Vendor Name: P&C Tech. Device Name: Motor Management Relay (PAC-M100) Highest DNP Level Supported: For Requests: Level 2 For Responses: Level 2 Device Function: Remote Master Remote
Notable objects, functions, and/or qualifiers supported, in addition to the Highest DNP Levels Supported. (The complete list is described in the attached implementation table): Binary Inputs(Object 1) Binary Input Changes(Object 2) Binary Outputs(Object 10) Binary Counters(Object 20) Analog Inputs(Object 30) Maximum Data Link Frame Size (octets): Transmitted: 292 Received: 292 Maximum Application Fragment Size (octets): Transmitted: 240 Received: 2048
Maximum Data Link Re-tries: None Fixed Configurable, range 0 to 5 Requires Data Link Layer Confirmation: Never Always Sometimes Configurable Requires Application Layer Confirmation: Never (recommended for master devices) Always (not recommended) When reporting Event Data
Timeouts while waiting for: Data Link Confirm: None Fixed at___ Variable
Configurable, range 0.001 s to 65 s Complete Appl. Fragment: Application Confirm: Complete Appl. Response: None None None Fixed at___ Fixed at 10 s Fixed at___ Variable Variable Variable Configurable Configurable Configurable
Others: Transmission Delay: Inter-character Timeout: Need Time Delay: Select/Operate Arm Timeout: Binary input change scanning period: Default Status Object/Variation: No Status objects reported Configurable (attach explanation) Default Static Object_____________ Default Static Variation __________ Default Event Object_____________ Default Event Variation __________ Point-by-point list attached Default Counter Object/Variation: No Counters reported Configurable (attach explanation) Default Static Object____________ Default Static Variation__________ Default Event Object____________ Default Event Variation _________ Point-by-point list attached configurable, range 0 to 65000 ms 50 ms configurable, range 0 to 65000 min(0: disable) configurable, range 1 to 65000 ms 50 ms Default Analog Object/Variation: No Analog objects reported Configurable (attach explanation) Default Static Object______________ Default Static Variation ___________ Default Event Object______________ Default Event Variation ___________ Point-by-point list attached Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value _________ Point-by-point list attached
Default Frozen Counter Object/Variation: No Frozen Counters reported Configurable (attach explanation) Default Static Object____________ Default Static Variation__________ Default Event Object____________ Default Event Variation __________ Point-by-point list attached Analog Deadbands: Fixed Configurable: Per Point Per Analog Type Global
Counters frozen by means of: Remote device time based Fixed time Configurable; range _____ to _____ Master Request (see implementation table
Configuring Analog Deadbands: Not Applicable Configuration Software Using Object 34 from the master station Both configuration software and Object 34
Are the updated deadband values preserved through a device reset: YES NO The number of multiple objects allowed in a single read request message: Number of multiple objects allowed: 16 Ability to DISABLE/ENABLE DNP database points: Not Applicable Per point Per object Global Never used Reason for setting: system error IIN 1-6 Device Trouble Bit
Sends/Executes Digital Control Operations: SELECT/OPERATE DIRECT OPERATE DIRECT OPERATE NO ACK Never Never Never Always Always Always Sometimes Sometimes Sometimes Configurable Configurable Configurable
Count > 1 Pulse On Pulse Off Latch On Latch Off Trip/Close Raise/Lower
Never Never
Always Always
Sometimes Sometimes
Configurable Configurable
Sends Unsolicited Responses: Never Configurable (attach explanation) Only certain objects Sometimes (attach explanation) Assign Class Function code supported: NO YES Per Object Per Point Configurable
Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change * No other options permitted. Is the Event Buffer size configurable: NO YES: fixed size: 255(BI Change Only) range: _________to_________
Supports Collision Avoidance: Never Always (attach explanation) Configurable (attach explanation) Source Address Filtering: Not Supported Configurable Supports Multi-drop communications: Sends Multi-Fragment Responses: Yes Yes No No
IMPLEMENTATION TABLE
DNP OBJECT & VARIATION OBJ VAR Description REQUEST Func Codes(dec) Qual Codes (hex) 00,01(start-stop) 1 (read) 0 Binary Input - All Variations 06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) Binary Input 1 1 (default) 07,08 (limited qty) 00,01(start-stop) 1(read) 2 Binary Input with Status 06 (no range,or all) 07,08 (limited qty) 1(read) 0 Binary Input Change - All Variations 07,08 (limited qty) 1(read) 1 2 07,08 (limited qty) 1(read) Binary Input Change with Time 2 (default) 07,08 (limited qty) 1(read) 0 10 1(read) Binary Output Status 2 (default) 07,08 (limited qty) 3(select) 4(operate) 12 1 Control Relay Output Block 5(direct op) 6(direct op noack) 00,01(start-stop) 1(read) 20 0 Binary Counter- All Variations 06 (no range,or all) 07,08 (limited qty) 17,28 (index) 129 (response) echo of request 06 (no range,or all) 129 (response) 17,28 (index) 00,01(start-stop) Binary Output Status-All Variation 00,01(start-stop) 06 (no range,or all) 07,08 (limited qty) 06 (no range,or all) 129 (response) 17,28 (index) 00,01(start-stop) Binary Input Change without Time 00,01(start-stop) 06 (no range,or all) 129 (response) 17,28 (index) 06 (no range,or all) 129 (response) 00,01(start-stop) 1(read) 06 (no range,or all) 129 (response) 00,01(start-stop) RESPONSE Func Codes(dec) Qual Codes(hex)
129 (response)
00,01(start-stop)
129 (response)
00,01(start-stop)
1(read) 06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) 1(read) 129 (response) 00,01(start-stop)
129 (response)
00,01(start-stop)
1(read) 06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) 1(read) 129 (response) 00,01(start-stop)
129 (response)
00,01(start-stop)
1(read) 07 (limited qty=1) 2(write) 129 (response) 1(read) 06 (no range,or all) 07,08 (limited qty) 1(read) 06 (no range,or all) 07,08 (limited qty) 1(read) 06 (no range,or all) 07,08 (limited qty) 1(read) 06 (no range,or all) 07,08 (limited qty) 07 (limited qty=1) 00(start-stop)
60
Class 0 Data
Class 1 Data
Class 2 Data
Class 3 Data
80
Internal Indications
----
60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87
46_2 Operated 46T Operated 46U Operated 59_1 Phase A Operated 59_1 Phase B Operated 59_1 Phase C Operated 59_2 Phase A Operated 59_2 Phase B Operated 59_2 Phase C Operated 27_1 Phase A Operated 27_1 Phase B Operated 27_1 Phase C Operated 27_2 Phase A Operated 27_2 Phase B Operated 27_2 Phase C Operated 59G_1 Operated 59G_2 Operated 47 Operated 50BF Operated 67 Phase A Operated 67 Phase B Operated 67 Phase C Operated 67N Operated Cold Load Operated Inrush Detection Operated 48 Operated 51L Operated 66/68 Operated
01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Binary Output
Point Description Index Open Breaker 1 0 Close Breaker 1 Open Breaker 2 1 Close Breaker 2 2 3 4 5 6 7 8 9 10 11
Object/Variation
Control Code
Count
Pulse On,Trip 02/01,02/02,12/01 Pulse On,Close Pulse On,Trip 02/01,02/02,12/01 Pulse On,Close 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close
1 1 1 1 1 1 1 1 1 1 1 1 1 1
Reset Annunciator Clear Event Data Clear Waveform Data Setting Group 1 Active Setting Group 2 Active Setting Group 3 Active Setting Group 4 Active Clear Energy Data Clear Thermal Data Reset MIN/MAX
Binary Counter
Point Description Index 0 1 2 3 4 5 6 7 8
# of Available Events # of Available Waveforms Break1 Trip Counter Break2 Trip Counter kW-Hours (import) kW-Hours (export) kVAR-Hours (+) kVAR-Hours (-) kVA-Hours
----------
**(Max 1024) **(Max 8) HFFFF HFFFF HFFFFFFFF HFFFFFFFF HFFFFFFFF HFFFFFFFF HFFFFFFFF
Analog Input
Point Description Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Line to line AB Voltage Magnitude. Line to line BC Voltage Magnitude. Line to line CA Voltage Magnitude. Phase A Voltage Magnitude. Phase B Voltage Magnitude. Phase C Voltage Magnitude. Phase N Voltage Magnitude. 3-Phase Average Voltage Magnitude Phase A Current Magnitude. Phase B Current Magnitude. Phase C Current Magnitude. Phase N Current Magnitude. 3-Phase Average Current Magnitude. Is Magnitude Positive Sequence Voltage Magnitude. Negative Sequence Voltage Magnitude. Zero Sequence Voltage Magnitude. Positive Sequence Current Magnitude. Negative Sequence Current Magnitude. Zero Sequence Current Magnitude. Phase A Watts Phase B Watts Phase C Watts 3-Phase Watts Phase A Vars Phase B Vars Phase C Vars 3-Phase Vars Phase A VA Phase B VA Phase C VA 3-Phase VA 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 --------------------------------0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~65.535 0.000~65.535 0.000~65.535 0.000~65.535 0.000~65.535 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~65.535 0.000~65.535 0.000~65.535 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 0.00~655.35 0.00~655.35 0.00~655.35 0.00~655.35 kV kV kV kV kV kV kV kV kA kA kA kA kA mA KV KV KV KA KA KA MW MW MW MW Mvar Mvar Mvar Mvar MVA MVA MVA MVA Object/Variation Class Range Unit
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Phase A Power Factor Phase B Power Factor Phase C Power Factor 3-Phase Power Factor Frequency Phase A Voltage THD Phase B Voltage THD Phase C Voltage THD Phase A Curernt THD Phase B Current THD Phase C Current THD Thermal Remain start monitoring time Remain cold start number Remain hot start number
30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04
----------------
-1.00~1.00 -1.00~1.00 -1.00~1.00 -1.00~1.00 0.00~655.35 0.0~100.0 0.0~100.0 0.0~100.0 0.0~100.0 0.0~100.0 0.0~100.0 0.0~250.0 0.0~120.0 1~5 0~5 Hz % % % % % % % min