NERC Protection System Protection Fundamentals Public 060210
NERC Protection System Protection Fundamentals Public 060210
Fundamentals
NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell
Agenda
Objective
Introduction to Protection
Generator and Power Plant Protection
Generator Basics
Unique Dynamic Characteristics of Generators Generator and Auxiliary System Protection Requirements
Agenda
Transmission System Protection Basics
Step Distance Principles
Types of Relaying and Schemes Used Pilot and Communications
Infeed
Benefit of Using Pilot Schemes and Effect on Coordination Issues
Pertinent IEEE Guides for Equipment and System Protection and References
Agenda
Summary of What is Important to Coordination
Disclaimer
The information from this webcast is provided for informational purposes only. An entity's adherence to the examples contained within this presentation does not constitute compliance with the NERC Compliance Monitoring and Enforcement Program ("CMEP") requirements, NERC Reliability Standards, or any other NERC rules. While the information included in this material may provide some of the methodology that NERC may use to assess compliance with the requirements of certain Reliability Standards, this material should not be treated as a substitute for the Reliability Standard or viewed as additional Reliability Standard requirements. In all cases, the entity should rely on the language contained in the Reliability Standard itself, and not on the language contained in this presentation, to determine compliance with the NERC Reliability Standards.
Objective
Increase knowledge of recommended protection for power plant and transmission system.
Provide transmission protection engineers with insight into power plant protection issues. Provide power plant protection engineers with insight into transmission protection issues. Provide planning engineers with insight into how power plant and transmission protection respond to system conditions.
Facilitate improved coordination between power plant and transmission system protection.
Introduction to Protection
Reliability
Security
Dependability
Coordination
Electrical Protection Definitions can be found in IEEE Dictionary Standard 100.
10
11
12
E air gap
V terminal
Synchronous Generator Equivalent Circuit identifying armature reaction and armature leakage reactance and air-gap voltage
Voltage Support
Generators on the system are used to maintain voltage. Automatic Voltage Regulators are set to meet a scheduled system voltage and provide reactive power support. Generators provide system control by maintaining terminal voltage during real and reactive power load changes.
13
System Frequency
Balance between generators and system loads. System frequency is maintained through turbine speed control. Excessive load will bog down the system frequency. Light load conditions will increase system frequency.
14
15
DC Current
Reference: Fitzgerald, A. E. , Kingsley, Charles, and Umans, Stephen, Electric Machinery, fourth edition, McGraw-Hill Book Company, New York, 1983.
Time (Cycles)
16
50BF
R
24
59GN /27TH
27
59
81
51G
51TG
21
32
40
46
50/27
51V
78
17
Overexcitation
Load Unbalance Loss-of-Field Loss-of-Synchronism (Outof-Step)
18
19
20
Coordination Concerns Undesired operation for system conditions; especially stressed voltage situations and power swings.
21
22
Undervoltage Protection (Function 27) High Side Protection at Point of Common Coupling
23
Protection measures system voltage at the point of common coupling. Provides a trip of the distributed resource on undervoltage if it is islanded with local load or is subjected to a prolonged system fault. Coordination Concerns Coordinate with:
Any system undervoltage protection,
System fault conditions and stressed system voltage conditions for which the system is designed to survive.
24
Provides alarming or tripping, automatic transfer to backup supply, starting emergency generation. Coordination Concerns Coordinate with:
Any system undervoltage protection, System fault conditions and stressed system voltage situations for which the system is designed to survive.
25
Auxiliary
GSU
System G
Trasfer Switch
System Auxiliary
GSU
System
26
27
28
29
Undesired tripping due to a higher set point should be avoided during stressed system conditions and disturbances that can be survived.
30
31
Provides protection against generator overvoltage. This prevents generator insulation breakdown for sustained overvoltage. Coordination Concerns Coordinate with any system overvoltage protection.
32
Coordination Concerns Proper time delay is required so that the protection does not trip due to inter-winding capacitance issues for faults on the system or instrument secondary grounds.
33
System power swings that are recoverable. Stability studies need to be performed.
34
The UFLS needs to take action first to arrest the abnormal frequency condition.
Generator Differential Protection (Function 87G) and Overall Differential Protection (Function 87U)
35
Protection measures difference current in its associated zone. Provides high-speed phase fault protection for the generator zone (87G) and unit overall zone (87U) Coordination Concerns None except to ensure overlaps are done correctly.
36
Backup Phase (Function 51T) and Backup Ground Overcurrent Protection (Function 51TG)
Protection measures GSU phase and neutral ground current. Provides back-up protection for faults in both the GSU and generator, and for system faults. Coordination Issues
Coordinate with generator protection and the slowest system protection. Use of the backup phase protection (Function 51T) is not recommended due to the difficulty of coordinating with system protection functions and the detection of faults due to the generator fault current decrement.
37
38
39
Transformer Differential Protection (Function 87T) Protection measures difference current in its associated transformer zone. Provides high speed phase fault protection for the transformer zone (87T).
40
41
HV Substation Breaker
42
Coordination Issues
All upstream (next level) protection settings and systems must be considered when evaluating the performance of breaker failure functions associated with generators.
Total clearing time, which includes breaker failure time, of each breaker in the generation station substation should coordinate with the critical clearing times associated with unit stability.
43
44
Infeed
Benefits of Using Pilot Schemes and Effect on Coordination Issues
45
Differential (87)
Step Distance Pilot (Communication-Aided) Schemes
46
47
Infeed
A source of fault current between a relay location and a fault location. Infeed has the effect of causing the relay to measure a higher impedance than the actual impedance between the relay and the fault location. The method of calculating the effect of infeed (also known as apparent impedance) is akin to a current divider relationship of two circuit paths in parallel.
The positive sequence equivalent diagram for the example is shown on the next slide.
48
49
+ XL2)= XB
IA + IB
Xline
XA = Xd + XTR
Restating I in terms of IA and recognizing the current divider relationship of the impedance branches:
IA =Irelay
Vgen = V relay
XB IA I X X A B
XA IA XLine
I = IA + IB XB IB
50
Impacts on dependability and security are dependent on the type of Pilot Scheme implemented.
These factors are related and require a balance.
Power Plant to Transmission System Protection Coordination could benefit from the use of Pilot Schemes due to higher speed and more selective operation.
Communication back to the plant system would also benefit the coordination.
51
IEEE Std. C37.106-2005 IEEE Guide for Abnormal Frequency Protection for Power Generating Plants
IEEE Std C37.113-1999(R2004) IEEE Guide for Protective Relay Applications to Transmission Lines IEEE Std. C37.119-2005 Guide for Breaker Failure Protection of Power Circuit Breakers IEEE Std. 242-2001 IAS Buff Book Protection and Coordination
References
IEEE Press Book - Protective Relaying for Power Systems: Volume 1, 1980. IEEE Press Book - Protective Relaying for Power Systems: Volume 2, 1992. J. Lewis Blackburn, Protective Relaying: Principles and Applications, Marcel Dekker, Inc., 1987. S. Horowitz and A. Phadke, Power System Relaying, John Wiley & Sons, Inc., 1992.
52
A. E. Fitzgerald, Charles Kingsley, Jr., Stephen D. Umans Electric Machinery, McGraw-Hill Book Company, 1983.
References
C. R. Mason, The Art and Science of Protective Relaying, Wiley, 1956.
53
54
55