ModbusRTUControl W ML1100 PDF
ModbusRTUControl W ML1100 PDF
Question
How can I control a PowerFlex 523 Drive over Modbus RTU using a MicroLogix 1100?
Answer
Because of the variety of uses for this information, the user of and those responsible for applying
this information must satisfy themselves as to the acceptability of each application and use of the
program. In no event will Rockwell Automation be responsible or liable for indirect or consequential
damages resulting from the use or application of this information.
The illustrations, charts and examples shown in this application note are intended solely to illustrate
the principles of programmable controllers and some of the methods used to apply them.
Particularly because of the many variables and requirements associated with any particular
installation, Rockwell Automation cannot assume responsibility or liability for actual use based upon
the illustrations used and applications.
Rockwell Automation assumes no patent liability with respect to use of information, circuits,
equipment, or software described in this text.
Reproductions of the contents of this application note, in whole or in part, without the express
written consent of Rockwell Automation are prohibited.
Intended Audience
This document is to be used by Rockwell Automation employees and customers supporting and
selling the MicroLogix 1100, PowerFlex 523.
Users are expected to have a thorough understanding and programming experience with RSLogix
500. This document is not intended for beginning programmers, many assumptions of knowledge
and how to program are made within this document.
System Layout
When making your Protocol Control selection under Control Line,when using the 1761-CBL-
NC01 you must be sure to properly select NO Handshaking (485 Network), otherwise you
may encounter issues such as MSG instructions generating error codes of 37H
LAD 4 MODBUS
LAD 5 PF4_CNTRL
4. Enter the following ladder logic for LAD 4 MODBUS. This subroutine will perform the
ModBus messaging to and from the PowerFlex drive
5. Configure each of the MSG instructions as shown below. Remember for PowerFlex 523
drives, you must add a value of " 1 " to the ModBus register (MB Data Address) that is listed
in the PowerFlex manual.
MSG Command Word
MSG Speed Reference
6. Enter the following ladder logic for LAD 5 PF4_CNTRL. This ladder the manual bits (b3:0/x)
for control the PowerFlex drive
You can download the project, ULOGIX1100_MODBUS_PF523_APPNOTE.RSS, in the bottom of
this technote.
Attachments
ULOGIX1100_MODBUS_PF523_APPNOTE.RSS
(/ci/fattach/get/1086571/0/filename/ULOGIX1100_MODBUS_PF523_APPNOTE.RSS)
(33.5 KB)
DISCLAIMER
This knowledge base web site is intended to provide general technical information on a particular
subject or subjects and is not an exhaustive treatment of such subjects. Accordingly, the information
in this web site is not intended to constitute application, design, software or other professional
engineering advice or services. Before making any decision or taking any action, which might affect
your equipment, you should consult a qualified professional advisor.
This page is best viewed in Internet Explorer 10, Firefox 31, Chrome 37, Safari 6 or newer.
New Site Feedback
Give Feedback
(http://www.rockwellautomation.com/global/blog/overview.page)
(https://www.facebook.com/ROKAutomation)
(https://plus.google.com/+RockwellautomationInc)
(https://www.linkedin.com/company/rockwell-
(http://www.slideshare.net/RockwellAutomation)
(http://twitter.com/ROKAutomation)
(http://www.youtube.com/rokautomation)
automation)