve Inf I2 I Fig. H12 : Zones of fusing and non-fusing for gG and gM fuses Conventional nonfusing current Inf Conventional fusing current I2 Conventional time (h) 1 1.5 In 2.1 In 1.5 In 1.9 In 1 1.25 In 1.6 In 1 1.25 In 1.6 In 2 1.25 In 1.6 In 3 1.25 In 1.6 In 4 Fig. H13 : Zones of fusing and non-fusing for LV types gG and gM class fuses (IEC 60269-1 and 60269-2-1) (1) Ich for gM fuses Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved t H - LV switchgear: functions & selection 2 The switchgear b The two examples given above for a 32 A fuse, together with the foregoing notes on standard test requirements, explain why these fuses have a poor performance in the low overload range b It is therefore necessary to install a cable larger in ampacity than that normally required for a circuit, in order to avoid the consequences of possible long term overloading (60% overload for up to one hour in the worst case) By way of comparison, a circuit-breaker of similar current rating: b Which passes 1.05 In must not trip in less than one hour; and b When passing 1.25 In it must trip in one hour, or less (25% overload for up to one hour in the worst case) Class aM (motor) fuses These fuses afford protection against short-circuit currents only and must necessarily be associated with other switchgear (such as discontactors or circuit-breakers) in order to ensure overload protection < 4 In. They are not therefore autonomous. Since aM fuses are not intended to protect against low values of overload current, no levels of conventional non-fusing and fusing currents are fixed. The characteristic curves for testing these fuses are given for values of fault current exceeding approximately 4 In (see Fig. H14), and fuses tested to IEC 60269 must give operating curves which fall within the shaded area. Class aM fuses protect against short-circuit currents only, and must always be associated with another device which protects against overload Note: the small “arrowheads” in the diagram indicate the current/time “gate” values for the different fuses to be tested (IEC 60269). Rated short-circuit breaking currents A characteristic of modern cartridge fuses is that, owing to the rapidity of fusion in the case of high short-circuit current levels(1), a current cut-off begins before the occurrence of the first major peak, so that the fault current never reaches its prospective peak value (see Fig. H15). H8 This limitation of current reduces significantly the thermal and dynamic stresses which would otherwise occur, thereby minimizing danger and damage at the fault position. The rated short-circuit breaking current of the fuse is therefore based on the rms value of the AC component of the prospective fault current. t No short-circuit current-making rating is assigned to fuses. Minimum pre-arcing time curve Reminder Short-circuit currents initially contain DC components, the magnitude and duration of which depend on the XL/R ratio of the fault current loop. Fuse-blown curve Close to the source (MV/LV transformer) the relationship Ipeak / Irms (of AC component) immediately following the instant of fault, can be as high as 2.5 (standardized by IEC, and shown in Figure H16 next page). 4 In x In Fig. H14 : Standardized zones of fusing for type aM fuses (all current ratings) I Prospective fault-current peak rms value of the AC component of the prospective fault curent Current peak limited by the fuse 0.01 s © Schneider Electric - all rights reserved Tf Ta Ttc t 0.005 s 0.02 s Tf: Fuse pre-arc fusing time Ta: Arcing time Ttc: Total fault-clearance time Fig. H15 : Current limitation by a fuse At lower levels of distribution in an installation, as previously noted, XL is small compared with R and so for final circuits Ipeak / Irms ~ 1.41, a condition which corresponds with Figure H15. The peak-current-limitation effect occurs only when the prospective rms AC component of fault current attains a certain level. For example, in the Figure H16 graph, the 100 A fuse will begin to cut off the peak at a prospective fault current (rms) of 2 kA (a). The same fuse for a condition of 20 kA rms prospective current will limit the peak current to 10 kA (b). Without a current-limiting fuse the peak current could attain 50 kA (c) in this particular case. As already mentioned, at lower distribution levels in an installation, R greatly predominates XL, and fault levels are generally low. This means that the level of fault current may not attain values high enough to cause peak current limitation. On the other hand, the DC transients (in this case) have an insignificant effect on the magnitude of the current peak, as previously mentioned. Note: On gM fuse ratings A gM type fuse is essentially a gG fuse, the fusible element of which corresponds to the current value Ich (ch = characteristic) which may be, for example, 63 A. This is the IEC testing value, so that its time/ current characteristic is identical to that of a 63 A gG fuse. This value (63 A) is selected to withstand the high starting currents of a motor, the steady state operating current (In) of which may be in the 10-20 A range. This means that a physically smaller fuse barrel and metallic parts can be used, since the heat dissipation required in normal service is related to the lower figures (10-20 A). A standard gM fuse, suitable for this situation would be designated 32M63 (i.e. In M Ich). The first current rating In concerns the steady-load thermal performance of the fuselink, while the second current rating (Ich) relates to its (short-time) startingcurrent performance. It is evident that, although suitable for short-circuit protection, (1) For currents exceeding a certain level, depending on the fuse nominal current rating, as shown below in Figure H16. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection Prospective fault current (kA) peak 2 The switchgear overload protection for the motor is not provided by the fuse, and so a separate thermal-type relay is always necessary when using gM fuses. The only advantage offered by gM fuses, therefore, when compared with aM fuses, are reduced physical dimensions and slightly lower cost. Maximum possible current peak characteristic i.e. 2.5 Irms (IEC) 100 20 (b) 10 Single units of switchgear do not, in general, fulfil all the requirements of the three basic functions, viz: Protection, control and isolation. 160A Nominal 100A fuse 50A ratings Where the installation of a circuit-breaker is not appropriate (notably where the switching rate is high, over extended periods) combinations of units specifically designed for such a performance are employed. The most commonly-used combinations are described below. (a) 5 Peak current cut-off characteristic curves 2 1 2.2 Combined switchgear elements (c) 50 1 2 5 10 20 Switch and fuse combinations 50 100 AC component of prospective fault current (kA) rms Fig. H16 : Limited peak current versus prospective rms values of the AC component of fault current for LV fuses Two cases are distinguished: b The type in which the operation of one (or more) fuse(s) causes the switch to open. This is achieved by the use of fuses fitted with striker pins, and a system of switch tripping springs and toggle mechanisms (see Fig. H17) b The type in which a non-automatic switch is associated with a set of fuses in a common enclosure. In some countries, and in IEC 60947-3, the terms “switch-fuse” and “fuse-switch” have specific meanings, viz: v A switch-fuse comprises a switch (generally 2 breaks per pole) on the upstream side of three fixed fuse-bases, into which the fuse carriers are inserted (see Fig. H18) v A fuse-switch consists of three switch blades each constituting a double-break per phase. H9 These blades are not continuous throughout their length, but each has a gap in the centre which is bridged by the fuse cartridge. Some designs have only a single break per phase, as shown in Figure H19. Fig. H17 : Symbol for an automatic tripping switch-fuse Fig. H18 : Symbol for a non-automatic fuse-switch Fig. H19 : Symbol for a non-automatic switch-fuse The current range for these devices is limited to 100 A maximum at 400 V 3-phase, while their principal use is in domestic and similar installations. To avoid confusion between the first group (i.e. automatic tripping) and the second group, the term “switch-fuse” should be qualified by the adjectives “automatic” or “non-automatic”. Fig. H20 : Symbol for a fuse disconnector + discontactor The fuse-disconnector must be interlocked with the discontactor such that no opening or closing manœuvre of the fuse disconnector is possible unless the discontactor is open ( Figure H20), since the fuse disconnector has no load-switching capability. A fuse-switch-disconnector (evidently) requires no interlocking (Figure H21). The switch must be of class AC22 or AC23 if the circuit supplies a motor. Fig. H21 : Symbol for a fuse-switch disconnector + discontactor Circuit-breaker + contactor Circuit-breaker + discontactor These combinations are used in remotely controlled distribution systems in which the rate of switching is high, or for control and protection of a circuit supplying motors. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fuse – disconnector + discontactor Fuse - switch-disconnector + discontactor As previously mentioned, a discontactor does not provide protection against shortcircuit faults. It is necessary, therefore, to add fuses (generally of type aM) to perform this function. The combination is used mainly for motor control circuits, where the disconnector or switch-disconnector allows safe operations such as: b The changing of fuse links (with the circuit isolated) b Work on the circuit downstream of the discontactor (risk of remote closure of the discontactor) H - LV switchgear: functions & selection 3 Choice of switchgear 3.1 Tabulated functional capabilities After having studied the basic functions of LV switchgear (clause 1, Figure H1) and the different components of switchgear (clause 2), Figure H22 summarizes the capabilities of the various components to perform the basic functions. Isolation Switchgear item H10 Isolator (or disconnector)(4) Switch(5) Residual device (RCCB)(5) Switchdisconnector Contactor Remote control switch Fuse Circuit breaker Circuit-breaker disconnector(5) Residual and overcurrent circuit-breaker (RCBO)(5) Point of installation (general principle) Control Functional Emergency switching Emergency stop (mechanical) Switching for mechanical maintenance Electrical protection Overload Short-circuit Electric shock b b b b b b (1) b (1) b (1) (2) b (1) (2) b b b b b (1) b (1) (2) b b b b (1) b (1) b (1) (2) b b b b (1) b (1) (2) b b b b b b b b (1) b (1) (2) b b b b b b (1) b (1) (2) b b b b Origin of each circuit All points where, for operational reasons it may be necessary to stop the process In general at the incoming circuit to every distribution board At the supply point to each machine and/or on the machine concerned At the supply point to each machine Origin of each circuit Origin of each circuit Origin of circuits where the earthing system is appropriate TN-S, IT, TT b b b (3) (1) Where cut-off of all active conductors is provided (2) It may be necessary to maintain supply to a braking system (3) If it is associated with a thermal relay (the combination is commonly referred to as a “discontactor”) (4) In certain countries a disconnector with visible contacts is mandatory at the origin of a LV installation supplied directly from a MV/LV transformer (5) Certain items of switchgear are suitable for isolation duties (e.g. RCCBs according to IEC 61008) without being explicitly marked as such Fig. H22 : Functions fulfilled by different items of switchgear 3.2 Switchgear selection © Schneider Electric - all rights reserved Software is being used more and more in the field of optimal selection of switchgear. Each circuit is considered one at a time, and a list is drawn up of the required protection functions and exploitation of the installation, among those mentioned in Figure H22 and summarized in Figure H1. A number of switchgear combinations are studied and compared with each other against relevant criteria, with the aim of achieving: b Satisfactory performance b Compatibility among the individual items; from the rated current In to the fault-level rating Icu b Compatibility with upstream switchgear or taking into account its contribution b Conformity with all regulations and specifications concerning safe and reliable circuit performance In order to determine the number of poles for an item of switchgear, reference is made to chapter G, clause 7 Fig. G64. Multifunction switchgear, initially more costly, reduces installation costs and problems of installation or exploitation. It is often found that such switchgear provides the best solution. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 4 Circuit-breaker The circuit-breaker/disconnector fulfills all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist As shown in Figure H23 the circuit-breaker/ disconnector is the only item of switchgear capable of simultaneously satisfying all the basic functions necessary in an electrical installation. Moreover, it can, by means of auxiliary units, provide a wide range of other functions, for example: indication (on-off - tripped on fault); undervoltage tripping; remote control… etc. These features make a circuit-breaker/ disconnector the basic unit of switchgear for any electrical installation. Functions Isolation Control Protection Functional Emergency switching Switching-off for mechanical maintenance Overload Short-circuit Insulation fault Undervoltage Remote control Indication and measurement Possible conditions b b b (With the possibility of a tripping coil for remote control) b b b b (With differential-current relay) b (With undervoltage-trip coil) b Added or incorporated b (Generally optional with an electronic tripping device) H11 Fig. H23 : Functions performed by a circuit-breaker/disconnector Power circuit terminals Contacts and arc-diving chamber Fool-proof mechanical indicator Latching mechanism Trip mechanism and protective devices Fig. H24 : Main parts of a circuit-breaker 4.1 Standards and description Standards For industrial LV installations the relevant IEC standards are, or are due to be: b 60947-1: general rules b 60947-2: part 2: circuit-breakers b 60947-3: part 3: switches, disconnectors, switch-disconnectors and fuse combination units b 60947-4: part 4: contactors and motor starters b 60947-5: part 5: control-circuit devices and switching elements b 60947-6: part 6: multiple function switching devices b 60947-7: part 7: ancillary equipment For domestic and similar LV installations, the appropriate standard is IEC 60898, or an equivalent national standard. Description Figure H24 shows schematically the main parts of a LV circuit-breaker and its four essential functions: b The circuit-breaking components, comprising the fixed and moving contacts and the arc-dividing chamber b The latching mechanism which becomes unlatched by the tripping device on detection of abnormal current conditions This mechanism is also linked to the operation handle of the breaker. b A trip-mechanism actuating device: v Either: a thermal-magnetic device, in which a thermally-operated bi-metal strip detects an overload condition, while an electromagnetic striker pin operates at current levels reached in short-circuit conditions, or v An electronic relay operated from current transformers, one of which is installed on each phase b A space allocated to the several types of terminal currently used for the main power circuit conductors Domestic circuit-breakers (see Fig. H25 next page) complying with IEC 60898 and similar national standards perform the basic functions of: b Isolation b Protection against overcurrent Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Industrial circuit-breakers must comply with IEC 60947-1 and 60947-2 or other equivalent standards. Domestic-type circuit-breakers must comply with IEC standard 60898, or an equivalent national standard H - LV switchgear: functions & selection 4 Circuit-breaker Some models can be adapted to provide sensitive detection (30 mA) of earthleakage current with CB tripping, by the addition of a modular block, while other models (RCBOs, complying with IEC 61009 and CBRs complying with IEC 60947-2 Annex B) have this residual current feature incorporated as shown in Figure H26. Apart from the above-mentioned functions further features can be associated with the basic circuit-breaker by means of additional modules, as shown in Figure H27; notably remote control and indication (on-off-fault). 1 3 5 2 4 Fig. H25 : Domestic-type circuit-breaker providing overcurrent protection and circuit isolation features O-OFF O--OFF O--OFF H12 Fig. H27 : “Multi 9” system of LV modular switchgear components Moulded-case circuit-breakers complying with IEC 60947-2 are available from 100 to 630 A and provide a similar range of auxiliary functions to those described above (see Figure H28). Air circuit-breakers of large current ratings, complying with IEC 60947-2, are generally used in the main switch board and provide protector for currents from 630 A to 6300 A, typically.(see Figure H29). In addition to the protection functions, the Micrologic unit provides optimized functions such as measurement (including power quality functions), diagnosis, communication, control and monitoring. © Schneider Electric - all rights reserved Fig. H26 : Domestic-type circuit-breaker as above (Fig. H25) with incorparated protection against electric shocks Fig. H28 : Example of a Compact NSX industrial type of circuitbreaker capable of numerous auxiliary functions Fig. H29 : Example of air circuit-breakers. Masterpact provides many control features in its “Micrologic” tripping unit Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 4 Circuit-breaker 4.2 Fundamental characteristics of a circuit-breaker The fundamental characteristics of a circuit-breaker are: b Its rated voltage Ue b Its rated current In b Its tripping-current-level adjustment ranges for overload protection (Ir(1) or Irth(1)) and for short-circuit protection (Im)(1) b Its short-circuit current breaking rating (Icu for industrial CBs; Icn for domestictype CBs). Rated operational voltage (Ue) This is the voltage at which the circuit-breaker has been designed to operate, in normal (undisturbed) conditions. Other values of voltage are also assigned to the circuit-breaker, corresponding to disturbed conditions, as noted in sub-clause 4.3. Rated current (In) This is the maximum value of current that a circuit-breaker, fitted with a specified overcurrent tripping relay, can carry indefinitely at an ambient temperature stated by the manufacturer, without exceeding the specified temperature limits of the current carrying parts. Example A circuit-breaker rated at In = 125 A for an ambient temperature of 40 °C will be equipped with a suitably calibrated overcurrent tripping relay (set at 125 A). The same circuit-breaker can be used at higher values of ambient temperature however, if suitably “derated”. Thus, the circuit-breaker in an ambient temperature of 50 °C could carry only 117 A indefinitely, or again, only 109 A at 60 °C, while complying with the specified temperature limit. H13 Derating a circuit-breaker is achieved therefore, by reducing the trip-current setting of its overload relay, and marking the CB accordingly. The use of an electronic-type of tripping unit, designed to withstand high temperatures, allows circuit-breakers (derated as described) to operate at 60 °C (or even at 70 °C) ambient. Note: In for circuit-breakers (in IEC 60947-2) is equal to Iu for switchgear generally, Iu being the rated uninterrupted current. Frame-size rating A circuit-breaker which can be fitted with overcurrent tripping units of different current level-setting ranges, is assigned a rating which corresponds to the highest currentlevel-setting tripping unit that can be fitted. Example A Compact NSX630N circuit-breaker can be equipped with 11 electronic trip units from 150 A to 630 A. The size of the circuit-breaker is 630 A. Overload relay trip-current setting (Irth or Ir) Rated current of the tripping unit In Adjustment range 160 A 360 A The thermal-trip relays are generally adjustable from 0.7 to 1.0 times In, but when electronic devices are used for this duty, the adjustment range is greater; typically 0.4 to 1 times In. Circuit breaker frame-size rating Overload trip current setting Ir 400 A Example (see Fig. H30) A NSX630N circuit-breaker equipped with a 400 A Micrologic 6.3E overcurrent trip relay, set at 0.9, will have a trip-current setting: 630 A Fig. H30 : Example of a NSX630N circuit-breaker equipped with a Micrologic 6.3E trip unit adjusted to 0.9, to give Ir = 360 A Ir = 400 x 0.9 = 360 A Note: For circuit-breakers equipped with non-adjustable overcurrent-trip relays, Ir = In. Example: for C60N 20 A circuit-breaker, Ir = In = 20 A. (1) Current-level setting values which refer to the currentoperated thermal and “instantaneous” magnetic tripping devices for over-load and short-circuit protection. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 0.4 In Apart from small circuit-breakers which are very easily replaced, industrial circuitbreakers are equipped with removable, i.e. exchangeable, overcurrent-trip relays. Moreover, in order to adapt a circuit-breaker to the requirements of the circuit it controls, and to avoid the need to install over-sized cables, the trip relays are generally adjustable. The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit-breaker will trip. It also represents the maximum current that the circuit-breaker can carry without tripping. That value must be greater than the maximum load current IB, but less than the maximum current permitted in the circuit Iz (see chapter G, sub-clause 1.3). 4 Circuit-breaker H - LV switchgear: functions & selection Short-circuit relay trip-current setting (Im) Short-circuit tripping relays (instantaneous or slightly time-delayed) are intended to trip the circuit-breaker rapidly on the occurrence of high values of fault current. Their tripping threshold Im is: b Either fixed by standards for domestic type CBs, e.g. IEC 60898, or, b Indicated by the manufacturer for industrial type CBs according to related standards, notably IEC 60947-2. For the latter circuit-breakers there exists a wide variety of tripping devices which allow a user to adapt the protective performance of the circuit-breaker to the particular requirements of a load (see Fig. H31, Fig. H32 and Fig. H33). H14 Type of protective relay Overload protection Short-circuit protection Domestic breakers IEC 60898 Thermalmagnetic Ir = In Low setting type B 3 In y Im y 5 In Standard setting type C 5 In y Im y 10 In High setting circuit type D 10 In y Im y 20 In(1) Modular industrial(2) circuit-breakers Thermalmagnetic Ir = In fixed Low setting type B or Z 3.2 In y fixed y 4.8 In Standard setting type C 7 In y fixed y 10 In High setting type D or K 10 In y fixed y 14 In Industrial(2) circuit-breakers IEC 60947-2 Thermalmagnetic Ir = In fixed Adjustable: 0.7 In y Ir y In Electronic Long delay 0.4 In y Ir y In Fixed: Im = 7 to 10 In Adjustable: - Low setting : 2 to 5 In - Standard setting: 5 to 10 In Short-delay, adjustable 1.5 Ir y Im y 10 Ir Instantaneous (I) fixed I = 12 to 15 In (1) 50 In in IEC 60898, which is considered to be unrealistically high by most European manufacturers (Merlin Gerin = 10 to 14 In). (2) For industrial use, IEC standards do not specify values. The above values are given only as being those in common use. Fig. H31 : Tripping-current ranges of overload and short-circuit protective devices for LV circuit-breakers t (s ) t (s ) Ir Im I(A Ii Icu © Schneider Electric - all rights reserved Ir: Overload (thermal or long-delay) relay trip-current Ir I(A Im Icu Fig. H32 : Performance curve of a circuit-breaker thermalmagnetic protective scheme setting Im: Short-circuit (magnetic or short-delay) relay tripcurrent setting Ii: Short-circuit instantaneous relay trip-current setting. Icu: Breaking capacity Fig. H33 : Performance curve of a circuit-breaker electronic protective scheme Schneider Electric - Electrical installation guide 2009 4 Circuit-breaker H - LV switchgear: functions & selection Isolating feature A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions prescribed for a disconnector (at its rated voltage) in the relevant standard (see sub-clause 1.2). In such a case it is referred to as a circuit-breaker-disconnector and marked on its front face with the symbol All Multi 9, Compact NSX and Masterpact LV switchgear of Schneider Electric ranges are in this category. The short-circuit current-breaking performance of a LV circuit-breaker is related (approximately) to the cos ϕ of the fault-current loop. Standard values for this relationship have been established in some standards Rated short-circuit breaking capacity (Icu or Icn) The short-circuit current-breaking rating of a CB is the highest (prospective) value of current that the CB is capable of breaking without being damaged. The value of current quoted in the standards is the rms value of the AC component of the fault current, i.e. the DC transient component (which is always present in the worst possible case of short-circuit) is assumed to be zero for calculating the standardized value. This rated value (Icu) for industrial CBs and (Icn) for domestic-type CBs is normally given in kA rms. Icu (rated ultimate s.c. breaking capacity) and Ics (rated service s.c. breaking capacity) are defined in IEC 60947-2 together with a table relating Ics with Icu for different categories of utilization A (instantaneous tripping) and B (time-delayed tripping) as discussed in subclause 4.3. Tests for proving the rated s.c. breaking capacities of CBs are governed by standards, and include: b Operating sequences, comprising a succession of operations, i.e. closing and opening on short-circuit b Current and voltage phase displacement. When the current is in phase with the supply voltage (cos ϕ for the circuit = 1), interruption of the current is easier than that at any other power factor. Breaking a current at low lagging values of cos ϕ is considerably more difficult to achieve; a zero power-factor circuit being (theoretically) the most onerous case. H15 In practice, all power-system short-circuit fault currents are (more or less) at lagging power factors, and standards are based on values commonly considered to be representative of the majority of power systems. In general, the greater the level of fault current (at a given voltage), the lower the power factor of the fault-current loop, for example, close to generators or large transformers. Figure H34 below extracted from IEC 60947-2 relates standardized values of cos ϕ to industrial circuit-breakers according to their rated Icu. b Following an open - time delay - close/open sequence to test the Icu capacity of a CB, further tests are made to ensure that: v The dielectric withstand capability v The disconnection (isolation) performance and v The correct operation of the overload protection have not been impaired by the test. Icu cos ϕ 6 kA < Icu y 10 kA 0.5 10 kA < Icu y 20 kA 0.3 20 kA < Icu y 50 kA 0.25 50 kA < Icu 0.2 Fig. H34 : Icu related to power factor (cos ϕ) of fault-current circuit (IEC 60947-2) 4.3 Other characteristics of a circuit-breaker Rated insulation voltage (Ui) This is the value of voltage to which the dielectric tests voltage (generally greater than 2 Ui) and creepage distances are referred to. The maximum value of rated operational voltage must never exceed that of the rated insulation voltage, i.e. Ue y Ui. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Familiarity with the following characteristics of LV circuit-breakers is often necessary when making a final choice. 4 Circuit-breaker H - LV switchgear: functions & selection Rated impulse-withstand voltage (Uimp) This characteristic expresses, in kV peak (of a prescribed form and polarity) the value of voltage which the equipment is capable of withstanding without failure, under test conditions. Generally, for industrial circuit-breakers, Uimp = 8 kV and for domestic types, Uimp = 6 kV. t (s) Category (A or B) and rated short-time withstand current (Icw) As already briefly mentioned (sub-clause 4.2) there are two categories of LV industrial switchgear, A and B, according to IEC 60947-2: b Those of category A, for which there is no deliberate delay in the operation of the “instantaneous” short-circuit magnetic tripping device (see Fig. H35), are generally moulded-case type circuit-breakers, and b Those of category B for which, in order to discriminate with other circuit-breakers on a time basis, it is possible to delay the tripping of the CB, where the fault-current level is lower than that of the short-time withstand current rating (Icw) of the CB (see Fig. H36). This is generally applied to large open-type circuit-breakers and to certain heavy-duty moulded-case types. Icw is the maximum current that the B category CB can withstand, thermally and electrodynamically, without sustaining damage, for a period of time given by the manufacturer. I(A) Im Rated making capacity (Icm) Fig. H35 : Category A circuit-breaker Icm is the highest instantaneous value of current that the circuit-breaker can establish at rated voltage in specified conditions. In AC systems this instantaneous peak value is related to Icu (i.e. to the rated breaking current) by the factor k, which depends on the power factor (cos ϕ) of the short-circuit current loop (as shown in Figure H37 ). H16 t (s ) Icu cos ϕ 6 kA < Icu y 10 kA 0.5 10 kA < Icu y 20 kA 0.3 20 kA < Icu y 50 kA 0.25 50 kA y Icu 0.2 Icm = kIcu 1.7 x Icu 2 x Icu 2.1 x Icu 2.2 x Icu Fig. H37 : Relation between rated breaking capacity Icu and rated making capacity Icm at different power-factor values of short-circuit current, as standardized in IEC 60947-2 I(A ) Im I Icw Icu Example: A Masterpact NW08H2 circuit-breaker has a rated breaking capacity Icu of 100 kA. The peak value of its rated making capacity Icm will be Fig. H36 : Category B circuit-breaker 100 x 2.2 = 220 kA. © Schneider Electric - all rights reserved In a correctly designed installation, a circuitbreaker is never required to operate at its maximum breaking current Icu. For this reason a new characteristic Ics has been introduced. It is expressed in IEC 60947-2 as a percentage of Icu (25, 50, 75, 100%) Rated service short-circuit breaking capacity (Ics) The rated breaking capacity (Icu) or (Icn) is the maximum fault-current a circuitbreaker can successfully interrupt without being damaged. The probability of such a current occurring is extremely low, and in normal circumstances the fault-currents are considerably less than the rated breaking capacity (Icu) of the CB. On the other hand it is important that high currents (of low probability) be interrupted under good conditions, so that the CB is immediately available for reclosure, after the faulty circuit has been repaired. It is for these reasons that a new characteristic (Ics) has been created, expressed as a percentage of Icu, viz: 25, 50, 75, 100% for industrial circuit-breakers. The standard test sequence is as follows: b O - CO - CO(1) (at Ics) b Tests carried out following this sequence are intended to verify that the CB is in a good state and available for normal service For domestic CBs, Ics = k Icn. The factor k values are given in IEC 60898 table XIV. In Europe it is the industrial practice to use a k factor of 100% so that Ics = Icu. (1) O represents an opening operation. CO represents a closing operation followed by an opening operation. Schneider Electric - Electrical installation guide 2009 4 Circuit-breaker H - LV switchgear: functions & selection Many designs of LV circuit-breakers feature a short-circuit current limitation capability, whereby the current is reduced and prevented from reaching its (otherwise) maximum peak value (see Fig. H38). The current-limitation performance of these CBs is presented in the form of graphs, typified by that shown in Figure H39, diagram (a) Fault-current limitation The fault-current limitation capacity of a CB concerns its ability, more or less effective, in preventing the passage of the maximum prospective fault-current, permitting only a limited amount of current to flow, as shown in Figure H38. The current-limitation performance is given by the CB manufacturer in the form of curves (see Fig. H39). b Diagram (a) shows the limited peak value of current plotted against the rms value of the AC component of the prospective fault current (“prospective” faultcurrent refers to the fault-current which would flow if the CB had no current-limiting capability) b Limitation of the current greatly reduces the thermal stresses (proportional I2t) and this is shown by the curve of diagram (b) of Figure H39, again, versus the rms value of the AC component of the prospective fault current. LV circuit-breakers for domestic and similar installations are classified in certain standards (notably European Standard EN 60 898). CBs belonging to one class (of current limiters) have standardized limiting I2t let-through characteristics defined by that class. In these cases, manufacturers do not normally provide characteristic performance curves. a) b) Limited current peak (kA) 22 Limited current peak (A2 x s) t n rre cu s d ic ite rist limcte on ra N ha c H17 4,5.105 2.105 Prospective AC component (rms) Prospective AC component (rms) 150 kA 150 kA Fig. H39 : Performance curves of a typical LV current-limiting circuit-breaker Current limitation reduces both thermal and electrodynamic stresses on all circuit elements through which the current passes, thereby prolonging the useful life of these elements. Furthermore, the limitation feature allows “cascading” techniques to be used (see 4.5) thereby significantly reducing design and installation costs The advantages of current limitation The use of current-limiting CBs affords numerous advantages: b Better conservation of installation networks: current-limiting CBs strongly attenuate all harmful effects associated with short-circuit currents b Reduction of thermal effects: Conductors (and therefore insulation) heating is significantly reduced, so that the life of cables is correspondingly increased b Reduction of mechanical effects: forces due to electromagnetic repulsion are lower, with less risk of deformation and possible rupture, excessive burning of contacts, etc. b Reduction of electromagnetic-interference effects: v Less influence on measuring instruments and associated circuits, telecommunication systems, etc. Icc Prospectice fault-current peak Limited current peak Example On a system having a prospective shortcircuit current of 150 kA rms, a Compact L circuit-breaker limits the peak current to less than 10% of the calculated prospective peak value, and the thermal effects to less than 1% of those calculated. Prospectice fault-current Limited current tc Fig. H38 : Prospective and actual currents t Cascading of the several levels of distribution in an installation, downstream of a limiting CB, will also result in important savings. The technique of cascading, described in sub-clause 4.5 allows, in fact, substantial savings on switchgear (lower performance permissible downstream of the limiting CB(s)) enclosures, and design studies, of up to 20% (overall). Discriminative protection schemes and cascading are compatible, in the Compact NSX range, up to the full short-circuit breaking capacity of the switchgear. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved These circuit-breakers therefore contribute towards an improved exploitation of: b Cables and wiring b Prefabricated cable-trunking systems b Switchgear, thereby reducing the ageing of the installation 4 Circuit-breaker H - LV switchgear: functions & selection The choice of a range of circuit-breakers is determined by: the electrical characteristics of the installation, the environment, the loads and a need for remote control, together with the type of telecommunications system envisaged Ambient temperature Temperature of air surrouding the circuit breakers Ambient temperature 4.4 Selection of a circuit-breaker Choice of a circuit-breaker The choice of a CB is made in terms of: b Electrical characteristics of the installation for which the CB is intended b Its eventual environment: ambient temperature, in a kiosk or switchboard enclosure, climatic conditions, etc. b Short-circuit current breaking and making requirements b Operational specifications: discriminative tripping, requirements (or not) for remote control and indication and related auxiliary contacts, auxiliary tripping coils, connection b Installation regulations; in particular: protection of persons b Load characteristics, such as motors, fluorescent lighting, LV/LV transformers The following notes relate to the choice LV circuit-breaker for use in distribution systems. Choice of rated current in terms of ambient temperature Single CB in free air Circuit breakers installed in an enclosure Fig. H40 : Ambient temperature The rated current of a circuit-breaker is defined for operation at a given ambient temperature, in general: b 30 °C for domestic-type CBs b 40 °C for industrial-type CBs Performance of these CBs in a different ambient temperature depends mainly on the technology of their tripping units (see Fig. H40). H18 Circuit-breakers with uncompensated thermal tripping units have a trip current level that depends on the surrounding temperature Uncompensated thermal magnetic tripping units Circuit-breakers with uncompensated thermal tripping elements have a trippingcurrent level that depends on the surrounding temperature. If the CB is installed in an enclosure, or in a hot location (boiler room, etc.), the current required to trip the CB on overload will be sensibly reduced. When the temperature in which the CB is located exceeds its reference temperature, it will therefore be “derated”. For this reason, CB manufacturers provide tables which indicate factors to apply at temperatures different to the CB reference temperature. It may be noted from typical examples of such tables (see Fig. H41) that a lower temperature than the reference value produces an up-rating of the CB. Moreover, small modular-type CBs mounted in juxtaposition, as shown typically in Figure H27, are usually mounted in a small closed metal case. In this situation, mutual heating, when passing normal load currents, generally requires them to be derated by a factor of 0.8. Example What rating (In) should be selected for a C60 N? b Protecting a circuit, the maximum load current of which is estimated to be 34 A b Installed side-by-side with other CBs in a closed distribution box b In an ambient temperature of 50 °C A C60N circuit-breaker rated at 40 A would be derated to 35.6 A in ambient air at 50 °C (see Fig. H41). To allow for mutual heating in the enclosed space, however, the 0.8 factor noted above must be employed, so that, 35.6 x 0.8 = 28.5 A, which is not suitable for the 34 A load. A 50 A circuit-breaker would therefore be selected, giving a (derated) current rating of 44 x 0.8 = 35.2 A. Compensated thermal-magnetic tripping units © Schneider Electric - all rights reserved These tripping units include a bi-metal compensating strip which allows the overload trip-current setting (Ir or Irth) to be adjusted, within a specified range, irrespective of the ambient temperature. For example: b In certain countries, the TT system is standard on LV distribution systems, and domestic (and similar) installations are protected at the service position by a circuitbreaker provided by the supply authority. This CB, besides affording protection against indirect-contact hazard, will trip on overload; in this case, if the consumer exceeds the current level stated in his supply contract with the power authority. The circuit-breaker (y 60 A) is compensated for a temperature range of - 5 °C to + 40 °C. b LV circuit-breakers at ratings y 630 A are commonly equipped with compensated tripping units for this range (- 5 °C to + 40 °C) Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 4 Circuit-breaker C60a, C60H: curve C. C60N: curves B and C (reference temperature: 30 °C) Rating (A) 20 °C 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C 1 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.88 2 2.08 2.04 2.00 1.96 1.92 1.88 1.84 1.80 3 3.18 3.09 3.00 2.91 2.82 2.70 2.61 2.49 4 4.24 4.12 4.00 3.88 3.76 3.64 3.52 3.36 6 6.24 6.12 6.00 5.88 5.76 5.64 5.52 5.40 10 10.6 10.3 10.0 9.70 9.30 9.00 8.60 8.20 16 16.8 16.5 16.0 15.5 15.2 14.7 14.2 13.8 20 21.0 20.6 20.0 19.4 19.0 18.4 17.8 17.4 25 26.2 25.7 25.0 24.2 23.7 23.0 22.2 21.5 32 33.5 32.9 32.0 31.4 30.4 29.8 28.4 28.2 40 42.0 41.2 40.0 38.8 38.0 36.8 35.6 34.4 50 52.5 51.5 50.0 48.5 47.4 45.5 44.0 42.5 63 66.2 64.9 63.0 61.1 58.0 56.7 54.2 51.7 Compact NSX100-250 N/H/L equippment with TM-D or TM-G trip units Rating Temperature (°C) (A) 10 15 20 25 30 35 40 45 50 55 16 18.4 18.7 18 18 17 16.6 16 15.6 15.2 14.8 25 28.8 28 27.5 25 26.3 25.6 25 24.5 24 23.5 32 36.8 36 35.2 34.4 33.6 32.8 32 31.3 30.5 30 40 46 45 44 43 42 41 40 39 38 37 50 57.5 56 55 54 52.5 51 50 49 48 47 63 72 71 69 68 66 65 63 61.5 60 58 80 92 90 88 86 84 82 80 78 76 74 100 115 113 110 108 105 103 100 97.5 95 92.5 125 144 141 138 134 131 128 125 122 119 116 160 184 180 176 172 168 164 160 156 152 148 200 230 225 220 215 210 205 200 195 190 185 250 288 281 277 269 263 256 250 244 238 231 60 14.5 23 29.5 36 46 57 72 90 113 144 180 225 60 °C 0.85 1.74 2.37 3.24 5.30 7.80 13.5 16.8 20.7 27.5 33.2 40.5 49.2 65 14 22 29 35 45 55 70 87.5 109 140 175 219 70 13.8 21 28.5 34 44 54 68 85 106 136 170 213 H19 Fig. H41 : Examples of tables for the determination of derating/uprating factors to apply to CBs with uncompensated thermal tripping units, according to temperature Electronic trip units An important advantage with electronic tripping units is their stable performance in changing temperature conditions. However, the switchgear itself often imposes operational limits in elevated temperatures, so that manufacturers generally provide an operating chart relating the maximum values of permissible trip-current levels to the ambient temperature (see Fig. H42). Moreover, electronic trip units can provide information that can be used for a better management of the electrical distribution, including energy efficiency and power quality. Masterpact NW20 version H1/H2/H3 L1 Withdrawable with horizontal plugs Withdrawable with on-edge plugs In (A) Maximum adjustment Ir In (A) Maximum adjustment Ir 40°C 45°C 50°C 55°C 60°C 2,000 1 2,000 1 2,000 1 1,980 0.99 1,890 0.95 2,000 1 200 1 1,900 0.95 1,850 0.93 1,800 0.90 Coeff. In (A) 1 2,000 NW20 withdrawable with horizontal plugs 0.95 1,890 NW20 L1 withdrawable with on edge plugs 0.90 1,800 20 25 30 35 40 45 50 55 60 θ°C Fig. H42 : Derating of Masterpact NW20 circuit-breaker, according to the temperature Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Electronic tripping units are highly stable in changing temperature levels H - LV switchgear: functions & selection 4 Circuit-breaker Selection of an instantaneous, or short-time-delay, tripping threshold Figure H43 below summarizes the main characteristics of the instantaneous or short-time delay trip units. Type t Tripping unit Low setting type B Applications b Sources producing low short-circuitcurrent levels (standby generators) b Long lengths of line or cable Standard setting type C b Protection of circuits: general case High setting type D or K b Protection of circuits having high initial transient current levels (e.g. motors, transformers, resistive loads) 12 In type MA b Protection of motors in association with discontactors (contactors with overload protection) I t I t H20 I t I Fig. H43 : Different tripping units, instantaneous or short-time-delayed The installation of a LV circuit-breaker requires that its short-circuit breaking capacity (or that of the CB together with an associated device) be equal to or exceeds the calculated prospective short-circuit current at its point of installation Selection of a circuit-breaker according to the short-circuit breaking capacity requirements The installation of a circuit-breaker in a LV installation must fulfil one of the two following conditions: b Either have a rated short-circuit breaking capacity Icu (or Icn) which is equal to or exceeds the prospective short-circuit current calculated for its point of installation, or b If this is not the case, be associated with another device which is located upstream, and which has the required short-circuit breaking capacity In the second case, the characteristics of the two devices must be co-ordinated such that the energy permitted to pass through the upstream device must not exceed that which the downstream device and all associated cables, wires and other components can withstand, without being damaged in any way. This technique is profitably employed in: b Associations of fuses and circuit-breakers b Associations of current-limiting circuit-breakers and standard circuit-breakers. The technique is known as “cascading” (see sub-clause 4.5 of this chapter) © Schneider Electric - all rights reserved The circuit-breaker at the output of the smallest transformer must have a short-circuit capacity adequate for a fault current which is higher than that through any of the other transformer LV circuit-breakers The selection of main and principal circuit-breakers A single transformer If the transformer is located in a consumer’s substation, certain national standards require a LV circuit-breaker in which the open contacts are clearly visible such as Compact NSX withdrawable circuit-breaker. Example (see Fig. H44 opposite page) What type of circuit-breaker is suitable for the main circuit-breaker of an installation supplied through a 250 kVA MV/LV (400 V) 3-phase transformer in a consumer’s substation? In transformer = 360 A Isc (3-phase) = 8.9 kA A Compact NSX400N with an adjustable tripping-unit range of 160 A - 400 A and a short-circuit breaking capacity (Icu) of 50 kA would be a suitable choice for this duty. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 4 Circuit-breaker Several transformers in parallel (see Fig. H45) b The circuit-breakers CBP outgoing from the LV distribution board must each be capable of breaking the total fault current from all transformers connected to the busbars, viz: Isc1 + Isc2 + Isc3 b The circuit-breakers CBM, each controlling the output of a transformer, must be capable of dealing with a maximum short-circuit current of (for example) Isc2 + Isc3 only, for a short-circuit located on the upstream side of CBM1. From these considerations, it will be seen that the circuit-breaker of the smallest transformer will be subjected to the highest level of fault current in these circumstances, while the circuit-breaker of the largest transformer will pass the lowest level of short-circuit current b The ratings of CBMs must be chosen according to the kVA ratings of the associated transformers Note: The essential conditions for the successful operation of 3-phase transformers in parallel may be summarized as follows: 1. the phase shift of the voltages, primary to secondary, must be the same in all units to be paralleled. 2. the open-circuit voltage ratios, primary to secondary, must be the same in all units. 3. the short-circuit impedance voltage (Zsc%) must be the same for all units. For example, a 750 kVA transformer with a Zsc = 6% will share the load correctly with a 1,000 kVA transformer having a Zsc of 6%, i.e. the transformers will be loaded automatically in proportion to their kVA ratings. For transformers having a ratio of kVA ratings exceeding 2, parallel operation is not recommended. 250 kVA 20 kV/400 V Compact NSX400N Fig. H44 : Example of a transformer in a consumer’s substation MV Tr1 LV A1 Tr3 LV A2 CBM B1 CBM B2 CBP Moreover, this table shows selected circuit-breakers of M-G manufacture recommended for main and principal circuit-breakers in each case. MV Tr2 Example (see Fig. H47 next page) b Circuit-breaker selection for CBM duty: For a 800 kVA transformer In = 1.126 A; Icu (minimum) = 38 kA (from Figure H46), the CBM indicated in the table is a Compact NS1250N (Icu = 50 kA) b Circuit-breaker selection for CBP duty: The s.c. breaking capacity (Icu) required for these circuit-breakers is given in the Figure H46 as 56 kA. A recommended choice for the three outgoing circuits 1, 2 and 3 would be currentlimiting circuit-breakers types NSX400 L, NSX250 L and NSX100 L. The Icu rating in each case = 150 kA. LV A3 H21 CBM B3 CBP E Fig. H45 : Transformers in parallel Number and kVA ratings Minimum S.C breaking of 20/0.4 kV transformers capacity of main CBs (Icu) kA 2 x 400 14 3 x 400 28 2 x 630 22 3 x 630 44 2 x 800 19 3 x 800 38 2 x 1,000 23 3 x 1,000 47 2 x 1,250 29 3 x 1,250 59 2 x 1,600 38 3 x 1,600 75 2 x 2,000 47 3 x 2,000 94 Main circuit-breakers (CBM) total discrimination with out going circuit-breakers (CBP) NW08N1/NS800N NW08N1/NS800N NW10N1/NS1000N NW10N1/NS1000N NW12N1/NS1250N NW12N1/NS1250N NW16N1/NS1600N NW16N1/NS1600N NW20N1/NS2000N NW20N1/NS2000N NW25N1/NS2500N NW25N1/NS2500N NW32N1/NS3200N NW32N1/NS3200N Minimum S.C breaking capacity of principal CBs (Icu) kA 27 42 42 67 38 56 47 70 59 88 75 113 94 141 Rated current In of principal circuit-breaker (CPB) 250A NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250L NSX250L NSX250L NSX250L NSX250L Fig. H46 : Maximum values of short-circuit current to be interrupted by main and principal circuit-breakers (CBM and CBP respectively), for several transformers in parallel Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved MV Figure H46 indicates, for the most usual arrangement (2 or 3 transformers of equal kVA ratings) the maximum short-circuit currents to which main and principal CBs (CBM and CBP respectively, in Figure H45) are subjected. It is based on the following hypotheses: b The short-circuit 3-phase power on the MV side of the transformer is 500 MVA b The transformers are standard 20/0.4 kV distribution-type units rated as listed b The cables from each transformer to its LV circuit-breaker comprise 5 metres of single core conductors b Between each incoming-circuit CBM and each outgoing-circuit CBP there is 1 metre of busbar b The switchgear is installed in a floormounted enclosed switchboard, in an ambientair temperature of 30 °C 4 Circuit-breaker H - LV switchgear: functions & selection These circuit-breakers provide the advantages of: v Absolute discrimination with the upstream (CBM) breakers v Exploitation of the “cascading” technique, with its associated savings for all downstream components Choice of outgoing-circuit CBs and final-circuit CBs Short-circuit fault-current levels at any point in an installation may be obtained from tables Use of table G40 From this table, the value of 3-phase short-circuit current can be determined rapidly for any point in the installation, knowing: b The value of short-circuit current at a point upstream of that intended for the CB concerned b The length, c.s.a., and the composition of the conductors between the two points A circuit-breaker rated for a short-circuit breaking capacity exceeding the tabulated value may then be selected. Detailed calculation of the short-circuit current level In order to calculate more precisely the short-circuit current, notably, when the shortcircuit current-breaking capacity of a CB is slightly less than that derived from the table, it is necessary to use the method indicated in chapter G clause 4. Two-pole circuit-breakers (for phase and neutral) with one protected pole only These CBs are generally provided with an overcurrent protective device on the phase pole only, and may be used in TT, TN-S and IT schemes. In an IT scheme, however, the following conditions must be respected: b Condition (B) of table G67 for the protection of the neutral conductor against overcurrent in the case of a double fault b Short-circuit current-breaking rating: A 2-pole phase-neutral CB must, by convention, be capable of breaking on one pole (at the phase-to-phase voltage) the current of a double fault equal to 15% of the 3-phase short-circuit current at the point of its installation, if that current is y 10 kA; or 25% of the 3-phase short-circuit current if it exceeds 10 kA b Protection against indirect contact: this protection is provided according to the rules for IT schemes H22 Insufficient short-circuit current breaking rating In low-voltage distribution systems it sometimes happens, especially in heavy-duty networks, that the Isc calculated exceeds the Icu rating of the CBs available for installation, or system changes upstream result in lower level CB ratings being exceeded b Solution 1: Check whether or not appropriate CBs upstream of the CBs affected are of the current-limiting type, allowing the principle of cascading (described in subclause 4.5) to be applied b Solution 2: Install a range of CBs having a higher rating. This solution is economically interesting only where one or two CBs are affected b Solution 3: Associate current-limiting fuses (gG or aM) with the CBs concerned, on the upstream side. This arrangement must, however, respect the following rules: v The fuse rating must be appropriate v No fuse in the neutral conductor, except in certain IT installations where a double fault produces a current in the neutral which exceeds the short-circuit breaking rating of the CB. In this case, the blowing of the neutral fuse must cause the CB to trip on all phases 3 Tr 800 kVA 20 kV/400 V CBM CBP1 400 A CBP2 100 A CBP3 200 A © Schneider Electric - all rights reserved Fig. H47 : Transformers in parallel The technique of “cascading” uses the properties of current-limiting circuit-breakers to permit the installation of all downstream switchgear, cables and other circuit components of significantly lower performance than would otherwise be necessary, thereby simplifying and reducing the cost of an installation 4.5 Coordination between circuit-breakers Cascading Definition of the cascading technique By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX currentlimiting circuit-breakers with powerful limiting performances is particularly interesting. Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection In general, laboratory tests are necessary to ensure that the conditions of implementation required by national standards are met and compatible switchgear combinations must be provided by the manufacturer 4 Circuit-breaker Conditions of implementation Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage. In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, Figure H48 indicates the cascading possibilities of circuit-breaker types C60, DT40N, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation. Short-circuit breaking capacity of the upstream (limiter) CBs Possible short-circuit breaking capacity of the downstream CBs (benefiting from the cascading technique) kA rms 150 70 50 150 70 36 30 30 25 20 NSX250L NSX250H NSX250N NG125L NG125L NG125N NG125N C60N/H<=32A C60N/H<=32A C60N/H<=32A C60L<=25A C60L<=25A C60L<=25A Quick PRD 40/20/8 C60H>=40A C60H>=40A C60H>=40A C120N/H C120N/H C120N/H C60N>=40A C60N>=40A C60N>=40A H23 Fig. H48 : Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation Advantages of cascading The current limitation benefits all downstream circuits that are controlled by the current-limiting CB concerned. The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in an installation where the downstream circuits would otherwise be inadequately rated. The result is: b Simplified short-circuit current calculations b Simplification, i.e. a wider choice of downstream switchgear and appliances b The use of lighter-duty switchgear and appliances, with consequently lower cost b Economy of space requirements, since light-duty equipment have generally a smaller volume Principles of discriminative tripping (selectivity) Discrimination is achieved by automatic protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see Fig. H49). A B Isc 0 Total discrimination Ir B 0 Isc B Partial discrimination B only opens A and B open Ir B Is Isc Isc Isc B Is = discrimination limit Fig. H49 : Total and partial discrimination Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Discrimination may be total or partial, and based on the principles of current levels, or time-delays, or a combination of both. A more recent development is based on the logic techniques. The Schneider Electric system takes advantages of both current-limitation and discrimination 4 Circuit-breaker H - LV switchgear: functions & selection Discrimination between circuit-breakers A and B is total if the maximum value of short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting of circuit-breaker A (Im A). For this condition, B only will trip (see Fig. H50). Discrimination is partial if the maximum possible short-circuit current on circuit B exceeds the short-circuit trip-current setting of circuit-breaker A. For this maximum condition, both A and B will trip (see Fig. H51). Protection against overload : discrimination based on current levels (see Fig. H52a) This method is realized by setting successive tripping thresholds at stepped levels, from downstream relays (lower settings) towards the source (higher settings). Discrimination is total or partial, depending on particular conditions, as noted above. As a rule of thumb, discrimination is achieved when: b IrA/IrB > 2: t Protection against low level short-circuit currents : discrimination based on stepped time delays (see Fig. H52b) This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source. B In the two-level arrangement shown, upstream circuit-breaker A is delayed sufficiently to ensure total discrimination with B (for example: Masterpact with electronic trip unit). A H24 Discrimination based on a combination of the two previous methods (see Fig. H52c) A time-delay added to a current level scheme can improve the overall discrimination performance. I Ir B Ir A Isc B Im A Fig. H50 : Total discrimination between CBs A and B The upstream CB has two high-speed magnetic tripping thresholds: b Im A: delayed magnetic trip or short-delay electronic trip b Ii: instantaneous strip t Discrimination is total if Isc B < Ii (instantaneous). Protection against high level short-circuit currents: discrimination based on arc-energy levels This technology implemented in the Compact NSX range (current limiting circuitbreaker) is extremely effective for achievement of total discrimination. B Principle: When a very high level short-circuit current is detected by the two circuitsbreaker A and B, their contacts open simultaneously. As a result, the current is highly limited. b The very high arc-energy at level B induces the tripping of circuit-breaker B b Then, the arc-energy is limited at level A and is not sufficient to induce the tripping of A A I Ir B Im A Is cB Ir A B only opens Is c A As a rule of thumb, the discrimination between Compact NSX is total if the size ratio between A and B is greater than 2.5. A and B open Fig. H51 : Partial discrimination between CBs A and B a) t b) B c) t A t B B A A Isc B A ∆t I © Schneider Electric - all rights reserved Ir B Ir A B I Isc B Fig. H52 : Discrimination Schneider Electric - Electrical installation guide 2009 Im A Ii A delayed instantaneous I 4 Circuit-breaker H - LV switchgear: functions & selection Current-level discrimination This technique is directly linked to the staging of the Long Time (LT) tripping curves of two serial-connected circuit-breakers. t D2 D1 D1 D2 I Ir2 Ir1 Isd 2 Isd1 Fig. H53 : Current discrimination The discrimination limit ls is: b Is = Isd2 if the thresholds lsd1 and lsd2 are too close or merge, b Is = Isd1 if the thresholds lsd1 and lsd2 are sufficiently far apart. As a rule, current discrimination is achieved when: b Ir1 / Ir2 < 2, b Isd1 / Isd2 > 2. The discrimination limit is: b Is = Isd1. H25 Discrimination quality Discrimination is total if Is > Isc(D2), i.e. Isd1 > Isc(D2). This normally implies: b a relatively low level Isc(D2), b a large difference between the ratings of circuit-breakers D1 and D2. Current discrimination is normally used in final distribution. Discrimination based on time-delayed tripping uses CBs referred to as “selective” (in some countries). Implementation of these CBs is relatively simple and consists in delaying the instant of tripping of the several series-connected circuit-breakers in a stepped time sequence Time discrimination This is the extension of current discrimination and is obtained by staging over time of the tripping curves. This technique consists of giving a time delay of t to the Short Time (ST) tripping of D1. D2 D1 t D1 Δt I Ir2 Fig. H54 : Time discrimination Schneider Electric - Electrical installation guide 2009 Ir1 Isd 2 Isd1 Ii1 © Schneider Electric - all rights reserved D2 H - LV switchgear: functions & selection 4 Circuit-breaker The thresholds (Ir1, Isd1) of D1 and (Ir2, Isd2) comply with the staging rules of current discrimination. The discrimination limit ls of the association is at least equal to li1, the instantaneous threshold of D1. Masterpact NT06 630 A Compact NSX 250 A H26 Compact NSX 100 A Multi 9 C60 Discrimination quality There are two possible applications: b on final and/or intermediate feeders A category circuit-breakers can be used with time-delayed tripping of the upstream circuit-breaker. This allows extension of current discrimination up to the instantaneous threshold li1 of the upstream circuit-breaker: Is = li1. If Isc(D2) is not too high - case of a final feeder - total discrimination can be obtained. b on the incomers and feeders of the MSB At this level, as continuity of supply takes priority, the installation characteristics allow use of B category circuit-breakers designed for time-delayed tripping. These circuit-breakers have a high thermal withstand (Icw u 50% Icn for t = 1s): Is = Icw1. Even for high lsc(D2), time discrimination normally provides total discrimination: Icw1 > Icc(D2). Note: Use of B category circuit-breakers means that the installation must withstand high electrodynamic and thermal stresses. Consequently, these circuit-breakers have a high instantaneous threshold li that can be adjusted and disabled in order to protect the busbars if necessary. Practical example of discrimination at several levels with Schneider Electric circuit-breakers (with electronic trip units) "Masterpact NT is totally selective with any moulded-case Compact NSX circuit breaker, i.e., the downstream circuit-breaker will trip for any short-circuit value up to its breaking capacity. Further, all Compact NSX CBs are totally selective, as long as the ration between sizes is greater than 1.6 and the ratio between ratings is greater than 2.5. The same rules apply for the total selectivity with the miniature circuitbreakers Multi9 further downstream (see Fig. H55). t A B Non tripping time of A Current-breaking time for B Only B opens I Ir B Icc B Icc © Schneider Electric - all rights reserved Fig. H55 : 4 level discrimination with Schneider Electric circuit breakers : Masterpact NT Compact NSX and Multi 9 Schneider Electric - Electrical installation guide 2009 H - LV switchgear: functions & selection 4 Circuit-breaker Energy discrimination with current limitation Cascading between 2 devices is normally achieved by using the tripping of the upstream circuit-breaker A to help the downstream circuit-breaker B to break the current. The discrimination limit Is is consequently equal to the ultimate breaking current Icu B of circuit-breaker B acting alone, as cascading requires the tripping of both devices. The energy discrimination technology implemented in Compact NSX circuit-breakers allows to improve the discrimination limit to a value higher than the ultimate breaking current Icu B of the downstream circuit-breaker. The principle is as follows: b The downstream limiting circuit-breaker B sees a very high short-circuit current. The tripping is very fast (<1 ms) and then, the current is limited b The upstream circuit-breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit-breaker. So, the circuit-breaker A helps the circuit-breaker B to trip, without tripping itself. The discrimination limit can be higher than Icu B and the discrimination becomes total with a reduced cost of the devices Natural total discriminitation with Compact NSX The major advantage of the Compact NSX range is to provide a natural total discrimination between two series-connected devices if: b The ratio of the two trip-unit current ratings is > 1.6 b The ratio of rated currents of the two circuit-breakers is > 2.5 Discrimination schemes based on logic techniques are possible, using CBs equipped with electronic tripping units designed for the purpose (Compact, Masterpact) and interconnected with pilot wires Logic discrimination or “Zone Sequence Interlocking – ZSI” H27 This type of discrimination can be achieved with circuit-breakers equipped with specially designed electronic trip units (Compact, Masterpact): only the Short Time Protection (STP) and Ground Fault Protection (GFP) functions of the controlled devices are managed by Logic Discrimination. In particular, the Instantaneous Protection function - inherent protection function - is not concerned. Settings of controlled circuit-breakers b time delay: there are no rules, but staging (if any)of the time delays of time discrimination must be applied (∆tD1 u ∆tD2 u ∆tD3), b thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 u IcrD2 u IcrD3). Note: This technique ensures discrimination even with circuit-breakers of similar ratings. Principles Activation of the Logic Discrimination function is via transmission of information on the pilot wire: b ZSI input: pilot wire D1 v low level (no downstream faults): the Protection function is on standby with a reduced time delay (y 0,1 s), v high level (presence of downstream faults): the relevant Protection function moves to the time delay status set on the device. interlocking order D2 b ZSI output: v low level: the trip unit detects no faults and sends no orders, v high level: the trip unit detects a fault and sends an order. Fig. H56 : Logic discrimination. Operation A pilot wire connects in cascading form the protection devices of an installation (see Fig. H56). When a fault occurs, each circuit-breaker upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuitbreaker to its natural time delay (high level input). The circuitbreaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved D3 interlocking order 4 Circuit-breaker H - LV switchgear: functions & selection Discrimination quality This technique enables: b easy achievement as standard of discrimination on 3 levels or more, b elimination of important stresses on the installation, relating to timedelayed tripping of the protection device, in event of a fault directly on the upstream busbars. All the protection devices are thus virtually instantaneous, b easy achievement of downstream discrimination with non-controlled circuit-breakers. 4.6 Discrimination MV/LV in a consumer’s substation In general the transformer in a consumer’s substation is protected by MV fuses, suitably rated to match the transformer, in accordance with the principles laid down in IEC 60787 and IEC 60420, by following the advice of the fuse manufacturer. 63 A H28 The basic requirement is that a MV fuse will not operate for LV faults occurring downstream of the transformer LV circuit-breaker, so that the tripping characteristic curve of the latter must be to the left of that of the MV fuse pre-arcing curve. 1,250 kVA 20 kV / 400 V Full-load current 1,760 A 3-phase short-circuit current level 31.4 kA This requirement generally fixes the maximum settings for the LV circuit-breaker protection: b Maximum short-circuit current-level setting of the magnetic tripping element b Maximum time-delay allowable for the short-circuit current tripping element (see Fig. H57) b Short-circuit level at MV terminals of transformer: 250 MVA b Transformer MV/LV: 1,250 kVA 20/0.4 kV b MV fuses: 63 A b Cabling, transformer - LV circuit-breaker: 10 metres single-core cables b LV circuit-breaker: Compact NSX 2000 set at 1,800 A (Ir) What is the maximum short-circuit trip current setting and its maximum time delay allowable? Compact NS2000 set at 1,800 A Fig. H57 : Example t (s) 1,000 The curves of Figure H58 show that discrimination is assured if the short-time delay tripping unit of the CB is set at: b A level y 6 Ir = 10.8 kA b A time-delay setting of step 1 or 2 NS 2000 set at 1,800 A 200 100 Minimum pre-arcing curve for 63 A HV fuses (current referred to the secondary side of the transformer) 10 1 4 6 8 0.2 0.1 Step 4 Step 3 Step 2 0.50 Step 1 © Schneider Electric - all rights reserved 0.01 I 1,800 A Ir 10 kA Isc maxi 31.4 kA Fig. H58 : Curves of MV fuses and LV circuit-breaker Schneider Electric - Electrical installation guide 2009 Chapter J Protection against voltage surges in LV Contents 1 2 3 General J2 1.1 What is a voltage surge? J2 1.2 The four voltage surge types J2 1.3 Main characteristics of voltage surges J4 1.4 Different propagation modes J5 Overvoltage protection devices J6 2.1 Primary protection devices (protection of installations against lightning) J6 2.2 Secondary protection devices (protection of internal installations against lightning) J8 Protection against voltage surges in LV J11 3.1 Surge protective device description J11 3.2 Surge protective device standards J11 3.3 Surge protective device data according to IEC 61643-1 standard J11 J13 3.5 Surge arrester installation standards J13 Choosing a protection device J14 4.1 Protection devices according to the earthing system J14 4.2 Internal architecture of surge arresters J15 4.3 Coordination of surge arresters J16 4.4 Selection guide J17 4.5 Choice of disconnector J22 4.6 End-of-life indication of the surge arrester J23 4.7 Application example: supermarket J24 J1 © Schneider Electric - all rights reserved 4 3.4 Lightning protection standards Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 1 General 1.1 What is a voltage surge? A voltage surge is a voltage impulse or wave which is superposed on the rated network voltage (see Fig. J1). Voltage Lightning type impulse (duration = 100 µs) "Operating impulse" type dumped ring wave (F = 100 kHz to 1 MHz) Irms Fig. J1 : Voltage surge examples This type of voltage surge is characterised by ( see Fig. J2): b The rise time (tf) measured in μs b The gradient S measured in kV/μs J2 A voltage surge disturbs equipment and causes electromagnetic radiation. Furthermore, the duration of the voltage surge (T) causes a surge of energy in the electrical circuits which is likely to destroy the equipment. Voltage (V or kV) U max 50 % t Rise time (tf) Voltage surge duration (T) Fig. J2 : Main overvoltage characteristics © Schneider Electric - all rights reserved 1.2 The four voltage surge types There are four types of voltage surges which may disturb electrical installations and loads: b Atmospheric voltage surges b Operating voltage surges b Transient overvoltage at industrial frequency b Voltage surges caused by electrostatic discharge Atmospheric voltage surges Lightning risk – a few figures Between 2,000 and 5,000 storms are constantly forming around the earth. These storms are accompanied by lightning which constitutes a serious risk for both people and equipment. Strokes of lightning hit the ground at a rate of 30 to 100 strokes per second. Every year, the earth is struck by about 3 billion strokes of lightning. Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 1 General b Throughout the world, every year, thousands of people are struck by lightning and countless animals are killed b Lightning also causes a large number of fires, most of which break out on farms (destroying buildings or putting them out of use) b Lightning also affects transformers, electricity meters, household appliances, and all electrical and electronic installations in the residential sector and in industry. b Tall buildings are the ones most often struck by lightning b The cost of repairing damage caused by lightning is very high b It is difficult to evaluate the consequences of disturbance caused to computer or telecommunications networks, faults in PLC cycles and faults in regulation systems. Furthermore, the losses caused by a machine being put out of use can have financial consequences rising above the cost of the equipment destroyed by the lightning. Characteristics of lightning discharge Figure J3 shows the values given by the lighting protection committee (Technical Committee 81) of the I.E.C. As can be seen, 50 % of lightning strokes are of a force greater than 33 kA and 5 % are greater than 85 kA. The energy forces involved are thus very high. Beyond peak probability P% 95 50 5 Current peak I (kA) 7 33 85 Gradient S (kA/μs) 9.1 24 65 Total duration T (s) 0.001 0.01 1.1 Number of discharges n 1 2 6 Fig. J3 : Lightning discharge values given by the IEC lightning protection committee J3 It is important to define the probability of adequate protection when protecting a site. Furthermore, a lightning current is a high frequency (HF) impulse current reaching roughly a megahertz. Lightning comes from the discharge of electrical charges accumulated in the cumulo-nimbus clouds which form a capacitor with the ground. Storm phenomena cause serious damage. Lightning is a high frequency electrical phenomenon which produces voltage surges on all conductive elements, and especially on electrical loads and wires. The effects of lightning A lightning current is therefore a high frequency electrical current. As well as considerable induction and voltage surge effects, it causes the same effects as any other low frequency current on a conductor: b Thermal effects: fusion at the lightning impact points and joule effect, due to the circulation of the current, causing fires b Electrodynamic effects: when the lightning currents circulate in parallel conductors, they provoke attraction or repulsion forces between the wires, causing breaks or mechanical deformations (crushed or flattened wires) b Combustion effects: lightning can cause the air to expand and create overpressure which stretches over a distance of a dozen metres or so. A blast effect breaks windows or partitions and can project animals or people several metres away from their original position. This shock wave is at the same time transformed into a sound wave: thunder b Voltage surges conducted after an impact on overhead electrical or telephone lines b Voltage surges induced by the electromagnetic radiation effect of the lightning channel which acts as an antenna over several kilometres and is crossed by a considerable impulse current b The elevation of the earth potential by the circulation of the lightning current in the ground. This explains indirect strokes of lightning by step voltage and the breakdown of equipment A sudden change in the established operating conditions in an electrical network causes transient phenomena to occur. These are generally high frequency or damped oscillation voltage surge waves (see Fig. J1). They are said to have a slow gradient: their frequency varies from several ten to several hundred kilohertz. Operating voltage surges may be created by: b The opening of protection devices (fuse, circuit-breaker), and the opening or closing of control devices (relays, contactors, etc.) b Inductive circuits due to motors starting and stopping, or the opening of transformers such as MV/LV substations b Capacitive circuits due to the connection of capacitor banks to the network b All devices that contain a coil, a capacitor or a transformer at the power supply inlet: relays, contactors, television sets, printers, computers, electric ovens, filters, etc. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Operating voltage surges J - Protection against voltage surges in LV 1 General Transient overvoltages at industrial frequency (see Fig. J4) These overvoltages have the same frequency as the network (50, 60 or 400 Hz); and can be caused by: b Phase/frame or phase/earth insulating faults on a network with an insulated or impedant neutral, or by the breakdown of the neutral conductor. When this happens, single phase devices will be supplied in 400 V instead of 230 V. b A cable breakdown. For example, a medium voltage cable which falls on a low voltage line. b The arcing of a high or medium voltage protective spark-gap causing a rise in earth potential during the action of the protection devices. These protection devices follow automatic switching cycles which will recreate a fault if it persists. t Normal voltage 230/400 V Transient overvoltage Normal voltage 230/400 V Fig. J4 : Transient overvoltage at industrial frequency J4 Voltage surges caused by electrical discharge In a dry environment, electrical charges accumulate and create a very strong electrostatic field. For example, a person walking on carpet with insulating soles will become electrically charged to a voltage of several kilovolts. If the person walks close to a conductive structure, he will give off an electrical discharge of several amperes in a very short rise time of a few nanoseconds. If the structure contains sensitive electronics, a computer for example, its components or circuit boards may be damaged. Three points must be kept in mind: b A direct or indirect lightning stroke may have destructive consequences on electrical installations several kilometres away from where it falls b Industrial or operating voltage surges also cause considerable damage b The fact that a site installation is underground in no way protects it although it does limit the risk of a direct strike 1.3 Main characteristics of voltage surges Figure J5 below sums up the main characteristics of voltage surges. Type of voltage surge Voltage surge coefficient Duration Front gradient or frequency Industrial frequency (insulation fault) Operation y 1.7 2 to 4 Industrial frequency (50-60-400 Hz) Average 1 to 200 kHz Atmospheric >4 Long 30 to 1,000 ms Short 1 to 100 ms Very short 1 to 100 μs Very high 1 to 1,000 kV/μs © Schneider Electric - all rights reserved Fig. J5 : Main characteristics of voltage surges Schneider Electric - Electrical installation guide 2009 1 General 1.4 Different propagation modes Common mode Common mode voltage surges occur between the live parts and the earth: phase/earth or neutral/earth (see Fig. J6). They are especially dangerous for devices whose frame is earthed due to the risk of dielectric breakdown. Ph Equipment Imc N Voltage surge common mode Imc Fig. J6 : Common mode Differential mode Differential mode voltage surges circulate between live conductors: Phase to phase or phase to neutral (see Fig. J7). They are especially dangerous for electronic equipment, sensitive computer equipment, etc. Imd Ph N J5 U voltage surge differential mode Equipment Imd Fig. J7 : Differential mode © Schneider Electric - all rights reserved J - Protection against voltage surges in LV Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 2 Overvoltage protection devices Two major types of protection devices are used to suppress or limit voltage surges: they are referred to as primary protection devices and secondary protection devices. 2.1 Primary protection devices (protection of installations against lightning) The purpose of primary protection devices is to protect installations against direct strokes of lightning. They catch and run the lightning current into the ground. The principle is based on a protection area determined by a structure which is higher than the rest. The same applies to any peak effect produced by a pole, building or very high metallic structure. There are three types of primary protection: b Lightning conductors, which are the oldest and best known lightning protection device b Overhead earth wires b The meshed cage or Faraday cage The lightning conductor The lightning conductor is a tapered rod placed on top of the building. It is earthed by one or more conductors (often copper strips) (see Fig. J8). J6 Copper strip down conductor © Schneider Electric - all rights reserved Test clamp Crow-foot earthing Fig. J8 : Example of protection using a lightning conductor Schneider Electric - Electrical installation guide 2009 2 Overvoltage protection devices The design and installation of a lightning conductor is the job of a specialist. Attention must be paid to the copper strip paths, the test clamps, the crow-foot earthing to help high frequency lightning currents run to the ground, and the distances in relation to the wiring system (gas, water, etc.). Furthermore, the flow of the lightning current to the ground will induce voltage surges, by electromagnetic radiation, in the electrical circuits and buildings to be protected. These may reach several dozen kilovolts. It is therefore necessary to symmetrically split the down conductor currents in two, four or more, in order to minimise electromagnetic effects. Overhead earth wires These wires are stretched over the structure to be protected (see Fig. J9). They are used for special structures: rocket launch pads, military applications and lightning protection cables for overhead high voltage power lines (see Fig. J10). Tin plated copper 25 mm 2 Metal post d > 0.1 h h J7 Frame grounded earth belt Fig. J9 : Example of lightning protection using overhead earth wires i i/2 i/2 Lightning protection cables Fig. J10 : Lightning protection wires Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved J - Protection against voltage surges in LV 2 Overvoltage protection devices J - Protection against voltage surges in LV Primary lightning conductor protection devices such as a meshed cage or overhead earth wires are used to protect against direct strokes of lighting.These protection devices do not prevent destructive secondary effects on equipment from occurring. For example, rises in earth potential and electromagnetic induction which are due to currents flowing to the earth. To reduce secondary effects, LV surge arresters must be added on telephone and electrical power networks. The meshed cage (Faraday cage) This principle is used for very sensitive buildings housing computer or integrated circuit production equipment. It consists in symmetrically multiplying the number of down strips outside the building. Horizontal links are added if the building is high; for example every two floors (see Fig. J11). The down conductors are earthed by frog’s foot earthing connections. The result is a series of interconnected 15 x 15 m or 10 x 10 m meshes. This produces better equipotential bonding of the building and splits lightning currents, thus greatly reducing electromagnetic fields and induction. J8 Fig. J11 : Example of protection using the meshed cage (Faraday cage) principle Secondary protection devices are classed in two categories: Serial protection and parallel protection devices. Serial protection devices are specific to a system or application. Parallel protection devices are used for: Power supply network, telephone network, switching network (bus). 2.2 Secondary protection devices (protection of internal installations against lightning) These handle the effects of atmospheric, operating or industrial frequency voltage surges. They can be classified according to the way they are connected in an installation: serial or parallel protection. Serial protection device This is connected in series to the power supply wires of the system to be protected (see Fig. J12). Power supply Installation to be protected Serial protection © Schneider Electric - all rights reserved Up Fig. J12 : Serial protection principle Transformers They reduce voltage surges by inductor effect and make certain harmonics disappear by coupling. This protection is not very effective. Filters Based on components such as resistors, inductance coils and capacitors they are suitable for voltage surges caused by industrial and operation disturbance corresponding to a clearly defined frequency band. This protection device is not suitable for atmospheric disturbance. Schneider Electric - Electrical installation guide 2009 2 Overvoltage protection devices Wave absorbers They are essentially made up of air inductance coils which limit the voltage surges, and surge arresters which absorb the currents. They are extremely suitable for protecting sensitive electronic and computing equipment. They only act against voltage surges. They are nonetheless extremely cumbersome and expensive. Network conditioners and static uninterrupted power supplies (UPS) These devices are essentially used to protect highly sensitive equipment, such as computer equipment, which requires a high quality electrical power supply. They can be used to regulate the voltage and frequency, stop interference and ensure a continuous electrical power supply even in the event of a mains power failure (for the UPS). On the other hand, they are not protected against large, atmospheric type voltage surges against which it is still necessary to use surge arresters. Parallel protection device The principle The parallel protection is adapted to any installation power level (see Fig. J13). This type of overvoltage protection is the most commonly used. Power supply Installation to be protected Parallel protection Up J9 Fig. J13 : Parallel protection principle Main characteristics b The rated voltage of the protection device must correspond to the network voltage at the installation terminals b When there is no voltage surge, a leakage current should not go through the protection device which is on standby b When a voltage surge above the allowable voltage threshold of the installation to be protected occurs, the protection device abruptly conducts the voltage surge current to the earth by limiting the voltage to the desired protection level Up (see Fig. J14). U (V) Up 0 I (A) Fig. J14 : Typical U/I curve of the ideal protection device When the voltage surge disappears, the protection device stops conducting and returns to standby without a holding current. This is the ideal U/I characteristic curve: b The protection device response time (tr) must be as short as possible to protect the installation as quickly as possible b The protection device must have the capacity to be able to conduct the energy caused by the foreseeable voltage surge on the site to be protected b The surge arrester protection device must be able to withstand the rated current In. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved J - Protection against voltage surges in LV J - Protection against voltage surges in LV 2 Overvoltage protection devices The products used b Voltage limiters They are used in MV/LV substations at the transformer output, in IT earthing scheme. They can run voltage surges to the earth, especially industrial frequency surges (see Fig. J15) MV/LV Overvoltage limiter PIM Permanent insulation monitor Fig. J15 : Voltage limiter © Schneider Electric - all rights reserved J10 b LV surge arresters This term designates very different devices as far as technology and use are concerned. Low voltage surge arresters come in the form of modules to be installed inside LV switchboard. There are also plug-in types and those that protect power outlets. They ensure secondary protection of nearby elements but have a small flow capacity. Some are even built into loads although they cannot protect against strong voltage surges b Low current surge arresters or overvoltage protectors These protect telephone or switching networks against voltage surges from the outside (lightning), as well as from the inside (polluting equipment, switchgear switching, etc.) Low current voltage surge arresters are also installed in distribution boxes or built into loads. Schneider Electric - Electrical installation guide 2009 3 Protection against voltage surges in LV 3.1 Surge protective device description A surge protective device (SDP) is a device that limits transient voltage surges and runs current waves to ground to limit the amplitude of the voltage surge to a safe level for electrical installations and equipment. The surge protective device includes one or several non linear components. The surge protective device eliminates voltage surges: b In common mode: Phase to earth or neutral to earth b In differential mode: Phase to phase or phase to neutral When a voltage surge exceeds the Uc threshold, the surge protective device (SDP) conducts the energy to earth in common mode. In differential mode the diverted energy is directed to another active conductor. The surge protective device has an internal thermal protection device which protects against burnout at its end of life. Gradually, over normal use after withstanding several voltage surges, the Surge Protective Device degrades into a conductive device. An indicator informs the user when end-of-life is close. Some surge protective devices have a remote indication. In addition, protection against short-circuits is ensured by an external circuit-breaker. 3.2 Surge protective device standards International standard IEC 61643-1 ed. 02/2005 Surge protective devices connected to low-voltage power distribution systems. Three test classes are defined: b Class I tests: They are conducted using nominal discharge current (In), voltage impulse with 1.2/50 μs waveshape and impulse current Iimp. The class I tests is intended to simulate partial conducted lightning current impulses. SPDs subjected to class I test methods are generally recommended for locations at points of high exposure, e.g., line entrances to buildings protected by lightning protection systems. b Class II tests: They are conducted using nominal discharge current (In), voltage impulse with 1.2/50 μs waveshape b Class III tests: They are conducted using the combination waveform (1.2/50 and 8/20 μs). SPDs tested to class II or III test methods are subjected to impulses of shorter duration. These SPDs are generally recommended for locations with lesser exposure. These 3 test classes cannot be compared, since each originates in a country and each has its own specificities. Moreover, each builder can refer to one of the 3 test classes. J11 European standard EN 61643-11 2002 Some requirements as per IEC 61643-1. Moreover SPDs are classified in three categories: Type 1: SPD tested to Class I Type 2: SPD tested to Class II Type 3: SPD tested to Class III 3.3 Surge protective device data according to IEC 61643-1 standard b Surge protective device (SPD): A device that is intended to limit transient overvoltages and divert surge currents. It contains at least one nonlinear component. b Test classes: Surge arrester test classification. b In: Nominal discharge current; the crest value of the current through the SPD having a current waveshape of 8/20. This is used for the classification of the SPD for the class II test and also for preconditioning of the SPD for class I and II tests. b Imax: Maximum discharge current for class II test; crest value of a current through the SPD having an 8/20 waveshape and magnitude according to the test sequence of the class II operating duty test. Imax is greater than In. b Ic: Continuous operating current; current that flows in an SPD when supplied at its permament full withstand operating voltage (Uc) for each mode. Ic corresponds to the sum of the currents that flow in the SPD’s protection component and in all the internal circuits connected in parallel. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved J - Protection against voltage surges in LV J - Protection against voltage surges in LV 3 Protection against voltage surges in LV b Iimp: Impulse current, it is defined by a current peak value Ipeak and the charge Q. Tested according to the test sequence of the operating duty test. This is used for the classification of the SPD for class I test. b Un: Rated network voltage. b Uc: Maximum continuous operating voltage; the maximum r.m.s. or d.c. voltage which may be continuously applied to the SPDs mode of protection. This is equal to the rated voltage. b Up: Voltage protection level; a parameter that characterizes the performance of the SPD in limiting the voltage across its terminals, which is selected from a list of preferred values. This value shall be greater than the highest value of the measured limiting voltages. The most common values for a 230/400 V network are: 1 kV - 1.2 kV - 1.5 kV - 1.8 kV - 2 kV - 2.5 kV. b Ures: Residual voltage, the peak value of the voltage that appears between the terminals of an SPD due to the passage of discharge current. The SPD is characterised by Uc, Up, In and Imax (see Fig. J16) b To test the surge arrester, standardized voltage and current waves have been defined that are specific to each country: v Voltage wave e.g. 1.2/50 μs (see Fig. J17) v Current wave Example 8/20 μs (see Fig. J18) U J12 Up Uc I In < 1 mA Imax Fig. J16 : Voltage/current characteristics I V Maxi 100 % Maxi 100 % 50 % 50 % t t 1,2 8 50 Fig. J17 : 1.2/50 μs wave Fig. J18 : 8/20 μs wave 20 © Schneider Electric - all rights reserved v Other possible wave characteristics: 4/10 μs, 10/1000 μs, 30/60 μs, 10/350 μs... Comparison between different surge protective devices must be carried out using the same wave characteristics, in order to get relevant results. Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 3 Protection against voltage surges in LV 3.4 Lightning protection standards The IEC 62305 series (part 1 to 5) restructures and updates the publications of IEC 61024 series, IEC 61312 series and IEC 61663 series. The need for protection, the economic benefits of installing protection measures and the selection of adequate protection measures should be determined in terms of risk management. Risk management is the subject of IEC 62305-2. The criteria for design, installation and maintenance of lightning protection measures are considered in three separate groups: b The first group concerning protection measures to reduce physical damage and life hazard in a structure is given in IEC 62305-3. b The second group concerning protection measures to reduce failures of electrical and electronic systems in a structure is given in IEC 62305-4. b The third group concerning protection measures to reduce physical damage and failures of services connected to a structure (mainly electrical and telecommunication lines) is given in IEC 62305-5. 3.5 Surge arrester installation standards b International: IEC 61643-12 selection and application principles b International: IEC 60364 Electrical installations of buildings v IEC 60364-4-443: protection for safety When an installation is supplied by, or includes, an overhead line, a protection device against atmospheric overvoltages must be foreseen if the keraunic level of the site being considered corresponds to the external influences condition AQ 1 (more than 25 days per year with thunderstorms). v IEC 60364-4-443-4: selection of equipment in the installation. This section helps with the choice of the protection level Up for the surge arrester in function of the loads to be protected. Rated residual voltage of protection devices must not be higher than the value in the voltage impulse withstand category II (see Fig. J19): Nominal voltage of the installation(1) V Three-phase Single-phase systems(2) systems with middle point 230/400(2) 277/480(2) 400/690 1,000 120-240 - Required impulse withstand voltage for kV Equipment at Equipment of Appliances the origin of distribution and the installation final circuits (impulse (impulse (impulse withstand withstand withstand category IV) category III) category II) 4 2.5 1.5 6 4 2.5 - 8 6 4 Values subject to system engineers J13 Specially protected equipment (impulse withstand category I) 0.8 1.5 2.5 (1) According to IEC 60038 (2) In Canada and USA for voltages to earth higher than 300 V, the impulse withstand voltage corresponding to the next higher voltage in column one applies. Category I is addressed to particular equipment engineering. Category II is addressed to product committees for equipment for connection to the mains. Category III is addressed to product committees of installation material and some special product committees. Category IV is addressed to supply authorities and system engineers (see also 443.2.2). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. J19 : Choosing equipment for the installation according to IEC 60364 J - Protection against voltage surges in LV 3 Protection against voltage surges in LV v IEC 60364-5-534: choosing and implementing electrical equipment This section describes surge arrester installation conditions: - According to earthing systems: The maximum continuous operating voltage Uc of SPDs shall be equal to or higher than shown in Fig. J20. SPDs connected between System configuration of distribution network TT TN-C TN-S Line conductor and neutral conductor 1.1 Uo NA 1.1 Uo 1.1 Uo NA Each line conductor and PE conductor 1.1 Uo NA 1.1 Uo 3Uo(1) Line-to-line voltage (1) Uo(1) NA Uo(1) Uo(1) NA NA 1.1 Uo NA NA NA Neutral conductor and PE conductor Each line conductor and PEN conductor IT with IT without distributed distributed neutral neutral NA: not applicable NOTE 1: Uo is the line-to-neutral voltage of the low-voltage system. NOTE 2: This table is based on IEC 61643-1 amendment 1. Fig. J20 : Minimum required Uc of the SPD dependent on supply system configuration - At the origin of the installation: if the surge arrester is installed at the source of an electrical installation supplied by the utility distribution network, its rated discharge current may be lower than 5 kA. If a surge arrester is installed downstream from an earth leakage protection device, an RCD of the s type, with immunity to impulse currents of less than 3 kA (8/20 μs), must be used. - Protection against overcurrent at 50 Hz and consequences of a SPD failure: protection against SPDs short-circuits is provided by the overcurrent protective devices F2 which are to be selected according to the maximum recommended rating for the overcurrent protective device given in the manufacturer's SPD instructions. - In the presence of lightning conductors: a surge arrester must be installed, additional specifications for surge arresters must be applied (see IEC 62305 part 4). © Schneider Electric - all rights reserved J14 (1) These values are related to worst case fault conditions, therefore the tolerance of 10 % is not taken into account Schneider Electric - Electrical installation guide 2009 4 Choosing a protection device When installing surge arresters, several elements must be considered, such as: b Cascading b Positioning with respect to residual current devices b The choice of disconnection circuit breakers The earthing system must also be taken into account. 4.1 Protection devices according to the earthing system b Common mode overvoltage: basic protection involves the installation of a common mode surge arrester between phase and PE or phase and PEN, whatever type of earthing system is used. b Differential mode overvoltage: in the TT and TN-S earthing systems, earthing the neutral leads to dissymmetry due to earthing impedances, which causes differential mode voltages to appear, whereas the overvoltage induced by a lightning strike is a common mode voltage. For example, let us consider a TT earthing system. A two-pole surge arrester is installed in common mode to protect the installation (see Fig. J21). I I I J15 I Fig. J21 : Common mode protection only The neutral earthing resistor R1 used for the pylons has a lower resistance than the earthing resistor R2 used for the installation. The lightning current will flow through circuit ABCD to earth via the easiest path. It will pass through varistors V1 and V2 in series, causing a differential voltage equal to twice the residual voltage of the surge arrester (Up1 + Up2) to appear at the terminals of A and C at the entrance to the installation in extreme cases. To protect the loads between Ph and N effectively, the differential mode voltage (between A and C) must be reduced. Another earthing system is therefore used (see Fig. J22). The lightning current flows through circuit ABH which has a lower impedance than circuit ABCD, as the impedance of the component used between B and H is null (gas filled spark gap). In this case, the differential voltage is equal to the residual voltage of the surge arrester (Up2). I I I Fig. J22 : Common + differentiel mode protection Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved J - Protection against voltage surges in LV J - Protection against voltage surges in LV 4 Choosing a protection device Between TT TN-S TN-C IT Differential Mode phase and neutral yes yes - - Common phase and earth yes yes yes yes phase and earth yes yes - yes (if distributed neutral) Fig. J23 : Connections to be made according to the earthing systems used, in the case of atmospheric overvoltages 4.2 Internal architecture of surge arresters b 2P, 3P, 4P surge arresters (see Fig. J24): v They provide protection against common-mode overvoltages only v They are appropriate for TN-C and IT earthing systems. J16 Fig. J24 : 2P, 3P, 4P surge arresters b 1P+N, 3P+N surge arresters (see Fig. J25): v They provide protection against common-mode and differential-mode overvoltages v They are appropriate for TT, TN-S, and IT earthing systems. Fig. J25 : 1P+N, 3P+N surge arresters © Schneider Electric - all rights reserved PE Earthing conductor Main earth terminal Fig. J26 : Connection example b Single-pole (1P) surge arresters (see Fig. J26): v They are used to satisfy the demand of different assemblies (according to the manufacturer’s instructions) by supplying only one product. However, special dimensioning will be required for N - PE protection (for example 1+N and 3P+N) v The assembly must be validated by means of the tests specified in EN 61643-11. Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 4 Choosing a protection device Cascading protection requires a minimum distance of at least 10 m between the two protection devices. This is valid, whatever the field of application: domestic, tertiary or industrial. 4.3 Coordination of surge arresters The overvoltage protection study of an installation may show that the site is highly exposed and that the equipment to be protected is sensitive. The surge arrester must be able to discharge high currents and have a low level of protection. This dual constraint cannot always be handled by a single surge arrester. A second one will therefore be required (see Fig. J27). The first device, P1 (incoming protection) will be placed at the incoming end of the installation. Its purpose will be to discharge the maximum amount of energy to earth with a level of protection y 2000 V that can be withstood by the electrotechnical equipment (contactors, motors, etc.). The second device (fine protection) will be placed in a distribution enclosure, as close as possible to the sensitive loads. It will have a low discharge capacity and a low level of protection that will limit overvoltages significantly and therefore protect sensitive loads (y 1500 V). I Fig. J27 : Cascading of surge arresters I I J17 Fig. J28 : Coordination of surge arresters The fine-protection device P2 is installed in parallel with the incoming protection device P1. If the distance L is too small, at the incoming overvoltage, P2 with a protection level of U2 = 1500 V will operate before P1 with a level of U1 = 2000 V. P2 will not withstand an excessively high current. The protection devices must therefore be coordinated to ensure that P1 activates before P2. To do this, we shall experiment with the length L of the cable, i.e. the value of the self-inductance between the two protection devices. This self-inductance will block the current flow to P2 and cause a certain delay, which will force P1 to operate before P2. A metre of cable gives a selfinductance of approximately 1µH. Ldi causes a voltage drop of approximately 100 V/m/kA, 8/20 µs The rule ΔU= dt wave. For L = 10 m, we get UL1 = UL2 ≈ 1000 V. To ensure that P2 operates with a level of protection of 1500 V requires U1 = UL1 + UL2 + U2 = 1000 + 1000 + 1500 V = 3500 V. Consequently, P1 operates before 2000 V and therefore protects P2. Note: if the distance between the surge arrester at the incoming end of the installation and the equipment to be protected exceeds 30 m, cascading the surge arresters is recommended, as the residual voltage of the surge arrester may rise to double the residual voltage at the terminals of the incoming surge arrester; as in the above example, the fine protection surge arrester must be placed as close as possible to the loads to be protected. © Schneider Electric - all rights reserved Installation rules (see page Q12). Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 4 Choosing a protection device 4.4 Selection guide 1 Estimate the value of the equipment to be protected To estimate its value, consider: b The cost of the equipment in financial terms b The economic impact if the equipment goes down. b Domestic equipment: v audio-video, computers v household appliances v burglar alarm. J18 b Sensitive equipment: v burglar alarm v fire alarm v access control v video surveillance. b Building equipment: v automated heating or b Professional equipment: v programmable machine v computer server v sound or light control system. b Heavy equipment: v medical infrastructure v production infrastructure v heavy computer processing. air-conditioning v lift. 2 Determine the electrical architecture of buildings 3 Understand the risk of the impact of lightning on the site Lightning protection can be calculated for an entire building or for part of a building that is electrically independent Depending on the size of the building and the extent of its electrical system, one or more surge arresters must be used in the various switchboards in the installation. b Detached house. b Apartment, small semi-detached house. b Communal part of a building. b Professional premises. b Tertiary and industrial buildings: v single switchboard, main switchboard v distribution board v sensitive equipment more than 30 m from the switchboard. Lightning is attracted by high points that conduct electricity. They can be: b Natural: tall trees, mountain crest, wet areas, ferrous soil b Artificial: chimney, aerial, pylon, lightning conductor. Indirect effects can be incurred within a fifty metre radius around the point of impact. Location of the building In an area where there is a particular hazard (pylon, tree, mountainous region, mountain crest, wet area or pond). In flat open country. In an exceptionally exposed area (lightning conductor on a building less than 50 metres away). © Schneider Electric - all rights reserved In an urban, peri-urban, grouped housing area. Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 1 Equipment to be protected 4 Choosing a protection device Domestic equipment Audio-video, computers, household appliances, burglar alarm, etc. 2 Determine the architecture of the building Apartment, small semi-detached house Detached house, Professional premises Communal part of a building J19 3 Risk level of the impact of a lightning strike Choice of type of surge arrester Type 1 25 kA Type 2 Type 2 + 10 kA 40 kA Type 2 40 kA Type 1 25 kA + Type 2 40 kA Type 1 25 kA Type 2 Type 2 + 40 kA 65 kA Type 2 40 kA Type 2 10 kA Note: Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level of Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and and Type 1 25 kA + Type 2 40 kA . . Lightning also propagates through telecommunications networks. It can damage all the equipment connected to these networks. Protection of telecommunications equipment Choice of surge arresters Analogue telephone networks < 200 V Schneider Electric - Electrical installation guide 2009 PRC b © Schneider Electric - all rights reserved Fig. J32 : Domestic equipment J - Protection against voltage surges in LV 1 4 Choosing a protection device Sensitive equipment: Equipment to be protected Building equipment: Burglar alarm, fire alarm, access control, video-surveillance, etc. Automated heating or air-conditioning, lift, etc. 2 Single switchboard, main switchboard Determine the architecture of the building J20 Distribution board Dedicated protection, more than 30 m from a switchboard 3 Risk level of the impact of a lightning strike Choice of type of surge arrester Type 1 25 kA or Type 2 Type 2 Type 2 35 kA 20 kA 40 kA 40 kA + Type 2 40 kA Type 2 20 kA Type 2 8 kA Note: Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level of Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and © Schneider Electric - all rights reserved Fig. J33 : Sensitive equipment, Building equipment Schneider Electric - Electrical installation guide 2009 . and . J - Protection against voltage surges in LV 1 4 Choosing a protection device Professional equipment Equipment to be protected Programmable machine, server, sound or light control system, etc. 2 Single switchboard, main switchboard Determine the architecture of the building Distribution board Dedicated protection, more than 30 m from a switchboard J21 3 Risk level of the impact of a lightning strike Choice of type of surge arrester Type 1 25 kA or Type 2 Type 2 Type 2 35 kA 40 kA 65 kA 65 kA + Type 2 40 kA Type 2 20 kA Type 2 8 kA Note: Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level of Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and and . . © Schneider Electric - all rights reserved Fig. J34 : Professional equipment Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 1 4 Choosing a protection device Heavy equipment Equipment to be protected Medical, production, or heavy computer processing infrastructure, etc. 2 Single switchboard, main switchboard Determine the architecture of the building J22 Distribution board Dedicated protection, more than 30 m from a switchboard 3 Risk level of the impact of a lightning strike Choice of type of surge arrester Type 1 25 kA Type 2 + 65 kA Type 2 40 kA Type 1 25 kA or 35 kA + Type 2 40 kA Type 1 25 kA or 35 kA + Type 2 40 kA Type 2 20 KA Type 2 8 kA Note: Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level of Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and and . . © Schneider Electric - all rights reserved Fig. J35 : Heavy equipment Lightning can also propagate through telecommunications and computer networks. It can damage all the equipment connected to these networks: telephones, modems, computers, servers, etc. Protection of telecommunications and computer equipment Choice of surge arresters Analogue telephone networks < 200 V PRC PRI b Digital networks, analogue lines < 48 V b Digital networks, analogue lines < 6 V VLV load supply < 48 V b Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 4 Choosing a protection device 4.5 Choice of disconnector The disconnector is necessary to ensure the safety of the installation b One of the surge arrester parameters is the maximum current (Imax 8/20 µs wave) that it can withstand without degradation. If this current is exceeded, the surge arrester will be destroyed; it will be permanently short circuited and it is essential to replace it. The fault current must therefore be eliminated by an external disconnector installed upstream. The disconnector provides the complete protection required by a surge arrester installation, i.e.: v It must be able to withstand standard test waves: - it must not trip at 20 impulses at In - it can trip at Imax without being destroyed v the surge arrester disconnects if it short-circuits. b The ready-to-cable surge arresters with an integrated disconnection circuit breaker are: v Combi PRF1 v Quick PF v Quick PRD. Surge arrester / disconnection circuit breaker correspondence table Type 1 Surge arrester names 6 kA Isc Imax or Iimp PRF1 Master 35 kA(1) PRD1 Master 25 kA(1) 36 kA 50 kA Compact NSX160B 160A Compact NSX160F 160A Compact NSX160N 160A NG 125 N C 80A NG 125L C 80A PRD1 25r NG 125 N C 80A NG 125L C 80A PRF1 D125 D curve Combi PRF1 15 kA 25 kA NG 125 N C 80A PF 65/ PRD 65r 65 kA(2) C60N 50A C curve C60H 50A C curve NG125L 50A C curve Fuse NH 50A gL/gG PF 40 / PRD 40r 40 kA(2) C60N 40A C curve C60H 40A C curve NG125L 40A C curve Fuse 22x58 40A gL/gG NG 125L C 80A Integrated 20 kA(2) Quick PF 10 10 kA(2) PF 8/ PRD 8r 8 kA(2) Quick PRD 20r Quick PRD 8 r 100 kA Integrated 12,5 kA(1) PF 20/ PRD 20r 70 kA J23 PRF1 12,5 r Quick PRD 40r Type 2 10 kA Contact us C60N 25A C curve C60H 25A C curve NG125L 25A C curve Integrated Fuse 22x58 25A gL/gG Contact us Integrated C60N 20A C curve C60H 20A C curve NG125L 20A C curve Integrated Contact us Isc: prospective short-circuit current at the point of installation. (1) Iimp. (2) Imax. Fig. J36 : Coordination table between SPD and its disconnector Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Types J - Protection against voltage surges in LV 4 Choosing a protection device 4.6 End-of-life indication of the surge arrester Various indication devices are provided to warn the user that the loads are no longer protected against atmospheric overvoltages. Type 1 surge arresters (with gas filled spark gap) PRF1 1P 260 V, Combi 1P+N and 3P+N and PRF1 Master These surge arresters have a light indicating that the module is in good working order. This indicator light requires a minimum operating voltage of 120 V AC. b The light does not come on: v if the operating voltage is y 120 V AC v if there is no network voltage v if the spark-over electronics are defective. Type 2 surge arresters (varistor, varistor + gas filled spark gap) PF, PRD At end of life, the surge arrester or the cartridge are destroyed. b This can occur in two ways: v internal end-of-life disconnection: the accumulated electric shocks cause the varistors to age, resulting in an increase in leakage current. Above 1 mA, a thermal runaway occurs and the surge arrester disconnects. v external end-of-life disconnection: this occurs in the event of an excessive overvoltage (direct lightning strike on the line); above the discharge capacity of the surge arrester, the varistor(s) are dead short-circuited to earth (or possibly between phase and neutral). This short-circuit is eliminated when the mandatory associated disconnection circuit breaker opens. Quick PRD and Quick PF Whatever the hazards of the power supply network, Quick PRD and Quick PF incorporate a perfectly coordinated disconnector. b In the event of lightning strikes < Imax: like all surge arresters, they have internal anti-ageing protection. b In the event of a lightning strike > Imax: Quick PRD and Quick PF are selfprotected by their integrated disconnector. b In the event of neutral disconnection or phase-neutral reversal occurring on the power supply: Quick PRD and Quick PF are self-protected by their integrated disconnector. To simplify maintenance work, Quick PRD is fitted with local indicators and draw-out cartridges that are mechanically combined with the disconnector. J24 Fig. J37 : Example of indication for PRD Quick PRD has indicator lights on the cartridges and on the integrated disconnector, so that the work to be carried out can quickly be located. For safety reasons, the disconnector opens automatically when a cartridge is removed. It cannot be set until the cartridge is plugged in. When changing the cartridge, a phase/neutral failsafe system ensures that it can be plugged in safely. Operating state continuous display Quick PRD has an integrated reporting contact to send information about the operating state of the surge arrester from a remote location. Monitoring the surge arresters installed throughout the installation makes it possible to be continuously aware of their operating state and to ensure that the protection devices are always in good working order. b A reporting contact gives the alert: v at end of life of a cartridge v if a cartridge is missing, as soon as it has been removed v if a fault occurs on the line (short-circuit, neutral disconnection, phase-neutral reversal) v in the event of local manual operation (handle down). © Schneider Electric - all rights reserved Fig. J39 : Example of indication for Quick PRD Quick PF has an optional indication reporting auxiliary (SR) that sends information about the operating state of the surge arrester from a remote location. Schneider Electric - Electrical installation guide 2009 J - Protection against voltage surges in LV 4 Choosing a protection device MV/LV transformer 160 kVA Main switchboard C60 40 A PRD 40 kA Switchboard 1 Switchboard 2 C60 20 A ID "si" ID "si" PRD 8 kA C60 20 A PRD 8 kA Heating Lighting Storeroom lighting Freezer Refrigerator Fire-fighting system Power outlets Alarm IT system Checkout J25 Fig. J39 : Application example : supermarket 4.7 Application example: supermarket Solutions and schematic diagram Cabling recommendations b Ensure the equipotentiality of the earth terminations of the building. b Reduce the looped power supply cable areas. Installation recommendations Fig. J40 : Telecommunications network b Install a surge arrester, Imax = 40 kA (8/20 µs) and a C60 disconnection circuit breaker rated at 20 A. b Install fine protection surge arresters, Imax = 8 kA (8/20 µs) and the associated C60 disconnection circuit breakers rated at 20 A. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved b The surge arrester selection guide has made it possible to determine the precise value of the surge arrester at the incoming end of the installation and that of the associated disconnection circuit breaker. b As the sensitive devices (Uimp < 1.5 kV) are located more than 30 m from the incoming protection device, the fine protection surge arresters must be installed as close as possible to the loads. b To ensure better continuity of service for cold room areas: v"si" type residual current circuit breakers will be used to avoid nuisance tripping caused by the rise in earth potential as the lightning wave passes through. b For protection against atmospheric overvoltages: v install a surge arrester in the main switchboard v install a fine protection surge arrester in each switchboard (1 and 2) supplying the sensitive devices situated more than 30 m from the incoming surge arrester v install a surge arrester on the telecommunications network to protect the devices supplied, for example fire alarms, modems, telephones, faxes. Chapter K Energy Efficiency in electrical distribution Contents 3 4 5 6 Introduction K2 Energy efficiency and electricity K3 2.1 Regulation is pushing energy efficiency worldwide K3 2.2 How to achieve Energy Efficiency K4 Diagnosis through electrical measurement K7 3.1 Physical value acquisition K7 3.2 Electrical data for real objectives K8 3.3 Measurement starts with the "stand alone product" solution K10 Energy saving solutions k13 4.1 Motor systems and replacement K13 4.2 Pumps, fans and variable speed drives K14 4.3 Lighting K18 4.4 Load management strategies K20 4.5 Power factor correction K22 4.6 Harmonic filtering K22 4.7 Other measures K23 4.8 Communication and Information System K23 4.9 Mapping of solutions K30 How to value energy savings K31 5.1 Introduction to IPMVP and EVO K31 K1 5.2 Principles and options of IPMVP K31 5.3 Six qualities of IPMVP K32 5.4 IPMVP'S options K32 5.5 Fundamental points of an M&V plan K33 From returns on investment to sustained performance K34 6.1 Technical support services K34 6.2 Operational support services K35 © Schneider Electric - all rights reserved 1 2 Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 1 Introduction While there are a number of factors influencing the attitudes and opinions towards energy efficiency – most notably the increasing cost of energy and a rising social conscience – it is likely to be legislative drivers that have the greatest impact on changing behaviours and practices. Respective governments internationally are introducing energy saving targets and effecting regulations to ensure they are met. Reducing greenhouse gas emissions is a global target set at the Earth Summit in Kyoto in 1997 and finally ratified by 169 countries in December 2006 enabling the Agreement’s enactment in February 2005. Under the Kyoto Protocol industrialised countries have agreed to reduce their collective emissions of greenhouse gases by 5.2% by 2008-2012 compared to the year 1990 (however, compared to the emissions levels expected by 2012 prior to the Protocol, this limitation represents a 29% cut). The target in Europe is an 8% reduction overall with a target for CO2 emissions to fall by 20% by 2020. Of the six greenhouse gases listed by Kyoto, one of the most significant by volume of emissions is carbon dioxide (CO2) and it is gas that is mainly emitted as a result of electricity generation and use, as well as direct thermal losses in, for example, heating. Up to 50% of CO2 emissions attributable to residential and commercial buildings is from electricity consumption. Moreover, as domestic appliances, computers and entertainment systems proliferate; and other equipment such as air conditioning and ventilation systems increase in use, electricity consumption is rising at a higher rate than other energy usage. The ability to meet targets by simply persuading people to act differently or deploy new energy saving or energy efficient technology is unlikely to succeed. Just considering construction and the built environment, new construction is far less than 2% of existing stock. If newly constructed buildings perform exactly as existing stock the result by 2020 will be an increase in electricity consumption of 22%. On the other hand, if all new construction has energy consumption of 50% less than existing stock, the result is still an increase of 18%. In order to reach a fall in consumption of 20% by 2020 the folllowing has to happen: b All new buildings constructed to consume 50% less energy b 1 in 10 existing buildings reduce consumption by 30% each year K2 (see Fig.K1). Significantly, by 2020 in most countries 80% of all buildings will have already been built. The refurbishment of existing building stock and improving energy management is vital in meeting emission reduction targets. Given that in the west, most buildings have already undergone thermal insulation upgrades such as cavity wall insulation, loft insulation and glazing, the only potential for further savings is by reducing the amount of energy consumed. 140 120 100 80 60 40 20 0 Action on existing built environment will almost certainly become compulsory to meet targets fixed for the coming years. A minimum renovation of 10% per year of existing stock is compulsory to reach less 20% Renovation = New = As a result, governments are applying pressures to meet the ambitious targets. It is almost certain that ever more demanding regulations will be enforced to address all energy uses, including existing buildings and, naturally, industry. At the same time energy prices are rising as natural resources become exhausted and the electrical infrastructure in some countries struggles to cope with increasing demand. Technology exists to help tackle energy efficiency on many levels from reducing electrical consumption to controlling other energy sources more efficiently. Strong regulatory measures may be required to ensure these technologies are adopted quickly enough to impact on the 2020 targets. 2018 2017 2016 2015 2014 2013 2012 2011 2010 2009 2008 2007 Base SC1 SC2 The most important ingredient however, lies with the ability of those in control of industry, business and government to concentrate their hearts and minds on making energy efficiency a critical target. Otherwise, it might not be just the Kyoto targets on which the lights go out. 70% of the savings 30% of the savings The message to heed is that if those empowered to save energy don’t do so willingly now, they will be compelled under legal threat to do so in the future. © Schneider Electric - all rights reserved Fig. K1 : How to reach a fall in consumption of 20% by 2020 Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 2 Energy efficiency and electricity 2.1 Regulation is pushing Energy Efficiency worldwide Kyoto Protocol was the start of fixing quantitative targets and agenda in CO2 emissions reduction with clear government's commitments. Beyond Kyoto commitment (which covers only the period up to 2012) many countries have fixed longer time frame and targets in line with the last GIEEC recommendations to UNFCC to stabilise the CO2 concentration at a level of 450 ppm (this should require a division by 2 before 2050 of the CO2 emission level based on 1990). European Union is a good example and firm commitment with a target of Iess 20% before 2020 has been taken by heads of EU member states in March 2007 (known as the 3x20: it includes reduction of 20% of CO2 emission, Improvement of 20% of the Energy Efficiency level and reaching 20% of the energy produced from renewable).This commitment of Iess 20% in 2020 couId be extended to less 30% in 2020 in case of post Kyoto international agreement. Some European Countries are planning commitment for the 2050 with level of reduction up to 50%. All of this illustrates that Energy Efficiency Iandscape and policies will be present in a long time frame. Reaching these targets wiII require real change and regulations, legislation, standardisation are enablers governments are re inforcing everyday. All over the world Régulation/Législation is strengthening stakeholders obligations and putting in place financial & fiscal schemes b In US v Energy Policy Act of 2005 v Building Codes v Energy Codes (10CFR434) v State Energy prograrn (10CFR420) v Energy Conservation for Consumer Goods (10CFR430) b In European Union v EU Emission Trading Scheme v Energy Performance of Building Directive v Energy Using Product Directive v End use of energy & energy services directive K3 b In China v China Energy Conservation Law v China Architecture law (EE in Building) v China Renewable Energy Law v Top 1000 Industrial Energy Conservation Program Building Energy Performance EE Dedicated directives Dec 02 EPB 2002/91 Energy Labelling of Domestic Appliances Jul 03 ELDA 2003/66 Emission Trading Scheme Oct 03 ETS 2003/87 Combined Heat & Power Feb 04 CHP 2004/8 Energy Using Products July 05 Eco Design 2005/32 End use of Energy & Energy Services April 06 EUE & ES 2006/32 Various legislative and financial-fiscal incentives schemes are developed at national and regional levels such as: b Auditing & assessment schemes b Performance labelling schemes b Building Codes b Energy Performance Certificates b Obligation to energy sellers to have their clients making energy savings b Voluntary agreements in Industry b Financial-market mechanism (tax credit, accelerated depreciation, white certificates,...) b Taxation and incentive schemes Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. K2 : EE Dedicated directives K - Energy Efficiency in electrical installations 2 Energy efficiency and electricity All sectors are concerned and regulations impact not only new construction and installation but as well the existing buildings in industrial or infrastructure environment. In parallel Standardisation work has started with a lot of new standards being issued or in progress. In building all energy use are concerned: b Lighting b Ventilation b Heating b Cooling and AC For industries as well as commercial companies Energy Management Systems standards ( in Iine with the well known ISO 9001 for quality and ISO 14001 for environment) are under process in Standardisation Bodies. Energy Efficiency Services standards are as well at work. K4 Active EE Passive EE 2.2 How to achieve Energy Efficiency b Efficient devices and efficient installation (10 to 15%) Low consumption devices, insulated building... b Optimized usage of installation and devices (5 to 15%) Turn off devices when not needed, regulate motors or heating at the optimized level… b Permanent monitoring and improvement program (2 to 8%) Rigorous maintenance program, measure and react in case of deviation Fig. K2 : 30% Savings are available today… 30% savings are available through existing EE solutions, but to really understand where these opportunities are, let’s understand first the main differences between Passive and Active EE. © Schneider Electric - all rights reserved Passive EE is regarded as the installation of countermeasures against thermal losses, the use of low consumption equipment and so forth. Active Energy Efficiency is defined as effecting permanent change through measurement, monitoring and control of energy usage. It is vital, but insufficient, to make use of energy saving equipment and devices such as low energy lighting. Without proper control, these measures often merely militate against energy losses rather than make a real reduction in energy consumed and in the way it is used. Everything that consumes power – from direct electricity consumption through lighting, heating and most significantly electric motors, but also in HVAC control, boiler control and so forth – must be addressed actively if sustained gains are to be made. This includes changing the culture and mindsets of groups of individuals, resulting in behavioural shifts at work and at home, but clearly, this need is reduced by greater use of technical controls. b 10 to 15% savings are achievable through passive EE measures such as installing low consumption devices, insulating building, etc. b 5 to 15% can be achieved through such as optimizing usage of installation and devices, turn off devices when not needed, regulating motors or heating at the optimized level… v Up to 40% of the potential savings for a motor system are realized by the Drive & Automation v Up to 30% of the potential for savings in a building lighting system can be realized via the lighting control system Schneider Electric - Electrical installation guide 2009 2 Energy efficiency and electricity b And a further 2 to 8% can also be achieved through active EE measures such as putting in place a permanent monitoring and improvement program But savings can be lost quickly if there is: b Unplanned, unmanaged shutdowns of equipment and processes b Lack of automation and regulation (motors, heating) b No continuity of behaviors Energy Efficiency : it's easy, just follow the 4 sustainability steps 1 Measure b Energy meters b Power quality meters 2 Fix the basics b Low consumption devices b Insulation material b Power quality b Power reliability 3 Automate b Building management systems b Lighting control systems b Motor control systems b Home control systems b Variable speed drive 4 Monitor and Improve b Energy management software b Remote monitoring systems Fig. K4 : The 4 sustainability steps Energy Efficiency is not different form other disciplines and we take a very rational approach to it, very similar to the 6Sigma DMAIC (Define, Measure, Analyze, Improve and Control) approach. As always, the first thing that we need to do is to measure in order to understand where are the main consumptions, what is the consumption pattern, etc. This initial measurement, together with some benchmarking information, will allow us see how good or bad we are doing, to define the main improvement axis and an estimation of what can be expected in terms of gains. We can not improve what we can not measure. K5 Then, we need to fix the basics or what is called passive EE. Change old enduse devices by Low consumption ones (bulbs, motors, etc), Improve the Insulation of your installations, and assure power quality reliability in order to be able to work in a stable environment where the gains are going to sustainable over time. After that, we are ready to enter into the automation phase or Active Energy efficiency. As already highlighted, everything that consumes power must be addressed actively if sustained gains are to be made. Active Energy Efficiency can be achieved not only when energy saving devices and equipment are installed, but with all kind of end-use devices. It is this aspect of control that is critical to achieving the maximum efficiency. As an example, consider a low consumption bulb that is left on in an empty room. All that is achieved is that less energy is wasted compared to using an ordinary bulb, but energy is still wasted! Responsible equipment manufacturers are continually developing more efficient products. However, while for the most part the efficiency of the equipment is a fair representation of its energy saving potential - say, in the example of a domestic washing machine or refrigerator - it is not always the case in industrial and commercial equipment. In many cases the overall energy performance of the system is what really counts. Put simply, if an energy saving device is left permanently on stand-by it can be less efficient than a higher consuming device that is always switched off when not in use. Summarizing, managing energy is the key to maximizing its usefulness and economizing on its waste. While there are increasing numbers of products that are now more energy efficient than their predecessors, controlling switching or reducing settings of variables such as temperature or speed, makes the greatest impact. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations K - Energy Efficiency in electrical installations 2 Energy efficiency and electricity The key to sustainable savings 100% b Up to 8% per year is lost without monitoring and maintenance program b Up to 12% per year is lost without regulation and control systems Optimized usage via automation Efficient devices and installation Energy Consumption 70% Monitoring & Maintenance Time Fig. K5 : Control and monitoring technologies will sustain the savings As you could see, 30% energy saving are available and quite easily achievable today but up to 8% per year can be lost without proper maintenance and diligent monitoring of your key indicators. Information is key to sustaining the energy savings. You cannot manage what you cannot measure and therefore metering and monitoring devices coupled with proper analysis provide the tools required to take on that challenge successfully. Lifecycle approach to Energy Efficiency K6 Energy Audit & Measure building, industrial process… Fix the basics Low consumption devices, Insulation material Power factor correction… Optimize through Automation and regulation Monitor, maintain, improve HVAC control, lighting control, variable speed drives… Meters installation Monitoring services EE analysis software Passive Energy Efficiency Control Improve Active Energy Efficiency © Schneider Electric - all rights reserved Fig. K6 : Lifecycle solutions for Energy Efficiency Energy Efficiency needs a structured approach in order to provide significant and sustainable savings. Schneider Electric take a customer lifecycle approach to tackle it. It starts with a diagnosis or audit on buildings and industrial processes… This will provide us an indication of the situation and the main avenues to pursue savings. But is not enough, it is just the beginning, what really counts is getting the results. Only companies having the means to be active in the whole process can be there with their customers up to the real savings and results. Then, we will fix the basics, automate and finally monitor, maintain and improve. Then we are ready to start again and continue the virtuous cycle. Energy Efficiency is an issue where a risk sharing and a win-win relation shall be established to reach the goal. As targets are fixed over long timeframe (less 20% in 2020 , less 50% in 2050), for most of our customers EE programs are not one-shot initiatives and permanent improvement over the time is key. Therefore, frame services contracts is the ideal way to deal with these customer needs. Schneider Electric - Electrical installation guide 2009 3 Diagnosis through electrical measurement The energy efficiency performance in terms of electricity can only be expressed in terms of fundamental physical measurements – voltage, current, harmonics, etc. These physical measurements are then reprocessed to become digital data and then information. In the raw form, data are of little use. Unfortunately, some energy managers become totally immersed in data and see data collection and collation as their primary task. To gain value from data they must be transformed into information (used to support the knowledge development of all those managing energy) and understanding (used to action energy savings). The operational cycle is based on four processes: data collection; data analysis; communication; and action (see Fig. K7). These elements apply to any information system. The cycle works under condition that an adequate communication network has been set up. Communication (information to understanding) Action (understanding to results) Data analysis (data to information) Data collection Fig. K7 : The operational cycle K7 The data processing level results in information that can be understood by the recipient profile: the ability to interpret the data by the user remains a considerable challenge in terms of decision making. The data is then directly linked to loads that consume electricity – industrial process, lighting, air conditioning, etc. – and the service that these loads provide for the company – quantity of products manufactured, comfort of visitors to a supermarket, ambient temperature in a refrigerated room, etc. The information system is then ready to be used on a day to day basis by users to achieve energy efficiency objectives set by senior managers in the company. 3.1 Physical value acquisition The quality of data starts with the measurement itself: at the right place, the right time and just the right amount. Basically, electrical measurement is based on voltage and current going through the conductors. These values lead to all the others: power, energy, power factor, etc. Firstly we will ensure consistency of the precision class of current transformers, voltage transformers and the precision of the measurement devices themselves. The precision class will be lower for higher voltages: an error in the measurement of high voltage for example represents a very large amount of energy. The total error is the quadratic sum of each error. ∑ of error = error 2 + error 2 + ... + error 2 Example: a device with an error of 2% connected on a CT ’s with an error of 2% that means: ∑ of error = ( 2 )2 + ( 2 ) 2 = 2,828% . That could mean a loss of 2,828 kWh for 100,000 kWh of consumption. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations K - Energy Efficiency in electrical installations 3 Diagnosis through electrical measurement Voltage measurement In low voltage, the voltage measurement is directly made by the measurement device. When the voltage level becomes incompatible with the device capacity, for example in medium voltage, we have to put in voltage transformers. A VT (Voltage transformer) is defined by: b its primary voltage and secondary voltage b its apparent power b its precision class A CT is defined by: b transformation ratio. For example: 50/5A b precision class Cl. Example: Cl=0.5 b precision power in VA to supply power to the measurement devices on the secondary. Example: 1.25 VA b limit precision factor indicated as a factor applied to In before saturation. Example: FLP (or Fs) =10 for measurement devices with a precision power that is in conformity. Current measurement Current measurement is made by split or closed-core CT’s placed around the phase and neutral conductors as appropriate. According to the required precision for measurement, the CT used for the protection relay also allows current measurement under normal conditions. Energy measurement To measure energy, we consider two objectives: b A contractual billing objective, e.g. between an electricity company and its client or even between an airport manager (sub-billing) and stores renting airport surface areas. In this case IEC 62053-21 for Classes 1 and 2 and IEC 62053-22 for Classes 0.5S and 0.2S become applicable to measure active energy. The full measurement chain – CT, VT and measurement unit – can reach a precision class Cl of 1 in low voltage, Cl 0.5 in medium voltage and 0.2 in high voltage, or even 0.1 in the future. b An internal cost allocation objective for the company, e.g. to break-down the cost of electricity for each product produced in a specific workshop. In this case of a precision class between 1 and 2 for the whole chain (CT, VT and measurement station) is sufficient. It is recommended to match the full measurement chain precision with actual measurement requirements: there is no one single universal solution, but a good technical and economic compromise according to the requirement to be satisfied. Note that the measurement precision also has a cost, to be compared with the return on investment that we are expecting. Generally gains in terms of energy efficiency are even greater when the electrical network has not been equipped in this way until this point. In addition, permanent modifications of the electrical network, according to the company’s activity, mainly cause us to search for significant and immediate optimizations straight away. K8 Example: A class 1 analogue ammeter, rated 100 A, will display a measurement of +/-1 A at 100 A. However if it displays 2 A, the measurement is correct to within 1 A and therefore there is uncertainty of 50%. A class 1 energy measurement station such as PM710 – like all other Power Meter and Circuit Monitor Measurement Units – is accurate to 1% throughout the measurement range as described in IEC standards 62053. PM700 measurement unit Other physical measurements considerably enhance the data: b on/off, open/closed operating position of devices, etc. b energy metering impulse b transformer, motor temperature b operation hours, quantity of switching operations b motor load b UPS battery load b event logged equipment failures b etc. © Schneider Electric - all rights reserved 3.2 Electrical data for real objectives Electrical data is transformed into information that is usually intended to satisfy several objectives: b It can modify the behaviour of users to manage energy wisely and finally lowers overall energy costs b It can contribute to field staff efficiency increase b It can contribute to decrease the cost of Energy b It can contribute to save energy by understanding how it is used and how assets and process can be optimized to be more energy efficient Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 3 Diagnosis through electrical measurement b It may help in optimizing and increasing the life duration of the assets associated to the electrical network b And finally it may be a master piece in increasing the productivity of the associated process (industrial process or even office, building management), by preventing, or reducing downtime, or insuring higher quality energy to the loads. Facility utility costs parallel the visualization of an iceberg (see Fig. K8). While an iceberg seems large above the surface, the size is completely overwhelming beneath the surface. Similarly, electrical bills are brought to the surface each month when your power provider sends you a bill. Savings in this area are important and can be considerable enough to be the only justification needed for a power monitoring system. However, there are other less obvious yet more significant savings opportunities to be found below the surface if you have the right tools at your disposal. Modify the behaviour of energy users Using cost allocation reports, you can verify utility billing accuracy, distribute bills internally by department, make effective fact-based energy decisions and drive accountability in every level of your organization. Then providing ownership of electricity costs to the appropriate level in an organization, you modify the behaviour of users to manage energy wisely and finally lowers overall energy costs. K9 Here are some examples of the main usage of the simplest monitoring systems: b Benchmark between zones to detect abnormal consumption. b Track unexpected consumption. b Ensure that power consumption is not higher that your competitors. b Choose the right Power delivery contract with the Power Utility. b Set-up simple load-shedding just focusing on optimizing manageable loads such as lights. b Be in a position to ask for damage compensation due to non-quality delivery from the Power Utilities – " The process has been stopped because of a sag on the networks". Implementing energy efficiency projects The Power monitoring system will deliver information that support a complete energy audit of a factility. Such audit can be the way to cover not only electricity but also Water, Air, Gas and Steam. Measures, benchmark and normalized energy consumption information will tell how efficient the industrial facilities and process are. Appropriate action plans can then be put in place. Their scope can be as wide as setting up control lighting, Building automation systems, variable speed drive, process automation, etc. Optimizing the assets One increasing fact is that electrical network evolves more and more and then a recurrent question occurs : Will my network support this new evolution? This is typically where a Monitoring system can help the network owner in making the right decision. By its logging activity, it can archive the real use of the assets and then evaluate quite accurately the spare capacity of a network, or a switchboard, a transformer… A better use of an asset may increase its life duration. Monitoring systems can provide accurate information of the exact use of an asset and then the maintenance team can decide the appropriate maintenance operation, not too late, or not too early. In some cases also, the monitoring of harmonics can be a positive factor for the life duration of some assets (such as motors or transformers). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. K8 : Facility utility costs parallel the visualisation of an iceberg Increase field staff efficiency One of the big challenges of field staff in charge of the electrical network is to make the right decision and operate in the minimum time. The first need of such people is then to better know what happens on the network, and possibly to be informed everywhere on the concerned site. This site-wise transparency is a key feature that enables a field staff to: b Understand the electrical energy flows – check that the network is correctly set-up, balanced, what are the main consumers, at what period of the day, or the week… b Understand the network behaviour – a trip on a feeder is easier to understand when you have access to information from downstream loads. b Be spontaneously informed on events, even outside the concerned site by using today’s mobile communication b Going straight forward to the right location on the site with the right spare part, and with the understanding of the complete picture b Initiate a maintenance action taking into account the real usage of a device, not too early and not too late b Therefore, providing to the electrician a way to monitor the electrical network can appear as a powerful mean to optimize and in certain case drastically reduce the cost of power. K - Energy Efficiency in electrical installations 3 Diagnosis through electrical measurement Increasing the productivity by reducing the downtime Downtime is the nightmare of any people in charge of an electrical network. It may cause dramatic loss for the company, and the pressure for powering up again in the minimum time – and the associated stress for the operator – is very high. A monitoring and control system can help reducing the downtime very efficiently. Without speaking of a remote control system which are the most sophisticated system and which may be necessary for the most demanding application, a simple monitoring system can already provide relevant information that will highly contribute in reducing the downtime: b Making the operator spontaneously informed, even remote, even out of the concerned site (Using the mobile communication such as DECT network or GSM/ SMS) b Providing a global view of the whole network status b Helping the identification of the faulty zone b Having remotely the detailed information attached to each event caught by the field devices (reason for trip for example) Then remote control of a device is a must but not necessary mandatory. In many cases, a visit of the faulty zone is necessary where local actions are possible. Increasing the productivity by improving the Energy Quality Some loads can be very sensitive to electricity quality, and operators may face unexpected situations if the Energy quality is not under control. Monitoring the Energy quality is then an appropriate way to prevent such event and / or to fix specific issue. 3.3 Measurement starts with the “stand alone product” solution Compact NSX with Micrologic trip unit K10 TeSys U motor controller The progress made in real time industrial electronics and IT are used in a single device: b to meet requirements for simplification of switchboards b to reduce acquisition costs and reduce the number of devices b to facilitate product developments by software upgrade procedures © Schneider Electric - all rights reserved ION 6200 metering unit The choice of measurement products in electrical equipment is made according to your energy efficiency priorities and also current technological advances: b measurement and protection functions of the LV or MV electrical network are integrated in the same device, Example: Sepam metering and protection relays, Micrologic tripping unit for Compact NSX and Masterpact, TeSys U motor controller, NRC12 capacitor bank controller, Galaxy UPSs b the measurement function is in the device, separate from the protection function, e.g. built on board the LV circuit breaker. Example: PowerLogic ION 6200 metering unit Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 3 Diagnosis through electrical measurement Example of solutions for a medium-sized site: Analysesample Ltd. is a company specialized in analyzing industrial samples from regional factories: metals, plastics, etc., to certify their chemical characteristics. The company wants to carry out better control of its electrical consumption for the existing electrical furnaces, its air conditioning system and to ensure quality of electrical supply for high-precision electronic devices used to analyze the samples. Electrical network protected and monitored via the Intranet site The solution implemented involves recovering power data via metering units that also allows measurement of basic electrical parameters as well as verification of energy power quality. Connected to a web server, an Internet browser allows to use them very simply and export data in a Microsoft Excel™ type spreadsheet. Power curves can be plotted in real time by the spreadsheet (see Fig. K9). Therefore no IT investment, either in software or hardware, is necessary to use the data. For example to reduce the electricity bill and limit consumption during nighttime and weekends, we have to study trend curves supplied by the measurement units (see Fig. K10). Fig. K9 : Example of electrical network protected and monitored via the Intranet site K11 © Schneider Electric - all rights reserved Fig. K10 : A Test to stop all lighting B Test to stop air conditioning Here consumption during non-working hours seems excessive, consequently two decisions were taken: b reducing night time lighting b stopping air conditioning during weekends The new curve obtained shows a significant drop in consumption. Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 3 Diagnosis through electrical measurement Below we give examples of measurements available via Modbus, RS485 or Ethernet (see Fig. K11): Measurement units MV protection and measurement relays LV protection and measurement relays Capacitor bank regulators Insulation monitors Power Meter, Circuit Monitor Sepam Masterpact & Compact Micrologic trip units Varlogic Vigilohm System Power, inst., max., min. b b b b - Energy, reset capability b b b - - Power factor, inst. b b b - - Cos φ inst. - - - b - Examples Keep control over power consumption Improve power supply availability K12 Current, inst., max., min., unbalance b b b b - Current, wave form capture b b b - - Voltage, inst., max., min., unbalance b b b b - Voltage, wave form capture b b b - - Device status b b b b - Faults history b b b - - Frequency, inst., max., min. b b b - - THDu, THDi b b b b - Load temperature, load and device thermal state b b - b - Insulating resistance - - - - b Motor controllers LV variable speed drives LV softstarters MV softstarters UPSs TeSys U ATV.1 ATS.8 Motorpact RVSS Galaxy Power, inst., max., min. - b - b b Energy, reset capability - b b b - Power factor, inst. - - b b b Manage electrical installation better Examples Keep control over power consumption © Schneider Electric - all rights reserved Improve power supply availability Current, inst., max., min., unbalance b b b b b Current, wave form capture - - - b b Device status b b b b b Faults history b b b b - THDu, THDi - b - - - Load temperature, load and device thermal state b b b b b Motor running hours - b b b - Battery follow up - - - - b Manage electrical installation better Fig. K11 : Examples of measurements available via Modbus, RS485 or Ethernet Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 4 Energy saving solutions Based on the reports collected by the power monitoring system or energy information system, appropriate energy efficiency projects can be selected. There are various strategies for choosing which projects to implement: b Often organizations like to get started with relatively low-cost, easy projects to generate some quick wins before making larger investments. b The simple payback period (the length of time the project will take to pay for itself) is a popular method to rank and choose projects. Its advantage is simplicity of the analysis. The disadvantage is that this method may not take into account the full long-term impact of the project. b Other more complex methods such as net present value or internal rate of return can also be used. Additional effort is required to make the analysis, but a truer indication of the full project benefits is obtained. Energy savings can be achieved in a number of ways: b Energy reduction measures that either use less energy to achieve the same results, or reduce energy consumption by ensuring that energy is not over-used beyond the real requirements. An example of the former is using high-efficiency lamps to provide the same illumination at lower energy cost. An example of the latter is reducing the number of lamps in over-illuminated areas to reduce lighting levels to the required level. b Energy cost saving measures that do not reduce the total energy consumed, but reduce the per-unit cost. An example is scheduling some activities at night to take advantage of time-of-day electricity tariffs. Peak demand avoidance and demand response schemes are other examples. b Energy reliability measures that not only contribute to operational efficiency by avoiding downtime, but which also avoid the energy losses associated with restarts or reworking spoiled batches. Comprehensive Energy Strategy K13 Reduce Consumption Optimize Utility Costs Improve Reliability & Availability Fig. K12 : Comprehensive Energy strategy 95 Since in industry, 60% of consumed electricity is used to run motors, there is a high likelihood that motor systems will appear strongly among the identified opportunities. Two reasons to consider replacing motors and thereby improve passive energy efficiency are: 85 EFF 2 2 pole 80 EFF 3 2&4 pole b to take advantage of new high-efficiency motor designs b to address oversizing 75 70 1 15 Rated Power (kW) 90 Fig. K13 : Definition of energy efficiency classes for LV motors established by the European Commission and CEMEP (European Committee of Manufacturers of Electrical Machines and Power Electronics) Depending on horsepower, high efficiency motors operate between 1% and 10% more efficiently than standard motors. Motors that operate for long periods may be good candidates for replacement with high efficiency motors, especially if the existing motor needs rewinding. Note that rewound motors are usually 3% – 4% less efficient than the original motor. However, if the motor receives low to moderate use (e.g. under 3000 hours per year), replacement of standard efficiency motors (particularly those that have not yet been re-wound) with high efficiency motors may not be economical. Also, it is important to ensure the critical performance characteristics (such as speed) of the new motor are equivalent to those of the existing motor. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 90 Efficiency (%) 4.1 Motor systems and replacement EFF 1 4 pole K - Energy Efficiency in electrical installations 4 Energy saving solutions Motors are most efficient when operated between about 60% and 100% of their fullrated load. Efficiency falls sharply when loading is below 50%. Historically, designers have tended to oversize motors by a significant safety margin in order to eliminate any risk of failure even under extremely unlikely conditions. Facility studies show that about one-third of motors are severely oversized and generally are running below 50% of rated load (1). Average loading of motors is around 60%(2). Oversized motors are not only inefficient but have higher initial purchase cost than correctly-sized units. Larger motors can also contribute to lower power factor, which may lead to reactive power charges on the electricity bill. Replacement considerations should take this into account along with the remaining useful life of the motor. In addition, note that some motors may be oversized but still be so lightly loaded or infrequently used that they do not consume enough electricity to make it cost-effective to install a different motor. Clearly, wherever appropriate the two approaches should be combined to replace over-sized standard motors with high-efficiency motors sized suitably for the application. Other tactics which can be applied to motor systems include: b Improve active energy efficiency by simply turn off motors when they are not required. This may require improvements in automatic control, or education, monitoring and perhaps incentives for operators. If the operator of the motor is not accountable for its energy consumption, they are more likely to leave it running even when not in use. b Check and if necessary correct shaft alignment, starting with the largest motors. Misaligned motor couplings waste energy and eventually lead to coupling failure and downtime. An angular offset of 0.6 mm in a pin coupling can result in a power loss of as much as 8%. 4.2 Pumps, fans and variable speed drives 63% of energy used by motors is for fluid applications such as pumps and fans. Many of these applications run the motor at full speed even when lower levels of flow are required. To obtain the level of flow needed, inefficient methods such as valves, dampers and throttles are often used. In a car, these methods would be equivalent to using the brake to control speed while keeping the gas or accelerator pedal fully depressed. These are still some of the most common control methods used in industry. Given that motors are the leading energy-consuming device, and pumps and fans are the largest category of motor-driven equipment, these applications are frequently among the top-ranked energy saving opportunities. K14 © Schneider Electric - all rights reserved An Altivar variable speed drive is an active EE approach that can provide the means to obtain the variable output required from the fan or pump along with significant energy savings and other benefits. Well-chosen projects can result in simple payback periods as short as ten months, with many useful projects in the range of paybacks up to three years. Variable speed drives (VSD) can be useful in many applications, including air compressors, plastic injection moulding machines, and other machines. Fig. K14 : Examples of centrifugal pump and fan which can benefit from variable speed control (1) Operations and Maintenance Manual for Energy Management - James E. Piper (2) US Department of Energy fact sheet Schneider Electric - Electrical installation guide 2009 4 Energy saving solutions Most pumps are required either to move fluids between a source and a destination (e.g. filling a reservoir at a higher level) or to circulate liquid in a system (e.g. to transfer heat). Fans are required to move air or other gases, or to maintain a pressure differential. To make the liquid or air flow at the required rate, pressure is required. Many pumping or ventilation systems require the flow or pressure to vary from time to time. To change the flow or pressure in the system, there are a number of possible methods. The suitability will depend on the design of the fan or pump, e.g. whether a pump is a positive displacement pump or rotodynamic pump, whether a fan is a centrifugal fan or axial fan. b Multiple pumps or fans: This leads to step increase when additional pumps or fans are switched in, making fine control difficult. Usually there are efficiency losses as the real needs are somewhere between the possible steps. b Stop/start control: This is only practical where intermittent flow is acceptable. b Flow control valve: This uses a valve to reduce the flow by increased frictional resistance to the output of the pump. This wastes energy since the pump is producing a flow which is then cut back by the valve. In addition, pumps have a preferred operating range, and increasing the resistance by this method can force the pump to operate in a range where its efficiency is lower (wasting even more energy) and where its reliability is reduced. b Damper: Similar in effect to a flow control valve in a pumping system, this reduces the flow by obstructing the output of the fan. This wastes energy since the fan is producing a flow which is then cut back by the damper. b Bypass control: This technique keeps the pump running at full power and routes surplus fluid output from the pump back to the source. It allows a low value of flow to be achieved without risk of increasing the output pressure, but inefficiency is very high since the energy used to pump the surplus fluid is entirely wasted. b Spillage valve: Similar in effect to a bypass control valve in a pumping system, this technique keeps the fan running at full power and vents surplus flow. Inefficiency is very high since the energy used to move the vented air or gas is entirely wasted. b Variable pitch: Some fan designs allow the angle of the blades to be adapted to change the output. b Inlet guide vane: these are structures using fins to improve or disrupt the routing of air or gas into a fan. In this way they increase or decrease the airflow going in and hence increase or decrease the output. actuator motor fixed shaft speed 100% of nominal fan or pump K15 sensor damper or valve reduced output 50% of nominal output 100% of nominal sensor fan or pump motor VSD power consumed 12.5% of nominal variable shaft speed 50% of nominal open output 50% of nominal unchanged output 50% of nominal Fig. K15 : Fan and pump control: in theory Wherever a fan or a pump has been installed for a range of required flow rates or pressure levels, it will have been sized to meet the greatest output demand. It will therefore usually be oversized, and will be operating inefficiently for other duties. Combining this with the inefficiency of the control methods listed above means that there is generally an opportunity to achieve an energy cost saving by using control methods which reduce the power to drive the pump or fan during the periods of reduced demand. However, a fan or pump that is not required to perform variable duties may be running at full speed without any of the above control methods, or with those control methods present but unused (e.g. valves or dampers set to fully open). In this case the device will be operating at or close to its best efficiency and a variable frequency drive will not bring any improvement. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations K - Energy Efficiency in electrical installations 4 Energy saving solutions For those fans and pumps which are required to generate varying levels of output, a variable frequency drive reduces the speed of the pump or fan and the power it consumes. Among fans, effectiveness will vary depending on the design. Centrifugal fans offer good potential, both with forward curved and backward curved impellers. Axial fans have a greater intrinsic efficiency and normally do not offer enough economic potential for a VSD application. In pumps, the effectiveness will vary depending on a number of factors, including the ‘static head’ of the system (the effects of a difference in height between the source and destination of the fluid) and ‘friction head’ (the effects of the liquid moving in the pipes, valves and equipment). The variable frequency drive should always be matched with the safe operating range of the pump. Generally, variable speed drives bring greater benefits in systems where the friction head is the dominant effect. In some cases, replacing the fan or pump with a more efficient design may bring greater benefits than retrofit of a VSD. A fan or pump that is infrequently used, even if it is inefficient, may not generate enough savings to make replacement or VSD retrofit cost-effective. However note that flow control by speed regulation is always more efficient than by control valve or bypass control. Fan and pump applications are governed by the affinity laws: b Flow is proportional to shaft speed v Half the shaft speed gives you half the flow b Pressure or head is proportional to the square of shaft speed v Half the shaft speed gives you quarter the pressure b Power is proportional to the cube of shaft speed v Half the shaft speed uses one–eighth of the power v Hence half the flow uses one-eighth of the power 120 100 K16 80 P (%) 60 40 20 0 0 20 40 60 80 100 120 Q (%) Fig. K16 : Theoretical power saving with a fan running at half speed Therefore, if you don’t need the fan or pump to run at 100% flow or pressure output, you can reduce the power consumed by the fan, and the amount of the reduction can be very substantial for moderate changes in flow. Unfortunately in practice, efficiency losses in the various components render the theoretical values not achievable. © Schneider Electric - all rights reserved P (W) 0 0 Q (m3/s) Fig. K17 : Power versus flow rate for the different fan control methods: downstream damper, inlet vanes, and variable speed (top to bottom). Schneider Electric - Electrical installation guide 2009 4 Energy saving solutions The actual achievable savings depend on the design of the fan or pump, its inherent efficiency profile, the size of the motor, the number of hours used per year, and the local cost of electricity. These savings can be estimated using a tool such as ECO8, or can be accurately forecast by installing temporary metering and analyzing the data obtained in the context of the appropriate curve. The drive can be integrated into a variety of possible control methods: b Control by fixing pressure but varying flow: This uses a pressure sensor connected to the VSD which in turn varies the speed allowing the fan or pump to increase or decrease the flow required by the system. This is a common method in water supply schemes where constant pressure is required but water is required at different flows dependant on the number of users at any given time. This is also common on centralised cooling and distribution systems and in irrigation where a varying number of spray heads or irrigation sections are involved. b Heating system control: In heating and cooling systems there is a requirement for flow to vary based on temperature. The VSD is controlled by a temperature sensor, which increases or decreases the flow of hot or cold liquid or air based on the actual temperature required by the process. This is similar to pressure control, where the flow also varies, but a constant temperature requirement from a temperature sensor replaces that from a pressure sensor. b Control by fixing flow but varying pressure: Constant flow may be required in irrigation and water supply systems. Since the water levels both upstream and downstream of the pumping station can change, the pressure will be variable. Also many cooling, chiller, spraying and washing applications require a specific volume of water to be supplied even if the suction and delivery conditions vary. Typically suction conditions vary when the height of a suction reservoir or tank drops and delivery pressure can change if filters blind or if system resistance increases occur through blockages etc. A flowmeter is used to keep the flow rate constant, normally installed in the discharge line. The benefits achieved include: b Reduced energy consumption and hence cost savings by replacing inefficient control methods or other obsolete components such as two-speed motors b Better control and accuracy in achieving required flow and pressure b Reduced noise and vibration, as the inverter allows fine adjustment of the speeds and so prevents the equipment running at a resonant frequency of the pipes or ductwork b Increased lifecycle and improved reliability, for example, pumps that are operated in a throttled condition usually suffer from reduced useful life b Simplified pipe or duct systems (elimination of dampers, control valves & by-pass lines) b Soft start & stop creates less risk of transient effects in the electrical network or mechanical stress on the rotating parts of the pump or fan. This also reduces water hammer in pumps, because the drive provides smooth acceleration and deceleration instead of abrupt speed variations b Reduced maintenance Without VSD With VSD Reduction % savings Average power use (2 motors per fan) 104 kW per motor 40 kW per motor 64 kW per motor 62% Electricity cost per fan £68.66 per tonne output £26.41 per tonne output £42.25 per tonne output CO2 rate 459,000 kg / year 175,541 kg / year 283,459 kg / year Annual running cost £34,884 £13,341 £21,542 Payback period 10 months with local capital allowances claimed 14 months without local capital allowances Fig. K18 : Example of savings for variable speed driven pumps Additionally, significant energy savings can be often be made simply by changing pulley sizes, to ensure a fan or pump runs at a more appropriate duty point. This doesn’t provide the flexibility of variable speed control but costs very little, can probably be done within the maintenance budget and doesn’t require capital approval. Schneider Electric - Electrical installation guide 2009 K17 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations K - Energy Efficiency in electrical installations 4 Energy saving solutions 4.3 Lighting Lighting can represent over 35% of energy consumption in buildings depending on the business. Lighting control is one of the easiest ways to save energy costs for low investment and is one of the most common energy saving measures. Lamps and ballasts © Schneider Electric - all rights reserved K18 Lighting design for commercial buildings is governed by standards, regulations and building codes. Lighting not only needs to be functional but must meet occupational health and safety requirements and be fit for purpose. In many instances, office lighting is over-illuminated, and substantial energy savings are possible by passive EE: replacing inefficient, old technology lamps with high efficiency, low wattage lamps in conjunction with electronic ballasts. This is especially appropriate in areas where lighting is required constantly or for long periods, because in such places there is less opportunity to save energy by turning lights off. Simple payback periods vary but many projects have paybacks of around two years. Depending on the needs, type and age of your lighting installation, more efficient lamps may be available. For example, 40-watt T12 fluorescent lamps may be replaced by newer 32-watt T8 fluorescent lamps. (T designates a tubular lamp. The number is the diameter in eights of an inch. T12 lamps are therefore 1.5 inches in diameter. Standards vary between countries.) Changing the lamp will also require changing the ballast. Fluorescent lamps contain gases that emit ultraviolet light when excited by electricity. The phosphor coating of the lamp converts the ultraviolet light into the visible spectrum. If the electricity entering the lamp is not regulated, the light will continue to gain in intensity. A ballast supplies the initial electricity to create the light and then regulates the current thereafter to maintain the correct light level. Ballasts are also used with arc lamps or mercury vapor lamps. New designs of electronic ballasts deliver considerable savings compared with older electromagnetic ballast designs. T8 lamps with electronic ballasts will use from 32% to 40% less electricity than T12 lamps with electromagnetic ballasts. Electronic ballasts do have a disadvantage compared to magnetic ballasts. Magnetic ballasts operate at line frequency (50 or 60 Hz), but electronic ballasts operate at 20,000 to 60,000 Hz and can introduce harmonic distortion or noise into the electrical network. This can contribute to overheating or reduced life of transformers, motors, neutral lines, overvoltage trips and damage to electronics. Usually this is not a problem apart from facilities with heavy lighting loads and a large number of electronic ballasts. Most makes of electronic ballasts integrate passive filtering within the ballast to keep the total harmonic distortion to less than 20 percent of fundamental current. If the facility has strict needs for power quality, (e.g. hospitals, sensitive manufacturing environments, etc) electronic ballasts are available having total harmonic distortion of five percent or less. Other types of lighting are also available and may be suitable depending on the requirements of the facility. An assessment of lighting needs will include evaluation of the activities taking place and the required degree of illumination and colour rendering. Many older lighting systems were designed to provide more light than current standards require. Savings can be made by redesigning a system to provide the minimum necessary illumination. The use of high efficiency lamps in conjunction with electronic ballasts have a number of advantages, firstly energy and cost savings can be easily qualified, modern lamps and electronic ballasts are more reliable leading to reduced maintenance costs, lighting levels are restored to more appropriate levels for office space, whilst complying with relevant building codes, practices and lighting standards, the incidence of ‘frequency beat” often associated with migraines and eye strain disappears and the color rendering of modern lamps produces a more conducive working environment. Reflectors A less common passive EE recommendation, but one which should be considered along with changing lamps and ballasts, is to replace reflectors. The reflector in a luminaire (light fixture) directs light from the lamps towards the area where it is intended to fall. Advances in materials and design have resulted in improved reflector designs which can be retrofitted to existing luminaires. This results in increased usable light, and may allow lamps to be removed, this saving energy while maintaining the needed level of lighting. Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations + 4 Energy saving solutions A KW2 high efficiency reflector has a spectral efficiency of over 90%. This means two lamps may be replaced by a single lamp. In this way it is possible to reduce energy costs attributed to lighting by 50% or more. Existing luminaires may be retrofitted with the space age technology reflector, whilst maintaining spatial distance between luminaires, making retrofitting easy and cost effective, with minimal disruption to the existing ceiling design. + Lighting control Below: KW/2's silver surface is shaped to reflect the maximum amount of light downward. + Fig. K19 : Overview on KW/2 principle Improved lighting control is another method of increasing efficiency in lighting. Such recommendations are less common, but the simple payback period is typically shorter, between six and twelve months. By itself, passive EE from lamps, ballasts and reflectors does not maximize savings, since an energy efficient lamp will still waste energy if left on when not required. Although users can be sensitized to switch off lights, in practice lapses are common, and automatic control is much more effective in obtaining and sustaining efficiency. The objective of lighting control schemes is to provide the comfort and flexibility that users require, while simultaneously ensuring active EE, minimizing costs by ensuring lights are turned off promptly whenever they are not needed. The sophistication of such schemes can vary considerably. Some of the simplest methods include: b Timer switches to turn off lights after a fixed period has passed. Timers are best deployed in areas where occupancy is well defined (e.g. in hotel corridors where the time for a person to pass through is predictable). b Occupancy sensors / movement detectors to turn off lights when no movement has been detected for a certain period. Occupancy sensors are best deployed in offices, storerooms, stairwells, kitchens and bathrooms where the use of the facilities cannot be predicted with a high degree of accuracy during the day. b Photoelectric cells / daylight harvesting sensors to control lights near windows. When bright exterior light is available, lamps are turned off or dimmed. b Programmable timers to switch lights on and off at predetermined times (e.g. shop fronts, ensure office lights are turned off at nights and weekends). b Dimmable lights to maintain a low level of illumination at off-peak periods (e.g. a car parking lot which needs to be fully illuminated during peak use, perhaps until midnight, but which can have lower ambient illumination from midnight until dawn) b Voltage regulators to optimize the power consumed. Ballasts perform this function on fluorescent lighting. Voltage regulators are also available for other lighting types such as high pressure sodium lamps. Fig. K20 : Examples of lighting control devices: timers, light detectors, movement detectors,... US Dept of Energy Industrial Assessment Centers database Schneider Electric - Electrical installation guide 2009 K19 © Schneider Electric - all rights reserved Above: Around 70% of a fluorescent tube's light is directed sideways and upwards to the light fittings surfaces; K - Energy Efficiency in electrical installations 4 Energy saving solutions Methods may be combined, e.g. the ability to dim lights in the parking lot may be combined with movement detectors or override switches with a timer to increase illumination when needed if a user requires access outside normal hours. More sophisticated and customizable schemes can be implemented with integrated lighting control systems. Aesthetic requirements can be incorporated, such as using programmable lighting panels to record a variety of lighting setups which can be reproduced at the touch of a button (e.g. for boardrooms requiring different light arrangements for meetings, presentations, demonstrations, etc). Wireless technology can make retrofit applications simple and economical. Lighting control systems such as C-Bus and KNX offer the additional advantage that they can be networked and integrated with the building management system, for greater flexibility of control, central monitoring and control function as well as combination of lighting controls with other building services such as HVAC for even greater energy savings. Lighting controls have the potential to realize energy savings of 30% but this depends very much on application. A lighting survey and energy audit can help define the best lighting solution for the premises and activities performed as well as identify areas for energy and cost savings. In addition to office space, Schneider offers solutions for exterior, car parking and landscape lighting for optimum lighting and energy savings. 4.4 Load management strategies Since electricity has to be generated in response to immediate needs, and cannot economically be stored, suppliers are obliged to size their generating capacity according to peak needs, which may occur infrequently. At other times, that capacity is surplus and represents capital tied up in facilities and equipment that are idle and unused. Suppliers are therefore motivated to smooth out peaks in electricity demand. Load management requires an active EE approach, since even high-efficiency devices will contribute to peak needs. K20 Peak demand avoidance One way utilities encourage users to avoid peaks is by transferring the cost of maintaining the peak production capacity to those users who contribute most to the peaks. Utilities structure their billing with various components. One is always the actual consumption in the billing period, but another component (the demand charge) is normally based on the peak usage at some point during the preceding period, which could be twelve months or another period such as a season. The demand charge is a premium that large users pay each month for the utility to have the extra generation capacity and infrastructure required to meet their peak demand levels whenever they need it – even if they don’t use it very often. If a customer can avoid setting peaks in their energy usage, they can minimize the part of their energy bill driven by the peak consumption, even if their total consumption remains the same. Note that setting a new peak has a continuing economic impact, because it determines the demand charge not only for that month, but for each subsequent month during the period defined by the tariff, which may be as much as a year. This means that a single short event that spikes consumption for as little as a few minutes can have a continuing effect on the electricity bill. kW Peak Demand © Schneider Electric - all rights reserved Peak Usage rescheduled to fit under lower threshold Shaved Peak Demand Time Fig. K21 : Example of load management strategy Schneider Electric - Electrical installation guide 2009 4 Energy saving solutions Peak demand avoidance applications are PLC controlled automatic electrical distribution control systems. A demand interval is defined as a particular level of consumption in a period of time (e.g. kWh in a 15 minute period). The objective is to keep the total energy consumed in each period below the limit. If the customer is consuming a large amount of power in a given period, the system will detect that a peak is approaching. An alarm is activated, and unless an operator overrides the system, it will begin to shed non-essential loads in a predetermined order, until the alarm condition is cleared, or the demand interval ends. All loads in a facility are defined in one of three categories: critical, essential, and non-essential loads. Usually only non-essential loads are shed, and the order of shedding can be configured. The peak set during month 2 will dictate the demand charge for the next 12 months (or some other peirod set by the tariff). kW Peak during month 2 1 2 3 4 5 The bill for month 4 will be based on the consumption (green) and the peak set during month 2 (red line). Fig. K22 : Impact of peak demand on electricity bill Providing the customer has enough non-essential loads to be able to impact their peak consumption, it may be possible to reduce the demand charge by as much as 10% to 30%. Demand charge can be up to 60% of the bill. The application usually pays for itself in one year or less. K21 Load scheduling Utilities often have different rates that apply for different times of the day. During normal daily business hours, the rates are the highest. Many users shift, or reschedule loads to take advantage of lower rates. These are loads that are not time sensitive or critical. Demand response (curtailment) Another tactic is demand response (also known as demand curtailment). Demand response is a means to manage the demand from customers taking supply conditions into account. Utilities may offer financial incentives to customers to reduce load during periods when the utility does not have the distribution capacity to handle the total demand. Typically this will be during the hottest months of the year, when consumer and business needs for cooling and ventilation are high and draw a lot of electricity in addition to normal requirements. In some countries, third-party aggregators may manage schemes that monitor the network capacity and the realtime price of electricity on the network. Participants in the scheme receive incentives to shed load, creating capacity which the aggregator can sell into the network. In each case, the utility or aggregator offers a contract including an agreement from the customer to reduce the kW consumption at their site down to a predetermined level when notified. These contracts may contain both emergency curtailments (when the participants in the scheme must comply or face penalties) and opt-in curtailments (where participants can evaluate the specific conditions for that particular curtailment and decide whether or not to accept). Usually the contract limits the duration of the curtailment (e.g. 2 to 6 hours) and the number of times per year the curtailment can be activated (3 to 5). Industrial customers tend to have more opportunity to participate, since building managers are less likely to be able to drop substantial loads without impacting the building occupants’ comfort. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations K - Energy Efficiency in electrical installations 4 Energy saving solutions A curtailment is activated following a notification by phone or via a signal output from the utility revenue meter. Typically there is 30 to 60 minutes advance notice. The customer systematically reduces load until the curtailment level is obtained, either by manually reducing or shutting off loads or by an automated PLC controlled system. The utility or aggregator then signals the start of the curtailment period. After the curtailment period is complete, the utility or aggregator signals the end of the curtailment period. The customer may then re-establish normal facility loading and production. The return on investment from demand response schemes will vary depending on local tariff rates and electricity market. The incentive generally takes the form of a credit for the demand reduction during the response period. If the customer has enough non-essential loads to be able to impact peak consumption, he may be able to benefit from incentives that in effect reduce the cost per unit by as much as 30%. Automated demand response control applications usually pay for themselves in one year or less. Without such a scheme, loads have to be turned off manually, with a significant chance of failure, for example, if a human operator does not act quickly enough. Failing to comply with a curtailment brings financial penalties, and so an automated application which can support both peak demand avoidance and demand curtailment can be a very good investment. Together with the control applications, a demand response portal can make participation in a demand response scheme much more convenient. Such a portal provides a means for a utility or aggregator to notify the participants of emergency or opt-in events. Participants can evaluate the conditions of an opt-in and view their current consumption and what they would have to do in order to comply with the request before accepting or rejecting the event. The portal also supports auditing or completed events to demonstrate compliance with the conditions. On-site generation K22 On-site generation increases the flexibility available to facility operators. Instead of shedding loads, on-site generation can provide the power required to keep running during a period of peak avoidance or demand curtailment. The automated control system can be extended to integrate control of on-site generation facilities into the scheme. If the customer is buying electricity from a supplier at a time-of-use rate, the control system can be configured to continuously monitor the current cost of electricity from the supplier and compare it to the cost of energy generated on site using another fuel source. When the cost of electricity rises above the cost of using the generator (replacing the fuel), the control scheme automatically shifts load to the on-site generation. When the cost falls, load is shifted back to the supply utility. However, in many places the local authorities only permit diesel generators to be used for a certain maximum number of hours per year, in order to limit emissions. This has to be taken into account as it limits the opportunities to make use of the generator. 4.5 Power factor correction If the electricity supplier charges penalties for reactive power, implementing power factor correction has the potential to bring significant savings on the electricity bill. Power factor correction solutions are typically passive EE measures that operate transparently once installed, and don’t require any changes to existing procedures or behaviour of staff. Simple payback periods can be less than a year. Power factor correction is treated in detail in chapter L. © Schneider Electric - all rights reserved 4.6 Harmonic filtering Many solutions to improve efficient use of electricity can have side effects, bring harmonics into the electrical network. High-efficiency motors, variable speed drives, electronic ballasts for fluorescent lights, and computers can all generate electrical pollution which can have significant effects. Harmonics can create transient overvoltage conditions that cause protection relays to trip and result in production downtime. They increase heat and vibration and thereby decrease efficiency and shorten life of neutral conductors, transformers, motors and generators. Power factor correction capacitors may magnify harmonics, and can suffer from overloading and premature aging. Management of harmonics is treated in detail in chapter M. Schneider Electric - Electrical installation guide 2009 4 Energy saving solutions 4.7 Other measures Outside the scope of the electrical installation, other energy savings measures may be available depending on the activities present on the site. Productivity enhancements in production such as reducing bottlenecks, eliminating defects and reducing materials can generate further savings. Combustion systems (such as furnaces, ovens, boilers) and thermal systems (such as steam systems, heat generation, containment and recovery, cooling towers, chillers, refrigerators, dryers) may also provide opportunities. 4.8 Communication and Information System Most organisations will already have some level of energy information system, even if it is not identified or managed as one. It should be appreciated that in a changing working world, any information system will need to develop to meet its prime objective - supporting management decision making: a key point is to make the energy information visible at any level of the organization through the communication infrastructure. Energy data is important data, it is one of the company’s assets. The company has IT managers who are already in charge of managing its other IT systems. These are important players in the power monitoring system and above all in that for data exchange within the corporate organization. Communication network at product, equipment and site level The day-to-day working of the energy information system can be illustrated by a closed loop diagram (see Fig. K23). ra Int Mo net* K23 s* dbu Understanding Information Data g atin e* unic devic m m o C nt reme measu Energy information systems * Communication network Fig. K23 : System hierarchy Various resources are used to send data from metering and protection devices installed in the user’s electrical cabinets, e.g. via Schneider ElectricTransparent Ready™. © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 4 Energy saving solutions The Modbus communication protocol Modbus is an industrial messaging protocol between equipment that is interconnected via a physical transmission link e.g. RS 485 or Ethernet (via TCP/IP) or modem (GSM, Radio etc). This protocol is very widely implemented on metering and protection products for electrical networks. Initially created by Schneider Electric, Modbus is now a public resource managed by an independent organization Modbus-IDA – enabling total opening up of its specification. An industrial standard since 1979, Modbus allows millions of products to communicate with one another. The IETF, international authority managing the Internet, has approved the creation of a port (502) for products connected to the Internet/Intranet and using the Ethernet Modbus TCP/IP communication protocol. Modbus is a query/reply process between two pieces of equipment based on data reading and writing services (function codes). The query is emitted by a single “master”, the reply is sent only by the “slave” equipment identified in the query (see Fig. K24). Each “slave” product connected to the Modbus network is set by the user with an ID number, called the Modbus address, between 1 and 247. The “master” – for example a web server included in an electrical cabinet – simultaneously queries all of the products with a message comprising its target’s address, function code, memory location in the product and quantity of information, at most 253 octets. Only a product set with the corresponding address answers the request for data. Exchange is only carried out on the initiative of the master (here the web server): this is the master-slave Modbus operating procedure. This query procedure followed by a reply, implies that the master will have all of the data available in a product when it is queried. The “master” manages all of the transaction queries successively if they are intended for the same product. This arrangement leads to the calculation of a maximum number of products connected to the master to optimize an acceptable response time for the query initiator, particularly when it is a low rate RS485 link. K24 Fig. K24 : The function codes allow writing or reading of data. A transmission error software detection mechanism called CRC16 allows a message with an error to be repeated and only the product concerned to respond. Your Intranet network © Schneider Electric - all rights reserved Data exchange from industrial data basically uses web technologies implemented permanently on the corporate communication network, and more particularly on its Intranet. The IT infrastructure manages the cohabitation of software applications: the company uses it to operate applications for the office, printing, data backup, for the corporate IT system, accounting, purchasing, ERP, production facility control, API, MES, etc. The cohabitation of data on the same communication network does not pose any particular technological problem. When several PC’s, printers and servers are connected to one another in the company’s buildings, very probably using the Ethernet local network and web services: this company is then immediately eligible to have energy efficiency data delivered by its electrical cabinets. Without any software development, all they need is an Internet browser. Schneider Electric - Electrical installation guide 2009 4 Energy saving solutions The data from these applications cross the local broadband Ethernet network up to 1 Gb/s: the communication media generally used in this world is copper or optic fiber, which allows connection everywhere, in commercial or industrial buildings and in electrical premises. If the company also has an internal Intranet communication network for emailing and sharing web servers data, it uses an extremely common standardized communication protocol: TCP/IP. The TCP/IP communication protocol is designed for widely used web services such as HTTP to access web pages, SMTP for electronic messaging between other services. Applications SNMP Transport NTP RTPS DHCP TFTP FTP HTTP UDP Link Physical SMTP Modbus TCP IP Ethernet 802.3 and Ethernet II Electrical data recorded in industrial web servers installed in electrical cabinets are sent using the same standardized TCP/IP protocol in order to limit the recurrent IT maintenance costs that are intrinsic in an IT network. This is the operating principle of Schneider Electric Transparent ReadyTM for communication of data on energy efficiency. The electrical cabinet is autonomous without the need for any additional IT system on a PC, all of the data related to energy efficiency is recorded and can be circulated in the usual way via the intranet, GSM, fixed telephone link, etc. Security Employees are well informed, more efficient and working in complete electrical safety: they no longer need to go into electrical rooms or make standard checks on electrical devices - they just have to consult data. Under these conditions, communicative systems give the company’s employees immediate and significant gains and avoid worrying about making mistakes. It becomes possible for electricians, maintenance or production technicians, on-site or visiting managers to work together in complete safety. According to the sensitivity of data, the IT manager will simply give users the appropriate access rights. K25 Marginal impact on local network maintenance The company’s IT manager has technical resources to add and monitor equipment to the local company network. Based on standard web services including the Modbus protocol on TCP/IP, and due to the low level of bandwidth requirement characteristic in electrical network monitoring systems as well as the use of technologies that are not impacted by viruses and worldwide IT standards, the IT manager does not have to make any specific investment to preserve the local network performance level or to protect against any additional security problems (virus, hacking, etc.). Empowering external partners According to the company’s security policy, it becomes possible to use support services of the usual partners in the electrical sector: contractors, utilities managers, panelbuilders, systems integrators or Schneider Electric Services can provide remote assistance and electrical data analysis to the company consuming electricity. The messaging web service can regularly send data by email or web pages can be remotely consulted using the appropriate techniques. © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 4 Energy saving solutions From Network Monitoring and Control System to Intelligent Power Equipment Traditionally and for years, monitoring and control systems have been centralized and based on SCADA (Supervisory, Control and Data acquisition) automation systems. Deciding on investing in such system – noted (3) in Figure K25 – was really reserved for high demanding installation, because either they were big power consumers, or their process was very sensitive to Power non quality. Based on automation technology, such systems were very often designed, customised by a system integrator, and then delivered on site. However the initial cost, the skills needed to correctly operate such system, and the cost of upgrades to follow the evolutions of the network may have discouraged potential users to invest. Then based on a dedicated solution for electrician, the other approach noted (2) is much more fitting the electrical network specific needs and really increases the payback of such system. However, due to its centralised architecture, the level cost of such solution may still appear high. On some sites Type (2) and (3) can cohabit, providing the most accurate information to the electrician when needed. Nowadays, a new concept of intelligent Power equipment – noted (1) – has come. considered as an entering step for going to level 2 or 3, due the ability of these solutions to co-exist on a site. Function levels General purpose monitoring system 3 General purpose site monitoring Eqt gateway Power Equipment K26 Specialised network monitoring Other utilities Process Specialised monitoring such as Power Logic IONEntreprise 2 Eqt gateway Power Equipment Web browser standard 1 Basic monitoring Eqt server Intelligent Power Equipment Other utilities Standard network Sensitive electrical networks © Schneider Electric - all rights reserved Fig. K26 : Monitoring system positioning Schneider Electric - Electrical installation guide 2009 High demanding sites System complexity 4 Energy saving solutions b Level 1 Intelligent equipment based architecture (see Fig. K26) This new architecture has appeared recently due to Web technology capabilities, and can really be positioned as an entry point into monitoring systems. Based on Web technologies it takes the maximum benefits of standard communication services and protocols, and license-free software. The access to electricity information can be done from everywhere in the site, and electrical staff can gain a lot in efficiency. Openness to the Internet is also offered for out of the site services. Standard remote Web browser Standard local Web browser Internet Intranet (Ethernet/IP) Equipment server Gateway Intelligence Power Equipment Modbus 1 2 3 Meter 1 Meter 2 Meter 3 Circuit breakers K27 Fig. K26 : Intelligent equipment architecture b Level 2 Electrician specialized centralised architecture (see Fig. K27) Dedicated to electrician, this architecture is based on a specific supervision centralised mean that fully match the needs for monitoring an electrical network. Then it offers naturally a lower level of skill to set up and maintain it – all Electrical Distribution devices are already present in a dedicated library. Finally its purchase cost is really minimized, due the low level of system integrator effort. Dedicated supervisor for electrician Modbus (SL or Ethernet/IP) Communicating Power Equipment Gateway Modbus 1 2 Circuit breakers Fig. K27 : ED specialist monitoring system Schneider Electric - Electrical installation guide 2009 3 Meter 1 Meter 2 Meter 3 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations K - Energy Efficiency in electrical installations 4 Energy saving solutions b Level 3 Conventional general purpose centralised architecture (see Fig. K28) Here is a typical architecture based on standard automation pieces such as SCADA systems, and gateways. This architecture is typically used for high demanding installation which requires high availability of electricity. In such case, real time performance is key, either to be achieved automatically or through 24/7 operation team on site. In order to comply with very high availability constraint, such system very often requests to support transparently (i.e with no visible impact) a first fault of system level components such as the SCADA itself, the communication infrastructure, ... Energy efficiency is also an important matter, and such solution should offer all the mean to clearly master the energy consumption and quality on site. Electrical assets protection is then the 3d main matter, and such solution should offer a mean to prevent any damage of these very expensive electrical and process assets. Connectivity with the Process control system is also required, especially through the remote control of the operating mode of motors (MV and LV). Solutions such as PowerLogic SCADA (Modbus or IEC 61850 based) appear the most appropriate. Conventional supervisor Modbus (SL or Ethernet/IP) Communicating Power Equipment Gateway Modbus K28 1 2 3 Meter 1 Meter 2 Meter 3 Circuit breakers Fig. K28 : Real-time conventional monitoring and control system e-Support becomes accessible © Schneider Electric - all rights reserved The setting up of an information system to support a global energy efficiency approach very quickly leads to economic gains, in general with an ROI of less than 2 years for electricity. An additional benefit, that is still underestimated today, is the leverage that this leads to in terms of information technologies in the electrical sector. The electrical network can be analyzed from time to time by third parties – in particular using external competencies via the internet for very specific issues: b Electricity supply contracts. Changing of supplier at a given point in time, e.g. permanent economic analysis of the costs related to consumption becomes possible without having to wait for an annual review. b Total management of electrical data – via internet – to transform it into relevant information that is fed back via a personalized web portal. Consumer usage information is now a value-added commodity, available to a wide range of users. It's easy to post customer usage data on the Internet – making it useful to the users is another matter. b Complex electrical fault diagnosis to call in an electrotechnical expert, a rare resource that is easily accessible on the web. b Monitoring of consumption and generating alerts in the case of abnormal consumption peaks. b A maintenance service that is no more than necessary to meet pressure on overheads via facility management services. Schneider Electric - Electrical installation guide 2009 4 Energy saving solutions Energy efficiency is no longer an issue that the company has to face on its own, many e-partners can back up the approach as necessary – in particular when the measurement and decision making assistance stage is reached, on condition that the electrical network is metered and communicative via internet. Implementation can be gradual starting by making a few key pieces of equipment communicative and gradually extending the system so as to be more accurate or to give wider coverage of the installation. The company can choose its policy: ask one or more partners to analyze the data, do it itself or combine these options. The company may decide to manage its electrical energy itself, or ask a partner to monitor the quality to ensure active monitoring of performances in terms of aging. Example: Schneider Electric proposes e-Services that offers load data visualization and analysis application in ASP mode. It simplifies processes for tenants with geographically diverse locations by providing convenient integrated billing and usage information for all locations combined. The system turns customer usage data into useful information, easily accessible to all internal users. It helps control costs by showing customers how their organizations use power. A wide range of functionality serves the needs of staff from the same platform: Data Access and Analysis , Historical and Estimated Bills, Rate Comparison, What-if Analysis - Assess the impact of operational changes, such as shifting energy between time periods or reducing usage by fixed amounts or percentages, Automatic Alarming, Memorized Reports, Benchmarking - Benchmark usage data from multiple facilities by applying normalization factors such as square footage, operating hours, and units of production. Multiple Commodities - Access usage data for gas and water as well as electricity etc. New York Chicago Los Angeles Seattle K29 Ethernet/VPN Ethernet/VPN Weather info WEB Utility tariffs & rates WEB Real-time pricing Electricity Water & Gas Power Quality XML Reports Energy Cost Analysis Normalize data using: - Temperature - Occupancy rates - Rooms - Other parameters Corporate Database ODBC Stores data including: - Occupancy rates - Square footage - Other parameters Fig. K29 : Typical solution example © Schneider Electric - all rights reserved K - Energy Efficiency in electrical installations Schneider Electric - Electrical installation guide 2009 K - Energy Efficiency in electrical installations 4 Energy saving solutions 4.9 Mapping of solutions: Energy savings Variable speed drives  High efficiency motors and transformers  MV motor supply Power factor correction Harmonic management    Configuration of circuits Back-up generators UPS (see page N11) Soft starters  Protection coordination iMCC Intelligent Equipment based architecture Level 1 Electrician specialized centralised architecture Level 2 Conventional general purpose centralised architecture Level 3 Fig. K31 : Mapping of solutions © Schneider Electric - all rights reserved K30 Schneider Electric - Electrical installation guide 2009 Cost optimization    Availability & Reliability                    K - Energy Efficiency in electrical distribution 5 How to value energy savings IPMVP (International Performance Measurement & Verification Protocol) is a methodology to value the energetic savings. Certain information in this chapter is taken from the IPMVP guide volume 1 published by EVO www.evo-world.org 5.1 Introduction to IPMVP and EVO Today, the interest in energy efficiency project, for whatever purpose, industrial or public, has never been greater. It is noticed that one of the most important barriers to a widespread implementation of energy efficiency projects is the lack of reliable and commercially-viable financing result. The more we invest for a project, the bigger the need for a reliable proof is. Therefore, there is a continuing need for standard methods to quantify the results of energy efficiency investments. That’s why Efficiency Valuation Organization (EVO) published IPMVP: International Performance Measurement and Verification Protocol, a guidance document describing common practice in measuring, computing and reporting savings achieved by energy efficiency projects at end user facilities. The first edition of IPMVP was published in March 1996 and the second in 2004. Until now, EVO has published three volumes of IPMVP: b Volume I : Concepts and Options for Determining Energy and Water Savings b Volume II : Indoor Environmental Quality (IEQ) Issues b Volume III : Applications The first volume is used by Schneider Electric in energy efficiency projects. This publication provides methods, with different levels of cost and accuracy, for determining savings either for the whole facility or for the energy efficiency action only. IPMVP also specifies the contents of a Measurement and Verification Plan (M&V Plan) which defines all activities necessary to demonstrate the short-term performance of an industrial retrofit project and its result. 5.2 Principles and options of IPMVP Principle of IPMVP K31 Energy Use Adjusted baseline energy Baseline energy Inreased production Savings Reporting period Measured energy Solution installation Baseline period Reporting period Time Before the installation of energy efficiency solution, a certain time interval is studied to determine the relationship between energy use and conditions of production, this period is called baseline. We can do the measurement during this time or more simply use the energy bill of the plant. Following the installation, this baseline relationship was used to estimate how much energy the plant would have used if there had been no solution (called the “adjusted-baseline energy”). The savings is the difference between the adjusted-baseline energy and the energy that was actually metered during the reporting period. Savings = (Adjusted Baseline Period Use or Demand - Reporting-Period Use or Demand) Or Savings = Baseline Period Use or Demand - Reporting-Period Use or Demand ± Adjustments Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. K31 : Principle of baseline definition K - Energy Efficiency in electrical distribution 5 How to value energy savings 5.3 Six qualities of IPMVP When an M&V plan is drawn up for an IPMVP action, it must guarantee six principles: b Accurate: M&V reports should be as accurate as the M&V budget will allow. M&V costs should normally be small relative to the monetary value of the savings being evaluated. b Complete: The reporting of energy savings should consider all effects of a project. b Conservative: Where judgements are made about uncertain quantities, M&V procedures should be designed to under-estimate savings. b Consistent: The reporting of a project’s energy effectiveness should be consistent between: v different types of energy efficiency projects; v different energy management professionals for any one project; v different periods of time for the same project; v and energy efficiency projects and new energy supply projects. b Relevant: The determination of savings should measure the performance parameters of concern, or least well known, while other less critical or predictable parameters may be estimated. b Transparent: All M&V activities should be clearly and fully disclosed. 5.4 IPMVP’s options Option A Option B Option C Option D Definition Retrofit isolation: key parameter measurement Retrofit isolation: all parameter measurement Whole facility Calibrated simulation Description Savings are determined by field measurement of the key performance parameter(s) which define the energy use of the system affected by the energy efficiency solution. Parameters not selected for field measurement are estimated. Savings are determined by field measurement of the energy use of the system affected by the solution. Savings are determined by measuring energy use at the whole facility or subfacility level. Continuous measurements of the entire facility’s energy use are taken throughout the reporting period. Savings are determined through simulation of the energy use of the whole facility, or of a sub-facility. Simulation routines are demonstrated to adequately model actual energy performance measured in the facility. Calculation of savings Engineering calculation of baseline and reporting period energy from: - short-term or continuous measurements of key operating parameter(s); and - estimated values. Short-term or continuous measurements of baseline and reporting period energy Analysis of whole facility baseline and reporting period data. Routine adjustments are required, using techniques such as simple comparison or regression analysis. Energy use simulation, calibrated with hourly or monthly utility billing data. When use this option? On one hand, this option can give a result with considerable uncertainty because of the estimation of some parameters. On the other hand, it is not expensive compared to the option B. Option B is less cheap than option A as all parameters are measured. But if a customer asks for a high precision level, it would be a good choice. When there is a multifaceted energy management program affecting many systems in a facility, a choice of option C can help in saving money and work. Option D is used only when the baseline data is missed. Example: a facility where no meter existed before solution’s installation and the measure of the baseline period takes too much time and money. © Schneider Electric - all rights reserved K32 Schneider Electric - Electrical installation guide 2009 5 How to value energy savings Option selection process Start ECM performance Facility performance Measure facility or ECM performance? Able to isolate ECM with meter(s)? No Expected savings >10%? No Yes Yes Need full perfomance demonstration? No No Need to separately assess each ECM? Analysis of main meter data Yes Install isolation meters for all parameters and assess interactive effects Missing baseline or reporting period data? Simulate system or facility Install isolation meters for key parameters assess interactive effects, and estimate well know parameters Missing baseline or reporting period data? Obtain calibration data Calibrate simulation Yes Simulate with and without ECM(s) No Yes Yes K33 No Option B Retrofit isolation: All parameter measurement Option A Retrofit isolation: Key parameter measurement Option C Whole facility Option D Calibrated simulation Fig. K32 : Option selection process 5.5 Fundamental points of an M&V plan b Energy efficiency project’s intent b Selected IPMVP option and measurement boundary b Baseline: period, energy and conditions b Reporting period : duration and condition b Basis for adjustment b Analysis procedure: the data analysis procedures, algorithms and assumptions to be used. b Energy prices b Meter specifications b Monitoring responsibilities b Expected accuracy b Budget for IPMVP activities b Report format b Quality assurance Our services with IPMVP Sign the energetic performance contract Establish an M&V plan Collect the baseline information Schneider Electric - Electrical installation guide 2009 Project installation Measure the reporting, report information and calculate the savings © Schneider Electric - all rights reserved K - Energy Efficiency in electrical distribution K - Energy Efficiency in electrical distribution 6 From returns on investment to sustained performance Once energy audits have been conducted and energy savings measures are put in place with quantified return, it is imperative to implement follow up actions to sustain performance. Without an ongoing cycle of continuous improvement, energy performance tends to revert to a level close to that before the implementation of savings measures. Energy Performance Curve Savings with On-going Services Savings without proper O&M Energy Audit & Consulting Energy Conservation Measures Services Contact The continuous improvement cycle requires the existence, productive use and maintenance of a power monitoring system. Such system will be used for proactive on-going analysis of site energy usage, as well as recommendations for improvements to the electrical distribution system. In order to ensure optimal performance of such system and the best use of the collected data, it is industry common practice to perform the technical and operational services described below. Schneider Electric experts can deliver such services upon request. K34 6.1 Technical support services Power Monitoring systems which are not actively maintained tend to deteriorate for a variety of reasons. b The software can lose communications with devices resulting in lost data. b During the life of any software product upgrades, service packs and patches are released to address issues such as: uncovered bugs, operating system software updates, new hardware product support etc. b Databases which are not maintained can become very large, unwieldy and even corrupt. b The electrical distribution system itself may be changing so that the power monitoring system no longer matches it. b Firmware updates for hardware devices are released periodically to address bugs or provide improved or additional functionality. Remote services © Schneider Electric - all rights reserved Support is provided by email, telephone and VPN or other remote connection from the support center to the customer’s server. Typical services available include: b Toll free hotline for troubleshooting assistance b Senior support representative assigned to site b Free software upgrades during the contract validity b Periodic remote system checks, maintenance and reporting b Remote software upgrades b 24/7 telephonic support Schneider Electric - Electrical installation guide 2009 6 From returns on investment to sustained performance On site services Monthly, quarterly, biannual or annual (as agreed) site visits for system maintenance. Typical services provided are: b Install all PowerLogic software upgrades b Perform firmware upgrades to all PowerLogic monitoring devices b System troubleshooting to the device level b Modification of graphic screens per customer input b Modification of alarms and data logs per customer input b Reconfiguration of system to match changes to the electrical distribution system 6.2 Operational support services These contracts are designed to meet the need for energy analysis and improvement recommendations. Hosted systems In this scenario the user’s usage data is pushed to a Schneider Electric hosted server. The user accesses his information via a web browser. Typical information made available is the following: b Energy consumption data b Carbon emissions data b Degree day analysis b Normalized performance indicators b Regression analysis b CUSUM analysis (Cumulative Sum) On site systems Here the user has a server at one or multiple sites. Different software packages can be in use depending on the need. The services include all the reports offered in the hosted system plus the following: b An up front site energy audit with improvement recommendations b Direct line to an energy consultant b Periodic data analysis, reporting and recommendations (monthly, quarterly, biannual or annual as required) b Consolidated data from multiple facilities b Load profiles b Power quality reporting K35 © Schneider Electric - all rights reserved K - Energy Efficiency in electrical distribution Schneider Electric - Electrical installation guide 2009 Schneider Electric - Electrical installation guide 2009 Chapter L Power factor correction and harmonic filtering Contents 1 Reactive energy and power factor L2 1.1 1.2 1.3 1.4 L2 L2 L3 L4 2 3 Why to improve the power factor? L5 2.1 Reduction in the cost of electricity 2.2 Technical/economic optimization L5 L5 How to improve the power factor? L7 3.1 Theoretical principles 3.2 By using what equipment? 3.3 The choice between a fixed or automatically-regulated bank of capacitors L7 L7 L9 4 Where to install power factor correction capacitors? L10 4.1 Global compensation 4.2 Compensation by sector 4.3 Individual compensation L10 L10 L11 5 How to decide the optimum level of compensation? L12 5.1 General method 5.2 Simplified method 5.3 Method based on the avoidance of tariff penalties 5.4 Method based on reduction of declared maximum apparent power (kVA) L12 L12 L14 6 7 8 9 Compensation at the terminals of a transformer L15 6.1 Compensation to increase the available active power output 6.2 Compensation of reactive energy absorbed by the transformer L15 L16 Power factor correction of induction motors L18 7.1 Connection of a capacitor bank and protection settings 7.2 How self-excitation of an induction motor can be avoided L18 L19 Example of an installation before and after power-factor correction L20 The effects of harmonics L21 9.1 Problems arising from power-system harmonics 9.2 Possible solutions 9.3 Choosing the optimum solution L21 L21 L23 10 Implementation of capacitor banks L24 10.1 Capacitor elements 10.2 Choice of protection, control devices and connecting cables L24 L25 L14 L1 © Schneider Electric - all rights reserved The nature of reactive energy Equipment and appliances requiring reactive energy The power factor Practical values of power factor Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 1 Reactive energy and power factor Alternating current systems supply two forms of energy: b “Active” energy measured in kilowatt hours (kWh) which is converted into mechanical work, heat, light, etc b “Reactive” energy, which again takes two forms: v “Reactive” energy required by inductive circuits (transformers, motors, etc.), v “Reactive” energy supplied by capacitive circuits (cable capacitance, power capacitors, etc) 1.1 The nature of reactive energy All inductive (i.e. electromagnetic) machines and devices that operate on AC systems convert electrical energy from the power system generators into mechanical work and heat. This energy is measured by kWh meters, and is referred to as “active” or “wattful” energy. In order to perform this conversion, magnetic fields have to be established in the machines, and these fields are associated with another form of energy to be supplied from the power system, known as “reactive” or “wattless” energy. The reason for this is that inductive circuit cyclically absorbs energy from the system (during the build-up of the magnetic fields) and re-injects that energy into the system (during the collapse of the magnetic fields) twice in every power-frequency cycle. An exactly similar phenomenon occurs with shunt capacitive elements in a power system, such as cable capacitance or banks of power capacitors, etc. In this case, energy is stored electrostatically. The cyclic charging and discharging of capacitive circuit reacts on the generators of the system in the same manner as that described above for inductive circuit, but the current flow to and from capacitive circuit in exact phase opposition to that of the inductive circuit. This feature is the basis on which power factor correction schemes depend. It should be noted that while this “wattless” current (more accurately, the “wattless” component of a load current) does not draw power from the system, it does cause power losses in transmission and distribution systems by heating the conductors. In practical power systems, “wattless” components of load currents are invariably inductive, while the impedances of transmission and distribution systems are predominantly inductively reactive. The combination of inductive current passing through an inductive reactance produces the worst possible conditions of voltage drop (i.e. in direct phase opposition to the system voltage). For these reasons (transmission power losses and voltage drop), the power-supply authorities reduce the amount of “wattless” (inductive) current as much as possible. “Wattless” (capacitive) currents have the reverse effect on voltage levels and produce voltage-rises in power systems. The power (kW) associated with “active” energy is usually represented by the letter P. The reactive power (kvar) is represented by Q. Inductively-reactive power is conventionally positive (+ Q) while capacitively-reactive power is shown as a negative quantity (- Q). The apparent power S (kVA) is a combination of P and Q (see Fig. L1). L2 Sub-clause 1.3 shows the relationship between P, Q, and S. S (kVA) Q (kvar) P (kW) © Schneider Electric - all rights reserved Fig. L1 : An electric motor requires active power P and reactive power Q from the power system 1.2 Equipement and appliances requiring reactive energy Fig. L2 : Power consuming items that also require reactive energy All AC equipement and appliances that include electromagnetic devices, or depend on magnetically-coupled windings, require some degree of reactive current to create magnetic flux. The most common items in this class are transformers and reactors, motors and discharge lamps (with magnetic ballasts) (see Fig. L2). The proportion of reactive power (kvar) with respect to active power (kW) when an item of equipement is fully loaded varies according to the item concerned being: b 65-75% for asynchronous motors b 5-10% for transformers Schneider Electric - Electrical installation guide 2009 The power factor is the ratio of kW to kVA. The closer the power factor approaches its maximum possible value of 1, the greater the benefit to consumer and supplier. PF = P (kW) / S (kVA) P = Active power S = Apparent power 1 Reactive energy and power factor 1.3 The power factor Definition of power factor The power factor of a load, which may be a single power-consuming item, or a number of items (for example an entire installation), is given by the ratio of P/S i.e. kW divided by kVA at any given moment. The value of a power factor will range from 0 to 1. If currents and voltages are perfectly sinusoidal signals, power factor equals cos ϕ. A power factor close to unity means that the reactive energy is small compared with the active energy, while a low value of power factor indicates the opposite condition. Power vector diagram b Active power P (in kW) v Single phase (1 phase and neutral): P = V I cos ϕ v Single phase (phase to phase): P = U I cos ϕ v Three phase (3 wires or 3 wires + neutral): P = 3U I cos ϕ b Reactive power Q (in kvar) v Single phase (1 phase and neutral): P = V I sin ϕ v Single phase (phase to phase): Q = U I sin ϕ v Three phase (3 wires or 3 wires + neutral): P = 3 U I sin ϕ b Apparent power S (in kVA) v Single phase (1 phase and neutral): S = V I v Single phase (phase to phase): S = U I v Three phase (3 wires or 3 wires + neutral): P = 3 U I where: V = Voltage between phase and neutral U = Voltage between phases I = Line current ϕ = Phase angle between vectors V and I. v For balanced and near-balanced loads on 4-wire systems Current and voltage vectors, and derivation of the power diagram The power “vector” diagram is a useful artifice, derived directly from the true rotating vector diagram of currents and voltage, as follows: The power-system voltages are taken as the reference quantities, and one phase only is considered on the assumption of balanced 3-phase loading. The reference phase voltage (V) is co-incident with the horizontal axis, and the current (I) of that phase will, for practically all power-system loads, lag the voltage by an angle ϕ. L3 The component of I which is in phase with V is the “wattful” component of I and is equal to I cos ϕ, while VI cos ϕ equals the active power (in kW) in the circuit, if V is expressed in kV. The component of I which lags 90 degrees behind V is the wattless component of I and is equal to I sin ϕ, while VI sin ϕ equals the reactive power (in kvar) in the circuit, if V is expressed in kV. If the vector I is multiplied by V, expressed in kV, then VI equals the apparent power (in kVA) for the circuit. The simple formula is obtained: S2 = P2 + Q2 The above kW, kvar and kVA values per phase, when multiplied by 3, can therefore conveniently represent the relationships of kVA, kW, kvar and power factor for a total 3-phase load, as shown in Figure L3 . ϕ V P = VI cos ϕ (kW) S = VI (kVA) Q = VI sin ϕ (kvar) Fig. L3 : Power diagram Schneider Electric - Electrical installation guide 2009 P = Active power Q = Reactive power S = Apparent power © Schneider Electric - all rights reserved L - Power factor correction and harmonic filtering 1 Reactive energy and power factor L - Power factor correction and harmonic filtering An example of power calculations (see Fig. L4 ) Type of circuit Apparent power Active power S (kVA) P (kW) Single-phase (phase and neutral) S = VI Single-phase (phase to phase) Example 5 kW of load cos ϕ = 0.5 S = UI 10 kVA Three phase 3-wires or 3-wires + neutral S = 3 UI Example Motor Pn = 51 kW 65 kVA cos ϕ = 0.86 ρ = 0.91 (motor efficiency) P = VI cos ϕ P = UI cos ϕ 5 kW Reactive power Q (kvar) Q = VI sin ϕ Q = UI sin ϕ 8.7 kvar P = 3 UI cos ϕ Q = 3 UI sin ϕ 56 kW 33 kvar Fig. L4 : Example in the calculation of active and reactive power 1.4 Practical values of power factor The calculations for the three-phase example above are as follows: Pn = delivered shaft power = 51 kW P = active power consumed Pn 51 P= = = 56 kW ρ 0.91 S = apparent power P 56 S= = = 65 kVA cos ϕ 0.86 So that, on referring to diagram Figure L5 or using a pocket calculator, the value of tan ϕ corresponding to a cos ϕ of 0.86 is found to be 0.59 Q = P tan ϕ = 56 x 0.59 = 33 kvar (see Figure L15). Alternatively Q = S2 - P2 = 652 - 562 = 33 kvar L4 Average power factor values for the most commonly-used equipment and appliances (see Fig. L6) Equipment and appliances b Common loaded at induction motor ϕ P = 56 kW Q = 33 kvar S= 65 kV © Schneider Electric - all rights reserved A Fig. L5 : Calculation power diagram 0% 25% 50% 75% 100% b Incandescent lamps b Fluorescent lamps (uncompensated) b Fluorescent lamps (compensated) b Discharge lamps b Ovens using resistance elements b Induction heating ovens (compensated) b Dielectric type heating ovens b Resistance-type soldering machines b Fixed 1-phase arc-welding set b Arc-welding motor-generating set b Arc-welding transformer-rectifier set b Arc furnace cos ϕ 0.17 0.55 0.73 0.80 0.85 1.0 0.5 0.93 0.4 to 0.6 1.0 0.85 0.85 0.8 to 0.9 0.5 0.7 to 0.9 0.7 to 0.8 0.8 Fig. L6 : Values of cos ϕ and tan ϕ for commonly-used equipment Schneider Electric - Electrical installation guide 2009 tan ϕ 5.80 1.52 0.94 0.75 0.62 0 1.73 0.39 2.29 to 1.33 0 0.62 0.62 0.75 to 0.48 1.73 1.02 to 0.48 1.02 to 0.75 0.75 L - Power factor correction and harmonic filtering 2 Why to improve the power factor? An improvement of the power factor of an installation presents several technical and economic advantages, notably in the reduction of electricity bills 2.1 Reduction in the cost of electricity Good management in the consumption of reactive energy brings economic advantages. These notes are based on an actual tariff structure commonly applied in Europe, designed to encourage consumers to minimize their consumption of reactive energy. The installation of power-factor correction capacitors on installations permits the consumer to reduce his electricity bill by maintaining the level of reactive-power consumption below a value contractually agreed with the power supply authority. In this particular tariff, reactive energy is billed according to the tan ϕ criterion. As previously noted: tan ϕ = Q (kvarh) P (kWh) The power supply authority delivers reactive energy for free: b If the reactive energy represents less than 40% of the active energy (tan ϕ < 0.4) for a maximum period of 16 hours each day (from 06-00 h to 22-00 h) during the most-heavily loaded period (often in winter) b Without limitation during light-load periods in winter, and in spring and summer. During the periods of limitation, reactive energy consumption exceeding 40% of the active energy (i.e. tan ϕ > 0.4) is billed monthly at the current rates. Thus, the quantity of reactive energy billed in these periods will be: kvarh (to be billed) = kWh (tan ϕ > 0.4) where: v kWh is the active energy consumed during the periods of limitation v kWh tan ϕ is the total reactive energy during a period of limitation v 0.4 kWh is the amount of reactive energy delivered free during a period of limitation tan ϕ = 0.4 corresponds to a power factor of 0.93 so that, if steps are taken to ensure that during the limitation periods the power factor never falls below 0.93, the consumer will have nothing to pay for the reactive power consumed. Against the financial advantages of reduced billing, the consumer must balance the cost of purchasing, installing and maintaining the power factor improvement capacitors and controlling switchgear, automatic control equipment (where stepped levels of compensation are required) together with the additional kWh consumed by the dielectric losses of the capacitors, etc. It may be found that it is more economic to provide partial compensation only, and that paying for some of the reactive energy consumed is less expensive than providing 100% compensation. The question of power-factor correction is a matter of optimization, except in very simple cases. 2.2 Technical/economic optimization A high power factor allows the optimization of the components of an installation. Overating of certain equipment can be avoided, but to achieve the best results, the correction should be effected as close to the individual inductive items as possible. Reduction of cable size Figure L7 shows the required increase in the size of cables as the power factor is reduced from unity to 0.4, for the same active power transmitted. Multiplying factor for the cross-sectional area of the cable core(s) cos ϕ 1 1.25 1.67 2.5 1 0.8 0.6 0.4 Fig. L7 : Multiplying factor for cable size as a function of cos ϕ Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Power factor improvement allows the use of smaller transformers, switchgear and cables, etc. as well as reducing power losses and voltage drop in an installation L5 L - Power factor correction and harmonic filtering 2 Why to improve the power factor? Reduction of losses (P, kW) in cables Losses in cables are proportional to the current squared, and are measured by the kWh meter of the installation. Reduction of the total current in a conductor by 10% for example, will reduce the losses by almost 20%. Reduction of voltage drop Power factor correction capacitors reduce or even cancel completely the (inductive) reactive current in upstream conductors, thereby reducing or eliminating voltage drops. Note: Over compensation will produce a voltage rise at the capacitor level. Increase in available power By improving the power factor of a load supplied from a transformer, the current through the transformer will be reduced, thereby allowing more load to be added. In practice, it may be less expensive to improve the power factor (1), than to replace the transformer by a larger unit. This matter is further elaborated in clause 6. © Schneider Electric - all rights reserved L6 (1) Since other benefits are obtained from a high value of power factor, as previously noted. Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 3 How to improve the power factor? Improving the power factor of an installation requires a bank of capacitors which acts as a source of reactive energy. This arrangement is said to provide reactive energy compensation a) Reactive current components only flow pattern IL - IC IC C IL IL R L Load IC C IL IL R L Load c) With load current added to case (b) IR IC C IL IR IR + IL L An inductive load having a low power factor requires the generators and transmission/distribution systems to pass reactive current (lagging the system voltage by 90 degrees) with associated power losses and exaggerated voltage drops, as noted in sub-clause 1.1. If a bank of shunt capacitors is added to the load, its (capacitive) reactive current will take the same path through the power system as that of the load reactive current. Since, as pointed out in sub-clause 1.1, this capacitive current Ic (which leads the system voltage by 90 degrees) is in direct phase opposition to the load reactive current (IL), the two components flowing through the same path will cancel each other, such that if the capacitor bank is sufficiently large and Ic = IL there will be no reactive current flow in the system upstream of the capacitors. This is indicated in Figure L8 (a) and (b) which show the flow of the reactive components of current only. In this figure: R represents the active-power elements of the load L represents the (inductive) reactive-power elements of the load C represents the (capacitive) reactive-power elements of the power-factor correction equipment (i.e. capacitors). It will be seen from diagram (b) of Figure L9, that the capacitor bank C appears to be supplying all the reactive current of the load. For this reason, capacitors are sometimes referred to as “generators of lagging vars”. In diagram (c) of Figure L9, the active-power current component has been added, and shows that the (fully-compensated) load appears to the power system as having a power factor of 1. b) When IC = IL, all reactive power is supplied from the capacitor bank IL - IC = 0 3.1 Theoretical principles R In general, it is not economical to fully compensate an installation. Figure L9 uses the power diagram discussed in sub-clause 1.3 (see Fig. L3) to illustrate the principle of compensation by reducing a large reactive power Q to a smaller value Q’ by means of a bank of capacitors having a reactive power Qc. In doing so, the magnitude of the apparent power S is seen to reduce to S’. Example: A motor consumes 100 kW at a power factor of 0.75 (i.e. tan ϕ = 0.88). To improve the power factor to 0.93 (i.e. tan ϕ = 0.4), the reactive power of the capacitor bank must be : Qc = 100 (0.88 - 0.4) = 48 kvar The selected level of compensation and the calculation of rating for the capacitor bank depend on the particular installation. The factors requiring attention are explained in a general way in clause 5, and in clauses 6 and 7 for transformers and motors. Load Fig. L8 : Showing the essential features of power-factor correction L7 Note: Before starting a compensation project, a number of precautions should be observed. In particular, oversizing of motors should be avoided, as well as the noload running of motors. In this latter condition, the reactive energy consumed by a motor results in a very low power factor (≈ 0.17); this is because the kW taken by the motor (when it is unloaded) are very small. P ϕ' ϕ Q' S' Q 3.2 By using what equipment? Compensation at LV Qc Fig. L9 : Diagram showing the principle of compensation: Qc = P (tan ϕ - tan ϕ’) At low voltage, compensation is provided by: b Fixed-value capacitor b Equipment providing automatic regulation, or banks which allow continuous adjustment according to requirements, as loading of the installation changes Note: When the installed reactive power of compensation exceeds 800 kvar, and the load is continuous and stable, it is often found to be economically advantageous to instal capacitor banks at the medium voltage level. © Schneider Electric - all rights reserved S Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering Compensation can be carried out by a fixed value of capacitance in favourable circumstances 3 How to improve the power factor? Fixed capacitors (see Fig. L10) This arrangement employs one or more capacitor(s) to form a constant level of compensation. Control may be: b Manual: by circuit-breaker or load-break switch b Semi-automatic: by contactor b Direct connection to an appliance and switched with it These capacitors are applied: b At the terminals of inductive devices (motors and transformers) b At busbars supplying numerous small motors and inductive appliance for which individual compensation would be too costly b In cases where the level of load is reasonably constant Fig. L10 : Example of fixed-value compensation capacitors Compensation is more-commonly effected by means of an automatically-controlled stepped bank of capacitors © Schneider Electric - all rights reserved L8 Automatic capacitor banks (see Fig. L11) This kind of equipment provides automatic control of compensation, maintaining the power factor within close limits around a selected level. Such equipment is applied at points in an installation where the active-power and/or reactive-power variations are relatively large, for example: b At the busbars of a general power distribution board b At the terminals of a heavily-loaded feeder cable Fig. L11 : Example of automatic-compensation-regulating equipment Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 3 How to improve the power factor? Automatically-regulated banks of capacitors allow an immediate adaptation of compensation to match the level of load The principles of, and reasons, for using automatic compensation A bank of capacitors is divided into a number of sections, each of which is controlled by a contactor. Closure of a contactor switches its section into parallel operation with other sections already in service. The size of the bank can therefore be increased or decreased in steps, by the closure and opening of the controlling contactors. A control relay monitors the power factor of the controlled circuit(s) and is arranged to close and open appropriate contactors to maintain a reasonably constant system power factor (within the tolerance imposed by the size of each step of compensation). The current transformer for the monitoring relay must evidently be placed on one phase of the incoming cable which supplies the circuit(s) being controlled, as shown in Figure L12. A Varset Fast capacitor bank is an automatic power factor correction equipment including static contactors (thyristors) instead of usual contactors. Static correction is particularly suitable for a certain number of installations using equipment with fast cycle and/or sensitive to transient surges. The advantages of static contactors are : b Immediate response to all power factor fluctuation (response time 2 s or 40 ms according to regulator option) b Unlimited number of operations b Elimination of transient phenomena on the network on capacitor switching b Fully silent operation By closely matching compensation to that required by the load, the possibility of producing overvoltages at times of low load will be avoided, thereby preventing an overvoltage condition, and possible damage to appliances and equipment. Overvoltages due to excessive reactive compensation depend partly on the value of source impedance. CT In / 5 A cl 1 Varmetric relay L9 Fig. L12 : The principle of automatic-compensation control 3.3 The choice between a fixed or automaticallyregulated bank of capacitors Where the kvar rating of the capacitors is less than, or equal to 15% of the supply transformer rating, a fixed value of compensation is appropriate. Above the 15% level, it is advisable to install an automatically-controlled bank of capacitors. The location of low-voltage capacitors in an installation constitutes the mode of compensation, which may be global (one location for the entire installation), partial (section-by-section), local (at each individual device), or some combination of the latter two. In principle, the ideal compensation is applied at a point of consumption and at the level required at any instant. In practice, technical and economic factors govern the choice. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Commonly-applied rules L - Power factor correction and harmonic filtering 4 Where to install correction capacitors? 4.1 Global compensation (see Fig. L13) Where a load is continuous and stable, global compensation can be applied Principle The capacitor bank is connected to the busbars of the main LV distribution board for the installation, and remains in service during the period of normal load. Advantages The global type of compensation: b Reduces the tariff penalties for excessive consumption of kvars b Reduces the apparent power kVA demand, on which standing charges are usually based b Relieves the supply transformer, which is then able to accept more load if necessary Comments b Reactive current still flows in all conductors of cables leaving (i.e. downstream of) the main LV distribution board b For the above reason, the sizing of these cables, and power losses in them, are not improved by the global mode of compensation. no.1 M M M M L10 Fig. L13 : Global compensation Compensation by sector is recommended when the installation is extensive, and where the load/time patterns differ from one part of the installation to another 4.2 Compensation by sector (see Fig. L14) Principle Capacitor banks are connected to busbars of each local distribution board, as shown in Figure L14. A significant part of the installation benefits from this arrangement, notably the feeder cables from the main distribution board to each of the local distribution boards at which the compensation measures are applied. Advantages The compensation by sector: b Reduces the tariff penalties for excessive consumption of kvars b Reduces the apparent power kVA demand, on which standing charges are usually based b Relieves the supply transformer, which is then able to accept more load if necessary b The size of the cables supplying the local distribution boards may be reduced, or will have additional capacity for possible load increases b Losses in the same cables will be reduced © Schneider Electric - all rights reserved no. 1 no. 2 no. 2 M M Fig. L14 : Compensation by sector M M Comments b Reactive current still flows in all cables downstream of the local distribution boards b For the above reason, the sizing of these cables, and the power losses in them, are not improved by compensation by sector b Where large changes in loads occur, there is always a risk of overcompensation and consequent overvoltage problems Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 4 Where to install correction capacitors? Individual compensation should be considered when the power of motor is significant with respect to power of the installation 4.3 Individual compensation Principle Capacitors are connected directly to the terminals of inductive circuit (notably motors, see further in Clause 7). Individual compensation should be considered when the power of the motor is significant with respect to the declared power requirement (kVA) of the installation. The kvar rating of the capacitor bank is in the order of 25% of the kW rating of the motor. Complementary compensation at the origin of the installation (transformer) may also be beneficial. Advantages Individual compensation: b Reduces the tariff penalties for excessive consumption of kvars b Reduces the apparent power kVA demand b Reduces the size of all cables as well as the cable losses Comments b Significant reactive currents no longer exist in the installation © Schneider Electric - all rights reserved L11 Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 5 How to decide the optimum level of compensation? 5.1 General method Listing of reactive power demands at the design stage This listing can be made in the same way (and at the same time) as that for the power loading described in chapter A. The levels of active and reactive power loading, at each level of the installation (generally at points of distribution and subdistribution of circuits) can then be determined. Technical-economic optimization for an existing installation The optimum rating of compensation capacitors for an existing installation can be determined from the following principal considerations: b Electricity bills prior to the installation of capacitors b Future electricity bills anticipated following the installation of capacitors b Costs of: v Purchase of capacitors and control equipment (contactors, relaying, cabinets, etc.) v Installation and maintenance costs v Cost of dielectric heating losses in the capacitors, versus reduced losses in cables, transformer, etc., following the installation of capacitors Several simplified methods applied to typical tariffs (common in Europe) are shown in sub-clauses 5.3 and 5.4. 5.2 Simplified method General principle An approximate calculation is generally adequate for most practical cases, and may be based on the assumption of a power factor of 0.8 (lagging) before compensation. In order to improve the power factor to a value sufficient to avoid tariff penalties (this depends on local tariff structures, but is assumed here to be 0.93) and to reduce losses, volt-drops, etc. in the installation, reference can be made to Figure L15 next page. From the figure, it can be seen that, to raise the power factor of the installation from 0.8 to 0.93 will require 0.355 kvar per kW of load. The rating of a bank of capacitors at the busbars of the main distribution board of the installation would be Q (kvar) = 0.355 x P (kW). L12 This simple approach allows a rapid determination of the compensation capacitors required, albeit in the global, partial or independent mode. Example It is required to improve the power factor of a 666 kVA installation from 0.75 to 0.928. The active power demand is 666 x 0.75 = 500 kW. In Figure L15, the intersection of the row cos ϕ = 0.75 (before correction) with the column cos ϕ = 0.93 (after correction) indicates a value of 0.487 kvar of compensation per kW of load. For a load of 500 kW, therefore, 500 x 0.487 = 244 kvar of capacitive compensation is required. © Schneider Electric - all rights reserved Note: this method is valid for any voltage level, i.e. is independent of voltage. Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering Before compensation tan ϕ 2.29 2.22 2.16 2.10 2.04 1.98 1.93 1.88 1.83 1.78 1.73 1.69 1.64 1.60 1.56 1.52 1.48 1.44 1.40 1.37 1.33 1.30 1.27 1.23 1.20 1.17 1.14 1.11 1.08 1.05 1.02 0.99 0.96 0.94 0.91 0.88 0.86 0.83 0.80 0.78 0.75 0.72 0.70 0.67 0.65 0.62 0.59 0.57 0.54 0.51 0.48 cos ϕ 0.40 0.41 0.42 0.43 0.44 0.45 0.46 0.47 0.48 0.49 0.50 0.51 0.52 0.53 0.54 0.55 0.56 0.57 0.58 0.59 0.60 0.61 0.62 0.63 0.64 0.65 0.66 0.67 0.68 0.69 0.70 0.71 0.72 0.73 0.74 0.75 0.76 0.77 0.78 0.79 0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 5 How to decide the optimum level of compensation? kvar rating of capacitor bank to install per kW of load, to improve cos ϕ (the power factor) or tan ϕ, to a given value tan ϕ cos ϕ 0.75 0.59 0.48 0.46 0.43 0.40 0.36 0.33 0.29 0.25 0.20 0.14 0.80 1.557 1.474 1.413 1.356 1.290 1.230 1.179 1.130 1.076 1.030 0.982 0.936 0.894 0.850 0.809 0.769 0.730 0.692 0.665 0.618 0.584 0.549 0.515 0.483 0.450 0.419 0.388 0.358 0.329 0.299 0.270 0.242 0.213 0.186 0.159 0.132 0.105 0.079 0.053 0.026 0.86 1.691 1.625 1.561 1.499 1.441 1.384 1.330 1.278 1.228 1.179 1.232 1.087 1.043 1.000 0.959 0.918 0.879 0.841 0.805 0.768 0.733 0.699 0.665 0.633 0.601 0.569 0.538 0.508 0.478 0.449 0.420 0.392 0.364 0.336 0.309 0.82 0.255 0.229 0.202 0.176 0.150 0.124 0.098 0.072 0.046 0.020 0.90 1.805 1.742 1.681 1.624 1.558 1.501 1.446 1.397 1.343 1.297 1.248 1.202 1.160 1.116 1.075 1.035 0.996 0.958 0.921 0.884 0.849 0.815 0.781 0.749 0.716 0.685 0.654 0.624 0.595 0.565 0.536 0.508 0.479 0.452 0.425 0.398 0.371 0.345 0.319 0.292 0.266 0.240 0.214 0.188 0.162 0.136 0.109 0.083 0.054 0.028 0.91 1.832 1.769 1.709 1.651 1.585 1.532 1.473 1.425 1.370 1.326 1.276 1.230 1.188 1.144 1.103 1.063 1.024 0.986 0.949 0.912 0.878 0.843 0.809 0.777 0.744 0.713 0.682 0.652 0.623 0.593 0.564 0.536 0.507 0.480 0.453 0.426 0.399 0.373 0.347 0.320 0.294 0.268 0.242 0.216 0.190 0.164 0.140 0.114 0.085 0.059 0.031 0.92 1.861 1.798 1.738 1.680 1.614 1.561 1.502 1.454 1.400 1.355 1.303 1.257 1.215 1.171 1.130 1.090 1.051 1.013 0.976 0.939 0.905 0.870 0.836 0.804 0.771 0.740 0.709 0.679 0.650 0.620 0.591 0.563 0.534 0.507 0.480 0.453 0.426 0.400 0.374 0.347 0.321 0.295 0.269 0.243 0.217 0.191 0.167 0.141 0.112 0.086 0.058 0.93 1.895 1.831 1.771 1.713 1.647 1.592 1.533 1.485 1.430 1.386 1.337 1.291 1.249 1.205 1.164 1.124 1.085 1.047 1.010 0.973 0.939 0.904 0.870 0.838 0.805 0.774 0.743 0.713 0.684 0.654 0.625 0.597 0.568 0.541 0.514 0.487 0.460 0.434 0.408 0.381 0.355 0.329 0.303 0.277 0.251 0.225 0.198 0.172 0.143 0.117 0.089 0.94 1.924 1.840 1.800 1.742 1.677 1.628 1.567 1.519 1.464 1.420 1.369 1.323 1.281 1.237 1.196 1.156 1.117 1.079 1.042 1.005 0.971 0.936 0.902 0.870 0.837 0.806 0.775 0.745 0.716 0.686 0.657 0.629 0.600 0.573 0.546 0.519 0.492 0.466 0.440 0.413 0.387 0.361 0.335 0.309 0.283 0.257 0.230 0.204 0.175 0.149 0.121 0.95 1.959 1.896 1.836 1.778 1.712 1.659 1.600 1.532 1.497 1.453 1.403 1.357 1.315 1.271 1.230 1.190 1.151 1.113 1.076 1.039 1.005 0.970 0.936 0.904 0.871 0.840 0.809 0.779 0.750 0.720 0.691 0.663 0.634 0.607 0.580 0.553 0.526 0.500 0.474 0.447 0.421 0.395 0.369 0.343 0.317 0.291 0.264 0.238 0.209 0.183 0.155 0.96 1.998 1.935 1.874 1.816 1.751 1.695 1.636 1.588 1.534 1.489 1.441 1.395 1.353 1.309 1.268 1.228 1.189 1.151 1.114 1.077 1.043 1.008 0.974 0.942 0.909 0.878 0.847 0.817 0.788 0.758 0.729 0.701 0.672 0.645 0.618 0.591 0.564 0.538 0.512 0.485 0.459 0.433 0.407 0.381 0.355 0.329 0.301 0.275 0.246 0.230 0.192 0.97 2.037 1.973 1.913 1.855 1.790 1.737 1.677 1.629 1.575 1.530 1.481 1.435 1.393 1.349 1.308 1.268 1.229 1.191 1.154 1.117 1.083 1.048 1.014 0.982 0.949 0.918 0.887 0.857 0.828 0.798 0.769 0.741 0.712 0.685 0.658 0.631 0.604 0.578 0.552 0.525 0.499 0.473 0.447 0.421 0.395 0.369 0.343 0.317 0.288 0.262 0.234 0.98 2.085 2.021 1.961 1.903 1.837 1.784 1.725 1.677 1.623 1.578 1.529 1.483 1.441 1.397 1.356 1.316 1.277 1.239 1.202 1.165 1.131 1.096 1.062 1.030 0.997 0.966 0.935 0.905 0.876 0.840 0.811 0.783 0.754 0.727 0.700 0.673 0.652 0.620 0.594 0.567 0.541 0.515 0.489 0.463 0.437 0.417 0.390 0.364 0.335 0.309 0.281 0.99 2.146 2.082 2.022 1.964 1.899 1.846 1.786 1.758 1.684 1.639 1.590 1.544 1.502 1.458 1.417 1.377 1.338 1.300 1.263 1.226 1.192 1.157 1.123 1.091 1.058 1.007 0.996 0.966 0.937 0.907 0.878 0.850 0.821 0.794 0.767 0.740 0.713 0.687 0.661 0.634 0.608 0.582 0.556 0.530 0.504 0.478 0.450 0.424 0.395 0.369 0.341 0.0 1 2.288 2.225 2.164 2.107 2.041 1.988 1.929 1.881 1.826 1.782 1.732 1.686 1.644 1.600 1.559 1.519 1.480 1.442 1.405 1.368 1.334 1.299 1.265 1.233 1.200 1.169 1.138 1.108 1.079 1.049 1.020 0.992 0.963 0.936 0.909 0.882 0.855 0.829 0.803 0.776 0.750 0.724 0.698 0.672 0.645 0.620 0.593 0.567 0.538 0.512 0.484 L13 Value selected as an example on section 5.2 Fig. L15 : kvar to be installed per kW of load, to improve the power factor of an installation Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Value selected as an example on section 5.4 L - Power factor correction and harmonic filtering 5 How to decide the optimum level of compensation? In the case of certain (common) types of tariff, an examination of several bills covering the most heavily-loaded period of the year allows determination of the kvar level of compensation required to avoid kvarh (reactiveenergy) charges. The pay-back period of a bank of power-factor-correction capacitors and associated equipment is generally about 18 months 5.3 Method based on the avoidance of tariff penalties The following method allows calculation of the rating of a proposed capacitor bank, based on billing details, where the tariff structure corresponds with (or is similar to) the one described in sub-clause 2.1 of this chapter. The method determines the minimum compensation required to avoid these charges which are based on kvarh consumption. The procedure is as follows: b Refer to the bills covering consumption for the 5 months of winter (in France these are November to March inclusive). Note: in tropical climates the summer months may constitute the period of heaviest loading and highest peaks (owing to extensive air conditioning loads) so that a consequent variation of high-tariff periods is necessary in this case. The remainder of this example will assume Winter conditions in France. b Identify the line on the bills referring to “reactive-energy consumed” and “kvarh to be charged”. Choose the bill which shows the highest charge for kvarh (after checking that this was not due to some exceptional situation). For example: 15,966 kvarh in January. b Evaluate the total period of loaded operation of the installation for that month, for instance: 220 hours (22 days x 10 hours). The hours which must be counted are those occurring during the heaviest load and the highest peak loads occurring on the power system. These are given in the tariff documents, and are (commonly) during a 16-hour period each day, either from 06.00 h to 22.00 h or from 07.00 h to 23.00 h according to the region. Outside these periods, no charge is made for kvarh consumption. b The necessary value of compensation in kvar = kvarh billed/number of hours of operation(1) = Qc The rating of the installed capacitor bank is generally chosen to be slightly larger than that calculated. Certain manufacturers can provide “slide rules” especially designed to facilitate these kinds of calculation, according to particular tariffs. These devices and accompanying documentation advice on suitable equipment and control schemes, as well as drawing attention to constraints imposed by harmonic voltages on the power system. Such voltages require either over dimensioned capacitors (in terms of heat-dissipation, voltage and current ratings) and/or harmonic-suppression inductors or filters. L14 For 2-part tariffs based partly on a declared value of kVA, Figure L17 allows determination of the kvar of compensation required to reduce the value of kVA declared, and to avoid exceeding it P = 85.4 kW ϕ' ϕ © Schneider Electric - all rights reserved Q' Cos ϕ = 0.7 Cos ϕ'= 0.95 S = 122 kVA S' = 90 kVA Q = 87.1 kvar Qc = 56 kvar Q' = 28.1 kvar S' Q S Qc Fig. L16 : Reduction of declared maximum kVA by powerfactor improvement 5.4 Method based on reduction of declared maximum apparent power (kVA) For consumers whose tariffs are based on a fixed charge per kVA declared, plus a charge per kWh consumed, it is evident that a reduction in declared kVA would be beneficial. The diagram of Figure L16 shows that as the power factor improves, the kVA value diminishes for a given value of kW (P). The improvement of the power factor is aimed at (apart from other advantages previously mentioned) reducing the declared level and never exceeding it, thereby avoiding the payment of an excessive price per kVA during the periods of excess, and/or tripping of the the main circuitbreaker. Figure L15 (previous page) indicates the value of kvar of compensation per kW of load, required to improve from one value of power factor to another. Example: A supermarket has a declared load of 122 kVA at a power factor of 0.7 lagging, i.e.an active-power load of 85.4 kW. The particular contract for this consumer was based on stepped values of declared kVA (in steps of 6 kVA up to 108 kVA, and 12 kVA steps above that value, this is a common feature in many types of two-part tariff). In the case being considered, the consumer was billed on the basis of 132 kVA. Referring to Figure L15, it can be seen that a 60 kvar bank of capacitors will improve the power factor of the load from 0.7 to 0.95 (0.691 x 85.4 = 59 kvar 85.4 in the figure). The declared value of kVA will then be = 90 kVA , i.e. an 0.95 improvement of 30%. (1) In the billing period, during the hours for which reactive energy is charged for the case considered above: 15,996 kvarh Qc = = 73 kvar 220 h Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 6 Compensation at the terminals of a transformer The installation of a capacitor bank can avoid the need to change a transformer in the event of a load increase 6.1 Compensation to increase the available active power output Steps similar to those taken to reduce the declared maximum kVA, i.e. improvement of the load power factor, as discussed in subclause 5.4, will maximise the available transformer capacity, i.e. to supply more active power. Cases can arise where the replacement of a transformer by a larger unit, to overcome a load growth, may be avoided by this means. Figure L17 shows directly the power (kW) capability of fully-loaded transformers at different load power factors, from which the increase of active-power output can be obtained as the value of power factor increases. tan ϕ cos ϕ 0.00 0.20 0.29 0.36 0.43 0.48 0.54 0.59 0.65 0.70 0.75 0.80 0.86 0.91 0.96 1.02 1 0.98 0.96 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.80 0.78 0.76 0.74 0.72 0.70 Nominal rating of transformers (in kVA) 100 160 250 315 400 100 160 250 315 400 98 157 245 309 392 96 154 240 302 384 94 150 235 296 376 92 147 230 290 368 90 144 225 284 360 88 141 220 277 352 86 138 215 271 344 84 134 210 265 336 82 131 205 258 328 80 128 200 252 320 78 125 195 246 312 76 122 190 239 304 74 118 185 233 296 72 115 180 227 288 70 112 175 220 280 500 500 490 480 470 460 450 440 430 420 410 400 390 380 370 360 350 630 630 617 605 592 580 567 554 541 529 517 504 491 479 466 454 441 800 800 784 768 752 736 720 704 688 672 656 640 624 608 592 576 560 1000 1000 980 960 940 920 900 880 860 840 820 800 780 760 740 720 700 1250 1250 1225 1200 1175 1150 1125 1100 1075 1050 1025 1000 975 950 925 900 875 1600 1600 1568 1536 1504 1472 1440 1408 1376 1344 1312 1280 1248 1216 1184 1152 1120 2000 2000 1960 1920 1880 1840 1800 1760 1720 1680 1640 1600 1560 1520 1480 1440 1400 Fig. L17 : Active-power capability of fully-loaded transformers, when supplying loads at different values of power factor Example: (see Fig. L18 ) L15 An installation is supplied from a 630 kVA transformer loaded at 450 kW (P1) with a 450 mean power factor of 0.8 lagging. The apparent power S1 = = 562 kVA 0.8 The corresponding reactive power Q1 = S12 − P12 = 337 kvar The anticipated load increase P2 = 100 kW at a power factor of 0.7 lagging. The apparent power S2 = 100 = 143 kVA The corresponding reactive0.7 power Q2 = S22 − P22 = 102 kvar What is the minimum value of capacitive kvar to be installed, in order to avoid a change of transformer? Total power now to be supplied: P = P1 + P2 = 550 kW Q The maximum reactive power capability of the 630 kVA transformer when delivering 550 kW is: Qm = S2 − P2 Q2 Q P2 S1 S P1 Q1 Qm = 6302 − 5502 = 307 kvar Total reactive power required by the installation before compensation: Q1 + Q2 = 337 + 102 = 439 kvar So that the minimum size of capacitor bank to install: Q m P Fig. L18 : Compensation Q allows the installation-load extension S2 to be added, without the need to replace the existing transformer, the output of which is limited to S Qkvar = 439 - 307 = 132 kvar It should be noted that this calculation has not taken account of load peaks and their duration. The best possible improvement, i.e. correction which attains a power factor of 1 would permit a power reserve for the transformer of 630 - 550 = 80 kW. The capacitor bank would then have to be rated at 439 kvar. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved S2 L - Power factor correction and harmonic filtering 6 Compensation at the terminals of a transformer 6.2 Compensation of reactive energy absorbed by the transformer Where metering is carried out at the MV side of a transformer, the reactive-energy losses in the transformer may need to be compensated (depending on the tariff) Perfect transformer All previous references have been to shunt connected devices such as those used in normal loads, and power factor-correcting capacitor banks etc. The reason for this is that shunt connected equipment requires (by far) the largest quantities of reactive energy in power systems; however, series-connected reactances, such as the inductive reactances of power lines and the leakage reactance of transformer windings, etc., also absorb reactive energy. Leakage reactance Secondary winding Primary winding The nature of transformer inductive reactances Where metering is carried out at the MV side of a transformer, the reactive-energy losses in the transformer may (depending on the tariff) need to be compensated. As far as reactive-energy losses only are concerned, a transformer may be represented by the elementary diagram of Figure L19. All reactance values are referred to the secondary side of the transformer, where the shunt branch represents the magnetizing-current path. The magnetizing current remains practically constant (at about 1.8% of full-load current) from no load to full load, in normal circumstances, i.e. with a constant primary voltage, so that a shunt capacitor of fixed value can be installed at the MV or LV side, to compensate for the reactive energy absorbed. Magnetizing reactance Fig. L19 : Transformer reactances per phase The reactive power absorbed by a transformer cannot be neglected, and can amount to (about) 5% of the transformer rating when supplying its full load. Compensation can be provided by a bank of capacitors. In transformers, reactive power is absorbed by both shunt (magnetizing) and series (leakage flux) reactances. Complete compensation can be provided by a bank of shunt-connected LV capacitors Reactive-power absorption in series-connected (leakage flux) reactance XL A simple illustration of this phenomenon is given by the vector diagram of Figure L20. The reactive-current component through the load = I sin ϕ so that QL = VI sin ϕ. The reactive-current component from the source = I sin ϕ’ so that QE = EI sin ϕ’. It can be seen that E > V and sin ϕ’ > sin ϕ. The difference between EI sin ϕ’ and VI sin ϕ gives the kvar per phase absorbed by XL. It can be shown that this kvar value is equal to I2XL (which is analogous to the I2R active power (kW) losses due to the series resistance of power lines, etc.). From the I2XL formula it is very simple to deduce the kvar absorbed at any load value for a given transformer, as follows: I If per-unit values are used (instead of percentage values) direct multiplication of I and XL can be carried out. XL L16 E Source V Load Example: A 630 kVA transformer with a short-circuit reactance voltage of 4% is fully loaded. What is its reactive-power (kvar) loss? 4% = 0.04 pu Ipu = 1 loss = I2XL = 12 x 0.04 = 0.04 pu kvar E where 1 pu = 630 kVA V IXL ' I I sin I sin ' At half load i.e. I = 0.5 pu the losses will be 0.52 x 0.04 = 0.01 pu = 630 x 0.01 = 6.3 kvar and so on... This example, and the vector diagram of Figure L20 show that: b The power factor at the primary side of a loaded transformer is different (normally lower) than that at the secondary side (due to the absorption of vars) b Full-load kvar losses due to leakage reactance are equal to the transformer percentage reactance (4% reactance means a kvar loss equal to 4% of the kVA rating of the transformer) b kvar losses due to leakage reactance vary according to the current (or kVA loading) squared © Schneider Electric - all rights reserved Fig. L20 : Reactive power absorption by series inductance The 3-phase kvar losses are 630 x 0.04 = 25.2 kvar (or, quite simply, 4% of 630 kVA). Schneider Electric - Electrical installation guide 2009 6 Compensation at the terminals of a transformer To determine the total kvar losses of a transformer the constant magnetizing-current circuit losses (approx. 1.8% of the transformer kVA rating) must be added to the foregoing “series” losses. Figure L21 shows the no-load and full-load kvar losses for typical distribution transformers. In principle, series inductances can be compensated by fixed series capacitors (as is commonly the case for long MV transmission lines). This arrangement is operationally difficult, however, so that, at the voltage levels covered by this guide, shunt compensation is always applied. In the case of MV metering, it is sufficient to raise the power factor to a point where the transformer plus load reactive-power consumption is below the level at which a billing charge is made. This level depends on the tariff, but often corresponds to a tan ϕ value of 0.31 (cos ϕ of 0.955). Rated power (kVA) 100 160 250 315 400 500 630 800 1000 1250 1600 2000 Reactive power (kvar) to be compensated No load Full load 2.5 6.1 3.7 9.6 5.3 14.7 6.3 18.4 7.6 22.9 9.5 28.7 11.3 35.7 20 54.5 23.9 72.4 27.4 94.5 31.9 126 37.8 176 Fig. L21 : Reactive power consumption of distribution transformers with 20 kV primary windings As a matter of interest, the kvar losses in a transformer can be completely compensated by adjusting the capacitor bank to give the load a (slightly) leading power factor. In such a case, all of the kvar of the transformer is being supplied from the capacitor bank, while the input to the MV side of the transformer is at unity power factor, as shown in Figure L22. L17 E (Input voltage) IXL I ϕ V (Load voltage) Load current I0 Compensation current Fig. L22 : Overcompensation of load to completely compensate transformer reactive-power losses In practical terms, therefore, compensation for transformer-absorbed kvar is included in the capacitors primarily intended for powerfactor correction of the load, either globally, partially, or in the individual mode. Unlike most other kvar-absorbing items, the transformer absorption (i.e. the part due to the leakage reactance) changes significantly with variations of load level, so that, if individual compensation is applied to the transformer, then an average level of loading will have to be assumed. Fortunately, this kvar consumption generally forms only a relatively small part of the total reactive power of an installation, and so mismatching of compensation at times of load change is not likely to be a problem. Figure L21 indicates typical kvar loss values for the magnetizing circuit (“no-load kvar” columns), as well as for the total losses at full load, for a standard range of distribution transformers supplied at 20 kV (which include the losses due to the leakage reactance). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved L - Power factor correction and harmonic filtering L - Power factor correction and harmonic filtering 7 Power factor correction of induction motors Individual motor compensation is recommended where the motor power (kVA) is large with respect to the declared power of the installation 7.1 Connection of a capacitor bank and protection settings General precautions Because of the small kW consumption, the power factor of a motor is very low at noload or on light load. The reactive current of the motor remains practically constant at all loads, so that a number of unloaded motors constitute a consumption of reactive power which is generally detrimental to an installation, for reasons explained in preceding sections. Two good general rules therefore are that unloaded motors should be switched off, and motors should not be oversized (since they will then be lightly loaded). Connection The bank of capacitors should be connected directly to the terminals of the motor. Special motors It is recommended that special motors (stepping, plugging, inching, reversing motors, etc.) should not be compensated. Effect on protection settings After applying compensation to a motor, the current to the motor-capacitor combination will be lower than before, assuming the same motor-driven load conditions. This is because a significant part of the reactive component of the motor current is being supplied from the capacitor, as shown in Figure L23. Where the overcurrent protection devices of the motor are located upstream of the motor capacitor connection (and this will always be the case for terminal-connected capacitors), the overcurrent relay settings must be reduced in the ratio: cos ϕ before compensation / cos ϕ after compensation For motors compensated in accordance with the kvar values indicated in Figure L24 (maximum values recommended for avoidance of self-excitation of standard induction motors, as discussed in sub-clause 7.2), the above-mentioned ratio will have a value similar to that indicated for the corresponding motor speed in Figure L25. 3-phase motors 230/400 V Nominal power kvar to be installed Speed of rotation (rpm) kW hp 3000 1500 1000 22 30 6 8 9 30 40 7.5 10 11 37 50 9 11 12.5 45 60 11 13 14 55 75 13 17 18 75 100 17 22 25 90 125 20 25 27 110 150 24 29 33 132 180 31 36 38 160 218 35 41 44 200 274 43 47 53 250 340 52 57 63 280 380 57 63 70 355 482 67 76 86 400 544 78 82 97 450 610 87 93 107 L18 Before compensation After compensation Transformer Power made available Active power Figure L24 : Maximum kvar of power factor correction applicable to motor terminals without risk of self excitation © Schneider Electric - all rights reserved C M Motor M 750 10 12.5 16 17 21 28 30 37 43 52 61 71 79 98 106 117 Reactive power supplied by capacitor Fig. L23 : Before compensation, the transformer supplies all the reactive power; after compensation, the capacitor supplies a large part of the reactive power Speed in rpm 750 1000 1500 3000 Reduction factor 0.88 0.90 0.91 0.93 Fig. L25 : Reduction factor for overcurrent protection after compensation Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering When a capacitor bank is connected to the terminals of an induction motor, it is important to check that the size of the bank is less than that at which self-excitation can occur 7 Power factor correction of induction motors 7.2 How self-excitation of an induction motor can be avoided When a motor is driving a high-inertia load, the motor will continue to rotate (unless deliberately braked) after the motor supply has been switched off. The “magnetic inertia” of the rotor circuit means that an emf will be generated in the stator windings for a short period after switching off, and would normally reduce to zero after 1 or 2 cycles, in the case of an uncompensated motor. Compensation capacitors however, constitute a 3-phase “wattless” load for this decaying emf, which causes capacitive currents to flow through the stator windings. These stator currents will produce a rotating magnetic field in the rotor which acts exactly along the same axis and in the same direction as that of the decaying magnetic field. The rotor flux consequently increases; the stator currents increase; and the voltage at the terminals of the motor increases; sometimes to dangerously-high levels. This phenomenon is known as self-excitation and is one reason why AC generators are not normally operated at leading power factors, i.e. there is a tendency to spontaneously (and uncontrollably) self excite. Notes: 1. The characteristics of a motor being driven by the inertia of the load are not rigorously identical to its no-load characteristics. This assumption, however, is sufficiently accurate for practical purposes. 2. With the motor acting as a generator, the currents circulating are largely reactive, so that the braking (retarding) effect on the motor is mainly due only to the load represented by the cooling fan in the motor. 3. The (almost 90° lagging) current taken from the supply in normal circumstances by the unloaded motor, and the (almost 90° leading) current supplied to the capacitors by the motor acting as a generator, both have the same phase relationship to the terminalvoltage. It is for this reason that the two characteristics may be superimposed on the graph. In order to avoid self-excitation as described above, the kvar rating of the capacitor bank must be limited to the following maximum value: Qc y 0.9 x Io x Un x 3 where Io = the no-load current of the motor and Un = phase-to-phase nominal voltage of the motor in kV. Figure L24 previous page gives appropriate values of Qc corresponding to this criterion. Example A 75 kW, 3,000 rpm, 400 V, 3-phase motor may have a capacitor bank no larger than 17 kvar according to Figure L24. The table values are, in general, too small to adequately compensate the motor to the level of cos ϕ normally required. Additional compensation can, however, be applied to the system, for example an overall bank, installed for global compensation of a number of smaller appliances. L19 High-inertia motors and/or loads In any installation where high-inertia motor driven loads exist, the circuit-breakers or contactors controlling such motors should, in the event of total loss of power supply, be rapidly tripped. If this precaution is not taken, then self excitation to very high voltages is likely to occur, since all other banks of capacitors in the installation will effectively be in parallel with those of the high-inertia motors. Fig. L26 : Connection of the capacitor bank to the motor Closing of the main contactor is commonly subject to the capacitor contactor being previously closed. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved The protection scheme for these motors should therefore include an overvoltage tripping relay, together with reverse-power checking contacts (the motor will feed power to the rest of the installation, until the stored inertial energy is dissipated). If the capacitor bank associated with a high inertia motor is larger than that recommended in Figure L24, then it should be separately controlled by a circuitbreaker or contactor, which trips simultaneously with the main motor-controlling circuit-breaker or contactor, as shown in Figure L26. L - Power factor correction and harmonic filtering 8 Example of an installation before and after power-factor correction Installation before P.F. correction � � � (1) kVA=kW+kvar kVA kW kvar 630 kVA b kvarh are billed heavily above the declared level b Apparent power kVA is significantly greater than the kW demand b The corresponding excess current causes losses (kWh) which are billed b The installation must be over-dimensioned Characteristics of the installation 500 kW cos ϕ = 0.75 b Transformer is overloaded b The power demand is P 500 S= = = 665 kVA cos ϕ 0.75 S = apparent power Installation after P.F. correction ��� kVA=kW+kvar kVA kW 630 kVA Characteristics of the installation 500 kW cos ϕ = 0.928 b Transformer no longer overloaded b The power-demand is 539 kVA b There is 14% spare-transformer capacity available 400 V 400 V b The current flowing into the installation downstream of the circuit breaker is P I= = 960 A 3U cos ϕ b The current flowing into the installation through the circuit breaker is 778 A b The losses in the cables are 7782 = 65% of the former value, 9602 thereby economizing in kWh consumed b Losses in cables are calculated as a function of the current squared: 9602 P=I2R L20 b The consumption of kvarh is v Eliminated, or v Reduced, according to the cos ϕ required b The tariff penalties v For reactive energy where applicable v For the entire bill in some cases are eliminated b The fixed charge based on kVA demand is adjusted to be close to the active power kW demand reduced to cos ϕ = 0.75 b Reactive energy is supplied through the transformer and via the installation wiring b The transformer, circuit breaker, and cables must be over-dimensioned cos ϕ = 0.928 b Reactive energy is supplied by the capacitor bank 250 kvar Capacitor bank rating is 250 kvar in 5 automatically-controlled steps of 50 kvar. © Schneider Electric - all rights reserved cos ϕ = 0.75 workshop cos ϕ = 0.75 workshop Note: In fact, the cos ϕ of the workshop remains at 0.75 but cos ϕ for all the installation upstream of the capacitor bank to the transformer LV terminals is 0.928. As mentioned in Sub-clause 6.2 the cos ϕ at the HV side of the transformer will be slightly lower (2), due to the reactive power losses in the transformer. Fig. K27 : Technical-economic comparison of an installation before and after power-factor correction (1) The arrows denote vector quantities. (2) Particularly in the pre-corrected case. Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 9 The effects of harmonics 9.1 Problems arising from power-system harmonics Equipment which uses power electronics components (variable-speed motor controllers, thyristor-controlled rectifiers, etc.) have considerably increased the problems caused by harmonics in power supply systems. Harmonics have existed from the earliest days of the industry and were (and still are) caused by the non-linear magnetizing impedances of transformers, reactors, fluorescent lamp ballasts, etc. Harmonics on symmetrical 3-phase power systems are generally odd-numbered: 3rd, 5th, 7th, 9th..., and the magnitude decreases as the order of the harmonic increases. A number of features may be used in various ways to reduce specific harmonics to negligible values - total elimination is not possible. In this section, practical means of reducing the influence of harmonics are recommended, with particular reference to capacitor banks. Capacitors are especially sensitive to harmonic components of the supply voltage due to the fact that capacitive reactance decreases as the frequency increases. In practice, this means that a relatively small percentage of harmonic voltage can cause a significant current to flow in the capacitor circuit. The presence of harmonic components causes the (normally sinusoidal) wave form of voltage or current to be distorted; the greater the harmonic content, the greater the degree of distortion. If the natural frequency of the capacitor bank/ power-system reactance combination is close to a particular harmonic, then partial resonance will occur, with amplified values of voltage and current at the harmonic frequency concerned. In this particular case, the elevated current will cause overheating of the capacitor, with degradation of the dielectric, which may result in its eventual failure. Several solutions to these problems are available. This can be accomplished by b Shunt connected harmonic filter and/or harmonic-suppression reactors or b Active power filters or b Hybrid filters Harmonics are taken into account mainly by oversizing capacitors and including harmonicsuppression reactors in series with them 9.2 Possible solutions Passive filter (see Fig. L28) Countering the effects of harmonics The presence of harmonics in the supply voltage results in abnormally high current levels through the capacitors. An allowance is made for this by designing for an r.m.s. value of current equal to 1.3 times the nominal rated current. All series elements, such as connections, fuses, switches, etc., associated with the capacitors are similarly oversized, between 1.3 to 1.5 times nominal rating. L21 Harmonic distortion of the voltage wave frequently produces a “peaky” wave form, in which the peak value of the normal sinusoidal wave is increased. This possibility, together with other overvoltage conditions likely to occur when countering the effects of resonance, as described below, are taken into account by increasing the insulation level above that of “standard” capacitors. In many instances, these two counter measures are all that is necessary to achieve satisfactory operation. Countering the effects of resonance Capacitors are linear reactive devices, and consequently do not generate harmonics. The installation of capacitors in a power system (in which the impedances are predominantly inductive) can, however, result in total or partial resonance occurring at one of the harmonic frequencies. Ihar The harmonic order ho of the natural resonant frequency between the system inductance and the capacitor bank is given by Harmonic generator Filter Fig. L28 : Operation principle of passive filter Ssc Q where Ssc = the level of system short-circuit kVA at the point of connection of the capacitor Q = capacitor bank rating in kvar; and ho = the harmonic order of the natural frequency fo i.e. fo for a 50 Hz system, or fo for a 60 Hz system. 50 60 Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved ho = L - Power factor correction and harmonic filtering 9 The effects of harmonics For example: ho = Ssc may give a value for ho of 2.93 which shows that the Q natural frequency of the capacitor/system-inductance combination is close to the 3rd harmonic frequency of the system. From ho = fo it can be seen that fo = 50 ho = 50 x 2.93 = 146.5 Hz 50 The closer a natural frequency approaches one of the harmonics present on the system, the greater will be the (undesirable) effect. In the above example, strong resonant conditions with the 3rd harmonic component of a distorted wave would certainly occur. In such cases, steps are taken to change the natural frequency to a value which will not resonate with any of the harmonics known to be present. This is achieved by the addition of a harmonic-suppression inductor connected in series with the capacitor bank. Is Ihar On 50 Hz systems, these reactors are often adjusted to bring the resonant frequency of the combination, i.e. the capacitor bank + reactors to 190 Hz. The reactors are adjusted to 228 Hz for a 60 Hz system. These frequencies correspond to a value for ho of 3.8 for a 50 Hz system, i.e. approximately mid-way between the 3rd and 5th harmonics. Iact Active filter Harmonic generator In this arrangement, the presence of the reactor increases the fundamental frequency (50 Hz or 60 Hz) current by a small amount (7-8%) and therefore the voltage across the capacitor in the same proportion. Linear load Fig. L29 : Operation principle of active filter This feature is taken into account, for example, by using capacitors which are designed for 440 V operation on 400 V systems. Active filter (see Fig. L29) Active filters are based on power electronic technology. They are generally installed in parallel with the non linear load. Is Ihar L22 Iact Active filter Active filters analyse the harmonics drawn by the load and then inject the same harmonic current to the load with the appropriate phase. As a result, the harmonic currents are totally neutralised at the point considered. This means they no longer flow upstream and are no longer supplied by the source. A main advantage of active conditioners is that they continue to guarantee efficient harmonic compensation even when changes are made to the installation. They are also exceptionally easy to use as they feature: b Auto-configuration to harmonic loads whatever their order of magnitude b Elimination of overload risks b Compatibility with electrical generator sets b Connection to any point of the electrical network b Several conditioners can be used in the same installation to increase depollution efficiency (for example when a new machine is installed) Active filters may provide also power factor correction. Harmonic generator Hybride filter Hybrid filter (see Fig. L30) This type of filter combines advantages of passive and active filter. One frequency can be filtered by passive filter and all the other frequencies are filtered by active filter. © Schneider Electric - all rights reserved Fig. L30 : Operation principle of hybrid filter Linear load Schneider Electric - Electrical installation guide 2009 9 The effects of harmonics 9.3 Choosing the optimum solution Figure L31 below shows the criteria that can be taken into account to select the most suitable technology depending on the application. Applications … with total power of non linear loads (variable speed drive, UPS, rectifier…) Power factor correction Necessity of reducing the harmonic distorsion in voltage for sensitive loads Necessity of reducing the harmonic distorsion in current to avoid cable overload Necessity of being in accordance with strict limits of harmonic rejected Passive filter Industrial greater than 200 kVA Active filter Tertiary lower than 200 kVA Hybrid filter Industrial greater than 200 kVA No No Fig. L31 : Selection of the most suitable technology depending on the application For passive filter, a choice is made from the following parameters: b Gh = the sum of the kVA ratings of all harmonic-generating devices (static converters, inverters, speed controllers, etc.) connected to the busbars from which the capacitor bank is supplied. If the ratings of some of these devices are quoted in kW only, assume an average power factor of 0.7 to obtain the kVA ratings b Ssc = the 3-phase short-circuit level in kVA at the terminals of the capacitor bank b Sn = the sum of the kVA ratings of all transformers supplying (i.e. directly connected to) the system level of which the busbars form a part If a number of transformers are operating in parallel, the removal from service of one or more, will significantly change the values of Ssc and Sn. From these parameters, a choice of capacitor specification which will ensure an acceptable level of operation with the system harmonic voltages and currents, can be made, by reference to Figure L32. L23 b General rule valid for any size of transformer Ssc 120 Standard capacitors Gh i Ssc Ssc i Gh i 120 70 Capacitor voltage rating increased by 10% (except 230 V units) Ssc 70 Capacitor voltage rating increased by 10% + harmonic-suppression reactor Gh > b Simplified rule if transformer(s) rating Sn y 2 MVA Gh i 0.15 Sn Standard capacitors 0.15 Sn < Gh i 0.25 Sn Capacitor voltage rating increased by 10% (except 230 V units) 0.25 Sn < Gh i 0.60 Sn Capacitor voltage rating increased by 10% + harmonic suppression reactor Gh > 0.60 Sn Filters Fig. L32 : Choice of solutions for limiting harmonics associated with a LV capacitor bank supplied via transformer(s) © Schneider Electric - all rights reserved L - Power factor correction and harmonic filtering Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 10 Implementation of capacitor banks 10.1 Capacitor elements Technology The capacitors are dry-type units (i.e. are not impregnated by liquid dielectric) comprising metallized polypropylene self-healing film in the form of a two-film roll. They are protected by a high-quality system (overpressure disconnector used with a high breaking capacity fuse) which switches off the capacitor if an internal fault occurs. The protection scheme operates as follows: b A short-circuit through the dielectric will blow the fuse b Current levels greater than normal, but insufficient to blow the fuse sometimes occur, e.g. due to a microscopic flow in the dielectric film. Such “faults” often re-seal due to local heating caused by the leakage current, i.e. the units are said to be “selfhealing” b If the leakage current persists, the defect may develop into a short-circuit, and the fuse will blow b Gas produced by vaporizing of the metallisation at the faulty location will gradually build up a pressure within the plastic container, and will eventually operate a pressure-sensitive device to short-circuit the unit, thereby causing the fuse to blow Capacitors are made of insulating material providing them with double insulation and avoiding the need for a ground connection (see Fig. L33). a) HRC fuse Discharge resistor Metallic disc Overpressure disconnect device L24 b) Electrical characteristics Standard © Schneider Electric - all rights reserved Operating range Rated voltage Rated frequency Capacitance tolerance Temperature range Maximum temperature (up to 65 kvar) Average temperature over 24 h Average annual temperature Minimum temperature Insulation level Permissible current overload Permissible voltage overload IEC 60439-1, NFC 54-104, VDE 0560 CSA Standards, UL tests 400 V 50 Hz - 5% to + 10% 55 °C 45 °C 35 °C - 25 °C 50 Hz 1 min withstand voltage : 6 kV 1.2/50 μs impulse withstand voltage : 25 kV Classic range(1) Comfort range(1) 30% 50% 10% 20% Fig. L33 : Capacitor element, (a) cross-section, (b) electrical characteristics (1) Merlin-Gerin designation Schneider Electric - Electrical installation guide 2009 L - Power factor correction and harmonic filtering 10 Implementation of capacitor banks 10.2 Choice of protection, control devices and connecting cables The choice of upstream cables and protection and control devices depends on the current loading. For capacitors, the current is a function of: b The applied voltage and its harmonics b The capacitance value The nominal current In of a 3-phase capacitor bank is equal to: In = Q with: Un 3 v Q: kvar rating v Un: Phase-to-phase voltage (kV) The permitted range of applied voltage at fundamental frequency, plus harmonic components, together with manufacturing tolerances of actual capacitance (for a declared nominal value) can result in a 50% increase above the calculated value of current. Approximately 30% of this increase is due to the voltage increases, while a further 15% is due to the range of manufacturing tolerances, so that 1.3 x 1.15 = 1.5 All components carrying the capacitor current therefore, must be adequate to cover this “worst-case” condition, in an ambient temperature of 50 °C maximum. In the case where temperatures higher than 50 °C occur in enclosures, etc. derating of the components will be necessary. Protection The size of the circuit-breaker can be chosen in order to allow the setting of long time delay at: b 1.36 x In for Classic range(1) b 1.50 x In for Comfort range(1) b 1.12 x In for Harmony range(1) (tuned at 2.7 f)(2) b 1.19 x In for Harmony range(1) (tuned at 3.8 f) b 1.31 x In for Harmony range(1) (tuned at 4.3 f) Short time delay setting (short-circuit protection) must be insensitive to inrush current. The setting will be 10 x In for Classic, Comfort and Harmony range(1). L25 Example 1 50 kvar – 400V – 50 Hz – Classic range 50, 000 In = = 72 A (400 x 1.732) Long time delay setting: 1.36 x 72 = 98 A Short time delay setting: 10 x In = 720 A Example 2 50 kvar – 400V – 50 Hz – Harmony range (tuned at 4.3 f) In = 72 A Long time delay setting: 1.31 x 72 = 94 A Short time delay setting: 10 x In = 720 A Upstream cables Figure L34 next page gives the minimum cross section area of the upstream cable for Rectiphase capacitors. The minimum cross section area of these cables will be 1.5 mm2 for 230 V. For the secondary side of the transformer, the recommended cross section area is u 2.5 mm2. (1) Merlin-Gerin designation (2) Harmony capacitor banks are equipped with a harmonic suppression reactor. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Cables for control L - Power factor correction and harmonic filtering 10 Implementation of capacitor banks Bank power (kvar) 230 V 400 V 5 10 10 20 15 30 20 40 25 50 30 60 40 80 50 100 60 120 70 140 90-100 180 200 120 240 150 250 300 180-210 360 245 420 280 480 315 540 350 600 385 660 420 720 Copper cross- section (mm2) 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 3 x 150 3 x 185 Aluminium cross- section (mm2) 16 16 16 16 25 35 50 70 95 120 185 240 2 x 95 2 x 120 2 x 150 2 x 185 2 x 240 2 x 300 3 x 185 3 x 240 3 x 240 3 x 300 Fig L34 : Cross-section of cables connecting medium and high power capacitor banks(1) Voltage transients High-frequency voltage and current transients occur when switching a capacitor bank into service. The maximum voltage peak does not exceed (in the absence of harmonics) twice the peak value of the rated voltage when switching uncharged capacitors. In the case of a capacitor being already charged at the instant of switch closure, however, the voltage transient can reach a maximum value approaching 3 times the normal rated peak value. L26 This maximum condition occurs only if: b The existing voltage at the capacitor is equal to the peak value of rated voltage, and b The switch contacts close at the instant of peak supply voltage, and b The polarity of the power-supply voltage is opposite to that of the charged capacitor In such a situation, the current transient will be at its maximum possible value, viz: Twice that of its maximum when closing on to an initially uncharged capacitor, as previously noted. For any other values of voltage and polarity on the pre-charged capacitor, the transient peaks of voltage and current will be less than those mentioned above. In the particular case of peak rated voltage on the capacitor having the same polarity as that of the supply voltage, and closing the switch at the instant of supply-voltage peak, there would be no voltage or current transients. © Schneider Electric - all rights reserved Where automatic switching of stepped banks of capacitors is considered, therefore, care must be taken to ensure that a section of capacitors about to be energized is fully discharged. The discharge delay time may be shortened, if necessary, by using discharge resistors of a lower resistance value. (1) Minimum cross-section not allowing for any correction factors (installation mode, temperature, etc.). The calculations were made for single-pole cables laid in open air at 30 °C. Schneider Electric - Electrical installation guide 2009 Chapter M Harmonic management Contents 1 2 3 4 The problem: why is it necessary to detect and eliminate harmonics? M2 Standards M3 General M4 Main effects of harmonics in installations M6 4.1 4.2 4.3 4.4 4.5 M6 M6 M7 M9 M10 5 Essential indicators of harmonic distortion and measurement principles M11 5.1 5.2 5.3 5.4 5.5 5.6 M11 M11 M11 M12 M12 M13 Resonance Increased losses Overloads on equipment Disturbances affecting sensitive loads Economic impact Power factor Crest factor Power values and harmonics Harmonic spectrum and harmonic distortion Total harmonic distortion (THD) Usefulness of the various indicators 6 Measuring the indicators M14 6.1 Devices used to measure the indicators 6.2 Procedures for harmonic analysis of distribution networks 6.3 Keeping a close eye on harmonics M14 M14 M15 7 8 Detection devices M16 Solutions to attenuate harmonics M17 M1 8.1 8.2 8.3 8.4 M17 M18 M20 M20 © Schneider Electric - all rights reserved Basic solutions Harmonic filtering The method Specific products Schneider Electric - Electrical installation guide 2009 M - Harmonic management 1 The problem: why is it necessary to detect and eliminate harmonics? Disturbances caused by harmonics Harmonics flowing in distribution networks downgrade the quality of electrical power. This can have a number of negative effects: b Overloads on distribution networks due to the increase in rms current b Overloads in neutral conductors due to the cumulative increase in third-order harmonics created by single-phase loads b Overloads, vibration and premature ageing of generators, transformers and motors as well as increased transformer hum b Overloads and premature ageing of power-factor correction capacitors b Distortion of the supply voltage that can disturb sensitive loads b Disturbances in communication networks and on telephone lines Economic impact of disturbances Harmonics have a major economic impact: b Premature ageing of equipment means it must be replaced sooner unless oversized right from the start b Overloads on the distribution network can require higher subscribed power levels and increase losses b Distortion of current waveforms provokes nuisance tripping that can stop production Increasingly serious consequences Only ten years ago, harmonics were not yet considered a real problem because their effects on distribution networks were generally minor. However, the massive introduction of power electronics in equipment has made the phenomenon far more serious in all sectors of economic activity. In addition, the equipment causing the harmonics is often vital to the company or organisation. Which harmonics must be measured and eliminated? The most frequently encountered harmonics in three-phase distribution networks are the odd orders. Harmonic amplitudes normally decrease as the frequency increases. Above order 50, harmonics are negligible and measurements are no longer meaningful. Sufficiently accurate measurements are obtained by measuring harmonics up to order 30. Utilities monitor harmonic orders 3, 5, 7, 11 and 13. Generally speaking, harmonic conditioning of the lowest orders (up to 13) is sufficient. More comprehensive conditioning takes into account harmonic orders up to 25. © Schneider Electric - all rights reserved M2 Schneider Electric - Electrical installation guide 2009 M - Harmonic management 2 Standards Harmonic emissions are subject to various standards and regulations: b Compatibility standards for distribution networks b Emissions standards applying to the equipment causing harmonics b Recommendations issued by utilities and applicable to installations In view of rapidly attenuating the effects of harmonics, a triple system of standards and regulations is currently in force based on the documents listed below. Standards governing compatibility between distribution networks and products These standards determine the necessary compatibility between distribution networks and products: b The harmonics caused by a device must not disturb the distribution network beyond certain limits b Each device must be capable of operating normally in the presence of disturbances up to specific levels b Standard IEC 61000-2-2 for public low-voltage power supply systems b Standard IEC 61000-2-4 for LV and MV industrial installations Standards governing the quality of distribution networks b Standard EN 50160 stipulates the characteristics of electricity supplied by public distribution networks b Standard IEEE 519 presents a joint approach between Utilities and customers to limit the impact of non-linear loads. What is more, Utilities encourage preventive action in view of reducing the deterioration of power quality, temperature rise and the reduction of power factor. They will be increasingly inclined to charge customers for major sources of harmonics Standards governing equipment b Standard IEC 61000-3-2 or EN 61000-3-2 for low-voltage equipment with rated current under 16 A b Standard IEC 61000-3-12 for low-voltage equipment with rated current higher than 16 A and lower than 75 A Maximum permissible harmonic levels International studies have collected data resulting in an estimation of typical harmonic contents often encountered in electrical distribution networks. Figure M1 presents the levels that, in the opinion of many utilities, should not be exceeded. Odd harmonic orders non-multiples of 3 Order h LV MV 5 6 6 7 5 5 11 3.5 3.5 13 3 3 17 2 2 19 1.5 1.5 23 1.5 1 25 1.5 1 > 25 0.2 0.2 + 25/h + 25/h EMV 2 2 1.5 1.5 1 1 0.7 0.7 0.1 + 25/h Odd harmonic orders multiples of 3 Order h LV MV 3 5 2.5 9 1.5 1.5 15 0.3 0.3 21 0.2 0.2 > 21 0.2 0.2 Even harmonic orders EMV 1.5 1 0.3 0.2 0.2 Order h 2 4 6 8 10 12 > 12 LV 2 1 0.5 0.5 0.5 0.2 0.2 MV 1.5 1 0.5 0.2 0.2 0.2 0.2 EMV 1.5 1 0.5 0.2 0.2 0.2 0.2 M3 © Schneider Electric - all rights reserved Fig. M1 : Maximum permissible harmonic levels Schneider Electric - Electrical installation guide 2009 M - Harmonic management 3 General The presence of harmonics indicates a distorted current or voltage wave. The distortion of the current or voltage wave means that the distribution of electrical energy is disturbed and power quality is not optimum. Harmonic currents are caused by non-linear loads connected to the distribution network. The flow of harmonic currents causes harmonic voltages via distributionnetwork impedances and consequently distortion of the supply voltage. Origin of harmonics Devices and systems that cause harmonics are present in all sectors, i.e. industrial, commercial and residential. Harmonics are caused by non-linear loads (i.e. loads that draw current with a waveform that is not the same as that of the supply voltage). Examples of non-linear loads are: b Industrial equipment (welding machines, arc furnaces, induction furnaces, rectifiers) b Variable-speed drives for asynchronous or DC motors b UPSs b Office equipment (computers, photocopy machines, fax machines, etc.) b Home appliances (television sets, micro-wave ovens, fluorescent lighting) b Certain devices involving magnetic saturation (transformers) Disturbances caused by non-linear loads: harmonic current and voltage Non-linear loads draw harmonic currents that flow in the distribution network. Harmonic voltages are caused by the flow of harmonic currents through the impedances of the supply circuits (transformer and distribution network for situations similar to that shown in Figure M2). A Zh B Ih Non-linear load Fig. M2 : Single-line diagram showing the impedance of the supply circuit for a harmonic of order h The reactance of a conductor increases as a function of the frequency of the current flowing through the conductor. For each harmonic current (order h), there is therefore an impedance Zh in the supply circuit. M4 When the harmonic current of order h flows through impedance Zh, it creates a harmonic voltage Uh, where Uh = Zh x Ih (Ohm law). The voltage at point B is therefore distorted. All devices supplied via point B receive a distorted voltage. For a given harmonic current, the distortion is proportional to the impedance in the distribution network. Flow of harmonic currents in distribution networks The non-linear loads can be considered to reinject the harmonic currents upstream into the distribution network, toward the source. © Schneider Electric - all rights reserved Figures M3 and M4 next page show an installation disturbed by harmonics. Figure M3 shows the flow of the current at 50 Hz in the installation and Figure M4 shows the harmonic current (order h). Schneider Electric - Electrical installation guide 2009 3 General Zl Non-linear load I 50 Hz Fig. M3 : Installation supplying a non-linear load, where only the phenomena concerning the 50 Hz frequency (fundamental frequency) are shown Zh Ih Vh Non-linear load Vh = Harmonic voltage = Zh x Ih Fig. M4 : Same installation, where only the phenomena concerning the frequency of harmonic order h are shown Supply of the non-linear load creates the flow of a current I50Hz (shown in figure M3), to which is added each of the harmonic currents Ih (shown in figure M4), corresponding to each harmonic order h. Still considering that the loads reinject harmonic current upstream into the distribution network, it is possible to create a diagram showing the harmonic currents in the network (see Fig. M5). Iha Backup power supply Rectifier Arc furnace Welding machine G Ihb Variable-speed drive Power-factor correction Ihd Fluorescent or discharge lamps Ihe Devices drawing rectified current (televisions, computer hardware, etc.) MV/LV M5 A Harmonic disturbances to distribution network and other users Linear loads (do not create harmonics) Note in the diagram that though certain loads create harmonic currents in the distribution network, other loads can absorb the harmonic currents. Fig. M5 : Flow of harmonic currents in a distribution network Harmonics have major economic effects in installations: b Increases in energy costs b Premature ageing of equipment b Production losses Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved M - Harmonic management M - Harmonic management 4 Main effects of harmonics in installations 4.1 Resonance The simultaneous use of capacitive and inductive devices in distribution networks results in parallel or series resonance manifested by very high or very low impedance values respectively. The variations in impedance modify the current and voltage in the distribution network. Here, only parallel resonance phenomena, the most common, will be discussed. Consider the following simplified diagram (see Fig. M6) representing an installation made up of: b A supply transformer b Linear loads b Non-linear loads drawing harmonic currents b Power factor correction capacitors For harmonic analysis, the equivalent diagram (see Fig. M7) is shown below. Impedance Z is calculated by: Z = jLsω 1-LsCω 2 neglecting R and where: Ls = Supply inductance (upstream network + transformer + line) C = Capacitance of the power factor correction capacitors R = Resistance of the linear loads Ih = Harmonic current Resonance occurs when the denominator 1-LsCw2 tends toward zero. The corresponding frequency is called the resonance frequency of the circuit. At that frequency, impedance is at its maximum and high amounts of harmonic voltages appear with the resulting major distortion in the voltage. The voltage distortion is accompanied, in the Ls+C circuit, by the flow of harmonic currents greater than those drawn by the loads. The distribution network and the power factor correction capacitors are subjected to high harmonic currents and the resulting risk of overloads. To avoid resonance, antiharmonic coils can be installed in series with the capacitors. 4.2 Increased losses Ih Losses in conductors The active power transmitted to a load is a function of the fundamental component I1 of the current. M6 When the current drawn by the load contains harmonics, the rms value of the current, Irms, is greater than the fundamental I1. C The definition of THD being: 2 Non-linear load Capacitor bank Linear load it may be deduced that: Irms = I1 1+ THD2 Fig. M6 : Diagram of an installation © Schneider Electric - all rights reserved Ls C R  Irms  THD =   −1  I1  Ih Z Fig. M7 : Equivalent diagram of the installation shown in Figure M6 Figure M8 (next page) shows, as a function of the harmonic distortion: b The increase in the rms current Irms for a load drawing a given fundamental current b The increase in Joule losses, not taking into account the skin effect (The reference point in the graph is 1 for Irms and Joules losses, the case when there are no harmonics) The harmonic currents provoke an increase in the Joule losses in all conductors in which they flow and additional temperature rise in transformers, devices, cables, etc. Losses in asynchronous machines The harmonic voltages (order h) supplied to asynchronous machines provoke in the rotor the flow of currents with frequencies higher than 50 Hz that are the cause of additional losses. Schneider Electric - Electrical installation guide 2009 4 Main effects of harmonics in installations 2.2 2 1.8 1.6 1.4 1.2 1 0.8 0 20 40 60 80 100 120 THD (%) Joules losses Irms Fig. M8 : Increase in rms current and Joule losses as a function of the THD Orders of magnitude b A virtually rectangular supply voltage provokes a 20% increase in losses b A supply voltage with harmonics u5 = 8% (of U1, the fundamental voltage), u7 = 5%, u11 = 3%, u13 = 1%, i.e. total harmonic distortion THDu equal to 10%, results in additional losses of 6% Losses in transformers Harmonic currents flowing in transformers provoke an increase in the “copper” losses due to the Joule effect and increased “iron” losses due to eddy currents. The harmonic voltages are responsible for “iron” losses due to hysteresis. It is generally considered that losses in windings increase as the square of the THDi and that core losses increase linearly with the THDu. In utility-distribution transformers, where distortion levels are limited, losses increase between 10 and 15%. Losses in capacitors The harmonic voltages applied to capacitors provoke the flow of currents proportional to the frequency of the harmonics. These currents cause additional losses. M7 Example A supply voltage has the following harmonics: Fundamental voltage U1, harmonic voltages u5 = 8% (of U1), u7 = 5%, u11 = 3%, u13 = 1%, i.e. total harmonic distortion THDu equal to 10%. The amperage of the current is multiplied by 1.19. Joule losses are multiplied by 1.192, i.e. 1.4. 4.3 Overloads on equipment Generators Generators supplying non-linear loads must be derated due to the additional losses caused by harmonic currents. The level of derating is approximately 10% for a generator where the overall load is made up of 30% of non-linear loads. It is therefore necessary to oversize the generator. Uninterruptible power systems (UPS) The current drawn by computer systems has a very high crest factor. A UPS sized taking into account exclusively the rms current may not be capable of supplying the necessary peak current and may be overloaded. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved M - Harmonic management M - Harmonic management 4 Main effects of harmonics in installations Transformers b The curve presented below (see Fig. M9) shows the typical derating required for a transformer supplying electronic loads kVA (%) 100 90 80 70 60 50 40 30 20 % Electronic load 10 0 0 20 40 60 80 100 Fig. M9 : Derating required for a transformer supplying electronic loads Example If the transformer supplies an overall load comprising 40% of electronic loads, it must be derated by 40%. b Standard UTE C15-112 provides a derating factor for transformers as a function of the harmonic currents. k= Th = 1   40 1+ 0.1  ∑ h1.6 Th2    h= 2 Ih I1 Typical values: b Current with a rectangular waveform (1/h spectrum (1)): k = 0.86 b Frequency-converter current (THD ≈ 50%): k = 0.80 M8 Asynchronous machines Standard IEC 60892 defines a weighted harmonic factor (Harmonic voltage factor) for which the equation and maximum value are provided below. HVF = 13 ∑ h= 2 Uh i 0.02 h2 Example A supply voltage has a fundamental voltage U1 and harmonic voltages u3 = 2% of U1, u5 = 3%, u7 = 1%. The THDu is 3.7% and the MVF is 0.018. The MVF value is very close to the maximum value above which the machine must be derated. Practically speaking, for supply to the machine, a THDu of 10% must not be exceeded. © Schneider Electric - all rights reserved Capacitors According to IEC 60831-1 standard, the rms current flowing in the capacitors must not exceed 1.3 times the rated current. Using the example mentioned above, the fundamental voltage U1, harmonic voltages u5 = 8% (of U1), u7 = 5%, u11 = 3%, u13 = 1%, i.e. total harmonic Irms distortion rated voltage. voltage.For Foraa = 1.19 , at the rated distortionTHDu THDuequal equalto to 10%, 10%, the the result result is I1 I rms voltageequal equaltoto1.1 1.1times timesthe therated ratedvoltage, voltage, the the current current limit limit is reached voltage reached = 1.3 is I1 and it is necessary to resize the capacitors. (1) In fact, the current waveform is similar to a rectangular waveform. This is the case for all current rectifiers (three-phase rectifiers, induction furnaces). Schneider Electric - Electrical installation guide 2009 4 Main effects of harmonics in installations M - Harmonic management Neutral conductors Consider a system made up of a balanced three-phase source and three identical single-phase loads connected between the phases and the neutral (see Fig. M10). Figure M11 shows an example of the currents flowing in the three phases and the resulting current in the neutral conductor. In this example, the current in the neutral conductor has an rms value that is higher than the rms value of the current in a phase by a factor equal to the square root of 3. The neutral conductor must therefore be sized accordingly. (A) Ir t Is t It t In M9 t t (ms) 0 20 40 Fig. M11 : Example of the currents flowing in the various conductors connected to a three-phase load (In = Ir + Is + It) Ir Load 4.4 Disturbances affecting sensitive loads Is Load Load In Distortion of the supply voltage can disturb the operation of sensitive devices: b Regulation devices (temperature) b Computer hardware b Control and monitoring devices (protection relays) Distortion of telephone signals Fig. M10 : Flow of currents in the various conductors connected to a three-phase source Harmonics cause disturbances in control circuits (low current levels). The level of distortion depends on the distance that the power and control cables run in parallel, the distance between the cables and the frequency of the harmonics. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Effects of distortion in the supply voltage It M - Harmonic management 4 Main effects of harmonics in installations 4.5 Economic impact Energy losses Harmonics cause additional losses (Joule effect) in conductors and equipment. Higher subscription costs The presence of harmonic currents can require a higher subscribed power level and consequently higher costs. What is more, utilities will be increasingly inclined to charge customers for major sources of harmonics. Oversizing of equipment b Derating of power sources (generators, transformers and UPSs) means they must be oversized b Conductors must be sized taking into account the flow of harmonic currents. In addition, due the the skin effect, the resistance of these conductors increases with frequency. To avoid excessive losses due to the Joule effect, it is necessary to oversize conductors b Flow of harmonics in the neutral conductor means that it must be oversized as well Reduced service life of equipment When the level of distortion in the supply voltage approaches 10%, the duration of the service life of equipment is significantly reduced. The reduction has been estimated at: b 32.5% for single-phase machines b 18% for three-phase machines b 5% for transformers To maintain the service lives corresponding to the rated load, equipment must be oversized. Nuisance tripping and installation shutdown Circuit-breakers in the installation are subjected to current peaks caused by harmonics. These current peaks cause nuisance tripping with the resulting production losses, as well as the costs corresponding to the time required to start the installation up again. Examples Given the economic consequences for the installations mentioned below, it was necessary to install harmonic filters. M10 Computer centre for an insurance company In this centre, nuisance tripping of a circuit-breaker was calculated to have cost 100 k€ per hour of down time. Pharmaceutical laboratory Harmonics caused the failure of a generator set and the interruption of a longduration test on a new medication. The consequences were a loss estimated at 17 M€. Metallurgy factory A set of induction furnaces caused the overload and destruction of three transformers ranging from 1500 to 2500 kVA over a single year. The cost of the interruptions in production were estimated at 20 k€ per hour. Factory producing garden furniture © Schneider Electric - all rights reserved The failure of variable-speed drives resulted in production shutdowns estimated at 10 k€ per hour. Schneider Electric - Electrical installation guide 2009 5 Essential indicators of harmonic distortion and measurement principles A number of indicators are used to quantify and evaluate the harmonic distortion in current and voltage waveforms, namely: b Power factor b Crest factor b Distortion power b Harmonic spectrum b Harmonic-distortion values These indicators are indispensable in determining any necessary corrective action. 5.1 Power factor Definition The power factor PF is the ratio between the active power P and the apparent power S. PF = P S Among electricians, there is often confusion with: cos ϕ = P1 S1 Where Where P1 = active power of the fundamental S1 = apparent power of the fundamental The cos ϕ concerns exclusively the fundamental frequency and therefore differs from the power factor PF when there are harmonics in the installation. Interpreting the power factor An initial indication that there are significant amounts of harmonics is a measured power factor PF that is different (lower) than the measured cos ϕ. 5.2 Crest factor Definition The crest factor is the ratio between the value of the peak current or voltage (Im or Um) and its rms value. b For a sinusoidal signal, the crest factor is therefore equal to 2. b For a non-sinusoidal signal, the crest factor can be either greater than or less than 2. M11 In the latter case, the crest factor signals divergent peak values with respect to the rms value. Interpretation of the crest factor The typical crest factor for the current drawn by non-linear loads is much higher than 2. It is generally between 1.5 and 2 and can even reach 5 in critical cases. A high crest factor signals high transient overcurrents which, when detected by protection devices, can cause nuisance tripping. 5.3 Power values and harmonics Active power The active power P of a signal comprising harmonics is the sum of the active powers resulting from the currents and voltages of the same order. Reactive power Reactive power is defined exclusively in terms of the fundamental, i.e. Q = U1 x I1 x sinϕ1 Distortion power When harmonics are present, the distortion power D is defined as D = (S2 - P2 - Q2)1/2 where S is the apparent power. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved M - Harmonic management M - Harmonic management 5 Essential indicators of harmonic distortion and measurement principles 5.4 Harmonic spectrum and harmonic distortion Principle Each type of device causing harmonics draws a particular form of harmonic current (amplitude and phase displacement). These values, notably the amplitude for each harmonic order, are essential for analysis. Individual harmonic distortion (or harmonic distortion of order h) The individual harmonic distortion is defined as the percentage of harmonics for order h with respect to the fundamental. U uh (%) = 100 h U1 or ih (%) = 100 Ih I1 Harmonic spectrum By representing the amplitude of each harmonic order with respect to its frequency, it is possible to obtain a graph called the harmonic spectrum. Figure M12 shows an example of the harmonic spectrum for a rectangular signal. Rms value The rms value of the voltage and current can be calculated as a function of the rms value of the various harmonic orders. Irms = ∞ ∑ I h2 h=1 and Urms = U(t) ∞ ∑Uh2 h=1 1 5.5 Total harmonic distortion (THD) t The term THD means Total Harmonic Distortion and is a widely used notion in defining the level of harmonic content in alternating signals. Definition of THD For a signal y, the THD is defined as: M12 ∞ THD = H% ∑ yh2 h= 2 y1 This complies with the definition given in standard IEC 61000-2-2. 100 Note that the value can exceed 1. According to the standard, the variable h can be limited to 50. The THD is the means to express as a single number the distortion affecting a current or voltage flowing at a given point in the installation. The THD is generally expressed as a percentage. 33 20 h 0 1 2 3 4 5 6 © Schneider Electric - all rights reserved Fig. M12 : Harmonic spectrum of a rectangular signal, for a voltage U (t) Current or voltage THD For current harmonics, the equation is: ∞ THDi = ∑ Ih2 h= 2 I1 Schneider Electric - Electrical installation guide 2009 M - Harmonic management 5 Essential indicators of harmonic distortion and measurement principles The equation below is equivalent to the above, but easier and more direct when the total rms value is available: 2  I rms  THD i =   −1  I1  For voltage harmonics, the equation is: ∞ ∑ Uh2 PF cos ϕ THD u = 1.2 h= 2 U1 Relation between power factor and THD (see Fig. M13) 1 When the voltage is sinusoidal or virtually sinusoidal, it may be said that: 0.8 P ≈ P1 = U1.I1.cosϕ1 0.6 Consequently : PF = 0.4 as: 0.2 THDi (%) 0 50 100 PF 150 P U1.I1.cosϕ1 ≈ S U1.Irms I1 1 = Irms 1+ THDi2 hence: PF ≈ cosϕ1 1+ THDi2 Figure M13 shows a graph of Fig. M13 : Variationof in as a function of the THDi, where cosϕ THDu = 0 PF as a function of THDi. cosϕ 5.6 Usefulness of the various indicators The THDu characterises the distortion of the voltage wave. Below are a number of THDu values and the corresponding phenomena in the installation: b THDu under 5% - normal situation, no risk of malfunctions b 5 to 8% - significant harmonic pollution, some malfunctions are possible b Higher than 8% - major harmonic pollution, malfunctions are probable. In-depth analysis and the installation of attenuation devices are required The THDi characterises the distortion of the current wave. The disturbing device is located by measuring the THDi on the incomer and each outgoer of the various circuits and thus following the harmonic trail. Below are a number of THDi values and the corresponding phenomena in the installation: b THDi under 10% - normal situation, no risk of malfunctions b 10 to 50% - significant harmonic pollution with a risk of temperature rise and the resulting need to oversize cables and sources b Higher than 50% - major harmonic pollution, malfunctions are probable. In-depth analysis and the installation of attenuation devices are required M13 Power factor PF Used to evaluate the necessary oversizing for the power source of the installation. Crest factor Used to characterise the aptitude of a generator (or UPS) to supply high instantaneous currents. For example, computer equipment draws highly distorted current for which the crest factor can reach 3 to 5. © Schneider Electric - all rights reserved Spectrum (decomposition of the signal into frequencies) It provides a different representation of electrical signals and can be used to evaluate their distortion. Schneider Electric - Electrical installation guide 2009 M - Harmonic management 6 Measuring the indicators 6.1 Devices used to measure the indicators Device selection The traditional observation and measurement methods include: b Observations using an oscilloscope An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope. The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be viewed. Note, however, that this method does not offer precise quantification of the harmonic components b Analogue spectral analysers They are made up of passband filters coupled with an rms voltmeter. They offer mediocre performance and do not provide information on phase displacement. Only the recent digital analysers can determine sufficiently precisely the values of all the mentioned indicators. Functions of digital analysers The microprocessors in digital analysers: b Calculate the values of the harmonic indicators (power factor, crest factor, distortion power, THD) b Carry out various complementary functions (corrections, statistical detection, measurement management, display, communication, etc.) b In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages Analyser operation and data processing The analogue signals are converted into a series of numerical values. Using this data, an algorithm implementing the Fast Fourier Transform (FFT) calculates the amplitudes and the phases of the harmonics over a large number of time windows. Most digital analysers measure harmonics up to order 20 or 25 when calculating the THD. Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software. M14 6.2 Procedures for harmonic analysis of distribution networks Measurements are carried out on industrial or commercial site: b Preventively, to obtain an overall idea on distribution-network status (network map) b In view of corrective action: v To determine the origin of a disturbance and determine the solutions required to eliminate it v To check the validity of a solution (followed by modifications in the distribution network to check the reduction in harmonics) Operating mode © Schneider Electric - all rights reserved The current and voltage are studied: b At the supply source b On the busbars of the main distribution switchboard (or on the MV busbars) b On each outgoing circuit in the main distribution switchboard (or on the MV busbars) For the measurements, it is necessary to know the precise operating conditions of the installation and particularly the status of the capacitor banks (operating, not operating, the number of disconnected steps). Analysis results b Determine any necessary derating of equipment in the installation or b Quantify any necessary harmonic protection and filtering systems to be installed in the distribution network b Enable comparison between the measured values and the reference values of the utility (maximum harmonic values, acceptable values, reference values) Schneider Electric - Electrical installation guide 2009 6 Measuring the indicators Use of measurement devices Measurement devices serve to show both the instantaneous and long-term effects of harmonics. Analysis requires values spanning durations ranging from a few seconds to several minutes over observation periods of a number of days. The required values include: b The amplitudes of the harmonic currents and voltages b The individual harmonic content of each harmonic order of the current and voltage b The THD for the current and voltage b Where applicable, the phase displacement between the harmonic voltage and current of the same harmonic order and the phase of the harmonics with respect to a common reference (e.g. the fundamental voltage) 6.3 Keeping a close eye on harmonics The harmonic indicators can be measured: b Either by devices permanently installed in the distribution network b Or by an expert present at least a half day on the site (limited perception) Permanent devices are preferable For a number of reasons, the installation of permanent measurement devices in the distribution network is preferable. b The presence of an expert is limited in time. Only a number of measurements at different points in the installation and over a sufficiently long period (one week to a month) provide an overall view of operation and take into account all the situations that can occur following: v Fluctuations in the supply source v Variations in the operation of the installation v The addition of new equipment in the installation b Measurement devices installed in the distribution network prepare and facilitate the diagnosis of the experts, thus reducing the number and duration of their visits b Permanent measurement devices detect any new disturbances arising following the installation of new equipment, the implementation of new operating modes or fluctuations in the supply network Take advantage of built-in measurement and detection devices Measurement and detection devices built into the electrical distribution equipment: b For an overall evaluation of network status (preventive analysis), avoid: v Renting measurement equipment v Calling in experts v Having to connect and disconnect the measurement equipment. M15 For the overall evaluation of network status, the analysis on the main low-voltage distribution switchboards (MLVS) can often be carried out by the incoming device and/or the measurement devices equipping each outgoing circuit b For corrective action, are the means to: v Determine the operating conditions at the time of the incident v Draw up a map of the distribution network and evaluate the implemented solution The diagnosis is improved by the use of equipment intended for the studied problem. © Schneider Electric - all rights reserved M - Harmonic management Schneider Electric - Electrical installation guide 2009 M - Harmonic management 7 Detection devices Measurements are the first step in gaining control over harmonic pollution. Depending on the conditions in each installation, different types of equipment provide the necessary solution. PowerLogic System with Power Meter and Circuit Monitor, Micrologic offer a complete range of devices for the detection of harmonic distortion Power-monitoring units Power Meter and Circuit Monitor in the PowerLogic System These products offer high-performance measurement capabilities for low and medium-voltage distribution networks. They are digital units that include powerquality monitoring functions. PowerLogic System is a complete offer comprising Power Meter (PM) and Circuit Monitor (CM). This highly modular offer covers needs ranging from the most simple (Power Meter) up to highly complex requirements (Circuit Monitor). These products can be used in new or existing installations where the level of power quality must be excellent. The operating mode can be local and/or remote. Depending on its position in the distribution network, a Power Meter provides an initial indication on power quality. The main measurements carried out by a Power Meter are: b Current and voltage THD b Power factor Depending on the version, these measurements can be combined with timestamping and alarm functions. A Circuit Monitor (see Fig. M14) carries out a detailed analysis of power quality and also analyses disturbances on the distribution network. The main functions of a Circuit Monitor are: b Measurement of over 100 electrical parameters b Storage in memory and time-stamping of minimum and maximum values for each electrical parameter b Alarm functions tripped by electrical parameter values b Recording of event data b Recording of current and voltage disturbances b Harmonic analysis b Waveform capture (disturbance monitoring) Micrologic - a power-monitoring unit built into the circuit-breaker For new installations, the Micrologic H control unit (see Fig. M15), an integral part of Masterpact power circuit-breakers, is particularly useful for measurements at the head of an installation or on large outgoing circuits. M16 The Micrologic H control unit offers precise analysis of power quality and detailed diagnostics on events. It is designed for operation in conjunction with a switchboard display unit or a supervisor. It can: b Measure current, voltage, active and reactive power b Measure current and voltage THD b Display the amplitude and phase of current and voltage harmonics up to the 51st order b Carry out waveform capture (disturbance monitoring) Fig. M14 : Circuit monitor The functions offered by the Micrologic H control unit are equivalent to those of a Circuit Monitor. © Schneider Electric - all rights reserved Operation of power-monitoring units Software for remote operation and analysis In the more general framework of a distribution network requiring monitoring, the possibility of interconnecting these various devices can be offered in a communication network, thus making it possible to centralise information and obtain an overall view of disturbances throughout the distribution network. Depending on the application, the operator can then carry out measurements in real time, calculate demand values, run waveform captures, anticipate on alarms, etc. The power-monitoring units transmit all the available data over either a Modbus, Digipact or Ethernet network. The essential goal of this system is to assist in identifying and planning maintenance work. It is an effective means to reduce servicing time and the cost of temporarily installing devices for on-site measurements or the sizing of equipment (filters). Fig. M15 : Micrologic H control unit with harmonic metering for Masterpact NT and NW circuit-breakers Supervision software SMS SMS is a very complete software used to analyse distribution networks, in conjunction with the products in the PowerLogic System. Installed on a standard PC, it can: b Display measurements in real time b Display historical logs over a given period b Select the manner in which data is presented (tables, various curves) b Carry out statistical processing of data (display bar charts) Schneider Electric - Electrical installation guide 2009 8 Solutions to attenuate harmonics There are three different types of solutions to attenuate harmonics: b Modifications in the installation b Special devices in the supply system b Filtering 8.1 Basic solutions To limit the propagation of harmonics in the distribution network, different solutions are available and should be taken into account particularly when designing a new installation. Position the non-linear loads upstream in the system Overall harmonic disturbances increase as the short-circuit power decreases. All economic considerations aside, it is preferable to connect the non-linear loads as far upstream as possible (see Fig. M16). Z2 Sensitive loads Z1 Non-linear loads Where impedance Z1 < Z2 Fig. M16 : Non-linear loads positioned as far upstream as possible (recommended layout) Group the non-linear loads When preparing the single-line diagram, the non-linear devices should be separated from the others (see Fig. M17). The two groups of devices should be supplied by different sets of busbars. M17 Sensitive loads Yes Line impedances No Non-linear load 1 Non-linear load 2 Fig. M17 : Grouping of non-linear loads and connection as far upstream as possible (recommended layout) Create separate sources In attempting to limit harmonics, an additional improvement can be obtained by creating a source via a separate transformer as indicated in the Figure M18 next page. The disadvantage is the increase in the cost of the installation. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved M - Harmonic management M - Harmonic management 8 Solutions to attenuate harmonics Non-linear loads MV network Linear loads Fig. M18 : Supply of non-linear loads via a separate transformer Transformers with special connections Different transformer connections can eliminate certain harmonic orders, as indicated in the examples below: b A Dyd connection suppresses 5th and 7th harmonics (see Fig. M19) b A Dy connection suppresses the 3rd harmonic b A DZ 5 connection suppresses the 5th harmonic h5, h7, h11, h13 h11, h13 h5, h7, h11, h13 Fig. M19 : A Dyd transformer blocks propagation of the 5th and 7th harmonics to the upstream network Install reactors When variable-speed drives are supplied, it is possible to smooth the current by installing line reactors. By increasing the impedance of the supply circuit, the harmonic current is limited. Installation of harmonic suppression reactors on capacitor banks increases the impedance of the reactor/capacitor combination for high-order harmonics. This avoids resonance and protects the capacitors. Select the suitable system earthing arrangement M18 TNC system In the TNC system, a single conductor (PEN) provides protection in the event of an earth fault and the flow of unbalance currents. Under steady-state conditions, the harmonic currents flow in the PEN. The latter, however, has a certain impedance with as a result slight differences in potential (a few volts) between devices that can cause electronic equipment to malfunction. The TNC system must therefore be reserved for the supply of power circuits at the head of the installation and must not be used to supply sensitive loads. TNS system This system is recommended if harmonics are present. The neutral conductor and the protection conductor PE are completely separate and the potential throughout the distribution network is therefore more uniform. © Schneider Electric - all rights reserved 8.2 Harmonic filtering In cases where the preventive action presented above is insufficient, it is necessary to equip the installation with filtering systems. There are three types of filters: b Passive b Active b Hybrid Schneider Electric - Electrical installation guide 2009 M - Harmonic management 8 Solutions to attenuate harmonics Passive filters Typical applications b Industrial installations with a set of non-linear loads representing more than 200 kVA (variable-speed drives, UPSs, rectifiers, etc.) b Installations requiring power-factor correction b Installations where voltage distortion must be reduced to avoid disturbing sensitive loads b Installations where current distortion must be reduced to avoid overloads I har Operating principle An LC circuit, tuned to each harmonic order to be filtered, is installed in parallel with the non-linear load (see Fig. M20). This bypass circuit absorbs the harmonics, thus avoiding their flow in the distribution network. Generally speaking, the passive filter is tuned to a harmonic order close to the order to be eliminated. Several parallel-connected branches of filters can be used if a significant reduction in the distortion of a number of harmonic orders is required. Filter Non-linear load Active filters (active harmonic conditioner) Typical applications b Commercial installations with a set of non-linear loads representing less than 200 kVA (variable-speed drives, UPSs, office equipment, etc.) b Installations where current distortion must be reduced to avoid overloads. Fig. M20 : Operating principle of a passive filter Operating principle These systems, comprising power electronics and installed in series or parallel with the non-linear load, compensate the harmonic current or voltage drawn by the load. Figure M21 shows a parallel-connected active harmonic conditioner (AHC) compensating the harmonic current (Ihar = -Iact). Is The AHC injects in opposite phase the harmonics drawn by the non-linear load, such that the line current Is remains sinusoidal. Iact Hybrid filters AHC Non-linear load Linear load Fig. M21 : Operating principle of an active filter Typical applications b Industrial installations with a set of non-linear loads representing more than 200 kVA (variable-speed drives, UPSs, rectifiers, etc.) b Installations requiring power-factor correction b Installations where voltage distortion must be reduced to avoid disturbing sensitive loads b Installations where current distortion must be reduced to avoid overloads b Installations where strict limits on harmonic emissions must be met Operating principle Passive and active filters are combined in a single system to constitute a hybrid filter (see Fig. M22). This new filtering solution offers the advantages of both types of filters and covers a wide range of power and performance levels. Is I har Iact AHC Non-linear load Hybride filter Fig. M22 : Operating principle of a hybrid filter Linear load M19 Selection criteria Passive filter It offers both power-factor correction and high current-filtering capacity. Passive filters also reduce the harmonic voltages in installations where the supply voltage is disturbed. If the level of reactive power supplied is high, it is advised to turn off the passive filter at times when the percent load is low. Preliminary studies for a filter must take into account the possible presence of a power factor correction capacitor bank which may have to be eliminated. Active harmonic conditioners They filter harmonics over a wide range of frequencies and can adapt to any type of load. On the other hand, power ratings are low. Hybrid filters They combine the performance of both active and passive filters. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved I har M - Harmonic management A complete set of services can be offered to eliminate harmonics: b Installation analysis b Measurement and monitoring systems b Filtering solutions 8 Solutions to attenuate harmonics 8.3 The method The best solution, in both technical and financial terms, is based on the results of an in-depth study. Harmonic audit of MV and LV networks By calling on an expert, you are guaranteed that the proposed solution will produce effective results (e.g. a guaranteed maximum THDu). A harmonic audit is carried out by an engineer specialised in the disturbances affecting electrical distribution networks and equipped with powerful analysis and simulation equipment and software. The steps in an audit are the following: b Measurement of disturbances affecting current and phase-to-phase and phaseto-neutral voltages at the supply source, the disturbed outgoing circuits and the non-linear loads b Computer modelling of the phenomena to obtain a precise explanation of the causes and determine the best solutions b A complete audit report presenting: v The current levels of disturbances v The maximum permissible levels of disturbances (IEC 61000, IEC 34, etc.) b A proposal containing solutions with guaranteed levels of performance b Finally, implementation of the selected solution, using the necessary means and resources. The entire audit process is certified ISO 9002. 8.4 Specific products Passive filters Passive filters are made up of coils and capacitors set up in resonant circuits tuned to the specific harmonic order that must be eliminated. A system may comprise a number of filters to eliminate several harmonic orders. Suitable for 400 V three-phase voltages, the power ratings can reach: b 265 kvar / 470 A for harmonic order 5 b 145 kvar / 225 A for harmonic order 7 b 105 kvar / 145 A for harmonic order 11 Passive filters can be created for all voltage and current levels. M20 Active filters b SineWave active harmonic conditioners v Suitable for 400 V three-phase voltages, they can deliver between 20 and 120 A per phase v SineWave covers all harmonic orders from 2 to 25. Conditioning can be total or target specific harmonic orders v Attenuation: THDi load / THDi upstream greater than 10 at rated capacity v Functions include power factor correction, conditioning of zero-sequence harmonics, diagnostics and maintenance system, parallel connection, remote control, Ibus/RS485 communication interface b Accusine active filters v Suitable for 400 and 480 V three-phase voltages, they can filter between 50 and 30 A per phase v All harmonic orders up to 50 are filtered v Functions include power factor correction, parallel connection, instantaneous response to load variations © Schneider Electric - all rights reserved Hybrid filters These filters combine the advantages of both a passive filter and the SineWave active harmonic conditioner in a single system. Schneider Electric - Electrical installation guide 2009 Chapter N Characteristics of particular sources and loads Contents 1 Protection of a LV generator set and the downstream circuits N2 1.1 1.2 1.3 1.4 N2 N5 N5 N10 Generator protection Downstream LV network protection The monitoring functions Generator Set parallel-connection 2 Uninterruptible Power Supply units (UPS) N11 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N11 N12 N15 N16 N18 N20 N22 N22 3 Protection of LV/LV transformers N24 3.1 Transformer-energizing inrush current 3.2 Protection for the supply circuit of a LV/LV transformer 3.3 Typical electrical characteristics of LV/LV 50 Hz transformers 3.4 Protection of LV/LV transformers, using Merlin Gerin circuit-breakers N24 N24 N25 4 Lighting circuits N27 4.1 4.2 4.3 4.4 N27 N29 N34 N42 5 Asynchronous motors N45 5.1 5.2 5.3 5.4 5.5 N45 N47 N49 N54 N54 Availability and quality of electrical power Types of static UPSs Batteries System earthing arrangements for installations comprising UPSs Choice of protection schemes Installation, connection and sizing of cables The UPSs and their environment Complementary equipment The different lamp technologies Electrical characteristics of lamps Constraints related to lighting devices and recommendations Lighting of public areas Functions for the motor circuit Standards Applications Maximum rating of motors installed for consumers supplied at LV Reactive-energy compensation (power-factor correction) N25 © Schneider Electric - all rights reserved N1 Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits Most industrial and large commercial electrical installations include certain important loads for which a power supply must be maintained, in the event that the utility electrical supply fails: b Either, because safety systems are involved (emergency lighting, automatic fireprotection equipment, smoke dispersal fans, alarms and signalization, and so on…) or b Because it concerns priority circuits, such as certain equipment, the stoppage of which would entail a loss of production, or the destruction of a machine tool, etc. One of the current means of maintaining a supply to the so-called “priority” loads, in the event that other sources fail, is to install a diesel generator set connected, via a change-over switch, to an emergency-power standby switchboard, from which the priority services are fed (see Fig. N1). G HV LV Change-over switch Non-priority circuits Priority circuits Fig N1 : Example of circuits supplied from a transformer or from an alternator 1.1 Generator protection Figure N2 below shows the electrical sizing parameters of a Generator Set. Pn, Un and In are, respectively, the power of the thermal motor, the rated voltage and the rated current of the generator. Un, In Pn R Thermal motor N2 S T N t (s) Fig N2 : Block diagram of a generator set 1,000 Overload protection The generator protection curve must be analysed (see Fig. N3). Standards and requirements of applications can also stipulate specific overload conditions. For example: © Schneider Electric - all rights reserved 100 12 10 7 I/In 1.1 1.5 3 2 1 I 0 0 1.1 1.2 1.5 2 3 4 Fig N3 : Example of an overload curve t = f(I/In) In 5 Overloads t >1h 30 s The setting possibilities of the overload protection devices (or Long Time Delay) will closely follow these requirements. Note on overloads b For economic reasons, the thermal motor of a replacement set may be strictly sized for its nominal power. If there is an active power overload, the diesel motor will stall. The active power balance of the priority loads must take this into account b A production set must be able to withstand operating overloads: v One hour overload v One hour 10% overload every 12 hours (Prime Power) Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits Short-circuit current protection Making the short-circuit current The short-circuit current is the sum: b Of an aperiodic current b Of a damped sinusoidal current The short-circuit current equation shows that it is composed of three successive phases (see Fig. N4). I rms 1 2 3 ≈ 3 In 1 - Subtransient conditions 2 - Transient conditions 3 - Steady state conditions Generator with compound excitation or over-excitation In Generator with serial excitation ≈ 0.3 In 0 t (s) 0 10 to 20 ms 0.1 to 0.3 s Fault appears Fig N4 : Short-circuit current level during the 3 phases b Subtransient phase When a short-circuit appears at the terminals of a generator, the current is first made at a relatively high value of around 6 to 12 In during the first cycle (0 to 20 ms). The amplitude of the short-circuit output current is defined by three parameters: v The subtransient reactance of the generator v The level of excitation prior to the time of the fault and v The impedance of the faulty circuit. The short-circuit impedance of the generator to be considered is the subtransient reactance x’’d expressed in % by the manufacturer. The typical value is 10 to 15%. We determine the subtransient short-circuit impedance of the generator: U2 x ′′d where S = 3 Un I n X ′′d(ohms) = n 100 S b Steady state phase The steady state occurs after 500 ms. When the fault persists, the output voltage collapses and the exciter regulation seeks to raise this output voltage. The result is a stabilised sustained short-circuit current: v If generator excitation does not increase during a short-circuit (no field overexcitation) but is maintained at the level preceding the fault, the current stabilises at a value that is given by the synchronous reactance Xd of the generator. The typical value of xd is greater than 200%. Consequently, the final current will be less than the full-load current of the generator, normally around 0.5 In. v If the generator is equipped with maximum field excitation (field overriding) or with compound excitation, the excitation “surge” voltage will cause the fault current to increase for 10 seconds, normally to 2 to 3 times the full-load current of the generator. Schneider Electric - Electrical installation guide 2009 N3 © Schneider Electric - all rights reserved b Transient phase The transient phase is placed 100 to 500 ms after the time of the fault. Starting from the value of the fault current of the subtransient period, the current drops to 1.5 to 2 times the current In. The short-circuit impedance to be considered for this period is the transient reactance x’d expressed in % by the manufacturer. The typical value is 20 to 30%. N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits Calculating the short-circuit current Manufacturers normally specify the impedance values and time constants required for analysis of operation in transient or steady state conditions (see Fig. N5). (kVA) x”d x’d xd 75 10.5 21 280 200 10.4 15.6 291 400 12.9 19.4 358 800 10.5 18 280 1,600 18.8 33.8 404 2,500 19.1 30.2 292 Fig N5 : Example of impedance table (in %) Resistances are always negligible compared with reactances. The parameters for the short-circuit current study are: b Value of the short-circuit current at generator terminals Short-circuit current amplitude in transient conditions is: In 1 I sc3 = (X’d in ohms) (X’ X ′d 3 or In 100 (x’d in%) x ′d Un is the generator phase-to-phase output voltage. I sc3 = Note: This value can be compared with the short-circuit current at the terminals of a transformer. Thus, for the same power, currents in event of a short-circuit close to a generator will be 5 to 6 times weaker than those that may occur with a transformer (main source). This difference is accentuated still further by the fact that generator set power is normally less than that of the transformer (see Fig. N6). Source 1 MV 2,000 kVA GS LV 42 kA 500 kVA 2.5 kA NC N4 NC D1 NO D2 Main/standby Non-priority circuits Priority circuits © Schneider Electric - all rights reserved NC: Normally closed NO: Normally open Fig N6 : Example of a priority services switchboard supplied (in an emergency) from a standby generator set When the LV network is supplied by the Main source 1 of 2,000 kVA, the short-circuit current is 42 kA at the main LV board busbar. When the LV network is supplied by the Replacement Source 2 of 500 kVA with transient reactance of 30%, the short-circuit current is made at approx. 2.5 kA, i.e. at a value 16 times weaker than with the Main source. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits 1.2 Downstream LV network protection Priority circuit protection Choice of breaking capacity This must be systematically checked with the characteristics of the main source (MV/LV transformer). Setting of the Short Time Delay (STD) tripping current b Subdistribution boards The ratings of the protection devices for the subdistribution and final distribution circuits are always lower than the generator rated current. Consequently, except in special cases, conditions are the same as with transformer supply. b Main LV switchboard v The sizing of the main feeder protection devices is normally similar to that of the generator set. Setting of the STD must allow for the short-circuit characteristic of the generator set (see “Short-circuit current protection” before) v Discrimination of protection devices on the priority feeders must be provided in generator set operation (it can even be compulsory for safety feeders). It is necessary to check proper staggering of STD setting of the protection devices of the main feeders with that of the subdistribution protection devices downstream (normally set for distribution circuits at 10 In). Note: When operating on the generator set, use of a low sensitivity Residual Current Device enables management of the insulation fault and ensures very simple discrimination. Safety of people In the IT (2nd fault) and TN grounding systems, protection of people against indirect contacts is provided by the STD protection of circuit-breakers. Their operation on a fault must be ensured, whether the installation is supplied by the main source (Transformer) or by the replacement source (generator set). Calculating the insulation fault current Zero-sequence reactance formulated as a% of Uo by the manufacturer x’o. The typical value is 8%. The phase-to-neutral single-phase short-circuit current is given by: Un 3 If = 2 X ′d + X ′o The insulation fault current in the TN system is slightly greater than the three phase fault current. For example, in event of an insulation fault on the system in the previous example, the insulation fault current is equal to 3 kA. 1.3 The monitoring functions Due to the specific characteristics of the generator and its regulation, the proper operating parameters of the generator set must be monitored when special loads are implemented. N5 The behaviour of the generator is different from that of the transformer: b The active power it supplies is optimised for a power factor = 0.8 b At less than power factor 0.8, the generator may, by increased excitation, supply part of the reactive power An off-load generator connected to a capacitor bank may self-excite, consequently increasing its overvoltage. The capacitor banks used for power factor regulation must therefore be disconnected. This operation can be performed by sending the stopping setpoint to the regulator (if it is connected to the system managing the source switchings) or by opening the circuit-breaker supplying the capacitors. If capacitors continue to be necessary, do not use regulation of the power factor relay in this case (incorrect and over-slow setting). Motor restart and re-acceleration A generator can supply at most in transient period a current of between 3 and 5 times its nominal current. A motor absorbs roughly 6 In for 2 to 20 s during start-up. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Capacitor bank N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits If the sum of the motor power is high, simultaneous start-up of loads generates a high pick-up current that can be damaging. A large voltage drop, due to the high value of the generator transient and subtransient reactances will occur (20% to 30%), with a risk of: b Non-starting of motors b Temperature rise linked to the prolonged starting time due to the voltage drop b Tripping of the thermal protection devices Moreover, all the network and actuators are disturbed by the voltage drop. Application (see Fig. N7) A generator supplies a set of motors. Generator characteristics: Pn = 130 kVA at a power factor of 0.8, In = 150 A x’d = 20% (for example) hence Isc = 750 A. b The Σ Pmotors is 45 kW (45% of generator power) Calculating voltage drop at start-up: Σ PMotors = 45 kW, Im = 81 A, hence a starting current Id = 480 A for 2 to 20 s. Voltage drop on the busbar for simultaneous motor starting: ∆U  I d − I n  =  in % U  I sc − I n  55% Δ∆UU==55% b the Σ Pmotors is 20 kW (20% of generator power) Calculating voltage drop at start-up: Σ PMotors = 20 kW, Im = 35 A, hence a starting current Id = 210 A for 2 to 20 s. Voltage drop on the busbar: ∆U  I d − I n  =  in % U  I sc − I n  which is not tolerable for motors (failure to start). Δ∆U = 10% which is high but tolerable (depending on the type of loads). G PLC N F N6 F Remote control 1 F F Remote control 2 Motors Resistive loads © Schneider Electric - all rights reserved Fig N7 : Restarting of priority motors (ΣP > 1/3 Pn) Restarting tips 1 starter b If the Pmax of the largest motor > Pn , a progressive soft starter must bemust be 3 installed on this motor If the Pmax of theblargest motor > If Σ Pmotors 1 Pn , amotor progressive mustmust be be managed by a PLC cascadestarter restarting 3 b If Σ Pmotors < 1Pn , there are no restarting problems 3 Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits Non-linear loads – Example of a UPS Non-linear loads These are mainly: b Saturated magnetic circuits b Discharge lamps, fluorescent lights b Electronic converters b Information Technology Equipment: PC, computers, etc. These loads generate harmonic currents: supplied by a Generator Set, this can create high voltage distortion due to the low short-circuit power of the generator. Uninterruptible Power Supply (UPS) (see Fig. N8) The combination of a UPS and generator set is the best solution for ensuring quality power supply with long autonomy for the supply of sensitive loads. It is also a non-linear load due to the input rectifier. On source switching, the autonomy of the UPS on battery must allow starting and connection of the Generator Set. Electrical utility HV incomer G NC NO Mains 2 feeder By-pass Mains 1 feeder Uninterruptible power supply Non-sensitive load Sensitive feeders Fig N8 : Generator set- UPS combination for Quality energy N7 UPS power UPS inrush power must allow for: b Nominal power of the downstream loads. This is the sum of the apparent powers Pa absorbed by each application. Furthermore, so as not to oversize the installation, the overload capacities at UPS level must be considered (for example: 1.5 In for 1 minute and 1.25 In for 10 minutes) b The power required to recharge the battery: This current is proportional to the autonomy required for a given power. The sizing Sr of a UPS is given by: Sr = 1.17 x Pn © Schneider Electric - all rights reserved Figure N9 next page defines the pick-up currents and protection devices for supplying the rectifier (Mains 1) and the standby mains (Mains 2). Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits Nominal power Pn (kVA) 40 60 80 100 120 160 200 250 300 400 500 600 800 Current value (A) Mains 1 with 3Ph battery 400 V - I1 86 123 158 198 240 317 395 493 590 793 990 1,180 1,648 Mains 2 or 3Ph application 400 V - Iu 60.5 91 121 151 182 243 304 360 456 608 760 912 1,215 Fig N9 : Pick-up current for supplying the rectifier and standby mains Generator Set/UPS combination b Restarting the Rectifier on a Generator Set The UPS rectifier can be equipped with a progressive starting of the charger to prevent harmful pick-up currents when installation supply switches to the Generator Set (see Fig. N10). Mains 1 GS starting t (s) UPS charger starting N8 20 ms 5 to 10 s Fig N10 : Progressive starting of a type 2 UPS rectifier b Harmonics and voltage distortion Total voltage distortion τ is defined by: © Schneider Electric - all rights reserved τ(%) = ΣUh2 U1 where Uh is the harmonic voltage of order h. This value depends on: v The harmonic currents generated by the rectifier (proportional to the power Sr of the rectifier) v The longitudinal subtransient reactance X”d of the generator v The power Sg of the generator Sr We define U′ Rcc(%) = X ′′d the generator relative short-circuit voltage, brought to Sg rectifier power, i.e. t = f(U’Rcc). Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits Note 1: As subtransient reactance is great, harmonic distortion is normally too high compared with the tolerated value (7 to 8%) for reasonable economic sizing of the generator: use of a suitable filter is an appropriate and cost-effective solution. Note 2: Harmonic distortion is not harmful for the rectifier but may be harmful for the other loads supplied in parallel with the rectifier. Application A chart is used to find the distortion τ as a function of U’Rcc (see Fig. N11). τ (%) (Voltage harmonic distortion) 18 Without filter 17 16 15 14 13 12 11 10 9 8 7 6 5 With filter (incorporated) 4 3 2 1 0 0 1 2 3 4 5 6 7 8 9 10 11 12 U'Rcc = X''dSr Sg Fig N11 : Chart for calculating harmonic distorsion The chart gives: b Either τ as a function of U’Rcc b Or U’Rcc as a function of τ From which generator set sizing, Sg, is determined. Schneider Electric - Electrical installation guide 2009 N9 © Schneider Electric - all rights reserved Example: Generator sizing b 300 kVA UPS without filter, subtransient reactance of 15% The power Sr of the rectifier is Sr = 1.17 x 300 kVA = 351 kVA For a τ < 7%, the chart gives U’Rcc = 4%, power Sg is: 15 Sg = 351 x ≈ 1,400 kVA 4 c b 300 kVA UPS with filter, subtransient reactance of 15% For τ = 5%, the calculation gives U’Rcc = 12%, power Sg is: 15 Sg = 351 x ≈ 500 kVA 12 Note: With an upstream transformer of 630 kVA on the 300 kVA UPS without filter, the 5% ratio would be obtained. The result is that operation on generator set must be continually monitored for harmonic currents. If voltage harmonic distortion is too great, use of a filter on the network is the most effective solution to bring it back to values that can be tolerated by sensitive loads. N - Characteristics of particular sources and loads 1 Protection of a LV generator set and the downstream circuits 1.4 Generator Set parallel-connection Parallel-connection of the generator set irrespective of the application type - Safety source, Replacement source or Production source - requires finer management of connection, i.e. additional monitoring functions. Parallel operation As generator sets generate energy in parallel on the same load, they must be synchronised properly (voltage, frequency) and load distribution must be balanced properly. This function is performed by the regulator of each Generator Set (thermal and excitation regulation). The parameters (frequency, voltage) are monitored before connection: if the values of these parameters are correct, connection can take place. Insulation faults (see Fig. N12) An insulation fault inside the metal casing of a generator set may seriously damage the generator of this set if the latter resembles a phase-to-neutral short-circuit. The fault must be detected and eliminated quickly, else the other generators will generate energy in the fault and trip on overload: installation continuity of supply will no longer be guaranteed. Ground Fault Protection (GFP) built into the generator circuit is used to: b Quickly disconnect the faulty generator and preserve continuity of supply b Act at the faulty generator control circuits to stop it and reduce the risk of damage This GFP is of the “Residual Sensing” type and must be installed as close as possible to the protection device as per a TN-C/TN-S (1) system at each generator set with grounding of frames by a separate PE. This kind of protection is usually called “Restricted Earth Fault”. MV incomer F HV busbar F G Generator no. 1 Generator no. 2 Protected area RS RS PE Unprotected area PE LV PEN PE PEN Phases Fig N13 : Energy transfer direction – Generator Set as a generator N N10 PE MV incomer Fig N12 : Insulation fault inside a generator F HV busbar F Generator Set operating as a load (see Fig. N13 and Fig. N14) One of the parallel-connected generator sets may no longer operate as a generator but as a motor (by loss of its excitation for example). This may generate overloading of the other generator set(s) and thus place the electrical installation out of operation. G © Schneider Electric - all rights reserved To check that the generator set really is supplying the installation with power (operation as a generator), the proper flow direction of energy on the coupling busbar must be checked using a specific “reverse power” check. Should a fault occur, i.e. the set operates as a motor, this function will eliminate the faulty set. Grounding parallel-connected Generator Sets LV Fig N14 : Energy transfer direction – Generator Set as a load Grounding of connected generator sets may lead to circulation of earth fault currents (triplen harmonics) by connection of neutrals for common grounding (grounding system of the TN or TT type). Consequently, to prevent these currents from flowing between the generator sets, we recommend the installation of a decoupling resistance in the grounding circuit. (1) The system is in TN-C for sets seen as the “generator” and in TN-S for sets seen as “loads” Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) 2.1 Availability and quality of electrical power The disturbances presented above may affect: b Safety of human life b Safety of property b The economic viability of a company or production process Disturbances must therefore be eliminated. A number of technical solutions contribute to this goal, with varying degrees of effectiveness. These solutions may be compared on the basis of two criteria: b Availability of the power supplied b Quality of the power supplied The availability of electrical power can be thought of as the time per year that power is present at the load terminals. Availability is mainly affected by power interruptions due to utility outages or electrical faults. A number of solutions exist to limit the risk: b Division of the installation so as to use a number of different sources rather than just one b Subdivision of the installation into priority and non-priority circuits, where the supply of power to priority circuits can be picked up if necessary by another available source b Load shedding, as required, so that a reduced available power rating can be used to supply standby power b Selection of a system earthing arrangement suited to service-continuity goals, e.g. IT system b Discrimination of protection devices (selective tripping) to limit the consequences of a fault to a part of the installation Note that the only way of ensuring availability of power with respect to utility outages is to provide, in addition to the above measures, an autonomous alternate source, at least for priority loads (see Fig. N15). 2.5 kA G Alternate source N11 Non-priority circuits Priority circuits This source takes over from the utility in the event of a problem, but two factors must be taken into account: b The transfer time (time required to take over from the utility) which must be acceptable to the load b The operating time during which it can supply the load The quality of electrical power is determined by the elimination of the disturbances at the load terminals. An alternate source is a means to ensure the availability of power at the load terminals, however, it does not guarantee, in many cases, the quality of the power supplied with respect to the above disturbances. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. N15 : Availability of electrical power N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) Today, many sensitive electronic applications require an electrical power supply which is virtually free of these disturbances, to say nothing of outages, with tolerances that are stricter than those of the utility. This is the case, for example, for computer centers, telephone exchanges and many industrial-process control and monitoring systems. These applications require solutions that ensure both the availability and quality of electrical power. The UPS solution The solution for sensitive applications is to provide a power interface between the utility and the sensitive loads, providing voltage that is: b Free of all disturbances present in utility power and in compliance with the strict tolerances required by loads b Available in the event of a utility outage, within specified tolerances UPSs (Uninterruptible Power Supplies) satisfy these requirements in terms of power availability and quality by: b Supplying loads with voltage complying with strict tolerances, through use of an inverter b Providing an autonomous alternate source, through use of a battery b Stepping in to replace utility power with no transfer time, i.e. without any interruption in the supply of power to the load, through use of a static switch These characteristics make UPSs the ideal power supply for all sensitive applications because they ensure power quality and availability, whatever the state of utility power. A UPS comprises the following main components: b Rectifier/charger, which produces DC power to charge a battery and supply an inverter b Inverter, which produces quality electrical power, i.e. v Free of all utility-power disturbances, notably micro-outages v Within tolerances compatible with the requirements of sensitive electronic devices (e.g. for Galaxy, tolerances in amplitude ± 0.5% and frequency ± 1%, compared to ± 10% and ± 5% in utility power systems, which correspond to improvement factors of 20 and 5, respectively) b Battery, which provides sufficient backup time (8 minutes to 1 hour or more) to ensure the safety of life and property by replacing the utility as required b Static switch, a semi-conductor based device which transfers the load from the inverter to the utility and back, without any interruption in the supply of power 2.2 Types of static UPSs Types of static UPSs are defined by standard IEC 62040. N12 The standard distinguishes three operating modes: b Passive standby (also called off-line) b Line interactive b Double conversion (also called on-line) These definitions concern UPS operation with respect to the power source including the distribution system upstream of the UPS. © Schneider Electric - all rights reserved Standard IEC 62040 defines the following terms: b Primary power: power normally continuously available which is usually supplied by an electrical utility company, but sometimes by the user’s own generation b Standby power: power intended to replace the primary power in the event of primary-power failure b Bypass power: power supplied via the bypass Practically speaking, a UPS is equipped with two AC inputs, which are called the normal AC input and bypass AC input in this guide. b The normal AC input, noted as mains input 1, is supplied by the primary power, i.e. by a cable connected to a feeder on the upstream utility or private distribution system b The bypass AC input, noted as mains input 2, is generally supplied by standby power, i.e. by a cable connected to an upstream feeder other than the one supplying the normal AC input, backed up by an alternate source (e.g. by an engine-generator set or another UPS, etc.) When standby power is not available, the bypass AC input is supplied with primary power (second cable parallel to the one connected to the normal AC input). The bypass AC input is used to supply the bypass line(s) of the UPS, if they exist. Consequently, the bypass line(s) is supplied with primary or standby power, depending on the availability of a standby-power source. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) UPS operating in passive-standby (off-line) mode Operating principle The inverter is connected in parallel with the AC input in a standby (see Fig. N16). b Normal mode The load is supplied by utility power via a filter which eliminates certain disturbances and provides some degree of voltage regulation (the standard speaks of “additional devices…to provide power conditioning”). The inverter operates in passive standby mode. b Battery backup mode When the AC input voltage is outside specified tolerances for the UPS or the utility power fails, the inverter and the battery step in to ensure a continuous supply of power to the load following a very short (<10 ms) transfer time. The UPS continues to operate on battery power until the end of battery backup time or the utility power returns to normal, which provokes transfer of the load back to the AC input (normal mode). Usage This configuration is in fact a compromise between an acceptable level of protection against disturbances and cost. It can be used only with low power ratings (< 2 kVA). It operates without a real static switch, so a certain time is required to transfer the load to the inverter. This time is acceptable for certain individual applications, but incompatible with the performance required by more sophisticated, sensitive systems (large computer centers, telephone exchanges, etc.). What is more, the frequency is not regulated and there is no bypass. Note: In normal mode, the power supplying the load does not flow through the inverter, which explains why this type of UPS is sometimes called “Off-line”. This term is misleading, however, because it also suggests “not supplied by utility power”, when in fact the load is supplied by the utility via the AC input during normal operation. That is why standard IEC 62040 recommends the term “passive standby”. AC input Charger Battery Inverter UPS operating in line-interactive mode Filter/ conditioner Normal mode Battery backup mode Load Fig. N16 : UPS operating in passive standby mode Normal AC input Bypass AC input If only one AC input Static switch Bypass Operating principle The inverter is connected in parallel with the AC input in a standby configuration, but also charges the battery. It thus interacts (reversible operation) with the AC input source (see Fig. N17). b Normal mode The load is supplied with conditioned power via a parallel connection of the AC input and the inverter. The inverter operates to provide output-voltage conditioning and/or charge the battery. The output frequency depends on the AC-input frequency. b Battery backup mode When the AC input voltage is outside specified tolerances for the UPS or the utility power fails, the inverter and the battery step in to ensure a continuous supply of power to the load following a transfer without interruption using a static switch which also disconnects the AC input to prevent power from the inverter from flowing upstream. The UPS continues to operate on battery power until the end of battery backup time or the utility power returns to normal, which provokes transfer of the load back to the AC input (normal mode). b Bypass mode This type of UPS may be equipped with a bypass. If one of the UPS functions fails, the load can be transferred to the bypass AC input (supplied with utility or standby power, depending on the installation). N13 Usage This configuration is not well suited to regulation of sensitive loads in the medium to high-power range because frequency regulation is not possible. For this reason, it is rarely used other than for low power ratings. Inverter Normal mode Battery backup mode Bypass mode Load Fig. N17 : UPS operating in line-interactive mode Operating principle The inverter is connected in series between the AC input and the application. b Normal mode During normal operation, all the power supplied to the load passes through the rectifier/charger and inverter which together perform a double conversion (AC-DCAC), hence the name. b Battery backup mode When the AC input voltage is outside specified tolerances for the UPS or the utility power fails, the inverter and the battery step in to ensure a continuous supply of power to the load following a transfer without interruption using a static switch. The UPS continues to operate on battery power until the end of battery backup time or utility power returns to normal, which provokes transfer of the load back to the AC input (normal mode). Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved UPS operating in double-conversion (on-line) mode Battery N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) b Bypass mode This type of UPS is generally equipped with a static bypass, sometimes referred to as a static switch (see Fig. N18). The load can be transferred without interruption to the bypass AC input (supplied with utility or standby power, depending on the installation), in the event of the following: v UPS failure v Load-current transients (inrush or fault currents) v Load peaks However, the presence of a bypass assumes that the input and output frequencies are identical and if the voltage levels are not the same, a bypass transformer is required. For certain loads, the UPS must be synchronized with the bypass power to ensure load-supply continuity. What is more, when the UPS is in bypass mode, a disturbance on the AC input source may be transmitted directly to the load because the inverter no longer steps in. Note: Another bypass line, often called the maintenance bypass, is available for maintenance purposes. It is closed by a manual switch. Normal AC input Bypass AC input If only one AC input Battery Static switch (static bypass) Inverter Manual maintenance bypass Load Normal mode Battery backup mode Bypass mode N14 Fig. N18 : UPS operating in double-conversion (on-line) mode Usage In this configuration, the time required to transfer the load to the inverter is negligible due to the static switch. Also, the output voltage and frequency do not depend on the input voltage and frequency conditions. This means that the UPS, when designed for this purpose, can operate as a frequency converter. © Schneider Electric - all rights reserved Practically speaking, this is the main configuration used for medium and high power ratings (from 10 kVA upwards).The rest of this chapter will consider only this configuration. Note: This type of UPS is often called “on-line”, meaning that the load is continuously supplied by the inverter, regardless of the conditions on the AC input source. This term is misleading, however, because it also suggests “supplied by utility power”, when in fact the load is supplied by power that has been reconstituted by the doubleconversion system. That is why standard IEC 62040 recommends the term “double conversion”. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) 2.3 Batteries Selection of battery type A battery is made up of interconnected cells which may be vented or of the recombination type. There are two main families of batteries: b Nickel-cadmium batteries b Lead-acid batteries b Vented cells (lead-antimony): They are equipped with ports to v Release to the atmosphere the oxygen and hydrogen produced during the different chemical reactions v Top off the electrolyte by adding distilled or demineralized water b Recombination cells (lead, pure lead, lead-tin batteries): The gas recombination rate is at least 95% and they therefore do not require water to be added during service life By extension, reference will be made to vented or recombination batteries (recombination batteries are also often called “sealed” batteries). The main types of batteries used in conjunction with UPSs are: b Sealed lead-acid batteries, used 95% of the time because they are easy to maintain and do not require a special room b Vented lead-acid batteries b Vented nickel-cadmium batteries The above three types of batteries may be proposed, depending on economic factors and the operating requirements of the installation, with all the available service-life durations. Capacity levels and backup times may be adapted to suit the user’s needs. The proposed batteries are also perfectly suited to UPS applications in that they are the result of collaboration with leading battery manufacturers. Selection of back up time Selection depends on: b The average duration of power-system failures b Any available long-lasting standby power (engine-generator set, etc.) b The type of application The typical range generally proposed is: b Standard backup times of 10, 15 or 30 minutes b Custom backup times The following general rules apply: b Computer applications Battery backup time must be sufficient to cover file-saving and system-shutdown procedures required to ensure a controlled shutdown of the computer system. Generally speaking, the computer department determines the necessary backup time, depending on its specific requirements. b Industrial processes The backup time calculation should take into account the economic cost incurred by an interruption in the process and the time required to restart. N15 Selection table In certain cases, however, vented batteries are preferred, notably for: b Long service life b Long backup times b High power ratings Vented batteries must be installed in special rooms complying with precise regulations and require appropriate maintenance. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Figure N19 next page sums up the main characteristics of the various types of batteries. Increasingly, recombination batteries would seem to be the market choice for the following reasons: b No maintenance b Easy implementation b Installation in all types of rooms (computer rooms, technical rooms not specifically intended for batteries, etc.) N - Characteristics of particular sources and loads Sealed lead-acid Vented lead-acid Nickel-cadmium 2 Uninterruptible Power Supply units (UPS) Service life Compact 5 or 10 years 5 or 10 years 5 or 10 years + + ++ Operatingtemperature tolerances + ++ +++ Frequency of maintenance Low Medium High Special room Cost No Yes no Low medium Low High Fig. N19 : Main characteristics of the various types of batteries Installation methods Depending on the UPS range, the battery capacity and backup time, the battery is: b Sealed type and housed in the UPS cabinet b Sealed type and housed in one to three cabinets b Vented or sealed type and rack-mounted. In this case the installation method may be v On shelves (see Fig. N20) This installation method is possible for sealed batteries or maintenance-free vented batteries which do not require topping up of their electrolyte. v Tier mounting (see Fig. N21) This installation method is suitable for all types of batteries and for vented batteries in particular, as level checking and filling are made easy. v In cabinets (see Fig. N22) This installation method is suitable for sealed batteries. It is easy to implement and offers maximum safety. Fig. N20 : Shelf mounting 2.4 System earthing arrangements for installations comprising UPSs Application of protection systems, stipulated by the standards, in installations comprising a UPS, requires a number of precautions for the following reasons: b The UPS plays two roles v A load for the upstream system v A power source for downstream system b When the battery is not installed in a cabinet, an insulation fault on the DC system can lead to the flow of a residual DC component Fig. N21 : Tier mounting This component can disturb the operation of certain protection devices, notably RCDs used for the protection of persons. Protection against direct contact (see Fig. N23) All installations satisfy the applicable requirements because the equipment is housed in cabinets providing a degree of protection IP 20. This is true even for the battery when it is housed in a cabinet. When batteries are not installed in a cabinet, i.e. generally in a special room, the measures presented at the end of this chapter should be implemented. N16 Note: The TN system (version TN-S or TN-C) is the most commonly recommended system for the supply of computer systems. Fig. N22 : Cabinet mounting Type of arrangement Operation © Schneider Electric - all rights reserved Techniques for protection of persons Advantages and disadvantages IT system b Signaling of first insulation fault b Locating and elimination of first fault b Disconnection for second insulation fault b Interconnection and earthing of conductive parts b Surveillance of first fault using an insulation monitoring device (IMD) b Second fault results in circuit interruption (circuit-breaker or fuse) b Solution offering the best continuity of service (first fault is signalled) b Requires competent surveillance personnel (location of first fault) TT system b Disconnection for first insulation fault TN system b Disconnection for first insulation fault b Earthing of conductive parts combined with use of RCDs b First insulation fault results in interruption by detecting leakage currents b Interconnection and earthing of conductive parts and neutral imperative b First insulation fault results in interruption by detecting overcurrents (circuit-breaker or fuse) b Easiest solution in terms of design and installation b No insulation monitoring device (IMD) required b However, each fault results in interruption of the concerned circuit b Low-cost solution in terms of installation b Difficult design (calculation of loop impedances) b Qualified operating personnel required b Flow of high fault currents Fig. N23 : Main characteristics of system earthing arrangements Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) Essential points to be checked for UPSs Figure N24 shows all the essential points that must be interconnected as well as the devices to be installed (transformers, RCDs, etc.) to ensure installation conformity with safety standards. T0 T0 neutral IMD 1 CB0 Earth 1 CB1 CB2 T1 T2 T1 neutral T2 neutral Bypass neutral Q1 UPS exposed conductive parts Q4S Q3BP N Q5N UPS output IMD 2 N17 Downstream neutral Earth 2 CB3 Load exposed conductive parts Fig. N24 : The essential points that must be connected in system earthing arrangements Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Earth 3 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) 2.5 Choice of protection schemes The circuit-breakers have a major role in an installation but their importance often appears at the time of accidental events which are not frequent. The best sizing of UPS and the best choice of configuration can be compromised by a wrong choice of only one circuit-breaker. Circuit-breaker selection Figure N25 shows how to select the circuit-breakers. Ir Ir down- upstream stream Select the breaking capacities of CB1 and CB2 for the short-circuit current of the most powerful source (generally the transformer) 100 GE CB2 curve CB3 curve However, CB1 and CB2 must trip on a short-circuit supplied by the least powerful source (generally the generator) 10 Tripping time (in seconds) Im downstream Im upstream 1 Generator short-circuit CB2 must protect the UPS static switch if a short circuit occurs downstream of the switch 0.1 Thermal limit of static power 0.01 CB2 CB1 CB2 The overload capacity of the static switch is 10 to 12 In for 20 ms, where In is the current flowing through the UPS at full rated load CB3 0.001 0.1 Energizing of a transformer 1 10 Energizing of all loads downstream of UPS 100 I/In of upstream circuit breaker N18 The Im current of CB2 must be calculated for simultaneous energizing of all the loads downstream of the UPS The trip unit of CB3 muqt be set not to trip for the overcurrent when the load is energized CB3 © Schneider Electric - all rights reserved If bypass power is not used to handle overloads, the UPS current must trip the CB3 circuit breaker with the highest rating Ir downstream Uc For distant short-circuits, the CB3 unit setting must not result in a dangerous touch voltage. If necessary, install an RCD Fig. N25 : Circuit-breakers are submitted to a variety of situations Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) Rating The selected rating (rated current) for the circuit-breaker must be the one just above the rated current of the protected downstream cable. Breaking capacity The breaking capacity must be selected just above the short-circuit current that can occur at the point of installation. Ir and Im thresholds The table below indicates how to determine the Ir (overload ; thermal or longtime) and Im (short-circuit ; magnetic or short time) thresholds to ensure discrimination, depending on the upstream and downstream trip units. Remark (see Fig. N26) b Time discrimination must be implemented by qualified personnel because time delays before tripping increase the thermal stress (I2t) downstream (cables, semiconductors, etc.). Caution is required if tripping of CB2 is delayed using the Im threshold time delay b Energy discrimination does not depend on the trip unit, only on the circuit-breaker Type of downstream circuit Ir upstream / Ir downstream Im upstream / Im downstream Im upstream / Im downstream Downstream trip unit Distribution Asynchronous motor ratio All types > 1.6 >3 ratio Magnetic >2 >2 ratio Electronic >1.5 >1.5 Fig. N26 : Ir and Im thresholds depending on the upstream and downstream trip units Special case of generator short-circuits Figure N27 shows the reaction of a generator to a short-circuit. To avoid any uncertainty concerning the type of excitation, we will trip at the first peak (3 to 5 In as per X”d) using the Im protection setting without a time delay. Irms 3 In Generator with over-excitation N19 In Generator with series excitation 0.3 In t Fig. N27 : Generator during short-circuit Schneider Electric - Electrical installation guide 2009 Transient conditions 100 to 300 ms © Schneider Electric - all rights reserved Subtransient conditions 10 to 20 ms N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) 2.6 Installation, connection and sizing of cables Ready-to-use UPS units The low power UPSs, for micro computer systems for example, are compact readyto-use equipement. The internal wiring is built in the factory and adapted to the characteristics of the devices. Not ready-to-use UPS units For the other UPSs, the wire connections to the power supply system, to the battery and to the load are not included. Wiring connections depend on the current level as indicated in Figure N28 below. Iu SW Static switch Mains 1 I1 Iu Load Rectifier/ charger Inverter Mains 2 Ib Battery capacity C10 Fig.N28 : Current to be taken into account for the selection of the wire connections Calculation of currents I1, Iu b The input current Iu from the power network is the load current b The input current I1 of the charger/rectifier depends on: v The capacity of the battery (C10) and the charging mode (Ib) v The characteristics of the charger v The efficiency of the inverter b The current Ib is the current in the connection of the battery These currents are given by the manufacturers. Cable temperature rise and voltage drops N20 The cross section of cables depends on: b Permissible temperature rise b Permissible voltage drop For a given load, each of these parameters results in a minimum permissible cross section. The larger of the two must be used. When routing cables, care must be taken to maintain the required distances between control circuits and power circuits, to avoid any disturbances caused by HF currents. Temperature rise Permissible temperature rise in cables is limited by the withstand capacity of cable insulation. © Schneider Electric - all rights reserved Temperature rise in cables depends on: b The type of core (Cu or Al) b The installation method b The number of touching cables Standards stipulate, for each type of cable, the maximum permissible current. Voltage drops The maximum permissible voltage drops are: b 3% for AC circuits (50 or 60 Hz) b 1% for DC circuits Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) Selection tables Figure N29 indicates the voltage drop in percent for a circuit made up of 100 meters of cable. To calculate the voltage drop in a circuit with a length L, multiply the value in the table by L/100. b Sph: Cross section of conductors b In: Rated current of protection devices on circuit Three-phase circuit If the voltage drop exceeds 3% (50-60 Hz), increase the cross section of conductors. DC circuit If the voltage drop exceeds 1%, increase the cross section of conductors. a - Three-phase circuits (copper conductors) 50-60 Hz - 380 V / 400 V / 415 V three-phase, cos ϕ = 0.8, balanced system three-phase + N In Sph (mN2) (A) 10 16 25 35 50 70 95 120 150 185 10 0.9 15 1.2 20 1.6 1.1 25 2.0 1.3 0.9 32 2.6 1.7 1.1 40 3.3 2.1 1.4 1.0 50 4.1 2.6 1.7 1.3 1.0 63 5.1 3.3 2.2 1.6 1.2 0.9 70 5.7 3.7 2.4 1.7 1.3 1.0 0.8 80 6.5 4.2 2.7 2.1 1.5 1.2 0.9 0.7 100 8.2 5.3 3.4 2.6 2.0 2.0 1.1 0.9 0.8 125 6.6 4.3 3.2 2.4 2.4 1.4 1.1 1.0 0.8 160 5.5 4.3 3.2 3.2 1.8 1.5 1.2 1.1 200 5.3 3.9 3.9 2.2 1.8 1.6 1.3 250 4.9 4.9 2.8 2.3 1.9 1.7 320 3.5 2.9 2.5 2.1 400 4.4 3.6 3.1 2.7 500 4.5 3.9 3.4 600 4.9 4.2 800 5.3 1,000 For a three-phase 230 V circuit, multiply the result by e For a single-phase 208/230 V circuit, multiply the result by 2 b - DC circuits (copper conductors) In Sph (mN2) (A) 25 35 100 5.1 3.6 125 4.5 160 200 250 320 400 500 600 800 1,000 1,250 50 2.6 3.2 4.0 70 1.9 2.3 2.9 3.6 95 1.3 1.6 2.2 2.7 3.3 120 1.0 1.3 1.6 2.2 2.7 3.4 150 0.8 1.0 1.2 1.6 2.2 2.7 3.4 185 0.7 0.8 1.1 1.3 1.7 2.1 2.8 3.4 4.3 240 300 0.9 1.2 1.4 1.9 2.3 2.9 3.6 4.4 6.5 0.9 1.2 1.5 1.9 2.4 3.0 3.8 4.7 240 0.5 0.6 0.6 1.0 1.3 1.6 2.1 2.6 3.3 4.2 5.3 300 0.4 0.5 0.7 0.8 1.0 1.3 1.6 2.1 2.7 3.4 4.2 5.3 N21 Special case for neutral conductors In three-phase systems, the third-order harmonics (and their multiples) of singlephase loads add up in the neutral conductor (sum of the currents on the three phases). For this reason, the following rule may be applied: neutral cross section = 1.5 x phase cross section Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. N29 : Voltage drop in percent for [a] three-phase circuits and [b] DC circuits N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) Example Consider a 70-meter 400 V three-phase circuit, with copper conductors and a rated current of 600 A. Standard IEC 60364 indicates, depending on the installation method and the load, a minimum cross section. We shall assume that the minimum cross section is 95 mm2. It is first necessary to check that the voltage drop does not exceed 3%. The table for three-phase circuits on the previous page indicates, for a 600 A current flowing in a 300 mm2 cable, a voltage drop of 3% for 100 meters of cable, i.e. for 70 meters: 3 x 70 = 2.1 % 100 Therefore less than 3% A identical calculation can be run for a DC current of 1,000 A. In a ten-meter cable, the voltage drop for 100 meters of 240 mN2 cable is 5.3%, i.e. for ten meters: 5.3 x 10 = 0.53 % 100 Therefore less than 3% 2.7 The UPSs and their environment The UPSs can communicate with electrical and computing environment. They can receive some data and provide information on their operation in order: b To optimize the protection For example, the UPS provides essential information on operating status to the computer system (load on inverter, load on static bypass, load on battery, low battery warning) b To remotely control The UPS provides measurement and operating status information to inform and allow operators to take specific actions b To manage the installation The operator has a building and energy management system which allow to obtain and save information from UPSs, to provide alarms and events and to take actions. This evolution towards compatibilty between computer equipment and UPSs has the effect to incorporate new built-in UPS functions. 2.8 Complementary equipment Transformers N22 A two-winding transformer included on the upstream side of the static contactor of circuit 2 allows: b A change of voltage level when the power network voltage is different to that of the load b A change of system of earthing between the networks Moreover, such a transformer : b Reduces the short-circuit current level on the secondary, (i.e load) side compared with that on the power network side b Prevents third harmonic currents which may be present on the secondary side from passing into the power-system network, providing that the primary winding is connected in delta. © Schneider Electric - all rights reserved Anti-harmonic filter The UPS system includes a battery charger which is controlled by thyristors or transistors. The resulting regularly-chopped current cycles “generate” harmonic components in the power-supply network. These indesirable components are filtered at the input of the rectifier and for most cases this reduces the harmonic current level sufficiently for all practical purposes. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 2 Uninterruptible Power Supply units (UPS) In certain specific cases however, notably in very large installations, an additional filter circuit may be necessary. For example when : b The power rating of the UPS system is large relative to the MV/LV transformer suppllying it b The LV busbars supply loads which are particularly sensitive to harmonics b A diesel (or gas-turbine, etc,) driven alternator is provided as a standby power supply In such cases, the manufacturer of the UPS system should be consulted Communication equipment Communication with equipment associated with computer systems may entail the need for suitable facilities within the UPS system. Such facilities may be incorporated in an original design (see Fig. N30a ), or added to existing systems on request (see Fig. N30b ). Fig. N30b : UPS unit achieving disponibility and quality of computer system power supply N23 © Schneider Electric - all rights reserved Fig. N30a : Ready-to-use UPS unit (with DIN module) Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 3 Protection of LV/LV transformers These transformers are generally in the range of several hundreds of VA to some hundreds of kVA and are frequently used for: b Changing the low voltage level for: v Auxiliary supplies to control and indication circuits v Lighting circuits (230 V created when the primary system is 400 V 3-phase 3-wires) b Changing the method of earthing for certain loads having a relatively high capacitive current to earth (computer equipment) or resistive leakage current (electric ovens, industrial-heating processes, mass-cooking installations, etc.) LV/LV transformers are generally supplied with protective systems incorporated, and the manufacturers must be consulted for details. Overcurrent protection must, in any case, be provided on the primary side. The exploitation of these transformers requires a knowledge of their particular function, together with a number of points described below. Note: In the particular cases of LV/LV safety isolating transformers at extra-low voltage, an earthed metal screen between the primary and secondary windings is frequently required, according to circumstances, as recommended in European Standard EN 60742. 3.1 Transformer-energizing inrush current At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N31). I t I 1st peak 10 to 25 In 5s In 20 ms Ir Im Ii Fig N31 : Transformer-energizing inrush current RMS value of the 1st peak N24 t I Fig N32 : Tripping characteristic of a Compact NS type STR (electronic) t The magnitude of the current peak depends on: b The value of voltage at the instant of energization b The magnitude and polarity of the residual flux existing in the core of the transformer b Characteristics of the load connected to the transformer The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms. © Schneider Electric - all rights reserved 3.2 Protection for the supply circuit of a LV/LV transformer I In 10In 14In RMS value of the 1st peak Fig N33 : Tripping characteristic of a Multi 9 curve D The protective device on the supply circuit for a LV/LV transformer must avoid the possibility of incorrect operation due to the magnetizing inrush current surge, noted above.It is necessary to use therefore: b Selective (i.e. slighly time-delayed) circuit-breakers of the type Compact NS STR (see Fig. N32) or b Circuit-breakers having a very high magnetic-trip setting, of the types Compact NS or Multi 9 curve D (see Fig. N33) Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 3 Protection of LV/LV transformers Example A 400 V 3-phase circuit is supplying a 125 kVA 400/230 V transformer (In = 180 A) for which the first inrush current peak can reach 12 In, i.e. 12 x 180 = 2,160 A. This current peak corresponds to a rms value of 1,530 A. A compact NS 250N circuit-breaker with Ir setting of 200 A and Im setting at 8 x Ir would therefore be a suitable protective device. A particular case: Overload protection installed at the secondary side of the transformer (see Fig. N34) An advantage of overload protection located on the secondary side is that the shortcircuit protection on the primary side can be set at a high value, or alternatively a circuit-breaker type MA (magnetic only) can be used. The primary side short-circuit protection setting must, however, be sufficiently sensitive to ensure its operation in the event of a short-circuit occuring on the secondary side of the transformer. NS250N Trip unit STR 22E 3 x 70 mm2 400/230 V 125 kVA Note: The primary protection is sometimes provided by fuses, type aM. This practice has two disadvantages: b The fuses must be largely oversized (at least 4 times the nominal full-load rated current of the transformer) b In order to provide isolating facilities on the primary side, either a load-break switch or a contactor must be associated with the fuses. Fig N34 : Example 3.3 Typical electrical characteristics of LV/LV 50 Hz transformers 5 100 6.3 110 8 130 10 150 12.5 16 160 170 20 270 25 310 250 320 390 500 600 840 800 1180 1240 1530 1650 2150 2540 3700 3700 5900 5900 6500 7400 9300 9400 11400 13400 4.5 4.5 4.5 5.5 5.5 5.5 5.5 5.5 5 5 4.5 5 5 5.5 4.5 5.5 8 105 400 5 10 115 530 5 12.5 120 635 5 16 140 730 4.5 20 150 865 4.5 25 175 1065 4.5 31.5 200 1200 4 40 215 1400 4 50 265 1900 5 63 305 2000 5 80 450 2450 4.5 100 450 3950 5.5 125 525 3950 5 160 635 4335 5 1-phase kVA rating No-load losses (W) Full-load losses (W) Short-circuit voltage (%) 31.5 40 350 350 50 410 63 460 80 520 100 570 125 680 160 680 200 790 5 250 950 5 315 400 500 630 800 1160 1240 1485 1855 2160 4.5 6 6 5.5 5.5 3.4 Protection of LV/LV transformers, using Merlin Gerin circuit-breakers Multi 9 circuit-breaker Transformer power rating (kVA) 230/240 V 1-ph 230/240 V 3-ph 400/415 V 1-ph 0.05 0.09 0.11 0.18 0.21 0.36 0.33 0.58 0.67 1.2 1.1 1.8 1.7 2.9 2.1 3.6 2.7 4.6 3.3 5.8 4.2 7.2 5.3 9.2 6.7 12 8.3 14 11 18 13 23 N25 400/415 V 3-ph Cricuit breaker curve D or K Size (A) 0.16 0.32 0.63 1.0 2.0 3.2 5.0 6.3 8.0 10 13 16 20 25 32 40 C60, NG125 C60, NG125 C60, NG125 C60, NG125 C60, NG125 C60, C120, NG125 C60, C120, NG125 C60, C120, NG125 C60, C120, NG125 C60, C120, NG125 C60, C120, NG125 C60, C120, NC100, NG125 C60, C120, NC100, NG125 C120, NC100, NG125 C120, NC100, NG125 C120, NG125 0.5 1 2 3 6 10 16 20 25 32 40 50 63 80 100 125 Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 3-phase kVA rating No-load losses (W) Full-load losses (W) Short-circuit voltage (%) N - Characteristics of particular sources and loads 3 Protection of LV/LV transformers Compact NSX100 to NSX250 circuit-breakers with TM-D trip units Transformer power rating (kVA) 230/240 V 1-ph 230/240 V 3-ph 400/415 V 1-ph 3 5…6 5 8…9 7…9 13…16 12…15 20…25 16…19 26…32 18…23 32…40 23…29 40…50 29…37 51…64 37…46 64…80 Circuit-breaker Trip unit NSX100B/F/N/H/S/L NSX100B/F/N/H/S/L NSX100B/F/N/H/S/L NSX100B/F/N/H/S/L NSX100B/F/N/H/S/L NSX160B/F/N/H/S/L NSX160B/F/N/H/S/L NSX250B/F/N/H/S/L NSX250B/F/N/H/S/L TM16D TM25D TM40D TM63D TM80D TM100D TM125D TM160D TM200D 400/415 V 3-ph 9…12 14…16 22…28 35…44 45…56 55…69 69…87 89…111 111…139 Compact NSX100 to NS1600 / Masterpact circuit-breakers with Micrologic trip units Transformer power rating (kVA) 230/240 V 1-ph 230/240 V 3-ph 400/415 V 1-ph 4…7 6…13 9…19 16…30 15…30 5…50 23…46 40…80 37…65 64…112 37…55 64…95 58…83 100…144 58…150 100…250 74…184 107…319 90…230 159…398 115…288 200…498 147…368 256…640 184…460 320…800 230…575 400…1,000 294…736 510…1,280 Circuit-breaker Trip unit Setting Ir max NSX100B/F/N/H/S/L NSX100B/F/N/H/S/L NSX160B/F/N/H/S/L NSX250B/F/N/H/S/L NSX400F/N/H/S NSX400L NSX630F/N//H/S/L NS630bN/bH NT06H1 NS800N/H - NT08H1- NW08N1/H1 NS1000N/H - NT10H1- NW10N1/H1 NS1250N/H - NT12H1 - NW12N1/H1 NS1600N/H - NT16H1 - NW16N1/H1 NW20N1/H1 NW25H2/H3 NW32H2/H3 Micrologic 2.2 or 6.2 40 Micrologic 2.2 or 6.2 100 Micrologic 2.2 or 6.2 160 Micrologic 2.2 or 6.2 250 Micrologic 2.3 or 6.3 400 Micrologic 2.3 or 6.3 400 Micrologic 2.3 or 6.3 630 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 Micrologic 5.0/6.0/7.0 0.8 0.8 0.8 0.8 0.7 0.6 0.6 1 1 1 1 1 1 1 1 400/415 V 3-ph 11…22 27…56 44…90 70…139 111…195 111…166 175…250 175…436 222…554 277…693 346…866 443…1,108 554…1,385 690…1,730 886…2,217 © Schneider Electric - all rights reserved N26 Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits A source of comfort and productivity, lighting represents 15% of the quantity of electricity consumed in industry and 40% in buildings. The quality of lighting (light stability and continuity of service) depends on the quality of the electrical energy thus consumed. The supply of electrical power to lighting networks has therefore assumed great importance. To help with their design and simplify the selection of appropriate protection devices, an analysis of the different lamp technologies is presented. The distinctive features of lighting circuits and their impact on control and protection devices are discussed. Recommendations relative to the difficulties of lighting circuit implementation are given. 4.1 The different lamp technologies Artificial luminous radiation can be produced from electrical energy according to two principles: incandescence and electroluminescence. Incandescence is the production of light via temperature elevation. The most common example is a filament heated to white state by the circulation of an electrical current. The energy supplied is transformed into heat by the Joule effect and into luminous flux. Luminescence is the phenomenon of emission by a material of visible or almost visible luminous radiation. A gas (or vapors) subjected to an electrical discharge emits luminous radiation (Electroluminescence of gases). Since this gas does not conduct at normal temperature and pressure, the discharge is produced by generating charged particles which permit ionization of the gas. The nature, pressure and temperature of the gas determine the light spectrum. Photoluminescence is the luminescence of a material exposed to visible or almost visible radiation (ultraviolet, infrared). When the substance absorbs ultraviolet radiation and emits visible radiation which stops a short time after energization, this is fluorescence. Incandescent lamps Incandescent lamps are historically the oldest and the most often found in common use. They are based on the principle of a filament rendered incandescent in a vacuum or neutral atmosphere which prevents combustion. A distinction is made between: b Standard bulbs These contain a tungsten filament and are filled with an inert gas (nitrogen and argon or krypton). b Halogen bulbs These also contain a tungsten filament, but are filled with a halogen compound and an inert gas (krypton or xenon). This halogen compound is responsible for the phenomenon of filament regeneration, which increases the service life of the lamps and avoids them blackening. It also enables a higher filament temperature and therefore greater luminosity in smaller-size bulbs. a- N27 The main disadvantage of incandescent lamps is their significant heat dissipation, resulting in poor luminous efficiency. Fluorescent lamps This family covers fluorescent tubes and compact fluorescent lamps. Their technology is usually known as “low-pressure mercury”. b- Fluorescent tubes dissipate less heat and have a longer service life than incandescent lamps, but they do need an ignition device called a “starter” and a device to limit the current in the arc after ignition. This device called “ballast” is usually a choke placed in series with the arc. Compact fluorescent lamps are based on the same principle as a fluorescent tube. The starter and ballast functions are provided by an electronic circuit (integrated in the lamp) which enables the use of smaller tubes folded back on themselves. Compact fluorescent lamps (see Fig. N35) were developed to replace incandescent lamps: They offer significant energy savings (15 W against 75 W for the same level of brightness) and an increased service life. Fig. N35 : Compact fluorescent lamps [a] standard, [b] induction Lamps known as “induction” type or “without electrodes” operate on the principle of ionization of the gas present in the tube by a very high frequency electromagnetic field (up to 1 GHz). Their service life can be as long as 100,000 hrs. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved In fluorescent tubes, an electrical discharge causes electrons to collide with ions of mercury vapor, resulting in ultraviolet radiation due to energization of the mercury atoms. The fluorescent material, which covers the inside of the tubes, then transforms this radiation into visible light. N - Characteristics of particular sources and loads 4 Lighting circuits Discharge lamps (see Fig. N36) The light is produced by an electrical discharge created between two electrodes within a gas in a quartz bulb. All these lamps therefore require a ballast to limit the current in the arc. A number of technologies have been developed for different applications. Low-pressure sodium vapor lamps have the best light output, however the color rendering is very poor since they only have a monochromatic orange radiation. High-pressure sodium vapor lamps produce a white light with an orange tinge. In high-pressure mercury vapor lamps, the discharge is produced in a quartz or ceramic bulb at high pressure. These lamps are called “fluorescent mercury discharge lamps”. They produce a characteristically bluish white light. Metal halide lamps are the latest technology. They produce a color with a broad color spectrum. The use of a ceramic tube offers better luminous efficiency and better color stability. Light Emitting Diodes (LED) The principle of light emitting diodes is the emission of light by a semi-conductor as an electrical current passes through it. LEDs are commonly found in numerous applications, but the recent development of white or blue diodes with a high light output opens new perspectives, especially for signaling (traffic lights, exit signs or emergency lighting). LEDs are low-voltage and low-current devices, thus suitable for battery-supply. A converter is required for a line power supply. The advantage of LEDs is their low energy consumption. As a result, they operate at a very low temperature, giving them a very long service life. Conversely, a simple diode has a weak light intensity. A high-power lighting installation therefore requires connection of a large number of units in series and parallel. Fig. N36 : Discharge lamps Technology Standard incandescent Application - Domestic use - Localized decorative lighting Halogen incandescent - Spot lighting - Intense lighting Fluorescent tube - Shops, offices, workshops - Outdoors Compact fluorescent lamp - Domestic use - Offices - Replacement of incandescent lamps - Workshops, halls, hangars - Factory floors HP mercury vapor © Schneider Electric - all rights reserved N28 High-pressure sodium Low-pressure sodium Metal halide - Outdoors - Large halls - Outdoors - Emergency lighting - Large areas - Halls with high ceilings LED - Signaling (3-color traffic lights, “exit” signs and emergency lighting) Technology Standard incandescent Halogen incandescent Fluorescent tube Compact fluorescent lamp HP mercury vapor High-pressure sodium Low-pressure sodium Metal halide LED Power (watt) 3 – 1,000 5 – 500 4 – 56 5 – 40 40 – 1,000 35 – 1,000 35 – 180 30 – 2,000 0.05 – 0.1 Advantages - Direct connection without intermediate switchgear - Reasonable purchase price - Compact size - Instantaneous lighting - Good color rendering - Direct connection - Instantaneous efficiency - Excellent color rendering - High luminous efficiency - Average color rendering - Low light intensity of single unit - Sensitive to extreme temperatures - Good luminous efficiency - Good color rendering - High initial investment compared to incandescent lamps - Good luminous efficiency - Acceptable color rendering - Compact size - Long service life - Very good luminous efficiency - Lighting and relighting time of a few minutes - Good visibility in foggy weather - Economical to use - Good luminous efficiency - Good color rendering - Long service life - Insensitive to the number of switching operations - Low energy consumption - Low temperature Disadvantages - Low luminous efficiency and high electricity consumption - Significant heat dissipation - Short service life - Average luminous efficiency - Lighting and relighting time of a few minutes - Long lighting time (5 min.) - Mediocre color rendering - Lighting and relighting time of a few minutes - Limited number of colors - Low brightness of single unit Efficiency (lumen/watt) 10 – 15 15 – 25 50 – 100 50 – 80 25 – 55 40 – 140 100 – 185 50 – 115 10 – 30 Fig. N37 : Usage and technical characteristics of lighting devices Schneider Electric - Electrical installation guide 2009 Service life (hours) 1,000 – 2,000 2,000 – 4,000 7,500 – 24,000 10,000 – 20,000 16,000 – 24,000 16,000 – 24,000 14,000 – 18,000 6,000 – 20,000 40,000 – 100,000 N - Characteristics of particular sources and loads 4 Lighting circuits 4.2 Electrical characteristics of lamps Incandescent lamps with direct power supply Due to the very high temperature of the filament during operation (up to 2,500 °C), its resistance varies greatly depending on whether the lamp is on or off. As the cold resistance is low, a current peak occurs on ignition that can reach 10 to 15 times the nominal current for a few milliseconds or even several milliseconds. This constraint affects both ordinary lamps and halogen lamps: it imposes a reduction in the maximum number of lamps that can be powered by devices such as remote-control switches, modular contactors and relays for busbar trunking. Extra Low Voltage (ELV) halogen lamps b Some low-power halogen lamps are supplied with ELV 12 or 24 V, via a transformer or an electronic converter. With a transformer, the magnetization phenomenon combines with the filament resistance variation phenomenon at switch-on. The inrush current can reach 50 to 75 times the nominal current for a few milliseconds. The use of dimmer switches placed upstream significantly reduces this constraint. b Electronic converters, with the same power rating, are more expensive than solutions with a transformer. This commercial handicap is compensated by a greater ease of installation since their low heat dissipation means they can be fixed on a flammable support. Moreover, they usually have built-in thermal protection. New ELV halogen lamps are now available with a transformer integrated in their base. They can be supplied directly from the LV line supply and can replace normal lamps without any special adaptation. Dimming for incandescent lamps This can be obtained by varying the voltage applied to the lampere This voltage variation is usually performed by a device such as a Triac dimmer switch, by varying its firing angle in the line voltage period. The wave form of the voltage applied to the lamp is illustrated in Figure N38a. This technique known as “cut-on control” is suitable for supplying power to resistive or inductive circuits. Another technique suitable for supplying power to capacitive circuits has been developed with MOS or IGBT electronic components. This techniques varies the voltage by blocking the current before the end of the half-period (see Fig. N38b) and is known as “cut-off control”. Switching on the lamp gradually can also reduce, or even eliminate, the current peak on ignition. a] As the lamp current is distorted by the electronic switching, harmonic currents are produced. The 3rd harmonic order is predominant, and the percentage of 3rd harmonic current related to the maximum fundamental current (at maximum power) is represented on Figure N39. 300 200 100 0 t (s) Note that in practice, the power applied to the lamp by a dimmer switch can only vary in the range between 15 and 85% of the maximum power of the lampere N29 -100 -200 -300 i3 (%) 0 0.01 0.02 50.0 b] 45.0 300 40.0 200 35.0 100 30.0 0 t (s) 25.0 15.0 -200 10.0 -300 0 0.01 5.0 0.02 0 Fig. N38 : Shape of the voltage supplied by a light dimmer at 50% of maximum voltage with the following techniques: a] “cut-on control” b] “cut-off control” Power (%) 0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0 Fig. N39 : Percentage of 3rd harmonic current as a function of the power applied to an incandescent lamp using an electronic dimmer switch Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 20.0 -100 N - Characteristics of particular sources and loads 4 Lighting circuits According to IEC standard 61000-3-2 setting harmonic emission limits for electric or electronic systems with current y 16 A, the following arrangements apply: b Independent dimmers for incandescent lamps with a rated power less than or equal to 1 kW have no limits applied b Otherwise, or for incandescent lighting equipment with built-in dimmer or dimmer built in an enclosure, the maximum permissible 3rd harmonic current is equal to 2.30 A Fluorescent lamps with magnetic ballast Fluorescent tubes and discharge lamps require the intensity of the arc to be limited, and this function is fulfilled by a choke (or magnetic ballast) placed in series with the bulb itself (see Fig. N40). This arrangement is most commonly used in domestic applications with a limited number of tubes. No particular constraint applies to the switches. Dimmer switches are not compatible with magnetic ballasts: the cancellation of the voltage for a fraction of the period interrupts the discharge and totally extinguishes the lampere The starter has a dual function: preheating the tube electrodes, and then generating an overvoltage to ignite the tube. This overvoltage is generated by the opening of a contact (controlled by a thermal switch) which interrupts the current circulating in the magnetic ballast. During operation of the starter (approx. 1 s), the current drawn by the luminaire is approximately twice the nominal current. Since the current drawn by the tube and ballast assembly is essentially inductive, the power factor is very low (on average between 0.4 and 0.5). In installations consisting of a large number of tubes, it is necessary to provide compensation to improve the power factor. For large lighting installations, centralized compensation with capacitor banks is a possible solution, but more often this compensation is included at the level of each luminaire in a variety of different layouts (see Fig. N41). a] Ballast b] C c] Ballast C a N30 C Lamp a Ballast Lamp Ballast Lamp Lamp a Compensation layout Application Comments Without compensation Parallel [a] Domestic Offices, workshops, superstores Single connection Risk of overcurrents for control devices Series [b] Duo [c] Choose capacitors with high operating voltage (450 to 480 V) Avoids flicker Fig. N41 : The various compensation layouts: a] parallel; b] series; c] dual series also called “duo” and their fields of application The compensation capacitors are therefore sized so that the global power factor is greater than 0.85. In the most common case of parallel compensation, its capacity is on average 1 µF for 10 W of active power, for any type of lampere However, this compensation is incompatible with dimmer switches. © Schneider Electric - all rights reserved Constraints affecting compensation Fig. N40 : Magnetic ballasts The layout for parallel compensation creates constraints on ignition of the lampere Since the capacitor is initially discharged, switch-on produces an overcurrent. An overvoltage also appears, due to the oscillations in the circuit made up of the capacitor and the power supply inductance. The following example can be used to determine the orders of magnitude. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits Assuming an assembly of 50 fluorescent tubes of 36 W each: b Total active power: 1,800 W b Apparent power: 2 kVA b Total rms current: 9 A b Peak current: 13 A With: b A total capacity: C = 175 µF b A line inductance (corresponding to a short-circuit current of 5 kA): L = 150 µH The maximum peak current at switch-on equals: 175 x 10-6 C = 230 2 = 350 A L 150 x 10-6 I c = Vmax The theoretical peak current at switch-on can therefore reach 27 times the peak current during normal operation. The shape of the voltage and current at ignition is given in Figure N42 for switch closing at the line supply voltage peak. There is therefore a risk of contact welding in electromechanical control devices (remote-control switch, contactor, circuit-breaker) or destruction of solid state switches with semi-conductors. (V) 600 400 200 0 t (s) -200 -400 -600 0 0.02 0.04 0.06 (A) 300 200 100 0 t (s) -100 N31 -200 -300 0 0.02 0.04 0.06 Fig. N42 : Power supply voltage at switch-on and inrush current Ignition of fluorescent tubes in groups implies one specific constraint. When a group of tubes is already switched on, the compensation capacitors in these tubes which are already energized participate in the inrush current at the moment of ignition of a second group of tubes: they “amplify” the current peak in the control switch at the moment of ignition of the second group. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved In reality, the constraints are usually less severe, due to the impedance of the cables. N - Characteristics of particular sources and loads 4 Lighting circuits The table in Figure N43, resulting from measurements, specifies the magnitude of the first current peak, for different values of prospective short-circuit current Isc. It is seen that the current peak can be multiplied by 2 or 3, depending on the number of tubes already in use at the moment of connection of the last group of tubes. Number of tubes already in use 0 14 28 42 Number of tubes connected 14 14 14 14 Inrush current peak (A) Isc = 1,500 A Isc = 3,000 A 233 250 558 556 608 607 618 616 Isc = 6,000 A 320 575 624 632 Fig. N43 : Magnitude of the current peak in the control switch of the moment of ignition of a second group of tubes Nonetheless, sequential ignition of each group of tubes is recommended so as to reduce the current peak in the main switch. The most recent magnetic ballasts are known as “low-loss”. The magnetic circuit has been optimized, but the operating principle remains the same. This new generation of ballasts is coming into widespread use, under the influence of new regulations (European Directive, Energy Policy Act - USA). In these conditions, the use of electronic ballasts is likely to increase, to the detriment of magnetic ballasts. Fluorescent lamps with electronic ballast Electronic ballasts are used as a replacement for magnetic ballasts to supply power to fluorescent tubes (including compact fluorescent lamps) and discharge lamps. They also provide the “starter” function and do not need any compensation capacity. The principle of the electronic ballast (see Fig. N44) consists of supplying the lamp arc via an electronic device that generates a rectangular form AC voltage with a frequency between 20 and 60 kHz. Supplying the arc with a high-frequency voltage can totally eliminate the flicker phenomenon and strobe effects. The electronic ballast is totally silent. During the preheating period of a discharge lamp, this ballast supplies the lamp with increasing voltage, imposing an almost constant current. In steady state, it regulates the voltage applied to the lamp independently of any fluctuations in the line voltage. Since the arc is supplied in optimum voltage conditions, this results in energy savings of 5 to 10% and increased lamp service life. Moreover, the efficiency of the electronic ballast can exceed 93%, whereas the average efficiency of a magnetic device is only 85%. The power factor is high (> 0.9). The electronic ballast is also used to provide the light dimming function. Varying the frequency in fact varies the current magnitude in the arc and hence the luminous intensity. N32 Inrush current © Schneider Electric - all rights reserved The main constraint that electronic ballasts bring to line supplies is the high inrush current on switch-on linked to the initial load of the smoothing capacitors (see Fig. N45). Technology Rectifier with PFC Rectifier with choke Magnetic ballast Fig. N44 : Electronic ballast Max. inrush current 30 to 100 In 10 to 30 In y 13 In Duration y 1 ms y 5 ms 5 to 10 ms Fig. N45 : Orders of magnitude of the inrush current maximum values, depending on the technologies used Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits In reality, due to the wiring impedances, the inrush currents for an assembly of lamps is much lower than these values, in the order of 5 to 10 In for less than 5 ms. Unlike magnetic ballasts, this inrush current is not accompanied by an overvoltage. Harmonic currents For ballasts associated with high-power discharge lamps, the current drawn from the line supply has a low total harmonic distortion (< 20% in general and < 10% for the most sophisticated devices). Conversely, devices associated with low-power lamps, in particular compact fluorescent lamps, draw a very distorted current (see Fig. N46). The total harmonic distortion can be as high as 150%. In these conditions, the rms current drawn from the line supply equals 1.8 times the current corresponding to the lamp active power, which corresponds to a power factor of 0.55. (A) 0.6 0.4 0.2 0 t (s) -0.2 -0.4 -0.6 0.02 0 Fig. N46 : Shape of the current drawn by a compact fluorescent lamp In order to balance the load between the different phases, lighting circuits are usually connected between phases and neutral in a balanced way. In these conditions, the high level of third harmonic and harmonics that are multiple of 3 can cause an overload of the neutral conductor. The least favorable situation leads to a neutral current which may reach 3 times the current in each phase. Harmonic emission limits for electric or electronic systems are set by IEC standard 61000-3-2. For simplification, the limits for lighting equipment are given here only for harmonic orders 3 and 5 which are the most relevant (see Fig. N47). Harmonic order 3 5 Active input power > 25W % of fundamental current 30 10 Active input power y 25W one of the 2 sets of limits apply: % of fundamental Harmonic current relative current to active power 86 3.4 mA/W 61 1.9 mA/W N33 Fig. N47 : Maximum permissible harmonic current Electronic ballasts usually have capacitors placed between the power supply conductors and the earth. These interference-suppressing capacitors are responsible for the circulation of a permanent leakage current in the order of 0.5 to 1 mA per ballast. This therefore results in a limit being placed on the number of ballasts that can be supplied by a Residual Current Differential Safety Device (RCD). At switch-on, the initial load of these capacitors can also cause the circulation of a current peak whose magnitude can reach several amps for 10 µs. This current peak may cause unwanted tripping of unsuitable devices. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Leakage currents N - Characteristics of particular sources and loads 4 Lighting circuits High-frequency emissions Electronic ballasts are responsible for high-frequency conducted and radiated emissions. The very steep rising edges applied to the ballast output conductors cause current pulses circulating in the stray capacities to earth. As a result, stray currents circulate in the earth conductor and the power supply conductors. Due to the high frequency of these currents, there is also electromagnetic radiation. To limit these HF emissions, the lamp should be placed in the immediate proximity of the ballast, thus reducing the length of the most strongly radiating conductors. The different power supply modes (see Fig. N48) Technology Standard incandescent Halogen incandescent ELV halogen incandescent Fluorescent tube Power supply mode Direct power supply Other device Dimmer switch Transformer Magnetic ballast and starter Electronic converter Electronic ballast Electronic dimmer + ballast Compact fluorescent lamp Mercury vapor High-pressure sodium Low-pressure sodium Metal halide Built-in electronic ballast Magnetic ballast Electronic ballast Fig. N48 : Different power supply modes 4.3 Constraints related to lighting devices and recommendations The current actually drawn by luminaires The risk This characteristic is the first one that should be defined when creating an installation, otherwise it is highly probable that overload protection devices will trip and users may often find themselves in the dark. It is evident that their determination should take into account the consumption of all components, especially for fluorescent lighting installations, since the power consumed by the ballasts has to be added to that of the tubes and bulbs. N34 The solution For incandescent lighting, it should be remembered that the line voltage can be more than 10% of its nominal value, which would then cause an increase in the current drawn. For fluorescent lighting, unless otherwise specified, the power of the magnetic ballasts can be assessed at 25% of that of the bulbs. For electronic ballasts, this power is lower, in the order of 5 to 10%. The thresholds for the overcurrent protection devices should therefore be calculated as a function of the total power and the power factor, calculated for each circuit. Overcurrents at switch-on © Schneider Electric - all rights reserved The risk The devices used for control and protection of lighting circuits are those such as relays, triac, remote-control switches, contactors or circuit-breakers. The main constraint applied to these devices is the current peak on energization. This current peak depends on the technology of the lamps used, but also on the installation characteristics (supply transformer power, length of cables, number of lamps) and the moment of energization in the line voltage period. A high current peak, however fleeting, can cause the contacts on an electromechanical control device to weld together or the destruction of a solid state device with semiconductors. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits Two solutions Because of the inrush current, the majority of ordinary relays are incompatible with lighting device power supply. The following recommendations are therefore usually made: b Limit the number of lamps to be connected to a single device so that their total power is less than the maximum permissible power for the device b Check with the manufacturers what operating limits they suggest for the devices. This precaution is particularly important when replacing incandescent lamps with compact fluorescent lamps By way of example, the table in Figure N49 indicates the maximum number of compensated fluorescent tubes that can be controlled by different devices with 16 A rating. Note that the number of controlled tubes is well below the number corresponding to the maximum power for the devices. Tube unit power requirement (W) Number of tubes corresponding to the power 16 A x 230 V 18 36 58 204 102 63 Maximum number of tubes that can be controlled by Contactors Remote CircuitGC16 A control breakers CT16 A switches C60-16 A TL16 A 15 50 112 15 25 56 10 16 34 Fig. N49 : The number of controlled tubes is well below the number corresponding to the maximum power for the devices But a technique exists to limit the current peak on energization of circuits with capacitive behavior (magnetic ballasts with parallel compensation and electronic ballasts). It consists of ensuring that activation occurs at the moment when the line voltage passes through zero. Only solid state switches with semi-conductors offer this possibility (see Fig. N50a). This technique has proved to be particularly useful when designing new lighting circuits. More recently, hybrid technology devices have been developed that combine a solid state switch (activation on voltage passage through zero) and an electromechanical contactor short-circuiting the solid state switch (reduction of losses in the semiconductors) (see Fig. N50b). N35 a b c © Schneider Electric - all rights reserved Fig. N50 : “Standard” CT+ contactor [a], CT+ contactor with manual override, pushbutton for selection of operating mode and indicator lamp showing the active operating mode [b], and TL + remote-control switch [c] (Merlin Gerin brand) Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads Modular contactors and impulse relays do not use the same technologies. Their rating is determined according to different standards. For example, for a given rating, an impulse relay is more efficient than a modular contactor for the control of light fittings with a strong inrush current, or with a low power factor (non-compensated inductive circuit). Type of lamp Unit power and capacitance of power factor correction capacitor Basic incandescent lamps LV halogen lamps Replacement mercury vapour lamps (without ballast) 40 W 60 W 75 W 100 W 150 W 200 W 300 W 500 W 1000 W 1500 W ELV 12 or 24 V halogen lamps With ferromagnetic transformer 20 W 50 W 75 W 100 W 20 W With electronic transformer 50 W 75 W 100 W Fluorescent tubes with starter and ferromagnetic ballast 1 tube 15 W without compensation (1) 18 W N36 1 tube with parallel compensation (2) © Schneider Electric - all rights reserved 2 or 4 tubes with series compensation 20 W 36 W 40 W 58 W 65 W 80 W 115 W 15 W 18 W 20 W 36 W 40 W 58 W 65 W 80 W 115 W 2 x 18 W 4 x 18 W 2 x 36 W 2 x 58 W 2 x 65 W 2 x 80 W 2 x 115 W Fluorescent tubes with electronic ballast 18 W 1 or 2 tubes 36 W 58 W 2 x 18 W 2 x 36 W 2 x 58 W 5 µF 5 µF 5 µF 5 µF 5 µF 7 µF 7 µF 7 µF 16 µF 4 Lighting circuits Choice of relay rating according to lamp type b Figure 51 below shows the maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp. As an indication, the total acceptable power is also mentioned. b These values are given for a 230 V circuit with 2 active conductors (single-phase phase/neutral or two-phase phase/phase). For 110 V circuits, divide the values in the table by 2. b To obtain the equivalent values for the whole of a 230 V three-phase circuit, multiply the number of lamps and the total acceptable power: v by 3 (1.73) for circuits without neutral; v by 3 for circuits with neutral. Note: The power ratings of the lamps most commonly used are shown in bold. Maximum number of light fittings for a single-phase circuit and maximum power output per circuit TL impulse relay CT contactor 16 A 32 A 16 A 25 A 40 A 40 25 20 16 10 8 5 3 1 1 115 85 70 50 35 26 18 10 6 4 1500 W to 1600 W 1500 W 70 28 19 14 60 25 18 14 1350 W to 1450 W 83 1250 W to 1300 W 70 62 35 31 21 20 16 11 60 50 45 25 22 16 13 11 7 56 1200 W to 1400 W 900 W 2000 W 28 28 17 15 12 8 80 40 26 40 20 13 106 66 53 42 28 21 13 8 4 2 4000 W to 4200 W 4000 W 180 74 50 37 160 65 44 33 3600 W to 3750 W 213 3200 W to 3350 W 186 160 93 81 55 50 41 29 160 133 120 66 60 42 37 30 20 148 3200 W to 3350 W 2400 W 5300 W 74 74 45 40 33 23 1450 W to 1550 W 212 106 69 106 53 34 3800 W to 4000 W 38 30 25 19 12 10 7 4 2 1 1550 W 57 to 45 2000 W 38 28 18 14 2100 W 10 6 3 2 15 10 8 6 62 25 20 16 300 W to 600 W 23 15 12 8 1250 W 90 to 39 1600 W 28 22 450 W to 900 W 22 330 W to 850 W 450 W to 1200 W 22 22 20 20 13 13 10 7 15 15 15 15 15 10 10 10 5 30 30 16 16 10 10 9 6 30 30 28 28 17 17 15 10 200 W 20 to 20 800 W 20 20 20 15 15 15 7 1100 W 46 to 24 1500 W 24 16 16 13 10 74 38 25 36 20 12 1300 W 111 to 58 1400 W 37 55 30 19 2300 W to 2850 W 3000 W 1850 W to 2250 W 300 W to 1200 W 1650 W to 2400 W 2000 W to 2200 W 63 A 4600 W to 5250 W 5500 W to 6000 W 42 27 23 18 182 76 53 42 850 W to 1950 W 70 1050 W to 2400 W 70 70 60 60 35 35 30 20 40 40 40 40 40 30 30 30 14 80 44 44 27 27 22 16 222 117 74 111 60 38 3650 W to 4200 W 600 W to 2400 W 2900 W to 3800 W 4000 W to 4400 W 172 125 100 73 50 37 25 15 8 5 6900 W to 7500 W 63 42 35 27 275 114 78 60 1250 W to 2850 W 100 1500 W to 3850 W 100 100 90 90 56 56 48 32 60 60 60 60 60 43 43 43 20 123 68 68 42 42 34 25 333 176 111 166 90 57 Fig. N51 : Maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp (Continued on opposite page) Schneider Electric - Electrical installation guide 2009 7500 W to 8000 W 5500 W to 6000 W 900 W to 3500 W 4450 W to 5900 W 6000 W to 6600 W Type of lamp Unit power and capacitance of power factor correction capacitor 4 Lighting circuits Maximum number of light fittings for a single-phase circuit and maximum power output per circuit TL impulse relay CT contactor 16 A 32 A 16 A 25 A Compact fluorescent lamps With external electronic ballast 5W 240 1200 W 630 3150 W 210 7W 171 to 457 to 150 9W 138 1450 W 366 3800 W 122 11 W 118 318 104 18 W 77 202 66 26 W 55 146 50 170 850 W 390 1950 W 160 With integral electronic ballast 5 W (replacement for incandescent 7 W 121 to 285 to 114 lamps) 9W 100 1050 W 233 2400 W 94 11 W 86 200 78 18 W 55 127 48 26 W 40 92 34 High-pressure mercury vapour lamps with ferromagnetic ballast without ignitor Replacement high-pressure sodium vapour lamps with ferromagnetic ballast with integral ignitor (3) Without compensation (1) 50 W not tested, 15 infrequent use 80 W 10 125 / 110 W (3) 8 250 / 220 W (3) 4 400 / 350 W (3) 2 700 W 1 With parallel compensation (2) 50 W 7 µF 10 80 W 8 µF 9 125 / 110 W (3) 10 µF 9 250 / 220 W (3) 18 µF 4 400 / 350 W (3) 25 µF 3 700 W 40 µF 2 1000 W 60 µF 0 Low-pressure sodium vapour lamps with ferromagnetic ballast with external ignitor 35 W 5 Without compensation (1) not tested, infrequent use 55 W 5 90 W 3 135 W 2 180 W 2 With parallel compensation (2) 35 W 20 µF 38 1350 W 102 3600 W 3 55 W 3 20 µF 24 63 90 W 26 µF 15 40 2 135 W 1 40 µF 10 26 180 W 45 µF 7 18 1 High-pressure sodium vapour lamps Metal-iodide lamps With ferromagnetic ballast with 35 W not tested, 16 external ignitor, without infrequent use 70 W 8 compensation (1) 150 W 4 250 W 2 400 W 1 1000 W 0 With ferromagnetic ballast with 35 W 6 µF 34 1200 W 88 3100 W 12 external ignitor and parallel to to 70 W 6 12 µF 17 45 compensation (2) 1350 W 22 3400 W 4 150 W 20 µF 8 250 W 32 µF 5 13 3 400 W 45 µF 3 8 2 1000 W 60 µF 1 3 1 2000 W 85 µF 0 1 0 With electronic ballast 35 W 38 1350 W 87 3100 W 24 to to 70 W 18 29 77 2200 W 33 5000 W 9 150 W 14 1050 W 330 to 222 1300 W 194 163 105 76 800 W 230 to 164 900 W 133 109 69 50 1650 W to 2000 W 750 W 20 to 15 1000 W 10 6 4 2 500 W 15 to 13 1400 W 10 6 4 2 1 1000 W to 1600 W 270 W to 360 W 100 W to 180 W 600 W 9 9 6 4 4 5 5 4 2 2 24 12 7 4 3 1 450 W 18 to 9 1000 W 6 4 3 2 1 850 W 38 to 29 1350 W 14 1150 W to 1300 W 750 W to 1600 W 320 W to 720 W 175 W to 360 W 850 W to 1200 W 650 W to 2000 W 1350 W to 2200 W 40 A 63 A 670 478 383 327 216 153 470 335 266 222 138 100 3350 W to 4000 W not tested 2350 W to 2600 W 710 514 411 340 213 151 3550 W to 3950 W 34 27 20 10 6 4 28 25 20 11 8 5 3 1700 W to 2800 W 53 40 28 15 10 6 43 38 30 17 12 7 5 2650 W to 4200 W 1400 W to 3500 W 14 14 9 6 6 10 10 8 5 4 500 W to 1100 W 42 20 13 8 5 2 31 16 10 7 5 3 2 68 51 26 1450 W to 2000 W 350 W to 720 W 1100 W to 4000 W 2400 W to 4000 W 2150 W to 5000 W 24 24 19 10 10 15 15 11 7 6 850 W to 1800 W 64 32 18 11 8 3 50 25 15 10 7 5 3 102 76 40 2250 W to 3200 W 550 W to 1100 W 1750 W to 6000 W 3600 W to 6000 W (1) Circuits with non-compensated ferromagnetic ballasts consume twice as much current for a given lamp power output. This explains the small number of lamps in this configuration. (2) The total capacitance of the power factor correction capacitors in parallel in a circuit limits the number of lamps that can be controlled by a contactor. The total downstream capacitance of a modular contactor of rating 16, 25, 40 or 63 A should not exceed 75, 100, 200 or 300 µF respectively. Allow for these limits to calculate the maximum acceptable number of lamps if the capacitance values are different from those in the table. (3) High-pressure mercury vapour lamps without ignitor, of power 125, 250 and 400 W, are gradually being replaced by high-pressure sodium vapour lamps with integral ignitor, and respective power of 110, 220 and 350 W. Fig. N51 : Maximum number of light fittings for each relay, according to the type, power and configuration of a given lamp (Concluded) Schneider Electric - Electrical installation guide 2009 N37 © Schneider Electric - all rights reserved N - Characteristics of particular sources and loads N - Characteristics of particular sources and loads 4 Lighting circuits Protection of lamp circuits: Maximum number of lamps and MCB rating versus lamp type, unit power and MCB tripping curve During start up of discharge lamps (with their ballast), the inrush current drawn by each lamp may be in the order of: b 25 x circuit start current for the first 3 ms b 7 x circuit start current for the following 2 s For fluorescent lamps with High Frequency Electronic control ballast, the protective device ratings must cope with 25 x inrush for 250 to 350 µs. However due to the circuit resistance the total inrush current seen by the MCB is lower than the summation of all individual lamp inrush current if directly connected to the MCB. The tables below (see Fig. N52 to NXX) take into account: b Circuits cables have a length of 20 meters from distribution board to the first lamp and 7 meters between each additional fittings. b MCB rating is given to protect the lamp circuit in accordance with the cable cross section, and without unwanted tripping upon lamp starting. b MCB tripping curve (C = instantaneous trip setting 5 to 10 In, D = instantaneous trip setting 10 to 14 In). Lamp power (W) 1 2 3 4 5 6 7 8 14/18 14 x2 14 x3 14 x4 18 x2 18 x4 21/24 21/24 x2 28 28 x2 35/36/39 35/36 x2 38/39 x2 40/42 40/42 x2 49/50 49/50 x2 54/55 54/55 x2 60 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Number of lamps per circuit 9 10 11 12 13 MCB rating C & D tripping curve 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 6 6 6 6 6 6 6 6 10 10 6 6 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 10 10 10 6 6 6 6 6 14 15 16 17 18 19 20 6 6 6 6 6 10 6 6 6 6 6 6 10 6 10 6 10 6 10 6 6 6 6 6 6 10 6 6 6 6 6 6 10 6 10 6 10 6 16 6 6 6 6 6 6 10 6 6 6 6 6 10 10 6 10 6 10 6 16 6 6 6 6 10 6 10 6 6 6 6 6 10 10 6 10 6 16 6 16 10 6 6 10 10 6 10 6 6 6 10 6 10 10 6 10 6 16 6 16 10 6 6 10 10 6 10 6 6 6 10 6 10 10 6 10 6 16 10 16 10 6 6 10 10 6 10 6 6 6 10 6 10 10 6 16 6 16 10 16 10 14 15 16 17 18 19 20 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 N38 © Schneider Electric - all rights reserved Fig. N52 : Fluorescent tubes with electronic ballast - Vac = 230 V Lamp power (W) 1 2 3 4 5 6 7 8 6 9 11 13 14 15 16 17 18 20 21 23 25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Number of lamps per circuit 9 10 11 12 13 MCB rating C & D tripping curve 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 Fig. N53 : Compact fluorescent lamps - Vac = 230 V Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits Lamp power (W) 1 2 3 4 5 6 7 8 50 80 125 250 400 1000 6 6 6 6 6 16 6 6 6 10 16 32 6 6 6 10 20 40 6 6 10 16 25 50 6 6 10 16 25 50 6 6 10 16 32 50 6 6 10 16 32 50 6 6 10 16 32 63 50 80 125 250 400 1000 6 6 6 6 6 10 6 6 6 6 10 20 6 6 6 10 16 25 6 6 6 10 16 32 6 6 6 10 20 40 6 6 6 10 20 40 6 6 10 16 25 50 6 6 10 16 25 63 Number of lamps per circuit 9 10 11 12 MCB rating C tripping curve 6 6 6 6 6 6 10 10 10 10 10 16 16 20 20 25 32 32 32 40 63 MCB rating D tripping curve 6 6 6 6 6 6 10 10 10 10 10 16 16 20 20 25 25 32 32 40 63 - 13 14 15 16 17 18 19 20 6 10 16 25 40 - 6 10 16 25 40 - 6 10 16 32 50 - 6 10 16 32 50 - 10 10 16 32 50 - 10 16 16 32 50 - 10 16 20 40 63 - 10 16 20 40 63 - 6 10 16 25 40 - 6 10 16 25 40 - 6 10 16 32 50 - 6 10 16 32 50 - 10 10 16 32 50 - 10 16 16 32 50 - 10 16 20 40 63 - 10 16 20 40 63 - Fig. N54 : High pressure mercury vapour (with ferromagnetic ballast and PF correction) - Vac = 230 V Lamp power (W) 1 2 Ferromagnetic ballast 18 6 6 26 6 6 35/36 6 6 55 6 6 91 6 6 131 6 6 135 6 6 180 6 6 Electronic ballast 36 6 6 55 6 6 66 6 6 91 6 6 Ferromagnetic ballast 18 6 6 26 6 6 35/36 6 6 55 6 6 91 6 6 131 6 6 135 6 6 180 6 6 Electronic ballast 36 6 6 55 6 6 66 6 6 91 6 6 3 4 5 6 7 8 Number of lamps per circuit 9 10 11 12 13 MCB rating C tripping curve 14 15 16 17 18 19 20 6 6 6 6 6 6 6 10 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 16 6 6 6 6 10 16 16 20 6 6 6 10 10 16 16 20 6 6 6 10 10 16 16 20 6 6 6 10 10 16 16 20 6 6 6 10 16 16 16 25 6 6 6 10 16 16 20 25 6 6 6 10 16 16 20 25 6 6 6 10 16 20 20 25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 MCB rating D tripping curve 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 16 6 6 10 16 6 6 10 16 6 6 10 16 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 6 6 6 6 6 6 6 10 6 6 6 6 6 6 10 10 6 6 6 6 6 10 10 10 6 6 6 6 6 10 10 16 6 6 6 6 6 10 10 16 6 6 6 6 10 10 10 16 6 6 6 6 10 10 16 16 6 6 6 6 10 16 16 20 6 6 6 6 10 16 16 20 6 6 6 10 10 16 16 20 6 6 6 10 10 16 16 20 6 6 6 10 16 16 16 25 6 6 6 10 16 16 20 25 6 6 6 10 16 16 20 25 6 6 6 10 16 20 20 25 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 10 6 6 6 16 6 6 10 16 6 6 10 16 6 6 10 16 6 6 6 6 10 10 10 16 6 6 6 6 10 10 10 16 6 6 6 6 10 10 16 16 N39 © Schneider Electric - all rights reserved Fig. N55 : Low pressure sodium (with PF correction) - Vac = 230 V Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads Lamp power (W) 1 2 Ferromagnetic ballast 50 6 6 70 6 6 100 6 6 150 6 6 250 6 10 400 10 16 1000 16 32 Electronic ballast 35 6 6 50 6 6 100 6 6 Ferromagnetic ballast 50 6 6 70 6 6 100 6 6 150 6 6 250 6 6 400 6 10 1000 10 20 Electronic ballast 35 6 6 50 6 6 100 6 6 4 Lighting circuits 3 4 5 6 7 8 Number of lamps per circuit 9 10 11 12 13 MCB rating C tripping curve 14 15 16 17 18 19 20 6 6 6 10 16 20 40 6 6 6 10 16 25 50 6 6 6 10 16 32 50 6 6 6 10 20 32 50 6 6 6 10 20 32 50 6 6 6 10 20 32 63 6 6 10 6 20 32 63 6 10 10 16 25 40 - 6 10 16 16 25 40 - 6 10 16 16 32 50 - 6 10 16 20 32 50 - 10 10 16 20 32 50 - 10 16 16 20 32 50 - 10 16 16 25 40 63 - 10 16 16 25 40 63 - 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 MCB rating D tripping curve 6 10 10 6 10 16 6 10 16 6 10 16 6 10 16 6 10 16 6 10 16 6 6 6 6 10 16 32 6 6 6 6 10 16 32 6 6 6 6 16 20 40 6 6 6 10 16 20 40 6 6 6 10 16 25 50 6 6 6 10 16 25 63 6 6 10 10 16 25 63 6 6 10 16 20 32 - 6 10 10 16 20 32 - 6 10 10 16 25 40 - 6 10 10 16 25 40 - 6 10 16 16 25 40 - 6 10 16 16 32 50 - 6 10 16 20 32 50 - 10 10 16 20 32 50 - 10 16 16 20 32 50 - 10 16 16 25 40 63 - 10 16 16 25 40 63 - 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 6 6 10 6 6 10 6 6 10 6 6 10 6 10 10 6 10 16 6 10 16 6 10 16 6 10 16 6 10 16 6 10 16 6 6 10 16 20 32 - 6 10 10 16 20 32 - 6 10 10 16 25 40 - Fig. N56 : High pressure sodium (with PF correction) - Vac = 230 V Lamp power (W) 1 2 Ferromagnetic ballast 35 6 6 70 6 6 150 6 6 250 6 10 400 6 16 1000 16 32 1800/2000 25 50 Electronic ballast 35 6 6 70 6 6 150 6 6 N40 Ferromagnetic ballast 35 6 6 70 6 6 150 6 6 250 6 6 400 6 10 1000 16 20 1800 16 32 2000 20 32 Electronic ballast 35 6 6 70 6 6 150 6 6 3 4 5 6 7 8 Number of lamps per circuit 9 10 11 12 13 MCB rating C tripping curve 14 15 16 17 18 19 20 6 6 10 16 20 40 63 6 6 10 16 25 50 63 6 6 10 16 25 50 63 6 6 10 20 32 50 - 6 6 10 20 32 50 - 6 6 10 20 32 63 - 6 6 10 20 32 63 - 6 10 16 25 40 63 - 6 10 16 25 40 63 - 6 10 16 32 50 63 - 6 10 20 32 50 63 - 6 10 20 32 50 63 - 6 16 20 32 50 63 - 6 16 25 40 63 63 - 6 16 25 40 63 63 - 6 6 6 6 6 10 6 6 10 6 6 10 6 6 10 6 6 10 6 6 6 6 6 6 6 6 6 10 10 10 16 16 16 MCB rating D tripping curve 6 10 16 6 10 16 6 10 16 6 10 16 6 10 20 6 10 20 6 10 20 6 6 6 10 16 32 40 40 6 6 6 10 16 32 50 50 6 6 6 16 20 40 63 63 6 6 10 16 20 50 63 - 6 6 10 16 25 50 - 6 6 10 16 25 63 - 6 6 10 16 25 63 - 6 6 16 20 32 - 6 6 16 20 32 - 6 10 16 25 40 - 6 10 16 25 40 - 6 10 16 25 40 - 6 10 16 32 50 - 6 10 20 32 50 - 6 10 20 32 50 - 6 16 20 32 50 - 6 16 25 40 63 - 6 16 25 40 63 - 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 6 6 10 6 6 10 6 6 16 6 6 16 6 10 16 6 10 16 6 10 16 6 10 16 6 10 16 6 10 20 6 10 20 6 10 20 13 14 15 16 17 18 19 20 - - - - - - - - - - - - - - - - 6 6 16 20 32 63 - 6 10 16 20 32 63 - 6 10 16 25 40 63 - © Schneider Electric - all rights reserved Fig. N57 : Metal halide (with PF correction) - Vac = 230 V Lamp power (W) 1 2 3 4 5 6 7 8 1800 2000 16 16 32 32 40 40 50 50 50 50 50 50 50 50 63 63 1800 2000 16 16 20 25 32 32 32 32 32 32 32 32 50 50 63 63 Number of lamps per circuit 9 10 11 12 MCB rating C tripping curve 63 63 MCB rating D tripping curve 63 - Fig. N58 : Metal halide (with ferromagnetic ballast and PF correction) - Vac = 400 V Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits Overload of the neutral conductor The risk In an installation including, for example, numerous fluorescent tubes with electronic ballasts supplied between phases and neutral, a high percentage of 3rd harmonic current can cause an overload of the neutral conductor. Figure N59 below gives an overview of typical H3 level created by lighting. Lamp type Incandescend lamp with dimmer ELV halogen lamp Typical power 100 W Setting mode Light dimmer Typical H3 level 5 to 45 % 25 W 5% Fluorescent tube 100 W < 25 W > 25 W 100 W Electronic ELV transformer Magnetic ballast Electronic ballast + PFC Magnetic ballast Electrical ballast Discharge lamp 10 % 85 % 30 % 10 % 30 % Fig. N59 : Overview of typical H3 level created by lighting The solution Firstly, the use of a neutral conductor with a small cross-section (half) should be prohibited, as requested by Installation standard IEC 60364, section 523–5–3. As far as overcurrent protection devices are concerned, it is necessary to provide 4-pole circuit-breakers with protected neutral (except with the TN-C system for which the PEN, a combined neutral and protection conductor, should not be cut). This type of device can also be used for the breaking of all poles necessary to supply luminaires at the phase-to-phase voltage in the event of a fault. A breaking device should therefore interrupt the phase and Neutral circuit simultaneously. Leakage currents to earth The risk At switch-on, the earth capacitances of the electronic ballasts are responsible for residual current peaks that are likely to cause unintentional tripping of protection devices. Two solutions The use of Residual Current Devices providing immunity against this type of impulse current is recommended, even essential, when equipping an existing installation (see Fig. N60). For a new installation, it is sensible to provide solid state or hybrid control devices (contactors and remote-control switches) that reduce these impulse currents (activation on voltage passage through zero). N41 Overvoltages The risk As illustrated in earlier sections, switching on a lighting circuit causes a transient state which is manifested by a significant overcurrent. This overcurrent is accompanied by a strong voltage fluctuation applied to the load terminals connected to the same circuit. These voltage fluctuations can be detrimental to correct operation of sensitive loads (micro-computers, temperature controllers, etc.) Sensitivity of lighting devices to line voltage disturbances Short interruptions b The risk Discharge lamps require a relighting time of a few minutes after their power supply has been switched off. Fig. N60 : s.i. residual current devices with immunity against impulse currents (Merlin Gerin brand) b The solution Partial lighting with instantaneous relighting (incandescent lamps or fluorescent tubes, or “hot restrike” discharge lamps) should be provided if safety requirements so dictate. Its power supply circuit is, depending on current regulations, usually distinct from the main lighting circuit. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved The Solution It is advisable to separate the power supply for these sensitive loads from the lighting circuit power supply. N - Characteristics of particular sources and loads 4 Lighting circuits Voltage fluctuations b The risk The majority of lighting devices (with the exception of lamps supplied by electronic ballasts) are sensitive to rapid fluctuations in the supply voltage. These fluctuations cause a flicker phenomenon which is unpleasant for users and may even cause significant problems. These problems depend on both the frequency of variations and their magnitude. Standard IEC 61000-2-2 (“compatibility levels for low-frequency conducted disturbances”) specifies the maximum permissible magnitude of voltage variations as a function of the number of variations per second or per minute. These voltage fluctuations are caused mainly by high-power fluctuating loads (arc furnaces, welding machines, starting motors). b The solution Special methods can be used to reduce voltage fluctuations. Nonetheless, it is advisable, wherever possible, to supply lighting circuits via a separate line supply. The use of electronic ballasts is recommended for demanding applications (hospitals, clean rooms, inspection rooms, computer rooms, etc). Developments in control and protection equipment The use of light dimmers is more and more common. The constraints on ignition are therefore reduced and derating of control and protection equipment is less important. New protection devices adapted to the constraints on lighting circuits are being introduced, for example Merlin Gerin brand circuit-breakers and modular residual current circuit-breakers with special immunity, such as s.i. type ID switches and Vigi circuit-breakers. As control and protection equipment evolves, some now offer remote control, 24-hour management, lighting control, reduced consumption, etc. 4.4 Lighting of public areas Normal lighting Regulations governing the minimum requirements for buildings receiving the public in most European countries are as follows: b Installations which illuminates areas accessible to the public must be controlled and protected independently from installations providing illumination to other areas b Loss of supply on a final lighting circuit (i.e. fuse blown or CB tripped) must not result in total loss of illumination in an area which is capable of accommodating more than 50 persons b Protection by Residual Current Devices (RCD) must be divided amongst several devices (i.e. more than on device must be used) Emergency lighting and other systems N42 When we refer to emergency lighting, we mean the auxiliary lighting that is triggered when the standard lighting fails. Emergency lighting is subdivided as follows (EN-1838): © Schneider Electric - all rights reserved Safety lighting It originates from the emergency lighting and is intended to provide lighting for people to evacuate an area safely or for those who try to fi nish a potentially dangerous operation before leaving the area. It is intended to illuminate the means of evacuation and ensure continuous visibility and ready usage in safety when standard or emergency lighting is needed. Safety lighting may be further subdivided as follows: Safety lighting for escape routes It originates from the safety lighting, and is intended to ensure that the escape means can be clearly identifi ed and used safely when the area is busy. Anti-panic lighting in extended areas It originates from the safety lighting, and is intended to avoid panic and to provide the necessary lighting to allow people to reach a possible escape route area. Emergency lighting and safety signs for escape routes The emergency lighting and safety signs for escape routes are very important for all those who design emergency systems. Their suitable choice helps improve safety levels and allows emergency situations to be handled better. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 4 Lighting circuits Standard EN 1838 ("Lighting applications. Emergency lighting") gives some fundamental concepts concerning what is meant by emergency lighting for escape routes: "The intention behind lighting escape routes is to allow safe exit by the occupants, providing them with suffi cient visibility and directions on the escape route …" The concept referred to above is very simple: The safety signs and escape route lighting must be two separate things. Functions and operation of the luminaires The manufacturing specifi cations are covered by standard EN 60598-2-22, "Particular Requirements - Luminaires for Emergency Lighting", which must be read with EN 60598-1, "Luminaires – Part 1: General Requirements and Tests". Duration A basic requirement is to determine the duration required for the emergency lighting. Generally it is 1 hour but some countries may have different duration requirements according to statutory technical standards. Operation We should clarify the different types of emergency luminaires: b Non-maintained luminaires v The lamp will only switch on if there is a fault in the standard lighting v The lamp will be powered by the battery during failure v The battery will be automatically recharged when the mains power supply is restored b Maintained luminaires v The lamp can be switched on in continuous mode v A power supply unit is required with the mains, especially for powering the lamp, which can be disconnected when the area is not busy v The lamp will be powered by the battery during failure. Design The integration of emergency lighting with standard lighting must comply strictly with electrical system standards in the design of a building or particular place. All regulations and laws must be complied with in order to design a system which is up to standard (see Fig. N61). The main functions of an emergency lighting system when standard lighting fails are the following: b Clearly show the escape route using clear signs. b Provide sufficient emergency lighting along the escape paths so that people can safely find their ways to the exits. N43 Fig. N61 : The main functions of an emergency lighting system European standards The design of emergency lighting systems is regulated by a number of legislative provisions that are updated and implemented from time to time by new documentation published on request by the authorities that deal with European and international technical standards and regulations. Each country has its own laws and regulations, in addition to technical standards Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved b Ensure that alarms and the fire safety equipment present along the way out are easily identifiable. N - Characteristics of particular sources and loads 4 Lighting circuits which govern different sectors. Basically they describe the places that must be provided with emergency lighting as well as its technical specifi cations. The designer's job is to ensure that the design project complies with these standards. EN 1838 A very important document on a European level regarding emergency lighting is the Standard EN 1838, "Lighting applications. Emergency lighting". This standard presents specifi c requirements and constraints regarding the operation and the function of emergency lighting systems. CEN and CENELEC standards With the CEN (Comité Européen de Normalisation) and CENELEC standards (Comité Européen de Normalisation Electrotechnique), we are in a standardised environment of particular interest to the technician and the designer. A number of sections deal with emergencies. An initial distinction should be made between luminaire standards and installation standards. EN 60598-2-22 and EN-60598-1 Emergency lighting luminaires are subject to European standard EN 60598-222, "Particular Requirements - Luminaires for Emergency Lighting", which is an integrative text (of specifi cations and analysis) of the Standard EN-60598-1, Luminaires – "Part 1: General Requirements and Tests". © Schneider Electric - all rights reserved N44 Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors The consequence of an incorrectly protected motor can include the following: The asynchronous (i.e. induction) motor is robust and reliable, and very widely used. 95% of motors installed around the world are asynchronous. The protection of these motors is consequently a matter of great importance in numerous applications. b For persons: v Asphyxiation due to the blockage of motor ventilation v Electrocution due to insulation failure in the motor v Accident due to non stopping of the motor following the failure of the control circuit in case of incorrect overcurrent protection b For the driven machine and the process v Shaft couplings and axles, etc, damaged due to a stalled rotor v Loss of production v Manufacturing time delayed b For the motor v Motor windings burnt out due to stalled rotor v Cost of dismantling and reinstalling or replacement of motor v Cost of repairs to the motor Therefore, the safety of persons and goods, and reliability and availability levels are highly dependant on the choice of protective equipment. In economic terms, the overall cost of failure must be considered. This cost is increasing with the size of the motor and with the difficulties of access and replacement. Loss of production is a further, and evidently important factor. Specific features of motor performance influence the power supply circuits required for satisfactory operation A motor power-supply circuit presents certain constraints not normally encountered in other (common) distribution circuits, owing to the particular characteristics, specific to motors, such as: b High start-up current (see Fig. N62) which is mostly reactive, and can therefore be the cause of important voltage drop b Number and frequency of start-up operations are generally high b The high start-up current means that motor overload protective devices must have operating characteristics which avoid tripping during the starting period 5.1 Functions for the motor circuit Functions generally provided are: b Basic functions including: v Isolating facility v Motor control (local or remote) v Protection against short-circuits v Protection against overload b Complementary protections including: v Thermal protection by direct winding temperature measurement v Thermal protection by indirect winding temperature determination v Permanent insulation-resistance monitoring v Specific motor protection functions N45 b Specific control equipment including: v Electromechanical starters v Control and Protective Switching devices (CPS) v Soft-start controllers v Variable speed drives t I" = 8 to 12 In Id = 5 to 8 In In = rated current of the motor Isolating facility It is necessary to isolate the circuits, partially or totally, from their power supply network for satety of personnel during maintenance work. “Isolation” function is provided by disconnectors. This function can be included in other devices designed to provide isolation such as disconnector/circuit-breaker. td 1 to 10s Motor control The motor control function is to make and break the motor current. In case of manual control, this function can be provided by motor-circuit-breakers or switches. In case of remote control, this function can be provided by contactors, starters or CPS. 20 to 30 ms In Id I" I Fig. N62 : Direct on-line starting current characteristics of an induction motor The control function can also be initiated by other means: b Overload protection b Complementary protection b Under voltage release (needed for a lot of machines) The control function can also be provided by specific control equipment. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Basic functions N - Characteristics of particular sources and loads 5 Asynchronous motors Protection against short-circuits b Phase-to-phase short-circuit This type of fault inside the machine is very rare. It is generally due to mechanical incident of the power supply cable of the motor. b Phase-to-earth short-circuit The deterioration of winding insulation is the main cause. The resulting fault current depends on the system of earthing. For the TN system, the resulting fault current is very high and in most cases the motor will be deteriorated. For the other systems of earthing, protection of the motor can be achieved by earth fault protection. For short-circuit protection, it is recommended to pay special attention to avoid unexpected tripping during the starting period of the motor. The inrush current of a standard motor is about 6 to 8 times its rated current but during a fault the current can be as high as 15 times the rated current. So, the starting current must not be seen as a fault by the protection. In addition, a fault occuring in a motor circuit must not disturb any upstream circuit. As a consequence, discrimination/selectivity of magnetic protections must be respected with all parts of the installation. Protection against overload Mechanical overloads due to the driven machine are the main origins of the overload for a motor application. They cause overload current and motor overheating. The life of the motor can be reduced and sometimes, the motor can be deteriorated. So, it is necessary to detect motor overload. This protection can be provided by: b Specific thermal overload relay b Specific thermal-magnetic circuit-breaker commonly referred to as “motor circuitbreaker” b Complementary protection (see below) like thermal sensor or electronic multifunction relay b Electronic soft start controllers or variable speed drives (see below) Complementary protections b Thermal protection by direct winding temperature measurement Provided by thermal sensors incorporated inside the windings of the motor and associated relays. b Thermal protection by indirect winding temperature determination Provided by multifunction relays through current measurement and taking into account the characteristics of the motors (e.g.: thermal time constant). b Permanent insulation-resistance monitoring relays or residual current differential relays They provide detection and protection against earth leakage current and short-circuit to earth, allowing maintenance operation before destruction of the motor. b Specific motor protection functions Such as protection against too long starting period or stalled rotor, protection against unbalanced, loss or permutation of phases, earth fault protection, no load protection, rotor blocked (during start or after)…; pre alarm overheating indication, communication, can also be provided by multifunction relays. N46 Specific control equipment © Schneider Electric - all rights reserved b Electromechanical starters (star-delta, auto-transformer, rheostatic rotor starters,…) They are generally used for application with no load during the starting period (pump, fan, small centrifuge, machine-tool, etc.) v Advantages Good torque/current ratio; great reduction of inrush current. v Disadvantages Low torque during the starting period; no easy adjustment; power cut off during the transition and transient phenomenon; 6 motor connection cables needed. b Control and Protective Switching devices (CPS) They provide all the basic functions listed before within a single unit and also some complementary functions and the possibility of communication. These devices also provide continuity of service in case of short-circuit. b Soft-start controllers Used for applications with pump, fan, compressor, conveyor. v Advantages Reduced inrush current, voltage drop and mechanical stress during the motor start; built-in thermal protection; small size device; possibility of communication v Disadvantages Low torque during the starting period; thermal dissipation. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors b Variable speed drives They are used for applications with pump, fan, compressor, conveyor, machine with high load torque, machine with high inertia. v Advantages Continuous speed variation (adjustment typically from 2 to 130% of nominal speed), overspeed is possible; accurate control of acceleration and deceleration; high torque during the starting and stopping periods; low inrush current, built-in thermal protection, possibility of communication. v Disadvantages Thermal dissipation, volume, cost. 5.2 Standards The motor control and protection can be achieved in different way: b By using an association of a SCPD (Short-Circuit-Protective-Device) and electromechanical devices such as v An electromechanical starters fulfilling the standard IEC 60947-4-1 v A semiconductor starter fulfilling the standard IEC 60947-4-2 v A variable speed drives fulfilling the standard series IEC 61800 b By using a CPS, single device covering all the basic functions, and fulfilling the standard IEC 60947-6-2 In this document, only the motor circuits including association of electromechanical devices such as, starters and protection against short-circuit, are considered. The devices meeting the standard 60947-6-2, the semiconductor starters and the variable speed drives will be considered only for specific points. A motor circuit will meet the rules of the IEC 60947-4-1 and mainly: b The co-ordination between the devices of the motor circuit b The tripping class of the thermal relays b The category of utilization of the contactors b The insulation co-ordination Note: The first and last points are satisfied inherently by the devices meeting the IEC 60947-6-2 because they provide a continuity of service. Standardization of the association circuit-breaker + contactor + thermal relay Type of current Alternating current Direct current Operating categories Typical uses AC-1 Non inductive or slightly inductive load, resistance furnace.Power distribution (lighting, generators, etc.). AC-2 Brush motor: starting, breaking.Heavy duty equipment (hoisting, handling, crusher, rolling-mill train, etc.). AC-3 Squirrel cage motor: starting, switching off running motors. Motor control (pumps, compressors, fans, machinetools, conveyors,presses, etc.). AC-4 Squirrel cage motor: starting, plugging, inching. Heavy-duty equipment (hoisting, handling, crusher, rolling-mill train, etc.). DC-1 Non inductive or slightly inductive load, resistance furnace. DC-3 Shunt wound motor: starting, reversing, counter-current breaking, inching.Dynamic breaking for direct current motors. DC-5 Series wound motor: starting, reversing, counter-current breaking, inching.Dynamic breaking for direct current motors. * Category AC-3 can be used for the inching or reversing, counter-current breaking for occasional operations of a limited length of time, such as for theassembly of a machine. The number of operations per limited length of time normally do not exceed five per minute and ten per 10 minutes. Fig. N63 : Contactor utilisation categories based on the purposes they are designed for, according to IEC 60947-1 Schneider Electric - Electrical installation guide 2009 N47 © Schneider Electric - all rights reserved Control devices categories The standards in the IEC 60947 series define the utilisation categoriesaccording to the purposes the control gear is designed for (see Fig. N63). Each category is characterised by one or more operating conditions such as: b Currents b Voltages b Power factor or time constant b And if necessary, other operating conditions N - Characteristics of particular sources and loads 5 Asynchronous motors The following is also taken into consideration: b Circuit making and breaking conditions b Type of load (squirrel cage motor, brush motor, resistor) b Conditions in which making and breaking take place (motor running,motor stalled, starting process, counter-current breaking, etc.) Coordination between protections and control It is coordination, the most efficient combination of the different protections(against short circuits and overloads) and the control device (contactor) which make up a motor starter unit. Studied for a given power, it provides the best possible protection of the equipment controlled by this motor starter unit (see Fig. N64). It has the double advantage of reducing equipment and maintenance costsas the different protections complement each other as exactly as possible,with no useless redundancy. Trip curve overload relay Fuse Trip of the overload relay alone Thermal limit of the breaker Overload relay limit Breaking current with SCPD (1) (1). Magnetic tripping of the breaker Fig. N64 : The basics of coordination © Schneider Electric - all rights reserved N48 There are different types of coordination Two types of coordination (type 1 and type 2) are defined by IEC 60947-4-1. b Type 1 coordination: The commonest standard solution. It requires that in event of a short circuit, the contactor or the starter do not put people or installations in danger. It admits the necessity of repairs or part replacements before service restoration. b Type 2 coordination: The high performance solution. It requires that in the event of a short circuit, the contactor or the starter do not put people or installations in danger and that it is able to work afterwards. It admits the risk of contact welding. In this case, the manufacturer must specify the measures to take for equipment maintenance. b Some manufacturers offer: The highest performance solution, which is “Total coordination”. This coordination requires that in the event of a short circuit, the contactor or the starter do not put people or installations in danger and that it is able to work afterwards. It does not admit the risk of contact welding and the starting of the motor starter unit must be immediate. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors Control and protection switching gear (CPS) CPS or “starter-controllers” are designed to fulfil control and protection functions simultaneously (overload and short circuit). In addition, they are designed to carry out control operations in the event of a short circuit. They can also assure additional functions such as insulation, thereby totally fulfilling the function of “motor starter unit”. They comply with standard IEC 60947-6-2, which notably defines the assigned values and utilisation categories of a CPS, as do standards IEC 60947-1 and 60947-4-1. The functions performed by a CPS are combined and coordinated in such a way as to allow for uptime at all currents up to the Ics working short circuit breaking capacity of the CPS. The CPS may or may not consist of one device, but its characteristics are assigned as for a single device. Furthermore, the guarantee of “total” coordination of all the functions ensures the user has a simple choice with optimal protection which is easy to implement. Although presented as a single unit, a CPS can offer identical or greater modularity than the “three product” motor starter unit solution. This is the case with the “Tesys U” starter-controller (see Fig. N65). Fig. N65 : Example of a CPS modularity (Tesys Ustarter controller by Telemecanique) N49 © Schneider Electric - all rights reserved This starter-controller can at any time bring in or change a control unit with protection and control functions for motors from 0.15A to 32A in a generic “base power” or “base unit” of a 32 A calibre. Additional functionality’s can also be installed with regard to: b Power, reversing block, limiter b Control v Functions modules, alarms, motor load, automatic resetting, etc, v Communication modules: AS-I, Modbus, Profibus, CAN-Open, etc, v Auxiliary contact modules, added contacts. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors Communications functions are possible with this system (see Fig. N66). Available functions: Standard Control units: Upgradeable Multifunction Starter status (ready, running, with default) Alarms (overcurrents…) Thermal alarm Remote resetting by bus Indication of motor load Defaults differentiation Parameter setting and protection function reference “Log file” function “Monitoring” function Start and Stop controls Information conveyed by bus (Modbus) and functions performed Fig. N66 : Tesys U Communication functions What sort of coordination does one choose? The choice of the coordination type depends on the operation parameters. It should be made to achieve the best balance of user needs and installation costs. b Type 1 Acceptable when uptime is not required and the system can be reactivated after replacing the faulty parts. In this case the maintenance service must be efficient (available andcompetent). The advantage is reduced equipment costs. b Type 2 To be considered when the uptime is required. It requires a reduced maintenance service. When immediate motor starting is necessary, “Total coordination”mustbe retained. No maintenance service is necessary. The coordinations offered in the manufacturers’ catalogues simplify the users’ choice and guarantees that the motor starter unit complies with the standard. 5.3 Applications N50 The control and protection of a motor can consist of one, two, three or four different devices which provide one or several functions. © Schneider Electric - all rights reserved In the case of the combination of several devices, co-ordination between them is essential in order to provide optimized protection of the motor application. To protect a motor circuit, many parameters must be taken into account. They depend on: b The application (type of driven machine, safety of operation, number of operations, etc.) b The continuity performance requested by the application b The standards to be enforced to provide security and safety. The electrical functions to be provided are quite different: b Start, normal operation and stop without unexpected tripping while maintaining control requirements, number of operations, durability and safety requirements (emergency stops), as well as circuit and motor protection, disconnection (isolation) for safety of personnel during maintenance work. Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors Basic protection schemes: circuit-breaker + contactor + thermal relay Among the many possible methods of protecting a motor, the association of a circuit breaker + contactor + thermal relay (1) provides many advantages Avantages The combination of devices facilitates installation work, as well as operation and maintenance, by: b The reduction of the maintenance work load: the circuit-breaker avoids the need to replace blown fuses and the necessity of maintaining a stock (of different sizes and types) b Better continuity performance: the installation can be re-energized immediately following the elimination of a fault and after checking of the starter b Additional complementary devices sometimes required on a motor circuit are easily accomodated b Tripping of all three phases is assured (thereby avoiding the possibility of “single phasing”) b Full load current switching possibility (by circuit-breaker) in the event of contactor failure, e.g. contact welding b Interlocking b Diverse remote indications b Better protection for the starter in case of overcurrent and in particular for impedant short-circuit (2) corresponding to currents up to about 30 times In of motor (see Fig. N67). b Possibility of adding RCD: v Prevention of risk of fire (sensitivity 500 mA) v Protection against destruction of the motor (short-circuit of laminations) by the early detection of earth fault currents (sensitivity 300 mA to 30 A) t 1.05 to 1.20 In Circuit breaker Magnetic relay Operating curve of thermal relay End of start-up period Contactor Thermal relay Cable thermal withstand limit 1 to 10 s Limit of thermal relay constraint Cable Motor Short circuit current breaking capacity of the association (CB + contactor) Operating curve of the MA type circuit breaker 20 to 30 ms In Is I" magn. I Short circuit current breaking capacity of the CB N51 Fig. N67 : Tripping characteristics of a circuit-breaker + contactor + thermal relay (1) (1) The combination of a contactor with a thermal relay is commonly referred to as a “discontactor”. (2) In the majority of cases, short-circuit faults occur at the motor, so that the current is limited by the cable and the wiring of the starter and are called impedant short-circuits Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Conclusion The combination of a circuit-breaker + contactor + thermal relay for the control and protection of motor circuits is eminently appropriate when: b The maintenance service for an installation is reduced, which is generally the case in tertiary and small and medium sized industrial sites b The job specification calls for complementary functions b There is an operational requirement for a load breaking facility in the event of need of maintenance. N - Characteristics of particular sources and loads 5 Asynchronous motors Key points in the successful combination of a circuit-breaker and a discontactor Standards define precisely the elements which must be taken into account to achieve a correct coordination of type 2: b Absolute compatibility between the thermal relay of the discontactor and the magnetic trip of the circuit-breaker. In Figure N68 the thermal relay is protected if its limit boundary for thermal withstand is placed to the right of the circuit-breaker magnetic trip characteristic curve. In the case of a motor control circuit-breaker incorporating both magnetic and thermal relay devices, coordination is provided by design. b The overcurrent breaking capability of the contactor must be greater than the current corresponding to the setting of the circuit-breaker magnetic trip relay. b When submitted to a short-circuit current, the contactor and its thermal relay must perform in accordance with the requirements corresponding to the specified type of co-ordination. Compact type MA t 1 Operating curve of the MA type circuit breaker 2 Operating curve of thermal relay 3 Limit of thermal relay constraint 2 Icc ext. 3 1 I Fig. N68 : The thermal-withstand limit of the thermal relay must be to the right of the CB magnetic-trip characteristic Short-circuit current-breaking capacity of a circuit-breaker + contactor combination It is not possible to predict the short-circuit current-breaking capacity of a circuit-breaker + contactor combination. Only laboratory tests by manufacturers allow to do it. So, Schneider Electric can give table with combination of N52 Multi 9 and Compact type MA circuit-breakers with different types of starters At the selection stage, the short-circuit current-breaking capacity which must be compared to the prospective short-circuit current is: b Either, that of the circuit-breaker + contactor combination if the circuit-breaker and the contactor are physically close together (see Fig. N69) (same drawer or compartment of a motor control cabinet). A short-circuit downstream of the combination will be limited to some extent by the impedances of the contactor and the thermal relay. The combination can therefore be used on a circuit for which the prospective short-circuit current level exceeds the rated short-circuit currentbreaking capacity of the circuit-breaker. This feature very often presents a significant economic advantage © Schneider Electric - all rights reserved b Or that of the circuit-breaker only, for the case where the contactor is separated (see Fig. N70) with the risk of short-circuit between the contactor and the circuitbreaker. M M Fig. N69 : Circuit-breaker and contactor mounted side by side Fig. N70 : Circuit-breaker and contactor mounted separately Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors Choice of instantaneous magnetic-trip relay for the circuitbreaker The operating threshold must never be less than 12 In for this relay, in order to avoid unexpected tripping due to the first current peak during motor starting. Complementary protections Complementary protections are: b Thermal sensors in the motor (windings, bearings, cooling-air ducts, etc.) b Multifunction protections (association of functions) b Insulation-failure detection devices on running or stationary motor Thermal sensors Thermal sensors are used to detect abnormal temperature rise in the motor by direct measurement. The thermal sensors are generally embedded in the stator windings (for LV motors), the signal being processed by an associated control device acting to trip the contactor or the circuit-breaker (see Fig. N71). Fig. N71 : Overheating protection by thermal sensors Mutifunction motor protection relay The multifunction relay, associated with a number of sensors and indication modules, provides protection for motor and also for some functions, protection of the driven machine such as: b Thermal overload b Stalled rotor, or starting period too long b Overheating b Unbalanced phase current, loss of one phase, inverse rotation b Earth fault (by RCD) b Running at no-load, blocked rotor on starting Preventive protection of stationary motors This protection concerns the monitoring of the insulation resistance level of a stationary motor, thereby avoiding the undesirable consequences of insulation failure during operation such as: b Failure to start or to perform correctly for motor used on emergency systems b Loss of production This type of protection is essential for emergency systems motors, especially when installed in humid and/or dusty locations. Such protection avoids the destruction of a motor by short-circuit to earth during starting (one of the most frequently-occuring incidents) by giving a warning informing that maintenance work is necessary to restore the motor to a satisfactory operationnal condition. Schneider Electric - Electrical installation guide 2009 N53 © Schneider Electric - all rights reserved The avantages are essentially: b A comprehensive protection, providing a reliable, high performance and permanent monitoring/control function b Efficient monitoring of all motor-operating schedules b Alarm and control indications b Possibility of communication via communication buses Example: Telemecanique LT6 relay with permanent monitoring/control function and communication by bus, or multifunction control unit LUCM and communication module for TeSys model U. N - Characteristics of particular sources and loads 5 Asynchronous motors Example of application: Motors driving pumps for “sprinklers” fire-protection systems or irrigation pumps for seasonal operation. A Vigilohm SN21 (Merlin Gerin) monitors the insulation of a motor, and signals audibly and visually any abnormal reduction of the insulation resistance level. Furthermore, this relay can prevent any attempt to start the motor, if necessary (see Fig. N72). SM21 M E R LIN G E R IN SM20 IN OUT Fig. N72 : Preventive protection of stationary motors Limitative protections Residual current diffential protective devices (RCDs) can be very sensitive and detect low values of leakage current which occur when the insulation to earth of an installation deteriorates (by physical damage, contamination, excessive humidity, and so on). Some versions of RCDs, with dry contacts, specially designed for such applications, provide the following: b To avoid the destruction of a motor (by perforation and short-circuiting of the laminations of the stator) caused by an eventual arcing fault to earth. This protection can detect incipient fault conditions by operating at leakage currents in the range of 300 mA to 30 A, according to the size of the motor (approx sensitivity: 5% In) b To reduce the risk of fire: sensitivity y 500 mA N54 For example, RH99M relay (Merlin Gerin) provides (see Fig. N73): b 5 sensitivities (0.3; 1; 3; 10; 30 A) b Possibility of discrimination or to take account of particular operation by virtue of 3 possible time delays (0, 90, 250 ms) b Automatic breaking if the circuit from the current transformer to the relay is broken b Protection against unwanted trippings b Protection against DC leakage currents (type A RCD) © Schneider Electric - all rights reserved RH99M M E R LIN G E R IN Fig. N73 : Example using relay RH99M Schneider Electric - Electrical installation guide 2009 N - Characteristics of particular sources and loads 5 Asynchronous motors The importance of limiting the voltage drop at the motor terminals during start-up In order to have a motor starting and accelerating to its normal speed in the appropriate time, the torque of the motor must exceed the load torque by at least 70%. However, the starting current is much higher than the full-load current of the motor. As a result, if the voltage drop is very high, the motor torque will be excessively reduced (motor torque is proportional to U2) and it will result, for extreme case, in failure to start. Example: b With 400 V maintained at the terminals of a motor, its torque would be 2.1 times that of the load torque b For a voltage drop of 10% during start-up, the motor torque would be 2.1 x 0.92 = 1.7 times the load torque, and the motor would accelerate to its rated speed normally b For a voltage drop of 15% during start-up, the motor torque would be 2.1 x 0.852 = 1.5 times the load torque, so that the motor starting time would be longer than normal In general, a maximum allowable voltage drop of 10% is recommended during start-up of the motor. 5.4 Maximum rating of motors installed for consumers supplied at LV The disturbances caused on LV distribution networks during the start-up of large direct-on-line AC motors can cause considerable nuisance to neighbouring consumers, so that most power-supply utilities have strict rules intended to limit such disturbances to tolerable levels. The amount of disturbance created by a given motor depends on the “strength” of the network, i.e. on the short-circuit fault level at the point concerned. The higher the fault level, the “stronger” the system and the lower the disturbance (principally voltage drop) experienced by neibouring consumers. For distribution networks in many countries, typical values of maximum allowable starting currents and corresponding maximum power ratings for direct-on-line motors are shown in Figures N74 and N75 below. Type of motor Location Single phase Dwellings Others Dwellings Others Three phase Maximum starting current (A) Overhead-line network Underground-cable network 45 45 100 200 60 60 125 250 Fig. N74 : Maximum permitted values of starting current for direct-on-line LV motors (230/400 V) N55 Location Dwellings Others Overhead line network Underground cable network Type of motor Single phase 230 V (kW) 1.4 3 Three phase 400 V Direct-on-line starting at full load (kW) 5.5 11 Other methods of starting (kW) 11 22 5.5 22 45 Since, even in areas supplied by one power utility only, “weak” areas of the network exist as well as “strong” areas, it is always advisable to secure the agreement of the power supplier before acquiring the motors for a new project. Other (but generally more costly) alternative starting arrangements exist, which reduce the large starting currents of direct-on-line motors to acceptable levels; for example, star-delta starters, slip-ring motor, “soft start” electronic devices, etc. 5.5 Reactive-energy compensation (power-factor correction) The method to correct the power factor is indicated in chapter L. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Fig. N75 : Maximum permitted power ratings for LV direct-on-line starting motors Chapter P Residential and other special locations Contents 1 Residential and similar premises P2 1.1 1.2 1.3 1.4 1.5 P2 P2 P4 P6 P7 2 Bathrooms and showers P8 2.1 Classification of zones 2.2 Equipotential bonding 2.3 Requirements prescribed for each zone P8 P11 P11 3 Recommendations applicable to special installations and locations P12 General Distribution boards components Protection of people Circuits Protection against overvoltages and lightning © Schneider Electric - all rights reserved P1 Schneider Electric - Electrical installation guide 2009 P - Residential and other special locations 1 Residential and similar premises 1.1 General Electrical installations for residential premises need a high standard of safety and reliability Related standards Most countries have national regulations and-or standards governing the rules to be strictly observed in the design and realization of electrical installations for residential and similar premises. The relevant international standard is the publication IEC 60364. The power distribution utility connects the LV neutral point to its MV/LV distribution tranformer to earth. All LV installations must be protected by RCDs. All exposed conductive parts must be bonded together and connected to the earth. The power network The vast majority of power distribution utilities connect the low voltage neutral point of their MV/LV distribution transformers to earth. The protection of persons against electric shock therefore depends, in such case, on the principle discussed in chapter F. The measures required depend on whether the TT, TN or IT scheme of earthing is adopted. RCDs are essential for TT and IT earthed installations. For TN installations, high speed overcurrent devices or RCDs may provide protection against direct contact of the electrical circuits. To extend the protection to flexible leads beyond the fixed socket outlets and to ensure protection against fires of electrical origin RCDs shall be installed. The quality of electrical equipment used in residential premises is commonly ensured by a mark of conformity situated on the front of each item 1.2 Distribution boards components (see Fig. P1) Distribution boards (generally only one in residential premises) usually include the meter(s) and in some cases (notably where the supply utilities impose a TT earthing system and/or tariff conditions which limit the maximum permitted current consumption) an incoming supply differential circuit-breaker which includes an overcurrent trip. This circuit-breaker is freely accessible to the consumer. Enclosure Service connection Distribution board Lightning protection Incoming-supply circuit breaker Combi surge arrester Overcurrent protection and isolation P2 Protection against direct and indirect contact, and protection against fire © Schneider Electric - all rights reserved Remote control MCB phase and neutral Differential MCB Differential load switch Remote control switch TL 16 A Energy management Programmable thermostat THP Load shedding switch CDSt Programmable time switch IHP Contactors, off-peak or manual control CT Fig. P1 : Presentation of realizable functions on a consumer unit Schneider Electric - Electrical installation guide 2009 P - Residential and other special locations 1 Residential and similar premises On installations which are TN earthed, the supply utilities usually protect the installation simply by means of sealed fuse cut-outs immediately upstream of the meter(s) (see Fig. P2). The consumer has no access to these fuses. Meter Fuse … or … Circuit breaker depending on earthing system Distribution board Fig. P2 : Components of a control and distribution board The incoming supply circuit-breaker (see Fig. P3) Fig. P3 : Incoming-supply circuit-breaker The consumer is allowed to operate this CB if necessary (e.g to reclose it if the current consumption has exceeded the authorized limit; to open it in case of emergency or for isolation purposes). The rated residual current of the incoming circuit-breaker in the earth leakage protection shall be 300 mA. If the installation is TT, the earth electrode resistance shall be less than 50 V  166  .. In practice, the earth electrode resistance of a new installation 300 mA R  ( ).. shall be less than 80 Ω 2 R The control and distribution board (consumer unit) (see Fig. P4) This board comprises: b A control panel for mounting (where appropriate) the incoming supply circuitbreaker and other control auxiliaries, as required b A distribution panel for housing 1, 2 or 3 rows (of 24 multi 9 units) or similar MCBs or fuse units, etc. b Installation accessories for fixing conductors, and rails for mounting MCBs, fuses bases, etc, neutral busbar and earthing bar, and so on b Service cable ducts or conduits, surface mounted or in cable chases embedded in the wall Note: to facilitate future modifications to the installation, it is recommended to keep all relevant documents (photos, diagrams, characteristics, etc.) in a suitable location close to the distribution board. The board should be installed at a height such that the operating handles, indicating dials (of meters) etc., are between 1 metre and 1.80 metres from the floor (1.30 metres in situations where handicapped or elderly people are concerned). Fig. P4 : Control and distribution board Lightning arresters The installation of lightning arresters at the service position of a LV installation is strongly recommended for installations which include sensitive (e.g electronic) equipment. P3 Resistance value of the earth electrode In the case where the resistance to earth exceeds 80 Ω, one or several 30 mA RCDs should be used in place of the earth leakage protection of the incoming supply circuit-breaker. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved If, in a TT scheme, the value of 80 Ω for the resistance of the electrode can not be met then, 30 mA RCDs must be installed to take over the function of the earth leakage protection of the incoming supply circuit-breaker These devices must automatically disconnect themselves from the installation in case of failure or be protected by a MCB. In the case of residential installations, the use of a 300 mA differential incoming supply circuit-breaker type S (i.e slightly timedelayed) will provide effective earth leakage protection, while, at the same time, will not trip unnecessarily each time a lightning arrester discharges the current (of an overvoltage-surge) to earth. P - Residential and other special locations 1 Residential and similar premises Where utility power supply systems and consumers’ installations form a TT earthed system, the governing standards impose the use of RCDs to ensure the protection of persons 1.3 Protection of people On TT earthed systems, the protection of persons is ensured by the following measures: b Protection against indirect contact hazards by RCDs (see Fig. P5) of medium sensitivity (300 mA) at the origin of the installation (incorporated in the incoming supply circuit-breaker or, on the incoming feed to the distribution board). This measure is associated with a consumer installed earth electrode to which must be connected the protective earth conductor (PE) from the exposed conductive parts of all class I insulated appliances and equipment, as well as those from the earthing pins of all socket outlets b When the CB at the origin of an installation has no RCD protection, the protection of persons shall be ensured by class II level of insulation on all circuits upstream of the first RCDs. In the case where the distribution board is metallic, care shall be taken that all live parts are double insulated (supplementary clearances or insulation, use of covers, etc.) and wiring reliably fixed b Obligatory protection by 30 mA sensitive RCDs of socket outlet circuits, and circuits feeding bathroom, laundry rooms, and so on (for details of this latter obligation, refer to clause 3 of this chapter) 300 mA 30 mA Diverse circuits Socket-outlets circuit 30 mA Bathroom and/or shower room Fig. P5 : Installation with incoming-supply circuit-breaker having instantaneous differential protection Incoming supply circuit-breaker with instantaneous differential relay P4 In this case: b An insulation fault to earth could result in a shutdown of the entire installation b Where a lightning arrester is installed, its operation (i.e. discharging a voltage surge to earth) could appear to an RCD as an earth fault, with a consequent shutdown of the installation © Schneider Electric - all rights reserved Recommendation of suitable Merlin Gerin components b Incoming supply circuit-breaker with 300 mA differential and b High sensitivity 30 mA RCD (for example differential circuit-breaker 1P + N type Declic Vigi) on the circuits supplying socket outlets b High sensitivity 30 mA RCD (for example differential load switch type ID’clic) on circuits to bathrooms, shower rooms, laundry rooms, etc. (lighting, heating, socket outlets) Incoming supply circuit-breaker with type S time delayed differential relay This type of CB affords protection against fault to earth, but by virtue of a short time delay, provides a measure of discrimination with downstream instantaneous RCDs. Tripping of the incoming supply CB and its consequences (on deep freezers, for example) is thereby made less probable in the event of lightning, or other causes of voltage surges. The discharge of voltage surge current to earth, through the surge arrester, will leave the type S circuit-breaker unaffected. Schneider Electric - Electrical installation guide 2009 P - Residential and other special locations 1 Residential and similar premises Recommendation of suitable Merlin Gerin components (see Fig. P6) b Incoming supply circuit-breaker with 300 mA differential type S and b High sensitivity 30 mA RCD (for example differential circuit-breaker 1P + N type Declic Vigi) on the circuits supplying washing machines and dish-washing machine b High sensitivity 30 mA RCD (for example differential load switch type ID’clic) on circuits to bathrooms, shower rooms, laundry rooms, etc. (lighting, heating, socket outlets) 300 mA - type S 30 mA 30 mA 30 mA 1 Diverse High-risk location Socketoutlet circuits (laundry room) circuit 2 Bathroom and/or shower room Fig. P6 : Installation with incoming-supply circuit-breaker having short time delay differential protection, type S Incoming supply circuit-breaker without differential protection 5 300 mA 3 4 30 mA 30 mA 30 mA Socket-outlet circuit Diverse circuits High-risk circuit (dish-washing machine) Fig. P7 : Installation with incoming-supply circuit-breaker having no differential protection Recommendation of suitable Merlin Gerin components Figure P7 refers: 1. Incoming-supply circuit-breaker without differential protection 2. Automatic disconnection device (if a lightning arrester is installed) 3. 30 mA RCD (for example differential circuit-breaker 1P + N type Declic Vigi) on each circuit supplying one or more socket-outlets 4. 30 mA RCD (for example differential load swith type ID’clic) on circuits to bathrooms and shower rooms (lighting, heating and socket-outlets) or a 30 mA differential circuit-breaker per circuit 5. 300 mA RCD (for example differential load swith) on all the other circuits P5 © Schneider Electric - all rights reserved Bathroom and/or shower room In this case the protection of persons must be ensured by: b Class II level of insulation up to the downstream terminals of the RCDs b All outgoing circuits from the distribution board must be protected by 30 mA or 300 mA RCDs according to the type of circuit concerned as discussed in chapter F. Where a voltage surge arrester is installed upstream of the distribution board (to protect sensitive electronic equipment such as microprocessors, videocassette recorders, TV sets, electronic cash registers, etc.) it is imperative that the device automatically disconnects itself from the installation following a rare (but always possible) failure. Some devices employ replaceable fusing elements; the recommended method however as shown in Figure P7, is to use a circuit-breaker. Schneider Electric - Electrical installation guide 2009 P - Residential and other special locations 1 Residential and similar premises The distribution and division of circuits provides comfort and facilitates rapid location of fault 1.4 Circuits Subdivision National standards commonly recommend the subdivision of circuits according to the number of utilization categories in the installation concerned (see Fig. P8): b At least 1 circuit for lighting. Each circuit supplying a maximum of 8 lighting points b At least 1 circuit for socket-outlets rated 10/16 A, each circuit supplying a maximum of 8 sockets. These sockets may be single or double units (a double unit is made up of two 10/16 A sockets mounted on a common base in an embedded box, identical to that of a single unit b 1 circuit for each appliance such as water heater, washing machine, dish-washing machine, cooker, refrigerator, etc. Recommended numbers of 10/16 A (or similar) socket-outlets and fixed lighting points, according to the use for which the various rooms of a dwelling are intended, are indicated in Figure P9 Room function Socketoutlets Lighting Heating Washing Cooking machine apparatus Fig. P8 : Circuit division according to utilization The inclusion of a protective conductor in all circuits is required by IEC and most national standards Minimum number of fixed lighting points 1 1 Minimum number of 10/16 A socket-outlets 5 3 Living room Bedroom, lounge, bureau, dining room Kitchen 2 4 (1) Bathroom, shower room 2 1 or 2 Entrance hall, box room 1 1 WC, storage space 1 Laundry room 1 (1) Of which 2 above the working surface and 1 for a specialized circuit: in addition an independent socket-outlet of 16 A or 20 A for a cooker and a junction box or socket-outlet for a 32 A specialized circuit Fig P9 : Recommended minimum number of lighting and power points in residential premises Protective conductors IEC and most national standards require that each circuit includes a protective conductor. This practice is strongly recommended where class I insulated appliances and equipment are installed, which is the general case. The protective conductors must connect the earthing-pin contact in each socketoutlet, and the earthing terminal in class I equipment, to the main earthing terminal at the origin of the installation. Furthermore, 10/16 A (or similarly sized) socket-outlets must be provided with shuttered contact orifices. Cross-sectional-area (c.s.a.) of conductors (see Fig. P10) © Schneider Electric - all rights reserved P6 The c.s.a. of conductors and the rated current of the associated protective device depend on the current magnitude of the circuit, the ambient temperature, the kind of installation, and the influence of neighbouring circuits (refer to chapter G) Moreover, the conductors for the phase wires, the neutral and the protective conductors of a given circuit must all be of equal c.s.a. (assuming the same material for the conductors concerned, i.e. all copper or all aluminium). Fig. P10 : Circuit-breaker 1 phase + N - 2 x 9 mm spaces Schneider Electric - Electrical installation guide 2009 P - Residential and other special locations 1 Residential and similar premises Figure P11 indicates the c.s.a. required for commonly-used appliances Protective devices 1 phase + N in 2 x 9 mm spaces comply with requirements for isolation, and for marking of circuit current rating and conductor sizes. Type of circuit single-phase 230 V 1 ph + N or 1 ph + N + PE Fixed lighting c. s. a. of the conductors Maximum power Protective device 1.5 mm2 (2.5 mm2) 2,300 W Circuit-breaker Fuse 16 A 10 A 10/16 A 2.5 mm2 (4 mm2) 4,600 W Circuit-breaker Fuse 25 A 20 A 2.5 mm2 (4 mm2) 4,600 W Circuit-breaker Fuse 25 A 20 A Dish-washing machine 2.5 mm2 (4 mm2) 4,600 W Circuit-breaker Fuse 25 A 20 A Clothes-washing machine 2.5 mm2 (4 mm2) 4,600 W Circuit-breaker Fuse 25 A 20 A Cooker or hotplate (1) 6 mm2 (10 mm2) 7,300 W Circuit-breaker Fuse 40 A 32 A Electric space heater 1.5 mm2 (2.5 mm2) 2,300 W Circuit-breaker Fuse 16 A 10 A Individual-load circuits Water heater (1) In a 230/400 V 3-phase circuit, the c. s. a. is 4 mm2 for copper or 6 mm2 for aluminium, and protection is provided by a 32 A circuit-breaker or by 25 A fuses. Fig. P11 : C. s. a. of conductors and current rating of the protective devices in residential installations (the c. s. a. of aluminium conductors are shown in brackets) 1.5 Protection against overvoltages and lightning The choice of surge arrester is described in chapter J Installation rules Three principal rules must be respected: 1 - It is imperative that the three lengths of cable used for the installation of the surge arrester each be less than 50 cm i.e.: b the live conductors connected to the isolating switch b from the isolating switch to the surge arrester b from the surge arrester to the main distribution board (MDB) earth bar (not to be confused with the main protective-earth (PE) conductor or the main earth terminal for the installation.The MDB earth bar must evidently be located in the same cabinet as the surge arrester. P7 3 - In the interest of a good continuity of supply it is recommended that the circuit-breaker be of the time-delayed or selective type. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 2 - It is necessary to use an isolating switch of a type recommended by the manufacturer of the surge arrester. P - Residential and other special locations 2 Bathrooms and showers Bathrooms and showers rooms are areas of high risk, because of the very low resistance of the human body when wet or immersed in water. Precaution to be taken are therefore correspondingly rigorous, and the regulations are more severe than those for most other locations. The relevant standard is IEC 60364-7-701. Precautions to observe are based on three aspects: b The definition of zones, numbered 0,1, 2, 3 in which the placement (or exclusion) of any electrical device is strictly limited or forbidden and, where permitted, the electrical and mechanical protection is prescribed b The establishment of an equipotential bond between all exposed and extraneous metal parts in the zones concerned b The strict adherence to the requirements prescribed for each particular zones, as tabled in clause 3 2.1 Classification of zones Sub-clause 701.32 of IEC 60364-7-701 defines the zones 0, 1, 2, 3 as shown in the following diagrams (see Fig. P12 below to Fig P18 opposite and next pages): Zone 1* Zone 1* Zone 2 Zone 3 Zone 0 Zone 2 Zone 0 0.60 m 2.40 m 2.40 m 0.60 m Zone 1 Zone 2 Zone 3 2.25 m Zone 1 Zone 0 0.60 m P8 Zone 3 2.40 m (*) Zone 1 is above the bath as shown in the vertical cross-section © Schneider Electric - all rights reserved Fig. P12 : Zones 0, 1, 2 and 3 in proximity to a bath-tub Schneider Electric - Electrical installation guide 2009 2 Bathrooms and showers Zone 0 Zone 1 Zone 2 Zone 0 Zone 1 Zone 3 Zone 2 Zone 3 2.40 m 0.60 m 2.40 m 0.60 m Zone 1 Zone 3 Zone 2 2.25 m Zone 1 Zone 0 2.40 m 0.60 m Fig. P13 : Zones 0, 1, 2 and 3 in proximity of a shower with basin Fixed shower head (1) Fixed shower head (1) 0.60 m Zone 1 0.60 m Zone 2 0.60 m Zone 1 0.60 m Zone 2 Zone 3 Zone 1 2.40 m Zone 2 2.40 m Zone 3 Zone 3 2.25 m (1) When the shower head is at the end of a flexible tube, the vertical central axis of a zone passes through the fixed end of the flexible tube Fig. P14 : Zones 0, 1, 2 and 3 in proximity of a shower without basin P9 0.60 m 0.60 m Fig. P15 : No switch or socket-outlet is permitted within 60 cm of the door opening of a shower cabinet Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Prefabricated shower cabinet P - Residential and other special locations 2 Bathrooms and showers Classes of external influences AD 3 BB 2 BC 3 Classes of external influences AD 3 BB 2 BC 3 Zone 3 Dressing cubicles (zone 2) AD 3 BB 3 BC 3 AD 7 BB 3 BC 3 AD 3 WC BB 2 BC 3 Shower cabinets (zone 1) Fig. P16 : Individual showers with dressing cubicles Classes of external influences Classes of external influences h < 1.10m AD 5 1.10m < h < 2.25m AD 3 BB 3 BC 3 h < 1.10m AD 5 1.10m < h < 2.25m AD 3 BB 3 BC 3 Dressing cubicles AD 7 BB 3 BC 3 Zone 2 Zone 1 WC AD 3 BB 2 BC 3 Fig. P17 : Individual showers with separate individual dressing cubicles Classes of external influences Classes of external influences AD 3 BB 2 BC 3 h < 1.10m AD 5 1.10m < h < 2.25m AD 3 BB 3 BC 3 h < 1.10m AD 5 1.10m < h < 2.25m AD 3 BB 3 BC 3 Dressing room Zone 2 Zone 2 Zone 1 AD 7 BB 3 BC 3 P10 Fig. P18 : Communal showers and common dressing room © Schneider Electric - all rights reserved Note: Classes of external influences (see Fig. E46). Schneider Electric - Electrical installation guide 2009 2 Bathrooms and showers 2.2 Equipotential bonding (see Fig. P19) To the earth electrode Metallic pipes hi 2m Water-drainage piping Socket-outlet Gaz Radiator Lighting Metal bath Equipotential conductors for a bathroom Metal door-frame Fig. P19 : Supplementary equipotential bonding in a bathroom 2.3 Requirements prescribed for each zone The table of clause 3 describes the application of the principles mentioned in the foregoing text and in other similar or related cases P11 © Schneider Electric - all rights reserved P - Residential and other special locations Schneider Electric - Electrical installation guide 2009 P - Residential and other special locations 3 Recommendations applicable to special installations and locations Figure P20 below summarizes the main requirements prescribed in many national and international standards. Note: Section in brackets refer to sections of IEC 60364-7 Locations Protection principles IP level 20 Domestic dwellings and other habitations Bathrooms or shower rooms (section 701) Zone 0 b TT or TN-S systems b Differential protection v 300 mA if the earth electrode resistance is y 80 ohms instantaneous or short time delay (type S) v 30 mA if the earth electrode resistance is u 500 ohms b surge arrester at the origin of the installation if v supply is from overhead line with bare conductors, and if v the keraunic level > 25 b a protective earth (PE) conductor on all circuits Supplementary equipotential bonding in zones 0, 1, 2 and 3 SELV 12 V only 27 Zone 1 SELV 12 V 25 Zone 2 SELV 12 V or 30 mA RCD 24 Zone 3 Swimming baths (section 702) Zone 0 © Schneider Electric - all rights reserved P12 Wiring and cables 28 Class II limited to strict minimum Class II limited to strict minimum Class II limited to strict minimum Zone 2 22 (indoor) 24 (outdoor) 24 Class II 44 Special appliances Special aplliances Water heater Special appliances Water heater Class II luminaires Class II limited to strict minimum Class II limited to strict minimum 25 Conventional voltage limit UL reduced to 25 V Conventional voltage limit UL reduced to 25 V Protection against fire risks by 500 mA RCDs Installation materials Only socket-outlets protected by : b 30 mA RCD or b Electrical separation or b SELV 50 V Zone 1 Saunas (section 703) Work sites (section 704) Agricultural and horticultural establishments (section 705) Restricted conductive locations (section 706) Socket-outlets Switch operating handles Protection by and similar devices on 30 mA RCDs distribution panels, to be mounted between 1 metre and 1.80 metre above the floor 21 Supplementary equipotential bonding in zones 0, 1, and 2 SELV 12 V Switchgear Special appliances Special appliances Only socket-outlets protected by : b 30 mA RCD or b electrical separation or b SELV 50 V Mechanically protected 35 2x Fig. P20 : Main requirements prescribed in many national and international standards (continued on opposite page) Schneider Electric - Electrical installation guide 2009 Adapted to temperature Protection by 30 mA RCDs Protection by 30 mA RCDs Protection of: b Portable tools by: v SELV or v Electrical separation b Hand-held lamps v By SELV b Fixed equipement by v SELV v Electrical separation v 30 mA RCDs v Special supplementary equipotential bonding P - Residential and other special locations 3 Recommendations applicable to special installations and locations Locations Protection principles Fountains (section 702) Protection by 30 mA RCDs and equipotential bonding of all exposed and extraneous conductive parts TN-S system recommended TT system if leakage current is limited. Protective conductor 10 mm2 minimum in aluminium. Smaller sizes (in copper) must be doubled. Data processing (section 707) Caravan park (section 708) Marinas and pleasure craft (section 709) The cable length for connection to pleasure craft must not exceeded 25 m Medical locations Group 2 : Operating theatres and similar (section 710) IT medical system equipotential grouding, limited to one operating theatre and not exceeding 10 kVA Medical locations Group 1 : Hospitalization and similar (section 710) Exhibitions, shows and stands (section 711) Balneotherapy (cure-centre baths) TT or TNS Motor-fuel filling stations Motor vehicules TT or TN-S systems IP level Wiring and cables 55 Flexible cable of 25 metres length Switchgear Only magnetic protection for the primary of LV/LV transformer. Monitoring of secondary loads and transformer temperature Socket-outlets Installation materials Socket-outlets shall be placed at a height of 0.80 m to 1.50 m from the ground. Protection of circuits by 30 mA RCDs (one per 6 socket-outlets) Protection of circuits by 30 mA RCDs (one per 6 socket-outlets) Protection of circuits by thermal-magnetic protection only. One to three per circuit. Protection by 30 mA RCDs 4x Individual: see section 701 (volumes 0 and 1) Collective: see section 702 (volumes 0 and 1) Explosion risks in security zones Protection by 30 mA RCDs Limited to the necessary minimum Protection by RCDs or by electrical separation External lighting installations (section 714) Mobile or transportable The use of TN-C system is not units (section 717) permitted inside any unit 23 Protection by 30 mA RCDs 30 mA RCDs must be used for all socket-outlets supplying equipment outside the unit P13 © Schneider Electric - all rights reserved Fig. P20 : Main requirements prescribed in many national and international standards (concluded) Schneider Electric - Electrical installation guide 2009 Chapter Q EMC guidelines Contents 1 2 3 Electrical distribution Q2 Earthing principles and structures Q3 Implementation Q5 3.1 Equipotential bonding inside and outside buildings 3.2 Improving equipotential conditions 3.3 Separating cables 3.4 False loor 3.5 Cable running 3.6 Implementation of shielded cables 3.7 Communication networks 3.8 Implementation of surge arrestors 3.9 Cabinet cabling 3.10 Standards Q5 Q5 Q7 Q7 Q8 Q11 Q11 Q12 Q15 Q15 4 Coupling mechanisms and counter-measures Q16 4.1 4.2 4.3 4.4 4.5 Q16 Q17 Q18 Q19 Q20 5 Wiring recommendations Q22 5.1 Signal classes 5.2 Wiring recommendations Q22 Q22 General Common-mode impedance coupling Capacitive coupling Inductive coupling Radiated coupling © Schneider Electric - all rights reserved Q1 Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 1 Electrical distribution The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. Figure Q1 below presents a summary of their main characteristics. European standards (see EN 50174-2 § 6.4 and EN 50310 § 6.3) recommend the TN-S system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment). Safety of persons Safety of property Availability of energy EMC behaviour TT Good RCD mandatory Good Medium fault current (< a few dozen amperes) Good Good - Risk of overvoltages - Equipotential problems - Need to manage devices with high leakage currents TN-S IT TN-C Good Continuity of the PE conductor must be ensured throughout the installation Poor Good Poor Low current for irst fault High fault current High fault current (around 1 kA) (< a few dozen mA), (around 1 kA) but high for second fault Good Excellent Good Excellent Poor (to be avoided) Poor (should never be used) - Few equipotential - Risk of overvoltages problems - Common-mode ilters - Neutral and PE are - Need to manage and surge arrestors the same devices with high must handle the phase- - Circulation of disturbed leakage currents to-phase voltages currents in exposed - High fault currents - RCDs subject to conductive parts (high (transient disturbances) nuisance tripping if magnetic-ield radiation) common-mode - High fault currents capacitors are present (transient disturbances) - Equivalent to TN system for second fault Fig. Q1 : Main characteristics of system earthing When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers speciically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS). Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system. Figure Q2 below illustrate these recommendations. © Schneider Electric - all rights reserved Lighting Q2 Disturbing Sensitive devices devices Disturbing Sensitive devices devices Not recommended Preferable Fig. Q2 : Recommendations of separated distributions Schneider Electric - Electrical installation guide 2009 Air conditioning Transformer Disturbing devices Sensitive devices Excellent 2 Earthing principles and structures This section deals with the earthing and equipotential bonding of information-technology devices and other similar devices requiring interconnections for signalling purposes. Earthing networks are designed to fulil a number of functions. They can be independent or operate together to provide one or more of the following: b Safety of persons with respect to electrical hazards b Protection of equipment with respect to electrical hazards b A reference value for reliable, high-quality signals b Satisfactory EMC performance The system earthing arrangement is generally designed and installed in view of obtaining a low impedance capable of diverting fault currents and HF currents away from electronic devices and systems. There are different types of system earthing arrangements and some require that speciic conditions be met. These conditions are not always met in typical installations. The recommendations presented in this section are intended for such installations. For professional and industrial installations, a common bonding network (CBN) may be useful to ensure better EMC performance with respect to the following points: b Digital systems and new technologies b Compliance with the EMC requirements of EEC 89/336 (emission and immunity) b The wide number of electrical applications b A high level of system safety and security, as well as reliability and/or availability For residential premises, however, where the use of electrical devices is limited, an isolated bonding network (IBN) or, even better, a mesh IBN may be a solution. It is now recognised that independent, dedicated earth electrodes, each serving a separate earthing network, are a solution that is not acceptable in terms of EMC, but also represent a serious safety hazard. In certain countries, the national building codes forbid such systems. Use of a separate “clean” earthing network for electronics and a “dirty” earthing network for energy is not recommended in view of obtaining correct EMC, even when a single electrode is used (see Fig. Q3 and Fig. Q4). In the event of a lightning strike, a fault current or HF disturbances as well as transient currents will low in the installation. Consequently, transient voltages will be created and result in failures or damage to the installation. If installation and maintenance are carried out properly, this approach may be dependable (at power frequencies), but it is generally not suitable for EMC purposes and is not recommended for general use. Surge arrestors "Clean" earthing network Electrical earthing network Separate earth electrodes Q3 Fig. Q3 : Independent earth electrodes, a solution generally not acceptable for safety and EMC reasons Surge arrestors "Clean" earthing network Electrical earthing network Single earth electrode Fig. Q4 : Installation with a single earth electrode Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Q - EMC guidelines Q - EMC guidelines 2 Earthing principles and structures The recommended coniguration for the earthing network and electrodes is two or three dimensional (see Fig. Q5). This approach is advised for general use, both in terms of safety and EMC. This recommendation does not exclude other special conigurations that, when correctly maintained, are also suitable. Equipotential bonding required for multi-level buildings Surge arrestors "Electrical" and "communication" earthing as needed Multiple interconnected earth electrodes Fig. Q5 : Installation with multiple earth electrodes In a typical installation for a multi-level building, each level should have its own earthing network (generally a mesh) and all the networks must be both interconnected and connected to the earth electrode. At least two connections are required (built in redundancy) to ensure that, if one conductor breaks, no section of the earthing network is isolated. Practically speaking, more than two connections are made to obtain better symmetry in current low, thus reducing differences in voltage and the overall impedance between the various levels in the building. The many parallel paths have different resonance frequencies. If one path has a high impedance, it is most probably shunted by another path with a different resonance frequency. On the whole, over a wide frequency spectrum (dozens of Hz and MHz), a large number of paths results in a low-impedance system (see Fig. Q6). Fig. Q6 : Each level has a mesh and the meshes are interconnected at several points between levels. Certain ground-floor meshes are reinforced to meet the needs of certain areas Each room in the building should have earthing-network conductors for equipotential bonding of devices and systems, cableways, trunking systems and structures. This system can be reinforced by connecting metal pipes, gutters, supports, frames, etc. In certain special cases, such as control rooms or computers installed on false loors, ground reference plane or earthing strips in areas for electronic systems can be used to improve earthing of sensitive devices and protection interconnection cables. © Schneider Electric - all rights reserved Q4 Schneider Electric - Electrical installation guide 2009 3 Implementation 3.1 Equipotential bonding inside and outside buildings The fundamental goals of earthing and bonding are the following: b Safety By limiting the touch voltage and the return path of fault currents b EMC By avoiding differences in potential and providing a screening effect. Stray currents are inevitably propagated in an earthing network. It is impossible to eliminate all the sources of disturbances for a site. Earth loops are also inevitable. When a magnetic ield affects a site, e.g. the ield created by lightning, differences in potential are created in the loops formed by the various conductors and the currents lowing in the earthing system. Consequently, the earthing network is directly affected by any counter-measures taken outside the building. As long as the currents low in the earthing system and not in the electronic circuits, they do no damage. However, when earthing networks are not equipotential, e.g. when they are star connected to the earth electrode, the HF stray currents will low wherever they can, including in control wires. Equipment can be disturbed, damaged or even destroyed. The only inexpensive means to divide the currents in an earthing system and maintain satisfactory equipotential characteristics is to interconnect the earthing networks. This contributes to better equipotential bonding within the earthing system, but does not remove the need for protective conductors. To meet legal requirements in terms of the safety of persons, suficiently sized and identiied protective conductors must remain in place between each piece of equipment and the earthing terminal. What is more, with the possible exception of a building with a steel structure, a large number of conductors for the surge-arrestor or the lightningprotection network must be directly connected to the earth electrode. The fundamental difference between a protective conductor (PE) and a surgearrestor down-lead is that the irst conducts internal currents to the neutral of the MV/LV transformer whereas the second carries external current (from outside the installation) to the earth electrode. In a building, it is advised to connect an earthing network to all accessible conducting structures, namely metal beams and door frames, pipes, etc. It is generally suficient to connect metal trunking, cable trays and lintels, pipes, ventilation ducts, etc. at as many points as possible. In places where there is a large amount of equipment and the size of the mesh in the bonding network is greater than four metres, an equipotential conductor should be added. The size and type of conductor are not of critical importance. It is imperative to interconnect the earthing networks of buildings that have shared cable connections. Interconnection of the earthing networks must take place via a number of conductors and all the internal metal structures of the buildings or linking the buildings (on the condition that they are not interrupted). In a given building, the various earthing networks (electronics, computing, telecom, etc.) must be interconnected to form a single equipotential bonding network. This earthing-network must be as meshed as possible. If the earthing network is equipotential, the differences in potential between communicating devices will be low and a large number of EMC problems disappear. Differences in potential are also reduced in the event of insulation faults or lightning strikes. If equipotential conditions between buildings cannot be achieved or if the distance between buildings is greater than ten metres, it is highly recommended to use optical ibre for communication links and galvanic insulators for measurement and communication systems. Q5 These measures are mandatory if the electrical supply system uses the IT or TN-C system. 3.2 Improving equipotential conditions Bonding networks Even though the ideal bonding network would be made of sheet metal or a ine mesh, experience has shown that for most disturbances, a three-metre mesh size is suficient to create a mesh bonding network. Examples of different bonding networks are shown in Figure Q7 next page. The minimum recommended structure comprises a conductor (e.g. copper cable or strip) surrounding the room. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Q - EMC guidelines Q - EMC guidelines 3 Implementation Mesh BN IBN PE Mesh BN Mesh IBN Local mesh Local mesh IBN Trunk Tree structure IBN Star (IBN) CBN BN: Bonding network CBN: Common bonding network IBN: Isolated bonding network Fig. Q7 : Examples of bonding networks The length of connections between a structural element and the bonding network does not exceed 50 centimetres and an additional connection should be installed in parallel at a certain distance from the irst. The inductance of the connection between the earthing bar of the electrical enclosure for a set of equipment and the bonding network (see below) should be less than one µHenry (0.5 µH, if possible). For example, it is possible to use a single 50 cm conductor or two parallel conductors one meter long, installed at a minimum distance from one another (at least 50 cm) to reduce the mutual inductance between the two conductors. Where possible, connection to the bonding network should be at an intersection to divide the HF currents by four without lengthening the connection. The proile of the bonding conductors is not important, but a lat proile is preferable. The conductor should also be as short as possible. Parallel earthing conductor (PEC) The purpose of a parallel earthing conductor is to reduce the common-mode current lowing in the conductors that also carry the differential-mode signal (the commonmode impedance and the surface area of the loop are reduced). © Schneider Electric - all rights reserved Q6 The parallel earthing conductor must be designed to handle high currents when it is used for protection against lightning or for the return of high fault currents. When cable shielding is used as a parallel earthing conductor, it cannot handle such high currents and the solution is to run the cable along metal structural elements or cableways which then act as other parallel earthing conductors for the entire cable. Another possibility is to run the shielded cable next to a large parallel earthing conductor with both the shielded cable and the parallel earthing conductor connected at each end to the local earthing terminal of the equipment or the device. For very long distances, additional connections to the network are advised for the parallel earthing conductor, at irregular distances between the devices. These additional connections form a shorter return path for the disturbing currents lowing through the parallel earthing conductor. For U-shaped trays, shielding and tubes, the additional connections should be external to maintain the separation with the interior (“screening” effect). Bonding conductors Bonding conductors may be metal strips, lat braids or round conductors. For highfrequency systems, metal strips and lat braids are preferable (skin effect) because a round conductor has a higher impedance than a lat conductor with the same cross section. Where possible, the length to width ratio should not exceed 5. Schneider Electric - Electrical installation guide 2009 3 Implementation 3.3 Separating cables The physical separation of high and low-current cables is very important for EMC, particularly if low-current cables are not shielded or the shielding is not connected to the exposed conductive parts (ECPs). The sensitivity of electronic equipment is in large part determined by the accompanying cable system. If there is no separation (different types of cables in separate cableways, minimum distance between high and low-current cables, types of cableways, etc.), electromagnetic coupling is at its maximum. Under these conditions, electronic equipment is sensitive to EMC disturbances lowing in the affected cables. Use of busbar trunking systems such as Canalis or busbar ducts for high power ratings is strongly advised. The levels of radiated magnetic ields using these types of trunking systems is 10 to 20 times lower than standard cables or conductors. The recommendations in the “Cable running” and “Wiring recommendations” sections should be taken into account. 3.4 False floors The inclusion of the loors in the mesh contributes to equipotentiality of the area and consequently to the distribution and dilution of disturbing LF currents. The screening effect of a false loor is directly related to its equipotentiality. If the contact between the loor plates is poor (rubber antistatic joints, for example) or if the contact between the support brackets is faulty (pollution, corrosion, mildew, etc. or if there are no support brackets), it is necessary to add an equipotential mesh. In this case, it is suficient to ensure effective electrical connections between the metal support columns. Small spring clips are available on the market to connect the metal columns to the equipotential mesh. Ideally, each column should be connected, but it is often suficient to connect every other column in each direction. A mesh 1.5 to 2 metres is size is suitable in most cases. The recommended cross-sectional area of the copper is 10 mm2 or more. In general, a lat braid is used. To reduce the effects of corrosion, it is advised to use tin-plated copper (see Fig. Q8). Perforated loor plates act like normal loor plates when they have a cellular steel structure. Preventive maintenance is required for the loor plates approximately every ive years (depending on the type of loor plate and the environment, including humidity, dust and corrosion). Rubber or polymer antistatic joints must be maintained, similar to the bearing surfaces of the loor plates (cleaning with a suitable product). False floor Q7 Spring clips Metal support columns u 10 mm2 Fig. Q8 : False floor implementation Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved Q - EMC guidelines Q - EMC guidelines 3 Implementation 3.5 Cable running Selection of materials and their shape depends on the following criteria: b Severity of the EM environment along cableways (proximity of sources of conducted or radiated EM disturbances) b Authorised level of conducted and radiated emissions b Type of cables (shielded?, twisted?, optical ibre?) b EMI withstand capacity of the equipment connected to the wiring system b Other environmental constraints (chemical, mechanical, climatic, ire, etc.) b Future extensions planned for the wiring system Non-metal cableways are suitable in the following cases: b A continuous, low-level EM environment b A wiring system with a low emission level b Situations where metal cableways should be avoided (chemical environment) b Systems using optical ibres For metal cableways, it is the shape (lat, U-shape, tube, etc.) rather than the crosssectional area that determines the characteristic impedance. Closed shapes are better than open shapes because they reduce common-mode coupling. Cableways often have slots for cable straps. The smaller the better. The types of slots causing the fewest problems are those cut parallel and at some distance from the cables. Slots cut perpendicular to the cables are not recommended (see Fig. Q9). Mediocre OK Better Fig. Q9 : CEM performance of various types of metal cableways In certain cases, a poor cableway in EMI terms may be suitable if the EM environment is low, if shielded cables or optical ibres are employed, or separate cableways are used for the different types of cables (power, data processing, etc.). It is a good idea to reserve space inside the cableway for a given quantity of additional cables. The height of the cables must be lower than the partitions of the cableway as shown below. Covers also improve the EMC performance of cableways. In U-shaped cableways, the magnetic ield decreases in the two corners. That explains why deep cableways are preferable (see Fig. Q10). © Schneider Electric - all rights reserved Q8 NO! YES! Area protected against external EM field Fig. Q10 : Installation of different types of cables Different types of cables (power and low-level connections) should not be installed in the same bundle or in the same cableway. Cableways should never be illed to more than half capacity. Schneider Electric - Electrical installation guide 2009 3 Implementation It is recommended to electromagnetically separate groups from one another, either using shielding or by installing the cables in different cableways. The quality of the shielding determines the distance between groups. If there is no shielding, suficient distances must be maintained (see Fig. Q11). The distance between power and control cables must be at least 5 times the radius of the larger power cable. Forbidden Ideal Correct Power cables Auxiliary circuits (relay contacts) Control (digital) Measurements (analogue) Note: All metal parts must be electrically interconnected Fig. Q11 : Recommendation to install groups of cables in metal cableways Metal building components can be used for EMC purposes. Steel beams (L, H, U or T shaped) often form an uninterrupted earthed structure with large transversal sections and surfaces with numerous intermediate earthing connections. Cables should if possible be run along such beams. Inside corners are better than the outside surfaces (see Fig. Q12). Recommended Acceptable Not recommended Fig. Q12 : Recommendation to install cables in steel beams Both ends of metal cableways must always be connected to local earth electrodes. For very long cableways, additional connections to the earthing system are recommended between connected devices. Where possible, the distance between these earthing connections should be irregular (for symmetrical wiring systems) to avoid resonance at identical frequencies. All connections to the earthing system should be short. Metal and non-metal cableways are available. Metal solutions offer better EMC characteristics. A cableway (cable trays, conduits, cable brackets, etc.) must offer a continuous, conducting metal structure from beginning to end. An aluminium cableway has a lower DC resistance than a steel cableway of the same size, but the transfer impedance (Zt) of steel drops at a lower frequency, particularly when the steel has a high relative permeability µr. Care must be taken when different types of metal are used because direct electrical connection is not authorised in certain cases to avoid corrosion. That could be a disadvantage in terms of EMC. When devices connected to the wiring system using unshielded cables are not affected by low-frequency disturbances, the EMC of non-metal cableways can be improved by adding a parallel earthing conductor (PEC) inside the cableway. Both ends must be connected to the local earthing system. Connections should be made to a metal part with low impedance (e.g. a large metal panel of the device case). The PEC should be designed to handle high fault and common-mode currents. Schneider Electric - Electrical installation guide 2009 Q9 © Schneider Electric - all rights reserved Q - EMC guidelines Q - EMC guidelines 3 Implementation Implementation When a metal cableway is made up of a number of short sections, care is required to ensure continuity by correctly bonding the different parts. The parts should preferably be welded along all edges. Riveted, bolted or screwed connections are authorised as long as the contact surfaces conduct current (no paint or insulating coatings) and are protected against corrosion. Tightening torques must be observed to ensure correct pressure for the electrical contact between two parts. When a particular shape of cableway is selected, it should be used for the entire length. All interconnections must have a low impedance. A single wire connection between two parts of the cableway produces a high local impedance that cancels its EMC performance. Starting at a few MHz, a ten-centimetre connection between two parts of the cableway reduces the attenuation factor by more than a factor of ten (see Fig. Q13). NO! NOT RECOMMENDED YES! Fig. Q13 : Metal cableways assembly Each time modiications or extensions are made, it is very important to make sure they are carried out according to EMC rules (e.g. never replace a metal cableway by a plastic version!). Covers for metal cableways must meet the same requirements as those applying to the cableways themselves. A cover should have a large number of contacts along the entire length. If that is not possible, it must be connected to the cableway at least at the two ends using short connections (e.g. braided or meshed connections). When cableways must be interrupted to pass through a wall (e.g. irewalls), lowimpedance connections must be used between the two parts (see Fig. Q14). © Schneider Electric - all rights reserved Q10 Mediocre OK Better Fig. Q14 : Recommendation for metal cableways assembly to pass through a wall Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 3 Implementation 3.6 Implementation of shielded cables When the decision is made to use shielded cables, it is also necessary to determine how the shielding will be bonded (type of earthing, connector, cable entry, etc.), otherwise the beneits are considerably reduced. To be effective, the shielding should be bonded over 360°. Figure Q15 below show different ways of earthing the cable shielding. For computer equipment and digital links, the shielding should be connected at each end of the cable. Connection of the shielding is very important for EMC and the following points should be noted. If the shielded cable connects equipment located in the same equipotential bonding area, the shielding must be connected to the exposed conductive parts (ECP) at both ends. If the connected equipment is not in the same equipotential bonding area, there are a number of possibilities. b Connection of only one end to the ECPs is dangerous. If an insulation fault occurs, the voltage in the shielding can be fatal for an operator or destroy equipment. In addition, at high frequencies, the shielding is not effective. b Connection of both ends to the ECPs can be dangerous if an insulation fault occurs. A high current lows in the shielding and can damage it. To limit this problem, a parallel earthing conductor (PEC) must be run next to the shielded cable. The size of the PEC depends on the short-circuit current in the given part of the installation. It is clear that if the installation has a well meshed earthing network, this problem does not arise. All bonding connections must be made to bare metal Not acceptable Acceptable Collar, clamp, etc. Bonding bar connected to the chassis Bonding wire Poorly connected shielding = reduced effectiveness Correct Collar, clamp, etc. Equipotential metal panel Ideal Cable gland = circumferential contact to equipotential metal panel Fig. Q15 : Implementation of shielded cables Q11 Communication networks cover large distances and interconnect equipment installed in rooms that may have distribution systems with different system earthing arrangements. In addition, if the various sites are not equipotential, high transient currents and major differences in potential may occur between the various devices connected to the networks. As noted above, this is the case when insulation faults and lightning strikes occur. The dielectric withstand capacity (between live conductors and exposed conductive parts) of communication cards installed in PCs or PLCs generally does not exceed 500 V. At best, the withstand capacity can reach 1.5 kV. In meshed installations with the TN-S system and relatively small communication networks, this level of withstand capacity is acceptable. In all cases, however, protection against lightning strikes (common and differential modes) is recommended. Schneider Electric - Electrical installation guide 2009 © Schneider Electric - all rights reserved 3.7 Communication networks Q - EMC guidelines 3 Implementation The type of communication cable employed is an important parameter. It must be suited to the type of transmission. To create a reliable communication link, the following parameters must be taken into account: b Characteristic impedance b Twisted pairs or other arrangement b Resistance and capacitance per unit length b Signal attenutation per unit length b The type(s) of shielding used In addition, it is important to use symmetrical (differential) transmission links because they offer higher performance in terms of EMC. In environments with severe EM conditions, however, or for wide communication networks between installations that are not or are only slightly equipotential, in conjunction with IT, TT or TN-C systems, it is highly recommended to use optical ibre links. For safety reasons, the optical ibre must not have metal parts (risk of electric shock if the ibre links two areas with different potentials). 3.8 Implementation of surge arrestors Connections They must be as short as possible. In fact, one of the essential characteristics for equipment protection is the maximum level of voltage that the equipment can withstand at its terminals. A surge arrester with a protection level suitable for the equipment to be protected should be chosen (see Fig. 16). The total length of the connections is L = L1 + L2 + L3. It represents an impedance of roughly 1 µH/m for high frequency currents. Application of the rule ∆U = L di dt with an 8/20 µs wave and a current of 8 kA leads to a voltage of 1,000 V peak per metre of cable. ∆U = 1.10-6 x 8.103 = 1,000 V 8.10-6 U equipment L1 disconnection circuit-breaker U1 L2 L = L1 + L2 + L3 < 50 cm surge arrester L3 Up load to be protected U2 Fig. Q16 : Surge arrester connection: L < 50 cm Q12 © Schneider Electric - all rights reserved This gives U equipment = Up + U1 + U2. If L1 + L2 + L3 = 50 cm, this will result in a voltage surge of 500 V for a current of 8 kA. Schneider Electric - Electrical installation guide 2009 3 Implementation Wiring rules b Rule 1 The irst rule to be respected is not to exceed a distance of 50 cm when connecting the surge arrester to its disconnection circuit-breaker. The surge arrester connections are shown in Figure Q17. d1 d1 D k PR Quic PD S tor nnec disco d2 d3 (8/20) 65kA(8/20) Imax: In: 20kA 1,5kV Up: 340Va Uc: SPD d3 d2 d1 + + d3 y 50 cm m d2 d1 + + d3 35 c Fig. Q17 : SPD with separate or integrated disconnector b Rule 2 The outgoing feeders of the protected conductors must be connected right at the terminals of the surge arrester and disconnection circuit-breaker (see Fig. Q18). Power supply Protected feeders L < 35 cm Quick PRD Fig. Q18 : Connections are right at the SPD's terminals Q13 © Schneider Electric - all rights reserved Q - EMC guidelines Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 3 Implementation b Rule 3 The phase, neutral and PE incoming wires must be tightly coupled to reduce the loop surfaces (see Fig. Q19). Clean cables polluted by neighbouring polluted cables Clean cable paths separated from polluted cable paths protected outgoing feeders Large frame loop surface NO YES Intermediate earth terminal LN Intermediate earth terminal Small frame loop surface Main earth terminal LN Main earth terminal Fig. Q19 : Example of wiring precautions to be taken in a box (rules 2, 3, 4, 5) b Rule 4 The surge arrester's incoming wires must be moved away from the outgoing wires to avoid mixing the polluted cables with the protected cables (see Fig. Q19). b Rule 5 The cables must be lattened against the metallic frames of the box in order to minimise the frame loops and thus beneit from a disturbance screening effect. If the box is made of plastic and the loads particularly sensitive, it must be replaced by a metal box. In all cases, you must check that the metallic frames of the boxes or cabinets are frame grounded by very short connections. Finally, if screened cables are used, extra lengths which serve no purpose ("pigtails"), must be cut off as they reduce screening effectiveness. © Schneider Electric - all rights reserved Q14 Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 3 Implementation 3.9 Cabinet cabling (Fig. Q20) Each cabinet must be equipped with an earthing bar or a ground reference metal sheet. All shielded cables and external protection circuits must be connected to this point. Anyone of the cabinet metal sheets or the DIN rail can be used as the ground reference. Plastic cabinets are not recommended. In this case, the DIN rail must be used as ground reference. Potential Reference Plate Fig. Q20 : The protected device must be connected to the surge-arrestor terminals 3.10 Standards It is absolutely essential to specify the standards and recommendations that must be taken into account for installations. Below are several documents that may be used: b EN 50174-1 Information technology - Cabling installation. Part 1: Speciication and quality assurance b EN 50174-2 Information technology - Cabling installation. Part 2: Installation planning and practices inside buildings © Schneider Electric - all rights reserved Q15 Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 4 Coupling mechanisms and counter-measures 4.1 General An EM interference phenomenon may be summed up in Figure Q21 below. Source Coupling Victim Origin of emitted disturbances Means by which disturbances are transmitted Equipment likely to be disturbed Example: Radiated waves Walkie-talkie TV set Fig. Q21 : EM interference phenomenon The different sources of disturbances are: b Radio-frequency emissions v Wireless communication systems (radio, TV, CB, radio telephones, remote controls) v Radar b Electrical equipment v High-power industrial equipment (induction furnaces, welding machines, stator control systems) v Ofice equipment (computers and electronic circuits, photocopy machines, large monitors) v Discharge lamps (neon, luorescent, lash, etc.) v Electromechanical components (relays, contactors, solenoids, current interruption devices) b Power systems v Power transmission and distribution systems v Electrical transportation systems b Lightning b Electrostatic discharges (ESD) b Electromagnetic nuclear pulses (EMNP) The potential victims are: b Radio and television receivers, radar, wireless communication systems b Analogue systems (sensors, measurement acquisition, ampliiers, monitors) b Digital systems (computers, computer communications, peripheral equipment) © Schneider Electric - all rights reserved Q16 The different types of coupling are: b Common-mode impedance (galvanic) coupling b Capacitive coupling b Inductive coupling b Radiated coupling (cable to cable, ield to cable, antenna to antenna) Schneider Electric - Electrical installation guide 2009 4 Coupling mechanisms and counter-measures 4.2 Common-mode impedance coupling Definition Two or more devices are interconnected by the power supply and communication cables (see Fig. Q22). When external currents (lightning, fault currents, disturbances) low via these common-mode impedances, an undesirable voltage appears between points A and B which are supposed to be equipotential. This stray voltage can disturb low-level or fast electronic circuits. All cables, including the protective conductors, have an impedance, particularly at high frequencies. Device 1 Device 2 Z sign. Stray overvoltage I2 ECPs Signal line ECPs I1 Z1 Z2 The exposed conductive parts (ECP) of devices 1 and 2 are connected to a common earthing terminal via connections with impedances Z1 and Z2. The stray overvoltage lows to the earth via Z1. The potential of device 1 increases to Z1 I1. The difference in potential with device 2 (initial potential = 0) results in the appearance of current I2. Z1 I2 Z1 I 1 = (Zsign + Z2) I 2 ⇒ = I 1 (Zsign + Z2) Current I2, present on the signal line, disturbs device 2. Fig. Q22 : Definition of common-mode impedance coupling Examples (see Fig. Q23) b Devices linked by a common reference conductor (e.g. PEN, PE) affected by fast or intense (di/dt) current variations (fault current, lightning strike, short-circuit, load changes, chopping circuits, harmonic currents, power factor correction capacitor banks, etc.) b A common return path for a number of electrical sources Disturbed cable Device 1 Device 2 Signal cable Disturbing current Difference in potential ZMC Fig. Q23 : Example of common-mode impedance coupling Schneider Electric - Electrical installation guide 2009 Fault currents Q17 Lightning strike © Schneider Electric - all rights reserved Q - EMC guidelines Q - EMC guidelines 4 Coupling mechanisms and counter-measures Counter-measures (see Fig. Q24) If they cannot be eliminated, common-mode impedances must at least be as low as possible. To reduce the effects of common-mode impedances, it is necessary to: b Reduce impedances: v Mesh the common references, v Use short cables or lat braids which, for equal sizes, have a lower impedance than round cables, v Install functional equipotential bonding between devices. b Reduce the level of the disturbing currents by adding common-mode iltering and differential-mode inductors Device 1 Z sign. Stray overvoltage Device 2 I2 Z sup. Z1 PEC I1 Z2 If the impedance of the parallel earthing conductor PEC (Z sup) is very low compared to Z sign, most of the disturbing current lows via the PEC, i.e. not via the signal line as in the previous case. The difference in potential between devices 1 and 2 becomes very low and the disturbance acceptable. Fig. Q24 : Counter-measures of common-mode impedance coupling 4.3 Capacitive coupling U Definition Vsource The level of disturbance depends on the voltage variations (dv/dt) and the value of the coupling capacitance between the disturber and the victim. t Vvictim Q18 Capacitive coupling increases with: b The frequency b The proximity of the disturber to the victim and the length of the parallel cables b The height of the cables with respect to a ground referencing plane b The input impedance of the victim circuit (circuits with a high input impedance are more vulnerable) b The insulation of the victim cable (εr of the cable insulation), particularly for tightly coupled pairs Figure Q25 shows the results of capacitive coupling (cross-talk) between two cables. t © Schneider Electric - all rights reserved Examples (see Fig. Q26 opposite page) Fig. Q25 : Typical result of capacitive coupling (capacitive cross-talk) b Nearby cables subjected to rapid voltage variations (dv/dt) b Start-up of luorescent lamps b High-voltage switch-mode power supplies (photocopy machines, etc.) b Coupling capacitance between the primary and secondary windings of transformers b Cross-talk between cables Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 4 Coupling mechanisms and counter-measures Differential mode Common mode Source Vs Vs DM Iv CM Victim Iv CM DM Source Victim Vs DM: Source of the disturbing voltage (differential mode) Iv DM: Disturbing current on victim side (differential mode) Vs CM: Source of the disturbing voltage (common mode) Iv CM: Disturbing current on victim side (common mode) Metal shielding Fig. Q26 : Example of capacitive coupling Counter-measures (see Fig. Q27) C Victim Fig. Q27 : Cable shielding with perforations reduces capacitive coupling 4.4 Inductive coupling Definition The disturber and the victim are coupled by a magnetic ield. The level of disturbance depends on the current variations (di/dt) and the mutual coupling inductance. Inductive coupling increases with: b The frequency b The proximity of the disturber to the victim and the length of the parallel cables, b The height of the cables with respect to a ground referencing plane, b The load impedance of the disturbing circuit. Examples (see Fig. Q28 next page) b Nearby cables subjected to rapid current variations (di/dt) b Short-circuits b Fault currents b Lightning strikes b Stator control systems b Welding machines b Inductors Schneider Electric - Electrical installation guide 2009 Q19 © Schneider Electric - all rights reserved Source b Limit the length of parallel runs of disturbers and victims to the strict minimum b Increase the distance between the disturber and the victim b For two-wire connections, run the two wires as close together as possible b Position a PEC bonded at both ends and between the disturber and the victim b Use two or four-wire cables rather than individual conductors b Use symmetrical transmission systems on correctly implemented, symmetrical wiring systems b Shield the disturbing cables, the victim cables or both (the shielding must be bonded) b Reduce the dv/dt of the disturber by increasing the signal rise time where possible Q - EMC guidelines 4 Coupling mechanisms and counter-measures Disturbing cable Disturbing cable H H Victim loop Victim pair i i Victim loop Differential mode Common mode Fig. Q28 : Example of inductive coupling Counter-measures b Limit the length of parallel runs of disturbers and victims to the strict minimum b Increase the distance between the disturber and the victim b For two-wire connections, run the two wires as close together as possible b Use multi-core or touching single-core cables, preferably in a triangular layout b Position a PEC bonded at both ends and between the disturber and the victim b Use symmetrical transmission systems on correctly implemented, symmetrical wiring systems b Shield the disturbing cables, the victim cables or both (the shielding must be bonded) b Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable) 4.5 Radiated coupling Definition The disturber and the victim are coupled by a medium (e.g. air). The level of disturbance depends on the power of the radiating source and the effectiveness of the emitting and receiving antenna. An electromagnetic ield comprises both an electrical ield and a magnetic ield. The two ields are correlated. It is possible to analyse separately the electrical and magnetic components. The electrical ield (E ield) and the magnetic ield (H ield) are coupled in wiring systems via the wires and loops (see Fig. Q29). E field H field i Q20 V © Schneider Electric - all rights reserved Field-to-cable coupling Fig. Q29 : Definition of radiated coupling Schneider Electric - Electrical installation guide 2009 Field-to-loop coupling 4 Coupling mechanisms and counter-measures When a cable is subjected to a variable electrical ield, a current is generated in the cable. This phenomenon is called ield-to-cable coupling. Similarly, when a variable magnetic ield lows through a loop, it creates a counter electromotive force that produces a voltage between the two ends of the loop. This phenomenon is called ield-to-loop coupling. Examples (see Fig. Q30) b Radio-transmission equipment (walkie-talkies, radio and TV transmitters, mobile services) b Radar b Automobile ignition systems b Arc-welding machines b Induction furnaces b Power switching systems b Electrostatic discharges (ESD) b Lighting E field EM field Signal cable Device 1 Device 2 i Device h h Area of the earth loop Ground reference plane Example of field-to-cable coupling Example of field-to-loop coupling Fig. Q30 : Examples of radiated coupling Counter-measures To minimise the effects of radiated coupling, the measures below are required. For field-to-cable coupling b Reduce the antenna effect of the victim by reducing the height (h) of the cable with respect to the ground referencing plane b Place the cable in an uninterrupted, bonded metal cableway (tube, trunking, cable tray) b Use shielded cables that are correctly installed and bonded b Add PECs b Place ilters or ferrite rings on the victim cable For field-to-loop coupling b Reduce the surface of the victim loop by reducing the height (h) and the length of the cable. Use the solutions for ield-to-cable coupling. Use the Faraday cage principle. Radiated coupling can be eliminated using the Faraday cage principle. A possible solution is a shielded cable with both ends of the shielding connected to the metal case of the device. The exposed conductive parts must be bonded to enhance effectiveness at high frequencies. Radiated coupling decreases with the distance and when symmetrical transmission links are used. Schneider Electric - Electrical installation guide 2009 Q21 © Schneider Electric - all rights reserved Q - EMC guidelines Q - EMC guidelines 5 Wiring recommendations 5.1 Signal classes (see Fig. Q31) 1 - Power connections (supply + PE) Device Shielded cables of different groups Unshielded cables of different groups 2 - Relay connections e h NO! Ground reference plane YES! 4 - Analogue link (sensor) 3 - Digital link (bus) Risk of cross-talk in common mode if e < 3 h Fig. Q31 : Internal signals can be grouped in four classes Sensitive cable Sensitive cable Disturbing cable Disturbing cable u1m 30 cm NO! Cross incompatible cables at right angles YES! Fig. Q32 : Wiring recommendations for cables carrying different types of signals NO! YES! Standard cable Four classes of internal signals are: b Class 1 Mains power lines, power circuits with a high di/dt, switch-mode converters, powerregulation control devices. This class is not very sensitive, but disturbs the other classes (particularly in common mode). b Class 2 Relay contacts. This class is not very sensitive, but disturbs the other classes (switching, arcs when contacts open). b Class 3 Digital circuits (HF switching). This class is sensitive to pulses, but also disturbs the following class. b Class 4 Analogue input/output circuits (low-level measurements, active sensor supply circuits). This class is sensitive. It is a good idea to use conductors with a speciic colour for each class to facilitate identiication and separate the classes. This is useful during design and troubleshooting. Two distinct pairs 5.2 Wiring recommendations Poorly implemented ribbon cable Correctly implemented ribbon cable Digital connection Analogue pair Bonding wires Q22 Disturbing cables (classes 1 and 2) must be placed at some distance from the sensitive cables (classes 3 and 4) (see Fig. Q32 and Fig. Q33) In general, a 10 cm separation between cables laid lat on sheet metal is suficient (for both common and differential modes). If there is enough space, a distance of 30 cm is preferable. If cables must be crossed, this should be done at right angles to avoid cross-talk (even if they touch). There are no distance requirements if the cables are separated by a metal partition that is equipotential with respect to the ECPs. However, the height of the partition must be greater than the diameter of the cables. © Schneider Electric - all rights reserved Fig. Q33 : Use of cables and ribbon cable Cables carrying different types of signals must be physically separated (see Fig. Q32 above) Schneider Electric - Electrical installation guide 2009 Q - EMC guidelines 5 Wiring recommendations A cable should carry the signals of a single group (see Fig. Q34) If it is necessary to use a cable to carry the signals of different groups, internal shielding is necessary to limit cross-talk (differential mode). The shielding, preferably braided, must be bonded at each end for groups 1, 2 and 3. It is advised to overshield disturbing and sensitive cables (see Fig. Q35) The overshielding acts as a HF protection (common and differential modes) if it is bonded at each end using a circumferential connector, a collar or a clampere However, a simple bonding wire is not suficient. NO! Shielded pair Electronic control device Sensor Unshielded cable for stator control Electromechanical device YES! Bonded using a clamp Shielded pair + overshielding Electronic control device Sensor Shielded cable for stator control Electromechanical device Fig. Q35 : Shielding and overshielding for disturbing and/or sensitive cables NO! Power + analogue YES! Digital + relay contacts Power + relay contacts Digital + analogue Avoid using a single connector for different groups (see Fig. Q36) Except where necessary for groups 1 and 2 (differential mode). If a single connector is used for both analogue and digital signals, the two groups must be separated by at least one set of contacts connected to 0 V used as a barrier. All free conductors (reserve) must always be bonded at each end (see Fig. Q37) For group 4, these connections are not advised for lines with very low voltage and frequency levels (risk of creating signal noise, by magnetic induction, at the transmission frequencies). Shielding Power connections Digital connections Relay I/O connections Analogue connections Fig. Q34 : Incompatible signals = different cables NO! YES! Electronic system NO! Electronic system YES! Wires not equipotentially bonded Q23 Analogue connections Fig. Q36 : Segregation applies to connectors as well! Equipotential sheet metal panel Fig. Q37 : Free wires must be equipotentially bonded Schneider Electric - Electrical installation guide 2009 Equipotential sheet metal panel © Schneider Electric - all rights reserved Digital connections Q - EMC guidelines 5 Wiring recommendations The two conductors must be installed as close together as possible (see Fig. Q38) This is particularly important for low-level sensors. Even for relay signals with a common, the active conductors should be accompanied by at least one common conductor per bundle. For analogue and digital signals, twisted pairs are a minimum requirement. A twisted pair (differential mode) guarantees that the two wires remain together along their entire length. NO! Area of loop too large PCB with relay contact I/Os YES! PCB with relay contact I/Os + Power supply + Power supply Fig. Q38 : The two wires of a pair must always be run close together Group-1 cables do not need to be shielded if they are filtered But they should be made of twisted pairs to ensure compliance with the previous section. Cables must always be positioned along their entire length against the bonded metal parts of devices (see Fig. Q39) For example: Covers, metal trunking, structure, etc. In order to take advantage of the dependable, inexpensive and signiicant reduction effect (common mode) and anticross-talk effect (differential mode). NO! NO! YES! Chassis 1 Chassis 1 Chassis 2 Chassis 2 Chassis 3 Chassis 3 YES! Metal tray Power supply Q24 Power or disturbing cables Relay cables I/O interface Power supply I/O interface All metal parts (frame, structure, enclosures, etc.) are equipotential Fig. Q39 : Run wires along their entire length against the bonded metal parts © Schneider Electric - all rights reserved Measurement or sensitive cables Fig. Q40 : Cable distribution in cable trays The use of correctly bonded metal trunking considerably improves internal EMC (see Fig. Q40) Schneider Electric - Electrical installation guide 2009