Water Distribution System
Water Distribution System
CE 370
The system should be capable of meeting the demands at all times and at satisfactory pressure
3
Pipe systems Pumping stations Storage facilities Fire hydrants House service connections Meters Other appurtenances
System Configurations
Distribution systems may be classified as:
Branching systems Grid systems A combination of the above two systems Street patterns Topography Degree and type of development of the area Location of the treatment and storage works.
System Configurations
Branching vs. grid systems:
A grid system is usually preferred over a branching system, since it can furnish a supply to any point from at least two directions The branching system has dead ends, therefore, does not permit supply from more than one direction. Should be avoided where possible. In locations where sharp changes in topography occur (hilly or mountainous areas), it is common practice to divide the distribution system into two or more service areas.
Pressure should be great enough to adequately meet consumer and fire-fighting needs. Pressure should not be excessive: Cost consideration Leakage and maintenance increase The capacity is determined on the bases of local water needs plus fire-fighting demand. Pipe sizes should be selected to avoid high velocities: Pipe sizes should selected based on flow velocity of 3-5 fps Where fire-fighting is required, minimum pipe diameter is 6 in.
8
Capacity:
Hydraulic Design
The design flowrate is based on the maximum of the following two rates:
Maximum day demand plus fire demand Maximum hourly rate Distribution system have series of pipes of different diameters. In order to simplify the analysis, skeletonizing is used. Skeletonizing is the replacement of a series of pipes of varying diameters with one equivalent pipe or replacing a system of pipes with one equivalent pipe.
9
Skeletonization
10
Hydraulic Design
Example:
Consider the piping system shown in the figure, replace (a) pipes BC and CD with an equivalent 12-in. pipe and (b) the system from B to D with an equivalent 20-in. pipe.
200 ft - 18 in.
C A B A
500 ft - 16 in.
900 ft - 12 in.
12
13
Hydraulic Design
5. the total head loss for 12-in equivalent pipe at 8 cfs is 45ft/1000ft (from nomograph) 6. head loss BCD = head loss BD, therefore; 6.72ft = Leq * (45/1000) Leq = 6.72 * (1000/45) = 149 ft
b) for pipes in parallel: 1. assume any value of head loss between BD (hL=5 ft) 2. for the equivalent pipe (L = 149 ft), head loss per 1000ft is; hL = (5/149)*1000 = 33.5ft/1000ft Diameter of equivalent pipe = 12-in Qeq = 6.8 cfs (from nomograph)
14
Hydraulic Design
3. for the 900 ft 12-in pipe: hL = (5/900)*1000 = 5.5ft/1000ft Q900 = 2.6 cfs (from nomograph) 4. total flow = 6.9 + 2.6 = 9.4 cfs 5. for Q = 9.4 cfs and 20-in pipe: head loss = 4.8ft/1000ft 5 ft (nomograph) 6. head loss 12-in pipe = head loss 20-in pipe = L * (4.8ft/1000ft) L = 5 * (1000/4.8) = 1042 ft
15
Hydraulic Design
Pipe networks: Pipe networks are composed of a number of constant-diameter
pipe sections containing pumps and fittings.
Node: end of each pipe section. (A, B, C, D, E, F, G, and H) Junction node: points where pipes meet and where flow may be
introduces or withdrawn. (B, C, D, E, F, and G)
Pipe Network
17
Hydraulic Design
Loop equations: Hydraulic performance of pipe networks are based
on mass continuity and energy conservation.
Continuity of mass:
Qin - Qout = Qe (J number of equations) Qin = inflow into node Qout = outflow from node Qe = external flow into the system or withdrawal
Conservation of energy:
hL = Ep (L number of equations) hL = head loss; Ep = pump head For fixed-grade nodes, the following can be written: E = hL - Ep (F-1 equations)
18
Hydraulic Design
Loop equations: (continue) Frictional losses in pipes:
hLP = KP Qn Where; KP = constant incorporating pipe size, its roughness, and units used n = an exponent The Hazen-Williams formula for head loss is given as: hLP = KP Q1.85
Minor losses:
These losses are due fittings, valves, meters, or other insertions that affect the flow. They are expressed as: hLM = KM Q2 Where; KM = minor loss constant
19
Hydraulic Design
Node equations: When considering nodes, the principle relationship used is the
continuity equation: Qin - Qout = Qe
Qe
20
10
Hydraulic Design
Node equations: If pump exist in the line, then junction nodes are specified at the inlet
and outlet.
for continuity: Qab = Qcd {(ha-hb)/Kab}1/n = {(hc-hd)/Kcd}1/n ha - hb = (Kab/Kcd) (hc hd) The head change across pump is: hc hb = P(Q) P(Q) = is the head developed by the pump = (550 hp)/(Q) hp = horsepower, = weight of water, Q = flow
21
Distribution Reservoirs
Definition:
Distribution reservoirs provide service storage to meet the widely fluctuating demands often imposed on the distribution system, to accommodate fire-fighting and emergency requirements, and to equalize operating pressure.
Types of reservoirs: Surface reservoir Usually lined with concrete, gunite, asphalt, or membrane. They may be covered or uncovered, but usually covered to prevent
contamination.
Standpipes or elevated tanks Normally employed where the construction of a surface reservoir Stand pipes are tall cylindrical tanks whose storage volume includes
an upper portion (useful storage) and a lower portion (supporting storage).
22
11
Surface Reservoir
23
Standpipes
24
12
Elevated tanks
25
Distribution Reservoirs
Location Distribution reservoirs should be located strategically for maximum
benefits.
Normally the reservoir should be near the center of use. For large areas, a number of reservoirs may be located at key locations A central location decreases the friction losses by reducing the distance
to the serviced area.
Storage function To provide head required head. To provide excess demand such as:
fire-fighting: should be sufficient to provide flow for 10-12 hours. emergency demands: to sustain the demand during failure of the supply
system and times of maintenance.
13
27
Pumping
Introduction Pumping is an important part of the transportation and distribution
system.
Requirements vary from small units (few gallons per minute) to large
units (several hundred cubic feet per second)
Types of pumps Low-lift pumps: used to lift water from a source to the treatment plant High-service pumps: used to discharge water under pressure to the
distribution system
Booster pumps: used to increase pressure in the distribution system. Recirculation pumps: used within a treatment plant. Well pumps: used to left water from wells.
28
14
Centrifugal pumps
Used to lift and transport water Widely used in water and wastewater applications due to: Simplicity of installation and operation. Compactness. Low cost compared to others. Operate under variety of conditions How do they operate: On the principle of centrifugal force; force of pushing outwards. The impeller driven at high speed throws water into the casing Water is channeled through a nozzle to the discharge piping
29
30
15
31
Centrifugal pumps
Pumping head The pump operates against a certain head called Total Dynamic Head
(TDH).
The difference in elevation between the level of the suction pool and the
pump centerline
16
33
Centrifugal pumps
Power The theoretical horsepower required may be found by using the
following equation: hp = QH/550 Where; Q = discharge, cfs = specific weight of water, 62.4 lb/ft3 H = total dynamic head, ft The actual hp required is obtained by dividing the theoretical hp by the efficiency of the pump.
34
17
Centrifugal pumps
System head
The system head is represented by a plot of TDH vs. discharge for the
system being studied.
The plot is used to help in selecting the pumping unit. The system head curve will vary with flow since HF and HV are both a
function of discharge.
Since the static head HL may vary as a result of fluctuating water levels,
it is necessary to plot system head curves covering the range of variations in static head.
35
36
18
Centrifugal pumps
Pump characteristics Each pump has its own characteristics relative to power requirements,
efficiency, and head developed as a function of rate of flow.
As the flow of the centrifugal pump increases, the head will fall. At maximum efficiency, the discharge is known as normal or rated
discharge.
38
19
39
Centrifugal pumps
Selection of pumping units Normally the engineer is given the system-head characteristics curve
and is required to find a pump or pumps to deliver the required flow.
The system-head curve is plotted with the pump characteristics curve. The operating point is located at the intersection of the system-head
curve and the pump characteristics curve. This point gives the head and flow at which the pump will be operating.
Pumps connected in series; the total head equals the sum of the heads
added by each pump (discharge stay constant).
40
20
41
21