Up550manual 3
Up550manual 3
Up550manual 3
IM 05E01C02-42E
1st Edition
Blank Page
<Toc> <Rev>
Introduction
Thank you for purchasing the UP550 program controller.
Program creation
3. Programming
General understand- 3.5 Program Parameter Map ing of programming 3.6 Lists of Program Parameters operations Operating 4. Operations procedures and troubleshooting Brief operation 6.1 Parameter Map
Contains the parameter map used as a guideline for setting parameters. Function description 6.2 Lists of Parameters Briefly describes the functions of parameters. In addition, each parameter table has a User Setting column, where and setpoint you can record your setpoints when setting them in the recording controller.
Media No. IM 05E01C02-42E (CD) 1st Edition : May 2000 (YK) All Rights Reserved Copyright 2000, Yokogawa M&C Corporation
IM 05E01C02-42E
<Toc> <Rev>
ii
I Safety Precautions
The following symbol is indicated on the controller to ensure safe use.
CAUTION
This symbol on the controller indicates that the operator must refer to an explanation in the users manual in order to avoid the risk of injury or death of personnel or damage to the instrument. The manual describes how the operator should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life.
The following symbols are used in the hardcopy users manuals and in the users manual supplied on the CD-ROM.
NOTE
Indicates that operating the hardware or software in a particular manner may damage it or result in a system failure.
IMPORTANT
Draws attention to information that is essential for understanding the operation and/or features of the controller.
IM 05E01C02-42E
<Int> <Rev>
Toc-1
Model UP550 Program Controller Users Manual for Cascade Primary-loop Control
IM 05E01C02-42E 1st Edition
CONTENTS
1. Installation .............................................................................................. 1-1
1.1 1.2 1.3 1.4 1.5 Model and Suffix Codes .................................................................................. 1-1 How to Install ................................................................................................... 1-2 How to Connect Wires .................................................................................... 1-5 Hardware Specifications ................................................................................ 1-7 Terminal Wiring Diagrams ............................................................................ 1-13
2.
3.
4.
IM 05E01C02-42E
<Int> <Rev>
Toc-2
4.11 4.12 Switching to Local-mode (LOCAL) Operation ............................................. 4-13 Changing Setpoint during Local-mode Operation ...................................... 4-14
5.
6.
7.
IM 05E01C02-42E
<Toc>
<1. Installation>
1-1
1.
Installation
This chapter describes installation, wiring, and other tasks required to make the controller ready for operation.
1.1
Optional functions
Check that the following items are provided: Program controller (of ordered model) .................................. 1 Brackets (mounting hardware) ............................................. 1 pair Unit label.............................................................................. 1 Users Manuals for Single-loop Control ................................ 7 (A2 size) Users Manual (Reference) (CD-ROM version) .................... 1
I Correspondence between the Model and Suffix Codes, and the Contact Input/Output Terminals Provided
Check the model ordered and the presence/absence of contact inputs and outputs in the following table.
indicate that the contacts are available.
Model and Suffix Codes UP550UP5500 1 Contact input terminals DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 DO1 Contact output terminals DO2 DO3 DO4 DO5 DO6 DO7
Note: For details on the functions of contact inputs/outputs, see 1.5 Terminal Wiring Diagrams.
IM 05E01C02-42E
<Toc>
<1. Installation>
1-2
1.2
How to Install
NOTE
To install the controller, select a location where: 1. 2. 3. 4. 5. 6. 7. 8. 9. no one may accidentally touch the terminals, mechanical vibrations are minimal, corrosive gas is minimal, temperature can be maintained at about 23C and the fluctuation is minimal, no direct radiant heat is present, no magnetic disturbances are caused, no wind blows against the terminal board (reference junction compensation element), no water is splashed, no flammable materials are around,
150mm
150mm
150mm 150mm
Never place the controller directly on flammable items or equipment. If the controller has to be installed close to flammable items or equipment, be sure to provide shielding panels all around the controller, at least 150 mm away from every side; the panels should be made of either 1.43 mm-thick metal-plated steel plates or 1.6 mmthick uncoated steel plates.
G Installation Position
Install the controller at an angle within 30 from horizontal with the front panel facing upward. Do not install it facing downward. The position of right and left sides should be horizontal.
30
Rear of controller
IM 05E01C02-42E
<Toc>
<1. Installation>
1-3
PVE1 PVE2
91.8
General installation
117 min.
(53)
145 min. N stands for the number of controllers to be installed. However, the measured value applies if N 5.
92
+0.8 0
92
+0.8 0
(25)
92
+0.8 0
112
96
IM 05E01C02-42E
<Toc>
<1. Installation>
1-4
I How to Install
Turn off the power to the controller before installing it on the panel because there is a possibility of electric shock.
CAUTION
After opening the mounting hole on the panel, follow the procedures below to install the controller: 1. 2. Insert the controller into the opening from the front of the panel so that the terminal board on the rear is at the far side. Set the brackets in place on the top and bottom of the controller as shown in the figure below, then tighten the screws of the brackets. Take care not to overtighten them.
Large bracket Panel
(top mounting hardware)
Small bracket
(bottom mounting hardware)
IM 05E01C02-42E
<Toc>
<1. Installation>
1-5
1.3
CAUTION
2)
NOTE
1) Provide power from a single-phase instrument power supply. If there is a lot of noise in the power line, insert an insulating transformer into the primary side of the line and use a line filter (recommended part: ZAC2205-00U from TDK) on the secondary side. As a countermeasures against noise, do not place the primary and secondary power cables close to each other. For thermocouple input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires. The cables to be used for wiring, terminal specifications, and recommended parts are as shown below. Control output relays may be replaced. However, because they have a life of 100,000 times that of the resistance load, use auxiliary relays to turn on/off a load. The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
2)
3) 4)
R
UPs contact Diode (Mount it directly to the relay coil terminal (socket).) UPs contact
Relay (Use one with a relay coil rating less than the UPs contact rating.)
Relay (Use one with a relay coil rating less than the UPs contact rating.)
IM 05E01C02-42E
<Toc>
<1. Installation>
1-6
3.7mm
7 mm or less 7 mm or less
3.7mm
or
G Terminal Covers
Target Model For UP550 Part Number T9115YD 1 Sales Unit
IM 05E01C02-42E
<Toc>
<1. Installation>
1-7
1.4
Hardware Specifications
PV Input Signals
Number of inputs: 1 (terminals
11 - 12 - 13 )
Input type: Universal input system. The input type can be selected with the software. Sampling period: Can be selected from 100, 200 and 500 ms. Initial value: 200 ms Burnout detection: Functions at TC, RTD and standard signal (0.4 to 2 V or 1 to 5 V) Upscale, downscale, and off can be specified. For standard signal, burnout is determined to have occurred if it is 0.1 V or less. Input bias current: 0.05 A (for TC or RTD b-terminal) Measurement current (RTD): About 0.13 mA Input resistance: 1 M or more for thermocouple or mV input About 1 M for DC voltage input Allowable signal source resistance: 250 or less for thermocouple or mV input Effects of signal source resistance: 0.1 V/ or less 2 k or less for DC voltage input Effects of signal source resistance: About 0.01%/100 Allowable wiring resistance: for RTD input Maximum 150 /wire: Conductor resistance between three wires should be equal However, maximum 10 /wire for a range of -150.0 to 150.0C. Wire resistance effect: 0.1C/10 Allowable input voltage: 10 V DC for thermocouple, mV, or RTD input 20 V DC for DC voltage input Noise rejection ratio: 40 dB (50/60 Hz) or more in normal mode 120 dB (50/60 Hz) or more in common mode Reference junction compensation error: 1.0C (15 to 35C) 1.5C (0 to 15C, 35 to 50C) Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples and RTD
Input type: Settable in a range of 0-2, 0-10, 0.4-2.0, or 1-5 V DC Sampling period: 100, 200 and 500 ms The sampling period of a auxiliary input signal is associated with the PV inputs sampling period. Input resistance: About 1 M Input accuracy: 0.3% of input span 1 digit for 0 to 2 V DC 0.2% of input span 1 digit for 0 to 10 V DC 0.375% of input span 1 digit for 0.4 to 2.0 V DC 0.3% of input span 1 digit for 1 to 5 V DC Under standard operating conditions (232C, 5510% RH, power frequency of 50/ 60 Hz)
IM 05E01C02-42E
<Toc>
<1. Installation>
1-8
Retransmission Output
Either PV, program setpoint, or control output is output. Either the retransmission output or the loop power supply can be used with terminals 14 - 15 . Number of outputs: 1 (terminals
14 - 15 )
Output signal: 4-20, 0-20, 20-4, or 20-0 mA DC (where, outputting signal levels of less than 0 mA is not feasible) Load resistance: 600 or less Output accuracy: 0.1% of span (5% of span for 1 mA or less.) Under standard operating conditions (232C, 5510% RH, power frequency of 50/ 60 Hz)
Control Output
Universal output system, The output type can be selected with the software. Current output (Standard type: terminals
Number of outputs
16 - 17 )
1 switched between a voltage pulse output and current output. 4-20, 0-20, 20-4, or 20-0 mA DC 600 or less 0.1% of span (5% of span for 1 mA or less) Under standard operating conditions (232C, 5510% RH, power frequency of 50/60 Hz)
16 - 17 )
Output signal On-voltage = 12 V or more (load resistance: 600 or more) Off-voltage = 0.1 V DC or less Resolution 10 ms or 0.1% of output, whichever is larger
1 Three terminals (NC, NO, and common) 250 V AC or 30 V DC, 3 A (resistance load) 10 ms or 0.1% of output, whichever is larger
IM 05E01C02-42E
<Toc>
<1. Installation>
1-9
Contact Inputs
Purpose: Program pattern no. selection, and run/reset switching Number of inputs: Differs with model and suffix codes as shown in the table below.
Model and Suffix Codes UP550UP5500 1 Number of Inputs 7 8
Input type: Non-voltage contact or transistor open collector input Input contact rating: 12 V DC, 10 mA or more On/off determination: For non-voltage contact input, contact resistance of 1 k or less is determined as on and contact resistance of 20 k or more as off. For transistor open collector input, input voltage of 2 V or less is determined as on and leakage current must not exceed 100 A when off. Minimum status detection hold time: PV inputs sampling period 3
Contact Outputs
Purpose: Event output, FAIL output, and others Number of outputs: 7 points Relay contact rating: 240 V AC, 1 A, or 30 V DC, 1 A Transistor contact rating: 24 V DC, 50 mA
Display Specifications
PV display: 5-digit, 7-segment, red LEDs, character height of 20 mm Setpoint display: 32128 dot LCD with back lighting Status indicating lamps: LEDs
IM 05E01C02-42E
<Toc>
<1. Installation>
1-10
Installation position: Up to 30 upward facing (not designed for facing downward) Wiring: M3.5 screw terminals (for signal wiring and power/ground wiring as well)
Note: The withstanding voltage is specified as 2300 V AC per minute to provide a margin of safety.
Insulation resistance: 20 M or more at 500 V DC between power terminals and grounding terminal Grounding: Class 3 grounding (grounding resistance of 100 or less)
IM 05E01C02-42E
<Toc>
<1. Installation>
1-11
Signal Isolations
PV input terminals: Isolated from other input/output terminals. Not isolated from the internal circuit. Auxiliary analog input terminals: Isolated from other input/output terminals and the internal circuit 15 V DC loop power supply terminals: Not isolated from analog current output and voltage pulse control output. Isolated from other input/output terminals and internal circuit. Analog current output terminals (for control output and retransmission): Not isolated between current outputs and from 15 V DC loop power supply and voltage pulse control output. Isolated from other input/output terminals and internal circuit. Voltage pulse control output terminals: Not isolated from current outputs and 15 V DC loop power supply. Isolated from other input/output terminals and internal circuit. Relay contact control output terminals: Isolated between contact output terminals and from other input/output terminals and internal circuit. Contact input terminals: Not isolated between contact input terminals and from communication terminals. Isolated from other input/output terminals and internal circuit. Relay contact output terminals: Not isolated between relay contact outputs. Isolated from other input/output terminals and internal circuit. Transistor contact output terminals: Not isolated between transistor contact outputs. Isolated from other input/output terminals and internal circuit. RS-485 communication terminals: Not isolated from contact input terminals. Isolated from other input/output terminals and internal circuit. Power terminals: Isolated from other input/output terminals and internal circuit. Grounding terminals: Isolated from other input/output terminals and internal circuit.
IM 05E01C02-42E
<Toc>
<1. Installation>
1-12
Environmental Conditions
Normal operating conditions: Ambient temperature: 0 to 50C (40C or less for side-by-side close installation) Temperature change rate: 10C/h or less Ambient humidity: 20 to 90% RH (no condensation allowed) Magnetic field: 400 A/m or less Continuous vibration at 5 to 14 Hz: Full amplitude of 1.2 mm or less Continuous vibration at 14 to 150 Hz: 4.9 m/s2 or less Short-period vibration: 14.7 m/s2, 15 seconds or less Shock: 14.7 m/s2 or less, 11 ms Installation height: Height above sea level of 2000 m or less Warm-up time: 30 minutes or more after power on Transportation and storage conditions: Temperature: -25 to 70C Temperature change rate: 20C/h or less Humidity: 5 to 95% RH (no condensation allowed) Effects of changes in operating conditions Effects from changes in ambient temperature: On voltage or thermocouple input, 1 V/C or 0.01% of F.S./C, whichever is larger On auxiliary analog input, 0.02% of F.S./C On RTD input, 0.05C/C (ambient temperature) or less On analog output, 0.05% of F.S./C or less On analog input, 1 V/10 V or 0.01% of F.S./10 V, whichever is larger On analog output, 0.05% of F.S./10 V or less
IM 05E01C02-42E
<Toc>
<1. Installation>
1-13
1.5
Terminal wiring diagrams are shown on and after the next page.
IM 05E01C02-42E
<Toc>
23 SDB(+) 24
SDA(-)
for controllers with communication functions. Maximum baud rate: 9600 bps
Tracking signal * Wiring can only be carried out for controllers with auxiliary analog input. Auxiliary analog input
Primary * Not configured at factory before shipment PV input See 2. Initial Settings. TC input 12 + RTD input 11 A
12 +
250 4-20mA
25 RDB(+) 26 27
RDA(-) SG
21 + 22 -
Specify in a range of 1-5 V DC, 0-2 V DC, or 0-10 V DC. Default: 1-5 V DC
41 42 43 44 45 46 47 48 49 50
31 32 33 34 35 36 37 38 39 40
21 22 23 24 25 26 27 28 29 30
11 12 13 14 15 16 17 18 19 20 16 +
4-20mADC
Note: Connecting a 250 resistor to the terminals is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
4 5 CAUTION
Before carrying out wiring, turn off the power to the controller and check that cables to be connected are not alive with a tester or the like because there is a possibility of electric shock.
Retransmission output 1*
* Factory-set to PV retransmission.
8 9 10
6 7 8 9 10
14 + 15 -
4-20 or 0-20 mA DC
Default: 4-20 mA DC
Allowable range: 100-240 V AC (10%) (free voltage) 50/60 Hz shared * The functions of the external outputs are the defaults for cascade primary-loop control. To change the functions, reconfigure the Contact Output Registration setup parameters.
* The functions of the external inputs are the defaults for cascade primary-loop control. To change the functions, reconfigure the Contact Input Registration setup parameters.
Contact
+5V DI1 +5V DI2 +5V DI3 +5V DI4 +5V +5V +5V DI7 COM DI5 DI6 19 18 40 39 38
Transistor contact
Relay Transistor
13
Start of program operation when DI5 changes from OFF to ON Stop of program operation when DI6 changes from OFF to ON Tracking switching signal output when DI7=ON, Result of PID computation output when DI7=OFF Common ON when using 16 or more of program patterns
<1. Installation>
37 36 20
Two-wire transmitter
14 4-20mADC 15
Loop power supply 14.518.0 V DC
COM 35
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load) Transistor contact rating: 24 V DC, 50 mA
Common
Note: Connecting a 100 resistor to the terminals is optional. Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
1-14
<Toc>
2-1
2.
Initial Settings
This chapter describes examples of setting PV input types. Refer to examples of various settings to understand how to set parameters required. Refer to 6.1 Parameter Map for an easy to understand explanation of setting various parameters. If you cannot remember how to carry out an operation during setting, press the DISP key no more than four times. This brings you to the display (operating display) that appears at power-on. After carrying out the settings described here, create programs in 3. Programming.
Setup Procedure
Power-on
Denotes a step that must always be followed. Denotes a step that should be followed as necessary.
Set UP mode 2.
See 2.2 Setting UP mode (Setting First at Power-on), or 2.3 Changing UP mode. Set PV input. (Factory-set to not configured.)
See 2.5 Changing Tracking Input Type. Initialize parameters. See 2.6 Initializing Parameters. Set setup parameters. Be sure to follow this step whenever a change of setting is made to the UP mode or to the PV input type.
See 3. Programming.
Controller operation
IM 05E01C02-42E
<Toc>
2-2
2.1
6. Process variable (PV) display 7. Setpoint display 10. MODE key 11. DISP key 12. and keys
1. 2.
Name of Part Indicator lamp for PV2 display Program monitor lamps
3.
Function Is lit when secondary PV is displayed on PV display. Not used in Cascade Primary-loop Control. : Is lit (in green) when a program setpoint is increasing. : Is lit (in green) when a program setpoint is constant. : Is lit (in green) when a program setpoint is decreasing. Display the statuses of PV events, time events and instrument alarm in orange. PVE1 and PVE2 lamps: Come on when PV event 1 and PV event 2 turn on. TME1 to TME4 lamps: Come on when time event 1 to time event 4 turn on. AL1 lamp: Comes on when instrument alarm 1 turns on. Is lit (in green) to indicate the status of operation or control. PRG:Is lit when in program mode. RST:Is lit when in reset mode. HLD:Is lit when in hold mode. LOC:Is lit when in local mode. MAN:Is lit when in manual mode. CAS:Not used in Cascade Primary-loop Control. Interface for an adapter cable used when setting and storing parameters from a PC. This requires an optional parameter setting tool. Displays PV. Displays an error code (in red) if an error occurs. Displays the name and value of a program setpoint (SP), output (OUT), deviation trend, valve opening, or a parameter. Displays an error code if an error occurs. The AL1 lamp comes on in orange if instrument alarm 1 occurs.
4.
5. 6. 7. 8. 9.
Light-loader interface Process variable (PV) display Setpoint display (LCD) Instrument alarm indicator lamps
SET/ENT
SET/ENT key
MODE
Used to switch or register a parameter. Pressing the key for more than 3 seconds allows you to switch between the operating display and the main menu for operating parameter setting display alternately. Presents a display for switching between the hold, advance, local, AUTO and MAN modes. Used to switch between displays. Pressing this key while any operating display is shown lets you switch to another prearranged operating display. Pressing this key while any display other than an operating display is shown lets you go one display back. (One to four presses (maximum) of this key lets you return to the current operating display, though the number of presses depends on the operating status.) Used to change numerical values. On setting displays for various parameters, you can change target setpoints, parameters, and output values (in manual operation). Pressing the key decreases a numerical value, while pressing the key causes it to increase. You can hold down a key to gradually increase the speed of change. These keys also switch between menu displays when a main menu or submenu of parameter setting display is shown.
DISP
12.
and
keys
PT.No
Use this key when the controller is at a reset to select a program pattern number on an operating display.
RUN RESET
Pressing this key for more than 2 seconds while an operating display is shown starts the controller. Pressing this key for more than 2 seconds while an operating display is shown stops the controller.
IM 05E01C02-42E
<Toc>
2-3
2.2
The following operation describes a procedure of setting a UP mode to Cascade Primaryloop Control (set 2).
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
IN
sub menu
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
4.
MD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
Press the key once to display the parameter UPM (controller mode).
SET/ENT
5.
SET/ENT
#1 SETUP 1
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
6.
The controller re-starts (which is normal). Then, set PV input type. See step 8 and later of 2.4 Setting Primary PV Input Type.
IN
sub menu
IM 05E01C02-42E
<Toc>
2-4
2.3
1.
Changing UP mode
The following operation describes a procedure of changing a UP mode to Cascade Primary-loop Control (set 2).
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
-270.0C
SEGNO: 0/ 0 RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
Press the key for more than 3 seconds to call up the main menu PROG.
SET/ENT
5.
PROG
UPMD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
6.
STUP
MD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
4.
7.
PARA
#1 SETUP 1
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
2-5
8.
10.
The controller re-starts (which is normal). Then, set PV input type. See step 8 and later of 2.4 Setting Primary PV Input Type.
IN
sub menu
SET/ENT
MODE
PT.No
DISP
RUN RESET
9.
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
2-6
2.4
RH1
0.0m /h
Parameters to be set for temperature input 1. PV input type (IN1): Set according to a sensor 2. Maximum value of PV input range (RH1): Set the maximum value of the range to be controlled. 3. Minimum value of PV input range (RL1): Set the minimum value of the range to be controlled.
Parameters to be set for voltage input 1. PV input type (IN1): Set according to an input signal 2. Maximum value of PV input range (RH1): Set the maximum value of an input signal. 3. Minimum value of PV input range (RL1): Set the minimum value of an input signal. 4. Position of PV input decimal point (SDP1): Set the position of the decimal point for PV input display. 5. Maximum value of PV input scale (SH1): Set the maximum value of the scale to be controlled. (Set a reading for the maximum value of the input signal.) 6. Minimum value of PV input scale (SL1): Set the minimum value of the scale to be controlled. (Set a reading for the minimum value of the input signal.)
NOTE
The controller may automatically initialize the registered operating parameter setpoints if any change is made to the data item PV Input Type (IN1), Maximum Value of PV Input Range (RH1), Minimum Value of PV Input Range (RL1), PV Input Decimal Point Position (SDP1), Maximum Value of PV Input Scale (SH1) or Minimum Value of PV Input Scale (SL1). After a change has been made to any of these data items, be sure to verify the registered operating parameter setpoints to ensure that they are correct. If any data item has been changed to its default, set it to a required value.
1.
Bring the operating display into view (display appears at power-on). The PV display in the figure below shows the error code for input burnout ( ) if PV input wiring is not yet complete. The error code disappears when you wire the PV input terminals correctly.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
-270.0C
SEGNO: 0/ 0 RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
IM 05E01C02-42E
<Toc>
2-7
2.
Press the key for more than 3 seconds to call up the main menu PROG.
7.
PROG
IN
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
8.
Press the key once to display the parameter IN1 (PV input type).
SET/ENT
STUP
#1
SETUP OFF
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
4.
9.
PARA
Press the or key to display the required setpoint. The figure below shows an example of setting the PV input type to a K-type thermocouple (-200.0C to 500.0C).
MENU:UPMD/IN input 1 type select IN1 = #1
changing! typeK3
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
5.
UPMD
10.
SET/ENT
SETUP typeK3
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
6.
MD
11.
#2 SETUP C
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
2-8
12.
Press the key once to display the parameter RH1 (maximum value of PV input range).
MENU:UPMD/IN input 1 range high RH1 = #3
15.
Press the key once to display the parameter RL1 (minimum value of PV input range).
SET/ENT
#4
SETUP 500.0
SETUP -200.0
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
13.
Press the or key to display the required setpoint. The figure below shows an example of setting the maximum value of the PV input range to 200.0C.
MENU:UPMD/IN input 1 range high RH1 = #3
16.
Press the or key to display the required setpoint. The figure below shows an example of setting the minimum value of the PV input range to 0.0C.
MENU:UPMD/IN input 1 range low #4 changing! 0.0
changing! 200.0
RL1
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
14.
SET/ENT
17.
SET/ENT
SETUP 200.0
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
If the type of input is voltage, also configure the PV Input Decimal Point Position (SDP1), Maximum Value of PV Input Scale (SH1) and Minimum Value of PV Input Scale (SL1) parameters that are displayed after this.
18.
Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below).
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
IM 05E01C02-42E
<Toc>
2-9
* Performance in the standard operating conditions (at 232C, 5510%RH, and 50/60 Hz power frequency) Note 1: The accuracy is 0.3C of instrument range 1 digit for a temperature range from 0C to 100C. Note 2: The accuracy is 0.5C of instrument range 1 digit for a temperature range from -100C to 200C. * To receive a 4-20 mA DC signal, select a standard signal of 1 to 5 V DC and connect it to a 250 resistor. This resistor is optional. Model: X010-250-2 (resistor with M3.5 crimp-on terminal lugs)
IM 05E01C02-42E
<Toc>
2-10
2.5
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
Press the key for more than 3 seconds to call up the main menu PROG.
SET/ENT
5.
PROG
UPMD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
6.
STUP
MD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
4.
7.
PARA
IN
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
2-11
8.
Press the key once to display the parameter IN3 (tracking input type).
MENU:UPMD/IN input 3 type select IN1 = #19
10.
SET/ENT
SETUP 1 - 5V
SETUP 0 - 10V
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
9.
Press the or key to display the required setpoint. The figure below shows an example of setting the tracking input type to a DC voltage (0 to 10 V DC).
MENU:UPMD/IN input 3 type select IN1 = #19
changing! 0 - 10V
SET/ENT
MODE
PT.No
DISP
RUN RESET
11.
Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below).
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
IM 05E01C02-42E
<Toc>
2-12
2.6
1.
Initializing Parameters
Be sure to follow the steps below after a change of setting has been made to the data item PV Input Type, PV Input Range or PV Input Scale.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
Press the key for more than 3 seconds to call up the main menu PROG.
SET/ENT
5.
PROG
UPMD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
6.
STUP
MD
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
4.
7.
PARA
INIT
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
2-13
8.
10.
Press the key once. The display momentarily becomes blank (which is normal), indicating the parameters have been initialized.
SET/ENT
SETUP OFF
#1 SETUP ON
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
9.
Press the
SET/ENT
MODE
PT.No
DISP
RUN RESET
11.
Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below).
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
IM 05E01C02-42E
Blank Page
<Toc>
<3. Programming>
3-1
3.
Programming
This chapter explains how to create programs by citing specific examples. Create user programs by referring to the given programming examples. Use the parameter map included in 3.5 Program Parameter Map, in order to further familiarize yourself with the required operations. Be sure to carry out the settings instructed in 2. Initial Settings before beginning any of the tasks discussed in this chapter.
3.1
I Programming Overview
Event output Set a deviation of 5C on both the positive and negative sides of a program setpoint to allow the controller to output an event signal if the temperature goes beyond the deviation range. Let the controller output an event signal when the temperature stabilizes to 80C.
Example of Creating Program Pattern 1 Temperature
Target setpoint (TSP1) to be reached by segment 2
80C
2
Target setpoint (TSP1) to be reached by segment 1 Target setpoint (TSP1) to be reached by segment 3
3
Starting target setpoint (SSP1) 25C 0C
Segment time for segment 1 Segment time for segment 2 Segment time for segment 3
Time
80 min.
10 min.
PV event 1
Outputs an alarm if the temperature goes beyond the range program setpoint 5C.
ON
OFF
Time event 1
The output turns on after 20 minutes have elapsed since the start of program operation. Then, it turns off after 100 minutes have elapsed from the start of program operation.
IM 05E01C02-42E
<Toc>
<3. Programming>
3-2
3.2
Number of repetitions (RCY) Start-of-repetition segment number (RST) End-of-repetition segment number (REN)
IM 05E01C02-42E
<Toc>
Unit 3 C Maximum value of PV input range (RH1) 100% Define when using the controller as a program pattern generator. See Users Manual (Reference) (CD-ROM version) for more information. Minimum value of PV input range (RL1) 0% 2 0 1 100 80C
<3. Programming>
9
3-3
25C
Segment No. Final target setpoint 1 (TSP1) Final target setpoint 2 (TSP2) Segment time (TIME/TM.RT) PID number (PID) (Note) Event number (EV1) PV event type (TY1)/on time of time event (ON1) PV event setpoint (PE1)/off time of time event (OFF1) Event number (EV2) PV event type (TY2)/on time of time event (ON2) PV event setpoint (PE2)/off time of time event (OFF2) Event number (EV3) PV event type (TY3)/on time of time event (ON3) PV event setpoint (PE3)/off time of time event (OFF3) Event number (EV4)
1 2 3 4 5 6 7 8 9 10 11 12 1
80C 80C 0C
20 min 80 min 10 min
21 7
1
0 min
5C 80 min
PV event type (TY4)/on time of time event (ON4) PV event setpoint (PE4)/off time of time event (OFF4) Event number (EV5) PV event type (TY5)/on time of time event (ON5) PV event setpoint (PE5)/off time of time event (OFF5) Event number (EV6) PV event type (TY6)/on time of time event (ON6) PV event setpoint (PE6)/off time of time event (OFF6) Event number (EV7) PV event type (TY7)/on time of time event (ON7) PV event setpoint (PE7)/off time of time event (OFF7) Event number (EV8) PV event type (TY8)/on time of time event (ON8) PV event setpoint (PE8)/off time of time event (OFF8) Junction code (JC) 0
Note: This parameter is shown for segment PID parameter when the setup parameter ZON is set to 0.
IM 05E01C02-42E
<Toc>
<3. Programming>
3-4
3.3
NOTE
Before creating the program, reverify the Maximum Value of PV Input Range (RH1), Minimum Value of PV Input Range (RL1), Program Time Unit (TMU), and Segment Setting Method (SEG.T) parameters. If the setting of the setup parameter SEG.T is changed, the program patterns created and stored so far will be all cleared (initialized)!! Be careful.
The programming example given in this section includes the following steps. Step 5 selects the program pattern number (PTN). Steps 7 to 9 configure the parameter Starting Target Setpoint (SSP1) (so that the program starts from 25C). Steps 11 to 13 configure the Final Target Setpoint (TSP1) parameter for segment 1. Steps 14 to 16 configure the Segment Time (TIME) parameter for segment 1. Steps 17 to 25 configure the PV Event parameters (EV1, TY1 and PE1). Step 28 configures the Final Target Setpoint (TSP1) parameter for segment 2 (not changed in this example). Steps 29 to 31 configure the Segment Time (TIME) parameter for segment 2. Steps 32 to 40 configure the Time Event parameters (EV1, ON1 and OFF1). Steps 43 to 45 configure the Final Target Setpoint (TSP1) parameter for segment 3. Steps 46 to 48 configure the Segment Time (TIME) parameter for segment 3.
1.
PV2
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
For steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
Press the key for more than 3 seconds to call up the main menu PROG.
SET/ENT
3.
PROG
LOC
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
3-5
4.
8.
PRG
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 25.0C.
MENU:PROG/PRG start set point 1 SSP1 = #3 changing! 25.0C
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
5.
Press the key once to display the Pattern Number parameter PTN. At this point, the PV display shows 01.00 (the first two digits denote the pattern number and the last two digits the segment number).
SET/ENT
9.
SET/ENT
PV Display
MENU:PROG/PRG PTno.input PTN = 1 #1
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
10.
Press the key once to display the Start Code parameter STC.
SET/ENT
#5
6.
Press the key once to display the Segment Number parameter SEG.
SET/ENT
STC
SET/ENT
#2
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
11.
7.
Press the key once to display the Starting Target Setpoint parameter SSP1.
SET/ENT
Press the key once to display the Target Setpoint parameter TSP1 for segment 1. At this point, the PV display shows 01.01 (the first two digits denote the pattern number and the last two digits the segment number).
SET/ENT
#3
PV Display
MENU:PROG/PRG target set point 1 TSP1 = 25.0C #24
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
3-6
12.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 80.0C.
MENU:PROG/PRG target set point 1 TSP1 = #24 changing! 80.0C
17.
Press the key once to display the Event Number parameter EV1.
SET/ENT
#29
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
18. 13.
Press the setpoint.
SET/ENT
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to PV event 1 (setpoint 21).
MENU:PROG/PRG event 1 no. select EV1 = #29 changing! 21
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
MODE
PT.No
DISP
RUN RESET
14.
Press the key once to display the Segment Time parameter TIME for segment 1.
SET/ENT
19.
SET/ENT
#26
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
15.
20.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 20 min. (0h20).
MENU:PROG/PRG segment time TIME = #26
Press the key once to display the PV Event Type parameter TY1.
SET/ENT
#30
changing! 0h20
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
16.
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
3-7
21.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to Deviation high and low limits Alarm (setpoint 7).
MENU:PROG/PRG PV event 1 type TY1 = #30 changing! 7
26.
Press the key once to display the Event Number parameter EV2.
SET/ENT
#32
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
27.
22.
SET/ENT
Press the key once to display the Junction Code parameter JC for segment 1. The setpoint of this parameter is not changed in this example.
SET/ENT
#53
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
23.
Press the key once to display the PV Event Setpoint parameter PE1.
SET/ENT
28.
#31
SET/ENT
MODE
PT.No
DISP
RUN RESET
Press the key once to display the Target Setpoint parameter TSP1 for segment 2. The setpoint of this parameter is not changed in this example. At this point, the PV display shows 01.02 (the first two digits denote the pattern number and the last two digits the segment number).
SET/ENT
PV Display
24.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 5.0C.
MENU:PROG/PRG PV event 1 set point PE1 = #31 changing! 5.0C
#24
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
29.
Press the key once to display the Segment Time parameter TIME for segment 2.
SET/ENT
25.
SET/ENT
#26
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
3-8
30.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 1 hr. and 20 min. (setpoint 1h20).
MENU:PROG/PRG segment time TIME = #26
34.
SET/ENT
changing! 1h20
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
35.
Press the key once to display the On Time of Time Event parameter ON1.
SET/ENT
31.
SET/ENT
#30
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
36.
32.
Press the key once to display the Event Number parameter EV1.
SET/ENT
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 0 min. (setpoint 0h00).
MENU:PROG/PRG time event 1 ON time ON1 = #30
#29
changing! 0h00
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
33.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to time event 1 (setpoint 1).
MENU:PROG/PRG event 1 no. select EV1 = #29
37.
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
changing! 1
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
SET/ENT
3-9
38.
Press the key once to display the Off Time of Time Event parameter OFF1.
MENU:PROG/PRG time event 1 OFF time OFF1 = OFF #31
43.
Press the key once to display the Target Setpoint parameter for segment 3. At this point, the PV display shows 01.03 (the first two digits denote the pattern number and the last two digits the segment number).
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
PV Display
MENU:PROG/PRG target set point 1 #24
39.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 1 hr. and 20 min. (setpoint 1h20).
MENU:PROG/PRG #31 time event 1 OFF time changing! OFF1 = 1h20
TSP1
80.0C
SET/ENT
MODE
PT.No
DISP
RUN RESET
44.
SET/ENT
MODE
PT.No
DISP
RUN RESET
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 0.0C.
MENU:PROG/PRG target set point 1 TSP1 = #24 changing! 0.0C
40.
SET/ENT
MODE
PT.No
DISP
RUN RESET
#31
45.
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
41.
Press the key once to display the Event Number parameter EV2.
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
#32
46.
SET/ENT
MODE
PT.No
DISP
RUN RESET
Press the key once to display the Segment Time parameter TIME for segment 3.
SET/ENT
#26
42.
Press the key once to display the Junction Code parameter JC for segment 2. The setpoint of this parameter is not changed in this example.
SET/ENT
TIME
SET/ENT
MODE
PT.No
DISP
RUN RESET
#53
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
3-10
47.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 10 min. (setpoint 0h10).
MENU:PROG/PRG segment time TIME = #26
48.
SET/ENT
changing! 0h10
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
49.
Programming is now complete. Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below).
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
IM 05E01C02-42E
<Toc>
<3. Programming>
3-11
3.4
80 min.
10 min.
Time
Change the setpoint of the Target Setpoint (TSP1) program parameter for segment 2 to 90.0.
IM 05E01C02-42E
<Toc>
<3. Programming>
3-12
1.
PV2
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
For steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
Press the key for more than 3 seconds to call up the main menu PROG.
SET/ENT
6.
Press the key once to display the Segment Number parameter SEG.
SET/ENT
PROG
#2
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
7.
Press the key twice to display the Start Code parameter STC.
SET/ENT
LOC
#5
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
4.
8.
PRG
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to time-prioritized PV start (setpoint 2).
MENU:PROG/PRG start code select #5 changing! 2
SET/ENT
MODE
PT.No
DISP
RUN RESET
STC
SET/ENT
MODE
PT.No
DISP
RUN RESET
5.
Press the key once to display the Pattern Number parameter PTN.
SET/ENT
#1
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<3. Programming>
SET/ENT
3-13
9.
12.
Press the or key to display the required setpoint. The figure below shows an example of the parameter set to 90.0C.
MENU:PROG/PRG target set point 1 TSP1 = #24
changing! 90.0C
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
10.
Press the key once to display the Target Setpoint parameter TSP1 for segment 1.
SET/ENT
13.
#24
SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
11.
Press the key seven times to display the Target Setpoint parameter TSP1 for segment 2. At this point, the PV display shows 01.02 (the first two digits denote the pattern number and the last two digits the segment number).
SET/ENT
PV Display
MENU:PROG/PRG target set point 1 TSP1 = 80.0C #24
SET/ENT
MODE
PT.No
DISP
RUN RESET
14.
Changing the program is now complete. Press the you to the display shown at power-on (figure below).
PV2
SET/ENT
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
IM 05E01C02-42E
<Toc>
<3. Programming>
3-14
3.5
Operating display
key Press this key for more than 3 seconds.
PROG
programming main menu
Press the key for more than 3 seconds to switch to an operating display.
SET/ENT
SET/ENT
key
DISP
key
key or
key
key or
A PRG
programming sub menu
LOC
local mode set sub menu
key
key or
key
SET/ENT
key
DISP
key
SET/ENT
key
DISP
key
Program pattern 1 LSP1 PID E21A E21B E22A E22B E23A E23B E24A E24B E25A E25B E26A E26B E27A E27B E28A E28B
Setpoint for local-mode operation PID group number for local-mode operation Local event-21 type Local event-21 setpoint Local event-22 type
SET/ENT
#1
key or
key
Segment 1
MENU:PROG/PRG SEGno. input SEG = 0 #2
Segment 2
#2
key or
#2
key or
key
key or
key
key
Local event-22 setpoint Local event-23 type Local event-23 setpoint Local event-24 type Local event-24 setpoint Local event-25 type Local event-25 setpoint Local event-26 type Local event-26 setpoint Local event-27 type Local event-27 setpoint Local event-28 type Local event-28 setpoint
key
SET/ENT
key
SET/ENT
key
SSP1
Final target setpoint Time-set segment time Ramp-set segment time PID group number
TIME is shown when the Segment Setting Method (SEG.T) parameter is set using a time setpoint; TM.RT is shown when the Segment Setting Method (SEG.T) parameter is set using a ramp grade setpoint. The controller is factory-set to show TIME. The parameter PID is shown for segment PID parameters when the setup parameter ZON is set to 0.
Final target setpoint Time-set segment time Ramp-set segment time PID group number
STC
STC= 1
Start code
STC 1
PID
1st group of wait zones 1st group of wait times 2nd group of wait zones 2nd group of wait times 3rd group of wait zones 3rd group of wait times 4th group of wait zones 4th group of wait times 5th group of wait zones
Event number On time of time event Off time of time event PV event type PV event setpoint
n = 1 to 8. If EVn = 1 to 16, then this parameter refers to time events 1 to 16. If EVn = 21 to 28, then this parameter refers to PV events 1 to 8.
Event number On time of time event Off time of time event PV event type PV event setpoint
SET/ENT
key
The parameter PID is shown for segment PID parameters when the setup parameter ZON is set to 0.
JC
Junction code
JC
Junction code
SET/ENT
5th group of wait times Number of repetitions Start-of-repetition segment number End-of-repetition segment number
key
SET/ENT
key
SET/ENT
key
IM 05E01C02-42E
<Toc>
<3. Programming>
3-15
EDIT
program edit sub menu
SET/ENT
key
DISP
key
Program patterns 2 to 30
MENU:PROG/PRG PTno. input PTN = 2 #1
ALL.S
key or
Segment 3
MENU:PROG/PRG SEGno. input SEG = 3 #2
key or key or
key
Segment 99
MENU:PROG/PRG SEGno. input SEG = 99 #2 MENU:PROG/PRG SEGno. input SEG = 0 #2
Shows the number of remaining unused segments. Shows the number of segments within a pattern. Shows the number of remaining unused events. Program pattern copying Program pattern clearance
key
key
SET/ENT
key
SET/ENT
key
SET/ENT
key
Final target setpoint Time-set segment time Ramp-set segment time PID group number
Final target setpoint Time-set segment time Ramp-set segment time PID group number
Event number On time of time event Off time of time event PV event type PV event setpoint
Event number On time of time event Off time of time event PV event type PV event setpoint
Pressing the DISP key once during programming returns to the display marked A .
JC
Junction code
JC
Junction code
SET/ENT
key
IM 05E01C02-42E
<Toc>
<3. Programming>
3-16
3.6
LSP1 PID
Setpoint for local-mode operation PID group number for local-mode operation
0.0 to 100.0% of PV input range Shown for segment PID parameters when the setup parameter ZON is set to 0. This parameter is factory-set so as not to appear. 1: Uses the 1st group of PID parameters. 2: Uses the 2nd group of PID parameters. 3: Uses the 3rd group of PID parameters. 4: Uses the 4th group of PID parameters. 5 to 8: Likewise, selecting these numbers uses the 5th to 8th groups of PID parameters.
E21A
OFF (0) OFF (0), 1 to 10, 28 to 31 1: PV high limit (energized, no stand-by action) 2: PV low limit (energized, no stand-by action) 3: Deviation high limit (energized, no stand-by action) 4: Deviation low limit (energized, no stand-by action) 5: Deviation high limit (de-energized, no stand-by action) 6: Deviation low limit (de-energized, no stand-by action) 7: Deviation high/low limits (energized, no stand-by action) 8: Deviation within high/low limits (energized, no stand-by action) 9: PV high limit (de-energized, no stand-by action) 10: PV low limit (de-energized, no stand-by action) PV/SP alarm: -100.0 to 100.0% of PV input range Deviation alarm: -100.0 to 100.0% of PV input range span Output value alarm: -5.0 to 105.0% PV/SP high limit alarm: 100.0% of PV input range. Deviation alarm: 0.0% of PV input range span. Other PV/SP low limit alarms: 0.0% of PV input range. Output high limit alarm: 100.0% Output low limit alarm: 0.0%
E21B
IM 05E01C02-42E
<Toc>
Parameter Symbol Name of Parameter Setting Range and Description
<3. Programming>
Initial Value
3-17
User Setting
E22A E22B E23A E23B E24A E24B E25A E25B E26A E26B E27A E27B E28A E28B
Local event-22 type Local event-22 setpoint Local event-23 type Local event-23 setpoint Local event-24 type Local event-24 setpoint Local event-25 type Local event-25 setpoint Local event-26 type Local event-26 setpoint Local event-27 type Local event-27 setpoint Local event-28 type Local event-28 setpoint
Same as the E21A parameter. Same as the E21B parameter. Same as the E21A parameter. Same as the E21B parameter. Same as the E21A parameter. Same as the E21B parameter. Same as the E21A parameter. Same as the E21B parameter. Same as the E21A parameter. Same as the E21B parameter. Same as the E21A parameter. Same as the E21B parameter. Same as the E21A parameter. Same as the E21B parameter.
G Program Parameters (Parameters for Setting the Conditions of Program Operation Startup)
Use the program pattern setup chart discussed in 3.2 Example of Program Pattern Setup Charts of this chapter, to record your setpoints of program parameters. Located in: Main menu = PROG ; Submenu = PRG
Parameter Symbol Name of Parameter Setting Range and Description Initial Value User Setting
Pattern number
1: Program pattern 1 2: Program pattern 2 3: Program pattern 3 4 to 30: Likewise, specifying these numbers sets their corresponding program pattern numbers. 0: Shows parameters for setting the starting target setpoint, start code, etc. 1 to 99: Specify the corresponding segment numbers. Specify 0 when creating a program for the first time. 0.0 to 100.0% of PV input range -1: Shows parameters for setting the wait and repeat actions. 0: Program operation begins with the starting target setpoint. 1: Ramp-prioritized PV start (program operation begins with the PV value by giving priority to the ramp of segment 1) 2: Time-prioritized PV start (program operation begins with the PV value by giving priority to the time of segment 1) TIP: The option -1 is not a setpoint. 0
Segment number
IM 05E01C02-42E
<Toc>
<3. Programming>
3-18
G Program Parameters (Parameters for Setting the Wait and Repeat Actions)
The parameters listed below are shown when the Start Code (STC) parameter is set to -1. Located in: Main menu = PROG ; Submenu = PRG
Parameter Symbol Name of Parameter Setting Range and Description Initial Value User Setting
1.WZ1 1.WTM 2.WZ1 2.WTM 3.WZ1 3.WTM 4.WZ1 4.WTM 5.WZ1 5.WTM RCY RST REN
1st group of wait zones 1st group of wait times 2nd group of wait zones 2nd group of wait times 3rd group of wait zones 3rd group of wait times 4th group of wait zones 4th group of wait times 5th group of wait zones 5th group of wait times Number of repetitions
OFF: No function 0.0 to 10.0% of PV input range span OFF: No function 0.01 to 99.59 (hour, minute or minute, second) Use the TMU setup parameter to set the time unit. Same as the 1st group of wait zones. Same as the 1st group of wait times. Same as the 1st group of wait zones. Same as the 1st group of wait times. Same as the 1st group of wait zones. Same as the 1st group of wait times. Same as the 1st group of wait zones. Same as the 1st group of wait times. 0 to 999: The controller repeats the segment specified by the RST and REN parameters as many times as defined by this parameter. CONT: The controller indefinitely repeats the segment specified by the RST and REN parameters. 1RSTREN99
OFF OFF
1 1
G Program Parameters (Parameters for Setting the Final Target Setpoints and Segment Times)
Located in: Main menu = PROG ; Submenu = PRG
Parameter Symbol Name of Parameter Setting Range and Description Initial Value User Setting
The final target setpoint of each segment. Time setpoint: - (unregistered) 0.00 to 99.59 (hour, minute or minute, second) Without a time setpoint, it is not possible to create programs. For ramp segments (ramp setpoint): - (unregistered), 0.0 to 100.0% of PV input range span per hour or minute For soak segments: 0.00 to 99.59 (hour, minute or minute, second) Without a time setpoint or a ramp grade setpoint, it is not possible to create programs. This parameter is shown for segment PID parameters when the setup parameter ZON is set to 0. This parameter is factory-set so as not to appear. 1 to 8 1
IM 05E01C02-42E
<Toc>
<3. Programming>
3-19
EVn
Event number
0: Unregistered. 1: Time event 1 (terminal numbers 34 - 35 ) 2: Time event 2 (terminal numbers 33 - 35 ) 3: Time event 3 (terminal numbers 32 - 35 ) 4: Time event 4 (terminal numbers 31 - 35 ) 5 to 16: Time events 5 to 16 (see the CD-ROM version users manual for details on the terminal number) 21: PV event 1 (terminal numbers 6 - 7 ) 22: PV event 2 (terminal numbers 5 - 7 ) 23 to 28: PV events 3 to 8 (see the CD-ROM version users manual for details on the terminal number)
OFF: Unused. OFF 0.00 to 99.59 (hour, minute or minute, second) OFF: Unused. OFF 0.00 to 99.59 (hour, minute or minute, second) OFF: OFF, 1 to 10, 28 to 31 1: PV high limit (energized, no stand-by action) 2: PV low limit (energized, no stand-by action) 3: Deviation high limit (energized, no stand-by action) 4: Deviation low limit (energized, no stand-by action) 5: Deviation high limit (de-energized, no standby action) 6: Deviation low limit (de-energized, no standby action) 7: Deviation high/low limits (energized, no stand-by action) 8: Deviation within high/low limits (energized, no stand-by action) 9: PV high limit (de-energized, no stand-by action) 10: PV low limit (de-energized, no stand-by action) See the next page for details on other alarm types. PV/SP alarm: -100.0 to 100.0% of PV input range Deviation alarm: -100.0 to 100.0% of PV input range span Output value alarm: -5.0 to 105.0% OFF
PEn
PV event setpoint
PV/SP high limit alarm: 100.0% of PV input range. Deviation alarm: 0.0% of PV input range span. Other PV/SP low limit alarms: 0.0% of PV input range. Output high limit alarm: 100.0% Output low limit alarm: 0.0%
JC
Junction code
0: Switching for continuation 0 1: Hold-on switching (the controller holds the end-of-segment setpoint when the segment is completed, to perform control). 2: Local-mode end (the controller switches to a local setpoint when the segment is completed). 11 to 15: Wait during switching between segments (see the CD-ROM version users manual). 21 to 25: Wait within a segment interval (see the CD-ROM version users manual). INSERT: Allows a segment to be added to the end of a specified segment. DELETE: Allows a specified segment to be deleted.
IM 05E01C02-42E
<Toc>
<3. Programming>
3-20
Contact Open/close shows status of relay contact, closes if alarm and lit and unlit shows status of lamp occurs
Contact Open/close shows status of relay contact, closes if alarm and lit and unlit shows status of lamp occurs Hysteresis
No alarm Hysteresis PV high limit Open (unlit) PV Closed (lit) Alarm setpoint Hysteresis PV low limit Closed (lit) Alarm setpoint Open (unlit) PV 2 1
Closed (unlit)
Closed (lit)
Hysteresis Deviation high limit Open (unlit) PV Target SP Closed (lit) Deviation setpoint 3 Deviation within high and low limits
Hysteresis Closed Hysteresis (lit) Open Open (unlit) (unlit) Deviation setpoint Target SP Hysteresis PV
Hysteresis Deviation low limit Closed (lit) Deviation setpoint PV Target SP Hysteresis De-energized on Closed deviation high (unlit) limit alarm Open (lit) PV Deviation setpoint Target SP Hysteresis SP high limit Closed (lit) Open (unlit) SP Alarm setpoint 28 Output high limit Open (unlit) Output value 5 De-energized on PV low limit Open (unlit) 4 De-energized on PV high limit Closed (unlit) PV
SP low limit
Hysteresis Closed (lit) Open (unlit) Alarm setpoint SP 29 Output low limit
Number of remaining unused segments. (ALL.S) Number of segments within a pattern. (PTN.S) Number of remaining unused events. (ALL.E) Program pattern copying (COPY) Program pattern clearance (CLEAR)
Read-only
Specify the numbers of the source-of-copying program pattern and target-of-copying program pattern. (1 to 30) Specify the number of the program pattern to be cleared. (1 to 30)
IM 05E01C02-42E
<Toc>
<3. Programming>
3-21
3.7
IM 05E01C02-42E
<Toc>
1. 2. 3. 4. 5. 6. 7. 8. 9.
<3. Programming>
Maximum value of PV input range: Setpoint of the Maximum Value of PV Input Range (RH1) setup parameter Minimum value of PV input range: Setpoint of the Minimum Value of PV Input Range (RL1) setup parameter PV input unit: Setpoint of the PV Input Unit (UNI1) setup parameter Program time unit: Setpoint of the Program Time Unit (TMU) setup parameter Segment setting method: Setpoint of the Segment Setting Method (SEG.T) setup parameter Starting target setpoint: Setpoint of the Starting Target Setpoint (SSP1) program parameter Start code: Setpoint of the Start Code (STC) program parameter Final target setpoint, segment time, Events (PV event and Time event) and Junction code: Setpoint of each program parameter Draw the program pattern.
3-22
System name Program No. Program name Model Serial No. Unit Maximum value of PV input range (RH1) 1 100% 3 UP550 Program time unit (TMU) Segment setting method (SEG.T) 4 5
Define this parameter when using the controller as a program pattern generator. See Users Manual (Reference) (CD-ROM version) for more information.
Minimum value of PV input range (RL1) 2 0% Segment No. Final target setpoint 1 (TSP1) Final target setpoint 2 (TSP2) Segment time (TIME/TM.RT)
Time setting (TIME) when the Segment Setting Method (SEG.T) parameter is set as SEG.T = 0; ramp setting (TM.RT) when the parameter is set as SEG.T = 1 Factory-set to Time setting (TIME). Shown for segment PID parameters when the setup parameter ZON is set to 0.
PID number (PID) Event number (EV1) PV event type (TY1)/on time of time event (ON1) PV event setpoint (PE1)/off time of time event (OFF1) Event number (EV2) PV event type (TY2)/on time of time event (ON2) PV event setpoint (PE2)/off time of time event (OFF2) Event number (EV3) PV event type (TY3)/on time of time event (ON3) PV event setpoint (PE3)/off time of time event (OFF3) Event number (EV4) 8 PV event type (TY4)/on time of time event (ON4) PV event setpoint (PE4)/off time of time event (OFF4) Event number (EV5) PV event type (TY5)/on time of time event (ON5) PV event setpoint (PE5)/off time of time event (OFF5) Event number (EV6) PV event type (TY6)/on time of time event (ON6) PV event setpoint (PE6)/off time of time event (OFF6) Event number (EV7) PV event type (TY7)/on time of time event (ON7) PV event setpoint (PE7)/off time of time event (OFF7) Event number (EV8) PV event type (TY8)/on time of time event (ON8) PV event setpoint (PE8)/off time of time event (OFF8) Junction code (JC)
IM 05E01C02-42E 1st Edition : May 31,2000-00
<Toc>
Starting target setpoint 1 (SSP1) Starting target setpoint 2 (SSP2) Start code (STC) 1st group of wait zones (1.WZ1) 1st group of wait times (1.WTM) 2nd group of wait zones (2.WZ1) 2nd group of wait times (2.WTM) 3rd group of wait zones (3.WZ1) 3rd group of wait times (3.WTM) 4th group of wait zones (4.WZ1) 4th group of wait times (4.WTM) 5th group of wait zones (5.WZ1) 5th group of wait times (5.WTM) Number of repetitions (RCY) Start-of-repetition segment number (RST) End-of-repetition segment number (REN) 9 7 6
<3. Programming>
Define this parameter when using the controller as a program pattern generator. See Users Manual (Reference) (CD-ROM version) for more information.
3-23
10
11
12
13
14
15
16
17
18
19
20
IM 05E01C02-42E
<Toc>
<3. Programming>
3-24
3.8
I Programming
Choose the desired method and unit from the two programming methods and time unit options discussed above. Then, create programs according to the chosen options.
Setpoint
Final target setpoint set for segment immediately preceding or the starting target setpoint if this is the point of starting program operation
Final target setpoint set for segment immediately preceding or the starting target setpoint if this is the point of starting program operation
Ramp grade
Time
IM 05E01C02-42E
<Toc>
<3. Programming>
3-25
<Controller Settings>
When changing the setpoint linearly over an hour When changing the setpoint linearly over a minute Setpoint of TMU (Program Time Unit) Setup Parameter hh:mm (factory-set default) mm:ss
Note: The Program Time Unit (TMU) parameter is the time unit you use when creating programs.
When creating a soak segment during programming, set a time (hour and minute or minute and second) rather than a ramp grade.
Setpoint
Final target setpoint set for segment immediately preceding or the starting target setpoint if this is the point of starting program operation
Time
For example, configure segment 1 so the temperature rises in increments of 5C per minute from 50C to 100C, as shown in the figure below.
Setpoint 100C Final target setpoint
Segment 1
Time
To change the temperature linearly over a minute, set the TMU parameter to mm:ss (minute and second) before you begin programming. When programming the controller, set the Segment Time (TIME) parameter for segment 1 to 5C. This allows the controller to raise the setpoint in increments of 5C per minute during the interval of segment 1.
IM 05E01C02-42E
<Toc>
<3. Programming>
3-26
<Controller Settings>
Set the STC (Start Code) program parameter to 0.
2. Letting the controller start from the current setpoint and run according to time settings defined for segment 1
This method is not available if the SEG.T (Segment Setting Method) parameter is set to ramp setting.
Starting Point of Operation a b c d e
Setpoint a b c d e
Segment Segment Segment Segment 2 3 4 Segment 5
Controller Behavior Begins to run from point a according to the time setting defined for segment 1. Begins to run from point b according to the time setting defined for segment 1. Begins to run from point c according to the time setting defined for segment 1. Begins to run from point d according to the time setting defined for segment 1. Begins to run from point e according to the time setting defined for segment 1.
Program setpoint
Time
<Controller Settings>
Set the STC (Start Code) program parameter to 2.
IM 05E01C02-42E
<Toc>
<3. Programming>
3-27
3. Letting the controller start from the current setpoint and run according to ramp settings defined for segment 1 of the created program
Starting Point of Operation a b c d e
Setpoint a b c d e E1
Segment Segment Segment Segment 2 3 4 Segment 5
Controller Behavior Begins to run from point C1 (ignores the time setting defined for segment 1). Begins to run from point C1 (ignores the time setting defined for segment 1). Begins to run from point C1 (ignores the time setting defined for segment 1). Begins to run from point D1 according to the preset ramp setting (the time setting defined for segment 1 is reduced). Begins to run from point E1 according to the preset ramp setting.
A1 B1 C1 D1 Program setpoint
Time
<Controller Settings>
Set the STC (Start Code) program parameter to 1.
PV input value
<Controller Settings> Configure the 1st group of PID constants (1.P, 1.I and 1.D operating parameters).
IM 05E01C02-42E
<Toc>
<3. Programming>
3-28
G Selection of PID Constants when the Control Range is Split into Three Zones
As shown in the figure below, three zones are set for the controller to automatically switch from one group of PID constants to another. Two zones can also be set for the controller to switch between two groups of PID constants. [1] [2] [3] The controller uses the 1st group of PID constants if the PV input value is within the zone set off by the minimum value of the PV input range and reference point 1. The controller uses the 2nd group of PID constants if the PV input value is within the zone set off by reference point 1 and reference point 2. The controller uses the 3rd group of PID constants if the PV input value is within the zone set off by reference point 2 and the maximum value of the PV input range.
Program setpoint 3 3rd group of PID constants 2 2nd group of PID constants PV input value 1 1st group of PID constants Minimum value of PV input range (RL1)
Maximum value of PV input range (RH1) Reference point 2 (2.RP1) Reference point 1 (1.RP1)
Segment 1
Segment 2
Segment 3
<Controller Settings> Splitting the control range into two zones To split the control range into two zones, define reference point 1 (i.e., the 1.RP1 setup parameter). Define the 1st and 2nd groups of PID constants (i.e., the 1.P, 1.I and 1.D operating parameters for the 1st group and the 2.P, 2.I and 2.D operating parameters for the 2nd group).
Splitting the control range into three zones To split the control range into three zones, define reference points 1 and 2 (i.e., the 1.RP1 and 2.RP1 setup parameters). Define the 1st, 2nd and 3rd groups of PID constants (i.e., the 1.P, 1.I and 1.D operating parameters for the 1st group, the 2.P, 2.I and 2.D operating parameters for the 2nd group and the 3.P, 3.I and 3.D operating parameters for the 3rd group).
IM 05E01C02-42E
<Toc>
<3. Programming>
3-29
[2]
Segment 1
Segment 2
[Method 2] As shown in the figure below, the controller selects an appropriate group of PID constants for each zone and, if the PV input value goes beyond the given deviation from the program setpoint, selects the PID constants of the group number set in PID group number (GRP). [1] The controller uses the 1st group of PID constants if the PV input value is both within the zone set off by the minimum value of the PV input range and reference point 1 and within the given reference deviation bandwidth. The controller uses the 2nd group of PID constants if the PV input value is both within the zone set off by reference points 1 and the maximum value of the PV input range, and within the given reference deviation bandwidth. The controller uses the PID constants of the group number set in PID group number (GRP).
PV input value
[2]
[3]
[3] [2]
Segment 1
Segment 2
IM 05E01C02-42E
<Toc>
<3. Programming>
3-30
Time
IM 05E01C02-42E
<Toc>
<4. Operations>
4-1
4.
Operations
This chapter describes key entries for operating the controller. For operations using external contact inputs, see 1.5 Terminal Wiring Diagrams. If you cannot remember how to carry out an operation during setting, press the DISP key no more than four times. This brings you to the display (operating display) that appears at poweron.
4.1
G Target SP Display
On the Setpoint display (LCD), the controller displays the current setpoint (SP) and final target setpoint (TSP), the program pattern number (PTNO) selected, the segment number (SEGNO) for which operation is in progress, the number of segments included in the selected program pattern, the program pattern name (only displayed when setting the program pattern name using an optional parameter setting tool (model: LL100-E10)).
G OUT Display
On the Setpoint display (LCD), the controller displays the current setpoint (SP), the PID number (PID) being used, the program pattern number (PTNO), the segment number (SEGNO) for which operation is in progress, and the number of segments included in the selected program pattern, and the output value to secondary-loop (OUT).
G Pattern Display
On the Setpoint display (LCD), the controller displays the selected program pattern.
G Event Display
On the Setpoint display (LCD), the controller displays the event number for which an event has occurred.
IM 05E01C02-42E
<Toc>
<4. Operations>
4-2
SP:
PTNO: 1 TM=0h20
SEGNO: 1/ 3 RCY: 0/ 0
25.0C
SP display
DISP
key
For monitoring only. However, allows the setpoint and segment time to be changed during hold mode operation (soak segment).
SP= PTNO= 1
25.0 / 80.0C
SEGNO: 1/ 3
Target SP display
DISP
key
OUT display
OUT:
35.0%
DISP
key
DV-trend /scan=
20sec
+ 0 -
DISP
key
PTN 1 SEG 1
Pattern display
DISP
key
Event display
DISP
key
IM 05E01C02-42E
<Toc>
<4. Operations>
4-3
4.2
Performing/Canceling Auto-tuning
Perform auto-tuning when you have finished creating program patterns. Make sure the controller is in program (RUN) mode and in automatic (AUTO) mode before carrying out auto-tuning. See 4.5 Switching between RUN and RESET Modes, to change to RUN or 4.6 Switching between AUTO and MAN, to change to AUTO. PID constants are obtained by using the current program setpoint value at the start of autotuning.
NOTE
When on-off control is being used, auto-tuning cannot be carried out. Moreover, do not perform auto-tuning when controlling any of the following processes. Control processes with quick response such as flow control or pressure control Processes where even temporary output on/off results in inconvenience Processes where a large output change at control element results in inconvenience Processes where variations in PV may exceed an allowable range, adversely affecting product quality
1.
Bring the operating display into view (display appears at power on).
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 1/ 3 RCY: 0/ 0
10.0C
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
2.
Press the key for more than 3 seconds to call up the main menu PROG.
SET/ENT
4.
SET/ENT
PROG
PAR
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
5.
LP1
#1
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
IM 05E01C02-42E
<Toc>
<4. Operations>
4-4
6.
Press the or key to display the required setpoint. Tuning for 1st group of PID is AT = 1.
MENU:LP1/PAR auto tuning switch AT = #1 changing! 1
7.
Press the key once to register the setpoint. (This starts auto-tuning.) key is pressed when AT = OFF, If the auto-tuning will be cancelled. In this case, PID contains the value existing before auto-tuning.
SET/ENT SET/ENT
SET/ENT
MODE
PT.No
DISP
RUN RESET
#1
SET/ENT
MODE
PT.No
DISP
RUN RESET
8.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
OUT:
100.0%
4.3
1.
Bring the operating display into view (display appears at power on).
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 1/ 3 RCY: 0/ 0
10.0C
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
IM 05E01C02-42E
<Toc>
<4. Operations>
SET/ENT
4-5
2.
Press the key for more than 3 seconds to call up the main menu PROG.
6.
PROG
#1
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
3.
7.
LP1
changing! 18.0%
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
4.
8.
SET/ENT
PAR
SET/ENT
MODE
PT.No
DISP
RUN RESET
SET/ENT
MODE
PT.No
DISP
RUN RESET
5.
The same steps can be used for integral time (1.I) and derivative time (1.D) that are displayed after this.
1.PID
SET/ENT
MODE
PT.No
DISP
RUN RESET
9.
Press the key for more than 3 seconds. This returns you to the display shown at power-on (figure below).
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 1/ 3 RCY: 0/ 0
10.0C
IM 05E01C02-42E
<Toc>
<4. Operations>
4-6
4.4
NOTE
If contact input, which is used to select between program pattern numbers is on, any program pattern number cannot be selected by key operation.
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 0 TM=-------
SEGNO: 0/ 0 RCY: 0/ 0
0.0C
2.
Press the
PT.No
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 0/ 3 RCY: 0/ 0
25.0C
IM 05E01C02-42E
<Toc>
<4. Operations>
4-7
4.5
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM=-------
SEGNO: 0/ 3 RCY: 0/ 0
25.0C
2.
Press the
RUN
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 1/ 3 RCY: 0/ 0
25.0C
3.
Press the
RESET
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM=-------
SEGNO: 0/ 3 RCY: 0/ 0
25.0C
When in the RESET mode, the controller provides the following input/output values.
PV input Control output Event output Value of process variable Preset output value (factory-set to 0%) OFF, if there is any event.
IM 05E01C02-42E
<Toc>
<4. Operations>
4-8
4.6
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h18
SEGNO: 1/ 3 RCY: 0/ 0
30.0C
2.
[To change from AUTO to MAN mode] Press the MODE key several times to display the MODE:MAN1 mode parameter. [To change from MAN to AUTO mode] Press the MODE key several times to display the MODE:AUTO1 mode parameter. The figure below is an example of changing the AUTO mode to the MAN mode.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
DISP
RUN RESET
#4
changing! MAN1
3.
Press the key once. The controller switches to either MAN-mode or AUTO-mode operation. The figure below is an example of the display after a change from the AUTO mode to the MAN mode.
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
OUT:
40.0%
IM 05E01C02-42E
<Toc>
<4. Operations>
4-9
4.7
A control output value is linked with a display value changed using the or that the control output changes as displayed without requiring the key.
SET/ENT
key. Note
1.
Bring manual operating display into view. For switching to manual operation, see 4.6 Switching between AUTO and MAN.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
OUT:
30.0%
SET/ENT
2.
Press the
or
key to change a control output value. You dont need to press the
PV2
key.
PV
PVE1
PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
OUT:
40.0%
IM 05E01C02-42E
<Toc>
<4. Operations>
4-10
4.8
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
DISP
RUN RESET
SP:
PTNO: 1 TM= 1h20
SEGNO: 2/ 3 RCY: 0/ 0
80.0C
2.
[To enable the hold mode of program operation] Press the MODE key once to display the HOLD:ON mode parameter. [To disable the hold mode of program operation] Press the MODE key once to display the HOLD:OFF mode parameter. The figure below is an example of enabling the hold mode of program operation.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
#1 changing! ON
SET/ENT
MODE
PT.No
DISP
RUN
HOLD :
3.
Press the
SET/ENT
key once. The controller switches to either hold mode or non-hold mode.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 2/ 3 RCY: 0/ 0
80.0C
* Other operating procedures for disabling the hold mode: [1] [2] Press the RUN key for two seconds during hold-mode operation. In this case, the controller resumes program operation. Execute the advance function during hold-mode operation. In this case, the segment is advanced.
IM 05E01C02-42E
<Toc>
<4. Operations>
4-11
4.9
1.
Set program operation in the hold mode. To do this, see 4.8 Enabling/Disabling Hold Mode of Program Operation.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 2/ 3 RCY: 0/ 0
80.0C
2.
Press the
SET/ENT
.
Make sure the symbol is shown.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 2/ 3 RCY: 0/ 0
80.0C
3.
Press the
or
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
85.0 ?
SEGNO: 2/ 3 RCY: 0/ 0
4.
Press the
SET/ENT
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h20
SEGNO: 2/ 3 RCY: 0/ 0
85.0C
IM 05E01C02-42E
<Toc>
<4. Operations>
4-12
1.
Bring the current operating display for program operation into view.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h17
SEGNO: 1/ 3 RCY: 0/ 0
30.0C
2.
Press the
MODE
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
DISP
RUN RESET
3.
Press the
SET/ENT
key once. The controller resumes operation from the target setpoint of segment 1.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 1h20
SEGNO: 2/ 3 RCY: 0/ 0
80.0C
IM 05E01C02-42E
<Toc>
<4. Operations>
4-13
1.
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
SP:
PTNO: 1 TM= 0h14
SEGNO: 1/ 3 RCY: 0/ 0
40.0C
2.
Press the
MODE
PV
PVE1 PVE2
TME
1 2 3 4
AL
#3 changing! ON
SET/ENT
MODE
PT.No
DISP
RUN
LOC
3.
Press the key once. The controller begins running with a local setpoint (L.SP). The figure below is an example of operating the controller with the local setpoint of 50.0C.
SET/ENT
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
L.
SP:
PTNO: 1 TM=-------
SEGNO: 0/ 3 RCY: 0/ 0
50.0C
IM 05E01C02-42E
<Toc>
<4. Operations>
4-14
1.
Change the controller to local-mode operation. To do this, see 4.11 Switching to Local-mode (LOCAL) Operation.
PV2
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
L.
SP:
PTNO: 1 TM=-------
SEGNO: 0/ 3 RCY: 0/ 0
50.0C
2.
Press the
or
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
L.
SP:
PTNO: 1 TM=-------
60.0 ?
SEGNO: 0/ 3 RCY: 0/ 0
3.
Press the
SET/ENT
PV
PVE1 PVE2
TME
1 2 3 4
AL
SET/ENT
MODE
PT.No
DISP
RUN RESET
L.
SP:
PTNO: 1 TM=-------
SEGNO: 0/ 3 RCY: 0/ 0
60.0C
IM 05E01C02-42E
<Toc>
5-1
5.
5.1
I Troubleshooting Flow
No
No Normal? No
Is key lock enabled? No communication capability.
Yes
IMPORTANT
Take note of the parameter settings when asking the vendor for repair.
IM 05E01C02-42E
<Toc>
5-2
I Errors at Power on
The following table shows errors that may be detected by the fault diagnosis function when the power is turned on.
Display position (Note) Error indication E000 E001 1 E002 PV decimal point blinks. Description of error Faulty RAM Faulty ROM None 0% or less or OFF OFF Undefined 0% or less Stopped Undefined Faulty Contact us for repair. PV Control output Alarm output Retransmission Communication Remedy output
Normal action Normal action Normal action Normal action (out of (out of (out of (out of accuracy) accuracy) accuracy) accuracy) Normal action Normal action Normal action
An error code is displayed in the event of an error, according to its type. An error code is a two-digit figure in which a combination of 6 bits of on and off is converted into a decimal number. The following shows the relationship between each bit and parameter to be checked for abnormality.
Bit No. Parameter to be checked 6 5 4 3 2 1 0 Calibration data
For example, if an error occurs with the operating parameter and calibration data, the error code will be as follows:
Bit No. Error Code 6 2
2
5 2
1
4 2
0
3 2
3
2 2
2
1 2
1
0 2
0
IM 05E01C02-42E
<Toc>
5-3
B.OUT
In AUTO: Dependent on the Preset value output BSL parameter In MAN: PV burnout error Up-scale: 105% Normal action Down-scale: -5% Excessive PV -5% or 105% Out of -5 to 105% Auto-tuning failure (Time-out) Feedback resistor burnout Normal action Normal action Action with PID existing before auto-tuning Stopped Normal action
Normal action
OVER or -OVER
Check process. Normal Check process. Press action any key to erase error indication. Stopped Check the feedback resistor. Check wires and communication parameters, and make resetting. Recovery at normal receipt Faulty if power off/on does not reset start the unit. Contact us for Stopped repair. Check for abnormal power.
E200
2 Left end of Setpoint display unit blinks. Faulty communication line Normal action Normal action
Decimal point at right end Runaway (due to lights. defective power Undefined or noise) All indications off Power off None
0% or less or OFF
OFF
0% or less
No display
Note 1: PV display 2: Setpoint display 3: Display showing the PV of the corresponding loop
IM 05E01C02-42E
<Toc>
5-4
G The Controller does not Show the Correct Process Variable (PV).
The UP550 controllers have a universal input. The type of PV input can be set/changed using the parameter IN1. At this point, the controller must be wired correctly according to the selected type of PV input. Check the wiring first if the controller fails to show the correct PV value. To do this, refer to 2. Initial Settings. With the parameters RH1, RL1, SDP1, SH1 and SL1, it is possible to scale the input signal and change its number of decimal places. Also check that these parameters are configured correctly.
G The Controller does not Provide any Control Output or the Control Output does not Change at all.
The UP550 controllers have a universal output. The type of control output can be set/changed using the parameter OT1. At this point, the controller must be wired correctly according to the selected type of control output. Check the wiring first if the controller provides no control output. To do this, refer to 1.5 Terminal Wiring Diagrams. With the parameters OH and OL, it is possible to set/change the high and low limits of control output. The control output may not change at all, however, because of restrictions on these parameters. Also check the restrictions on these parameters. The control output can only be changed when the controller is in the MAN mode. If the MAN lamp is off (i.e., the controller is in the AUTO mode), you cannot change the control output using key operation.
G The Control Output does not Change soon after the Target Setpoint SP has been Changed.
If this happens, check the setpoint of the parameter MOD1. In cases where fixedpoint control is selected as the PID control mode (MOD1 = 1), tracking based on the Iterm works to prevent the control output from changing suddenly even if the target setpoint SP is varied. The control output therefore may appear to be working incorrectly at first; however it gradually adapts itself to the new target setpoint. Be especially careful when the controller is in the fixed-point control mode; the control output may fail to change and therefore result in a loss of control if you change the target setpoint SP too frequently.
IM 05E01C02-42E 1st Edition : May 31,2000-00
<Toc>
5-5
5.2
5.2.1
Maintenance
This section describes the cleaning and maintenance of the UP550.
Cleaning
The front panel and operation keys should be gently wiped with a dry cloth.
NOTE
Do not use alcohol, benzine, or any other solvents.
5.2.2
Replacing Brackets
When the brackets are broken or lost, purchase the following brackets for replacement.
Target Model UP550 Part No. T9115NL Sales Unit A large bracket and small bracket in pair
SEE ALSO
1.2 How to Install, for how to replace brackets.
5.2.3
IM 05E01C02-42E
<Toc>
5-6
Do not touch the terminals on the rear panel when power is being supplied to the controller. Doing so may result in electric shock.
CAUTION
Before attaching the terminal cover, turn off the source circuit breaker and use a tester to check that the power cable is not conducting any electricity.
1.
Before attaching the terminal cover, fold it once or twice so that the side which has the Handle With Care symbol ( ), is on the outside.
Fold over. Grooved
NOTE
Do not fold the terminal cover the wrong way, doing so not only reduces the covers strength but may also cause the hinge to crack, thereby disabling attachment.
2.
With the cover properly folded, fit its top and bottom holes to the protrusions of the mounting brackets.
Fit the hole of the terminal cover to the protrusion on the mounting bracket.
IM 05E01C02-42E
<Toc>
5-7
5.2.4
If any of these parts, except control output relays, cause a controller failure due to deterioration, contact your dealer for replacement at your cost. Control output relays can be replaced by yourself. SEE ALSO
5.2.5 Replacing Control Output Relays, for how to replace the control output relays.
IM 05E01C02-42E
<Toc>
5-8
5.2.5
Always turn off the power before starting the work in order to avoid electric shock.
CAUTION 1.
Do not pull out the internal unit for any other purpose other than to replace the control output relays.
Insert a flat-blade screwdriver (tip width of 6 mm is recommended) into the opening with the tip in parallel with the front panel, and then turn the screwdriver gently. Take this procedure to four openings 1, 2, 3 and 4 (see the figure below) on the upper and lower parts of the bezel, in order. The bezel slightly moves forward from the housing.
1 2
4 3
2.
Push up the center of the bottom gasket of bezel by a finger to release the latch.
Latch (invisible in the panel) Center of the bottom gasket
IM 05E01C02-42E
<Toc>
5-9
3. 4.
Insert the flat-blade screwdriver into the four openings and flip the tip forward to move the bezel more forward. Hold the bezel and pull it along with the internal unit out of the housing. (Note) Be careful not to damage the RJC sensor.
5.
The location and number of the relays differ depending on the model code of the UP550. Confirm the location of the control output relay to be replaced before pulling out the relay.
Upper
Relay (UP550-0)
6.
Pull out the relay to be replaced. The control output relays are easy to remove and mount, since they are connected via a socket onto the print boards.
Insert the new relay in the socket. Use the following relay.
Manufacturer Model Power supply OMRON G6B-2114P-FD-US-P6B 12 V DC
IM 05E01C02-42E
<Toc>
5-10
7.
Insert the internal unit into the housing. Apply power to the controller and confirm that the initial operating display is shown. If the operating display is not shown properly, turn off the controller and pull out the internal unit. Then, insert it into the housing again.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-1
6.
6.1
Parameters
Parameter Map
This section contains Operating Parameter Map and Setup Parameter Map for UP550 as a guideline for setting parameters. These maps are helpful in finding the positions of the displays when setting the parameters, and should be used as a quick reference for the entire range of parameter displays.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-2
SET1S DISP
MODE DISP
SET3S
SET3S or DISP
Main menu
SELECT display 1
SELECT display 2
HOLD ADV LOC MODE (A/M1) MODE MODE (LSP/ CAS) SST
PROG
AL
LP1
SET
SET
SET
DISP
submenu
PAR
1.PID
7.PID
8.PID
SET SELECT display 4 To program parameter setting display submenu [LOC] on the Program Parameter Map A1 A2 A3 A4 AT SC BS FL ORB ORH ORL S.TM
SET 1.P 1.I 1.D 1.OH 1.OL 1.MR 1.H 1.DR 1.Pc 1.Ic 1.Dc 1.Hc 1.DB 1.PO 1.Oc
SET 7.P 7.I 7.D 7.OH 7.OL 7.MR 7.H 7.DR 7.Pc 7.Ic 7.Dc 7.Hc 7.DB 7.PO 7.Oc
SET 8.P 8.I 8.D 8.OH 8.OL 8.MR 8.H 8.DR 8.Pc 8.Ic 8.Dc 8.Hc 8.DB 8.PO 8.Oc
SELECT display 5
*1
*2
*3
*4 *3
*1 *2 *3 *4
Not displayed for ON/OFF control Not displayed for heating/cooling control or position proportional control Displayed for heating/cooling control Displayed for heating/cooling control or position proportional control
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-3
Press the Press the Press the Press the Press the Press the
SET/ENT
key once. key once. key once. key for 1 second. key for 3 seconds. or key once.
MODE
DISP
SET/ENT
SET/ENT
*5 LP2
*6 USR PYS1
*7 PYS2 STUP
SET
SET
SET
SET
U1 U2 U3
Same as LP1
1.a1 1.b1 1.a2 1.b2 1.a3 1.b3 1.a4 1.b4 1.a5 1.b5 1.a6 1.b6 1.a7 1.b7 1.a8 1.b8 1.a9 1.b9 1.a10 1.b10 1.a11 1.b11 1.PMD
2.a1 2.b1 2.a2 2.b2 2.a3 2.b3 2.a4 2.b4 2.a5 2.b5 2.a6 2.b6 2.a7 2.b7 2.a8 2.b8 2.a9 2.b9 2.a10 2.b10 2.a11 2.b11 2.PMD
To setup parameter setting display main menu [PARA] on the Setup Parameter Map
Pressing the DISP key once when a parameter setting display is shown retrieves the menu of that parameter setting display. Example: Pressing the DISP key once when the [PAR] submenu is displayed, will display the [LP1] main menu. Conversely, the [PAR] submenu will reappear by pressing the DISP key once when the [PAR] submenus FL parameter display is shown. * SELECT displays 1 to 5 are shown only when they are registered.
*5 Main menu LP2 is displayed when UP mode is Cascade control. *6 Main menu USR is displayed when UP mode is Loop control with PV switching or Loop control with PV auto-selector. *7 Main menu PYS2 is displayed when UP mode is Cascade control, Loop control with PV switching.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-4
PARA
CMLP
submenu
SET
DISP
SET
DISP
SP
ALM
CTL
AIN
RET
TRND
LOCK
SET SPT TMU SEG.T PT2.G PNC SPH1 SPL1 SPH2 SPL2
SET PEH1 PEH2 PEH3 PEH4 PEH5 PEH6 PEH7 PEH8 AL1 AL2 AL3 AL4 HY1 HY2 HY3 HY4 AMD
SET OPR1 OPR2 MOD1 MOD2 AR1 AR2 ZON R.MD R.TM GRP 1.RP1 2.RP1 3.RP1 4.RP1 5.RP1 6.RP1 RHY1 RDV1 1.RP2 2.RP2 3.RP2 4.RP2 5.RP2 6.RP2 RHY2 RDV2
SET / PTNo RUN MODE PROG LP1 LP2 PID USR PYS1 PYS2 PWD
Pressing the
DISP
key once when a parameter setting display is shown retrieves the submenu of that parameter setting display.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-5
SET DISP
SET/ENT
DISP
CONF
UPMD
TEST (Note)
INIT
SET SET DISP SET DISP INI *1 CSEL DO DI MD IN OUT R485 *2 VALV
SET PROG RST R/L1 LOC HOLD ADV A/M1 A/M2 L/C PTN.0 PTN.1 PTN.2 PTN.3 PTN.4 DP1 MG1 MG2 MG3 MG4
SET IN1 UNI1 RH1 RL1 SDP1 SH1 SL1 BSL1 RJC1 IN3 UNI3 RH3 RL3 SDP3 SH3 SL3 BSL3 P.UN1 P.DP1 P.RH1 P.RL1
SET OT1 OT2 CT1 CTc1 AO1 AO2 AO3 A1H A1L A2H A2L A3H A3L
Note: The parameter items shown on the [TEST] submenu of the setup parameter setting display are to be used by Yokogawa service personnel to check the controller functions. User cannot set or change these parameters.
*1 Submenu R485 is displayed only for the controller with communication function. *2 Submenu VALV is displayed only for the position proportional controller.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-6
6.2
Lists of Parameters
This section describes the functions of parameters briefly. In addition, each parameter table has a User Setting column, where you can record your setpoints when setting them in the controller. * Parameters relating to PV or program setpoints should all be set in real numbers. For example, use temperature values to define program setpoints and PV event setpoints for temperature input. * The User Setting column in the table is provided for the customer to record setpoints. * Numbers in ( ) are the parameter setpoints that apply when the communication function is used. ex. AUTO1 (0), MAN1 (1).
MODE
Pause of program operation Advance of segment (skip) Local-mode operation AUTO/MAN switching Start-of-program segment number
Set as HOLD = ON to enable the hold mode of program operation. Set as ADV = ON to advance from the current segment to the next segment. Set as LOC = ON to switch from program operation or RESET mode to local-mode operation. To switch between AUTO and MAN: To switch to AUTO mode, set as MODE: AUTO1 (0). To switch to MAN mode, set as MODE: MAN1 (1). 1 to 99 Program operation begins with the segment whose number is specified by this parameter.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-7
I Operating Parameters
G Instrument Alarm Setting Parameters
Located in: Main menu = AL
Parameter Symbol Name of Parameter Instrument alarm-1 setpoint Instrument alarm-2 setpoint Instrument alarm-3 setpoint Instrument alarm-4 setpoint Setting Range and Description Allows alarm action to be set irrespective of the program. PV alarm / SP alarm: -100.0 to 100.0% of PV input range Deviation alarm: -100.0 to 100.0% of PV input range span Output alarm: -5.0 to 105.0% Initial Value PV high limit/SP high limit alarm: 100.0% of PV input range Deviation alarm: 0.0% of PV input range span Other PV/SP low limit alarm: 0.0% of PV input range Output high limit alarm: 100.0% Output low limit alarm: 0.0% User Setting
A1 A2 A3 A4
G Operation-related Parameters
Located in: Main menu = LP1 ; Submenu = PAR
Parameter Symbol Name of Parameter Auto-tuning Setting Range and Description OFF (0): No auto-tuning 1: Auto-tuning for 1st group of PID 2: Auto-tuning for 2nd group of PID 3: Auto-tuning for 3rd group of PID 4: Auto-tuning for 4th group of PID 5 to 8: Perform auto-tuning on a group basis in the same way as 1 to 4 9: Performs auto-tuning to all groups 1 to 8. Initial Value OFF (0) User Setting
AT SC
SUPER function
OFF (0): Disable 1: Overshoot suppressing function Suppresses overshoots generated by abrupt changes in the target setpoint or by disturbances. 2: Hunting suppressing function (Stable mode) Suitable to stabilize the state of control when the load varies greatly, or the target setpoint is changed. Enables to answer the wider characteristic changes compared with Response mode. 3: Hunting suppressing function (Response mode) Enables quick follow-up and short converging time of PV for the changed target setpoint. Note: Use SUPER function (SC) 2 or 3 in PID control or PI control. SUPER function 2 or 3 is not available in the following controls: 1) ON/OFF control 2) P control (control for proportional band only) 3) PD control (control for proportional band and derivative item only) 4) Heating/cooling control Do not use hunting suppressing function when control processes with response such as flow or pressure control.
OFF (0)
PV input bias
-100.0% to 100.0% of PV input range span Used to correct the PV input value. OFF (0), 1 to 120 sec. Used when the PV input value fluctuates. 0.0 to 100.0% of PV input range span
PV input filter ON/OFF rate detection band ON/OFF rate high limit ON/OFF rate low limit Starting time of program pattern operation
0.0% of PV input range span OFF (0) 1.0% of PV input range span 100.0% 0.0% 0.00
ORL + 1 digit to 105.0% -5.0% to (ORH - 1 digit) 0.00 to 99.59 (hour, minute or minute, second) The controller begins control when the specified time has passed after power-on.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-8
G PID-related Parameters
Located in: Main menu = LP1 ; Submenu = 1.PID
Parameter Symbol Name of Parameter Proportional band Integral time Derivative time Output high limit Output low limit Setting Range and Description 0.1 to 999.9% of PV input range OFF (0), 1 to 6000 sec. OFF (0), 1 to 6000 sec. -5.0 to 105.0% (1.OL < 1.OH) -5.0 to 105.0% (1.OL < 1.OH) SD (shutdown): Set in manual operation in 4-20 mA control output. Output is 0 mA. -5.0 to 105.0% (enabled when integral time 1.I is OFF) The manual reset value equals the output value when PV = SP is true. For example, if the manual reset value is 50%, the output value is 50% when PV = SP becomes true. In ON/OFF control: 0.0 to 100.0% of PV input range span. Hysteresis can be set in the program setpoint when the controller is performing ON/OFF control. Point of ON/OFF action (Program setpoint) Hysteresis Initial Value 5.0% 240 sec. 60 sec. 100% 0.0% User Setting
Manual reset
50.0%
1.H
Output On
Off PV value
1.DR
REVERSE (0): reverse action, DIRECT (1): direct action Control output 100%
Reverse action Direct action
REVERSE (0)
0%
+
Deviation (PV-SP)
1.PO
Preset output
0.0%
If you are using two or more groups of PID parameters, use the following table to record their values.
Parameter n.P n.I n.D n.OH n.OL n.MR n.H n.DR n.PO n=2 n=3 n=4 n=5 n=6 n=7 n=8
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-9
1.a1
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-10
User Setting
Parameter Symbol
Name of Parameter
Initial Value 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0.0% of PV input range 0.0% of PV input range span 0.0% of PV input range when in ten-segment linearizer approximation 0
1.a1 1.b1 1.a2 1.b2 1.a3 1.b3 1.a4 1.b4 1.a5 1.b5 1.a6 1.b6 1.a7 1.b7 1.a8 1.b8 1.a9 1.b9 1.a10 1.b10 1.a11 1.b11 1.PMD
Ten-segment linearizer 1 input-1 Ten-segment linearizer 1 output-1 Ten-segment linearizer 1 input-2 Ten-segment linearizer 1 output-2 Ten-segment linearizer 1 input-3 Ten-segment linearizer 1 output-3 Ten-segment linearizer 1 input-4 Ten-segment linearizer 1 output-4 Ten-segment linearizer 1 input-5 Ten-segment linearizer 1 output-5 Ten-segment linearizer 1 input-6 Ten-segment linearizer 1 output-6 Ten-segment linearizer 1 input-7 Ten-segment linearizer 1 output-7 Ten-segment linearizer 1 input-8 Ten-segment linearizer 1 output-8 Ten-segment linearizer 1 input-9 Ten-segment linearizer 1 output-9 Ten-segment linearizer 1 input-10 Ten-segment linearizer 1 output-10 Ten-segment linearizer 1 input-11 Ten-segment linearizer 1 output-11 Ten-segment linearizer 1 mode
-66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation -66.7% to 105.0% of PV input range -66.7% to 105.0% of PV input range span -66.7% to 105.0% of PV input range when in ten-segment linearizer approximation 0: Ten-segment linearizer biasing 1: Ten-segment linearizer approximation
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-11
I Setup Parameters
G Program Setpoint-related Parameters
Located in: Main menu = PARA ; Submenu = SP
Parameter Symbol Name of Parameter SP tracking selection Setting Range and Description OFF (0), ON (1) Tracking is performed when the mode changes from program to Local (The local setpoint keeps track of the program setpoint.) Sets the time unit of a program. hh:mm (0): hour, minute mm:ss (1): minute, second Defines the method of programming. Note that changing the setpoint of this parameter deletes the program in question. 0: Programming by setting segment times 1: Programming by setting segment ramps The controller can serve as a program pattern generator. Thus, another program pattern can be created in addition to the control-purpose program pattern. Note that the segment time setpoints of the created program pattern are the same as those of the control-purpose program pattern. OFF (0): Not used. ON (1): Used. The controller resets (clears) the program pattern number on the operating display to 0 at the end of program operation. OFF (0): Not cleared. ON (1): Cleared. Place limits on the program setpoints when the controller is in program operation. 0.0% to 100.0% of PV input range. Note that SPL1 < SPH1 Place limits on the program setpoints when the controller is in program pattern-2 retransmission. 0.0% to 100.0% of PV input range. Note that SPL2 < SPH2 Initial Value OFF (0) User Setting
hh:mm (0)
OFF (0)
OFF (0)
Program setpoint-1 limiter upper limit Program setpoint-1 limiter lower limit Program setpoint-2 limiter upper limit Program setpoint-2 limiter lower limit
100.0% of PV input range 0.0% of PV input range 100.0% of PV input range 0.0% of PV input range
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-12
G Alarm-related Parameters
Located in: Main menu = PARA ; Submenu = ALM
Parameter Symbol Name of Parameter PV event 1 hysteresis PV event 2 hysteresis PV event 3 hysteresis PV event 4 hysteresis PV event 5 hysteresis Off PV event 6 hysteresis PV event 7 hysteresis Hysteresis: 0.0 to 100.0% PV event 8 hysteresis Instrument alarm-1 type Instrument alarm-2 type Instrument alarm-3 type Instrument alarm-4 type Instrument alarm-1 hysteresis OFF (0), 1 to 20, 25 to 31 1: PV high limit (energized, no stand-by action) 2: PV low limit (energized, no stand-by action) 3: Deviation high limit (energized, no stand-by action) 4: Deviation low limit (energized, no stand-by action) 5: Deviation high limit (de-energized, no stand-by action) 6: Deviation low limit (de-energized, no stand-by action) For other alarm types, see the next page. 0.0 to 100.0% of PV input range span Output alarm: 0.0 to 100.0% Allows margins to be set for an alarm setpoint. With the hysteresis settings, it is possible to prevent relays from chattering. Hysteresis for PV high limit alarm Point of ON/OFF action (Alarm setpoint) Output On 1 2 1 2 0.5% of PV input range span Output alarm: 0.5% Hysteresis for PV high limit alarm Point of ON/OFF action Output (PV event setpoint) On Setting Range and Description Initial Value User Setting
PEH1 PEH2 PEH3 PEH4 PEH5 PEH6 PEH7 PEH8 AL1 AL2 AL3 AL4 HY1 HY2 HY3 HY4 AMD
Allows margins to be set for a PV event setpoint. With the hysteresis settings, it is possible to prevent relays from chattering.
0.5%
Hysteresis PV value
Off
Hysteresis PV value
Alarm mode
Allows the instrument alarm function to be enabled or disabled according to the operating condition. 0: Always active 1: Not active when in RESET mode 2: Not active when in RESET mode or manual operation
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-13
Contact Open/close shows status of relay contact, closes if alarm and lit and unlit shows status of lamp occurs
Contact Open/close shows status of relay contact, closes if alarm and lit and unlit shows status of lamp occurs Hysteresis
No alarm Hysteresis 1 PV high limit Open (unlit) PV Closed (lit) Alarm setpoint Hysteresis 2 PV low limit Closed (lit) Alarm setpoint Open (unlit) PV 12 11
Closed (unlit)
16
Closed (lit)
17
Hysteresis 3 Deviation high limit Open (unlit) PV Target SP Closed (lit) Deviation setpoint 13 Deviation within high and low limits
Hysteresis Closed Hysteresis (lit) Open Open (unlit) (unlit) Deviation setpoint Target SP Hysteresis PV
18
Hysteresis Deviation low limit Closed (lit) Deviation setpoint PV Target SP Hysteresis De-energized on Closed deviation high (unlit) limit alarm Open (lit) PV Deviation setpoint Target SP Hysteresis SP high limit Closed (lit) Open (unlit) SP Alarm setpoint 28 Output high limit Open (unlit) Output value 5 De-energized on PV low limit 15 Open (lit) Open (unlit) 4 De-energized on PV high limit 14 Closed (unlit) PV
Alarm setpoint
SP low limit
Hysteresis Closed (lit) Open (unlit) Alarm setpoint SP 29 Output low limit
The following alarm types are used only for Instrument Alarm.
25: 26: 27: Sensor grounding alarm Fault diagnosis output (Note 1) FAIL output (Note 2)
Note 1: The fault diagnosis output turns on in case of input burnout, A/D converter failure, or reference junction compensation (RJC) failure. For input burnout or A/D converter failure, the control output is set to the setpoint of the Preset Output Value operating parameter (PO). Note 2: The FAIL output is on during normal operation and turns off case failure.
Stand-by Action
C Treated as normal
Normal
The alarm output does not turn on in this region even if the PV value is below the low limit of the alarm setpoint. Time
Power-on
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-14
Restart mode
Restart timer
OFF (0) 0.1 to 100.0%/sec. can limit control output velocity 0: Standard PID control (with output bump at SP change) 1: Fixed Point control (without output bump at SP change) Choose Fixed Point Control when controlling pressure or flow rate. AUTO (0), 50.0 to 200.0% The larger Setting, the sooner PID computation (integral computation) stops. Used when the control output travels up to 100% or down to 0% and stays at this point. 0: Segment PID 1: Zone PID If set to Segment PID, allows PID constants to be selected for each segment. If set to Zone PID, automatically selects PID constants according to the temperature range set in the given Reference Point parameter. CONT (0): Continues action set before power failure. MAN (1): Starts from manual operation status RESET (2): Continues action set before power failure and starts computation from the preset output value. 0 to 10 sec. Sets time between power on and the instant where controller starts computation. Allows you to determine how many groups of setpoint, alarm and PID parameters the controller should show. 1: Show one set. 2: Show two sets. 3: Show three sets. 4: Show four sets. 5 to 8: Show as many groups of parameters as have been set. 0.0 to 100.0% of PV input range. Note that 1.RP1 2.RP1 3.RP1 4.RP1 5.RP1 6.RP1. Sets reference points at which switching is carried out between groups of PID constants according to the given temperature zone. You can set a maximum of six reference points and therefore a maximum of seven temperature zones. The example below sets reference points 1 and 2 to provide 3 zones to switch PID constants automatically.
OFF (0)
AUTO (0)
CONT (0)
0 sec.
Zone PID reference point-4 Zone PID reference point-5 Zone PID reference point-6
Maximum value of PV input range RH1 Reference point 2 2.RP1 Reference point 1 1.RP1 Minimum value of PV input range RL1
Setpoint
Zone 3 The controller is operated with the 3rd group of PID constants. Zone 2 The controller is operated with the 2nd group of PID constants.
PV input value
Zone 1 The controller is operated with the 1st group of PID constants.
Time
IM 05E01C02-42E
<Toc>
Parameter Symbol Name of Parameter
<6. Parameters>
Setting Range and Description Initial Value
6-15
User Setting
RHY1 RDV1
0.0 to10.0% of PV input range span Allows hysteresis to be set for switching at a reference point. Used to select a group of PID parameters according to a deviation from the given program setpoint. The controller uses the PID parameters of the number selected in PID group number (GRP) if the PV input falls outside the given deviation range. The following example shows a case when only the reference deviation is set without setting any reference point. The selected group of PID parameters is as follows. Since region 1 is within the deviation range, the controller uses the 1st group of PID parameters. Since region 2 is outside the deviation range, the controller uses the PID parameters of the number selected in PID group number (GRP).
PV input value Maximum value of PV input range RH1 A slope is set to vary the program setpoint.
[2] [2]
Target setpoint
Segment 1
Segment 2
Analog input-1 filter Analog input-1 square-root computation Analog input-1 low signal cutoff
Used to correct the PV input value beforehand. When in normal operation, use the PV Input Bias (BS) operating parameter. -100.0% to 100.0% of PV input range span OFF (0): Disable 1 to 120 sec. Performs square-root computation for the PV input value. OFF (0): Do not compute the square root ON (1): Compute the square root 0.0% to 5.0% The slope equals 1 at levels below the low-signal cutoff point.
1.0%
Although not used in Cascade Primary-loop Control, it is shown on the display. Although not used in Cascade Primary-loop Control, it is shown on the display. Although not used in Cascade Primary-loop Control, it is shown on the display. Although not used in Cascade Primary-loop Control, it is shown on the display.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-16
RET1
Maximum value of retransmission output-1 scale Minimum value of retransmission output-1 scale Retransmission output-2 type Maximum value of retransmission output-2 scale Minimum value of retransmission output-2 scale
TSC1 TTM
Allows the deviation axis of the Deviation Trend operating display to be rescaled. 0.1 to 100.0% of PV input range span Allows the time axis of the Deviation Trend operating display to be rescaled. 1 to 600 sec.
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-17
G Security-related Parameters
Located in: Main menu = CMLP ; Submenu = LOCK
Parameter Symbol Name of Parameter Setting Range and Description Initial Value OFF (0) OFF (0) OFF (0) OFF (0) OFF (0) User Setting
M/L PTNo RUN MODE PROG LP1 LP2 PID USR PYS1 PYS2 PWD
Locking of front panel up/down keys (LandM) Locking of front panel PT.No key Locking of front panel RUN key Locking of front panel MODE key Locking of operating parameter main menu PROG display Operating parameter main menu [LP1] lock
OFF (0): Unlock ON (1): Lock OFF (0): Unlock ON (1): Lock OFF (0): Unlock ON (1): Lock OFF (0): Unlock ON (1): Lock OFF (0): Unlock ON (1): Lock OFF (0): Unlock ON (1): Lock
OFF (0)
Although not used in Cascade Primary-loop Control, it is shown on the display. Operating parameter submenu [PID] lock OFF (0): Unlock ON (1): Lock OFF (0)
Although not used in Cascade Primary-loop Control, it is shown on the display. Operating parameter main menu [PYS1] lock OFF (0): Unlock ON (1): Lock OFF (0)
Although not used in Cascade Primary-loop Control, it is shown on the display. Password setting 0: Password not set 1 to 30000 Note: If a password is set, the setup parameters cannot be displayed without entering the correct password. 0
SELECT display-1 registration SELECT display-2 registration SELECT display-3 registration SELECT display-4 registration SELECT display-5 registration
OFF (0), 101 to 1023 Select the desired parameter from among the operating and setup parameters, then register the number (D register No.) accompanying that parameter. For example, registering 231 for C.S1 allows you to change instrument alarm-1 setpoint in operating display. Numbers for registering instrument alarm SP parameter for operating display: Instrument alarm-1 setpoint: 231 Instrument alarm-2 setpoint: 232 Instrument alarm-3 setpoint: 233 Instrument alarm-4 setpoint: 234
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-18
Relay output flag registration for DO1 Relay output flag registration for DO2 Relay output flag registration for DO3 Open-collector transistor output flag registration for DO4 Open-collector transistor output flag registration for DO5 Open-collector transistor output flag registration for DO6 Open-collector transistor output flag registration for DO7
The following setpoints are registration numbers for cascade primary-loop control only. 5705: PV event 1 output 0: No function 5706: PV event 2 output 5689: Instrument alarm 1 output 5129: Time event 1 output 5130: Time event 2 output 5131: Time event 3 output 1613: Fail output See External contact output in 1.5 Terminal Wiring Diagrams.
5130
5131
1613
Setting Range and Description These parameters determine which contact input to use to make selections/switches listed on the left. DI1: 5161 No function: 0 DI2: 5162 DI3: 5163 DI4: 5164 DI5: 5165 DI6: 5166 DI7: 5167 DI8: 5168 The contact inputs are factory-set as shown below. Contact inputs 1 to 4 (DI1 to DI4): Program pattern number selection (see below) Contact input 5 (DI5): Start of program operation Contact input 6 (DI6): Stop of program operation Contact input 7 (DI7): Tracking switching signal Contact input 8 (DI8): ON when using 16 or more of program patterns Program pattern number selection
1 ON OFF OFF OFF 9 DI1 DI2 DI3 DI4 ON OFF OFF ON 2 OFF ON OFF OFF 10 OFF ON OFF ON 3 ON ON OFF OFF 11 ON ON OFF ON 4 OFF OFF ON OFF 12 OFF OFF ON ON 5 ON OFF ON OFF 13 ON OFF ON ON 6 OFF ON ON OFF 14 OFF ON ON ON 7 ON ON ON OFF 15 ON ON ON ON 8 OFF OFF OFF ON
User Setting
PROG RST LOC HOLD ADV A/M1 A/M2 L/C PTN.0 PTN.1 PTN.2 PTN.3 PTN.4 MG1 MG2 MG3 MG4
5166
0 0
Bit 0 of program pattern number Bit 1 of program pattern number Bit 2 of program pattern number Bit 3 of program pattern number Bit 4 of program pattern number Interruptive message display 1 Interruptive message display 2 Interruptive message display 3 Interruptive message display 4
DI3 DI4
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-19
G UP Mode Parameters
Located in: Main menu = UPMD ; Submenu = MD
Parameter Symbol Name of Parameter Controller mode (UP mode) PV sampling period setting Sampling period error counter (reading only) Setting Range and Description 2: Cascade Primary-loop control For another Controller mode, see Users Manual (Reference) (CD-ROM version). 100, 200 and 500 ms The controller restarts if any change is made to the PV sampling period; this does not affect other parameter settings at all, however. 0 to 30000 Initial Value 1 User Setting
200 ms
Shows 0 at power-on.
G Input-related Parameters
Located in: Main menu = UPMD ; Submenu = IN
Parameter Symbol Name of Parameter Setting Range and Description Initial Value OFF (0) User Setting
Specify the type of PV input as a range code. See Instrument Input Range Codes in 2. Initial Settings.
Select the unit of PV input. % (0): Percent - (2): No unit C (1): Degree Celsius F (5): Fahrenheit Set the instrument input range (RL1 < RH1). - For temperature input Set the range of temperature that is actually controlled. - For voltage input Set the range of a voltage signal that is applied. The scale across which the voltage signal is actually controlled should be set using the parameters Maximum Value of PV Input Scale (SH1) and Minimum Value of PV Input Scale (SL1). Set the position of the decimal point of voltage-mode PV input. 0 to 4 0: No decimal place 1: One decimal place, 2 to 4: Two, three, four decimal places Set the read-out scale of voltage-mode PV input. -19999 to 30000, where SL1 < SH1
PV input decimal point position (shown when in voltage-input mode) Max. value of PV input scale (shown when in voltage-input mode) Min. value of PV input scale (shown when in voltage-input mode) Selection of PV input burnout action
RJC1
Allows the PV input value to be determined as shown below in case of PV input burnout. 105% of PV input range if set to Upscale -5.0% of PV input range if set to Downscale OFF (0): Disable UP (1): Upscale DOWN (2): Downscale Allows input compensation to be applied to thermocouple input. OFF (0): Absent ON (1): Present
ON (1)
IM 05E01C02-42E
<Toc>
Parameter Symbol Name of Parameter Setting Range and Description
<6. Parameters>
Initial Value 1 to 5 V (41)
6-20
User Setting
Tracking input type (INPUT 3 terminals) Terminals 21 and 22 Tracking input unit
Maximum value of tracking input range Minimum value of tracking input range Tracking input decimal point position Max. value of tracking input scale Min. value of tracking input scale Tracking input burnout action selection
Specify the type of tracking input as a range code. See Instrument Input Range Codes in the 2. Initial Settings. Select the unit of tracking input. % (0): Percent F (5): Fahrenheit C (1): Degree Celsius - (2): No unit Set the range of a voltage signal. (RL3 < RH3)
% (0)
5.000
P.UN1 P.DP1
PV unit
P.RH1 P.RL1
Allows the tracking input value to be determined as shown below in case of tracking input burnout. 105% of tracking input scale if set to Upscale -5.0% of tracking input scale if set to Downscale OFF (0): Disable UP (1): Upscale DOWN (2): Downscale Set the unit of PV. % (0): Percent F (5): Fahrenheit C (1): Degree Celsius - (2): No unit Under normal operation, set the same value as in the PV Input Decimal Point Position (SDP1) parameter. To shift the decimal point for temperature input, use this parameter. For example, set as P.DP1 = 0 to change a temperature reading of one decimal place to that of no decimal places. This involves reconfiguring the P.RH1 and P.RL1 parameters. 0 to 4 Under normal operation, keep the values of these parameters between the maximum and minimum values of the PV input range. -19999 to 30000 P.RL1 < P.RH1, where P.RH1-P.RL1 30000
OFF (0)
Maximum value of PV input range or scale Minimum value of PV input range or scale
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-21
G Output-related Parameters
Located in: Main menu = UPMD ; Submenu = OUT
Parameter Symbol Name of Parameter Control output type Setting Range and Description Time proportional PID relay contact output (terminals 1 - 2 - 3 ) 0 1 Time proportional PID voltage pulse output (terminals 16 - 17 ) 2 Current output (terminals 16 - 17 ) 3 ON/OFF control relay contact output (terminals 1 - 2 - 3 ) 1 to 1000 sec. Initial Value 2 User Setting
OT1 CT1
30 sec.
Analog output-1 type (OUTPUT 1: Terminals 16 and 17 ) Analog output-2 type (OUTPUT 2: Terminals 46 and 47 ) Analog output-3 type (OUTPUT 3: Terminals 14 and 15 ) Analog output-1 100% segmental point Analog output-1 0% segmental point Analog output-2 100% segmental point Analog output-2 0% segmental point Analog output-3 100% segmental point Analog output-3 0% segmental point
Allows control output or retransmission output to be presented as one of the following current signals. 0: 4 to 20 mA 1: 0 to 20 mA 2: 20 to 4 mA 3: 20 to 0 mA
Set the values of segmental points for the 0% and 100% output levels at which the values are presented via OUTPUT-1 (terminals 16 and 17 ). See I Performing Split Computations below. -5.0% to 105.0% Set the values of segmental points for the 0% and 100% output levels at which the values are presented via OUTPUT-2 (terminals 46 and 47 ). See I Performing Split Computations below. -5.0% to 105.0% Set the values of segmental points for the 0% and 100% output levels at which the values are presented via OUTPUT-3 (terminals 14 and 15 ). See I Performing Split Computations below. -5.0% to 105.0%
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-22
The figure below shows an example where both analog outputs-1 and 3 are set to the current signal of 4 to 20 mA DC. The type of output signal can be determined separately for each of the analog outputs listed above, using the following three parameters. Analog output-1: Analog output-2: Analog output-3: Analog output-1 type (AO1) Analog output-2 type (AO2) Analog output-3 type (AO3)
Analog output-1 100% segmental point (A1H)
16
75 Analog output-1
12
50
25
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-23
[Parallel-mode Output] The following explains an example of letting Analog OUTPUT-1 (terminals 16 and 17 ) and Analog OUTPUT-3 (terminals 14 and 15 ) present the parallel-mode characteristics of split computations. [1] [2] [3] [4] [5] [6] Set the Control Output Type (OT1) parameter to 2. This sets the control output to current output. Set the Retransmission Output 1 (RET1) parameter to 3. This sets the retransmission output to control output retransmission. Set the Analog Output-1 100% Segmental Point (A1H) parameter to 100%. Set the Analog Output-1 0% Segmental Point (A1L) parameter to 25%. Set the Analog Output-3 100% Segmental Point (A3H) parameter to 75%. Set the Analog Output-3 0% Segmental Point (A3L) parameter to 0%.
The figure below shows an example where both analog outputs-1 and 3 are set to the current signal of 20 to 0 mA DC. The type of output signal can be determined separately for each of the analog outputs listed above, using the following three parameters. Analog output-1: Analog output-2: Analog output-3: Analog output-1 type (AO1) Analog output-2 type (AO2) Analog output-3 type (AO3)
Analog output-3 100% segmental point (A3H) mA 0 % 100 Analog output-1 100% segmental point (A1H)
25 Analog output-1 0% segmental point (A1L) 0 0 25 50 75 100 % Output value before split computation
IM 05E01C02-42E
<Toc>
<6. Parameters>
6-24
G Communication Parameters
Located in: Main menu = UPMD ; Submenu = R485
Parameter Symbol Name of Parameter Protocol selection Setting Range and Description 0: PC link communication 1: PC link communication (with sum check) 2: Ladder communication 3: Coordinated master station 7: MODBUS (ASCII) 8: MODBUS (RTU) 600 (0), 1200 (1), 2400 (2), 4800 (3), 9600 (4) (bps) NONE (0): None EVEN (1): Even ODD (2): Odd 1, 2 7, 8; 7 is fixed for MODBUS (ASCII) 8 is fixed for MODBUS (RTU), Ladder 1 to 99 However, the maximum number of stations connectable is 31. 0 to 10 ( 10 ms) 0 Initial Value User Setting
PSL1
1 8
Address
G Parameter-initializing Parameters
Located in: Main menu = UPMD ; Submenu = INIT
Parameter Symbol Name of Parameter Setting Range and Description Initial Value User Setting
INI
Parameter initialization
OFF (0)
IM 05E01C02-42E
<Toc>
7-1
7.
IM 05E01C02-42E
<Toc>
7-2
Contact input
250 DI8 DI5 DI6 DI7
21 22
terminals
Input selection Unit selection Analog input range conversion Analog input bias Square root extraction Analog input filter 10-seg. linearizer approx./bias PV input bias PV input filter
INPUT3
Program operation
Tracking signal
Tracking ON
Manual operation Control computation MAN
A/M
AUTO
Output limiter PV event output Time event output Instrument alarm output
STOP/RUN switching
FAIL output
Retransmission output
DO1
RET1
DO2
DO3
DO4
DO5
DO6
DO7
PV PV Instrument Time Time Time event 1 event 2 alarm 1 event 1 event 2 event 3
OUTPUT2
ON in normal condition
OUTPUT1
OUTPUT3
OUTPUT1
Current 16
17
250
21 22
INPUT1
INPUT3
DI8
Secondary-loop PV input
Cascade input
Cascade operation stops when DI8=OFF ON in AUTO or Target setpoint MAN operation retransmission OFF in operation stops
DO3 OUTPUT3
Function
14
15
terminals
Current
IM 05E01C02-42E
<Toc>
7-3
I Primary-loop PV Input
Primary-loop PV input (INPUT1) is a universal input, which can receive signals from thermocouple, RTD, or DC voltage signals. The controller is capable of biasing, square root extraction, first-order lag computation (filtering), ten-segment linearizer approximation, and ten-segment linearizer biasing on input signals. Each function can be set by the following parameters.
Setup Parameters
Function Input selection Unit selection Analog input bias Square root extraction Analog input filter IN1 UNI1 A.BS1 A.SR1, A.LC1 A.FL1 Parameter Main menu UPMD UPMD UPMD CMLP CMLP CMLP IN IN IN AIN AIN AIN Submenu
Note: PV input bias (BS) and PV input filter (FL) among the operating parameters are used as bias and filter when normal operation. Analog input bias (A.BS1) and analog input filter (A.FL1) among the setup parameters are used when PV correction value is decided in advance.
Operating Parameters
Function Ten-segment linearizer mode Ten-segment linearizer approximation/biasing 1.PMD 1.a1 to 1.a11, 1.b1 to 1.b11 Parameter Main menu PYS1 PYS1 Submenu None None
I Tracking Input
Tracking input (INPUT3) is used for tracking target setpoint signals from the secondaryloop controller. Connect to analog output 3 (OUTPUT3) of secondary-loop controller, since the cascade primary-loop control is used with the cascade secondary-loop control. When DI7 (contact input 7) is ON, the tracking input is the output of primary-loop controller. When DI7 (contact input 7) is OFF, the result of PID computation of primary-loop controller is output. No computation is executed for the tracking input.
IM 05E01C02-42E
<Toc>
7-4
Note: If DI8 is set to ON, the program pattern of the number added 16 to the one selected by ON/OFF using DI1 to DI4, is selected.
For example, set contact input 2 (DI2) only to ON to change the program pattern 1 to the program pattern 2. Set contact input 1 (DI1) and contact input 2 (DI2) to ON to select the program pattern 3.
I PID
It is possible to use a maximum of eight groups of PID parameters.
Operating Parameters
Function Proportional band (P) Integral time (I) Derivative time (D) n.P n.I n.D Parameter Main menu LP1 LP1 LP1 Submenu n.PID n.PID n.PID
IM 05E01C02-42E
<Toc>
7-5
I Control Output
Control output (OUTPUT1) is set for the current output signal. Connect to the cascadeinput terminal of the secondary-loop controller. The parameter setting is not required.
I Contact Output
PV event 1 is output via DO1 (contact output 1). PV event 2 is output via DO2 (contact output 2). Instrument alarm 1 is output via DO3 (contact output 3). Time event 1 is output via DO4 (contact output 4). Time event 2 is output via DO5 (contact output 5). Time event 3 is output via DO6 (contact output 6). FAIL signal is output via DO7 (contact output 7). ON in the normal condition and OFF in the FAIL condition. The controller has a FAIL contact output terminal for outputting a FAIL signal to the secondary-loop controller. Connect to contact input 7 (DI7) of the secondary-loop controller, since the cascade primary-loop control is used with cascade secondary-loop control.
I Retransmission Output
PV, program setpoint, or control output can be output to retransmission output 1 (OUTPUT3). Each function can be set by the following parameters.
Setup Parameters
Function Retransmission output 1 type Retransmission output 1 scale RET1 RTH1, RTL1 Parameter Main menu CMLP CMLP Submenu RET RET
Setup Parameters
Function Retransmission output 1 type RET1 Parameter Main menu CMLP Submenu RET
IM 05E01C02-42E
Blank Page
<Int> <Toc>
Revision Information
G Title : Model UP550 Program Controller Users Manual for Cascade Primary-loop Control G Manual No. : IM 05E01C02-42E May 2000/1st Edition Newly published
Written by
Products Documents Controllers & Conditioners Division Yokogawa M&C Corporation Published by Yokogawa M&C Corporation 1-19-18 Nakacho, Musashino-shi, Tokyo 180-0006, JAPAN
IM 05E01C02-42E
Blank Page