Fusible Link Temperature Selection Chart

FL-1:
for

05

through

10 Spring Packs (LT, MT)


LINK YIELD TEMPERATURE
165F/74C 212F/100C 286F/138C 360F/182C

LINK PART NUMBER


FL-1-165 FL-1-212 FL-1-286 FL-1-360

MAXIMUM AMBIENT TEMPERATURE


135F/57C 185F/82C 253F/123C 330F/166C

Please consult factory for special order links

Factory Mutual approved; UL and C-UL Listed Minimum Continuous Load: 5 lbs. (2,3 kg) Maximum Continuous Load: 50 lbs. (22,7 kg)

Fusible Link Halves: Stainless Steel Fusible Assembly: Solder, Copper, Stainless Steel

NOTE: Model FL-1 Fusible Links are not rated for use in corrosive atmospheres.

K-Style:

for

12

through

14X Spring Packs (HT, BT)


LINK YIELD TEMPERATURE
135F/57C 165F/74C 212F/100C 280F/138C 360F/182C

LINK PART NUMBER


110135 314165 110212 110280 110360

MAXIMUM AMBIENT TEMPERATURE


104F/41C 135F/57C 185F/82C 253F/123C 330F/166C

Please consult factory for special order links

Minimum Load: 3 lbs. (1.36 kg.) Maximum Load : 50 lbs. (22.68 kg.)

UL listed Corrosion resistant bronze construction

WS-Style:

for

14

through

20 Spring Packs (BT)


LINK YIELD TEMPERATURE MAX. AMBIENT TEMP.

LINK PART NUMBER

WS2-72

162 F / 72 C 200 F / 93 C 286 F / 141 C 360 F / 182 C

109 F / 42 C 145 F / 63 C 232 F / 111 C 305 F / 152 C

NOTE: CANNOT BE USED ON FMAPPROVED ASSEMBLIES

WS2-93 WS2-141 WS2-182

Please consult factory for special order links

WS-style links are used primarily on the BT series design. Links are stacked to provide sure holding until yield temperature is reached.

BI-TORQ Valve Automation and our soldered fusible link manufacturers suggest the annual replacement of fusible links as part of scheduled plant maintenance.

1N050 Linlar Drive P .O. Box 309 La Fox, Il 60147

tel:

630-208-9343 fax: 630-232-6235 www.bitorq.com