Chapter 4
TEMPERATURE IN STEEL SECTIONS
4.1. INTRODUCTION
The increase in steel temperature depends on the temperature of the
fire compartment, the area of steel exposed to the fire and the amount of the
applied fire protection. This chapter will focus on the transfer of the heat
from the fire compartment to the structural elements. Several fire protection
systems can be used to improve the performance of steel sections in a fire
and these are described later in this chapter.
The heat transfer from the hot gases into the surface of the structural
elements by a combination of convection and radiation is normally treated as
a boundary condition. The heat transfer within the structural member is by
conduction and is governed by the well known Fourier equation of heat
transfer. The chapter starts by presenting the complex governing equation for
heat conduction and goes on to show how simplified and more practical
methods can be developed for steel elements.
4.2. THE HEAT CONDUCTION EQUATION AND ITS BOUNDARY
CONDITIONS
The governing equation for the two-dimensional non-linear, transient
heat conduction within the cross section of a structural element, takes the
following form:
w
wT
w
wT
(Oa
) (Oa
) Q
wx
wx
wy
wy
U a ca
wT
wt
(4.1)
Fire Design of Steel Structures
Jean-Marc Franssen and Paulo Vila Real
© 2012 ECCS – European Convention for Constructional Steelwork. Published 2012 by ECCS – European Convention for Constructional Steelwork
_____
45
4. TEMPERATURE IN STEEL SECTIONS
where O a is the thermal conductivity, Q the internal heat source that is
equal to zero in the case of non-combustible members, U a the unit mass of
steel, ca the specific heat of steel, T the temperature and t the time.
The temperature field which satisfies Eq. (4.1) within the structural
element must satisfy the following boundary conditions:
i) prescribed temperatures T on a part *T of the boundary;
ii) specified heat flux q on a part *q of the boundary; iii) heat transfer by
convection between the part *c of the boundary at temperature T and the
surrounding ambient temperature Tf
qc Dc (T Tf ) on *c
(4.2)
where D c is the coefficient of heat transfer by convection [W/m2K] and qc is
the heat flux by convection per unit area.
iv) heat transfer by radiation between the part *r of the boundary at an
absolute temperature T and the fire environment at an absolute temperature
Tr
qr
_____
46
VH (T 4 T r4 ) on *r
(4.3)
where V is the Stephan Boltzmann constant ( 5.67 u108 W/m2K4 ), H the
emissivity and qr is the heat flux by radiation per unit area. This equation
can become linear as follows:
qr
VH (T 4 T r4 ) VH (T 2 T r2 )(T T r )(T T r ) D r (T T r )
on *r (4.4)
Dr
where D r can be considered as the coefficient of heat transfer by radiation.
In the case of combined convection and radiation and if, as usually
happens, T r Tf , the combined heat flux is given by:
q cr
qc q r
D c (T T f ) D r (T T r ) D cr (T T f )
(4.5)
where
D cr D c D r
(4.6)
4.3. ADVANCED CALCULATION MODEL. FE SOLUTION OF THE HEAT TRANSFER EQ.
is the combined convection and radiation coefficient which is temperature
dependent.
It should be noted that both the governing Eq. (4.1) and boundary
condition Eq. (4.5) are non-linear. The former is due to the thermal
conductivity and specific heat that are temperature dependent (see Annex A),
and the latter is due to the radiative boundary condition which involves a
non-linear term of the temperature, as shown in Eq. (4.4). Therefore a
closed-form solution to the governing Eq. (4.1) and its boundary condition
Eq. (4.5) is not possible, even for the cases with the simplest geometry.
Numerical methods such as the finite element method are usually required to
solve this kind of heat transfer problems and such a method is presented in
the next section. EN 1993-1-2 gives simplified methods for unprotected and
protected steelwork exposed to the fire, and these methods are presented in
Sections 4.5 and 4.6, respectively.
4.3. ADVANCED CALCULATION MODEL. FINITE ELEMENT
SOLUTION OF THE HEAT CONDUCTION EQUATION
Using finite elements : e to discretize the domain :, together with a
weak formulation and using the Galerkin method for choosing the weighting
functions, the following system of differential equations is obtained:
Kș Cș F
(4.7)
where
E
K lm
¦³
e 1
§ wN l
wN
wN ·
wN
¨
Oa m l Oa m ¸¸d: e
e ¨
:
wy
wy ¹
wx
© wx
E
Clm
¦³
e 1
E
Fl
¦³
e 1
:
e
N l Q d: e
:e
e 1
¦³
e 1
*ce
D cr N l N m d*ce (4.8)
U a c a N l N m d: e
Q
¦³
H
*qe
N l q d*qe
(4.9)
H
¦³
e 1
*ce
N l D cr Tf d*ce
(4.10)
_____
47
4. TEMPERATURE IN STEEL SECTIONS
and E is the total number of elements, Q is the number of elements with
boundary type *q , H is the number of elements with boundary type *c and
(or) *r , and Nl and Nm are shape functions.
Adopting a finite difference discretisation in time, the system of
ordinary differential equations (4.7) can be rewritten for the time t nD :
ˆ
K
n Dșn D
ˆ
F
n D ; 0 D d 1 n 0,1,2,...N 1
(4.11)
where
ˆ
K
nD
1
Cn D ; 0 D d 1
D't
(4.12)
1
Cn Dș n ; 0 D d 1
D't
(4.13)
K nD
and
ˆ
F
nD
Fn D
Solving the system of equations (4.11), for șn D , at time tnD , the
value of ș at the end of the time interval 't , ( i. e., at time t n 1 ) is given
by:
șn 1
_____
48
1
§ 1·
ș n D ¨1 ¸ ș n
D
© D¹
(4.14)
These are the initial conditions for the next time interval. Varying the
D parameter, several time integration schemes are obtained. If D z 0 the
methods are called implicit. The most popular schemes are those for which:
x
x
D 1 2 (Crank-Nicolson);
D 2 3 (Galerkin);
x
D
1 (Euler Backward).
The algorithm from equations (4.11) to (4.14) has the same stability
criteria for both linear and non-linear problems and is unconditionally stable
for D t 1 2 , in the sense that the process will always converge, although
some oscillation can occur if the time interval is too big.
4.3. ADVANCED CALCULATION MODEL. FE SOLUTION OF THE HEAT TRANSFER EQ.
4.3.1. Temperature field using the finite element method
Numerical simulation of the thermal response of a steel HE 400 B
profile subjected to the standard fire curve ISO 834 acting on all four sides
as shown in Fig. 4.1 is presented in this section.
Fig. 4.1: Steel profile exposed to fire on all four sides
Due to the symmetry, only one quarter of the cross section is analysed.
Fig. 4.2 shows the finite element mesh adopted.
_____
49
Fig. 4.2: Finite element mesh used
The temperature field after a standard fire duration of 15, 30, 60 and
90 minutes is shown in Fig. 4.3. The emissivity in Eq. (4.3) was taken as
H 0.5 . The coefficient of heat transfer by convection, D c ,in Eq. (4.2) was
taken as 25 W/m2K.
4. TEMPERATURE IN STEEL SECTIONS
After 15 minutes of exposure
_____
50
After 30 minutes of exposure
After 60 minutes of exposure
After 90 minutes of exposure
Fig. 4.3: Temperature field of an HE 400 B heated on all four sides
The temperature field on the steel profile HE 400 B after 30 minutes
depicted in Fig. 4.3, shows an almost uniform temperature field where the
difference between the maximum and minimum temperature is only 57 ºC.
This result is normally attributed to the high value of the thermal
conductivity of the steel that leads to a quick propagation of heat producing
an almost uniformly distributed field of temperature in the cross section. It
can be shown that this difference is due to the relative thickness of the
sections and not to the high value of the thermal conductivity of steel. In
fact, the notion of relative thickness is translated physically through the
notion of section factor, see Section 4.4.
Assuming a uniform temperature distribution makes Eq. (4.1) much
simpler to apply.
Simple models for the calculation of the steel temperature are based on
the assumption of a uniform temperature distribution throughout the cross
4.4. SECTION FACTOR
section as given in EN 1993-1-2 and presented in the next sections.
4.4. SECTION FACTOR
Before presenting the simple methods for the evaluation of the thermal
response of a steel member, the concept of a parameter that governs the rate
of temperature rise is presented.
The rate of temperature rise depends on the mass and the surface area
of the member exposed to the fire. Light members such as purlins or lattice
girders heat up much faster than heavy sections such as columns. The rate of
heating of a given member is described by its “Section Factor” or “Massivity
Factor”, A/V, which is the ratio of the surface area exposed to the heat flux
and the volume of the member per unit length.
For unprotected members Eurocode 3 defines the section factor as
Am/V [m-1].
For prismatic members with boundary conditions that are constant
along the length, the temperature distribution is two-dimensional and the
massivity factor is the ratio of the perimeter of the section exposed to the
fire, in meters, and the cross-sectional area of the member, in m2 as follows
Am
V
Pul
Aul
P
[m-1]
A
(4.15)
where l the length of the member.
Table 4.1 and Table 4.2 show the basic principle for evaluating the
“Section Factor” or “Massivity Factor” for unprotected and protected steel
members, respectively.
The cross-sectional area A is always the area of the steel section. The
heated perimeter Am of an unprotected member will depend on the number
of sides exposed to the fire. The perimeter A p of protected members also
depends on the number of heated sides and on the type of insulation used.
For box protection, generally the box perimeter that corresponds to the
smallest box surrounding the section is considered and for sprayed insulation
or intumescent paint, the perimeter of the steel cross section is used. More
detailed cases are shown in Annex A.
_____
51
4. TEMPERATURE IN STEEL SECTIONS
The rate at which a steel member will increase in temperature is
proportional to the surface, A, of steel exposed to the fire and inversely
proportional to the mass or volume, V, of the member. In a fire, a member
with a low section factor will heat up more slowly than one with a high
section factor. This is illustrated in Fig. 4.4.
Table 4.1: Definition of section factors for unprotected steel members
Sketch
Description
Section factor ( Am / V )
4 sides exposed
steel perimeter
exposed to fire
ņņņņņņņņņņ
A
3 sides exposed
steel perimeter
exposed to fire
ņņņņņņņņņņ
A
_____
52
h
4 sides exposed
b
2 (b + h )
ņņņņņņņņņņ
A
Note: A is the steel cross section area.
P - high
A - low
Am
- high
V
Fast heating
Slow heating
Fig. 4.4: The section factor
P - low
A - high
Am
- low
V
4.4. SECTION FACTOR
Table 4.2: Definition of section factors for protected steel members
Sketch
Description
Section factor ( Ap / V )
Contour encasement
of uniform thickness
exposed to fire on four
sides
steel perimeter
ņņņņņņņņņņ
Contour encasement
of uniform thickness,
exposed to fire
on three sides
A
steel perimeter - b
ņņņņņņņņņņ
A
b
h
Hollow encasement
of uniform thickness
exposed to fire on four
sides
2 (b + h )
ņņņņņņņņņņ
A
Hollow encasement
of uniform thickness,
exposed to fire
on three sides
b + 2h
ņņņņņņņņņņ
A
b
h
b
Note: A is the steel cross section area.
Table 4.3 shows some examples of section factors for protected
sections. The section factor for a profile with contour encasement is the same
as that for the unprotected profile.
_____
53
4. TEMPERATURE IN STEEL SECTIONS
Table 4.3: Section factors
Profile
contour
3 sides
contour
4 sides
box
3 sides
box
4 sides
IPE 100
HE 100 A
334
217
388
264
247
137
300
185
IPE 400
HE 400 A
152
101
174
120
116
68
137
87
IPE 600
HE 600 A
115
87
129
100
91
65
105
78
4.5. TEMPERATURE OF UNPROTECTED STEELWORK EXPOSED
TO FIRE
_____
54
EN 1993-1-2 provides a simple equation for calculating the thermal
response of unprotected steel members. Assuming an equivalent uniform
temperature distribution throughout the cross section, the increase in
temperature 'Ta,t in an unprotected steel member during a time interval 't
is given by:
'T a,t
ksh
Am / V
hnet, d 't [ºC]
ca Ua
(4.16)
where
k sh
Am / V
Am
- is the correction factor for the shadow effect, from Eq. (4.17);
- is the section factor for unprotected steel members, ( t 10 ) [m-1];
- is the surface area of the member per unit length, [m2/m];
V
ca
- is the volume of the member per unit length, [m3/m];
- is the specific heat of steel, [J/kgK];
4.5. TEMPERATURE OF UNPROTECTED STEELWORK EXPOSED TO FIRE
hnet ,d
- is the design value of the net heat flux per unit area according to
Eq. (3.4) from Chapter 3, representing the thermal actions and
reproduced here. This flux is the sum of a convective part hnet ,c and
a radiative part hnet ,r :
hnet .d
2
hnet ,c hnet , r [W/m ];
hnet,c
D c (T g T m ) [W/m2];
where
Dc
- is the coefficient of heat transfer by convection given in
Tg
Eq.(3.4) and reproduced in table 4.4;
- is the gas temperature of the fire compartment defined in
Tm
)
Hm
Hf
Chapter 3, [ºC];
- is the surface temperature of the steel member;
hnet, r ) H f H m 5.67 u 108 [(Tr 273)4 (Tm 273)4 ] [W/m2];
- is the view factor or configuration factor that is usually taken
equal to 1.0 (see Chapter 3 or Table 4.4);
- is the surface emissivity of the member (see Eq.(3.4));
- is the emissivity of the fire (usually H f 1.0 );
Tr
- is the radiation temperature of the fire environment normally
taken T r T g ;
Ua
- is the unit mass of steel, 7850 [kg/m3];
't
- is the time interval [s] ( d 5 [s]).
_____
55
Table 4.4: Coefficient of heat transfer by convection and view factor
D c [W/m2K]
)
Radiation considered separately
4
z0
Radiation implicitly considered in the
convection
9
0
Standard fire curve ISO 834
25
Hydrocarbon curve
50
z0
z0
Parametric fire, zone fire models or external
members
35
z0
Unexposed side of separating elements
Surface exposed to the fire
4. TEMPERATURE IN STEEL SECTIONS
In equation (4.16) the value of the section factor Am / V should not be
taken less than 10 m-1 (because such a massive section would not have a
uniform temperature) 1 and ' t should not be taken as more than 5 seconds.
Eq. (4.16) can only be solved if the initial conditions and the boundary
conditions (convection and radiation) are known. A common assumption
regarding the initial conditions is that prior to the occurrence of fire the
temperature of the whole section is 20 ºC.
The values for the coefficients of both radiative and convective heat
transfer proposed in Eurocode 3 were chosen such that a reasonable
agreement with test results was obtained. However, empirical coefficients
taking into account the so-called “shadow effect” (see Fig. 4.5) had to be
introduced in Eq. (4.16) so that realistic values of the surface emissivity of
steel (Hm = 0.7, a high but physically realistic value) and the fire emissivity
(Hf = 1.0, a direct consequence of using the plate thermometer for furnace
control in fire tests) can be used (Twilt et al., 2001).
The view factor is always taken as 1.0 if the radiative flux given by the
above equation is used in Eq. (4.16) written for a fully engulfed element.
This factor can be calculated with a value lower than 1.0 when the fire
source is localised and only part of the flux radiated by the fire source
reaches the element (see Fig. 4.5) or when the concave shape of the profile is
taken in to account, as will be shown in Section 4.9.
_____
56
Shadow effect
No shadow effect
Fig. 4.5: Influence of shape on the shadow effect
For cross sections with a convex shape (e.g. rectangular or circular
hollow sections) fully embedded in fire, the shadow effect does not play a
role and consequently the correction factor k sh equals unity.
For I-sections under nominal fire actions, the correction factor for the
1
This condition is verified for all commercial sections.
4.5. TEMPERATURE OF UNPROTECTED STEELWORK EXPOSED TO FIRE
shadow effect may be determined from:
ksh
0.9[ Am / V ]b /[ Am / V ]
(4.17a)
where
[ Am / V ]b -
is the box value of the section factor. The box value of the
section factor of a steel section is defined as the ratio between
the exposed surface area of a notional bounding box to the
section and the volume of steel, as shown in Table 4.5, [m-1].
In all other cases, the value of ksh shall be taken as:
k sh
[ Am / V ]b /[ Am / V ]
(4.17b)
Ignoring the shadow effect (i.e., k sh
1 ) leads to conservative solutions.
Instead of using the modified section factor, k sh [ Am / V ] , in Eq. (4.16),
one can use
ksh[ Am / V ] 0.9[ Am / V ]b
(4.18a)
if the correction factor for the shadow effect is given by Eq. (4.17a) or
ksh [ Am / V ] [ Am / V ]b
(4.18b)
if the correction factor for the shadow effect is given by Eq. (4.17b).
In both cases only the box value of the section factor, [ Am / V ]b , is
needed.
Annex E presents tables (Vila Real et al., 2009a) with values of the
section factor for unprotected ( Am / V ) and protected ( Ap / V ) I and H
European hot rolled steel profiles as well as values of the modified section
factor ( k sh Am / V ) including the correction factor for the shadow effect ( k sh )
in accordance with EN 1993-1-2.
An iterative procedure must be used to solve the simplified heat
conduction equation (4.16) because the specific heat ca and the net heat flux
h net , d are both temperature dependent.
_____
57
4. TEMPERATURE IN STEEL SECTIONS
Table 4.5: Box value of the section factor [ Am / V ]b
Section factor
[Am / V]b
Sketch
b
h
h
2(b + h)
ņņņņņņņņņņņņņ
Steel crossSection area
2h + b
ņņņņņņņņņņņņņ
Steel crossSection area
b
_____
58
box perimeter*
ņņņņņņņņņņņņņ
Steel crossSection area
* The dotted line defines the box perimeter that corresponds to the smallest
box surrounding the section (Franssen J-M, et al., 2009)
Table 4.6 gives the temperature after 30 minutes and 60 minutes of
standard fire ISO 834 exposure, for different values of the modified section
factor k sh [ Am / V ] .
4.5. TEMPERATURE OF UNPROTECTED STEELWORK EXPOSED TO FIRE
Table 4.6: Temperatures after 30 and 60 min of ISO 834 exposure
k sh [ Am / V ] [m-1]
Ta (30 min) [ºC]
Ta (60 min) [ºC]
10
20
30
40
50
60
70
80
90
100
120
140
160
180
200
250
300
257.2
431.3
553.9
636.2
690.3
721.3
734.1
741.0
753.0
767.3
792.5
809.0
818.8
824.6
828.2
832.6
834.7
549.3
735.6
834.4
900.5
922.9
930.7
934.0
935.8
937.1
938.0
939.3
940.2
940.9
941.4
941.8
942.5
943.0
Fig. 4.6 shows the development of the temperature for some HEB
profiles, obtained using Eq. (4.16), considering ksh 1.0 and the section
factors given in Table 4.7.
_____
59
Table 4.7: Section factors for HEB profiles
HE100B HE200B HE300B HE400B HE500B HE600B
-1
Am/V [m ]
ºC
218
147
116
98
89
86
1000
900
ISO 834
800
700
600
HEB100
500
400
300
HEB600
200
100
0
0
500
1000
1500
2000
2500
3000
3500
4000
segundos
Seconds
Fig. 4.6: Influence of section factor Am / V on the temperature rise in HEB profiles
4. TEMPERATURE IN STEEL SECTIONS
The S shape observed in the rise of the steel temperature between 700 ºC
and 800 ºC is due to the latent heat of metallurgical phase change of the steel in
this range of temperatures. This effect is taken into account through the rapid
increase in the specific heat of steel around 735 ºC shown in Fig. A.1.
If a constant specific heat of 600 [J/(kgK)] is used, as suggested for simple
calculation methods in the ENV version of the Eurocode 3 (1995), this
plateaux does not exist, as shown in Fig. 4.7.
ºC 1000
900
800
700
600
ca, temperature dependent
500
ca = 600 J/KgK
400
300
200
100
0
0
500
1000
1500
2000
2500
3000
3500
4000
seconds
Fig. 4.7: Influence of the use of a constant value of the steel specific heat of 600 J/(KgK)
_____
60
By programming Eq. (4.16), it is easy to build tables or nomograms like
the ones presented in Annex A for unprotected steel profiles subjected to the
ISO 834 fire curve. The use of these tables and nomograms avoids the need to
solve Eq. (4.16). The nomograms from Annex A are reproduced in Figs. 4.8
and 4.9. Knowing the section factor of the steel profile, k sh [ Am / V ] the
temperature at a given time can be evaluated using these nomograms.
[ºC]
900
800
30 min.
700
20 min.
600
15 min.
10 min.
500
400
5 min.
300
200
100
0
0
50
100
150
200
250
300
350
400
k sh Am / V [m 1 ]
Fig. 4.8: Temperature as a function of the massivity factor for various times for
unprotected sections subjected to the ISO 834 fire
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
[ºC]
60 m 1
100 m 1
40 m 1
25 m 1
800
200 m 1
700
15 m 1
600
500
400
300
200
k sh Am / V
10 m 1
100
0
0
10
20
30
40
50
60
Time [min.]
Fig. 4.9: Temperature as a function of time for various massivity factors for
unprotected sections subjected to the ISO 834 fire
For a parametric fire as defined in Chapter 3, it is not easy to build
such nomograms or tables and numerical calculation must be used. Fig. 4.10
shows the temperature development of a HE 220 B profile heated on all four
sides by a parametric fire. These results were obtained with the program
Elefir-EN, which is presented in Chapter 8.
1000
900
800
700
600
[ºC] 500
400
300
200
100
0
Parametric fire
_____
61
Steel temperature
0
20
40
60
80
100
120
140
160 [min]
Fig. 4.10: Temperature development in a compartment with a parametric fire and
the corresponding temperature of an unprotected HE 220 B
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED
TO FIRE
It is common practice to use thermal insulation to protect the steel
where fire resistance higher than 30 minutes is required. There are many
4. TEMPERATURE IN STEEL SECTIONS
forms of passive fire protection systems available to control the rate of
temperature rise in steel members exposed to fire. It was shown in Table 4.2
that the insulation materials can be applied as contour encasement or hollow
encasement. Basically there are three types of insulating materials:
- Sprays;
- Boards;
- Intumescent paint.
EN 1993-1-2 provides a simple design method to evaluate the
temperature development of steel members insulated with fire protection
materials. Assuming uniform temperature distribution, the temperature
increase 'Ta,t of an insulated steel member during a time interval ' t , is
given by
'T a ,t
O p A p / V T g ,t T a ,t
't eI /10 1 'T g ,t [ºC]
d p ca U a 1 I / 3
(4.19)
and
'Ta,t t 0 if 'T g , t ! 0
where the amount of heat stored in the protection is
I
_____
62
c p d p U p Ap
ca U a
V
(4.20)
and
Ap / V - is the section factor for steel members insulated by fire
Ap
protection material, [m-1]. Annex A.3 gives the section factor
for a range of practical cases;
- is the appropriate area of fire protection material per unit
Op
length of the member [m2/m];
- is the volume of the member per unit length, [m3/m];
- is the thermal conductivity of the fire protection system,
dp
[W/mK]. Annex A.6 gives the thermal conductivity for a
range of practical fire protection systems;
- is the thickness of the fire protection material [m];
cp
- is the specific heat of the fire protection material, [J/kgK].
V
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
Up
Annex A.6 gives the specified heat for a range of fire
protection systems;
- is the unit mass of the protection. Annex A.6 gives the unit
mass for a range of fire protection materials [ kg / m3 ];
ca
- is the temperature dependent specific heat of steel, from
Ta,t
Annex A.1 [J/kgK];
- is the steel temperature at time t [°C];
T g ,t
- is the ambient gas temperature at time t [°C];
'T g ,t
- is the increase of the ambient gas temperature during the time
Ua
interval 't [K];
- is the unit mass of steel, 7850 [kg/m3];
't
- the time interval [seconds] ( d 30 [s]).
Equation (4.19) is an approximation and only valid for small values of
the factor I. According to Wang Z (2004) this factor should normally not be
higher than 1.5, but this limitation is not given in the Eurocode.
The design value of the net heat flux reflecting the heat transfer by
convection and radiation does not appear in Eq. (4.19). In fact the
temperature drop over the insulation is relatively large and, consequently,
the surface temperature of the insulation is close to the gas temperature. The
thermal resistance between the gas and the surface of the insulation is
neglected ( T g | Tm ) and the temperature rise in the steel section is governed
by the difference in temperature between the surface of the insulation (i. e.,
the gas temperature) and the steel profile, with only the insulation material
providing thermal resistance to the heat conduction (Fig. 4.11).
Steel
Tg
Tg
Tm
Tg ~ Tm
Ta
Insulation material
Fig. 4.11: Temperature in protected steelwork
_____
63
4. TEMPERATURE IN STEEL SECTIONS
_____
64
The thermal properties of the insulation material that appear in
Eq. (4.19) must be determined experimentally in accordance with
prEN 13381-4 (2008). According to this European standard, tests on loaded
and unloaded beams as well as tests on unloaded short columns, with various
massivity factors and various protection thicknesses, subjected to the
standard fire should be made. The thermal conductivity of the insulation
material is calculated from the recorded steel temperature using the inverse
of Eq. (4.19). The unit mass and the constant specific heat must be provided
by the manufacturer of the product. If the specific heat is unknown, a value
of 1000 J/kgK should be assumed, Franssen et al. (2009).
The thermal conductivity of most commonly used passive fire
protection materials increases with increasing temperature. Therefore the
values of the thermal properties given for room temperature applications
should not be used as this will lead to unsafe results in the fire situation.
Eq. (4.19) has to be integrated with respect to time to obtain the
development of the temperature in the steel section as a function of time.
EN 1993-1-2 recommends that the time step interval ' t should not be taken
as more than 30 seconds, a value that will ensure convergence even with an
explicit integration scheme.
Any negative increment of the temperature 'Ta,t, given by Eq. (4.19),
corresponding to an increase of the gas temperature, 'Tg,t > 0, must be
considered as zero.
In the absence of specific data, the generic data given in Table A.6 of
Annex A.6 may be used, (ECCS, 1995).
The tabulated values for the thermal conductivity, Op, are normally for
dry materials. For moist fire protection materials, the steel temperature
increase, 'Ta,t, may be modified to allow for a time delay tv in the rise of the
steel temperature when it reaches 100 ºC, due to the latent heat of vaporization
of the moisture, as shown in Fig. 4.12. The length of the horizontal plateau at
100 ºC can be evaluated from the following expression, ECCS (1983):
tv
pU p d p
5O p
2
[min.] (p in %)
(4.21)
where, p is the moisture content of the protection material. No delay is
allowed if the moisture is included in the value of the thermal conductivity,
ECCS (1983).
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
ºC 1000
900
ISO 834
800
700
600
Steel temperature (dry insulation)
500
400
300
200
Steel temperature (insulation containing moisture)
100
0
tv
0
400
800
1200
1600
2000
2400
2800
3200
3600
seconds
Fig. 4.12: Time delay due to the moisture content.
For light weight insulation materials Eq. (4.19) can be simplified by
taking I 0 . The method given in ECCS (1983) suggests that the heat
capacity of the protection material can be ignored if it is less than half that of
steel section, such that
d p Ap c p U p
In this expression, Ua
ca U aV
2
7850 [kg/m3] and a value ca
(4.22)
600 [J/kgK], for
the specific heat of the steel can be used to check if the material is a light
weight material or not.
If the specific heat of the protection material, c p , is neglected, the
amount of heat stored at the protection can be taken as I
0 and Eq. (4.19)
becomes
'T a , t
O p Ap
1
d p V ca U a
T g , t T a , t 't
(4.23)
The advantage of using this equation is that it is possible to build
tables of two entries or nomograms like the ones presented in Annex A. One
of the entries is the time and the other is the modified massivity factor
Ap O p
V dp
(4.24)
The table and the nomograms presented in Annex A.5 have been
_____
65
4. TEMPERATURE IN STEEL SECTIONS
developed for the standard fire curve ISO 834 using Eq. (4.23) with a time
step of 10 seconds. This table and the nomograms provide conservative
results, because the amount of heat stored in the protection together with any
moisture it may contain have been neglected.
The use of the table and the nomograms from Annex A.5 avoid the
need for solving the Eq. (4.19). The nomograms from Annex A have been
reproduced schematically in Fig. ( 4.13) and (4.14). In both nomograms the
temperature is given as a function of the modified massivity factor, given in
Eq. (4.24).
[ºC]
240 min.
180 min.
120 min.
800
90 min.
700
60 min.
600
500
30 min.
400
300
200
100
0
0
_____
66
250
500
750
1000
1250
1500
1750
Ap O p
V dp
2000
[ W/m 3 K ]
Fig. 4.13: Temperature as a function of the modified massivity factor for various
times, for protected profiles subjected to the ISO 834 curve
1500 W/m 3 K 1000 W/m 3 K 800 W/m3 K
[ºC] 800
600 W/m3 K
2000 W/m3 K
700
400 W/m 3 K
600
300 W/m3 K
500
200 W/m 3 K
400
300
200
Ap O p
V dp
100
0
0
30
60
90
120
150
180
100 W/m 3 K
210
240
Time [min.]
Fig. 4.14: Temperature as a function of time for various modified massivity factors,
for protected profiles subjected to the ISO 834 curve
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
The table and the nomograms given in Annex A.5 were created
assuming I 0 , and are therefore only valid for ligh tweight insulation
material.
The table and nomograms can be used for heavy materials provided
the modified massivity factor is corrected, using the following expression,
according to ECCS (1985):
Ap O p
V dp
·
§
1
¸¸
¨¨
©1I 2 ¹
(4.25)
This procedure gives good results for temperatures in the range of
350 ºC to 700 ºC, which is representative of the critical temperatures that
normally occur in structural steel members. This is helpful in the pre-design
phase when estimating the thickness of fire protection. The estimated
thickness together with Eq. (4.19) can be used to obtain a more accurate
result.
The importance of correcting the modified massivity factor (4.24)
according to the expression (4.25) is demonstrated in the following example.
Consider a steel member protected with gypsum boards, which is a
heavy fire insulation material with the following characteristics:
Ap
110 m-1
V
Op
0.2 W/(mK)
cp
1700 J/(kgK)
dp
0.023 m
_____
67
U p 800 kg/m3
These values lead to a ratio of heat stored in the protection:
I
c p d p U p Ap
ca U a
V
1700.0 0.023 800
110 0.731
600 7850
The table given below shows the temperatures obtained with the
Eq. (4.19) using the program Elefir-EN and with the nomograms from
Annex A.5 considering the modified massivity factor given by Eq. (4.24)
and the same factor corrected as in Eq. (4.25).
4. TEMPERATURE IN STEEL SECTIONS
Time
Eq. (4.19)
Nomogram with
(minutes)
(ºC)
Ap O p
V dp
15
30
60
120
84
186
370
627
140
263
460
699
Nomogram with
Ap O p
V dp
(+67.2%)
(+41.3%)
(+24.4%)
(+11.5%)
112
210
381
616
§ 1 ·
¸¸
¨¨
©1I 2 ¹
(+31.0%)
(+13.1%)
(+2.9%)
(-1.7%)
( ) error comparing with the solution from Eq. (4.19).
From this table it can be concluded that the nomogram built for light
weight insulation materials gives good approximation to the results from Eq.
(4.19) if the corrected massivity factor Eq. (4.25) is used.
Fig. 4.15 shows the influence of the parameter I for this example.
ºC
800
c)
700
600
500
400
b)
300
_____
68
200
100
a)
0
0
1000
2000
3000
4000
5000
6000
7000
8000
9000 10000
seconds
Fig. 4.15: Influence of the parameter I , in a heavy fire insulation material.
a) Eq. (4.19); b) Eq. 4.23 with Eq.(4.25); c) Eq. 4.19 with I 0 or Eq. (4.23)
Consider now a steel profile protected with a light weight fire
insulation material, such as mineral wool, the characteristics of which are
listed below:
Ap
V
225 m-1
Op
0.2 W/(mK)
cp
1200 J/(kgK)
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
dp
0.02 m
U p 150 kg/m3
Fig. 4.16 shows that the influence of the amount of heat stored in the
protection, I , is not relevant, and so Eq. (4.19) can be used with I 0.0 , for
light weight fire insulation material, i. e., tables or nomograms, like the ones
presented in Annex A, can be used without any correction.
Levematerial
LightProtecção
weight protection
ºC 1000
800
600
I
400
0.0 { I z 0 .0
200
0
0
1000
2000
3000
4000
5000
6000
7000
8000
seconds
segundos
Fig. 4.16: Influence of the parameter, I , in light weight fire insulation material
Fig. 4.17 shows the temperature development of an unprotected
HE 220 A profile heated on four sides by the fire defined in example 3.3.
ºC 900
800
700
600
500
400
300
200
100
0
Parametric fire
Steel temperature
0
20
40
60
80
100
120
140
160
[min]
Fig. 4.17: Temperature of an unprotected HE 220 A heated by the parametric fire
from example 3.3
_____
69
4. TEMPERATURE IN STEEL SECTIONS
If the same profile is fire protected with gypsum board encasement with a
thickness of d p 15 mm, the temperature development is shown in Fig. 4.18.
ºC
900
800
700
600
500
400
300
200
100
0
Parametric fire
Temperature of unprotected steel
Temperature of the protected steel
0
20
40
60
80
100
120
140
160
[min]
Fig. 4.18: Temperature of a HE 220 A heated by the parametric fire of example 3.3
Example 4.1: What is the temperature of an unprotected rectangular bar
with a cross section of 200 u 50 mm2 after 30 minutes of standard fire
exposure on four sides?
_______________________________
The section factor of this convex section takes the value:
_____
70
Am / V
2 u (b t )
but
As the section is convex, k sh
2 u (0.2 0.05)
0.2 u 0.05
50 m 1
1 , and the modified section factor is
k sh [ Am / V ] 1.0 50 50 m-1
With this section factor and by interpolation in Table A.4, a temperature of
678.5 ºC is obtained.
If Eq. (4.19) is used with the program Elefir-EN, a value of the temperature
of 690 ºC is obtained.
_____________________________________________________________
Example 4.2: What is the temperature of an unprotected circular hollow
section with a diameter of d 220 mm and a thickness of t 5 mm after 60
minutes of standard fire exposure?
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
t
d
_______________________________
The external perimeter is
S d
P
691 .15 mm
The area of the cross section is
S
A
4
>d
2
( d 2t ) 2
@
3377.21 mm2
The section factor is
Am
V
P
A
0.2047 mm-1 = 204.7 m-1
According to Annex A.2, the section factor is given by:
Am
V
P
A
As the section is convex, k sh
d
1
200 m-1
|
(d t )t t
1 , and the modified section factor, using the
later value of the section factor, is
k sh [ Am / V ] 200 m-1
Table A.4 from Annex A gives the temperature of 942 ºC.
_____________________________________________________________
Example 4.3: What is the temperature of an unprotected HE 200 A profile
after 30 minutes of standard fire exposure on four sides?
_______________________________
The section factor for an HE 200 A is:
Am / V
211 m-1
_____
71
4. TEMPERATURE IN STEEL SECTIONS
The HE 200 A has the following geometric characteristics:
b 200 mm
h 190 mm
2
A 53 .83 cm
and the box value of the section factor [ Am / V ]b takes the value
[ Am / V ]b
2 u (b h)
A
2 u (0.2 0.19)
144.9 m-1
53.83 u 10 4
The shadow factor, k sh is given by:
k sh
0.9[ Am / V ]b /[ Am / V ] 0.9 144.9 / 211 0.618
Taking into account the shadow effect, the modified section factor has the
value
ksh[ Am / V ] 0.618 211 130.4 m-1
This value should be obtained without evaluating k sh , using Eq. (4.18a):
k sh [ Am / V ] 0.9[ Am / V ]b
_____
72
0.9 144.9 130.4 m-1
Interpolating in Table A.4 yields a temperature of 786 ºC.
If Eq. (4.16) is used, a temperature of 802 ºC is obtained.
_____________________________________________________________
Example 4.4: What is the thickness of fibre-cement board encasement for a
IPE 300 heated on three sides to be classified as R90 if the critical
temperature is 654 ºC?
_______________________________
The following thermal properties of the fibre-cement are defined in Annex A.6:
Op
0.15 W /(m K )
cp
1200 J/(kgK)
Up
800 kg/m3
The massivity factor for the IPE 300 with hollow encasement heated on
three sides is:
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
Ap / V
139 m 1
By interpolation in Table A.5 from Annex A, for a temperature of 654 ºC, at
90 minutes of standard fire exposure, the modified section factor is:
Ap O p
d 1210 W/(m 3 K )
V dp
and the thickness is
dp t
Ap / V
1210
Op
139
0.15 0.017 m 17 mm
1210
This thickness can be corrected if the amount of heat stored in the protection,
I , is taken into account, according Eq. (4.20) and using Eq. (4.25) to obtain
the corrected thickness.
Ap O p
1
d 1210 W/(m 3 K)
V d p 1I / 2
The following iterative procedure is needed to evaluate the corrected
thickness:
dp
I
c p d p U p Ap
ca U a
V
dp t
Ap
V
Op
1
1210 1 I / 2
0.017
1200 0.017 800
139
600 7850
0.0139
0.0139
1200 0.0139 800
139
600 7850
0.0144
0.0144
1200 0.0144 800
139
600 7850
0.0143
0.0143
1200 0.0143 800
139
600 7850
0.0143
With this procedure a thickness of 14.3 mm is obtained, instead of 17 mm.
_____________________________________________________________
_____
73
4. TEMPERATURE IN STEEL SECTIONS
Example 4.5: At what time will a HE 220 B column protected with a 20mm
thick gypsum board reach a temperature of 559 ºC when heated by the
standard fire curve on four sides?
_______________________________
The massivity factor for the HE 220 B with hollow encasement heated on
four sides is Ap / V 96 m 1 .
Annex A.6 gives the thermal properties of gypsum boards:
Op
0.2 W/(m K)
c p 1700 J(kg K)
U p 800 kg/m3
p 20% (moisture content)
As the thickness of the insulation is known, the ratio of heat stored in the
protection can be evaluated as
I
cpd pU p
ca U a
1700 0.02 800
96
600 7850
Ap
V
0.554
and the corrected modified section factor
_____
74
Ap O p
1
V d p 1I / 2
96
0.2
1
0.02 1 0.554 / 2
752 W/(m3 K)
Based on this value and for the temperature of 559 ºC, a double interpolation
in the table of Annex A.5 gives a time of 97 minutes.
The delay time due to the moisture content is, according to Eq. (4.21):
tv
pU p d p
5O p
2
20 800 0.02 2
5 0 .2
6 min .
The time to reach the temperature of 559 ºC is then:
t
97 6 103 min .
If the program Elefir-EN is used the temperature of 559 ºC is reached after
98.9 minutes, as shown in Fig. 4.19.
4.6. TEMPERATURE OF PROTECTED STEELWORK EXPOSED TO FIRE
ºC 1200
ISO 834
1000
Steel temperature
800
559 ºC
600
400
200
0
0
20
40
60
80
100
120
[min]
Fig. 4.19: Temperature of a HE 220 B protected with gypsum boards
_____________________________________________________________
Example 4.6: Consider a IPE 300 profile protected with 20mm thick
fibre-cement board encasement. Calculate the temperature after 60 minutes
of standard fire exposure on four sides taking into account the amount of
heat stored in the protection and the time delay due to the moisture content.
_______________________________
The following thermal properties of the fibre-cement board are defined in
Annex A.6:
Op
0.15 W/(m K)
cp
1200 J/(kgK)
Up
800 kg/m3
p
_____
75
5% (moisture content)
The fire insulation material is considered as a heavy material if its heat
capacity is bigger than half that of the steel section, i.e.:
d p Ap c p U p !
c a U aV
2
As the section factor of the IPE 300 is A p / V
167 m 1 , that relation is
verified
0.02 167 1200 800 !
600 7850
2
4. TEMPERATURE IN STEEL SECTIONS
3206400 ! 2355000
and the 20 mm thick fibre-cement can be considered as a heavy material.
The ratio of heat stored in the protection takes the value:
cP d P U p
I
ca U a
1200 0.02 800
167
600 7850
Ap
V
0.681
and the corrected section factor:
Ap O p
1
V d p 1I / 2
934 W/(m3K)
Interpolating in Table A.5 from Annex A yields a temperature of 453 ºC.
If Eq. (4.19) is used, for example with the software Elefir-EN, the
temperature of 451 ºC is obtained, which is close to the value obtained by
interpolation.
The time increase in fire resistance due to the moisture content of the
protection can be calculated as follows:
tv
_____
76
pU p d p
5O p
2
5 800 0.02 2
5 0.15
2.13 # 2 min .
Taking into account this delay, the temperature is calculated after
60 2 58 minutes instead of 60 minutes. Eq. (4.19) gives, after 58
minutes, the temperature
T
439 ºC
With the software Elefir-EN a temperature of 443 ºC is obtained if the
moisture content is taken into account.
It should be noted that if the fibre-cement board was considered as light
weight insulation material and the corrected section factor was not used, then
table A.6 would give for
Am O p
V dp
167
0.15
1252.5 W/m3K
0.02
a temperature of T 526 ºC instead of the 453 ºC previously obtained, with
an error of | 16 .7% , but on the safe side.
4.7. INTERNAL STEELWORK IN A VOID PROTECTED BY HEAT SCREENS
4.7. INTERNAL STEELWORK IN A VOID PROTECTED BY HEAT
SCREENS
This section deals with two different geometrical situations.
The first situation is when a steel beam is underneath a slab, with a
horizontal heat screen present underneath the profile, as shown in Fig. 4.20.
Heat screen
Fire
Fig. 4.20: Steel beam with a heat screen underneath (elevation)
The second situation is when a steel column is located between two
vertical heat screens. Fig.4.21 shows a column with heat screens on both
sides and the fire on one side only. In other situations, the fire could be on
each side of the column.
Heat screen
Heat screen
Fire
Fig. 4.21: Protected steel column with heat screens on both sides (plan view)
_____
77
4. TEMPERATURE IN STEEL SECTIONS
In both cases, there is a gap between the heat screen and the steel
section. If the heat screen touches the steel section, the method describes in
this section does not apply.
The development of the temperature in the steel section must be
calculated by one of the methods described in Sections 4.5 or 4.6, depending
on whether or not the steel member is thermally protected. The fire
temperature is taken as the gas temperature in the void, and this is
determined experimentally according to EN 13381-1 (2006), for horizontal
protective membranes, or EN 13381-2 (2008), for vertical protective
membranes, as appropriate.
4.8. EXTERNAL STEELWORK
4.8.1. General principles
_____
78
This section deals with steel members that are located outside the
envelope of the building and are heated by flames coming from inside the
building. The temperature and the size of the flames are determined using
the methods given in Section 3.7.
The temperature distribution in external steelwork is determined in a
steady state situation based on the steady state radiative fluxes determined
according to Section 3.7. This means that a temperature will be determined in
the steel section, but no information will be available about the time required
for this temperature to be established. As a consequence, the verification of the
stability of the steel member is only possible in the temperature or in the load
domain, but not in the time domain. The result will be either a fail or a pass. If
the calculation shows that the stability is ensured, any fire requirement
expressed in term of fire class will be satisfied. If the calculation shows that
the stability is not ensured, it will not be possible to determine the time of
collapse and, thus, the fire resistance class of the member. Recent research
work has been undertaken to extend the theory to transient situations, but the
results of this work have not yet been introduced in the Eurocode.
The temperature in the steel section results from an energy balance
between the radiative heat flux received from the fire compartment and the
radiative and convective heat flux emanating from the openings, on one
4.8. EXTERNAL STEELWORK
hand, and the radiative and convective heat flux lost to the ambient
atmosphere, on the other hand.
The influence of heat screens must be considered. If the heat screens
are non-combustible and have a fire resistance EI of at least 30 minutes
according to EN ISO 13501-2, it is assumed that there is no radiative heat
transfer to those sides of the section that are protected by the screens.
Geometrical parameters such as size and location of the steel member
with respect to the compartment and its openings and size of the openings
must be considered.
The detailed procedure is described in Annex B of Eurocode 3. Only
the general principles are described in this book.
The assumptions are that the fire is confined to one compartment only
and that all openings in the façade are rectangular.
A distinction is made between members that are engulfed in flames
and members that are not engulfed in flames, depending on their position
relative to the openings:
x A member that is not engulfed in flames receives heat from all the
openings in the wall that it is facing and from all flames coming out of
these openings.
x A member that is engulfed in flames receives heat only from the
engulfing flame (convection and radiation) and from the opening from
which this flame is emanating (radiation).
The equilibrium temperature in the steel member Tm is calculated from
the heat balance given in Eq. (4.26) for a member not engulfed in flames and
in Eq. (4.27) for a member engulfed in flames.
V Tm4 D Tm
¦I
V Tm4 D Tm
z
¦ I f D 293
I z I f D Tz
(4.26)
(4.27)
where V is the Stefan Boltzmann constant equal to 5.67u10-8 W/m²K4, D is
the convective heat transfer coefficient, Iz is the radiative heat flux from a
flame, If is the radiative heat flux from an opening and Tz is the flame
temperature.
The convective heat transfer coefficient D is calculated from the rules
given in Annex B of Eurocode 1, see Section 3.7 of this book, using an
effective cross section dimension equal to the average of both dimensions in
the section.
_____
79
4. TEMPERATURE IN STEEL SECTIONS
The radiative heat flux from an opening is calculated from Eq. (4.28).
If
I f 1 D f V T f4
(4.28)
where If is the overall configuration factor of the member from that opening
and Df is the absorptivity of the flame, to be determined according to the
rules given in Annex B of Eurocode 3.
It is not possible to repeat in detail in this book all the rules that are
given in Eurocode 1 and Eurocode 3. An example is given hereafter that will
allow the reader to follow the procedure for a simple case and find his way
through all the clauses of the Eurocodes where this procedure is described.
4.8.2. Example
A hotel is constructed from a steel skeleton that supports modular
prefabricated rooms. Part of the structure is external, as shown in Fig. 4.22.
The floor to floor height is 2.8 m and the grid is 3 m wide. The windows are
1.5 m wide and 1 m high. The external steel structure is 1 m away from the
façade. Each room is 2.8 m wide and 6 m deep, with a floor to ceiling height
of 2.5 m. The effect of the wind is not considered.
Calculate the temperature in the external 0.2 m u 0.2 m steel square tube
columns.
_____
80
2800
3000
1000
Fig. 4.22: Two elevations of the façade of a hotel
[mm]
4.8. EXTERNAL STEELWORK
The area of the window (1.5 m²) is less than 50% of the area of the wall (7 m²).
There is no forced draught and the door of the room is assumed to be closed.
_______________________________
Rate of heat release in the compartment.
Floor area Af = 6 u 2.8 = 16.8 m²
Design fire load qf,d = 377 MJ/m² (taken as qf,k)
Qfuel control = 377 u 16.8 / 1200 = 5.28 MW, see Eq. (3.35)
D/W = 6 / 2.8 = 2.14, see Eq. (3.34) (B.1 in Eurocode 1)
Height of the window heq = 1 m
Area of vertical openings Av = 1.5 u 1 = 1.5 m²
Total area of enclosure At = 2 u 16.8 + 2 u 2.5 (6 + 2.8) = 77.6 m²
Opening factor O = 1.5 u (1)0.5 / 77.6 = 0.019 m1/2
Qair control = 3.15 1 e0.036 0.019 1.5 1 = 2.74 MW, see Eq. (3.35)
2.14
=> Q = 2.74 MW
Temperature of the fire compartment
:
Tf
16.8u 377
= 587, see Eq. (3.37)
1.5u 77.6
6000 1 e 0.1 0.019
0.019 1 e 0.00286u 587 20 = 689°C
Flame height
LL
§ 2.74 ·
1.9 ¨
¸
© 1.5 ¹
2
3
1 = 1.84 m, see Eq. (3.38)
Flame temperature at the window
Lf = 1.84 + 1/2 = 2.34
L f wt Q = 2.34 u 1.5 2.74 = 1.401 > 1. We take L f wt Q = 1.0
TW
520 1 0.4725 u 1.0 20 = 1006°C
_____
81
4. TEMPERATURE IN STEEL SECTIONS
650
1500
f
667
d
e
PLAN VIEW
b
233
c
a
Lx
C
Level of steel
temperature calculation
1840
B
A
333
333
233
_____
82
667
[mm]
ELEVATION
Fig. 4.23: Shape of the flame
Shape of the flame
See Fig. 4.23
Temperature along the flame
LX wt Q = LX u 1.5 / 2.74 = 0.55 LX, must be smaller than 1.
LX must be lower than 1.83 m.
TZ 1006 20 1 0.4725u 0.55 LX 20 = 986 (1 - 0.26 u LX) + 20
= 1006 – 256 LX, see Eq. (3.40)
4.8. EXTERNAL STEELWORK
The temperature varies linearly along the flame axis. From 1006°C at the
window, see point A on Fig. 4.23, the temperature decreases to 885°C at
point B (LX = 0.471 m) and 538°C at point C, located 1.83 - 0.471 = 1.359 m
above point B.
Above Point C, where LX wt Q is larger than 1, the Eurocode is not
clear about the temperature distribution. It is assumed here that the term
LX wt Q is replaced by 1 in the equation and the temperature keeps the
same value of 538°C until the tip of the flame.
Clause B.1.4 (4) of Eurocode 3 states that the radiative heat flux from
the flames may be based on the dimensions of an equivalent rectangular
flame. This approximation would clearly simplify the process but it has
nevertheless not been made here. This is because the Eurocode is not very
clear about the size and equivalent temperature of this equivalent rectangular
flame. For example, Fig. B.3 shows a height z of the equivalent flame, and z
is said to be defined in Annex B of Eurocode 1 but z is not used in
Eurocode 1. If z is the height of the window, then the equivalent rectangular
flame is not linked to the height of the real flame LL. Also, the temperature
of the flame should be taken at a distance l from the opening equal to h/2
(Eq. B.11a) and, assuming that h is the height of the window, this point has
also no correlation with the flame length.
This is why physical principals and "using appropriate adaptations of
the treatments given in B.2", see B.1.3 (4), have been used here.
It is not possible to determine directly the vertical position along the
column where the level of temperature is the highest. Strictly speaking, the
temperature should be evaluated at different positions along the column. The
crushing load of the column is then determined by the maximum temperature
of all sections. If the failure mode is by buckling, it will be more difficult to
evaluate the load bearing capacity of the column with a temperature that
varies along the length using simple models.
Because of the longer length of the vertical part of the flame (i.e., the
part that extends along the wall above the window), it is assumed that the
point of maximum temperature is facing this vertical part. Because of higher
temperatures prevailing in the lower part of the flame, it is assumed that the
point of maximum temperature is slightly below mid-level of the vertical
part. The temperature will be calculated in this example only at a level of
0.6 m above point B.
_____
83
4. TEMPERATURE IN STEEL SECTIONS
For a precise determination of the steel temperature at this point, the
vertical part of the flame should be divided along the height in a number of
different zones, each one having its own temperature. For simplicity, the
temperature in the vertical part of the flame will be approximated as constant
and equal to the value at 0.6 m, i.e., LX = 1.071. This temperature is 732°C.
The lateral triangular part of the flame (the part that contains the line AB on the elevation of Fig. 4.23) is also visible from the section, see the plan
view. To allow direct application of the formulae for view factors, it will be
approximated as a square surface of equal surface area
(0.222 m² = 0.47 m u 0.47 m), with a uniform temperature equal to 945°C
(average between TA and TB) and located at the centre of gravity of the
triangle. This equivalent square surface is represented by a dotted line on the
elevation.
View factors
_____
84
1.a) Between the centre of side b-c on the profile and the vertical plane d-e
on the flame, see the plan view on Fig. 4.23. The planes are parallel and the
configuration corresponds to the one depicted in Fig. 3.6 and Fig. 3.8.
Distance (horizontal) between the two planes s = 0.233 m.
The vertical part of the flame is divided into 4 zones (2 of them with
negative contribution) and the calculations are summarized in the following
table.
Zone 1
Zone 2
Zone 3
Zone 4
Total
h (vertical)
0.60
0.60
1.24
1.24
-
w (horizontal)
2.25
0.75
2.25
0.75
-
I
0.233
-0.227
0.245
-0.237
0.014
1.b) Between the centre of side b-c on the profile and the plane e-f on the
flame, see the plan view on Fig. 4.23. The planes are perpendicular and the
configuration corresponds to the one depicted in Fig. 3.7 and Fig. 3.8.
Distance (horizontal) between points P and x: s = 0.75 m.
The vertical part of the flame is divided into 4 zones and the calculations are
summarized in the following table.
4.8. EXTERNAL STEELWORK
Zone 1
Zone 2
Zone 3
Zone 4
Total
h (vertical)
0.60
0.60
1.24
1.24
-
w
w (horizontal)
0.900
0.233
0.900
0.233
-
I
0.059
-0.008
0.081
-0.010
0.121
The total view factor from the side b-c to the section of the flame at 732°C is
thus equal to 0.014 + 0.121 = 0.135.
2) Between the centre of side b-c on the profile and the lateral triangular part
of the flame. The planes are perpendicular and the configuration corresponds
to the one depicted in Fig. 3.7.
Distance (horizontal) between points P and x: s = 0.75 m.
The vertical part of the flame is divided into 4 zones and the calculations are
summarized in the following table.
h (vertical)
Zone 1
Zone 2
Zone 3
Zone 4
Total
1.057
1.057
0.587
0.587
-
w (horizontal)
w
0.913
0.443
0.913
0.443
-
I
0.078
-0.031
-0.059
0.024
0.012
3.a) Between the centre of side a-b on the profile and the vertical plane e-f
on the flame, see plan view on Fig. 4.23. Distance (horizontal) between the
two parallel planes s = 0.65 m. The calculations are summarized in the
following table.
h (vertical)
Zone 1
Zone 2
Zone 3
Zone 4
Total
0.60
0.60
1.24
1.24
-
w (horizontal)
w
1.00
0.33
1.00
0.33
-
I
0.154
-0.089
0.195
-0.108
0.151
_____
85
4. TEMPERATURE IN STEEL SECTIONS
3.b) Between the centre of side a-b on the profile and the plane e-d on the
flame, see the plan view on Fig. 4.23. The planes are perpendicular.
Distance (horizontal) between points P and x: s = 0.333 m.
Zone 1
Zone 2
Zone 3
Zone 4
Total
h (vertical)
w
w (horizontal)
I
0.60
0.60
1.24
1.24
-
2.15
0.65
2.15
0.65
-
0.163
-0.119
0.196
-0.133
0.106
The total view factor from the side a-b of the section to the flame at 732°C is
thus equal to 0.151 + 0.106 = 0.257.
4) Between the centre of side a-b on the profile and the lateral triangular part
of the flame. Distance (horizontal) between the two parallel planes
s = 0.65 m.
Zone 1
Zone 2
Zone 3
Zone 4
Total
_____
86
h (vertical)
1.057
1.057
0.587
0.587
-
w (horizontal)
1.013
0.543
1.013
0.543
-
I
0.189
-0.147
-0.152
0.121
0.011
5) Between the centre of side b-c on the profile and the window. Distance
(horizontal) between the two parallel planes s = 0.90 m.
h (vertical)
w
w (horizontal)
I
Zone 1
1.6
2.25
0.209
Zone 2
1.6
0.75
-0.149
Zone 3
0.6
2.25
-0.135
Zone 4
0.6
0.75
0.102
Total
-
-
0.027
4.8. EXTERNAL STEELWORK
6) Between the centre of side a-b on the profile and the window. The planes
are perpendicular. Distance (horizontal) between points P and x: s = 1.0 m.
h (vertical)
w
w (horizontal)
I
Zone 1
1.6
2.15
0.121
Zone 2
1.6
0.65
-0.037
Zone 3
0.6
2.15
-0.069
Zone 4
0.6
0.65
0.024
Total
-
-
0.039
Radiative heat flux from the opening, see Eq. (B.3) in Eurocode 3
Overall configuration factor from the opening, see Eq. (B.4) in Eurocode 3:
If = (0.027 u 200 + 0.039 u 200) / ( 4 u 200) = 0.017
Emissivity of the opening, see B.1.3 (6) in Eurocode 3:
Hf = 1.0
Absorptivity of the flame, see B.2.4 (1) in Eurocode 3:
az = 0
If = 0.017 u 1 u (1-0) u 5.67 u 10-8 u (689+273)4 = 826 W/m²
Radiative heat flux from the flame
Radiation from the part of the flame above the window.
Overall configuration factor from the flame, see Eq. (B.5) in Eurocode 3.
Iz = (0.135 u 200 + 0.257 u 200) / ( 4 u 200) = 0.098
Emissivity of the flame:
Flame thickness = 1.5 m, Eq. (B.10a) in Eurocode 3.
Hf = 1 - e-0.3 u 1.5 = 0.362, Eq. (B.26) in Eurocode 1
Iz1 = 0.098 u 0.362 u 5.67 u 10-8 u (732+273)4 = 2052 W/m²
Radiation from the triangular part of the flame.
Overall configuration factor from the flame, see Eq. (B.5) in Eurocode 3
_____
87
4. TEMPERATURE IN STEEL SECTIONS
Iz = (0.012 u 200 + 0.011 u 200) / ( 4 u 200) = 0.006
Iz1 = 0.006 u 0.362 u 5.67 u 10-8 u (945+273)4 = 271 W/m²
Convective heat transfer coefficient
Effective cross sectional dimension:
deq = 0.2, see B.1.3 (2) in Eurocode 3
Dc = 4.67 (1/0.2)0.4 (2.74/1.5)0.6 = 12.8, see B.4.1 (12) in Eurocode 1
Equation of equilibrium, Eq. (B.1) in Eurocode 3
5.67 u10-8 T4 + 12.8 T = 826 + 2052 + 271 + 293 u 12.8
This yields as a solution: T = 412 K or 139°C.
This temperature is, in this academic example, rather low. A new calculation
should normally be made taking into account the effect of wind. The process
is similar to the one described here; only the geometrical quantities are more
complicated.
4.9. VIEW FACTORS IN THE CONCAVE PART OF A STEEL
PROFILE
_____
88
A view factor can be introduced to account for “parts” of the structural
element that shielded from radiative heat (ECCS TC3, 2001). It is defined as
the ratio between radiative heat leaving an emitting surface and the radiative
heat arriving at a receiving surface.
The general formula for the view factor is (ECCS TC3, 2001,
Drysdale D, 1999)
I
1
Ar
³³
Ae Ar
cosIe cosIr
dAe dAr
S r2
(4.29)
For two-dimensional cases (see Fig. 4.24) the view factor can be given
by (ECCS TC3, 2001):
I
AC BD AD BC
2CD
but I d 1.0
(4.30)
4.9. VIEW FACTORS IN THE CONCAVE PART OF A STEEL PROFILE
By definition, the value of the view factor is between zero and unity.
Its value depends on the distance between the two surfaces, the size of the
surfaces and their relative orientation (see Fig. 4.24).
C
Ar
Ir
D
r
Ie
A
Ae
B
Fig. 4.24: Emitting and receiving surfaces for radiative heat
( Ae - emitting surface; Ar - receiving surface)
As an example, Fig. 4.25 shows the values of the view factors for the
internal surfaces of a fully fire engulfed HE 400 B. These are the view
factors between the surface of the box contour through which the energy
passes and each of the internal surfaces of the section that receive this
energy. Each view factor can be calculated according to Eq. (4.30) and using
Fig. 4.26 for this particular case.
i)
I
ii)
I
iii)
I
For the web surface according to Fig. 4.26a
AC BD AD BC
2 143.25 2 143.25 2 352 2
2CD
2 352
0.67
For the top flange surface according to Fig. 4.26b
AC BD AD BC
143.25 2 352 2 0 352 143.25
2CD
2 143.25
0.40
For the bottom flange surface according to Fig. 4.26c
AC BD AD BC
143.25 352 0 143.25 2 352 2
2CD
2 143.25
0.40
_____
89
4. TEMPERATURE IN STEEL SECTIONS
143.25 mm
0.40
352 mm
0.67
0.40
Fig. 4.25: View factors for an HE 400 B
It can be verified that the total amount of energy received by the
chamber of the section is proportional to 2u0.40u143.25 + 0.67u352 = 352,
which is exactly equal to the factor proportional to the energy crossing the
dotted line on Fig. 4.25, considering I 1.0 , i.e., 1.0u352 = 352.
143.25
143.25
D
C
B
352
B D
A
B
352
352
C
143.25
A
C
A D
a)
b)
c)
Fig. 4.26: Emitting (AB) and receiving (CD) surfaces for radiative heat.
a) For the web surface; b) For the top flange surface; c) For the bottom flange surface
_____
90
This concept can be used, for example, when the temperature of the
web of a section has to be determined in order to evaluate the shear
resistance of the web. This procedure is more detailed and more precise than
the utilisation of the shadow factor present in Eq. (4.16) because the shadow
factor is the weighted average value of the view factors calculated on the
whole perimeter of the section1.
For example, for the HE 400 B and neglecting the radius of root fillet
between the web and the flanges, the values for the perimeter, Am , the box
value of the perimeter, Am,b , the area of the cross section, V, the box value
of the section factor, [ Am / V ]b and the section factor, Am / V , are:
Am 1973 mm
Am,b 1400 mm
1
Except for the factor 0.9 for hot rolled H or I sections, that has no physical
meaning and is deemed to disappear in the next revision of the Eurocode.
4.10. TEMPERATURE IN STEEL MEMBERS SUBJECTED TO LOCALISED FIRES
V 19152 mm2
[ Am / V ]b 1400/ 19152 0.073 mm-1 = 73 m-1
Am / V 1973/ 19152 0.103 mm-1 = 103 m-1
The correction factor for the shadow effect given by Eq. (4.17b), takes
the value:
ksh [ Am / V ]b /[ Am / V ] 0.073 / 0.103 0.708
which is exactly the same as the weighted average value of the view factors,
) , calculated on the whole perimeter of the section
)
4 0.4 143.5 2 0.67 352 2 1.0 300 4 1.0 24
1973
0.708
For the calculation of the temperature using an advanced calculation
model, the view factors can be evaluated and applied individually to each
surface, as shown on Fig. 4.25. For all the external surfaces of the profile a
view factor ) 1 .0 can be conservatively adopted or evaluated as in Annex
G of Eurocode 1. If a simpler solution is sought and some level of
approximation is acceptable, the averaged value of the view factor (equal to
the shadow factor) can be applied to the whole cross section.
Using the shadow factor in the simple design equation (4.16) is an
approximation because the convective part of the net heat flux, hnet,c , is also
affected by the correction factor k sh .
4.10. TEMPERATURE IN STEEL MEMBERS SUBJECTED TO
LOCALISED FIRES
EN 1993-1-2 gives two different equations for calculating the
temperature of steel members subjected to localised fire depending on whether
the members are protected or not. The procedures that are used to evaluate the
temperature in the case of localised fires are presented in this section.
4.10.1. Unprotected steel members
For unprotected sections, the heat flux is give by Eq. (4.16) and this is
used to evaluate the temperature. This heat flux, hnet , d hnet ,c hnet , r , defined in
_____
91
4. TEMPERATURE IN STEEL SECTIONS
Eq. (4.16), is easily calculated if the gas temperature, T g , is known. For
localised fires not impinging the ceiling, the gas temperature is given by
Eq. (3.24) (Heskestad Method). In the case where the localised fire impinges on
the ceiling, the heat flux is given by Eq. (3.32) (Hasemi Method), and this can be
used directly for calculating the temperature in unprotected steel members.
Fig. 4.27 shows the development of the flame length for the localized
fire given in Example 3.7, with the same maximum fire area of 72 m2, but
with a distance from the source to the ceiling of 6 meters, instead of 3
meters. As the maximum length of the flame is 5.8 meters, the flame is not
impinging the ceiling and the temperature of the gas is given by Eq. (3.24).
For this case, the temperature of an unprotected IPE 300 beam heated on
four sides is depicted in Fig. 4.28. The cross section of the beam is on the
flame axis and located at the level of the ceiling.
Fig. 4.29 shows the temperature development of an IPE 300 heated on
four sides, by the same localised fire but with a distance from the source to
the ceiling of 3 meters, i.e., the flame is impinging the ceiling.
m 7
6
5
Flame lenght
4
Ceiling
3
_____
92
2
1
0
0
20
40
60
80
100
120
[min]
Fig. 4.27: Length of the flame
ºC 600
Gas
500
Unprotected Steel
400
300
200
100
0
0
20
40
60
80
100
120
[min]
Fig. 4.28: Gas and unprotected IPE 300 temperature development when the flame
does not impinge the ceiling
4.10. TEMPERATURE IN STEEL MEMBERS SUBJECTED TO LOCALISED FIRES
900
800
700
600
500
[ºC]
400
300
200
100
0
Gas
Unprotected Steel
0
20
40
60
80
100
120
[min]
Fig. 4.29: Gas and unprotected IPE 300 temperature development when the flame is
impinging the ceiling
4.10.2. Protected steel members
For protected steel members, the equation used for calculating the
temperature is only based on the gas temperature, see Eq. (4.19). For
localised fires not impinging the ceiling the gas temperature is given by Eq.
(3.24) and the development of the steel temperature is calculated from Eq.
(4.19). Fig. 4.30 shows the temperature development of a cross section on
the axis of the flame of a protected IPE 300 heated on four sides by the
localised fire of example 3.7 with a distance from the source to the ceiling of
6 meters, i.e., not impinging the ceiling.
ºC 600
Gas
500
Protected Steel
400
300
200
100
0
0
20
40
60
80
100
120
[min]
Fig. 4.30: Temperature development of gas and protected IPE 300 when the flame
does not impinge the ceiling
_____
93
4. TEMPERATURE IN STEEL SECTIONS
Eq. (4.19) can not be applied directly in the case of a fire impinging
the ceiling, because the effect of the fire is given as an impinging flux, see
Eq. (3.32). A procedure has to be established to transform the impinging heat
flux into an equivalent gas temperature. Cadorin et al. (2003) suggests
deducing a fictitious temperature that has the same effect on steel elements
as the heat flux calculated with this method. This is the temperature of a steel
profile with a very high massivity factor. This steel profile has a temperature
which is very close to the gas temperature. This procedure is used in the
program Elefir-EN presented in Chapter 8. The program first evaluates the
gas temperature as the temperature of an unprotected steel profile with very
high section factor (Am/V = 10000 m-1 is adopted) using Eq. (4.16) and the
net heat flux given by Eq. (3.33). After evaluating the gas temperature, the
temperature of the protected steel profile is then calculated using Eq. (4.19).
If the distance from the source to the ceiling is 3 meters, as in
Example 3.7, the flame impinging the ceiling and the temperature
development of a protected IPE 300 just above the fire source is shown in
Fig. 4.31.
ºC
_____
94
900
800
700
600
500
400
300
200
100
0
Gas
Protected steel
0
20
40
60
80
100
120
[min]
Fig. 4.31: Temperature development of Gas and protected IPE 300 when the flame
impinges the ceiling
4.11. TEMPERATURE IN STAINLESS STEEL MEMBERS
Annex C of EN 1993-1-2 provides guidance on the thermal properties
of stainless steels. These properties can also be found in the Annex A of this
4.11. TEMPERATURE IN STAINLESS STEEL MEMBERS
book.
Compared with carbon steel, the thermal properties of stainless steel
are quite different. The main differences are:
- The increase of specific heat with increasing temperature is slightly
lower in stainless steel than in carbon steel. Furthermore carbon
steel has a larger increase in specific heat at 735 ºC due to a
metallurgical phase change which is not present in stainless steel.
This is shown in Fig. 4.32.
- Compared to carbon steel, at ambient temperature, stainless steel has
a much lower thermal conductivity. However, the thermal
conductivity of stainless steel increases at elevated temperature
and even exceeds the value for carbon steel at temperatures above
1000 ºC. This behaviour is shown in Fig. 4.33.
C a (J/kgK)
5000
Carbon steel
Stainless steel
4000
3000
_____
95
2000
1000
T (ºC)
0
0
200
400
600
800
1000
1200
Fig. 4.32: Specific heat of stainless steel and carbon steel as a function of
temperature
Another difference lies in the surface emissivity of the member, Hm,
which is equal to 0.4 for stainless steel and 0.7 for carbon steel.
4. TEMPERATURE IN STEEL SECTIONS
O a (W/mK)
60
Stainless steel
Carbon steel
50
40
30
20
10
T (ºC)
0
0
200
400
600
800
1000
1200
Fig. 4.33: Conductivity of stainless steel and carbon steel as a function of
temperature
Fig. 4.34 compares the temperature development of an IPE 450
exposed on four sides to the ISO 834 fire curve.
[ºC] 1000
900
800
700
_____
96
600
500
Stainless steel
400
Carbon steel
300
200
100
0
0
5
10
15
20
25
30
35
40
45
50
55
60
Time [min]
Fig. 4.34: Temperature development of a carbon steel and a stainless steel IPE 450,
heated on four sides by the ISO 834 fire curve
This figure shows that the time-temperature curve for stainless steel
does not exhibit the S shape of the carbon steel curve in the temperature
range between 700 ºC and 800 ºC; this is due to the absence of the peak
value on the heat capacity of stainless steel (see Fig. 4.32). The slower
4.11. TEMPERATURE IN STAINLESS STEEL MEMBERS
increase in temperature of stainless steel in the early stage of the fire is due
to a combination of the lower values of thermal diffusivity Oa /(Ua ca ) (see
Fig. 4.35) and surface emissivity compared to carbon steel. In the later stage
of the fire, both steel temperature curves tend toward the ISO fire curve. In
this case, the role played by the surface emissivity is much more important
than the role played by the thermal diffusivity.
m2/s
1.6E-05
Carbon Steel
1.2E-05
Stainless steel
8.0E-06
4.0E-06
0.0E+00
0
200
400
600
800
1000
1200 ºC
Fig. 4.35: Thermal diffusivity of carbon steel and stainless steel
Annex A provides tables and nomograms to evaluate the temperature
of unprotected stainless steel profiles exposed to the standard fire curve ISO
834, avoiding the need to perform the time integration of Eq. (4.16), as
illustrated in the next example.
4.11.1. Example
What is the temperature of the unprotected circular hollow section of
Example 4.2 after 60 minutes of standard fire curve exposure if it is made of
stainless steel?
_______________________________
Solution:
According to Annex A.2, the section factor is given by:
Am
V
P
A
1
d
|
200 m-1
(d t )t t
_____
97
4. TEMPERATURE IN STEEL SECTIONS
As the section is convex, k sh
1 , and the modified section factor is given
by:
k sh [ Am / V ] 200 m-1
Table A.8 from Annex A gives temperature of 940 ºC (942 °C for example
4.2). This is compared to a temperature of 942 ºC for a similar carbon steel
section.
_____
98