Cover

Documentation of Production Processes with WinCC flexible


WinCC flexible 2008 SP1 Application Description June 2010

Applications & Tools


Answers for industry.

Industry Automation and Drives Technologies Service & Support Portal This article is taken from the Service Portal of Siemens AG, Industry Automation and Drives Technologies. The following link takes you directly to the download page of this document. http://support.automation.siemens.com/WW/view/en/42931547

If you have any questions regarding this document, please send us an e-mail to the following address: online-support.automation@siemens.com

Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

Automation Task

1 2 3 4 5 6 7

Automation Solution Function Mechanisms of this Application

Startup of the Application

Documentation of Production Processes

Operating the Application

Links & Literature

History
Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

Warranty and Liability

Warranty and Liability


Note The application examples are not binding and do not claim to be complete regarding configuration, equipment and any eventuality. The application examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. These application examples do not relieve you of the responsibility to use sound practices in application, installation, operation and maintenance. When using these Application Examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Application Examples at any time without prior notice. If there are any deviations between the recommendations provided in this application example and other Siemens publications e.g. Catalogs the contents of the other documents have priority.

We accept no liability for information contained in this document. Any claims against us based on whatever legal reason resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (Produkthaftungsgesetz), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (wesentliche Vertragspflichten). However, claims arising from a breach of a condition which goes to the root of the contract shall be limited to the foreseeable damage which is intrinsic to the contract, unless caused by intent or gross negligence or based on mandatory liability for injury of life, body or health. The above provisions do not imply a change in the burden of proof to your detriment. It is not permissible to transfer or copy these Application Examples or excerpts thereof without express authorization from Siemens Industry Sector.

Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

Table of Contents

Table of Contents
Warranty and Liability ................................................................................................. 4 1 Automation Task................................................................................................ 6 1.1 1.2 1.3 2 Introduction........................................................................................... 6 Overview of the automation problem ................................................... 7 Description of the automation task....................................................... 7

Automation Solution ......................................................................................... 8 2.1 2.2 2.2.1 2.2.2 2.3 Overview of the overall solution ........................................................... 8 Description of the core functionality ..................................................... 9 Overview and description of the user interface.................................. 11 Process sequence of main functionality............................................. 13 Hardware and software components used......................................... 14

Function Mechanisms of this Application .................................................... 16 3.1 3.2 3.3 3.3.1 3.4 3.5 3.6 3.7 3.8 3.8.1 3.8.2 3.9 General overview ............................................................................... 16 Functionality of the screens ............................................................... 17 Functionality of the archives............................................................... 19 Notes on the archives......................................................................... 19 Functionality of the scripts.................................................................. 20 Functionality of the audit .................................................................... 23 Functionality of the messages............................................................ 24 Functionality of the user administration.............................................. 24 Functionality of the Excel templates................................................... 25 Adjusting the PharmaBatchReport.xls file ....................................... 26 Using the Excel templates at Excel 2007 ........................................ 28 Archived files on the memory card..................................................... 28

Copyright Siemens AG 2010 All rights reserved

4 5

Startup of the Application............................................................................... 29 Operating the Application............................................................................... 31 5.1 5.2 Operating the HMI configuration ........................................................ 31 Operating the EXCEL templates ........................................................ 37

Links & Literature ............................................................................................ 40 6.1 6.2 Literature ............................................................................................ 40 Internet Links...................................................................................... 40

History............................................................................................................... 41

Documentation of Production Processes V1.0, Entry ID: 42931547

1 Automation Task 1.1 Introduction

1
1.1

Automation Task
Introduction
During the every day production process various production processes are started and terminated via the HMI operator panel. This includes: general operator actions adjusting of production parameters output of process values output of process alarms

For a number of operator actions it is difficult in retrospect to assign individual operator actions and alarms to a certain process/batch. The application is used to assign previously described points specifically to one batch in form of a batch report and hence document the single process. A batch report (batch log) is required in many areas within industrial production, especially in the pharmaceutical, food and beverage industry.
Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

1 Automation Task 1.2 Overview of the automation problem

1.2

Overview of the automation problem


The following figure gives an overview of the automation task.

Figure 1-1

Logging of user actions

Logging of alarms and process values

Production process

Archiving
Copyright Siemens AG 2010 All rights reserved

Saving and evaluating the data on the PC via MS-Excel functions

1.3

Description of the automation task


When starting a production process (batch) via the operator panel, the following points are stored on an operator panel: operator actions at the operator panel configuration changes of process values error messages current process values

The storage location for the files can be defined variably here. Each batch receives a unique batch ID and all data associated with the batch process are grouped in a folder. The files come in csv-format so they can be evaluated and edited via standard tools. Furthermore, there is the option to copy the entire folder content of a batch process on a PC and group it to a batch report via MS-Excel functionalities.

Documentation of Production Processes V1.0, Entry ID: 42931547

2 Automation Solution 2.1 Overview of the overall solution

2
2.1
Layout

Automation Solution
Overview of the overall solution
The following figure shows a layout of the most important components of the solution:
Figure 2-1

PC station Operator panel

Copyright Siemens AG 2010 All rights reserved

Memory card Ethernet connection

Operator panel: MP 277 or MP 377 Memory card Audit option MS-Excel Ethernet interface

PC station:

All process values and alarms are simulated on the operator panel via script or are given manually via the operator panel. Software: WinCC flexible 2008 SP1 MS Excel 2003

Topics not covered by this application This application does not contain a description on the WinCC flexible 2008 software for creating an Ethernet connection between an operator panel and a PC station on VBS / VBA-Script

Basic knowledge of this topic is assumed or can be read up in the respective FAQs and manuals (see chapter 6 Links & Literature).

Documentation of Production Processes V1.0, Entry ID: 42931547

2 Automation Solution 2.2 Description of the core functionality

2.2

Description of the core functionality


The core functionality is the recording of process values and user actions occurring within one batch process. Furthermore, additional data such as context data and actual values are stored. The data is secured on a memory card and can subsequently be transferred to a PC. The attached Excel file (with macro) PharmaBatchReport.xls creates one report file from the csv-files generated by the operator panel which lists all values in a structured format. So at the end there is one report file available for each batch for documentation purposes. Example of context data: Batch ID Job number Job name

Figure 2-2
Copyright Siemens AG 2010 All rights reserved

t0 Audit Trail Data Log Alarms Log context data actual values Batch 1
Excel + Macro

tn

Batch 2
Excel + Macro

Batch n
Excel + Macro

Batch Report for batch 1

Batch Report for batch 1

Batch Report for batch n

Note

The example project on hand can only serve as a template since the requirements are normally very plant specific. The example application can be expanded and adjusted at will.

Documentation of Production Processes V1.0, Entry ID: 42931547

2 Automation Solution 2.2 Description of the core functionality Audit (regulated project) Via the WinCC flexible Audit option the user actions and system processes are recorded. Depending on the configuration, audit-relevant processes are recorded. Detailed information on the Audit topic is available in the Online help of WinCC flexible. The processes which have been realized audit-relevant are given in the attached project.

Scripts The main functions are realized with scripts. A detailed description is available in chapter 3.4 Functionality of the scripts. With the various scripts, tags are archived, data copied to the PC and read. You can adjust the scripts to your respective requirements.

Copyright Siemens AG 2010 All rights reserved

10

Documentation of Production Processes V1.0, Entry ID: 42931547

2 Automation Solution 2.2 Description of the core functionality

2.2.1

Overview and description of the user interface


A brief description of the configured screen is given below

Table 2-1 No. 1. Description 01_Start screen: Batch Report Demonstration For demonstration purposes two processes can be started via the screen. Each production step is selected via the respective button. Prior to starting a process a respective batch ID and batch name must be assigned. Furthermore, the current state of 20 tags is graphically displayed. 2.
Copyright Siemens AG 2010 All rights reserved

Screen

02_Messages screen: Alarms Two alarm displays are illustrated in this screen. The first alarm display shows pending and unacknowledged alarms. The second alarm display shows alarms from the alarm log.

3.

03_TagLogging screen: Trend display In this screen the values of two tags are represented in a trend display.

Documentation of Production Processes V1.0, Entry ID: 42931547

11

2 Automation Solution 2.2 Description of the core functionality


No. 4. Description 04_Config screen: Configuration Various functions can be performed via the screen. Specifying the storage path on the memory card for the Batch data on the operator panel Specifying the storage path for the Batch data on the PC Copying Batch data from the operator panel to the PC Furthermore, pending alarms are displayed via the Alarms display. Screen

Copyright Siemens AG 2010 All rights reserved

12

Documentation of Production Processes V1.0, Entry ID: 42931547

2 Automation Solution 2.2 Description of the core functionality

2.2.2

Process sequence of main functionality


Start screen Batch Report Demonstration Starting the process via the Preparation button

no

User logged on?

no

Batch ID and batch name assigned?

Copyright Siemens AG 2010 All rights reserved

Start Batch

Start Cleaning (I or II)

Start Sterilization

Start Filling (50 / 100ml)

Terminate/cancel Batch

Note

A controller is not necessary for this example. All values are simulated via scripts.

Documentation of Production Processes V1.0, Entry ID: 42931547

13

2 Automation Solution 2.3 Hardware and software components used

2.3

Hardware and software components used


The application was created with the following components:

Hardware components
Table 2-2 Component MP 377 Touch 12 SD Card 256 MByte Qty. 1 1 MLFB/order number 6AV6 644-0AA01-2AX0 6AV6 671-8XB10-0AX0 Note Alternatively MP 277 see FAQ entry:

http://support.autom ation.siemens.com/ WW/view/en/21847 868


Standard PC 1

Standard software components


Table 2-3 Component
Copyright Siemens AG 2010 All rights reserved

Qty. 1

MLFB/order number 6AV6612-0AA51-3CA5

Note Alternatively, WinCC flexible 2008 Advanced can be used (6AV66130AA51-3CA5) The SP1 is available as download.

WinCC flexible 2008 Standard

WinCC flexible 2008 SP1

Siehe Customer Support Seiten

http://support.automation .siemens.com/
WinCC flexible /Audit for Panels 1 6AV6618-7HB01-3AB0

14

Documentation of Production Processes V1.0, Entry ID: 42931547

2 Automation Solution 2.3 Hardware and software components used

Example files and projects The following table contains all files and projects used in this example.
Table 2-4 Component 42931547_WinCC_flexible_Batch_Repor t_CODE_V10.zip 42931547_WinCC_flexible_Batch_Repor t_DOKU_V10_d.pdf 42931547_Template_Batch_Report_v10. zip Note HMI configuration for MP 377 Touch This document The zip.-file contains two folders: Template_BatchReport_Excel_V1.2 1) Sample_Data_BatchReport 2)

1)

Folder Template_BatchReport_Excel_V1.2: HmiCheckLogIntegrity.exe PharmaBatchReport.xls ReportTemplate.xls

The folder contains files required for implementing a Batch Report.


Copyright Siemens AG 2010 All rights reserved

A description of the files is available in chapter 3.8.


2)

Folder Sample_Data_BatchReport:

The folder contains the process files of two batches including the report file. The application of the table is described in chapter 5.2. The tables serve as example to learn about the functionality of the application.

Documentation of Production Processes V1.0, Entry ID: 42931547

15

3 Function Mechanisms of this Application 3.1 General overview

3
3.1
Figure 3-1

Function Mechanisms of this Application


The individual pictures, used scripts and functions are described in greater detail in the following sub-chapters.

General overview

Copyright Siemens AG 2010 All rights reserved

The following objects and functions are used in the configuration. Screens Archives Scripts Audit option Alarms User administration

16

Documentation of Production Processes V1.0, Entry ID: 42931547

3 Function Mechanisms of this Application 3.2 Functionality of the screens

3.2
Table 3-1 No. 1.

Functionality of the screens


Description Screen

Values are assigned to tags and alarms are triggered via a simulation. For this purpose the system function SimulateTag is used for the screen design. The following tags are simulated:

Temperature (Batch_Report\Temperature) Quantity (Batch_Report\Quantity) Alarms generated (Batch_Report\AlarmVar1)

Please generally view the properties of the individual objects in the screens. They can only be listed rudimentary in this document. 2. 01_Start screen: This screen serves for simulating a batch process. For the screen design a script is executed which assigns values to the storage location. Similar to a step chain the individual functions can only be selected if appropriate frame conditions apply. You will receive a warning message if a condition is not fulfilled: Pressing the button always enables the subsequent step. Each operation of the buttons is archived in the Audit Trail file. Via the buttons the scripts are called through which the batch process is archived. 02_Messages screen: The displayed error alarms are generated is the SimulateTag system function. Values from 0 to 8 are assigned to the AlarmVar1 tags in a cycle of 10 seconds and the configured bit alarm is created this way.

Copyright Siemens AG 2010 All rights reserved

3.

Documentation of Production Processes V1.0, Entry ID: 42931547

17

3 Function Mechanisms of this Application 3.2 Functionality of the screens


No. 4. Description 03_TagLogging screen: The displayed trend values are generated via the SimulateTag system function. Values from 0 to 100 are assigned to the Temperature tag in a 1 second cycle. Values from 20 to 80 are assigned to the Quantity tag in a 2 seconds cycle. Screen

5.

Copyright Siemens AG 2010 All rights reserved

04_Config screen: Values are assigned to the storage paths when starting the panel via the S5_SetDefaultPath script. The storage path can also be assigned manually. The data is copied from the memory card to the PC through the S1_Copy_files_to_PC script via the Export zum PC button.

18

Documentation of Production Processes V1.0, Entry ID: 42931547

3 Function Mechanisms of this Application 3.3 Functionality of the archives

3.3

Functionality of the archives


In the application the following archives are used: Tag archives Alarm logs Audit trail

Via the archives the respective tags, alarms and operations are recorded. The archived tags are given in the attached project. Please use the cross references list:

3.3.1

Notes on the archives


When using archives, the following must be observed. For the archives to be displayed correctly and evaluated on your PC the region and language options of the operator panel must match those of your PC. Check the used decimal separators and list separators

Language settings of the operator panel


Copyright Siemens AG 2010 All rights reserved

1. Open the Control Panel. 2. Open the Regional Settings. 3. In the Regional Settings tab you can select various countries and adopt their country-specific settings. In the Number tab you can manually adjust country-specific settings Language settings PC (operating system Windows XP) 1. Open the Control Panel. 2. Open the Regional and Language Settings. 3. In the Regional Options tab you can select various Countries and adopt their country-specific settings. Via the Customize... button you can manually adjust country-specific settings S3_SaveBatchData script Please look at the information on the topic Language-specific settings in script S3_SaveBatchData.

Documentation of Production Processes V1.0, Entry ID: 42931547

19

3 Function Mechanisms of this Application 3.4 Functionality of the scripts

3.4

Functionality of the scripts


With this script the csv-files generated on the operating device are copied to a PC. Subsequently the data on the memory card are deleted (no double data management).

S1_Copy_files_to_PC

S2_PrepBatchConditions This script creates a temp folder on the memory card. In this temp folder the audit trail file is temporarily stored first. Through copying the audit trail file is marked with a time stamp. The time stamp consists of data, time and the device name of the operator panel and is automatically assigned by the system. Example: Original Temp folder AuditTrail0.csv AuditTrail0_20100510_083709_HMI_Demo_Batch.csv

In the audit trail file the user actions and system functions related to the current batch process are logged.
Copyright Siemens AG 2010 All rights reserved

S3_SaveBatchData When terminating the batch program the script S3_SaveBatchData is executed. Via the script the current values of the Injection_1 to Injection_160 tag and the context data are stored in a CSV-file (BatchData.csv). The script copies all batch files into a previously defined folder on the memory card (storage path and folder are assigned via a script). The following csv-files are copied: AuditTrail0l.csv TagArchiv0.csv TagArchiv10.csv Alarms0.csv BatchData.csv

20

Documentation of Production Processes V1.0, Entry ID: 42931547

3 Function Mechanisms of this Application 3.4 Functionality of the scripts Language-specific settings in the S3_SaveBatchData script Depending on the list separator which you have set on your HMI operator panel and PC, you have to adapt the script accordingly. Please also refer to the notes of the previous chapter 3.3.1 Notes on the archives.
Figure 3-2

1
Copyright Siemens AG 2010 All rights reserved

Point 1: On PC systems in German language the list separator is a semicolon by default. In this case you activate line 50 to 64. Line 68 to 82 must then be commented. Point 2: On PC systems not in German language the list separator is usually a comma. In this case you activate line 68 to 82. Line 50 to 64 must then be commented.

Documentation of Production Processes V1.0, Entry ID: 42931547

21

3 Function Mechanisms of this Application 3.4 Functionality of the scripts S4_Script_Storage_Path The script is called via the scripts S2_PrepBatchConditions and S3_SaveBatchData. The script creates the storage path in which the batch files are stored. S5_SetDefaultPath The paths are preassigned via the script in which the later future are stored. S6_Sim_Injections Tags Injection_1 to Injection_160 are preassigned with a value of 0 to 2 via the script. The values are determined via random generator. The script is used for displaying the status of injection processes for a filling process. Value 0 Value 1 Value 2 Error (red) OK (green) Warning (yellow)

The values are archived and later evaluated in the report file.
Copyright Siemens AG 2010 All rights reserved

S7_StartBatchConditions Via this script the various start requirements to be fulfilled when starting a batch process are checked (for example, a user must be logged on, etc.). Furthermore, the start time of the batch process is stored. S8_Tag_Persistence Via the script the values of the tag stored in the script is saved to a file. It serves for saving the preset values prior to switching the operator panel off. The script is executed in the application before terminating the runtime. S9_Tag_Persistence_Get Via this script, the values stored via the S8_Tag_Persistence script are read out again and assigned to the individual tags. The script is executed in the application after starting the runtime.

Note

When changing the storage location or names of tags in your configuration, please also check the existing scripts. Normally you have to perform appropriate adjustments in the scripts.

22

Documentation of Production Processes V1.0, Entry ID: 42931547

3 Function Mechanisms of this Application 3.5 Functionality of the audit

3.5

Functionality of the audit


The Audit Trail function and the Electronic signature are provided with the Audit option. This supports the user in fulfilling increased quality requirements of his/her project, for example, for plants requiring validation according to 21 CFR Part 11. The Audit option is called up in the Properties of the context menu of the project. In the "GMP Settings" area you activate the "Regulated project" checkbox.
Figure 3-3

Copyright Siemens AG 2010 All rights reserved

The following Audit functions are used in this application: Audit Trail archive: Project window > Archives > AuditTrail With Audit Trail you configure an archive in which all audit-relevant user actions and system processes are recorded during Runtime. GMP settings at several tags: Properties window > Properties > GMP settings Here you define which tags are BMP-relevant and whether the user must acknowledge a value change of the tag during runtime with his/her electronic signature. System function "Record user action": With this system function you record the user actions in the Audit trail which are not automatically entered in the Audit trail. Furthermore, using this system function you can prompt the user to give an acknowledgement or an electronic signature for the operator action as well as a comment.

The tags and objects (buttons) classified as GMP-relevant are given in the attached configuration.

Documentation of Production Processes V1.0, Entry ID: 42931547

23

3 Function Mechanisms of this Application 3.6 Functionality of the messages

3.6

Functionality of the messages


For illustration purposes some bit alarms have been configured in the configuration. These are triggered by a simulation The alarms are used for supplying the alarm log with data.

3.7

Functionality of the user administration


The GMP functionality requires a user administration. The following users are used: Admin user1 user2 Password: 100 Password: 111 Password: 222

In the application all users have administrative rights.


Copyright Siemens AG 2010 All rights reserved

The various users are used for receiving different entries in the Audit trail file.

24

Documentation of Production Processes V1.0, Entry ID: 42931547

3 Function Mechanisms of this Application 3.8 Functionality of the Excel templates

3.8

Functionality of the Excel templates


The application includes the following files: HmiCheckLogIntegrity.exe PharmaBatchReport.xls ReportTemplate.xls

These three files together must be located in one folder. The csv-files copied by the operator panel are edited via the PharmaBatchReport.xls file and grouped into one Batch Report file. The PharmaBatchReport.xls file contains scripts which access the two files HmiCheckLogIntegrity.exe and ReportTemplate.xls. HmiCheckLogIntegrity.exe The correctness of the check sums in the files can be verified with the command line tool HmiCheckLogIntegrity.exe. In this case the intactness of the Audit Trail file is verified (it is checked whether the file has been manipulated). The program HmiCheckLogIntegrity.exe is also available in the installation directory of WinCC flexible in the folder "WinCC flexible 2008 Runtime"
(e.g. C:\Program Files\Siemens\SIMATIC WinCC flexible\WinCC flexible 2008 Runtime)

Copyright Siemens AG 2010 All rights reserved

Always use the HmiCheckLogIntegrity.exe file appropriate for your WinCC flexible version. The file is required for implementing the Batch Report file. PharmaBatchReport.xls The PharmaBatchReport.xls file generates a Batch Report file (batch log file) from the csv-file created by the operator panel. To implement this functionality you need the two following files. HmiCheckLogIntegrity.exe ReportTemplate.xls.

The two files must be located in the same directory as the PharmaBatchReport.xls file. A detailed description on how the PharmaBatchReport.xls file is available in chapter Operating the EXCEL templates. ReportTemplate.xls The file is used as a template for the batch report. The files generated via the PharmaBatchReport.xls file are written to this report template.

Documentation of Production Processes V1.0, Entry ID: 42931547

25

3 Function Mechanisms of this Application 3.8 Functionality of the Excel templates

3.8.1

Adjusting the PharmaBatchReport.xls file


The PharmaBatchReport.xls file contains a script which is divided into various functions. Via the Visual Basic-Editor you can open the scripts and edit them afterwards. In Module1 you can call up all functions and adjust them if necessary.
Figure 3-4

Direct selection of the various functions

Copyright Siemens AG 2010 All rights reserved

Adjust tags Via the PharmaBatchReport.xls file the tag archive TagArchiv0 and TagArchiv10 is read out. For the evaluation in the PharmaBatchReport.xls file it is important that the tag name and the storage path matches that specified in WinCC flexible. Check the entries in the script at: WriteDataChartTagArchiv0 WriteDataChartTagArchiv10

26

Documentation of Production Processes V1.0, Entry ID: 42931547

3 Function Mechanisms of this Application 3.8 Functionality of the Excel templates Example: WinCC flexible: Storage path: Batch_Report\Temperature EXCEL PharmaBatchReport.xls file: Script function: WriteDataChartTagArchiv0
Figure 3-5

Instruction
Copyright Siemens AG 2010 All rights reserved

1. Call the PharmaBatchReport.xls file 2. Open the Visual Basic Editor. 3. Open Module1. 4. In the module you call the WriteDataChartTagArchiv0 function 5. Navigate to line Z 729 or Z 732. There you find the tags Temperature and Quantity. Adjust the name and the storage path accordingly if necessary.

Documentation of Production Processes V1.0, Entry ID: 42931547

27

3 Function Mechanisms of this Application 3.9 Archived files on the memory card

3.8.2

Using the Excel templates at Excel 2007


The Excel templates were created for Excel 2003 When using Excel 2007 you perform the instructions below.

PharmaBatchReport.xls 1. Open the PharmaBatchReport.xls file with Excel 2007. 2. Save the file via the menu command Save as...> Excel Macro-Enabled Workbook. The new name of the file is PharmaBatchReport.xlsm. ReportTemplate.xls 3. Open the ReportTemplate.xls file with Excel 2007. 4. Save the file via the menu command Save as...> Excel Workbook. The new name of the file is ReportTemplate.xlsx. The Report file is generated as in Excel 2003.
Copyright Siemens AG 2010 All rights reserved

A detailed description on how the PharmaBatchReport.xls file is available in chapter 5.2 Operating the EXCEL templates.

3.9

Archived files on the memory card


On the memory card the following files are stored. The files are located in folder Batchdata. The files are created by the system or via a script. Alarms0_xxx_HMI_Demo_Batch.csv AuditTrail0_xxx_HMI_Demo_Batch.csv BatchData.csv TagArchiv0_xxx_HMI_Demo_Batch.csv TagArchiv10_xxx_HMI_Demo_Batch.csv

xxx = time and date stamp of the operator panel

28

Documentation of Production Processes V1.0, Entry ID: 42931547

4 Startup of the Application 3.9 Archived files on the memory card

4
General

Startup of the Application


The WinCC flexible configuration contains scripts which only work in connection with operator panels as of series 270 e.g. (MP 277 / MP 377). Note The used source code cannot be used for a PC Runtime. You cannot simulate the configuration with a PC-Runtime.

Excel templates: Please ensure that the following files are contained in a folder. HmiCheckLogIntegrity.exe PharmaBatchReport.xls ReportTemplate.xls

Batch Report folder


Copyright Siemens AG 2010 All rights reserved

For each batch process a separate folder must be created on the PC. The folder must only contain the respective data of one batch process. Windows Explorer (PC) Via the operator panel you can copy archive data located on the memory card to the PC. To copy the data to the PC you need to share a drive in the Windows Explorer (Properties > Sharing). Through the copying process the csv-files are prefixed by the batch ID. This batch ID must match the name of the folder in the Windows Explorer.

Ethernet connection Create an Ethernet connection with the connected operator panel. The connection is required if you wish to transfer the csv-file to the PC. HMI configuration Please ensure that the configured storage location is supported by the operator panel. If necessary, you have to adjust the storage path in the scripts and archives.

Documentation of Production Processes V1.0, Entry ID: 42931547

29

4 Startup of the Application 3.9 Archived files on the memory card Operator panel Supply the operator panel with a memory card and transfer the configuration to the operator panel. To assign the storage path on the PC (for the csv-files to be copied) the following must be known: PC computer name (Start > Settings > Control Panel > System > Computer Name) Share name (folder in the Windows Explorer)

Assigning the storage path The complete name for the storage path is composed as follows: \\computer name\share name\batch ID (The default storage path can be assigned via script, whereby the batch ID must only be assigned at Runtime) The assigned storage path must be created on the PC (the assigned storage path is not automatically created)

Copyright Siemens AG 2010 All rights reserved

30

Documentation of Production Processes V1.0, Entry ID: 42931547

5 Operating the Application 5.1 Operating the HMI configuration

5
5.1

Operating the Application


Operating the HMI configuration
The operation of the individual screens is listed below.

Screen: 01_Start Demonstration Batch Report On this screen a batch process is simulated. All processes serve the purpose of familiarizing the user with the functionality for creating a Batch Report (batch log).
Table 5-1 No. 1. Action (1) Login and Logoff: Before being able to perform an action, you must login via the LOGIN button. Possible names are: Admin 100 User1 111 User2 222 If a user has logged in and within 5 minutes there is no operation at the operator panel, the user is logged off again. Alternatively you can log off via the LOGOFF button. (1) Starting the batch process: After a successful logon you start the process via the Preparation button. The production parameters can now be assigned. (2) Entering the production parameters: To continue further you need to assign a batch ID first as well as a batch name. The batch ID must only be assigned once. The parameters for Method Duration Speed can be changed as desired. The values are used for the recording in the Audit Trail file. 3. (1) Starting the production process: The production process is started via the Start Batch button. Similar to a sequential control configuration the subsequent step is enabled by the preceding one. Pressing the Stop batch button terminates the production process and a new process can be started. Two different processes can be started. (Cleaning I and Cleaning II). Screen

Copyright Siemens AG 2010 All rights reserved

2.

Documentation of Production Processes V1.0, Entry ID: 42931547

31

5 Operating the Application 5.1 Operating the HMI configuration


No. 4. Action (1) Alarms: On this screen the alarms are not output via the standard alarm display but via a configured text line. The text line is only shown if an alarm is pending. In the following cases an alarm is output: If no batch ID or batch name has been entered when starting the production process. If a batch ID has been entered which already exists. If no user has logged in. Via the button next to the text line the alarm is acknowledged and the text line is hidden. (1) Terminating runtime: Runtime is terminated via the button. Always press this button before switching off the operator panel. (2) Calling further screens: Via the buttons the screens displayed on the buttons are called. Screen

5.

Copyright Siemens AG 2010 All rights reserved

2
6. Further display values: (1) Current process parameters: After pressing a process button (e.g. Cleaning I) the respective parameters are adopted and displayed for checking.

1
(2) Status display of a filling process: The status of injection processes for a filling process is simulated via a script. Depending on the assigned value, the status of the individual valves is represented in color. The status values are logged in a data log and listed in the Batch Report. Example: red Error green OK yellow Warning white no current status exists

32

Documentation of Production Processes V1.0, Entry ID: 42931547

5 Operating the Application 5.1 Operating the HMI configuration Screen: 02_Messages Alarms On this screen the alarms created via a simulation are output.
Table 5-2 No. 1. Action Alarm display: (1) Start button: The Start button takes you back to the start screen. (2) Pending and unacknowledged alarms: All pending and unacknowledged alarms are displayed via this screen. To acknowledge an alarm the user must be logged in. (3) Alarm log: The archived alarms are output via the alarm log.

Screen

Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

33

5 Operating the Application 5.1 Operating the HMI configuration Screen: 03_TagLogging Trend display On this screen two simulated tag values are output in a trend display.
Table 5-3 No. 1. Action Trend display: Via the trend display the simulated values for Temperature and Quantity are displayed. (1) Start button: The Start button takes you back to the start screen.

Screen

Screen: 04_Config Configuration


Copyright Siemens AG 2010 All rights reserved

On this screen the various configurations are made.


Table 5-4 No. 1. Action Buttons (1) Start button: The Start button takes you back to the start screen. (2) WinCE button: The button takes you directly to the Explorer view of the operating system of the operator panel. From there you have direct access to the memory card to view individual files and their names. (Details see Table 5-1 no 4) (2) English (German) button: This button enables selecting the language. The options are English or German. (3) Export to PC button: This button transfers the data of a batch (csvfiles) from the memory card to the PC. Requirement is that the operator has logged in and no production process is running. After a respective batch has been transferred to the PC, it is automatically deleted from the memory card. If you try to export the same batch again, a respective warning message appears. Screen

1 2

34

Documentation of Production Processes V1.0, Entry ID: 42931547

5 Operating the Application 5.1 Operating the HMI configuration


No. 2. Action (1) Specify storage location: The storage location for the csv-files on the memory card as well as for the PC are automatically assigned. You can retrospectively adjust these paths via this screen. Storage path for "batch data": The csv-files are stored on the memory card under this given path. Storage path on the PC: The csv-files are copied to the PC under this given path. Please note that the given folders on the PC must already exist. The storage path is composed as follows: \\computer name\share name\batch ID Batch ID no: For each production process a batch ID is assigned at the beginning of a process. You have to specify this batch ID for the Export of the files. Note: If you do not know exactly the batch ID on the memory card then you can call and check the data on the memory card via the WinCE button. (2) Alarm display: Pending alarms (no error messages) are displayed via the alarm display. The alarms are displayed for the duration of 10 seconds. (1) Warning message If you wish to transfer the data of a batch via the Export to PC button, certain requirements must be fulfilled. If these are not fulfilled, a text line with a respective note are displayed. Screen

Copyright Siemens AG 2010 All rights reserved

3.

1
Possible warning messages: Directory with Batch-ID doesnt exist Batch export directory is empty Batch-ID or one of the paths is empty Filecopy to computer failed, check network communication with computer Batch export directory is empty (The texts are stored in the script in English language). Via the button next to the text line the alarm is acknowledged and the text line is hidden.

Documentation of Production Processes V1.0, Entry ID: 42931547

35

5 Operating the Application 5.1 Operating the HMI configuration


No. 4. Explorer view Pressing the WinCE button takes you to the Explorer view of the operator panel. There you have the option of viewing the data on the memory card. This is especially helpful if you do not know exactly the batch ID to be exported. Action Screen

2
Copyright Siemens AG 2010 All rights reserved

Figure 5-1 4 (1) Explorer view after pressing the WinCE button. (2) Viewing the data storage on the memory card (Storage Card MMC) (3) Viewing the data after opening the Batchdata folder (This folder contains the stored process data suitable for the respective batch ID) (4) Viewing the data after opening the batch ID folder 100 The batch ID folder contains all relevant data for this process. The folder content can be copied to the PC via the Export function (Export to PC button).

36

Documentation of Production Processes V1.0, Entry ID: 42931547

5 Operating the Application 5.2 Operating the EXCEL templates

5.2

Operating the EXCEL templates


The application example contains the folder Demo_BatchReport_Excel_V1.2. The folder contains the following three files: HmiCheckLogIntegrity.exe PharmaBatchReport.xls ReportTemplate.xls

These three files must always be located together in one folder. The name of the folder can be selected by the user. For further processing a Batch Report you only need the PharmaBatchReport.xls file. PharmaBatchReport.xls
Table 5-5 No. 1. Action Opening the PharmaBatchReport.xls file Open the PharmaBatchReport.xls file with a double-click. Depending on your security settings you receive a warning message that the Exce file contains macros. Confirm the query with Enable macros (1) Button via which the Batch Report is selected (2) On these screens the read values are temporarily stored. Screenshot

Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

37

5 Operating the Application 5.2 Operating the EXCEL templates


No. 2. Action Calling a batch report 1. Acknowledge the button select file location and generate batch protocol 2. Navigate to the folder which contains the batch report file. 3. Then press the OK button. Note: The batch report files have the file extension *.csv. Therefore no files are displayed in the folder window when calling the folder. 4. After pressing the OK button a script runs in the background. The report file is created. Screenshot

Copyright Siemens AG 2010 All rights reserved

Note: You receive a warning message if the condition does not apply: If you do not wish to evaluate a further batch report file you can close the PharmaBatchReport.xls file again. This file does not need to be saved.

38

Documentation of Production Processes V1.0, Entry ID: 42931547

5 Operating the Application 5.2 Operating the EXCEL templates Report_xxx.xls file
Table 5-6 No. 1. Action View of the generated report file Via the PharmaBatchReport.xls Excel file the Report_xxx.xls file is generated. The name of the report file is composed as follows: Report_(Batch-ID).xls The Report_xxx.xls file contains all data produced during the batch process. The report file contains a total of 6 worksheets. NewResultSheet1 (current screen) graphic evaluation of tag values. NewTagArchiv0-ChartData List of tag values of the Quantity and Temperature tags. NewTagArchiv0-ChartData List of tag values of the tags Injection_1 to Injection_10. NewAlarmResultSheet1 List of alarms. NewAlarmResultSheet1 List of all operations. NewResultBatchData List of tag values of the tags Injection_1 to Injection_160. The file is automatically stored in the Batch ID folder. Screenshot

Copyright Siemens AG 2010 All rights reserved

Documentation of Production Processes V1.0, Entry ID: 42931547

39

6 Links & Literature

6
6.1

Links & Literature


Literature
The following list is by no means complete and only provides a selection of appropriate sources.
Table 6-1 Topic /1/ /2/ Audit VBS Title Information on Audit is available in the WinCC flexible help or in the Getting Started on the WinCC flexible options. Information on VBS is available in the WinCC flexible help or in the manual in chapter System functions and runtime scripting.

6.2

Internet Links
The following list is by no means complete and only provides a selection of appropriate sources.
Table 6-2

Copyright Siemens AG 2010 All rights reserved

Topic \1\ \2\ \3\ \4\ \5\ Reference to this entry Siemens I IA/DT Customer Support FAQ Manual FAQ

Title
http://support.automation.siemens.com/WW/view/de/42931547 http://support.automation.siemens.com How do you integrate an operator panel into a local network? http://support.automation.siemens.com/WW/view/de/13336639 WinCC flexible Getting Started options http://support.automation.siemens.com/WW/view/de/18657078 What do you need to watch out for when naming archives and when archiving tags in a csv file on Windows-based systems? http://support.automation.siemens.com/WW/view/de/31155956 Which external storage locations are available on the various operator panels (WinCC flexible/ProTool) for archiving data? http://support.automation.siemens.com/WW/view/de/26190516 Which external filing location for archiving data is available for the various operator panels (WinCC flexible/ProTool)? http://support.automation.siemens.com/WW/view/de/35935468 Which external storage media can be used with the SIMATIC panels,or which memory card interfaces they have. http://support.automation.siemens.com/WW/view/de/21847868

\6\

FAQ

\7\

FAQ

\8\

FAQ

40

Documentation of Production Processes V1.0, Entry ID: 42931547

7 History

History
Table 7-1 Version V1.0 Date 23.06.2010 First issue Changes

Copyright Siemens AG 2010 All rights reserved