Flat Slab Excel

This document provides design calculations for a flat slab with the following information: - Dimensions and material properties of the slab are given - Preliminary slab thickness of 9 inches is selected based on deflection and minimum thickness requirements - Shear strength is verified at d/2 distance around supports and for wide beam action - Moments are calculated and distributed for different slab regions - Reinforcement is designed for various regions to resist bending moments - Transfer of shear and unbalanced moment at the exterior column is designed with additional reinforcement

Uploaded by

asad_naqvi
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
3K views

Flat Slab Excel

This document provides design calculations for a flat slab with the following information: - Dimensions and material properties of the slab are given - Preliminary slab thickness of 9 inches is selected based on deflection and minimum thickness requirements - Shear strength is verified at d/2 distance around supports and for wide beam action - Moments are calculated and distributed for different slab regions - Reinforcement is designed for various regions to resist bending moments - Transfer of shear and unbalanced moment at the exterior column is designed with additional reinforcement

Uploaded by

asad_naqvi
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 6

Mu =

Vu =
Yr =
C1 =
C2=
d=
a=
b=
c=
Ac =
J/c =

87.9
50
0.4
24
24
6.75
27.375
30.75
8.764803
577.125
5634.237

Vu = Vu/Ac +Yr x Mn / ( J/c ) =

Mu =
Vu =
Yr =
C1 =
C2=
d=
a=
b=
c=
c' = a - c =
Ac =
J/c' =(J/c)(c/c') =

161.5214

87.9
50
0.4
18
24
6.75
21.375
30.75
6.216199
15.1588
496.125
2310.443

Vu = Vu/Ac -Yr x Mn / ( J/c' ) =

-81.8333

FLAT SLAB
DATA
L1 =
L2 =
C1 =
C2 =
Ln =
fc' =
fy =

20.5
16
18
18
19
3,000
50,000

ft.
ft.
in.
in.
ft.
psi
psi

DESIGN
Preliminary design of slab thickness "h"
a) Control of deflection
h = Ln / 33 =
7.6 in.
This is larger than the 5 in. minimum specified for slabs without drop panels.
Therefore use a slab thickness
h =
9 in.
Average effective depth =
d = h - 0.75 - 1/2" bar =
7.75 in.
b) Shear strength of slab
Factored dead load = wd =
Factored live load = wl =
Total factored load = wu =

(h*12.5+FF+SD)*1.4 =
LL*1.7 =

312.9 psf
102 psf
414.9 psf

Investigation for wide beam action on 12" wide strip at "d" distance from face of support
L1/2 - C1/2 - d =
8.854167 ft.
Vu =
3.67 kip
Vc = 2* fc' *bw*d =
10.19 kip
Vc =0.85*Vc=
8.66 kip
3.67 is less than
8.66
OK
Shear strength in two way action at d/2 distance around a support
4*(C1+d/2+d/2) =
bo =
103 in.
2
Vu = wu*[L1*L2 - ((C1+d/2+d/2)/12) ] =
134.18 kip
Vc = 4* fc' *bo*d =
174.89 kip
Vc =0.85*Vc= 148.65 kip
134.18 is less than
148.65
OK

Live Load
Finishes
Super Dead

60
91
20

Factored moments in slab


Total factored moment per span
2
Mo = wu*L2*Ln / 8

299.6 k-ft.

Distribution of the total factored moment Mo per span into negative and positive moments

TOTAL MOMENT
( k-ft.)

COLUMN STRIP
MOMENT ( k-ft )

MIDDLE STRIP
MOMENT ( k-ft )

End span:
Exterior Negative
Positive
Interior Negative

0.26*Mo=
0.52*Mo=
0.70*Mo=

77.9 0.26*Mo=
155.8 0.31*Mo=
209.7 0.53*Mo=

77.9
92.9
158.8

0.21*Mo=
0.17*Mo=

62.9
50.9

Interior span:
Positive
Negative

0.35*Mo=
0.65*Mo=

104.8 0.21*Mo=
194.7 0.49*Mo=

62.9
146.8

0.14*Mo=
0.16*Mo=

41.9
47.9

SPAN LOCATION

Mu

Spacing of
#12 bar
provided

As=Mu/3.9d

As (min.))

77.9
92.9
158.8

120
120
120

6.75
6.75
6.75

2.959
3.528
6.031

1.944
1.944
1.944

10"
8"

0
62.9
50.9

120
120
120

6.75
6.75
6.75

0.000
2.390
1.934

1.944
1.944
1.944

10"
10"
10"

146.8
62.9

120
120

6.75
6.75

5.576
2.390

1.944
1.944

10"

47.9
41.9

120
120

6.75
6.75

1.821
1.593

1.944
1.944

10"
10"

END SPAN
COLUMN Exterior Negative
STRIP
Positive
Interior Negative
MIDDLE
STRIP

Exterior Negative
Positive
Interior Negative

INTERIOR SPAN
COLUMN Interior Negative
STRIP
Positive
.
MIDDLE
STRIP

Interior Negative
Positive

Transfer of gravity load shear and moment at exterior column.

a) Factored shear force transfer at exterior column:


Vu = wu*L1*L2/2 =
68.0436 kip
b) Unbalanced moment transfer at exterior column:

t f x Mu =

0.6*Mu =

46.73 k-ft.

unbalanced moment transfer section = t = C1+2(1.5*h) =


45 in.
Above unbalanced moment must be transferred within the effective width of
45 in.
Add 2 # 16 bars additional over column.
Check moment strength for 4 # 12 + 2 # 16 bars
with in
45 in. slab width.
2
For 4 # 12 + 2 # 16 bars:
As =
1.324 in .
w=
As*fy/fc' *t*d =
Mn / fc'*b*d2 =
From table 9-2
0.0879
2
Mn = w*fc'*b*d =
59.39 k-ft
Mn = 0.9 x Mn =
53.45 k-ft

0.063

>

46.73 k-ft.
Safe

psf
psf
psf

Spacing of
#16 bar
provided

8"

8"