Pac m100 DNP Profile 20091012

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

DNP3

DEVICE PROFILE DOCUMENT

Vendor Name: P&C Tech. Device Name: Motor Management Relay (PAC-M100) Highest DNP Level Supported: For Requests: Level 2 For Responses: Level 2 Device Function: Remote Master Remote

Notable objects, functions, and/or qualifiers supported, in addition to the Highest DNP Levels Supported. (The complete list is described in the attached implementation table): Binary Inputs(Object 1) Binary Input Changes(Object 2) Binary Outputs(Object 10) Binary Counters(Object 20) Analog Inputs(Object 30) Maximum Data Link Frame Size (octets): Transmitted: 292 Received: 292 Maximum Application Fragment Size (octets): Transmitted: 240 Received: 2048

Maximum Data Link Re-tries: None Fixed Configurable, range 0 to 5 Requires Data Link Layer Confirmation: Never Always Sometimes Configurable Requires Application Layer Confirmation: Never (recommended for master devices) Always (not recommended) When reporting Event Data

Maximum Application Layer Re-tries: None Configurable

When sending multi-frame fragment responses Sometimes Configurable

Timeouts while waiting for: Data Link Confirm: None Fixed at___ Variable

Configurable, range 0.001 s to 65 s Complete Appl. Fragment: Application Confirm: Complete Appl. Response: None None None Fixed at___ Fixed at 10 s Fixed at___ Variable Variable Variable Configurable Configurable Configurable

Others: Transmission Delay: Inter-character Timeout: Need Time Delay: Select/Operate Arm Timeout: Binary input change scanning period: Default Status Object/Variation: No Status objects reported Configurable (attach explanation) Default Static Object_____________ Default Static Variation __________ Default Event Object_____________ Default Event Variation __________ Point-by-point list attached Default Counter Object/Variation: No Counters reported Configurable (attach explanation) Default Static Object____________ Default Static Variation__________ Default Event Object____________ Default Event Variation _________ Point-by-point list attached configurable, range 0 to 65000 ms 50 ms configurable, range 0 to 65000 min(0: disable) configurable, range 1 to 65000 ms 50 ms Default Analog Object/Variation: No Analog objects reported Configurable (attach explanation) Default Static Object______________ Default Static Variation ___________ Default Event Object______________ Default Event Variation ___________ Point-by-point list attached Counters Roll Over at: No Counters Reported Configurable (attach explanation) 16 Bits 32 Bits Other Value _________ Point-by-point list attached

Default Frozen Counter Object/Variation: No Frozen Counters reported Configurable (attach explanation) Default Static Object____________ Default Static Variation__________ Default Event Object____________ Default Event Variation __________ Point-by-point list attached Analog Deadbands: Fixed Configurable: Per Point Per Analog Type Global

Counters frozen by means of: Remote device time based Fixed time Configurable; range _____ to _____ Master Request (see implementation table

for supported function codes) Both

Configuring Analog Deadbands: Not Applicable Configuration Software Using Object 34 from the master station Both configuration software and Object 34

Are the updated deadband values preserved through a device reset: YES NO The number of multiple objects allowed in a single read request message: Number of multiple objects allowed: 16 Ability to DISABLE/ENABLE DNP database points: Not Applicable Per point Per object Global Never used Reason for setting: system error IIN 1-6 Device Trouble Bit

Sends/Executes Digital Control Operations: SELECT/OPERATE DIRECT OPERATE DIRECT OPERATE NO ACK Never Never Never Always Always Always Sometimes Sometimes Sometimes Configurable Configurable Configurable

Count > 1 Pulse On Pulse Off Latch On Latch Off Trip/Close Raise/Lower

Never Never Never Never Never Never Never

Always Always Always Always Always Always Always

Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes Sometimes

Configurable Configurable Configurable Configurable Configurable Configurable Configurable

Queue Clear Queue

Never Never

Always Always

Sometimes Sometimes

Configurable Configurable

Sends Unsolicited Responses: Never Configurable (attach explanation) Only certain objects Sometimes (attach explanation) Assign Class Function code supported: NO YES Per Object Per Point Configurable

Sends Static Data in Unsolicited Responses: Never When Device Restarts When Status Flags Change * No other options permitted. Is the Event Buffer size configurable: NO YES: fixed size: 255(BI Change Only) range: _________to_________

Configurable Per Class buffer: NO YES

Supports Collision Avoidance: Never Always (attach explanation) Configurable (attach explanation) Source Address Filtering: Not Supported Configurable Supports Multi-drop communications: Sends Multi-Fragment Responses: Yes Yes No No

IMPLEMENTATION TABLE
DNP OBJECT & VARIATION OBJ VAR Description REQUEST Func Codes(dec) Qual Codes (hex) 00,01(start-stop) 1 (read) 0 Binary Input - All Variations 06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) Binary Input 1 1 (default) 07,08 (limited qty) 00,01(start-stop) 1(read) 2 Binary Input with Status 06 (no range,or all) 07,08 (limited qty) 1(read) 0 Binary Input Change - All Variations 07,08 (limited qty) 1(read) 1 2 07,08 (limited qty) 1(read) Binary Input Change with Time 2 (default) 07,08 (limited qty) 1(read) 0 10 1(read) Binary Output Status 2 (default) 07,08 (limited qty) 3(select) 4(operate) 12 1 Control Relay Output Block 5(direct op) 6(direct op noack) 00,01(start-stop) 1(read) 20 0 Binary Counter- All Variations 06 (no range,or all) 07,08 (limited qty) 17,28 (index) 129 (response) echo of request 06 (no range,or all) 129 (response) 17,28 (index) 00,01(start-stop) Binary Output Status-All Variation 00,01(start-stop) 06 (no range,or all) 07,08 (limited qty) 06 (no range,or all) 129 (response) 17,28 (index) 00,01(start-stop) Binary Input Change without Time 00,01(start-stop) 06 (no range,or all) 129 (response) 17,28 (index) 06 (no range,or all) 129 (response) 00,01(start-stop) 1(read) 06 (no range,or all) 129 (response) 00,01(start-stop) RESPONSE Func Codes(dec) Qual Codes(hex)

DNP OBJECT & VARIATION OBJ VAR Description

REQUEST Func Codes(dec) Qual Codes (hex) 00,01(start-stop) 1(read)

RESPONSE Func Codes(dec) Qual Codes(hex)

32-Bit Binary Counter

06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) 1(read)

129 (response)

00,01(start-stop)

16-Bit Binary Counter

06 (no range,or all) 07,08 (limited qty) 00,01(start-stop)

129 (response)

00,01(start-stop)

32-Bit Binary Counter without Flag 5 (default)

1(read) 06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) 1(read) 129 (response) 00,01(start-stop)

16-Bit Binary Counter without Flag

06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) 1(read)

129 (response)

00,01(start-stop)

Analog Input- All Variations

06 (no range,or all) 07,08 (limited qty) 00,01(start-stop)

16-Bit Analog Input 30 2 (default)

1(read) 06 (no range,or all) 07,08 (limited qty) 00,01(start-stop) 1(read) 129 (response) 00,01(start-stop)

16-Bit Analog Input without Time

06 (no range,or all) 07,08 (limited qty)

129 (response)

00,01(start-stop)

Time and Date 50 1 (default) 52 2 Time Delay Fine

1(read) 07 (limited qty=1) 2(write) 129 (response) 1(read) 06 (no range,or all) 07,08 (limited qty) 1(read) 06 (no range,or all) 07,08 (limited qty) 1(read) 06 (no range,or all) 07,08 (limited qty) 1(read) 06 (no range,or all) 07,08 (limited qty) 07 (limited qty=1) 00(start-stop)

60

Class 0 Data

Class 1 Data

Class 2 Data

Class 3 Data

DNP OBJECT & VARIATION OBJ VAR Description

REQUEST Func Codes(dec) Qual Codes (hex) 00(start-stop)

RESPONSE Func Codes(dec) Qual Codes(hex)

80

Internal Indications

2(write) (index must=7)

----

No Object(function code only) No Object(function code only) No Object(function code only)

13(cold restart) 14(warm restart) 23(delay meas.)

DNP Point LISTS


Binary Input
Point Description Index 0 1 2 3 ~18 19 ~ 34 35 ~ 38 39 40 ~ 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 System Reset System Warm Restart System Error Contact Input 1 Operated 01/01,01/02,02/01,02/02 ~ Contact Input 16 Operated Contact Output 1 Operated 01/01,01/02,02/01,02/02 ~ Contact Output 16 Operated Setting Group 1 Active 01/01,01/02,02/01,02/02 ~ Setting Group 4 Active Breaker Local / Remote Breaker1 Status Changed 01/01,01/02,02/01,02/02 ~ Breaker2 Status Changed 50_1 Phase A Operated 50_1 Phase B Operated 50_1 Phase C Operated 50_2 Phase A Operated 50_2 Phase B Operated 50_2 Phase C Operated 51 Phase A Operated 51 Phase B Operated 51 Phase C Operated 50N_1 Operated 50N_2 Operated 51N Operated 67Ns Operated 49 Operated 37 Phase A Operated 37 Phase B Operated 37 Phase C Operated 46_1 Operated 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 01/01,01/02,02/01,02/02 1 1 1 1 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 1 1 1 Object/Variation Class

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87

46_2 Operated 46T Operated 46U Operated 59_1 Phase A Operated 59_1 Phase B Operated 59_1 Phase C Operated 59_2 Phase A Operated 59_2 Phase B Operated 59_2 Phase C Operated 27_1 Phase A Operated 27_1 Phase B Operated 27_1 Phase C Operated 27_2 Phase A Operated 27_2 Phase B Operated 27_2 Phase C Operated 59G_1 Operated 59G_2 Operated 47 Operated 50BF Operated 67 Phase A Operated 67 Phase B Operated 67 Phase C Operated 67N Operated Cold Load Operated Inrush Detection Operated 48 Operated 51L Operated 66/68 Operated

01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02 01/01,01/02,02/01,02/02

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

Binary Output
Point Description Index Open Breaker 1 0 Close Breaker 1 Open Breaker 2 1 Close Breaker 2 2 3 4 5 6 7 8 9 10 11

*.Count Field : No Action(0),Execute Once(>0) **.On/Off Time Field ignore

Object/Variation

Control Code

Count

Pulse On,Trip 02/01,02/02,12/01 Pulse On,Close Pulse On,Trip 02/01,02/02,12/01 Pulse On,Close 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 02/01,02/02,12/01 Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close Pulse On,Close

1 1 1 1 1 1 1 1 1 1 1 1 1 1

Reset Annunciator Clear Event Data Clear Waveform Data Setting Group 1 Active Setting Group 2 Active Setting Group 3 Active Setting Group 4 Active Clear Energy Data Clear Thermal Data Reset MIN/MAX

Binary Counter
Point Description Index 0 1 2 3 4 5 6 7 8

*.Counter freeze command has no meaning . Object/Variation Class RollOver

# of Available Events # of Available Waveforms Break1 Trip Counter Break2 Trip Counter kW-Hours (import) kW-Hours (export) kVAR-Hours (+) kVAR-Hours (-) kVA-Hours

20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/06 20/02,20/05 20/02,20/05 20/02,20/05 20/02,20/05 20/02,20/05

----------

**(Max 1024) **(Max 8) HFFFF HFFFF HFFFFFFFF HFFFFFFFF HFFFFFFFF HFFFFFFFF HFFFFFFFF

Analog Input
Point Description Index 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Line to line AB Voltage Magnitude. Line to line BC Voltage Magnitude. Line to line CA Voltage Magnitude. Phase A Voltage Magnitude. Phase B Voltage Magnitude. Phase C Voltage Magnitude. Phase N Voltage Magnitude. 3-Phase Average Voltage Magnitude Phase A Current Magnitude. Phase B Current Magnitude. Phase C Current Magnitude. Phase N Current Magnitude. 3-Phase Average Current Magnitude. Is Magnitude Positive Sequence Voltage Magnitude. Negative Sequence Voltage Magnitude. Zero Sequence Voltage Magnitude. Positive Sequence Current Magnitude. Negative Sequence Current Magnitude. Zero Sequence Current Magnitude. Phase A Watts Phase B Watts Phase C Watts 3-Phase Watts Phase A Vars Phase B Vars Phase C Vars 3-Phase Vars Phase A VA Phase B VA Phase C VA 3-Phase VA 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 --------------------------------0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~65.535 0.000~65.535 0.000~65.535 0.000~65.535 0.000~65.535 0.000~655.35 0.000~655.35 0.000~655.35 0.000~655.35 0.000~65.535 0.000~65.535 0.000~65.535 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 -327.67~327.67 0.00~655.35 0.00~655.35 0.00~655.35 0.00~655.35 kV kV kV kV kV kV kV kV kA kA kA kA kA mA KV KV KV KA KA KA MW MW MW MW Mvar Mvar Mvar Mvar MVA MVA MVA MVA Object/Variation Class Range Unit

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46

Phase A Power Factor Phase B Power Factor Phase C Power Factor 3-Phase Power Factor Frequency Phase A Voltage THD Phase B Voltage THD Phase C Voltage THD Phase A Curernt THD Phase B Current THD Phase C Current THD Thermal Remain start monitoring time Remain cold start number Remain hot start number

30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04 30/02,30/04

----------------

-1.00~1.00 -1.00~1.00 -1.00~1.00 -1.00~1.00 0.00~655.35 0.0~100.0 0.0~100.0 0.0~100.0 0.0~100.0 0.0~100.0 0.0~100.0 0.0~250.0 0.0~120.0 1~5 0~5 Hz % % % % % % % min