PTB 1-92
PTB 1-92
PTB 1-92
April 23, 1990 Fast bus transfer is normally used for transferring a bus supplying motors to an emergency power source on failure of the normal source of power. It is essential that this transfer be accomplished with a minimum of "dead time" to prevent loss of critical motors or damage to the motors on re-energization. Two schemes of operation are used for fast transfer. In the first, the trip signal to the opening breaker and the close signal to the closing breaker are given simultaneously. With this method, there is a possibility of overlap between the two sources, which may lead to the incoming breaker closing into a fault. This can be prevented by adding a few milliseconds of time delay to the closing signal. In the second scheme, the closing signal of the second breaker is initiated by a "b" contact of the opening breaker. This may be either standard "b" contact or a fast "b" contact. We have recently run timing tests on the "Dash 3" PowlVac circuit breaker to determine fast transfer dead times. The result, which apply to 5PV0250-3 and 15PV0500-3 breakers, both 1200A and 2000A, are given in the following table. Source of Closing Signal No Arcing Simultaneous Close and Trip Signals Trip Then Close, Using Fast "b" Contact Trip Then Close, Using Standard "b" Contact Possible overlap 7.0 - 17.0 53.0 - 63.0 57.5 - 67.5 Dead Time, ms With Arcing (1.0)* - 9.0 45.0 - 55.0 49.5 - 59.5
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #2 Closing and Latching Capability of Medium Voltage Power Circuit Breakers
May 18, 1990 ANSI Standard C37.06-1987, American National Standard for Switchgear - AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities, includes a column in Table 1 headed Closing and Latching Capability. In older editions of this standard, the current value in this column was given in rms kiloamperes, and was determined by multiplying the maximum symmetrical interrupting capability by 1.6. In the 1987 edition, this current is expressed in crest kiloamperes, and the value is determined by multiplying the maximum symmetrical interrupting capability by 2.7. Other standards had previously required the closing and latching current to have a crest value of 2.7 times the maximum symmetrical interrupting current, so the performance required of the circuit breaker has not really changed. Only the method of stating the requirement has changed. This change was made to bring the ANSI standard in line with the IEC standard, which also expresses closing and latching capability in crest amperes. Since many specification writers will be using older standards, or copying older specifications, we will probably see both methods of specifying closing and latching current used in specifications for many years. The following table gives both sets of values. Rated Maximum Voltage kV, rms 4.76 4.76 8.25 15.0 15.0 15.0 Rated Short Circuit Current kA, rms 29 41 33 18 28 37 Closing and Latching Capability per ANSI C37.06 1979 Edition kA, rms 58 78 66 37 58 77 1987 Edition kA, Crest 97 132 111 62 97 130
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #2 Closing and Latching Capability of Medium Voltage Power Circuit Breakers
page 2 If the specified value of closing and latching current matches a value from either edition of the standard, we can assume that a standard breaker is desired. If there is any possibility of confusion, the specifier should be contacted to determine which basis is being used to specify the close and latch rating.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #3 Capacitance Current Switching Capability of PowlVac Circuit Breakers
June 7, 1990 We have recently had capacitance current switching tests performed on our "Dash 3" PowlVac circuit breakers, using GE interrupters. The results of these tests showed that these breakers are qualified as definite purpose circuit breakers, in accordance with ANSI Standard C37.06-1987, Table 1A, for both isolated and back-to-back switching of capacitors. Table 1 lists the maximum rating of capacitor bank that can be switched by each rating of circuit breaker when applied in accordance with ANSI/IEEE Standard C37.012-1979. The values in the table were calculated using a total current multiplier of 1.25 for ungrounded capacitor banks and 1.35 for grounded banks. These multipliers include allowances for higher than normal voltage, capacitor tolerance, and harmonic components in the current. See ANSI/IEEE C37.012-4.7.1. When PowlVac circuit breakers are used in a back-to-back switching situation, inrush currents and frequencies must be limited to the values given in Table 1A of ANSI C37.06-1987. This may require the addition of reactance between the two capacitor banks. Table 1: Capacitor Bank Switching Capability of "Dash 3" PowlVac Circuit Breakers Maximum Nameplate Rating of Capacitor Bank, MVAR Ungrounded Bank 1200A Breaker 2.4 05PV0250 4.76kV 250MVA 4.16 4.76 11.5 12.47 15PV0500 15.0kV 500MVA 13.2 13.8 14.4 2.09 3.63 4.15 10.04 10.88 11.52 12.05 12.57 2000A Breaker 3.33 5.76 6.60 15.93 17.28 18.29 19.12 19.95 Grounded Bank 1200A Breaker 1.94 3.36 3.85 9.30 10.08 10.67 11.15 11.64 2000A Breaker 3.08 5.34 6.11 14.75 16.00 16.94 17.71 18.48
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #3 Capacitance Current Switching Capability of PowlVac Circuit Breakers
page 2 Note: This table does not apply to PowlVac circuit breakers using Mitsubishi interrupters. We have not tested those breakers for capacitance current switching capability, but we do have some data from Mitsubishi that allows us to apply them. Such applications should be referred to me for checking.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
The circuit breaker cannot be inserted into the cell without plugging in the umbilical cord. Once the circuit breaker racking mechanism has been operated to start the circuit breaker insertion process, the plug cannot be removed. It is therefore not possible to disconnect the control circuits of a circuit breaker that is in service. Unplugging the umbilical cord trips the circuit breaker if it is closed and discharges the closing spring if it is charged. Since the plug must be removed in order to remove the circuit breaker from its cell, these interlocks insure that the circuit breaker is open and all energy storage springs are discharged when the circuit breaker is taken out of the cell.
Q. Why does Powell differ from all other manufacturers in the method of disconnecting the control connections to the circuit breaker? A. Powell does not differ from "all other manufacturers". While the umbilical cord design has not been used frequently in the United States, other American manufacturers have used it. It is also commonly used in Europe. We chose to use this design because we think it offers superior performance in total.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Q. Does the umbilical cord design meet ANSI standards? A. Yes. This design, including required interlocking, is covered in detail in ANSI/IEEE Standard C37.20.2-6.2.7. The PowlVac circuit breaker meets these requirements.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Cycloaliphatic epoxy ("cyclo") weighs less than 70% of porcelain's weight. The thermal coefficient of expansion of cyclo is 1/20th that of porcelain. The tensile strength of cyclo is about 11 times that of glazed porcelain. The compression strength of cyclo is 4 to 6 times that of glazed porcelain. The flexural strength of cyclo is 16 to 18 times that of glazed porcelain. The Izod impact strength, unnotched, is about the same as glazed porcelain. Dimensional and shape control is much easier in cyclos than in porcelain. While the repairability of cyclos is limited, porcelain is unrepairable.
The dielectric constant of cyclo is only about two-thirds that of porcelain. The temperature class of porcelain is much higher than that of cyclo, but cyclo mixtures with temperature classes of 105 C or 130 C are readily available. The track resistance of cyclo is slightly less than that of porcelain. The water absorption of cyclo is slightly greater than that of porcelain, but is still in the range of 2/10's of 1%.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Finally, cyclo exhibits excellent resistance to common industrial chemicals, is readily washable, and has excellent erosion resistance and weathering properties. In summary, we believe that the excellent physical properties of cyclo make it the insulating material of choice in spite of some small sacrifice in electrical properties. This is especially true for applications requiring great strength under severe dynamic loading, such as support insulators in circuit breakers and switchgear.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
where
is the seismic zone coefficient, which varies from 0.125 for Zone 0 to 1 for Zone 4,
is the occupancy factor, which varies from 1 for Category I to 1.5 for Category III,
is the horizontal force factor, which is 0.3 for all machinery in a building,
and
From basic mechanics, Force = Mass x Acceleration. In the above formula, Fp is a force. Wp is a weight, which is the product of a mass and the acceleration of gravity, or g. It follows that the product of Z, I and Cp is a dimensionless coefficient for g. For a worst case situation, where the switchgear is installed in a critical occupancy in Zone 4, the value of this coefficient is 1 x 1.5 x 0.3, or 0.45. Since seismic testing is performed in terms of acceleration rather than force applied, the test level for a worst case installation should be 0.45 g. The other aspect of suitability is the performance of the equipment under the specified conditions. Here, we have absolutely no guidance from ANSI standards. Based on past experience and input from various users, Powell has decided that the following are reasonable criteria for suitability:
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #10 Transient Recovery Voltage (TVR) Values for Testing PowlVac Circuit Breakers
January 10, 1991 The interrupting performance of any circuit interrupter is affected by the transient recovery voltage appearing across the first pole to interrupt. Both the absolute value of this voltage and its rate of rise are important in determining the interrupter's ability to meet its interrupting rating. The required values of transient recovery voltage are included in ANSI/IEEE C37.06-1987, along with the other ratings of circuit breakers.
The conventional way of specifying the rate of rise of the transient recovery voltage is to specify the peak value (E2) and the time required to reach that peak (T2). The rate of rise is then determined by dividing E2 by T2. The nominal values are those for a full rated short circuit interruption. For lower currents, both higher peaks and faster times are specified. Table 6 of ANSI/IEEE C37.06-1987 lists the multiplying factors to be applied to E2 and T2 for interrupting currents below the full rating of a circuit breaker.
Table 1 of ANSI/IEEE C37.06-1987, which gives the preferred ratings of indoor oilless circuit breakers, such as PowlVac breakers, calls for E2 to be 1.88 times the breaker's rated maximum voltage for tests at 100% of the circuit breaker's interrupting rating. Unfortunately, values of T2 are not standardized, leaving the manufacturer with no guidance on this subject. In order to assign some reasonable value to T2, Powell decided to use the rate-of-rise values given in Table IIA of IEC Standard 56, interpolating between the listed values to match the ANSI voltage ratings, and multiplying the rate-of-rise values by E2 to obtain T2. The values obtained by this method were used in the testing of PowlVac circuit breakers, and are given in the table below.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #10 Transient Recovery Voltage (TVR) Values for Testing PowlVac Circuit Breakers
page 2
PowlVac Transient Recovery Voltage Test Values Transient Recovery Voltage Current % of Interrupter Rating Rated Maximum Voltage = 15 kV Rated Maximum Voltage = 4.76 kV
7 to 13 20 to 30 40 to 60 100
29 29 49 73.6
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #12 Continuous Current Carrying Capability of Low Voltage Circuit Breakers
March 4, 1991 Various types of low voltage circuit breakers have differing continuous duty capabilities. Some are rated to carry 100 percent of their trip rating continuously, while others are rated to carry only 80 percent of their trip rating continuously. It is important that we understand the difference and apply these breakers properly. The general run of molded case circuit breakers in frame sizes of 400 A and below are rated to carry only 80 percent of their rated trip current on a continuous basis. Particularly when these breakers are mounted close to each other in a panelboard, the extra heat generated by carrying 100 percent of the trip rating will both lead to false tripping and cause long-term degradation of the insulating material of which these breakers are made. On the other hand, all low voltage power circuit breakers and the general run of insulated case circuit breakers are capable of carrying 100 percent of their trip rating on a continuous basis. Some confusion can arise when using large molded case circuit breakers, in frame sizes of 600 A and above. These breakers may be rated either 80 percent or 100 percent, depending on the model and the manufacturer. As you would expect, the 100% breaker costs considerably more than the 80% breaker. Some models have both 80% and 100% ratings available. The 100% rated breaker may require a larger enclosure and/or more ventilation than the 80% rated breaker of the same model. Please observe the following application rules: 1) Apply MCCB's in 400 A frame size and smaller based on continuous loads of not more than 80% of the circuit breaker's trip rating. If trip ratings are selected by our customer, assume that they are based on the 80% load requirement. 2) Apply insulated case breakers and low voltage power circuit breakers based on continuous loads of not more than 100% of the breaker's trip rating. If trip ratings are selected by our customer, assume that they are based on the 100% load requirement., Be sure that the insulated case breakers selected are 100% rated.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #12 Continuous Current Carrying Capability of Low Voltage Circuit Breakers
page 2 3) Apply large molded case circuit breakers based on either the 80% or the 100% rating, making sure that the breaker selected fits the application, and that adequate space and ventilation is provided for the breaker chosen. If trip ratings are selected by our customer, be sure that you understand which basis was used for selection.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
An investigation of the failed autotransformers by their manufacturer showed that the failure had been a surface flashover from the line end of the winding either to another tap of the winding or to a ground point. There was no damage to the winding or the core, and the autotransformers could be easily repaired and put back into service. We consulted with both the autotransformer manufacturer and the manufacturer of the contactors used in the starter, and found that there had been previous experiences of this problem. The flashovers occurred because system transients generated during the starting sequence caused an excessive voltage to appear on the line end of the autotransformer winding. Upon analysis, we found several conditions that contributed to this problem:
The starter was located at the end of a rather weak supply line. During the starting sequence, the user switched in a rather large capacitor bank to minimize the line voltage drop. This bank was switched off automatically, during the starting sequence, when the voltage recovered to a fixed point. The autotransformer was set on the 80% tap. We are uncertain of the setting of the timer used to transfer from the starting connection to the running connection.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Insulate the transformer connection points, both the taps that are used and the unused taps. This should be done on all future starters of this type. Use a lower voltage tap on the autotransformer, such as 65% or 50%, if the motor will accelerate successfully on these taps. For induction motors, be sure that the timer that transfers to the running connection is set at a long enough time so that the motor is fully accelerated before changing to the running connection. Add an instantaneous current relay to the circuit, set to pick up at about 5 A and drop out just below that current. This relay will pick up when the motor is started and drop out when it reaches full speed. Connect the coil of this relay in any phase CT. Use the contact of this relay to bypass the timing relay contact, insuring that the motor has fully accelerated before the starter is transferred to the running connection. See the control circuit below. In the future, please include this relay in all starters of this type.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
In extreme cases, it may be necessary to connect intermediate class surge arresters to the line taps of the two autotransformer coils.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #15 Directional Overcurrent and Directional Power Relays
May 24, 1991 From time to time we experience some confusion about the difference between directional overcurrent relays, ANSI device 67, and directional power relays, ANSI device 32. Although there are some similarities between these two types of relays, they are really very different in both construction and application. Directional overcurrent relays (67) respond to excessive current flow in a particular direction in the power system. The relay typically consists of two elements. One is a directional element, which determines the direction of current flow with respect to a voltage reference. When this current flow is in the predetermined trip direction, this directional element enables ("turns on") the other element, which is a standard overcurrent relay, complete with taps and time dial, as found on a normal non-directional overcurrent relay. Because these relays are designed to operate on fault currents, the directional unit is made so that it operates best on a highly lagging current, which is typical of faults in power systems. Directional overcurrent relays are normally used on incoming line circuit breakers on buses which have two or more sources. They are connected to trip an incoming line breaker for fault current flow back into the source, so that a fault on one source is not fed by the other sources. In complex distribution or subtransmission networks, these relays may be used to improve coordination of the system. Directional power relays (32) measure real power , so they operate best at a high power factor. Various degrees of sensitivity and speed of operation are available in various models of directional power relays. There are three typical uses of these relays:
Connected to measure power flow into a generator, the relay will operate to trip the generator breaker if the generator begins to draw power from the system and act as a motor. This is usually due to loss of prime mover power. Connected to measure power flow into a transformer from the secondary side, a very sensitive directional power relay can measure core loss power input to the transformer, detecting loss of the primary source to the transformer. The transformer can then be disconnected from the system. A directional power relay can be used to limit power flow in a circuit. The relay may trip a breaker or initiate control action to change the system configuration. By using quadrature potential connections or a phase shifting transformer, these relays can be made to measure vars . A typical use would be to limit the real or reactive power drawn from a utility source to a contractual level.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #15 Directional Overcurrent and Directional Power Relays
page 2 Neither the functions (67 and 32) nor the actual relays are interchangeable. Be sure to use the function and the hardware which fit the application.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
The heating contactor must be a full line voltage contactor, as the motor winding side of this contactor is energized at line voltage when the motor is running. The running contactor and the heating contactor must be mechanically and electrically interlocked so that only one of them can be closed at any time. There needs to be a time delay between the opening of the running contactor and the closing of the heating contactor, to allow the residual voltage on the motor to decay before the motor windings are connected to the low voltage source. Since it is not critical to apply the heating circuit immediately, it is recommended that this time delay be in the order of 2 to 5 minutes. Tests show that there is an open circuit time of approximately 75-80 milliseconds when the running contactor is picked up by a "b" contact of the heating contactor. The user should consider whether this is an adequate time period to prevent unwanted system problems. If not, a time delay of a few seconds can be inserted in the pickup circuit of the running contactor to be sure that the heating contactor has cleared before the motor is energized by the operating voltage. The voltage applied to the motor windings must be carefully selected to produce the proper heating. This value must be selected by the user, based on input from the motor manufacturer.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #17 Ground Lead Disconnectors on Distribution-Class Surge Arresters
July 18, 1991 Many current models of zinc oxide distribution or riser pole arresters come equipped with ground lead disconnectors. This is a device which is mounted on the ground end of the arrester and which looks about like a small hockey puck. The enclosure is black, blue or green plastic, a couple of inches in diameter and an inch or so tall. The normal failure mode of these arresters is a short circuit to ground, causing ground fault current to flow. This current will cause the arrester body to fail if it is not stopped quickly. The first function of the ground lead disconnector is to disconnect the ground lead of the surge arrester in case of an internal failure of the arrester, preventing explosive failure of the arrester body. The ground lead disconnector contains a cartridge in series with a gap. The gap is shunted by a resistor. As the current rises, the voltage across the gap increases until the gap flashes over, creating an arc which ignites the cartridge, blowing the ground lead free. The ground lead disconnector is not a fault current interrupter. The arc drawn by the ground lead as it separates from the body of the arrester may or may not go out on its own. If it does not go out, a circuit breaker, recloser or fuse must operate to extinguish the arc. The ground lead disconnector is expected to create a gap which will not reignite when power is reapplied to the circuit, but the gap which will be created is a function of the length and flexibility of the ground lead. The second function of the ground lead is to give a visible indication of arrester failure for arresters mounted on overhead distribution lines. If a lineman sees an arrester with its ground lead hanging in midair, he knows that he has a failure which must be replaced. These explosive ground lead disconnectors are not suitable for use in metal-enclosed equipment. We do not want the explosion and subsequent uncontrolled arc inside equipment, where the clearances are not nearly as great as on overhead lines, and where secondary damage from the arc is much more likely to occur. The visible indication function of the disconnector is useless if the device is mounted within an enclosed equipment. All surge arresters used in Powell's equipments should be of the type without ground lead disconnectors. If a user requests that we include a surge arrester with a ground lead disconnector, we should offer an equivalent model without the disconnector.
All of these breakers are rated 5 cycles interrupting time in accordance with the preferred ratings found in Table 1 of ANSI C37.06-1987, even though they may be faster. The "Dash 2" breaker, in particular, is very nearly a 3 cycle breaker.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #19 Use of PowlVac Circuit Breakers for Continuous Currents Above 3000 Amperes
August 26, 1991 In accordance with ANSI/IEEE Standard C37.06, the highest continuous current rating of our standard line of PowlVac circuit breakers is 3000 A. For systems that require continuous current ratings above 3000 A, we can offer two possible solutions. First, we can offer our standard 3000 A circuit breaker with cooling fans. We have a design that has been successfully tested at 3750 A, and the results of that test indicate that the fan-cooled breaker may be applied at 4000 A without overheating. This design requires a unit somewhat wider than the standard 36inch switchgear unit to include the necessary air ducts. The standard fan control equipment includes a current-actuated control to start the fans at about 2500 A and an alarm circuit which uses air flow switches to detect and alarm loss of cooling air at currents above this level. A completely redundant second set of fans can be furnished if desired. Fan cooling is our preferred method of obtaining higher continuous current ratings. A second method of providing for high continuous currents is to parallel two circuit breakers. Using this approach, we can provide for continuous currents of about 3500 A by paralleling two 2000 A breakers and about 5000 A by paralleling two 3000 A breakers. When breakers are paralleled, the interrupting rating is neither increased nor decreased. Precise timing in closing or opening the two paralleled breakers is not critical, as whichever breaker closes first can carry the continuous current for the few milliseconds until the second breaker closes, and the last breaker to open has the capability of interrupting the full fault current. Paralleling of breakers does require special circuitry to balance the currents between the two breakers and individual overcurrent protection for each breaker as well as combined overcurrent protection for the entire circuit. Main bus construction must also be very carefully balanced to insure equal impedance in both legs of the circuit. Parallel breakers should only be used for a user who refuses to use fan cooled circuit beakers. Regardless of which breaker uprating method is used, special attention must be given to the design of any portions of the switchgear bus which are rated over 3000 A. If the main bus exceeds 3000 A, standard PowlVac bus cannot be used, and the required special bus design limits the switchgear to one-high construction.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #20 Application of Dummy Circuit Breakers in Metal-Clad Switchgear
August 27, 1991 Dummy circuit breakers are used in metal-clad switchgear to provide a method of disconnecting and isolating a circuit or circuits without using a circuit breaker. A common use of a dummy circuit breaker is as a temporary connection in a switchgear cell where a circuit breaker will be installed as part of a planned future expansion. Another use might be to isolate one end of a tie bus or cable from a switchgear bus. Because a dummy circuit breaker is really a set of three jumper bars mounted on a breaker carriage, it has absolutely no current interrupting rating. If an attempt is made to withdraw the dummy circuit breaker with current flowing, arcing will occur at the primary disconnect fingers. This may result in operator injury, equipment damage, or both. Therefore, dummy circuit breakers normally are interlocked with other switching devices so that the dummy cannot be withdrawn until the other devices are opened, insuring that no current is flowing in the dummy. A particular application that can be troublesome is isolating a tie cable that has been opened by a circuit breaker at the other end. If the cable is still attached to an energized bus through the dummy breaker, cable charging current will flow through the dummy. It only takes a few hundred feet of 15 kV cable to draw a charging current of as much as half an amp. This highly capacitive current is difficult to interrupt. It is recommended that the interlocking for any circuit involving power cable and a dummy circuit breaker be arranged so that the cable is completely deenergized before the dummy circuit breaker is removed to isolate the cable. Deenergizing the unloaded bus of a lineup of metal-clad switchgear by withdrawing a dummy circuit breaker is an acceptable application. The limited length and very low capacitance of a switchgear bus structure keeps the charging current low enough to be successfully interrupted by withdrawing a dummy circuit breaker.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Voltage transformers: A set of three wye connected VT's or two open delta connected VT's can be switched with a rollout or tiltout without any interlocking of the secondary circuit. Control power transformers: A CPT up to 50 kVA single phase or 75 kVA three phase can be switched with a rollout or tiltout provided the carriage is interlocked so that the CPT must be unloaded before opening the primary device. The CPT may be mounted on the rollout or tiltout, or the rollout or tiltout may contain only the fuses for a stationary mounted CPT. Larger CPT's must be switched with some other mechanism, such as a load break disconnect switch. Capacitors: Rollouts or tiltouts must not be used to switch capacitors.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #22 Short Circuit Currents Crest, rms Symmetrical and rms Asymmetrical
December 4, 1991 The figure below shows a typical short circuit current wage form and defines the various component parts of this wave. At the moment of initiation of a short circuit the ac current wave, which is normally symmetrical about the zero axis BX is offset by some value, creating a waveform which is symmetrical about another axis, CC'. The degree of asymmetry is a function of several variables, including the parameters of the power system up to the point of the short circuit and the point on the ac wave at which the short circuit was initiated. In a 3-phase circuit, there is usually one phase which is offset significantly more than the other two phases.
It is convenient to analyze this asymmetrical waveform as consisting of a symmetrical ac wave superimposed on a dc current. CC' represents the dc current, and the value of that current at any instant is represented by the ordinate of CC'. The dc component of the current normally decays rapidly, and reaches an insignificant value within 0.1 s in most power systems. The rate of decay is a function of the system parameters. When the initial value of the dc current is equal to the initial peak value of the ac current, the resulting waveform is said to be fully offset, or to have a 100% dc component. It is possible, in some power systems, to have an offset in excess of 100%, which may result in a waveform that has no current zeros for one or more cycles of the ac power frequency. The ac component of the short circuit current will also decay, at a rate dependant on the system parameters. In general, the closer the fault is to generators or other large rotating machinery, the faster the decay will be.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #22 Short Circuit Currents Crest, rms Symmetrical and rms Asymmetrical
page 2 In the figure, IMC is the crest, or peak, value of the short circuit current. It is the maximum instantaneous current in the major loop of the first cycle of short circuit current. The rms symmetrical value of the short circuit current at any instant, such as EE', is the rms value of the ac portion of the current wave. Its value is equal to , and it is shown graphically by the distance from CC' to DD'. The rms asymmetrical value of the short circuit current is the rms value of the combined ac and dc waves, and it is calculated by the formula:
Powell Technical Brief #23 Using Design Tests to Qualify Several Ratings of Equipment
December 5, 1991 The many variations in construction and ratings encountered in the typical switchgear or motor control product line make the planning of design and conformance test programs quite complex at times. Of course, it is possible to run every test on every possible rating of equipment but such an extensive program is very expensive and is seldom required to fully document the performance of a product line. The ANSI standards for switchgear recognize this complexity and provide for the qualification of a piece of equipment for all lower ratings provided test results show it to be qualified for the highest rating for which it is used. Some of the conformance test standards in the ANSI C37.50 series discuss the principles of testing to qualify multiple ratings. These standards also give guidance in the grouping of equipment ratings for testing. A typical example of qualifying multiple ratings by a single test is the bus structure used in PowlVac metal-clad switchgear. This bus structure is the same for all voltage and short circuit ratings, varying only for continuous current ratings. To demonstrate the momentary and short-time current ratings of this bus structure, tests are performed on the bus with the lowest continuous current rating, 1200 A, which uses the smallest, weakest bars of any continuous current rating of PowlVac bus. The tests are performed at the maximum momentary current, 132 kA crest, and the maximum short-time current, 49 kA rms, required for any rating of PowlVac switchgear. It is fairly obvious that passing these tests qualifies the 1200 A bus for this rating and for all lower momentary and short-time current ratings. What may not be quite so obvious is that successful tests on the 1200 A bus also qualify higher continuous current ratings, such as 2000 A and 3000 A. These higher bus ratings are covered because they use larger bus bars, which are mechanically stronger and which have greater thermal capacity than the bus bars used in the 1200 A bus. The grouping of ratings and the selection of which rating to test requires a thorough knowledge not only of the standards but also of the particular product line being tested. The grouping of ratings may differ for different tests. It also may differ for different products, or different manufacturers offerings in the same product line. The example given in the previous paragraph is true for PowlVac switchgear, but may not necessarily be true for other manufacturers' similar products. Although Powell and many other manufacturers have used these principles in performing their design tests for many years, not everyone in the industry understands the concept. To aid in this understanding, all future Powell test reports will document the additional ratings covered by any test.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #24 Sizing Bus Bars in Switchgear and Motor Control
February 7, 1992 We occasionally get questions about how we select the size of bus bar for various continuous current ratings in Powell equipments. The answer is that we use temperature rise as the basic criterion. All of the ANSI, IEEE and NEMA standards for switchgear and motor control have requirements for the maximum operating temperature of various parts of the equipment. For bus bars, the requirement is generally for a temperature rise of no more than 65C, although this may vary for different classes of equipment. These requirements are designed to prevent overheating the insulation supporting and enclosing the bus bars, since excessive temperature shortens the life of the insulation. A number of factors affect the temperature rise of bus bars. Some of the major ones are:
Size and material (copper or aluminum) of the bus bar. Whether the bar is insulated. Surprisingly, a bus bar covered with insulation generally runs cooler than an equivalent bare bus bar, because the usually darker color of the insulating material is a better radiator of heat than the shiny surface of a bare bus bar. Size and material (magnetic or non-magnetic) of the enclosure around the bus. Flow of ventilating air past the bus bars or the bus enclosure. Proximity of other conductors and other heat-producing devices.
The complex interaction of these and other factors makes it nearly impossible to calculate temperature rise, and leads to the requirement in all applicable standards for continuous current tests to determine the temperature rise of a bus design. Specifications will sometimes call for bus sized by current density, a favorite requirement being 1000 A per square inch for copper bus. This may be a good way to choose bus sizes for the mythical "single conductor in free air", but it isn't a satisfactory way to design buswork in practical equipments. Consider the following chart, based on bus sizes used in our PowlVac metal-clad switchgear: Switchgear Bus Rating Number of bus bars per phase Size of bus bar, inches Cross section area of bus, square inches Current density, amps per square inch 1200 A 2000 A 3000 A 1 1 1200 1 3 667 2 6 500 1/4 x 4 1/2 x 6 1/2 x 6
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #24 Sizing Bus Bars in Switchgear and Motor Control
page 2 The last line of the chart shows that the temperature rises of the three bus ratings are almost identical in spite of the 2.4:1 ratio of the current densities.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Medium Voltage Switchgear and Breakers Altitude (ft)* 3300 (1000 m) (and below) 5000 (1500 m) 10,000 (3000 m) Voltage Current 1.00 0.95 0.80 1.00 0.99 0.96
You will notice that there are different altitudes given for low voltage and medium voltage. I have never been able to get a reasonable answer as to why this is true, and I understand that the committee responsible for the standards is reviewing these values with the idea of reconciling them. In all cases, the current correction factor is applied to the continuous current rating of the switchgear and the circuit breakers. This does not usually present a problem, as we seldom design a system with load currents over 95% of the equipment rating. The current derating does not apply to interrupting current or any of the other high-current ratings of the breakers.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #27 Testing of Switchgear and Motor Control Equipment
April 14, 1992 Although each particular product line is governed by its own industry standards, switchgear and motor control equipment of the types built by Powell are generally subject to three major categories of tests. As defined in ANSI/IEEE C37.20.2-1987 for Metal-Clad and Station-Type Cubicle Switchgear, these categories are: Design Tests: Tests made by the manufacturer to determine the adequacy of the design of a particular type, style or model of equipment or its component parts to meet its assigned ratings and to operate satisfactorily under normal service conditions or under special service conditions if specified, and may be used to demonstrate compliance with the applicable standards of the industry. Production Tests: Tests made for quality control by the manufacturer on every device or on representative samples, or on parts, or materials required to verify during production that the product meets the design specifications and applicable standards. Conformance Tests: Conformance tests demonstrate compliance with the applicable standards. The test specimen is normally subjected to all planned production tests prior to the initiation of the conformance test program. Typical design tests for equipment and circuit breakers will include continuous current (heat runs), momentary and short time current, low-frequency withstand (hipot), impulse withstand (BIL) for mediumvoltage equipment, and mechanical tests to demonstrate the effectiveness of interlocks. In addition, circuit breakers are subjected to a series of interrupting tests to demonstrate their ability to interrupt currents of various magnitudes, operational life tests, and several types of timing tests. Many of these tests are somewhat destructive, and therefore they are run on manufacturer's prototypes, not on production equipment which is supplied to customers. Conformance tests generally include certain of the design tests, chosen to demonstrate compliance with the standards. These tests are frequently used for third-party certification of a design. Production tests include hipot to demonstrate insulation integrity and mechanical and control circuit tests to demonstrate proper operation. In addition, circuit breakers receive timing tests to show proper closing and opening speed. Records of these tests, which Powell furnishes to customers on request, can be used as baseline data for future maintenance programs.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #27 Testing of Switchgear and Motor Control Equipment
page 2 Each type of test, and each test within a given type, has a particular part to play in the overall process of producing quality equipment properly rated for a user's needs. No single test demonstrates the proper design and operation of switchgear or motor control equipment. It takes a combination of tests to do the job properly.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #28 Short Circuit Current Levels Used to Test Various Types of Circuit Breakers
August 25, 1992 When applying interrupters of various types, it is important that we understand the meaning of the interrupting rating given to these devices. Consider, for instance, the methods of making interrupting tests on various types of circuit breakers. As the breakers get smaller and less costly, the test methods in the industry standards generally get less demanding. When testing the interrupting capability of a high-voltage (over 1000V) circuit breaker, the current measured is the actual fault current flowing through the circuit breaker at the moment of the interruption. To rate a breaker of this class as a 25kA interrupter, it must actually interrupt 25kA. Momentary and short-time current requirements of the switchgear are also based on actual current flowing during the test. The reference standards are ANSI/IEEE C37.04, C37.06 and C37.09 for the circuit breakers and C37.20.2 for the switchgear. For low voltage circuit breakers, this requirement changes to rating by prospective current. The test terminals of the laboratory source are short-circuited, as indicated by point A in Figure 1, and the required current flow is established. That short circuit is then removed and the equipment to be tested is connected to the test source. A short circuit is then applied to the equipment and the test made. The location of the short varies with the type of circuit breaker or equipment being tested:
Figure 1: Fault Locations for Testing Low Voltage Equipments (A) Low Voltage Power Circuit Breakers (B) Molded Case Circuit Breakers (C) Low Voltage Motor Control Centers
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #28 Short Circuit Current Levels Used to Test Various Types of Circuit Breakers
page 2
For a low voltage power circuit breaker, the fault is placed at the load terminals of the breaker, at point B in Figure 1. The reference standards are ANSI/IEEE C37.13 for the circuit breakers and C37.20.1 for the switchgear equipment. For a molded case circuit breaker, the fault is also placed at the load terminals of the circuit breaker, at point C in Figure 1. However, 4 feet of appropriately-sized conductor may be included between the test station terminals and the line terminals of the circuit breaker under test. The reference standard is UL 489. For a typical combination motor starter unit in a motor control center, the fault is placed at the end of 4 feet of appropriately-sized conductor connected to the load terminals of the starter unit, at point D in Figure 1. The reference standard is UL 845.
At each step of this chain, impedance is added to the test circuit, reducing the actual fault current the circuit breaker is required to interrupt. Several papers presented at recent IEEE conferences have raised questions about the adequacy of equipment certified to some of these test standards to interrupt all possible faults downstream of the circuit breaker. At least two IEEE subcommittees are discussing this matter.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #29 Interchangeability of Drawout Circuit Breakers in Switchgear Assemblies
August 28, 1992 One of the key features of switchgear assemblies using drawout circuit breakers is the interchangeability of circuit breakers within an assembly. This feature allows users to make use of spare circuit breakers to replace circuit breakers which must be taken out of service for maintenance, minimizing down time when a circuit breaker problem occurs. The ANSI standard for Metal Enclosed Low Voltage Power Circuit Breaker Switchgear, ANSI/IEEE C37.20.1, addresses interchangeability in 6.11.4. This section requires that "All removable elements of the same type and rating on a given assembly shall be physically interchangeable in the corresponding stationary housings. This need not include electrical interchangeability of electrical control circuits." Switchgear of this type and the circuit breakers used in it typically have mechanical interference mechanisms for breakers of the same physical size but of different ratings. These mechanisms typically prevent interchanging breakers if either the frame size (maximum continuous current rating) or the interrupting rating differ. Trip device characteristics and ratings and electrical accessories available on this class of circuit breaker are so numerous and changeable that no attempt is made to prevent interchangeability of breakers with differences in these features. The ANSI standard for Metal Clad Switchgear, ANSI/IEEE C37.20.2, addresses interchangeability in 6.2.5. This section requires that "All removable elements of the same type and rating on a given assembly shall be physically and electrically interchangeable. Removable elements not of the same type and rating shall not be interchangeable." Since the breakers used in this class of switchgear are not provided with variable trip devices or very many optional electrical features, this is seldom a problem. Occasionally, however, a user desires to have some electrical accessory on some but not all breakers of a given rating in a particular assembly. Most commonly, this is an undervoltage device, which may be required on motor feeder breakers but not on other breakers of the same rating. When this occurs, the easiest way to solve the problem is to furnish the required modification on all breakers of that rating in the assembly. If this is not acceptable to the user, it may be necessary to make specific modifications to the control circuitry of the breaker with the accessory to prevent breaker interchangeability.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #29 Interchangeability of Drawout Circuit Breakers in Switchgear Assemblies
page 2 As part of the standard design of our PowlVac circuit breakers, we provide interference mechanisms which prevent a breaker with a lower rating from being used in a cell with a higher rating, but allow a higher-rated breaker to be used in a lower-rated cell. While this feature is not strictly in accordance with the ANSI requirements, it allows users to minimize the number of spare circuit breakers required to replace all breakers in the assembly without using any breaker in a cell where it would not meet the needs of that circuit.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
In general, static devices are more accurate and more repeatable than the equivalent electromechanical devices. A single static device can perform the functions of many electro-mechanical devices. Equivalent functions can often be obtained at lower cost, particularly if a multi-function device is used. Some functions or operating characteristics which are not possible with available electromechanical devices can be done with static devices. Static devices can be provided with communications capability which is not available in electromechanical devices. Static devices can be made highly resistant to corrosive or dirty atmospheres.
However, not every engineer is happy with the idea of relying on static devices for protection functions. Some of the reasons are:
Possibility of total failure of the protective system due to failure of one component on the critical path, such as a common power supply. Long-term familiarity and satisfactory experience with electro-mechanical devices. Lack of service capabilities for static devices. Existing company standards. Concerns about possible failure in adverse environments, both physical and electrical.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
A highly distorted voltage wave can have a peak value much greater than the peak value of a sine wave of the same rms value. The repeated application of a higher peak value may result in premature failure of the insulating systems in the switchgear. Since the effective resistance of a conductor goes up as frequency rises, a current wave rich in harmonics may cause greater heating in the switchgear power conductors than a sine wave of the same rms value. However, since we seldom load switchgear to its maximum continuous current rating, this effect will probably not be a problem. Circuit breakers interrupt current flow at a current zero. A badly distorted current wave may contain current zeroes at locations other than the normal zero of the fundamental sine wave. If present, these spurious current zeroes could cause premature interruption and restrike during a circuit breaker opening operating. The effect of harmonics on the operation of protective and metering systems is not fully documented. Thermal devices, such as fuses or thermal elements in circuit breakers, are inherently rms sensing, as are many modern solid-state protective packages, but the heating effect of a harmonic-rich current on the protected load may require a different level of protection. Other relays may be designed to operate on certain selected frequencies and may thus operate incorrectly in the presence of a significant level of harmonics. Fortunately, high fault currents are generally not severely distorted, as the limiting impedance is that of the power system, and a level of harmonic current which may be quite significant when compared to load current is much less significant when compared to fault current.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #32 Replacing Older Medium Voltage Circuit Breakers with Vacuum Circuit Breakers
October 19, 1992 Many older installations of metal-clad switchgear are candidates for modernizing or upgrading. The interrupting duty may have grown past the interrupting capacity of the existing circuit breakers, maintenance costs may be getting out of hand, or circuit breaker parts may no longer be available. Modernization may be accomplished by either of two methods, conversion of the existing equipment or replacement of the circuit breaker with a new, modern vacuum breaker. In some cases, modernization may involve conversion of the switchgear equipment and replacement of the circuit breaker. Modernization may also involve an increase in one or more ratings of the switchgear and/or circuit breaker. Powell offers a series of PowlVac circuit breakers, both conversions and replacement breakers, to aid in modernization. In any case, users should insist that modernization be done in accordance with applicable industry standards to insure that the modernized switchgear meets the required ratings. For replacement circuit breakers, this is fairly simple. The breakers should be tested in accordance with ANSI/IEEE C37.09-1979 and ANSI/IEEE C37.20.2-1987, just like any other new circuit breaker that is used in metal-clad switchgear. The only caution is that certain tests, including continuous current, momentary current, and BIL, should be performed in a switchgear cell of the basic design in which the breaker will be used. All of these tests involve interaction between the cell and the circuit breaker. For instance, we have performed full wave impulse (BIL) tests where both the breaker alone and the cell alone passed the test, but the combination would not pass, requiring additional work to the breaker to achieve the desired result. A new ANSI standard, ANSI/IEEE C37.59-1991, IEEE Standard Requirements for Conversion of Power Switchgear Assemblies, covers conversion of both switchgear equipments and power circuit breakers. This standard specifies the design and testing requirements for conversion, including uprating, of existing equipment. Requirements for new documentation, including nameplates and instructions, are included. Any user considering converting low-voltage or medium-voltage switchgear equipment should review this standard and insist that vendors conform to it. Powell, through our Powell Apparatus Service Division, offers both conversions and replacement breakers meeting these standards.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
True bus differential relaying compares all currents entering and leaving a switchgear bus. Within the limits of the accuracy of the CT's and the relays, true bus differential relaying will detect all faults on the protected bus. Since all currents are taken into account, the relays can be very fast. However, bus differential relaying provides no backup to the feeder overcurrent relaying, so additional overcurrent relays are required on main and tie breakers to provide this backup function. Also, high speed bus differential relaying can be quite expensive, and many switchgear users do not feel that it is economically justified. Partial differential relaying sums the currents entering or leaving a switchgear bus through main and tie breakers. If a fault exists on the protected bus, the currents will add in the relays, but if fault current is flowing through the bus to a fault on another bus, the currents will subtract and the relays will not respond. If the fault is on a feeder, the partial differential relays will act as backup to the feeder overcurrent relays.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Trip currents of modern medium voltage circuit breakers may be much lower than those of older breakers. For instance, at 125 V dc, typical trip currents are now in the 3A range, with some breakers drawing only a little over 1 A. Trip times are faster than in the past. Figure 1 is the trace of the trip current of a typical PowlVac circuit breaker. You will see that the duration of the trip current is about 41 or 42 ms, or 2 cycles on a 60 Hz basis. The target relay takes about 1 cycle to pick up.
Trip current rises slowly, barely reaching its nominal rating before being cut off, as seen in Figure 1. Some faults may cause the closure of two or more relay contacts at the same time, paralleling the target coils of these relays and reducing the current through each one. One manufacturer recommends expecting two relays to close simultaneously on time delay relays and three on instantaneous relays with target coils. (Note: The instantaneous elements on most 50/51 relays have mechanical targets, and are not a problem.) Thus, the selected tap on the target coil should operate properly on no more than half of the rated trip current of the breaker.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
The insulation is extremely rugged and has excellent dielectric properties. Conductors of any size and shape can be coated with equal ease. Using extruded rigid tubing limits the choice of conductor cross-sections to those for which the extruded tubing is available, which may not be the optimum size from a current-carrying or electric field standpoint. Already-bent bars can be coated, eliminating the need for tape or boots at bends. Unlike some heat-shrink tubings, the insulation conforms to the bar at all angles and bends. Heatshrink tubing may pull away from the bar at the inside of a bend. Since the coating conforms to the surface of the bus, there is no possibility of setting up a partialdischarge cell between the surface of the bus and the insulation. This is especially important at voltages above 15 kV.
We believe that this new insulating process is another step in our process of continuous improvement of Powell switchgear.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #37 Testing for Loss of Vacuum in Vacuum Interrupters
March 5, 1993 In the 30 years or so that they have been used in circuit breakers, vacuum interrupters have proved to be extremely rugged, reliable devices. However, like any man-made device, they can fail. A frequentlyasked question is "How can I tell if my vacuum interrupter has lost vacuum?" Modern vacuum interrupters are evacuated to a pressure on the order of 10-7 Torr. A Torr is the pressure exerted by 1 mm of mercury, or 1/760 of a standard atmosphere. 10-7 Torr is approximately equal to the pressure of the atmosphere on the surface of the moon. Testing by manufacturers of vacuum interrupters shows that the vacuum interrupter will still interrupt its rated interrupting current at a pressure <= 10-3 Torr, but at pressure above 10-3 Torr is interrupting capability falls off. Thus, a successful loss of vacuum test must detect the difference between pressures above and below 10-3 Torr. An ideal loss of vacuum test would be an on-line test that constantly monitored the pressure within the vacuum interrupter and alarmed when this critical pressure was approached. Unfortunately, no such device is presently commercially available. The present state of the art leads Powell to recommend the use of a high voltage test across the contacts of an open vacuum interrupter. This test should be at least 25 kV, 50/60 Hz, or the equivalent dc voltage, 35 kV(1). A breakdown on this test indicates a loss of vacuum in the interrupter. If dc is used in this test, it must be supplied from a full-wave rectifier. The use of a half-wave in the power supply can lead to applying excessive dc voltage to the vacuum interrupter. In all cases, the manufacturer's instruction book for the circuit breaker should be consulted for proper procedure and cautions before making the test. At least one switchgear manufacturer is stating that loss of vacuum can be detected by disconnecting the movable contact of the vacuum interrupter from the mechanism and manually pulling on the movable contact. Atmospheric pressure (760 Torr) on the exposed side of the movable contact pushes the contact closed with a force proportional to the area of the contact. This force is about 40 pounds for a typical vacuum interrupter used in our PowlVac ( circuit breakers. If there is a complete loss of vacuum, this 40-pound force disappears, and a pull test will certainly be effective. However, partial loss of vacuum in the 10-2 Torr pressure range puts the vacuum interrupter at risk of not performing properly, but decreases the 40-pound force by only a fraction of an ounce. This minor change in contact loading would hardly be detectable by a good force gauge, much less by feel. Powell therefore does not recommend this pull test as a satisfactory loss of vacuum test. (1) revised 6-4-93
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #38 Using Switchgear at Frequencies Other Than 60Hz
April 21, 1993 All ANSI circuit breaker and switchgear equipment standards specify a rated frequency of 60 Hz, and all Powell switchgear is designed for and tested at 60 Hz. The nameplates of PowlVac circuit breakers carry a rated frequency of 60 Hz. However, many applications of Powell switchgear are made at other frequencies, particularly 50 Hz, and users may question the suitability of the circuit breakers and equipment at other frequency. The following paragraphs discuss the effect of frequency on various major characteristics of switchgear. BIL: Since the BIL rating is the ability to withstand a dc impulse, power system frequency has no effect on the BIL rating of switchgear equipment. Power Frequency Withstand: Although this rating is best demonstrated by a test at rated frequency, ANSI/IEEE C37.09 allows the test to be made at rated frequency 20%. This allows 50 Hz tests to establish a 60 Hz rating, and vice versa. Since the voltage level is the same, regardless of frequency, and the rate-of-rise of the voltage increases with frequency, the higher frequency test is slightly more severe than the lower frequency test. Thus, an equipment which is tested at 60 Hz is satisfactory at any lower frequency. Continuous Current: The ac resistant of a conductor, and thus the heat loss at a given current, increases with frequency. The ANSI standards require continuous current test to be made at a frequency no lower than the rated frequency. The standards actually allow the assigning of a higher continuous current rating at very low frequencies, such as 25 Hz. Momentary, Short Time and Interrupting Currents: Again, ANSI/IEEE C37.09 allows these test to be made at rated frequency (20%, so tests at either 50 Hz or 60 Hz can cover both frequencies. For lower frequencies, it may be necessary to derate the interrupting capacity of vacuum interrupters. One of Powell's vacuum interrupter suppliers has tested at various frequencies and suggests the following derating formula:
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #38 Using Switchgear at Frequencies Other Than 60Hz
page 2 Where = power system frequency, 16 2/3Hz <= f < 50 Hz = short circuit current at frequency f = short circuit current at 60 Hz Summarizing, switchgear equipment and power circuit breakers rated 60 Hz may be applied at 50 Hz without changing ratings. At lower frequencies, some derating of interrupting capacity may be required, and some increase of continuous current rating may be possible. Of course, devices in the switchgear, such as relays, instruments and instrument transformers, must be checked for application at the power system frequency.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Use a thermal-magnetic circuit breaker rather than an MCP. NEC 430-52, Exception No. 2C, allows an inverse time circuit breaker rated up to 400% of the motor full load current to be used for motors with less than 100A full load current. Small circuit breakers, up to 150A rating, have fixed instantaneous settings, with minimum pickup varying from 7.5 to 12 times rated current, so the instantaneous pickup can be from 30 to 48 time the motor full load current, rather than the 13 times required for an MCP. You have degraded the protection of the circuit, but you have met the Code. A fine print note in NEC 430-52 allows an instantaneous trip circuit breaker to include a damping means to accommodate a transient motor inrush current without nuisance tripping of the circuit breaker. If you can find one of these, you can use it, but so far as we know, no such device is commercially available.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Use a fused switch instead of a circuit breaker to supply your motor circuit, and find a fuse that meets the requirements of 430-52 and still allows you to start the motor. Ignore the NEC. Not a recommended move, but I understand that it is being done.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #40 Temperature of Cable Terminations and Cable Compartments in Switchgear
April 23, 1993 One of the important features of almost all low-voltage and medium-voltage switchgear is provision for terminating power cables. Power cables are sensitive to the temperature of the surrounding air, and must be chosen carefully to operate in the various environments in which they are installed. A single run of power cable may pass through several different environments, and the effect of each environment on the cable selection must be considered. One of these environments may be within the switchgear cable area. In metal-enclosed switchgear, power cables usually terminate on buswork, not directly on the terminals of the main switching device. This is in contrast to panelboard, switchboard and motor control center construction, where power cables may terminate on the terminals of molded-case circuit breakers or starters. The allowable temperature rise of the connections to insulated cables and the allowable temperature of the air surrounding these cables is given in the ANSI switchgear standards, ANSI/IEEE C37.20.1 for low-voltage switchgear, ANSI/IEEE C37.20.2 for metal-clad switchgear, and ANSI/IEEE C37.20.3 for metal-enclosed interrupter switchgear. All three of these standards require the same temperature for these features. 4.5.5 of each of these standards limits the temperature of the air surrounding insulated power cables to 65C, when the switchgear assembly is equipped with devices having the maximum current rating for which the assembly is designed, is carrying rated continuous current, and is in an ambient temperature of 40C. Table 4 of each standard limits the temperature rise of silver or tin-surfaced connections to insulated cables to 45C, or a total temperature of 85C. The tests to demonstrate conformance with these limiting temperature rises require including appropriate sizes and lengths of power cables in the continuous current path. When cables are connected to metal-enclosed switchgear, the cable selection must take into account the air and terminal temperatures encountered in the switchgear.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #41 Plating of Contact Surfaces in Switchgear and Circuit Breakers
June 3, 1993 The various ANSI standards covering metal-enclosed switchgear and circuit breakers used in this switchgear prescribe temperature rise limits for various parts of the equipment. Included are limitations for buses with plated and unplated joints in switchgear, and for plated and unplated contacts and connections in circuit breakers. In all cases the temperature rise allowed is considerably higher for plated connections than it is for unplated connections. Typically, the limit for unplated copper connections is 30C rise, while the limit for plated connections is 65C rise. The higher temperature rise is allowed for plated connections because plated copper does not oxidize nearly as rapidly as bare copper. Copper oxide is not a good conductor, and once the oxide forms, the resistance and the temperature rise of the conductor usually increase rapidly. Since limiting the temperature rise is 30C would require manufacturers to double the amount of copper used, joints are almost universally plated. The two materials commonly used for plating are silver and tin. The standard for high voltage circuit breakers speaks of "silver, silver alloy, or equivalent" surfaces, with "equivalent" being undefined. This standard was last revised in 1979. The low-voltage and medium-voltage switchgear standards, revised in 1987, speak of "silver surfaced, tin surfaced, or equivalent" connections. Which material is better, silver or tin? At Powell, we generally use silver, particularly for sliding contacts. Silver plating is harder than tin plating, and withstands the stress of a moving joint, such as a hinge point or a primary disconnect, better than tin plating. However, tin plating is superior in certain industrial atmospheres, such as those containing hydrogen sulfide. On request, Powell will provide tin plating on the connections of the bus bars in equipments. For various technical and manufacturing reasons, it is not practical to substitute tin for silver on surfaces within circuit breakers, or on circuit breaker primary disconnects. If the atmosphere attacks silver surfaces, they should be coated with contact lubricating grease to prevent corrosion problems.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #42 Momentary Rating and Construction of Bus in Metal-Enclosed Switchgear
June 4, 1993 The bus in metal-enclosed power switchgear is required by ANSI standards to have a momentary current rating equivalent to the momentary rating of the circuit breaker, switch or fuse used in the particular switchgear equipment. In the case of low voltage switchgear, where the circuit breaker momentary rating may vary with the breaker frame size, a particular assembly is required to have the momentary rating of the smallest frame size of circuit breaker used in the assembly. Thus, if the circuit breakers or other switching devices are properly applied, the equipment momentary will match both the needs of the system and the rating of the switching device. Where bus duct is used in conjunction with metal-enclosed switchgear, the bus duct momentary rating should match that of the switchgear. Momentary ratings are normally proved by high current testing. The bus must withstand the test without any permanent deformation of the bus bar, of if there is permanent deformation, it must not be sufficient to prevent the equipment from passing its standard dielectric tests (hipot and impulse). There also must be no breakage of the bus supports. There are a number of design variables that enter into the ability of the bus structure to withstand a momentary current. The forces involved are quite high. For a bus consisting of one " x 4" bar per phase, on 6" phase centers, a 50 kA current creates a force on each bus bar of nearly 17,000 pounds per foot of length. Both the bus supports and the bars themselves must withstand this force. The force is directly proportional to the square of the current and inversely proportional to the phase spacing, so moving the bus bars apart decreases the force. The force is also affected to a small degree by the dimensions and shape of the bus bars. The ability of the bars to withstand the force created by the momentary current is a function of the size, shape, and material of the bar and the arrangement of the bars with respect to each other, i.e., flat-to-flat or edge-to-edge. In mechanical terms, these determine the section modulus of the bars in the phase-tophase direction. The deflection of the bars is also affected by the length of the span, or the distance between supports. The strength of the bus support structure is determined by the material and configuration of the supports and the distance between them.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #42 Momentary Rating and Construction of Bus in Metal-Enclosed Switchgear
page 2 The standards require test to demonstrate the momentary rating of the bus, and most bus structures within switchgear are somewhat complex and not subject to easy analysis, so we seldom use calculations for the design of bus structures. However, for relatively simple bus configurations, such as bus duct, it may be easy to modify a design based on previous test data. For instance, if phases are spread apart further than they were in the tested sample, the allowable increase in spacing between supports can be easily calculated.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
11
In the 1979 edition, device 7 was an anode circuit breaker, a device frequently used in mercury arc rectifier equipments but no longer seen in this day of solid state rectifiers. In the 1987 edition, device 7 was "Reserved for future application." In the 1991 edition, device 7 is used for a rate-of-rise current relay. For many years, the description of device 50, which is commonly thought of as an instantaneous overcurrent relay, included the rate-of-rise feature. This feature is no longer part of device 50's description. In 1979, device 11 was reserved for future application. Beginning with the 1987 edition, device 11 became a multifunction device. This is defined as a device with three or more important functions. Typical use would be for a multifunction motor protective relay. When device 11 is used, the functions included in it should be defined in the drawing legend.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
24
In 1979, device 24 was reserved for future application. Beginning with the 1987 edition, device 24 became a volts per hertz relay. These relays are typically used to protect large generators from overvoltage during subsynchronous operation, and are seldom seen in Powell switchgear. I mention it because there are still those among us who remember the use of 24 for a bus tie circuit breaker. In the standard, the proper number for a bus tie breaker has been 52BT since some time in the 1950's, but we still see the designation 24 from time to time. Up through 1979, device 47 was a phasesequence voltage relay. Starting with the 1987 edition, this definition was expanded to read phase-sequence or phase-balance voltage relay, and the description specifically lists negative phase sequence overvoltage as one of its applications. See device 7. Up through 1987, device 82 is described as a dc reclosing relay. In the 1991 edition the description is expanded to read dc loadmeasuring reclosing relay.
47
50 82
Some other changes were made, but these are the ones most likely to affect switchgear for utility and industrial distribution systems.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #44 Preparing Foundations for Indoor Installation of Switchgear
August 2, 1993 Nearly every manufacturer of switchgear and motor control equipment will tell users that the equipment must be installed on a level foundation. If the equipment includes drawout circuit breakers or contactors, most manufacturers will recommend that steel channels or rails be imbedded in the floor to provide support and a level surface. These recommendations lead inevitably to two questions: "How level is level?" and "Do I really have to install the floor steel?" The quick answers to these are "Damn flat!" and "No, but you'll be sorry if you don't." Some smaller equipments, like low voltage motor control centers and switchboards, either come with their own built-in base channels or are not terribly sensitive to slightly uneven floors. For larger equipments, however, a level floor is absolutely necessary to maintain the critical alignment of drawout devices. Manufacturers have been rather shy about putting a tolerance on "level" over the years, but the lore in the industry seems to be that a one-eighth inch slope, evenly spread over the front-to-back or the end-to-end dimension of the lineup, is tolerable. For indoor equipments without built-in bases, maintaining such a tolerance almost certainly requires carefully installed floor channels. Once you decide that floor steel is required, here are a few cautions about using it:
Be sure to locate the channels where the manufacturer shows them. Normally, each lineup has a channel near the front of the gear and another near the rear of the gear. These are usually located under the bolt-down holes in the equipment, so their location is important. Frequently, in deep switchgear, such as PowlVac metal-clad switchgear, a third channel is shown somewhere between the first two. Often, this channel does not match any bolt-down holes, so its location may not seem to be as important as the location of the other two channels. However, the manufacturer may have located this channel under some feature of the design which need good support, so its location may be as important as the locations of the other two channels. The concrete needs to be no higher than the floor steel. If the circuit breakers roll out on the floor, the floor on the drawout side of the switchgear needs to be flush with the top of the floor steel so the breakers will roll in and out smoothly. Once a level surface is established by the floor channels, be sure that the equipment sits flush on the surface of the channels. This may seem elementary, but I have seen installations where one side of a 36" unit was flush with the channel and the other side was " above the channel. All the effort and expense put into the level floor channels was negated by a poor installation of the equipment on the channels.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #45 MVA Interrupting Rating of Circuit Breakers Used in Metal-Clad Switchgear
September 22, 1993 Modern medium voltage circuit breakers used in metal-clad switchgear have no MVA interrupting rating. Undoubtedly, this statement will come as a surprise to some readers of this PTB. Although it is quite common for all of us to talk about 500 MVA circuit breakers or 1000 MVA circuit breakers, this rating does not appear anywhere in the ANSI standards applying to these breakers, nor does it appear anywhere on the nameplate of the breakers. A little history is in order. The first ANSI standards covering circuit breakers, including those for use in metal-clad switchgear, were developed about 50 years ago. Under these standards, interrupting ratings were based on the total current interrupted, including the dc component. These "total current" standards included ANSI C37.4 through C37.9 and C37.12. In the rating structure used in these standards, MVA was included, and those of us who date back to that era got used to referring to breakers by their MVA rating. In 1964, a new series of ANSI standards were first published. These standards used symmetrical, rather than total, current as the basis for interrupting rating. These new standards no longer referred to MVA in their rating structure. The interrupting rating in these standards is expressed kiloamperes. After a couple of decades of development, these standards now include six documents:
ANSI/IEEE C37.04-1979 Rating Structure ANSI C37.06-1987 Preferred Ratings ANSI/IEEE C37.09-1979 Test Procedure ANSI/IEEE C37.010-1979 Application Guide - General ANSI/IEEE C37.011-1979 Application Guide - Transient Recovery Voltage ANSI/IEEE C37.012-1979 Application Guide - Capacitance Current Switching
However, so that manufacturers would not have to retest all their breakers, certain equivalences were established, and for a few years the preferred rating tables carried "nominal" MVA ratings for "identification". This last appeared in the 1971 edition of ANSI C37.06, but was missing from the 1979 edition. Unfortunately, we have continued to use these identifications informally, and sometimes we get wrapped around the axle about just what they mean, particularly when applied to circuit breakers used at a voltage considerably less than their rated maximum voltage, such as 4760 V breakers used at 2400 V. The chart below compares the nominal MVA ratings to the actual MVA ratings calculated using the rated interrupting currents established in the current standards.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #45 MVA Interrupting Rating of Circuit Breakers Used in Metal-Clad Switchgear
page 2 Rated Maximum Voltage kV, rms 4.76 Rated Short Circuit Current kA, rms 29 250 System Operating Voltage kV, rms 4.76 4.16 2.4 4.76 4.76 41 350 4.16 2.4 8.25 8.25 33 500 7.2 6.6 15.0 15.0 18 500 13.8 11.5 15.0 15.0 28 750 13.8 11.5 15.0 15.0 37 1000 13.8 11.5 Interrupting Current @ Operating Voltage kA 29 33 36 41 47 49 33 38 41 18 20 23 28 30 36 37 40 48 Actual MVA @ Operating Voltage(1) MVA 239 238 150 338 338 204 472 472 469 468 478 458 727 717 717 961 956 956
Nominal MVA
(1) Slight variations in MVA may be due to rounding of interrupting current values.
If you are interested in the development of these standards, a good history of these standards appears in the forewords of the various documents.
This formula yields a constant MVA interrupting rating, equal to the square root of three times VI, between V and V/K, and a constant current interrupting rating, equal to KI, at voltages below V/K. Two things need to be said about the K factor. First, the concept agrees with the physical reality of oilblast and air-magnetic circuit breakers. Breakers using these technologies really do have higher interrupting ability at lower voltages, and assigning a K factor other than one allows a wider application of a given circuit breaker. However, circuit breakers using vacuum or SF6 puffer interrupters are essentially constant current interrupters up to a limiting maximum voltage, so a K factor other than one does not match the physical attributes of circuit breakers using these technologies. In the latest (1987) edition of ANSI C37.06, K has been set to 1.0 for all circuit breakers except indoor oilless circuit breakers, which are the breakers used in metal-clad switchgear.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #48 Temperature Rating of Conductors Connected to Molded Case Circuit Breakers
December 2, 1993 Books can be written, and probably have been written, on the subject of proper sizing of conductors to meet all the various requirements of the National Electrical Code. This PTB will address one small facet of that overall problem: the temperature rating of conductors connected to the terminals of molded case circuit breakers. The NEC, as a general principle, requires most material used in electrical systems to be listed by a thirdpart certifier, such as UL, and to be installed in accordance with the conditions attached to that listing. In UL's Electrical Construction Materials Directory ("Green Book") we find the following conditions attached to the listing of circuit breakers: 2. Circuit breakers with a current rating of 125 amperes or less are marked as being suitable for 60C, 75C only, or 60/75C rated conductors. It is acceptable to use conductors with a higher insulation rating, if the ampacity is based on the conductor temperature rating marked on the breaker. 3. Circuit breakers rated 125 amperes or less and marked suitable for use with 75C rated conductors are intended for field use with 75C rated conductors at full 75C ampacity only when the circuit breaker is installed in a circuit breaker enclosure or individually mounted in an industrial control panel with no other component next to it, unless the end use equipment (panelboard, switchboard, service equipment, power outlet, etc.) is also marked suitable for use with conductors rated 75C. 4. A circuit breaker with a current rating of more than 125 amperes is suitable for use with conductors rated 75C. In view of these rules, you might ask why anyone would want to use conductors with a higher temperature rating than the breaker rating, when these higher rated conductors are presumably more expensive than lower rated conductors. Outside of the possibility of convenience (the 90C wire was laying around doing nothing), you may find that other derating factors applying elsewhere in the conductor run will reduce the allowable ampacity so that the 60C or 75C rating at the terminal is met without difficulty. As an example, a #4/0 AWG copper conductor with 90C insulation has an ampacity of 260 A per Table 310-16 of the NEC. However, if you connect this conductor to a molded case circuit breaker terminal, its ampacity is limited to the ampacity of the same size conductor with 75C insulation, or 230 A. The MCCB terminal temperature rating is the limiting factor in this conductor application. Now, let's look at a circuit with two of these conductors per phase in parallel, with all size conductors run in the same conduit. Note 8 to Table 310-16 requires an adjustment of the ampacity to 80% of the ampacity listed in the table when there are 4 to 6 current carrying conductors in one raceway.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #48 Temperature Rating of Conductors Connected to Molded Case Circuit Breakers
page 2 The two 90C cables now have an ampacity of 2 x 260 x 0.8 = 416 A. At the MCCB terminals, the allowable current is twice the 75C rating of the cable, or 460 A. Now the MCCB terminal temperature is no longer the limiting factor, and the use of the 90C insulation is advantageous. If 75C insulation were used, the wire size would have to be 250 kcmil to carry 408 A, and the conduit size would have to be increased from 2" to 3".
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #50 NEC Article 384 Switchboards and Panelboards
December 10, 1993 Every three years the National Electrical Code is revised, and a cottage industry springs up to inform all of us about the changes made in the new version of the Code. However, sometimes when you are looking for the intent for the detailed meaning of a particular section of the Code, it is just as useful to know what proposed changes were not made, and why the code-making panel rejected the proposal. This information appears in the NFPA Technical Committee Report (TCR), which is issued during each code cycle. In this document, each proposal for revision of the NEC is reproduced, along with the panel's action and the panel's reason for taking that action. In the 1992 TCR, which preceded the 1993 revision of the NEC, there were two interesting rejected proposals with regard to 384-4 - Installation. The first of these suggested adding the following text: "Where water sprinklers are in a position where they can deliver water to service equipment or service bus duct, then that service equipment and service bus duct shall be rated as raintight." The code-making panel unanimously rejected that proposal, with the following comment: "Experience has proven that if a fire activates sprinklers, the sprinklers, if properly installed and maintained, provide effective protection with virtually no hazard to personnel and with no measurable increase in damage to the equipment as compared with the damage done by heat, flame, smoke and the manual hose streams." The other proposal suggested removing the words "foreign to the electrical equipment" from the text of the section. The proposer's substantiation was: "This particular sentence in the 1990 NEC as written can be interpreted as permitting the installation of a dry type, floor mounted transformer below a panelboard. The transformer is equipment not foreign to the electrical equipment (panelboard), thus permitting the installation below the panelboard." The code-making panel also unanimously rejected the proposal, with the comment: "Such a transformer not being foreign to electrical equipment is permitted in the dedicated panelboard space provided it does not intrude into the 110-16 work space."
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #50 NEC Article 384 Switchboards and Panelboards
page 2
Figure 1 shows three examples of a transformer located near a panelboard. View 1, with the transformer mounted below the panelboard, is not permitted, as the transformer intrudes into the work space required by 110-16 of the NEC. Views 2 and 3 are both installations permitted by the NEC. In View 2, the transformer is located above the work space, which only extends up to 6 feet from the floor. In View 3, the panelboard has been mounted away from the wall so that the transformer does not extend into the work space. Note that the "dedicated space" above and below the panelboard is the width and depth of the panelboard and extends from the floor to a point 25 feet above the floor, or to the structural ceiling, whichever is lower. A typical hung ceiling of drop-in panels is not considered to be a structural ceiling for this purpose.
Properly secured doors, covers, etc., do not open. Parts which may cause a hazard do not fly off. Arcing does not cause a hole in the surfaces covered by the type under test. Black cotton cloth indicators are placed around the equipment under test, up to a height of 2 meters, wherever flame or hot gases might escape. These indicators must not ignite. The grounding connection must remain effective.
When applying arc resistant switchgear, several items need to be kept in mind:
The arc-resistant rating is at a particular voltage and short-circuit current level. These ratings should match the ratings of the switchgear and circuit breakers, and the requirements of the system. The area of exposure should be considered. See descriptions in Table 1.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Restricted to authorized personnel only. Test Front. Arc-resistant construction at the Test sides which are readily front only. accessible. Unrestricted accessibility, including general public. Test all accessible sides. -------------------------Arc-resistant construction at the front, back and sides. Arc-resistant construction at the front, back and sides, and between compartments within the same cell or between cells. 160 ms 1 second 10 cm from unit (all types) Type B: 10 cm from unit Type A: 150 grams per square meter Type B: 40 grams per square meter
Duration of Tests: Pressure 0.1 second (100 ms) Withstand Duration of Tests: 1 second Burnthrough Type A: 30 com from unit Indicator Location
Note: Thanks to Crouse-Hinds for the information calling industry attention to this situation.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Proper assembly of the hardware is vital to a low-resistance joint. The hardware should be assembled as shown in Figure 1, with the flat washers next to the bus bars on both sides of the joint and the lock washer under the nut. The bolt should be long enough that a minimum of two full threads extend out of the nut when the bolt is tightened. For the 1/2-13 size, use a bolt one inch longer than the combined thickness of the bus bars being bolted together. Other bolt sizes may take longer or shorter bolts to compensate for differences in the thickness of the nuts and washers used. The bolt should not be longer than necessary, either, as extra bolt length usually decreases the clearance from the bolt end to the nearest other phase or to ground. Proper bolt torque is vital to a good joint. Grade 5 hardware is used to allow high installation torque. Torques to be used for various size bolts are shown in the table. This information is given on a label installed in Powell switchgear near bolted field connections. Do not overtorque the bolts. Excessive torque can stretch the bolt past its elastic limit and cause failure. I've seen bolts which were barely half their original diameter in the middle removed from bus joints. 5/8 - 11 1/2 - 13 3/8 - 16 1/4 - 20 Bolt Size 5-7 Torque, pounds-feet 55-70 35-50 20-30
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #54 Arc Resistant Switchgear Construction or Arc Detection Devices?
November 16, 1994 In PTB 51, I discussed the arc resistant construction which is now available in Powell's PowlVac metalclad switchgear. As noted in the PTB, arc-resistant switchgear must resist two phenomena - increased internal pressure and burnthrough. These two phenomena operate in two different time frames. Burnthrough is a relatively long-time event. The test to prove resistance to burnthrough is of 1 second duration. Internal pressure, on the other hand, reaches its peak in 5 to 10 milliseconds after the arc begins. Any damage that is going to be done by the pressure wave will happen in that time frame. For instance, in one of our first tests of a preliminary arc resistant design, the front door of a breaker cell was launched across the test cell at that time, digging a divot out of the concrete wall on the other side of the test cell. Several manufacturers are now offering optical arcing sensors as an alternative to arc resistant construction. These sensors will detect an arc within the switchgear and signal a backup breaker to trip, clearing the arcing fault. However, consider the timing involved. Assuming that the sensor itself has a zero time of response to the presence of an arc, the backup breaker must still open and interrupt before the arc is extinguished. The fastest circuit breakers commonly used in metal-clad switchgear are 3-cycle breakers. This breaker takes 3 cycles, or 50 milliseconds on a 60 Hz system, to interrupt a circuit once its trip coil is energized. This time of operation will give good protection against burnthrough, but by this time the internal pressure in the switchgear has long since reached its peak, and any physical damage that pressure is going to cause has already happened. Optical arc sensors may offer excellent protection to gas-insulated substations, where the principal problem is protection against burnthrough. However, no detection system can protect metal-clad switchgear of normal, unreinforced construction against damage from arc-generated pressure because the backup breaker cannot open fast enough to prevent this damage. If resistance to damage due to arcgenerated pressure is desired, the arc-resistant design of metal-clad switchgear must be used.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Install it properly. Make sure the foundation is level, and that the equipment has been set level on the foundation and properly secured. Check alignment of all disconnects and interlocks on drawout circuit breakers to make sure that they fit properly into the cell. Be sure all bus splices are assembled properly, with the right size splice plates and the right size and number of bolts, properly torqued, and insulated if insulation is required. Connect cables carefully. Check out all control wire connections. Don't overheat it. Heat is one of the two great enemies of electrical insulation. Don't overload the equipment in service. Make sure that ventilation is adequate, and that any filters or other ventilating openings in the switchgear are clean and that air flow is not restricted. If artificial cooling is required to keep the ambient temperature within limits (usually a maximum of 40C), be sure it operates properly. Keep it dry. Moisture is the other great enemy of insulation. Make sure there are no leaks that will allow rain or other moisture to dampen the switchgear. For outdoor installations and indoor installations in damp climates, space heaters are recommended to deter condensation. Take care of it. The equipment should be inspected, cleaned, and lubricated on a regular schedule, and after any traumatic event, such as interrupting a major fault.
Treat your switchgear well, and it will last you a long time. Abuse it or neglect it, and it will die young.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #56 Control Wire and Wire Markers in Switchgear and Motor Control
December 19, 1994 ANSI standards for metal-enclosed switchgear require the use of either Type TBS or Type SIS wire for control wire in this type of equipment. Further, the wire is required to have a minimum size of #14 AWG, and to be flexible (41 strand or more) where it is connected across a hinge. Powell's standard is to use Type SIS flexible wire for all switchgear wiring. The wire will be #14 AWG unless a larger wire is required by the circuit or is specified by the purchaser. Switchgear control wire has traditionally been colored gray, although this is not called for by any industry standard. Powell's standard is to use gray wire except for ground wires, which are green. Other colors may be used if specified by the purchaser, but elaborate color coding can be rather costly, as wire manufacturers require sizeable runs of special items such as unusual colors. Special wire types can also be used when required, but are also subject to special charges for nonstandard wire mill runs. Wire markers, or wire tags, are used in most equipment we produce, but are not required by standards. Therefore, they must be specified by the purchaser when desired. When wire markers are used, Powell's standard is a white tube marked with black characters. The wire marker is marked with the wire number shown on the schematic and wiring diagrams. Special wire markers can be furnished on request. Some special features requested from time to time include special sleeve materials, special colors, heat shrink installation, and special wire designations or numbering. All of these can be furnished, but at a cost.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #60 Switching Small Currents with Vacuum Circuit Breakers
January 30, 1995 We occasionally see a specification which requires that the medium voltage circuit breakers that are supplied should be capable of switching very small currents, in the range of a few percent of the breaker's continuous current rating. Generally speaking, switching of low currents is not a problem for vacuum circuit breakers. Air-magnetic circuit breakers, which have been successfully used for many years in medium voltage switchgear, do have some problems with switching low currents. These breakers depend on a magnetic field generated by the current flowing through auxiliary coils in the interrupter circuit to drive the arc into the arc chute for successful interruption. When the current is very low, only a small field is generated, and the necessary arc movement may not be obtained. Almost all varieties of air-magnetic circuit breakers are equipped with a "puffer" device, a small air piston driven by the opening of the breaker. This piston is equipped with a nozzle that is directed at the area where the arc is truck by the opening of the breaker, so that the arc is literally blown into the arc chute. This device is needed on air-magnetic circuit breakers to insure interruption of small currents. At least in part because of this problem with the interruption of small currents, the ANSI standard for circuit breaker rating allows the interrupting time for the interrupting of current below 25% of the required asymmetrical interrupting capability to exceed the rated interrupting time by as much at 50%. Vacuum breakers, on the other hand, handle small currents with ease. We have tested one model of PowlVac circuit breaker at inductive currents as low as 25-30 A, and some other models at capacitive currents as low as half an amp. Load current switching tests have been made on all of our present production models of PowlVac circuit breaker at inductive current levels in the 250-260 A range. All of these tests were successful, and the interruptions took no longer than high current interruptions. The oscillograms indicated no distress in the interruptions. As far as we are concerned, interruption of low currents is a non-problem for PowlVac circuit breakers.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Overcurrent: A current exceeding the rated current. Short circuit: The accidental or intentional connection, by a relatively low resistance or impedance, of two or more points in a circuit which are normal at different voltages. Short circuit current: An overcurrent resulting from a short circuit due to a fault or an incorrect connection in an electric circuit. Overload: Operating conditions in an electrically undamaged circuit which cause an overcurrent. Overload current: An overcurrent occurring in an electrically undamaged circuit. Fault current: A current resulting from an insulation failure or the bridging of insulation.
An overload current is always an overcurrent, but not all overcurrents are overload currents. An overload is not a fault. A short circuit current is both a fault current and an overcurrent. However, not all fault currents are short circuit currents. Also, not all overcurrents are short circuit currents. A fault current is not necessarily an overcurrent. Under some fault conditions, the fault current may be much less than the rated current. A typical example is a ground fault current on a highresistance grounded system. This current may be only an amp or two, compared to a rated current of up to several thousand amps.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #62 Choosing Current Transformers for Relaying Use
March 28, 1995 Current transformers used for relaying under high current conditions must have a relay rating. This rating is expressed as the letter "C" or the letter "T" followed by a number. The number represents the voltage output at the CT terminals with 20 times normal secondary current flowing (100A for a typical 5 A secondary CT), without exceeding 10% ratio error. Standard values are 10, 20, 50, 100, 200 and 400. The "C" or "T" describes the method used for determining this voltage. The voltage for CT's with a "T" designation has been determined by test, the usual method for wound primary CT's. Recent work by a working group of the IEEE Power Systems Relaying Committee has shown that lowratio CT's applied to systems with high fault current levels may saturate under fault conditions and cause improper or no operation of the overcurrent relays. Extreme saturation of the CT's can result in very narrow pulses of secondary current, only a few electrical degrees wide. Although the magnitude of the pulse may be above the pickup setting of the relay, the current does not flow for long enough at a time to operate the relay. To be sure that the CT's do not saturate, the relay rating of the CT should be twice the voltage necessary to drive the maximum fault current through the connected burden. For example, assume a bus with 24 kA available fault current and a CT rated 400/5 A (80:1 ratio). Divide 24,000 A by the CT ratio, 80, to determine the secondary current, 300 A, under maximum fault conditions. If the secondary burden is 0.33 ohms, the voltage required is 300x0.33, or 100 V. A CT with a relay rating of C200 or T200 should be chosen for this application. Where low-ratio CT's are needed on a system with a high available fault current, it may be very difficult to find a CT with the necessary relay rating. Several possible ways to improve the situation are to use higher ratio CT's, to use higher accuracy CT's, to use lower burden relays, to divide the burden between two sets of CT's, or to use separate instantaneous overcurrent relays connected to a separate set of high-ratio CT's. If you want to review the entire report of the PSRC working group, you can find it published in two different IEEE Transactions. The report title is "Relay Performance with Low Ratio CT's and High Fault Currents". It may be found in IEEE Transactions on Power Delivery, Vol. 8, No. 3, July 1993, pp. 884897, and in IEEE Transactions on Industry Applications, Vol. 31, No. 2, March/April 1995, pp. 392-404.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #64 Load Switching Capability of NEMA General Purpose Contactors
June 22, 1995 NEMA general purpose contactors, of the type generally used in motor control centers, have a number of different load switching ratings, depending on the type of load being switched, the duty cycle of the load, and the switching sequence being used. The table below shows the ratings assigned to size 1 through size 5 for use on 60 Hz, 480 V systems, with motors rated 460 V.
Motor HP Full Voltage NEMA Starting, NonSize of Contactor plugging and Nonjogging duty
rms Amperes
Peak CircuitClosing Switching Rating Inrush Inrush Amps <= >20x (Inrush) Continuous Tungsten Resistance 20x <=40X Current Lamps Loads & Full Full (300V Discharge Load Load max.) Lamps 288 483 947 1581 3163 27 45 90 135 270 15 30 60 120 240 27 45 90 135 270 8.5 14 28 47 94 4.3 7.2 14 23 47
1 2 3 4 5
10 25 50 100 200
These values are taken from tables in NEMA Standard ICS2-1988. Other tables in this standard give ratings for other sizes of contactors, other voltages and frequencies, single phase, other motor duties and starting methods, etc.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #64 Load Switching Capability of NEMA General Purpose Contactors
page 2 In most cases, the rating limit is established by the contactor's ability to close a certain peak current. Loads with high inrush characteristics require oversized contactors to handle the inrush current without damage. For instance, consider a 15 kVA, 480 V, 3 phase transformer, which has a full load current of 18 A. This is well within the continuous current rating of a size 1 contactor, but switching the primary of this transformer required a size 3 contactor if the inrush current is <= 20 x full load, and a size 4 contactor if the inrush current is between 20 x and 40 x full load.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
A typical auxiliary CT circuit is shown in the figure above. The auxiliary CT secondary burden,
, is
reflected into the main CT secondary circuit by the square of the current ratios, per the following formula:
where
From this equation you can see that using an auxiliary CT to step the main CT secondary current up increases the burden on the main CT by the square of the step-up ratio, whereas using the auxiliary CT to step the main CT secondary current down decreases the burden by the square of the step-down ratio. From this, it would seem that, if you are matching two main CT ratios by using an auxiliary CT, it would always be preferable to step down the higher main CT secondary current, which is the current from the main CT with the lower ratio.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
The higher ratio CTs may have a higher burden capability than the lower ratio CTs, and thus be capable of handling a larger burden with the same accuracy. The lower current resulting from the step-down transformation may require a lower relay setting to achieve the desired sensitivity, and this lower setting may greatly increase the relay burden.
As always, the best solution is to do a complete burden calculation to see which way, step-up or stepdown, gives the best results. "Best results" means that all of the devices, including the main CTs, the auxiliary CTs, and the relays or meters connected in the circuit, are operating within their capabilities, and that the overall circuit will give the performance desired under all operating conditions.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #67 Using Latched Contactors in Medium Voltage Motor Control Centers
November 13, 1995 The motor starting contactors used in medium voltage motor control are usually held closed by an operating coil, which is energized to close the contactor. When the coil is deenergized, the contactor opens. Since the contactor's coils is usually energized from a control power transformer connected to the primary circuit of the starter, this design provides automatic undervoltage protection for the motor. For loads other than motors, however, it is sometimes desirable to maintain the circuit during an undervoltage condition. This is commonly done for transformer feeders originating in the medium voltage MCC. To handle this type of circuit, latched contactors are available. When closed by its operating coil, a latched contactor will remain closed even if the closing coil is deenergized. The latched contactor is opened by energizing a trip coil, something like a circuit breaker is opened. Latched contactors may be equipped with manual closing and/or tripping operators if desired. These may be in addition to or in place of the operating coils, leading to quite a few possible combinations of operators. Several cautions are in order when latched contactors are used:
For non-motor loads, such as transformers or capacitors, the motor starting current-limiting fuses should be replaced with general purpose current-limiting fuses. These fuses may stand alone as the overcurrent protection, or they may be supplemented with overcurrent relays for better overload protection. Since automatic undervoltage protection disappears when a latched contactor is used, separate undervoltage relays must be provided if undervoltage protection is needed. There is a major difference between the control circuit for a latched contactor and the control circuit for a circuit breaker. The latched contactor has no anti-pump feature. If a latched contactor is presented with simultaneous, maintained close and trip signals, it will cycle closed and open until one of the signals is removed or until the contactor destroys itself. A circuit breaker, on the other hand, will close once and open once, then remain open until the closing signal is removed and reestablished. Control and interlocking circuits used with latched contactors should be investigated very carefully to make sure that there is not a circuit that could result in damage to the contactors.
Properly applied latched contactors are useful devices, but they don't work just like circuit breakers. Be sure you understand the differences and take them into account when using latched contactors.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #68 Instantaneous Ground Fault Relays (50GS) and Zero-Sequence CTs
November 28, 1995 In PTB 62, I discussed the problem of low-ratio CTs used on systems with high fault current, and I mentioned the IEEE working group report on this subject. Because of the emphasis in this report on making sure that CTs do not saturate, a number of people have become concerned about the operation of instantaneous ground fault relays connected to zero-sequence, or core balance, CTs. Because of this concern, Powell recently ran a series of tests to check the operation of typical CT-relay combinations. Two different relays were tested with each of two CTs. The relays were the GE HFC and the ABB IT. Electro-mechanical relays were chosen for the test because their higher burden places a greater load on the CTs. The CTs used were both made by ITI. The first Model 141-500, 50/5, C10 accuracy. The second was Model 143-500, 50/5, C20 accuracy. The test results are given in the table below. Relay Under Test HFC IT Relay Pickup Setting 0.5 A 0.15 A Current Transformer 141-500 143-500 141-500 143-500 Primary Pickup Current 15.8 A 13.6 A 6.5 A 5.4 A Time to trip at indicated current (ms) Pickup 600 A 1200 A 1800 A 39.3 36.35 95.2 132.4 34.85 33.75 61.3 56.3 24.05 27.05 67.7 60.0 36.9 31.95 72.6 68.9
Both of these relays operated correctly and reliably with both CTs. However, we also tested a third relay, the ABB ITH, a high dropout version of the IT. We found that this relay was not reliable in this service. It picked up at quite low values, and operated well with primary currents up to about 150 A. At the higher currents, 600 A and up, it chattered quite badly and did not close its contacts for long enough to operate a circuit breaker. Asking around, I found that this relay had been recommended for 50 GS service some years ago, but its manufacturer (Westinghouse at that time) changed the recommendation when the chattering problem was discovered. Based on this information and the tests, Powell strongly recommends that the ITH relay not be used as a 50GS relay. Summarizing, both the HFC and the IT work quite well at primary ground fault currents up to 1800 A, even though the CTs are badly saturated at that current level. This circuit, with these CTs and relays, should not be used on solidly grounded systems with high ground fault current. For these systems, residually-connected relays should be used, or the zero-sequence CTs should have higher ratios.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #69 Wound Rotor Induction Motors and Starters
January 5, 1996 The garden variety of induction motor used in industry is the squirrel cage induction motor. Many of the characteristics of these motors, such as starting inrush current, starting torque, and slip, are fixed. Although a motor designer can vary these characteristics at the design stage, once the motor is manufactured these characteristics are fixed. The wound rotor induction motor has a rotor winding that is not short-circuited on the rotor, like a squirrel cage motor, but is brought to slip rings so that the rotor circuit can be modified by inserting external resistance. This added resistance can accomplish two things:
Since the starting torque developed in an induction motor by a given starting current is proportional to the rotor resistance, adding resistance during the starting cycle can increase the starting torque, or lower the starting current for the same torque. By decreasing the rotor resistance as the motor accelerates, the torque can be controlled to provide a smooth acceleration of the load, sometimes called a "soft start". This can be very helpful for loads such as cranes, hoists, and loaded conveyors. Since the slip of an induction motor increases as the rotor resistance increases, some speed control is possible using a wound rotor motor and varying the rotor resistance while running.
Controllers for wound rotor motors include for the stator the same protection and switching functions that are used for squirrel cage motors. For the rotor, a multi-step resistor and switching means for that resistor are required. For a soft start application, the resistor is switched out of the circuit step by step as the motor accelerates. Once it reaches full speed, the resistor is completely shorted out, and the motor runs like a squirrel cage motor. The number of steps varies, depending on the motor size and the starting characteristics desired, but generally falls in the range of 3 to 7 steps. The switching may be done by a manual drum switch or by a series of contactors activated by timers. For speed control, some resistance remains in the rotor circuit for all speeds except maximum speed. The running resistor may be further steps of fixed resistance, like the starting resistors, or a continuously variable resistance, like a liquid rheostat.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #69 Wound Rotor Induction Motors and Starters
page 2 Wound rotor motors have some drawbacks. Both the motor and the controller are more complex and cost more than a similar squirrel cage motor and its controller. The added running resistance in the rotor circuit of the motor on speed control increases losses, and thus operating costs, and the maximum speed is limited to something less than synchronous speed for the number of poles in the motor. Because of these limitations, many users now turn to squirrel cage motors and variable frequency drives to meet their needs for both soft start and speed control.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #71 Starting Methods for Large Medium Voltage Motors
February 9, 1996 Most ac motors, both synchronous and induction, are started "across the line"; that is, the starting contactor or circuit breaker connects the 3-phase motor winding directly to the 3-phase power supply. However, when motors are large with respect to the capacity of the power system it is often necessary to use a starting method that reduces the impact on the power system caused by starting the large motor. Several methods of accomplishing this task are available. This reduced-impact starting is frequently referred to as reduced voltage starting because most of the common methods involve applying a reduced voltage to the motor winding. Some of the more common methods are described below.
Autotransformer: An autotransformer is connected between the power source and the motor during the starting period. Motor starting autotransformers usually have taps that apply 80%, 65%, or 50% of the line voltage to the motor to start. Line current is reduced by the square of the tap; that is, using the 80% tap on the autotransformer requires only 64% of the across the line starting current. Starting torque is also 64% on the 80% tap. Unless otherwise requested, the autotransformer will be the medium duty type, allowing 3 starts, followed by an hour's rest before repeating the three starts. Modern starters use the closed transition switching sequence, in which the autotransformer winding is converted briefly to a series reactor near the end of the starting sequence, then shorted out. This sequence requires three switching devices (circuit breakers or contactors). Reactor: A reactor is connected in series with the motor. These reactors usually have taps that apply 80%, 65%, or 50% of the line voltage to the motor to start. Line current is reduced to the tap value; that is, using the 80% tap on the reactor requires 80% of the across the line starting current. Starting torque is reduced by the square of the tap, and is 64$ on the 80% tap. The reactor may be placed on the line side of the motor or in the neutral. Reactor start requires only two switching devices. Capacitor: A bank of capacitors is connected in parallel with the motor during starting, canceling out the large reactive current drawn by the motor on starting. The motor thinks it is seeing a full voltage start, while the power system thinks it is seeing a running motor. The capacitors are removed from the circuit as the motor reaches running speed. Two switching devices are required. Wound Rotor: For induction motors only. See PTB 69 for further information. Solid-state Drives: A wide variety of starting and speed control performance can be obtained through the use of modern solid-state drives.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #72 Open Circuit Protectors for Current Transformers
April 10, 1996 Current transformers should never be operated with an open secondary circuit. If the secondary of a CT carrying primary current is open circuited, a high voltage can be developed across the CT terminals. Depending of the characteristics of the particular CT, this voltage may be several hundred volts if the primary current is high enough. This voltage may be dangerous to personnel servicing the equipment and damaging to the CT itself or to devices connected to the CT. To guard against this possibility, devices used in CT secondary circuits are designed to prevent open circuits. For instance, ammeter switches have overlapping contacts so that the circuit is never opened as the ammeter is transferred from phase to phase, and drawout relay cases have shorting contacts in current circuits so that the CT circuits are shorted before the relay coil is removed from the circuit. Also, CT secondary circuits are often wired to special terminal blocks which allow a short circuit to be placed on the CT secondary if it is necessary to service the secondary circuit. For those users who wish even further protection against the possibility of an accidental open circuit in a CT secondary, open circuit protectors are available. These are useful especially where the CT secondary leads are long and subject to possible damage, such as in substations where CT leads from high voltage circuit breakers or transformers may runs as much as several hundred feet to reach the secondary devices. Some users require these devices in metal-enclosed switchgear, but only about 5% or less of the switchgear we build has these protectors. There are two basic types of protectors available - variable resistance and electronic. They both work by limiting the CT secondary voltage, but in very different ways. The variable resistance type carries enough current to limit the voltage across the protector, much in the manner of an MOV or a surge arrester. However, in order to protect itself, this device includes a heater element in series with the variable resistor and a bimetallic contact which will short out the CT secondary before the variable resistor element is damaged. The electronic type monitors instantaneous voltage, and shorts the CT secondary through an SCR if the instantaneous voltage exceeds the set point. This short remains for the rest of the half-cycle of the voltage wave on which it occurs, and is then removed. Each half cycle is separately monitored and acted upon. Both types of protector come in several voltage classes. It is very important when applying these protectors that the proper voltage class be chosen, and coordinated with the operation of the relays at maximum fault current. This is especially important for CTs connected to high impedance bus differential relays, which are normally voltage actuated. The protector must operate for a true open circuit, but must not operate to short circuit the CTs under fault conditions, preventing desired relay operation.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #73 Metal-Clad Switchgear or Metal-Enclosed Switchgear: Which is it?
April 23, 1996 Would you be surprised if I said it might be both? Metal-clad switchgear is one of three common types of metal-enclosed switchgear, as defined in ANSI standards. Before I confuse you further, a definition is in order. Metal-enclosed power switchgear: A switchgear assembly completely enclosed on all sides and top with sheet metal (except for ventilating openings and inspection windows) containing primary power circuit switching or interrupting devices, or both, with buses and connections. The assembly may include control and auxiliary devices. Access to the interior of the enclosure is provided by doors or removable covers, or both. This definition appears in all three of the ANSI/IEEE standards covering the types of metal-enclosed power switchgear: C37.20.1, Metal-Enclosed Low Voltage Power Circuit Breaker Switchgear; C37.20.2, Metal-Clad Switchgear and C37.20.3, Metal-Enclosed Interrupter Switchgear. Let's look at some of the things that define each of these types. Metal-enclosed low voltage power circuit breaker switchgear is obviously for use on low voltage systems. The maximum ratings in C37.20.1 are 635 V for ac switchgear and up to 3200 V for dc switchgear. The interrupting device is a low voltage power circuit breaker, either withdrawable or stationary. It may be either manually or electrically operated, fused or unfused. Each circuit breaker is enclosed in a grounded metal compartment, but other isolation, such as between buses and cable connections, is not required. Shutters are not required over bus connections when drawout breakers are used, and bare bus is standard. While some of these features may be available as options (Powell can provide all of them), they are not required by the standard. Under the ANSI standards, low voltage switchgear cannot be considered metal-clad. Metal-clad switchgear requires that the main switching and interrupting device be drawout. It may be either a circuit breaker (usual) or a load-break interrupter switch (unusual). Circuit breakers are always electrically operated. Extensive barriering, shutters over the primary circuit elements when the interrupter is withdrawn, and insulation-covered bus are all required. The minimum rated voltage listed in C37.20.2 is 4.76 kV. This rating is commonly used on 2400 V ac circuits, but is seldom used at lower voltages. Ratings are available up to 38 kV. Metal-clad is usually considered the top of the line of medium-voltage metal-enclosed switchgear.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #73 Metal-Clad Switchgear or Metal-Enclosed Switchgear: Which is it?
page 2 Metal-enclosed interrupter switchgear covers the same voltage range as metal-clad, but is of simpler construction. The main switching device is an interrupter switch, usually load-break, which may be stationary (usual) or drawout (unusual). Overcurrent protection is usually provided by fuses. Bare bus is standard and required barriering is minimal. Although electrical operators are available, the switches are usually manually operated.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #74 Enclosures for Metal-Enclosed Switchgear and Motor Control
July 12, 1996 The enclosures which are a part of metal-enclosed switchgear and motor control equipment furnished by Powell serve two major purposes. First, they protect users of this equipment from injury by preventing access to live parts by foreign objects, including parts of the human body. Second, they protect the working parts of the equipment from the effects of the environmental conditions in which the equipment is installed. However, while performing these two duties the enclosures also allow reasonable access to parts for operation and maintenance, and must allow ventilation adequate to keep the equipment within its temperature limitations while operating. There are three major sources of enclosure information applicable to metal-enclosed switchgear and motor control: ANSI/IEEE, NEMA, and IEC standards. ANSI/IEEE C37 Series: C37.20.1, C37.20.2, and C37.20.3 are the basic standards for metal-enclosed switchgear. These standards recognize only two types of enclosure, indoor and outdoor. NEMA 250: This standard lists numerous varieties of enclosures for electrical equipment, but applies only to equipment rated 2000 V maximum. It is the source of the definitions for the familiar NEMA 1, NEMA 3R, NEMA 4, etc., enclosures. IEC 529: This standard also lists numerous varieties of enclosures for electrical equipment, and there is no voltage limitation. It is often referred to as the "IP Code", because each enclosure type number is preceded by the letters "IP" (for International Protection). IEC 694: This standard covers high-voltage switchgear and controlgear. It refers to IEC 529, but specifically limits high-voltage switchgear and controlgear enclosures to enclosure types with no degree of protection against harmful ingress of water (second characteristic numeral X). Outdoor equipment uses the suffix W. Each standard defines its various enclosure types and prescribes appropriate tests to demonstrate the effectiveness of the enclosure. Unfortunately, there is no exact equivalence between the enclosure types in the various standards, but the following table shows a comparison of the closest types in each standard.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #74 Enclosures for Metal-Enclosed Switchgear and Motor Control
page 2 ANSI/IEEE C37 Series Indoor Outdoor NEMA 250 NEMA 1 NEMA 3R IEC 529 IP20 IP24 IEC 694 IP2X IP2XW
In addition to the standard indoor and outdoor enclosures, Powell offers arc resistant indoor enclosures for PowlVac metal-clad switchgear and weather-proof Power Control Room (PCR) enclosures for all types of equipment.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
In order to create the pressure necessary to deform the micro projections on the bus bars, the bolt torque must be rather high. Proper torques are given in PTB 53. To achieve high torques and large contact areas, it is preferable to use a few large bolts rather than many small ones. For most main buses in switchgear and motor control, we prefer to us 1/2" bolts. It is our experience, based on numerous temperature rise tests, that 1/2" bolts make a very satisfactory joint for bus rated up to 4000 A. Since most joints are made by bolting a bus bar to a splice plate or a riser bus, and then bolting the next section of bus to this same splice plate or riser bus, the complete bus-to-bus splice will normally have four bolts. Copper bus bars are normally plated with silver, tin, or nickel at all joints in order to prevent the formation of copper oxide in the joint. Copper oxide is a semiconductor, and its presence leads to increased resistance and high temperature in the joint.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Figure 1
The coupling capacitance is primarily made up of the capacitance of the system dielectric between the phase conductor and ground. The value of the voltage transformers magnetizing reactance varies as a function of the amount of flux going through the iron. This results in an LC circuit and requires only a simple voltage transient to excite the resonant frequency. Once the ringing begins the voltage across the individual components of magnetizing reactance and coupling capacitance can reach high levels and the ringing can go undamped if the voltage transformer is lightly loaded. The loading of the VT has a very important part to play in limiting the magnitude of current in the oscillation circuit since the resistance of the load will act as a current divider and send a portion of the current to ground. This graph from the IEEE Red Book shows the impact of load on the magnitude of the current in the ringing circuit (see Figure 2).
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Figure 2
During the oscillation, the current can drive the magnetizing force to saturate the VT. When the VT is saturated, the reactance to ground will diminish and the current to ground through the primary of the VT will go high. At the end of the sinusoid the VT will drop out of saturation, but with a low loss system the stored charge remains relatively high across the system coupling capacitance. As the polarity of the sinusoid changes the process repeats itself. The current surges, through the VT primary during the periods of saturation, can be much greater than full load rating but not approaching fault current levels, making it very difficult for the fuses on the primary of the VT to interrupt. Thus current surging may result in a blown VT fuse but often results in a shorted VT. To keep the resonance magnitude down, the secondary side of the VT circuit can be artificially loaded. There are two common methods of loading used to minimize the effects of ferroresonance. One is to install the VTs with their secondary windings connected in a broken delta and with a resistor completing the broken delta circuit. The watts of the resistor should equal 50% of the VA of a single VT.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #81 Direct Control of Motor Contactors via PLCs and Distributive Control Systems
October 28, 1997 As we automate the process systems more and more we are looking for direct control of the motor starters with PLCs and Distributive Control Systems (DCS). A commonly asked question is whether the interposing relay situated between the two systems is really needed or not. I have gone through and looked at the more common systems and put together this technical brief to highlight some of the concerns involving the interposing relay. Digital Outputs Modules The electro-mechanical and the solid state (triac) output modules are commonly available for either PLCs or DCSs. Both of these digital output modules are listed in the vendor literature as having a 120 Vac rating of such and such current. Two amps seem to be the most popular for the electro-mechanical value and amp for the solid state output. The thing I had difficulty finding was the expected power factor of the load. A power factor of 0.5 seemed to be the most common although I did find one manufacturer who based his rating on a power factor of 1.0. The expected power factor obviously changes from one manufacturer to the next for both PLC and DCS. The normal contactor coil has a power factor of 0.1, at this level the output rating should be derated by 50%. This is without the consideration of the wire impedance connecting the two systems. In addition to confirming the make and break capability, the application engineer should realize that the turn off of the standard starter results in an inductive kick that sends a significant voltage spike though the system. The output relay ends up with contact pitting and the contactor coil receives a steep fronted voltage spike which shortens the life of the insulation. The spike can be limited by installing a snubber circuit across the output contacts. For solid state outputs the snubber is a 0.1 microfrad capacitor and a 100 ohm resister series together. The cap should have about a 400 Vdc rating for a 120 volt control system. For the electromechanical output internal protection is usually provided for loads up to 1 amp after that you need to provide it separately. In most cases the manufacturer has a kit available as an option. The triac outputs add an additional level of possible problem due to the triacs leakage current during turn off and forward bias requirements. The forward bias means that the triac must maintain some minimum current flow to keep the device in the on state. The leakage current is a small quantity of current that trickles through the device even after turn off. This few milli amps will be in parallel with the distributed wire capacitance of the wire between the control system and the MCC to make the turn off a significant problem. This appears to make the triac an undesirable combination with the standard contactor.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #81 Direct Control of Motor Contactors via PLCs and Distributive Control Systems
page 2 Smart Motor Control When using many of the new smart motor control centers the control circuit is no longer interrupting the coil current directly, if it is wired properly! So the concerns relative to interrupting a large inductive load are eliminated. The electro-mechanical relay output is less likely to have problems getting the two systems to match-up. The reliability of the triac output module will allow it to do more operations successfully than the electromechanical, but since the coil is not operated directly, you may have to add a swamping resistor in parallel with the MCC input to make sure the circuit draws sufficient current to keep the triac forward biased. In addition, the high relay input impedance of the smart MCC and the distributed wire capacitance may begin to play a part in the functionality of the stop circuit. The longer the length of the control circuit the higher the leakage current and the more likely resistance may need to be added to assure that the circuit will recognize a stop command. A separate concern about doing away with the interposing relay you may want to discuss with the end user is the safety aspects of bringing 120 volt control power from the MCC starter drawers into the PLC or DCS. The way most plant treat the insides of their PLC and DCS is as though there is no voltage level greater that 50 volts to ground. At 50 volts and below OSHA Standard 1910 and NFPA 70Es Electrical Safe Work Practices & Working Space Requirements need not apply. But by bringing the 110 Vac into the control system the rules identified in OSHA 1910 are applicable. In some cases this can have a tremendous impact on the cost of doing work. Based on the legwork I have done the interposing relay still makes good sense until the confidence in the twisted pair communication allows us direct communication between the smart MCC and the PLC or DCS, with a stop station in the field next to the load. If we can help with this or any other topic please do not hesitate to call.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #85 The Application of 600 Volt Class Current Transformers in Medium Voltage Switchgear
August 10, 1999 ANSI Medium Voltage Switchgear commonly uses 600-Volt Class window type current transformers in medium voltage circuits. For many years manufacturers have installed 600-volt class current transformers in medium voltage switchgear. The preferred location for the current transformers is the circuit breaker spouts. To certify the dielectric capability of the equipment the switchgear type tests are performed with the maximum number of current transformers mounted on the circuit breakers cells feed through bushings. A typical configuration of the switchgear with the smallest air gaps is then subjected to the series of Basic Impulse Levels Tests required by ANSI. The success of the BIL testing in the area around the circuit breaker feed through bushings relies on the following combination of insulation:
The solid dielectric of the circuit breakers feed through bushings The air gap between the conductor and spout The air gap between the spout and the case of the current transformer The 600 volt class insulation of the current transformer
This series combination of various insulating mediums provides an insulating system that goes through the dielectric testing along with the entire switchgear system. During the power frequency test (high potential) and the impulse test required in ANSI C37.20.2, it is proven that the system dielectric strength exceeds the nominal BIL rating for the voltage class. Bus Mounted Current Transformers Occasionally the clients current transformer requirements exceed the physical mounting capacity of the circuit breaker spouts. In these cases it becomes necessary to add additional window type current transformers. These additional current transformers are mounted in the cable compartment around the run-back bus. Since these are non-standard components, they do not get included in the switchgear BIL testing. To maintain the BIL of the equipment an industry rule of thumb for both factory and field installations requiring bus mounted window type current transformers is to allow a 1 inch air gap between the insulated bus and the current transformer housing. Powell went through the process of testing the 1-inch air gap rule of thumb with various bus insulation systems that we use in the manufacture of the switchgear. We have established an internal matrix that applies to the various insulating systems, the associated standard current transformer and a special "increased dielectric" current transformer. The table below indicates what configurations were acceptable when tested for 95kV BIL.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #85 The Application of 600 Volt Class Current Transformers in Medium Voltage Switchgear
page 2 Table of BIL Tests on 6.5 Inch Bus Mounted Window Type Current Transformer Number of Bus Insulation Standard Current Increased Dielectric Bars per Phase Material Transformer Current Transformer and Size (inches) Hipoxy-2000 (1) 1/2 x 3 (1) 1/4 x 4 (1) 3/4 x 4 (2) 1/2 x 3 (2) 1/2 x 4 (2) 3/4 x 4 GE-Noryl (1) 1/4 x 4 (2) 3/4 x 4 Scotch BBI-4A Passed Failed @ 82kV Failed @ 78kV Failed @ 94kV Failed @ 74kV Failed @ 72kV No Test No Test Passed Passed Passed Passed Passed Passed Passed Failed @ 94kV
(3) 3/4 x 4 No Test Passed (sandwiched) Note: Standard current transformers would be suitable for all switchgear designs requiring 60kV.
Powell Technical Brief #86 Altitude De-rating of Fuses, Surge Arresters and Potential Transformers
August 11, 1999 As a dielectric dry air works satisfactorily. However as the altitude at which we apply our electrical equipment increases, the effectiveness of the dielectric property decreases. An increased altitude also decreases the continuous current carrying capability of electrical equipment due to the reduced thermal conductivity of the lower density air. In the past we have discussed the altitude de-rating factors for switchgear (see PTB 25). The IEEE Standard for Metal Clad Switchgear (C37.20.2) explains that switchgear assemblies, which depend on air as an insulating medium, will have a lower dielectric withstand capability when operating in altitudes above 3300 feet. This Powell Technical Brief will explain how altitude de-rating effects the installation of medium voltage fuses, surge arresters, and voltage transformers. Fuse De-rating The IEEE Standard for Conditions and Definitions for High Voltage Fuses, Distribution Enclosed Single Pole Switches, Fuse Disconnecting Switches, and Accessories (C37.40 section 2.3) offers de-rating factors for high voltage fuses. The de-rating is a function of the ability of the fuse to clear a fault and achieve a dielectric across the fuse element gap faster than the system voltage across the fuse can be established. This de-rating would be applicable for non-sealed fuses like expulsion fuses and current limiting fuses, where the outside air is the insulating means used to isolate the line and faulted load. Since the dielectric strength of air is reduced as the altitude is increased, the fuse has to be de-rated in accordance with the published chart. (see Table) The thinner air also results in lower thermal conductivity, which requires a de-rating of the continuous current. To compensate for the reduced thermal conductivity the standard allows for a reduction in either the maximum ambient temperature or the continuous current rating, but not both. Rated Dielectric Ambient Altitude in Feet Continuous Strength Temperature Current 0 to 3,330 3,301 to 5,000 5,001 to 10,000 10,001 to 16,000 1.00 0.95 0.80 0.65 1.00 0.99 0.96 0.92 1.00 0.98 0.92 0.848
When the dielectric strength of the fuse is de-rated, the application engineer is often required to choose a fuse of higher voltage class. This approach may result in higher current chopping and associated voltage transients. An alternate solution is the hermetically sealed fuse, which does not require de-rating of the internal operating mechanism. Note that hermetically sealed fuses are both expensive and may have a long delivery time. Care must also be taken to confirm that the outer creepage distance is acceptable within the de-rated values.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217 Tel: 713.944.6900 Fax: 713.947.4453 www.powellind.com info@powellind.com
Powell Technical Brief #86 Altitude De-rating of Fuses, Surge Arresters and Potential Transformers
page 2 Surge Arrester De-rating There are two types of surge arresters in common use today -- the expulsion-type arrester and the metal oxide arrester. The expulsion-type arresters have an internal system that depends on ambient air as a dielectric and, as such, must be de-rated as a function of altitude just as fuses. The metal oxide surge arresters are sealed and outside air does not play a part in the isolating process, so the surge arrester does not require de-rating for the internals to operate properly. However, air also plays a part in the external surface creepage distance of the housing. The outer surface has a certain creepage distance that prevents the surge arrester housing from tracking across the surface of the arrester. Powell Technical Brief # 59 describes the acceptable surface creepage distance for various impulse levels given insulated conductors. The insulated conductor distances can only be used if an insulating boot properly covers the ferrule at the top of the arrester. Care must be exercised when applying the altitude de-rating factor. To maintain the desired discharge level of the arrester and the required creep distance, it may be necessary to have special arresters manufactured with a standard duty cycle arrester in a housing with higher creep levels. A special caution when applying de-rated higher voltage current limiting fuses. Each fuse has a characteristic current chop that results in a maximum allowable voltage transient of three times the rated fuse voltage. The transients that result from applying a higher voltage class fuse due to altitude de-rating can often result in the surge arrester conducting during a fuse interruption. This should be avoided for line side station class and intermediate class arresters as the conducting impedance of this arrester is low enough that conducting during a fault will cause serious damage. Distribution class arresters have a high enough conducting impedance that this is not a problem.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #86 Altitude De-rating of Fuses, Surge Arresters and Potential Transformers
page 3 Voltage Transformer De-rating When voltage transformers are applied at higher altitudes, ANSI C57.13, section 4.3, identifies the derating factors. This de-rating requires use of a higher voltage class transformer with the appropriate primary voltage and the ratio to maintain the desired secondary voltage. For example: Given a line-up of switchgear operating at 4.16kV at an altitude of 10,000 feet, the appropriate choice is a voltage transformer with a primary voltage of 4200 Volts and a secondary of 120 Volts. The transformer would have an insulation class of 8.7kV with a BIL at sea level of 75kV. When the 80% de-rating factor is applied due to the altitude, this VT has a BIL of 60kV. This Powell Technical Brief should clarify some of the concerns expressed by customers on recently shipped substations installed at higher altitudes. If I can be of further assistance please do not hesitate to call.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Figure 1 To demonstrate what happens with a second ground on the current transformer circuit, Figure 1 shows a typical differential relay with two current transformers. The recommended method of grounding is to install a single ground point at the first point of application (switchboard or relay panel) of the current transformer secondary circuit.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Figure 2 A substation circuit breaker should have the wye or delta connections made-up at the CT terminal blocks in the equipment. If the protective relay is mounted in the breaker the wye connection is grounded at the circuit breaker. If the protective relays are mounted in a separate building, then the wye connection is in the breaker but is grounded at the relay house. The same applies for current transformers in the transformer tank. The CTs are grounded at the place where the metering or relaying is located (see Figure 2).
Figure 3 Note: For a fault, external to the protective zone, insufficient voltage develops across the operating relay to pick up the coil.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217 Tel: 713.944.6900 Fax: 713.947.4453 www.powellind.com info@powellind.com
Figure 4 Note: With a fault in the protective zone, sufficient voltage develops across the operating relay coil to pick up the coil. In the final example (Figure 5) there is a second ground is on a current transformer mounted near where a ground fault occurs. If the fault creates a ground potential rise of 100 volts, then the protective relay will experience sufficient voltage across the operating coil to cause the relay to nuisance trip even though the fault was outside the fault zone. Just as with any other event there is an exception to this standard. Many of the new multifunction relays (ABB, Schweitzer, GE/Multilin, and Basler) are designed to connect all current transformers coming into the relay in a wye connection. Each wye has to be grounded. The most desirable way to do this is to bus the wye points together at the relay panel and have a single conductor to ground, to make certain the relay has but one ground potential. As you can see, there are significant considerations in the proper grounding of current transformer circuits.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Figure 5 Note: With a second ground at a remote location, the voltage across the operating coil is sufficient to result in a miss-operation for an external fault and cause a nuisance trip situation.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
An example of how the chart works: For a 480V system the maximum voltage will be proportional to the new systems nominal system voltage by the ratio of the maximum per unit voltage (127 per unit) to the nominal voltage (120 per unit). X Maximum Voltage Rating = 480 Maximum Voltage Rating for 480V is 508V. = 120 per unit 127 per unit
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #89 The New Medium Voltage Circuit Breaker Interrupting Ratings Based on K Factors of 1
July 31, 2001 The ANSI Standard for Medium Voltage Circuit Breaker Test Procedures, IEEE C37.09 was revised in 1999. This standard defines the short circuit tests required to certify a medium voltage circuit breakers interrupting rating. In the past the interrupting rating changed as a function of the voltage at which the breaker was applied. The new standards are an effort to recognize that modern vacuum and SF6 interrupting technologies more closely represent a constant current interrupting device, independent of the nominal system voltage. The standards evolved from the 1945 revision when breakers were rated based on interrupting MVA (see figure below). In 1968 the standards established varying k factors to adjust interrupting rating as a function of the voltage. The k factor reflects the performance of the oil and air interrupting technologies available at that time. This practice ended with the 1999 change, where circuit breaker k factors were all set at to a value of one. The k factor of 1 results in all medium voltage breakers, tested to the 1999 version of C37.09, having a constant interrupting rating irrespective of nominal system voltage. The changes in interrupting rating at the system voltage can be seen in the graphs below.
Using the 1968 standards, the 250MVA breaker had a 29kA interrupting rating if applied at 4.76kV while the same breaker applied at 4.16kV had a 33kA interrupting rating and when applied at 3.85kV it had a 35.5kA rating. Using the 1999 standards, a newly certified 36kA breaker with a k factor of 1 will retain the 36kA interrupting rating independent of the applied voltage.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #89 The New Medium Voltage Circuit Breaker Interrupting Ratings Based on K Factors of 1
page 2
Important Note: Circuit breaker short circuit interrupting rating is the symmetrical RMS current at the time power contacts part. These new rating structures do not change the rating of circuit breakers certified prior to the 1999 revision. They only impact breakers that are certified to the new testing standards. The new 1.0 k factor ratings will simplify breaker application and align with the long-standing IEC nomenclature. It is important that we do not make the mistake of trying to apply a short circuit rating that varies as a function of the voltage to circuit breakers certified to have a k factor of 1.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #89 The New Medium Voltage Circuit Breaker Interrupting Ratings Based on K Factors of 1
page 3
Powell Technical Brief #90 Asymmetrical Interrupting Current Rating of Medium Voltage Circuit Breakers
September 15, 2001 As discussed in the last Powell Technical Brief, the 1999 revision of ANSI Standard C37.04 and C37.09 changed several definitions relating to the rating structure of medium voltage circuit breakers. The earlier revision of the circuit breaker standards utilized the S factor as a multiplying factor that defined the total current a breaker was rated to interrupt at contact part. The newest revision of C37.04 replaced the S factor with the %dc as the method of evaluating the asymmetrical current offset. The %dc is utilized to calculate the total interrupting current. The asymmetrical current is an important component of the total fault current. It is critical that not only the symmetrical interrupting current, but also the circuit breaker total interrupting rating be greater than the system worst-case available fault condition. In the past, we have been able to pay very little attention to the possibility of a system x/r ratio higher than the nominal value of 17 and the resulting total current. Today, with more generation being installed, the momentary rating and the total current capability play a greater role in the sizing of equipment because local generation increases system x/r ratio.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #90 Asymmetrical Interrupting Current Rating of Medium Voltage Circuit Breakers
page 2 The maximum fault current occurs during the first loop of sinusoidal current after the instant of fault initiation. An asymmetrical offset containing a dc component of as much as 160% of the symmetrical current can be impressed on top of the symmetrical ac current in one or two of the three phase currents. This dc component quickly decays and the fault current is greatly reduced in magnitude by the time the contacts part on the circuit breaker (see figure on structure of an asymmetrical current wave). The speed at which this dc component decays is a function of the system x/r ratio. A high x/r ratio means a greater system inductance will dominate the fault current and slow the attenuation of the dc offset.
The %dc that circuit breakers are certified to interrupt, is based on the contact part time and a standard x/r decrement curve. (Refer to Figure 1 above). The combination of the contact part time and the nominal x/r value, results in the maximum value for % dc that the circuit breaker must interrupt. The nominal x/r of 17 coincides well with the typical 60 Hz industrial substation and utilities distribution systems.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #90 Asymmetrical Interrupting Current Rating of Medium Voltage Circuit Breakers
page 3 The %dc is then used to compute the total interrupting current of the circuit breaker at the moment of contact part. The following equation shows how this total current is computed.
Utilizing the chart and this formula we can compute the total current. An illustration will help clarify the calculation. To find the asymmetrical interrupting capability of a 36kA, 3-cycle rated breaker with a published opening time of 25msec, a contact part time of 33msec is used. The contact part time includes cycle of minimum relaying time added to the opening time of the breaker. Using the 33msec contact part time of our sample, we find the breaker is capable of interrupting the 36kA symmetrical current with a 50% dc component riding on top of the symmetrical current when these values are plugged into the formula above, the total rms current is 44kA. Since, this breaker is certified as a 3-cycle breaker it is certified to interrupt a total current of 44kA at time from 3 cycles to 2 seconds. Note that if a 5-cycle breaker was certified, the contact part time is 50 msec. The total interrupting current rating would be 40kA, whether it clears in 5-cycles or 2 seconds. Where does this all become significant? With more and more generation being installed we find that the system x/r ratio plays a much more significant part in applying equipment properly. In many generator bus cases the equipment may have to be oversized to handle the higher level of total current or the tripping of the breaker may have to be delayed a few cycles to allow the dc to decay to an acceptable level.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
These numbers, which apply to air at sea level pressure, are based on measurements over the years. They are basic physical facts. Now, lets see how dew point and relative humidity work. Imagine that at 3:00 pm you measure the air temperature at 30C and you measure its humidity at 9 grams per cubic meter of air. What would happen if this air cooled to 10C with no water vapor being added or taken away? As is cools to 10C, the air becomes saturated; that is, it cannot hold any more water vapor than 9 grams per cubic meter. Cool the air even a tiny bit more and its water vapor will begin condensing to form dew. Back at 3:00 pm, when the measurements were taken, we could say that the airs dew point was 10C. That is, if this particular air were cooled to 10C at ground level, its humidity would begin condensing to form dew. How about relative humidity? At 3:00 pm the air has 9 grams of water vapor per cubic meter of air. We divide 9 by 30 and multiply by 100 to get a relative humidity of 30%. The air actually has 30% of the water vapor it could hold at its current temperature. Cool the air to 20C. Now we divide 9 grams of water vapor, the vapor actually in the air, by 17, the amount of vapor it could hold at its new temperature, and multiply by 100 to get a relative humidity of approximately 53%. Finally, when the air cools to 10C, we divide 9 by 9 and multiply by 100 to get a relative humidity of 100%. The air now has as much vapor as it can hold at its new temperature.
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Electrical Group Powell Electrical Systems, Inc. PO Box 12818 Houston, TX 77217
Powell Technical Brief #92 Arc Resistant Switchgear Tested to ANSI C37.20.7 and NFPA70E
The intent of the 2004 version of NFPA70E, Standard for Electrical Safety in the Work Place, is to minimize the at-risk procedures used by operators of electrical equipment. The first step is to minimize risk by having operators perform work with the equipment only in an electrically safe condition, the second step is to design the hazard out of the normal work procedures, and the third step is to rely on Personal Protective Equipment to minimize the risk to the individual performing the task. Arc resistant switchgear can assist with the first step effort by providing enhanced safety conditions when the operator task involves energized equipment and possible exposure to an arcing fault. Tasks in this category include: Racking a medium voltage circuit breaker to or from the bus connected position Racking a VT or CPT roll-out to or from the bus connected position Opening and closing a circuit breaker Calibrating and troubleshooting devices within the instrument compartment
The purpose of arc resistant switchgear certified to ANSI C37.20.7 is to eliminate the risk from the arc blast and the by-products (heat, pressure, shrapnel, and molten copper) during normal tasks performed on the equipment. During arc fault design tests the energy release by an arcing fault is monitored by mounting racks of a black cotton material in panels covering the surface of the switchgear. This material is similar to 4.5oz/yd untreated t-shirt material identified as Hazard/Risk Category 0 per NFPA70E Table 130.7(c) (11). The panels are mounted at 3.9 inches from all possible seams and one of the many acceptance criteria of ANSI C37.20.7 is that none of the cotton indicators ignites during or following a test. While the focus of NFPA70E is the heat from the arc in medium voltage switchgear, it is the pressure wave associated with the arc fault that dictates the design of the switchgear. The switchgear designed for arc resistant protection requires heavy reinforcing of the entire structure. In conclusion, arc resistant switchgear designs the hazard out of the tasks and reduces the level of risk for normal tasks to a zone 0 category. The result is a reduced need for PPE. The design focus of arc resistant switchgear is to provide the necessary enhanced safety features while requiring no addition maintenance, calibration, or final element tests to assure functionality.