5e1c2 41
5e1c2 41
5e1c2 41
IM 05E01C02-41E
IM 05E01C02-41E
1st Edition
Blank Page
<Toc> <Rev> i
Introduction
Thank you for purchasing the UP550 program controller.
Media No. IM 05E01C02-41E (CD) 1st Edition : May 2000 (YK) IM 05E01C02-41E 1st Edition : May 31,2000-00
All Rights Reserved Copyright © 2000, Yokogawa M&C Corporation
<Toc> <Rev> ii
■ Safety Precautions
The following symbol is indicated on the controller to ensure safe use.
This symbol on the controller indicates that the operator must refer to an explanation in the
user’s manual in order to avoid the risk of injury or death of personnel or damage to the
instrument. The manual describes how the operator should exercise special care to avoid
CAUTION electric shock or other dangers that may result in injury or loss of life.
The following symbols are used in the hardcopy user’s manuals and in the user’s manual
supplied on the CD-ROM.
NOTE
Indicates that operating the hardware or software in a particular manner may damage it or
result in a system failure.
IMPORTANT
Draws attention to information that is essential for understanding the operation and/or
features of the controller.
Model UP550
Program Controller
User’s Manual for Single-loop Control
IM 05E01C02-41E 1st Edition
CONTENTS
1. Installation .............................................................................................. 1-1
1.1 Model and Suffix Codes .................................................................................. 1-1
1.2 How to Install ................................................................................................... 1-2
1.3 How to Connect Wires .................................................................................... 1-5
1.4 Hardware Specifications ................................................................................ 1-7
1.5 Terminal Wiring Diagrams ............................................................................ 1-13
2. Initial Settings ......................................................................................... 2-1
2.1 Names and Functions of Front Panel Parts ................................................... 2-2
2.2 Setting PV Input Type (Setting First at Power-on) ......................................... 2-3
2.3 Changing PV Input Type ................................................................................. 2-8
2.4 Setting Control Output Type
(except for a Position Proportional Controller) ........................................... 2-10
2.5 Calibrating Valve Position (for a Position Proportional Controller Only) .. 2-13
2.6 Initializing Parameters .................................................................................. 2-15
3. Programming .......................................................................................... 3-1
3.1 Overview of Program Patterns ....................................................................... 3-1
3.2 Example of Program Pattern Setup Charts ................................................... 3-2
3.3 Creating Program Patterns............................................................................. 3-4
3.4 Changing Program Patterns .......................................................................... 3-11
3.5 Program Parameter Map ............................................................................... 3-14
3.6 Lists of Program Parameters ....................................................................... 3-16
3.7 Program Pattern Setup Charts ..................................................................... 3-21
3.8 Explanation of Program Functions .............................................................. 3-24
4. Operations .............................................................................................. 4-1
4.1 Monitoring-purpose Operating Displays Available during Operation ......... 4-1
4.2 Performing/Canceling Auto-tuning ................................................................ 4-4
4.3 Setting PID Manually ....................................................................................... 4-5
4.4 Selecting Program Pattern Number (PT.No) .................................................. 4-7
4.5 Switching between RUN and RESET Modes ................................................. 4-8
4.6 Switching between AUTO and MAN ............................................................... 4-9
4.7 Manipulating Control Output during Manual Operation ............................. 4-10
4.8 Enabling/Disabling Hold Mode of Program Operation ............................... 4-13
4.9 Changing Program Setpoints when in Hold Mode ...................................... 4-14
4.10 Executing “Advance” Function ................................................................... 4-15
1. Installation
This chapter describes installation, wiring, and other tasks required to make the
controller ready for operation.
■ Correspondence between the Model and Suffix Codes, and the Contact
Input/Output Terminals Provided
Check the model ordered and the presence/absence of contact inputs and outputs in the
following table.
NOTE
To install the controller, select a location where:
1. no one may accidentally touch the terminals,
2. mechanical vibrations are minimal,
150mm
3. corrosive gas is minimal,
4. temperature can be maintained at about 23C and
150mm 150mm
the fluctuation is minimal,
150mm
5. no direct radiant heat is present,
6. no magnetic disturbances are caused,
7. no wind blows against the terminal board (reference junction compensation element),
8. no water is splashed,
9. no flammable materials are around,
● Installation Position
Install the controller at an angle within 30 from horizontal with the front panel facing up-
ward. Do not install it facing downward. The position of right and left sides should be hori-
zontal.
Front panel
of controller Must not
exceed 30
30 Rear of
controller
PVE1
PVE2
91.8
112
96
Small bracket
1 to 10 mm (Panel thickness)
+0.8
0
92
+0.8
92 0 (25)
Turn off the power to the controller before installing it on the panel because there is a
possibility of electric shock.
CAUTION
After opening the mounting hole on the panel, follow the procedures below to install the
controller:
1. Insert the controller into the opening from the front of the panel so that the terminal
board on the rear is at the far side.
2. Set the brackets in place on the top and bottom of the controller as shown in the figure
below, then tighten the screws of the brackets. Take care not to overtighten them.
Large bracket
Panel (top mounting hardware)
Terminal board
Direction to insert the
controller
Insert the controller
into the opening at Insert a screwdriver into the
the front of the panel.
brackets to tighten the screws.
Small bracket
(bottom mounting hardware)
1) Before carrying out wiring, turn off the power to the controller and check that the
cables to be connected are not alive with a tester or the like because there is a possi-
bility of electric shock.
CAUTION 2) Wiring must be carried out by personnel who have basic electrical knowledge and
practical experience.
NOTE
1) Provide power from a single-phase instrument power supply. If there is a lot of noise in
the power line, insert an insulating transformer into the primary side of the line and use
a line filter (recommended part: ZAC2205-00U from TDK) on the secondary side.
As a countermeasures against noise, do not place the primary and secondary power
cables close to each other.
2) For thermocouple input, use shielded compensating lead wires for wiring. For RTD
input, use shielded wires that have low conductor resistance and cause no significant
differences in resistance between the three wires.
The cables to be used for wiring, terminal specifications, and recommended parts are
as shown below.
3) Control output relays may be replaced. However, because they have a life of 100,000
times that of the resistance load, use auxiliary relays to turn on/off a load.
4) The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves
causes malfunction or relay failure; always insert a CR filter for use with alternating
current or a diode for use with direct current, as a spark-removal surge suppression
circuit, into the line in parallel with the load.
O.C Relay
R R
Diode
(Mount it directly
UP’s contact UP’s contact Relay
Relay to the relay coil CR filter
(Use one with a relay coil terminal (socket).) (Use one with a relay coil (Mount it directly
rating less than the UP’s rating less than the UP’s to the relay coil
contact rating.) contact rating.) terminal (socket).)
2
0.3 to 1.65 mm 0.8 N·m or less
3.7mm 3.7mm
7 mm or less
7 mm or less
or
● Terminal Covers
• Input type: Universal input system. The input type can be selected with the software.
• Sampling period: Can be selected from 100, 200 and 500 ms. Initial value: 200 ms
• Burnout detection: Function at TC, RTD, standard signal (0.4 to 2 V or 1 to 5 V)
Upscale, downscale, and off can be specified.
For standard signal, burnout is determined to have occurred if it is 0.1 V or less.
• Input bias current: 0.05 A (for TC or RTD b-terminal)
• Measurement current (RTD): About 0.13 mA
• Input resistance: 1 M or more for thermocouple or mV input
About 1 M for DC voltage input
• Allowable signal source resistance: 250 or less for thermocouple or mV input
Effects of signal source resistance: 0.1 V/ or less
2 k or less for DC voltage input
Effects of signal source resistance: About 0.01%/100
• Allowable wiring resistance: for RTD input
Maximum 150 /wire: Conductor resistance between three wires should be equal
However, 10 /wire for a maximum range of -150.0 to 150.0C.
Wire resistance effect: 0.1C/10
• Allowable input voltage: 10 V DC for thermocouple, mV, or RTD input
20 V DC for DC voltage input
• Noise rejection ratio: 40 dB (50/60 Hz) or more in normal mode
120 dB (50/60 Hz) or more in common mode
• Reference junction compensation error: 1.0C (15 to 35C)
1.5C (0 to 15C, 35 to 50C)
• Applicable standards: JIS, IEC, DIN (ITS-90) for thermocouples and RTD
• Slide resistance value: 100 to 2.5 k of overall resistance (burnout detection for
sliding wire provided)
• Measuring resolution: 0.1% of overall resistance
Retransmission Output
Either PV, program setpoint, or control output is output.
Either the retransmission output or the loop power supply can be used with terminals
14 - 15 .
• Output signal: 4-20, 0-20, 20-4, or 20-0 mA DC (where, outputting signal levels of less
than 0 mA is not feasible)
• Load resistance: 600 or less
• Output accuracy: 0.1% of span (5% of span for 1 mA or less.)
Under standard operating conditions (232C, 5510% RH, power frequency of 50/
60 Hz)
Control Output
Universal output system, The output type can be selected with the software.
Relay contact output(s) for the position proportional type.
• Current output
(Standard type: terminals 16 - 17 ; heating-side output: terminals 16 - 17 , cooling-side
output: terminals 46 - 47 )
Contact Inputs
• Purpose: Program pattern no. selection, and run/reset switching
• Number of inputs: Differs with model and suffix codes as shown in the table below.
Contact Outputs
• Purpose: Event output, FAIL output, and others
• Number of outputs: 7 points
• Relay contact rating: 240 V AC, 1 A, or 30 V DC, 1 A
• Transistor contact rating: 24 V DC, 50 mA
Display Specifications
• PV display: 5-digit, 7-segment, red LEDs, character height of 20 mm
• Setpoint display: 32128 dot LCD with back lighting
• Status indicating lamps: LEDs
NOTE
Do not use unassigned terminals as relay terminals.
Terminal wiring diagrams are shown on and after the next page.
<Toc>
RS-485 communication * Wiring can only be carried out * Wiring can only be carried out for PV input * Not configured at factory before shipment 䊏 Receiving 4-20 mA DC Current
for controllers with controllers with auxiliary analog input. See “2. Initial Settings.” Signals with the Controller
communication functions. This input is not used in single-loop * When receiving 4-20 mA DC current signals,
23 SDB(+) Maximum baud rate: 9600 bps TC input RTD input set the PV input type to 1-5 V DC (setpoint “41”).
control, however.
24 SDA(-) Auxiliary analog input 11 A
12 + 12 +
25 RDB(+) 12 b 250 Ω 4-20mA
21 + Specify in a range of 13 -
Control output
26 1-5 V DC, 0-2 V DC, 13 -
RDA(-) 13 B
or 0-10 V DC.
Relay contact output Note: Select this option from 22 -
the OT1 parameter. 27 SG mV/V input
Default: 1-5 V DC Note: Connecting a 250 Ω resistor to the terminals is
NC 1 * Time proportional PID relay optional.
contact output is configured Model: X010-250-2 (resistor with M3.5 crimp-on terminal
NO 2 at factory before shipment. 12 + lugs)
1 41 31 21 11
COM 3 2 42 32 22 12 13 - NOTE
Installation category (overvoltage category): II (IEC1010-1)
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
3 43 33 23 13
4 44 34 24 14 Retransmission output 1* * Factory-set to “PV retransmission.”
Power supply
5 45 35 25 15 Note: Select this option from the OT1 parameter.
Power supply Control output * Retransmission output 2 is available only when
“relay” is selected as the type of control output. 14 +
L CAUTION 6 46 36 26 16 4-20 or
8 Current/voltage Retransmission 0-20 mA DC
Before carrying out wiring, turn off the power
N to the controller and check that cables to be 7 47 37 27 17 pulse output output 2* 15 -
9 connected are not alive with a tester or the like Default: Unspecified
because there is a possibility of electric shock. 8 48 38 28 18 retransmission type Default: 4-20 mA DC Load resistance: 600 Ω or less
10 16 + 0-20mADC, 16 + 15 V DC loop power supply* * Retransmission output 1 is not available
9 49 39 29 19 4-20mADC 0-20mADC,
Allowable range: 100-240 V AC (10%) Voltage pulse (12 V) 4-20mADC if a 15 V DC loop power supply is used.
17 - 17 -
(free voltage) 10 50 40 30 20
50/60 Hz shared
14 +
Default: 4-20 mA DC 14.5-18.0 V DC
(21 mA DC max.)
* The functions of a contact output can be varied by changing * The functions of a contact input can be varied by changing 15 -
the setting of the contact output registration parameter. the setting of the contact input registration parameter.
External contact outputs External contact inputs
UP Switch between the ON and OFF states of the DI1 to DI4 UP Contact +5V Transistor contact
PV event 1 output DO1 6 contact inputs to select from program pattern numbers 1 to 15. DI1
(Select a number during a RESET state.) DI1 19 19
+5V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
PV event 2 output DO2 5 DI2
Relay
DI1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON DI2 18 +5V 18
DI2 OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON
Instrument alarm
DO3 4 DI3 OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON DI3
40
1 output DI3 40 +5V
DI4 OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON
Common COM 7 DI4
DI4 39 +5V 39
Time event 1 Start of program operation when DI5
output
DO4 34 DI5 38 +5V 38
DI5 changes from OFF to ON
Time event 2 Stop of program operation when
DI6
DO5 33 DI6 37 +5V 37
Transistor
<1. Installation>
Time event 3 Start of local-mode operation when DI7 36 36
output
DO6 32 DI7 changes from OFF to ON
* OT1 is a setup parameter.
COM You can change the settings of the parameter OT1 to change the control output type.
IM 05E01C02-41E
1-14
■ UP550 Heating/Cooling Type (Model UP550-2䊐), Single-loop Heating/Cooling Control
<Toc>
Cooling-side control Cooling-side control RS-485 communication * Wiring can only be carried out for controllers
output output with communication functions.
Current/voltage pulse output Relay contact output Note: Select this option from Maximum baud rate: 9600 bps
the OT1 parameter. 23 SDB(+) PV input * Not configured at factory before shipment 䊏 Receiving 4-20 mA DC Current
NC 48 * Wiring can only be carried out for See “2. Initial Settings.” Signals with the Controller
* Time proportional PID controllers with auxiliary analog input.
+ 46 24 SDA(-) * When receiving 4-20 mA DC current signals,
0-20 mA DC relay contact output is This input is not used in single-loop TC input RTD input
4-20 mA DC, NO 49 set the PV input type to 1-5 V DC (setpoint “41”).
voltage pulse (12 V) configured at factory 25 RDB(+) control, however.
- 47 before shipment. 11 A
COM 50 Auxiliary analog input 12 +
26 RDA(-) 12 +
12 b
Contact rating: 250 V AC, 3 A 250 Ω 4-20mA
30 V DC, 3 A (resistance load) 13 -
27 SG 21 + Specify in a range of 13 B 13 -
Heating-side control output
1-5 V DC, 0-2 V DC,
Relay contact output or 0-10 V DC.
Note: Select this option from the 22 - mV/V input
OT1 parameter. Note: Connecting a 250 Ω resistor to the terminals is
NC 1 Default: 1-5 V DC
* Time proportional PID relay contact optional.
output is configured at factory 12 + Model: X010-250-2 (resistor with M3.5 crimp-on terminal
NO 2 1 41 31 21 11 lugs)
before shipment.
13 - NOTE
2 42 32 22 12
COM 3 Installation category (overvoltage category): II (IEC1010-1)
DI1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON DI2 18 +5V 18
DI2 OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF ON ON
Instrument alarm
DO3 4 DI3 OFF OFF OFF ON ON ON ON OFF OFF OFF OFF ON ON ON ON DI3
40
1 output DI3 40 +5V
DI4 OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON ON ON
Common COM 7 DI4
DI4 39 +5V 39
Time event 1 Start of program operation when DI5
output
DO4 34 DI5 38 +5V 38
DI5 changes from OFF to ON
DI6
<1. Installation>
Time event 2 Stop of program operation when
DO5 33 DI6 37 +5V 37
Transistor
DI7
Time event 3 Start of local-mode operation when DI7 36 36
output
DO6 32 DI7 changes from OFF to ON
COM
Time event 4 COM 20 20
output
DO7 31 Common
+5V
Common COM 35 ON when using 16 or more of program patterns DI8
DI8 28 28
Relay contact rating: 240 V AC, 1 A COM
30 V DC, 1 A (resistance load) Common COM 30 30
Transistor contact rating: 24 V DC, 50 mA
1st Edition : May 31,2000-00
1-15
Cooling side: Relay output Cooling side: Relay output Cooling side: Relay output Cooling side: Voltage pulse output Cooling side: Voltage pulse output Cooling side: Voltage pulse output Cooling side: Current output Cooling side: Current output Cooling side: Current output
(terminals 48 , 49 and 50 ) (terminals 48 , 49 and 50 ) (terminals 48 , 49 and 50 ) (terminals 46 and 47 ) (terminals 46 and 47 ) (terminals 46 and 47 ) (terminals 46 and 47 ) (terminals 46 and 47 ) (terminals 46 and 47 )
The types of control output, “relay output” and “voltage pulse output” shown in the table above refer to those of time proportional control.
To change to a relay output for on-off control, select “Relay Terminals” and change the setpoint of the proportional band to “0.”
■ UP550 Position Proportional Type (Model UP550-1䊐), Single-loop Position Proportional Control
<Toc>
RS-485 communication * Wiring can only be carried PV input * Not configured at factory before shipment 䊏 Receiving 4-20 mA DC Current
out for controllers with * Wiring can only be carried out See “2. Initial Settings.” Signals with the Controller
communication functions. for controllers with auxiliary * When receiving 4-20 mA DC current signals,
23 SDB(+) Maximum baud rate: TC input RTD input
analog input. set the PV input type to 1-5 V DC (setpoint “41”).
9600 bps This input is not used in 11 A
24 SDA(-)
single-loop control, however. 12 + 12 +
Auxiliary analog input 12 b
25 RDB(+) 250 Ω 4-20mA
13 -
13 B 13 -
26 RDA(-)
21 + Specify in a range of
1-5 V DC, 0-2 V DC, mV/V input
Position proportional control output 27 SG
22 - or 0-10 V DC.
Note: Connecting a 250 Ω resistor to the terminals is
optional.
Relay contact output Feedback input Default: 1-5 V DC 12 + Model: X010-250-2 (resistor with M3.5 crimp-on terminal
0%
lugs)
H
48 47 13 -
(Direct)
1 41 31 21 11 NOTE
L Installation category (overvoltage category): II (IEC1010-1)
49 46
(Reverse) 2 42 32 22 12
COM 50 100%
45 3 43 33 23 13
Contact rating: 250 V AC, 3 A Resistance: 100 to 2.5 k Retransmission output 1* * PV retransmission is configured at factory
30 V DC, 3 A (resistance load)
4 44 34 24 14 before shipment.
Power supply 5 45 35 25 15
14 +
4-20 mA DC,
Power supply CAUTION 6 46 36 26 16 0-20 mA DC
Before carrying out wiring, turn off the power Retransmission 15 -
L
8 to the controller and check that cables to be 7 47 37 27 17 output 2
connected are not alive with a tester or the like Default: 4-20 mA DC Load resistance: 600 Ω or less
Default: Unspecified
N because there is a possibility of electric shock. 8 48 38 28 18 retransmission type 15 V DC loop power supply* * If 15 V DC loop power supply is used,
9
16 + retransmission output 1 cannot be used.
9 49 39 29 19 0-20mADC,
10 4-20mADC
10 50 40 30 20 17 - 14 +
14.5-18.0VDC
Allowable range: 100-240 V AC (10%) (21 mA DC max.)
Default: 4-20 mA DC
(free voltage) 15 -
50/60 Hz shared
* The functions of a contact input can be varied by changing
* The functions of a contact output can be varied by changing
the setting of the contact input registration parameter.
the setting of the contact output registration parameter.
External contact inputs
External contact outputs
Switch between the ON and OFF states of the DI1 to DI4 Contact +5V Transistor contact 䊏 15 V DC Power Supply Wired to Sensor in
UP UP
PV event 1 output DO1 6
contact inputs to select from program pattern numbers 1 to 15. DI1 Two-wire System Configuration
(Select a number during a RESET state.) DI1 19 19
+5V
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
DI2
PV event 2 output DO2 5 DI1 ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON DI2 18 18
Relay
<1. Installation>
Stop of program operation when 37
Time event 2 DI6 37 +5V
DO5 33 DI6 changes from OFF to ON Two-wire
Transistor
output transmitter
IM 05E01C02-41E
DI7
Start of local-mode operation when DI7 36 36 14
Time event 3
output
DO6 32 DI7 changes from OFF to ON
COM Loop power
COM 20 20 4-20mADC supply
Time event 4 Common 14.5-
output
DO7 31
18.0 V DC
+5V 15
ON when using 16 or more of program patterns DI8
Common COM 35 DI8 28 28
Relay contact rating: 240 V AC, 1 A COM Note: Connecting a 100 resistor to the terminals is optional.
30 V DC, 1 A (resistance load) Common COM 30 30
Model: X010-100-2 (resistor with M3.5 crimp-on terminal lugs)
1st Edition : May 31,2000-00
1-16
<Toc> <2. Initial Settings> 2-1
2. Initial Settings
This chapter describes examples of setting PV input types, control output types.
Carrying out settings described herein allows you to perform basic control. Refer to
examples of various settings to understand how to set parameters required. Refer to
“6.1 Parameter Map” for an easy to understand explanation of setting various
parameters. If you cannot remember how to carry out an operation during setting,
press the DISP key no more than four times. This brings you to the display (operating
display) that appears at power-on. After carrying out the settings described here,
create programs in “3. Programming.”
Setup Procedure
Position No
proportional
controller?
Yes
Set setup
parameters.
Set operating
parameters.
Set program
patterns.
Controller operation
lamps
PVE2
10. MODE key
8. Instrument alarm
indicator lamps 11. DISP key
4. Status indicator
lamps 12. and keys
5. Light-loader
interface
9. SET/ENT key
15. RESET key
13. PT.No key
14. RUN key
Used to switch between displays. Pressing this key while any operating display is shown
lets you switch to another prearranged operating display. Pressing this key while any
11. DISP key DISP display other than an operating display is shown lets you go one display back.
(One to four presses (maximum) of this key lets you return to the current operating display,
though the number of presses depends on the operating status.)
Used to change numerical values. On setting displays for various parameters, you can change target
setpoints, parameters, and output values (in manual operation). Pressing the key decreases a
12. and keys numerical value, while pressing the key causes it to increase. You can hold down a key to gradually
increase the speed of change. These keys also switch between menu displays when a main menu or
submenu of parameter setting display is shown.
Use this key when the controller is at a reset to select a program pattern number on
13. PT.No key PT.No
an operating display.
Pressing this key for more than 2 seconds while an operating display is shown starts the
14. RUN key RUN
controller.
Pressing this key for more than 2 seconds while an operating display is shown stops the
15. RESET key RESET
controller.
NOTE
• The controller displays an operating display when the power is turned on. The
submenu “IN” appears at this point if the type of PV input has not been defined yet. In
this case, first press the key once to display the parameter “IN1” for the PV input
SET/ENT
type and use the key to display the input range code to use, then press the SET/ENT
key to register it. Then, set the maximum value (RH1) and minimum value (RL1) of the
PV input range (for voltage input, set the maximum value (SH1) and minimum value
(SL1) of the PV input scale). See the operating procedure below for more details.
• The controller is configured to the default of each parameter at the factory before
shipment.
First check these defaults listed in “6.2 Lists of Parameters” and change their values if
necessary.
Displays
submenu “IN”.
PVE1
PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
IN
PT.No RUN RESET
input set
SETUP sub menu
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
parameter IN1 (PV input type). parameter “UNI1” (PV input unit).
MENU:UPMD/IN #1 MENU:UPMD/IN #2
input 1 type select input 1 unit select
SETUP SETUP
IN1 = OFF UNI1 = °C
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the or key to display the 6. Press the key once to display the
SET/ENT
change.
SET/ENT
MODE DISP
key once to register the setting the maximum value of the PV input
setpoint. range to 200.0°C.
MENU:UPMD/IN #1 MENU:UPMD/IN #3
input 1 type select input 1 range high
SETUP changing!
IN1 = typeK3 RH1 = 200.0
Blinks during
change.
SET/ENT SET/ENT
MODE DISP MODE DISP
8. Press the
SET/ENT
key once to register the 10. Press the or key to display the
setpoint. required setpoint.
The figure below shows an example of
MENU:UPMD/IN #3
input 1 range high setting the minimum value of the PV input
SETUP range to 0.0°C.
RH1 = 200.0
MENU:UPMD/IN #4
input 1 range low
SET/ENT
MODE DISP
changing!
RL1 = 0.0
PT.No RUN RESET
Blinks during
change.
SET/ENT
MODE DISP
SET/ENT
MODE DISP
12. Press the key for more than 3 seconds. This returns you to the display shown at power-on
SET/ENT
(figure below).
PV2 PV
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
NOTE
The controller may automatically initialize the registered operating parameter setpoints if
any change is made to the data item PV Input Type (IN1), Maximum Value of PV Input
Range (RH1), Minimum Value of PV Input Range (RL1), PV Input Decimal Point Position
(SDP1), Maximum Value of PV Input Scale (SH1) or Minimum Value of PV Input Scale
(SL1). After a change has been made to any of these data items, be sure to verify the
registered operating parameter setpoints to ensure that they are correct. If any data item
has been changed to its default, set it to a required value.
PV input terminal
Thermocouple/mV/V input.............................. 12 - 13
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
PROG UPMD
programming UP550 configuration
main menu SETUP main menu
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the key once to display the main 6. Press the key once to display the
SET/ENT
STUP MD
password input UP mode set
main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
PARA IN
setup parameter input set
SETUP main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT
MODE DISP
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT
MODE DISP
SET/ENT
MODE DISP
18. Press the key for more than 3 seconds. This returns you to the display shown at power-on
SET/ENT
(figure below).
PV2 PV
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
PROG OUT
programming output set
main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the key once to display the main 8. Press the key once to display the
SET/ENT
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT
MODE DISP
submenu “MD”.
MD
UP mode set
SETUP sub menu
SET/ENT
MODE DISP
11. Press the key for more than 3 seconds. This returns you to the display shown at power-on
SET/ENT
(figure below).
PV2 PV
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
PROG UPMD
programming UP550 configuration
main menu SETUP main menu
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the key once to display the main 6. Press the key once to display the
SET/ENT
STUP MD
password input UP mode set
main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
PARA VALV
setup parameter valve control
SETUP main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT
MODE DISP
SET/ENT
MODE DISP
13. Press the key for more than 3 seconds. This returns you to the display shown at power-on
SET/ENT
(figure below).
PV2 PV
SET/ENT
MODE DISP
SP:
L. 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
PROG UPMD
programming UP550 configuration
main menu SETUP main menu
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the key once to display the main 6. Press the key once to display the
SET/ENT
STUP MD
password input UP mode set
main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
PARA INIT
setup parameter parameter initialize
SETUP main menu SETUP sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT
MODE DISP
11. Press the key for more than 3 seconds. This returns you to the display shown at power-on
SET/ENT
(figure below).
PV2 PV
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
3. Programming
This chapter explains how to create programs by citing specific examples. Create
user programs by referring to the given programming examples. Use the parameter
map included in “3.5 Program Parameter Map,” in order to further familiarize your-
self with the required operations.
Be sure to carry out the settings instructed in “2. Initial Settings” before beginning
any of the tasks discussed in this chapter.
Event output
• Set a deviation of 5⬚C on both the positive and negative sides of a program setpoint to
allow the controller to output an event signal if the temperature goes beyond the
deviation range.
• Let the controller output an event signal when the temperature stabilizes to 80⬚C.
2
80°C
Target setpoint
Target setpoint (TSP1) to be reached
(TSP1) to be reached by segment 3
1 by segment 1
Starting target
setpoint (SSP1)
25°C
0°C
Segment time for segment 1 Segment time for segment 2 Segment time for segment 3 Time
20 min. 80 min. 10 min.
Start of program operation
PV event 1 Outputs an alarm if the temperature goes beyond the range “program setpoint ⫾5°C.”
ON OFF
Time event 1
The output turns on after 20 minutes have elapsed since the start of program operation.
Then, it turns off after 100 minutes have elapsed from the start of program operation.
1. Maximum value of PV input range: Setpoint of the “Maximum Value of PV Input Range
(RH1)” setup parameter
2. Minimum value of PV input range: Setpoint of the “Minimum Value of PV Input Range
(RL1)” setup parameter
3. PV input unit: Setpoint of the “PV Input Unit (UNI1)” setup parameter
4. Program time unit: Setpoint of the “Program Time Unit (TMU)” setup parameter
5. Segment setting method: Setpoint of the “Segment Setting Method (SEG.T)” setup
parameter
6. Starting target setpoint: Setpoint of the “Starting Target Setpoint (SSP1)” program
parameter
7. Start code: Setpoint of the “Start Code (STC)” program parameter
8. Final target setpoint, Segment time, Events (PV event and Time event) and Junction
code: Setpoint of each program parameter
9. Draw the program pattern.
Unit 3 °C 9
Segment No. 1 2 3 4 5 6 7 8 9 10 11 12 1
Final target setpoint 1 (TSP1) 80°C 80°C 0°C
Final target setpoint 2 (TSP2)
Segment time (TIME/TM.RT) 20 min 80 min 10 min
PID number (PID) (Note)
Event number (EV1) 21 1
PV event type (TY1)/on time of time event (ON1) 7 0 min
PV event setpoint (PE1)/off time of time event (OFF1) 5°C 80 min
Event number (EV2)
PV event type (TY2)/on time of time event (ON2)
PV event setpoint (PE2)/off time of time event (OFF2)
Event number (EV3)
PV event type (TY3)/on time of time event (ON3)
PV event setpoint (PE3)/off time of time event (OFF3)
Event number (EV4)
Not used in this example.
8 PV event type (TY4)/on time of time event (ON4) Not used in this example.
PV event setpoint (PE4)/off time of time event (OFF4)
Event number (EV5)
PV event type (TY5)/on time of time event (ON5)
PV event setpoint (PE5)/off time of time event (OFF5)
Event number (EV6)
PV event type (TY6)/on time of time event (ON6)
PV event setpoint (PE6)/off time of time event (OFF6)
Event number (EV7)
PV event type (TY7)/on time of time event (ON7)
PV event setpoint (PE7)/off time of time event (OFF7)
Event number (EV8)
PV event type (TY8)/on time of time event (ON8)
PV event setpoint (PE8)/off time of time event (OFF8)
Junction code (JC) 0 0 0
Note: This parameter is shown for segment PID parameter when the setup parameter “ZON” is set to 0.
NOTE
Before creating the program, reverify the Maximum Value of PV Input Range (RH1), Mini-
mum Value of PV Input Range (RL1), Program Time Unit (TMU), and Segment Setting
Method (SEG.T) parameters.
If the setting of the setup parameter “SEG.T” is changed, the program patterns created and
stored so far will be all cleared (initialized)!! Be careful.
The programming example given in this section includes the following steps.
• Step 5 selects the program pattern number (PTN).
• Steps 7 to 9 configure the parameter Starting Target Setpoint (SSP1) (so that the
program starts from 25°C).
• Steps 11 to 13 configure the Final Target Setpoint (TSP1) parameter for segment 1.
• Steps 14 to 16 configure the Segment Time (TIME) parameter for segment 1.
• Steps 17 to 25 configure the PV Event parameters (EV1, TY1 and PE1).
• Step 28 configures the Final Target Setpoint (TSP1) parameter for segment 2 (not
changed in this example).
• Steps 29 to 31 configure the Segment Time (TIME) parameter for segment 2.
• Steps 32 to 40 configure the Time Event parameters (EV1, ON1 and OFF1).
• Steps 43 to 45 configure the Final Target Setpoint (TSP1) parameter for segment 3.
• Steps 46 to 48 configure the Segment Time (TIME) parameter for segment 3.
Displays a
PV2 PV process variable
(PV) value.
RST lamp PVE1
PVE2
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
For steps 2 and later, illustrations of the LCD are cited to explain the procedure.
PROG LOC
programming local mode set
main menu sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
4. Press the key once to display the 8. Press the or key to display the
submenu “PRG”. required setpoint.
The figure below shows an example of the
PRG parameter set to “25.0⬚C”.
programming
main menu MENU:PROG/PRG #3
start set point 1
changing!
SSP1 = 25.0°C
SET/ENT
MODE DISP
SET/ENT
MODE DISP
SSP1 = 25.0°C
PV Display
SET/ENT
MODE DISP
MENU:PROG/PRG #1
PTno.input PT.No RUN RESET
PTN = 1
SET/ENT
MODE DISP 10. Press the key once to display the Start
SET/ENT
SEG = 0
SET/ENT
MODE DISP
11. Press the key once to display the
SET/ENT
TSP1 = 25.0°C
SET/ENT
MODE DISP
SET/ENT
MODE DISP
12. Press the or key to display the 17. Press the key once to display the
SET/ENT
SET/ENT
MODE DISP
key once to register the The figure below shows an example of the
setpoint. parameter set to “PV event 1” (setpoint 21).
MENU:PROG/PRG #24 MENU:PROG/PRG #29
target set point 1 event 1 no. select
changing!
TSP1 = 80.0°C EV1 = 21
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT
MODE DISP
SET/ENT
PT.No RUN RESET
MODE DISP
15. Press the or key to display the Event Type parameter “TY1”.
required setpoint.
MENU:PROG/PRG #30
The figure below shows an example of the PV event 1 type
parameter set to “20 min. (0h20)”. TY1 = OFF
MENU:PROG/PRG #26
segment time
changing! SET/ENT
MODE DISP
TIME = 0h20 PT.No RUN RESET
SET/ENT
MODE DISP
TIME = 0h20
SET/ENT
MODE DISP
21. Press the or key to display the 26. Press the key once to display the
SET/ENT
SET/ENT
MODE DISP
TY1 = 7 JC = 0
SET/ENT SET/ENT
MODE DISP MODE DISP
PV Display
PE1 = 5.0°C
29.
SET/ENT
MODE DISP
Press the key once to display the
SET/ENT
setpoint.
TIME = -
MENU:PROG/PRG #31
PV event 1 set point
SET/ENT
MODE DISP
PE1 = 5.0°C PT.No RUN RESET
SET/ENT
MODE DISP
SET/ENT
MODE DISP
setpoint.
ON1 = OFF
MENU:PROG/PRG #26
segment time
SET/ENT
MODE DISP
TIME = 1h20
PT.No RUN RESET
SET/ENT
MODE DISP
SET/ENT
MODE DISP
EV1 = 1
SET/ENT
MODE DISP
Time of Time Event parameter “OFF1”. Target Setpoint parameter for segment 3.
At this point, the PV display shows “01.03”
MENU:PROG/PRG #31
time event 1 OFF time (the first two digits denote the pattern
number and the last two digits the segment
OFF1 = OFF
number).
SET/ENT
MODE DISP PV Display
PT.No RUN RESET
MENU:PROG/PRG #24
target set point 1
required setpoint.
The figure below shows an example of the SET/ENT
MODE DISP
(setpoint 1h20)”.
MENU:PROG/PRG #31
time event 1 OFF time
changing! 44. Press the or key to display the
OFF1 = 1h20 required setpoint.
The figure below shows an example of the
SET/ENT
MODE DISP
parameter set to “0.0⬚C”.
PT.No RUN RESET
MENU:PROG/PRG #24
target set point 1
changing!
TSP1 = 0.0°C
MENU:PROG/PRG #31
time event 1 OFF time
OFF1 = 1h20
TSP1 = 0.0°C
MENU:PROG/PRG #32
event 2 no. select
EV2 = 0
SET/ENT
MODE DISP
Segment Time parameter “TIME” for
PT.No RUN RESET segment 3.
MENU:PROG/PRG #26
segment time
JC = 0
SET/ENT
MODE DISP
SET/ENT
MODE DISP
49. Programming is now complete. Press the key for more than 3 seconds. This returns you to
SET/ENT
ON. TME
1
2
PRG
RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
The Target
Temperature Setpoint (TSP1) parameter for
90°C segment 2 is changed from
80.0°C to 90.0°C.
80°C
Current
Starting target
PV
setpoint (SSP1)
25°C
0°C
Before change: The Target Setpoint (TSP1) program parameter for Change the setpoint of the
segment 2 was set to “80.0°C”. Target Setpoint (TSP1)
After change: The Target Setpoint (TSP1) program parameter for program parameter for
segment 2 is set to “90.0°C”. segment 2 to “90.0”.
Displays a
PV2 PV process variable
(PV) value.
RST lamp PVE1
PVE2
ON. TME
1
2
PRG
RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
For steps 2 and later, illustrations of the LCD are cited to explain the procedure.
SET/ENT SET/ENT
MODE DISP MODE DISP
SET/ENT SET/ENT
MODE DISP MODE DISP
4. Press the key once to display the 8. Press the or key to display the
submenu “PRG”. required setpoint.
The figure below shows an example of the
PRG parameter set to “time-prioritized PV start
programming (setpoint 2)”.
main menu
MENU:PROG/PRG #5
start code select
SET/ENT
MODE DISP
changing!
STC = 2
PT.No RUN RESET
SET/ENT
MODE DISP
PTN = 1
SET/ENT
MODE DISP
9. Press the
SET/ENT
key once to register the 12. Press the or key to display the
setpoint. required setpoint.
The figure below shows an example of the
MENU:PROG/PRG #5
start code select parameter set to “90.0°C”.
STC = 2 MENU:PROG/PRG #24
target set point 1
changing!
TSP1 = 90.0°C
SET/ENT
MODE DISP
SET/ENT
MODE DISP
SET/ENT
MODE DISP
PV Display
MENU:PROG/PRG #24
target set point 1
TSP1 = 80.0°C
SET/ENT
MODE DISP
ON.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
Press
the key
SET/ENT
key or key
key A
or
LOC key
PRG key or key
local mode set programming
sub menu sub menu
SET/ENT SET/ENT
key DISP key key DISP key
Program pattern 1
Setpoint for MENU:PROG/PRG #1 key or key
LSP1 local-mode operation PTno. input
PTN = 1
PID group number for
PID local-mode operation key
Segment 1 Segment 2 or
Local event-21
E21A type
MENU:PROG/PRG
SEGno. input
#2 key or key MENU:PROG/PRG
SEGno. input
#2 key or key MENU:PROG/PRG
SEGno. input
#2 key
Local event-22
E22A type
SET/ENT SET/ENT SET/ENT
key key key
Local event-22
E22B setpoint
Local event-23
E23A type
Local event-23 “TIME” is shown when the Segment
E23B Starting target
setpoint SSP1 setpoint TSP1 Final target setpoint Setting Method (SEG.T) parameter TSP1 Final target setpoint
is set using a time setpoint; “TM.RT”
Local event-24 Time-set is shown when the Segment Setting Time-set
E24A type TIME Method (SEG.T) parameter is set TIME
segment time segment time
using a ramp grade setpoint.
Local event-24 Ramp-set The controller is factory-set to Ramp-set
E24B setpoint TR.RT TR.RT
segment time show “TIME”. segment time
Local event-25 STC≠ –1 The parameter “PID” is shown for
E25A type STC Start code PID PID group number segment PID parameters when the PID PID group number
setup parameter “ZON” is set to 0.
Local event-25
E25B setpoint STC= –1
Local event-26
E26A type
Local event-26 1st group of
E26B setpoint 1.WZ1 wait zones Evn Event number n = 1 to 8. Evn Event number
If EVn = 1 to 16, then this parameter
Local event-27 1st group of On time of refers to time events 1 to 16. On time of
E27A type 1.WTM wait times ONn time event If EVn = 21 to 28, then this parameter ONn time event
refers to PV events 1 to 8.
Local event-27 2nd group of Off time of Off time of
E27B setpoint 2.WZ1 wait zones OFFn time event OFFn time event
Local event-28 2nd group of
E28A type 2.WTM wait times TYn PV event type TYn PV event type
3rd group of
3.WTM wait times
SET/ENT
key 4th group of
4.WZ1 wait zones
Start-of-repetition
RST segment number
End-of-repetition
REN segment number
SET/ENT
key
EDIT
program edit
sub menu
SET/ENT
key DISP key
Program patterns 2 to 30
MENU:PROG/PRG #1 Shows the number of
PTno. input ALL.S remaining unused
segments.
PTN = 2 Shows the number of
key key key PTN.S segments within
Segment 3 or or
Segment 99 or
a pattern.
Shows the number of
MENU:PROG/PRG
SEGno. input
#2 key key MENU:PROG/PRG
SEGno. input
#2 MENU:PROG/PRG
SEGno. input
#2 key ALL.E remaining unused
events.
SEG = 3 SEG = 99 SEG = 0 Program pattern
COPY copying
Program pattern
CLEAR clearance
SET/ENT SET/ENT
key key
SET/ENT
key
These parameter symbols
appear on the PV display.
Time-set Time-set
TIME segment time TIME segment time
Ramp-set Ramp-set
TR.RT segment time TR.RT segment time
On time of On time of
ONn time event ONn time event
SET/ENT
key
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Setpoint for local-mode 0.0 to 100.0% of PV input range 0.0% of PV input range
LSP1 operation
PID group number for Shown for segment PID parameters when the 1
PID local-mode operation setup parameter “ZON” is set to 0. This
parameter is factory-set so as not to appear.
1: Uses the 1st group of PID parameters.
2: Uses the 2nd group of PID parameters.
3: Uses the 3rd group of PID parameters.
4: Uses the 4th group of PID parameters.
5 to 8: Likewise, selecting these numbers uses
the 5th to 8th groups of PID parameters.
Local event-21 type OFF (0), 1 to 10, 28 to 31 OFF (0)
E21A 1: PV high limit (energized, no stand-by action)
2: PV low limit (energized, no stand-by action)
3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action)
5: Deviation high limit (de-energized, no stand-by Ref.5.2(9)
action)
6: Deviation low limit (de-energized, no stand-by
action)
7: Deviation high/low limits (energized, no stand-by
action)
8: Deviation within high/low limits (energized, no
stand-by action)
9: PV high limit (de-energized, no stand-by action)
10: PV low limit (de-energized, no stand-by action)
Local event-21 PV/SP alarm: -100.0 to 100.0% of PV input PV/SP high limit alarm:
E21B setpoint range 100.0% of PV input range.
Deviation alarm: -100.0 to 100.0% of PV Deviation alarm:
input range span 0.0% of PV input range span.
Output value alarm: -5.0 to 105.0% Other PV/SP low limit alarms:
0.0% of PV input range.
Output high limit alarm: 100.0%
Output low limit alarm: 0.0%
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Segment PID group This parameter is shown for segment PID parameters when 1
PID number the setup parameter “ZON” is set to 0.
Ref.5.1(2)
This parameter is factory-set so as not to appear.
1 to 8
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Hysteresis Hysteresis
Hysteresis
Closed Open Closed
Deviation high (lit) (unlit) (lit)
PV low limit Closed (lit) Open (unlit) 2 7
and low limits
Deviation setpoint PV
Alarm setpoint PV
Target SP
Hysteresis
Hysteresis
Deviation low Closed (lit) Open (unlit) De-energized on Closed
4 Open (lit) 9
limit PV high limit (unlit)
Deviation setpoint
PV PV Alarm setpoint
Target SP
Hysteresis
Hysteresis
De-energized on
Closed Open (lit) De-energized on Closed
deviation high (unlit) 5 Open (lit) 10
PV low limit (unlit)
limit alarm Deviation
PV setpoint Alarm setpoint PV
Target SP
Hysteresis Hysteresis
Closed (lit) Closed (lit)
SP high
28 Output high limit 30
limit Open (unlit) Open (unlit)
Hysteresis Hysteresis
Closed (lit) Closed (lit)
SP low
29 Output low limit 31
limit Open (unlit) Open (unlit)
Symbol on Name of Parameter Setting Range and Description Initial Value User Target Item
PV Display Setting in CD-ROM
System name
Program No.
Program time unit (TMU) 4
Program name
Segment setting method (SEG.T) 5
Model UP550 -
Serial No.
Unit 3
7 8 9 10 11 12 13 14 15 16 17 18 19 20
Choose the desired method and unit from the two programming methods and time unit
options discussed above. Then, create programs according to the chosen options.
Setpoint
Final target
setpoint
When creating a soak segment during programming, set a time (“hour and minute” or
“minute and second”) rather than a ramp grade.
Setpoint
Final target
Final target setpoint set for
setpoint
segment immediately preceding
or the starting target setpoint
if this is the point of starting Segment time
program operation Define as
“hour and minute” or
“minute and second.”
Time
For example, configure segment 1 so the temperature rises in increments of 5⬚C per
minute from 50⬚C to 100⬚C, as shown in the figure below.
Setpoint
Final target
setpoint
100°C
Ramp upgrade of
5°C per minute
50°C
Segment 1 Time
To change the temperature linearly over a minute, set the TMU parameter to “mm:ss”
(minute and second) before you begin programming.
When programming the controller, set the Segment Time (TIME) parameter for segment 1
to 5⬚C.
This allows the controller to raise the setpoint in increments of 5⬚C per minute during the
interval of segment 1.
Setpoint
Segment 1 Segment 2
Time
Segment time
Start of program operation
<Controller Settings>
Set the STC (Start Code) program parameter to “0”.
2. Letting the controller start from the current setpoint and run according to
time settings defined for segment 1
This method is not available if the SEG.T (Segment Setting Method) parameter is set to
“ramp setting.”
Setpoint
a Final target setpoint
b
Program
c setpoint
d
<Controller Settings>
Set the STC (Start Code) program parameter to “2”.
Setpoint
a
A1
B1
b
Program
C1 setpoint
c
d D1
E1
e
<Controller Settings>
Set the STC (Start Code) program parameter to “1”.
Program setpoint
Maximum value of
PV input range (RH1)
1st group of
PV input value PID constants
Minimum value of
PV input range (RL1)
Segment 1 Segment 2
<Controller Settings>
- Configure the 1st group of PID constants
(1.P, 1.I and 1.D operating parameters).
[1] The controller uses the 1st group of PID constants if the PV input value is within the
zone set off by the minimum value of the PV input range and reference point 1.
[2] The controller uses the 2nd group of PID constants if the PV input value is within the
zone set off by reference point 1 and reference point 2.
[3] The controller uses the 3rd group of PID constants if the PV input value is within the
zone set off by reference point 2 and the maximum value of the PV input range.
Maximum value of
PV input range (RH1) Program setpoint
3 3rd group of
Reference point 2 PID constants
(2.RP1)
2 2nd group of
PID constants
Reference point 1
(1.RP1)
PV input value
1 1st group of
PID constants
Minimum value of
PV input range (RL1)
Segment 1 Segment 2 Segment 3
<Controller Settings>
• Splitting the control range into two zones
- To split the control range into two zones, define reference point 1 (i.e., the 1.RP1
setup parameter).
- Define the 1st and 2nd groups of PID constants (i.e., the 1.P, 1.I and 1.D
operating parameters for the 1st group and the 2.P, 2.I and 2.D operating
parameters for the 2nd group).
• Splitting the control range into three zones
- To split the control range into three zones, define reference points 1 and 2
(i.e., the 1.RP1 and 2.RP1 setup parameters).
- Define the 1st, 2nd and 3rd groups of PID constants (i.e., the 1.P, 1.I and 1.D
operating parameters for the 1st group, the 2.P, 2.I and 2.D operating parameters
for the 2nd group and the 3.P, 3.I and 3.D operating parameters for the 3rd
group).
[Method 1]
As shown in the figure below, the controller selects the PID constants of the group number
set in PID group number (GRP) if the PV input value goes beyond the given deviation from
the program setpoint.
[1] The controller uses the 1st group of PID constants.
[2] The controller uses the PID constants of the group number set in PID group number
(GRP).
PV input value
Maximum value of
PV input range (RH1)
[2]
[2]
Reference
deviation (RDV1)
[1] Reference
deviation (RDV1)
[1]
Program setpoint
[1]
[2]
Minimum value of
PV input range (RL1) Segment 1 Segment 2
[Method 2]
As shown in the figure below, the controller selects an appropriate group of PID constants
for each zone and, if the PV input value goes beyond the given deviation from the program
setpoint, selects the PID constants of the group number set in PID group number (GRP).
[1] The controller uses the 1st group of PID constants if the PV input value is both within
the zone set off by the minimum value of the PV input range and reference point 1 and
within the given reference deviation bandwidth.
[2] The controller uses the 2nd group of PID constants if the PV input value is both within
the zone set off by reference points 1 and the maximum value of the PV input range,
and within the given reference deviation bandwidth.
[3] The controller uses the PID constants of the group number set in PID group number
(GRP).
PV input value
Maximum value of
PV input range (RH1)
[3]
[3]
Reference
[2] deviation (RDV1)
[2] Reference
deviation (RDV1)
Reference point 1
(1.RP1) [1]
Program setpoint
[1]
[3]
Minimum value of
PV input range (RL1) Segment 1 Segment 2
End of program
Setpoint
Time
4. Operations
This chapter describes key entries for operating the controller. For operations using
external contact inputs, see “1.5 Terminal Wiring Diagrams.” If you cannot remem-
ber how to carry out an operation during setting, press the DISP key no more than
four times. This brings you to the display (operating display) that appears at power-
on.
● SP Display
On the Setpoint display (LCD), the controller displays the current setpoint (SP), the pro-
gram pattern number (PTNO) selected, the segment number (SEGNO) for which operation
is in progress, the number of segments included in the selected program pattern, the
remaining time of the segment for which operation is in progress, the current number of
repetitions (RCY), and the total sum of repetitions.
● Target SP Display
On the Setpoint display (LCD), the controller displays the current setpoint (SP) and final
target setpoint (TSP), the program pattern number (PTNO) selected, the segment number
(SEGNO) for which operation is in progress, the number of segments included in the
selected program pattern, the program pattern name (only displayed when setting the
program pattern name using an optional parameter setting tool (model: LL100-E10)).
● OUT Display
On the Setpoint display (LCD), the controller displays the current setpoint (SP), the PID
number (PID) being used, the program pattern number (PTNO), the segment number
(SEGNO) for which operation is in progress, and the number of segments included in the
selected program pattern, and the control output value (OUT), however, the valve opening
(0 to 100%) in position proportional control.
● Pattern Display
On the Setpoint display (LCD), the controller displays the selected program pattern.
DISP key
0
Deviation Trend display For monitoring only.
-
DISP key
PTN
1
SEG Pattern display For monitoring only.
1
DISP key
TME 1
DISP key
● SP Display
On the Setpoint display (LCD), the controller displays the current setpoint (SP), the pro-
gram pattern number (PTNO) selected, the segment number (SEGNO) for which operation
is in progress, the number of segments included in the selected program pattern, the
remaining time of the segment (TM) for which operation is in progress, the current number
of repetitions (RCY), and the total sum of repetitions.
● Target SP Display
On the setpoint display (LCD), the controller displays the current setpoint (SP) and final
target setpoint (TSP), the program pattern number (PTNO) selected, the segment number
(SEGNO) for which operation is in progress, the number of segments included in the
selected program pattern, the program pattern name (only displayed when setting the
program pattern name using an optional parameter setting tool (model: LL100-E10).
● Pattern Display
On the Setpoint display (LCD), the controller displays the selected program pattern.
● Event Display
On the Setpoint display (LCD), the controller displays the event number for which an event
has occurred.
DISP key
DISP key
0
Deviation Trend display For monitoring only.
-
DISP key
PTN
1
SEG Pattern display For monitoring only.
1
DISP key
TME 1
DISP key
NOTE
When on-off control is being used, auto-tuning cannot be carried out. Moreover, do not
perform auto-tuning when controlling any of the following processes.
• Control processes with quick response such as flow control or pressure control
• Processes where even temporary output on/off results in inconvenience
• Processes where a large output change at control element results in inconvenience
• Processes where variations in PV may exceed an allowable range, adversely affect-
ing product quality
1. Bring the operating display into view (display appears at power on).
PV2 PV
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
PROG PAR
programming parameter
main menu sub menu
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the key twice to display the main 5. Press the key once again to display
SET/ENT
SET/ENT SET/ENT
MODE DISP MODE DISP
6. Press the or key to display the 7. Press the key once to register the
SET/ENT
required setpoint. Tuning for 1st group of setpoint. (This starts auto-tuning.)
PID is AT = 1. If the key is pressed when AT = OFF,
SET/ENT
SET/ENT
MODE DISP
ON.
PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SP = 10.0°C PID: 1
MAN lamp SET/ENT
MODE DISP PTNO: 1 SEGNO: 1/ 3
blinks. PT.No RUN RESET
OUT: 100.0%
1. Bring the operating display into view (display appears at power on).
PV2 PV
SET/ENT
MODE DISP
SP: 10.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 1/ 3
TM= 0h20 RCY: 0/ 0
In steps 2 and later, illustrations of the LCD are cited to explain the procedure.
SET/ENT SET/ENT
MODE DISP MODE DISP
3. Press the key twice to display the main 7. Press the or key to display the
menu “LP1”. required setpoint.
MENU:LP1/1.PID #1
LP1 proportional band
loop 1 parameter changing!
main menu 1.P = 18.0%
Blinks during
change.
SET/ENT SET/ENT
MODE DISP MODE DISP
8. Press the
SET/ENT
SET/ENT SET/ENT
MODE DISP MODE DISP
5. Press the key once to display the The same steps can be used for integral
submenu “1.PID”. time (1.I) and derivative time (1.D) that are
displayed after this.
1.PID
PID parameter SPno.1
sub menu
SET/ENT
MODE DISP
9. Press the key for more than 3 seconds. This returns you to the display shown at power-on
SET/ENT
(figure below).
PV2 PV
ON. PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 10.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 1/ 3
TM= 0h20 RCY: 0/ 0
NOTE
If contact input, which is used to select between program pattern numbers is on, any
program pattern number cannot be selected by key operation.
ON. TME
1
2
PRG
RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 0.0°C
PT.No RUN RESET
PTNO: 0 SEGNO: 0/ 0
TM=------- RCY: 0/ 0
2. Press the PT.No key. This selects the program pattern number.
SET/ENT
MODE DISP
SP: 25.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM= 0h20 RCY: 0/ 0
PV2 PV
Select the program
pattern number of the
RST lamp PVE1
PVE2
controller being operated.
ON. TME
1
2
PRG
RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 25.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM=------- RCY: 0/ 0
2. Press the RUN key for 2 seconds. The selected program pattern starts.
PV2 PV
Start of operation Displays the time
PRG lamp PVE1
of segment 1.
ON.
PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 25.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 1/ 3
TM= 0h20 RCY: 0/ 0
3. Press the RESET key for 2 seconds. The running program stops.
PV2 PV
Stop of operation The time reading
RST lamp PVE1
PVE2
changes to "-------".
ON. TME
1
2
PRG
RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 25.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM=------- RCY: 0/ 0
When in the RESET mode, the controller provides the following input/output values.
NOTE
If AUTO and MAN have been switched using contact input, when the contact input is ON,
switching between AUTO and MAN cannot be achieved by keystroke.
SET/ENT
MODE DISP
SP: 30.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 1/ 3
TM= 0h18 RCY: 0/ 0
PVE1
PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
MODE DISPLAY #4
SET/ENT
MODE DISP AUTO/MAN1 select
PT.No RUN RESET
changing!
MODE : MAN1
3. Press the key once. The controller switches to either MAN-mode or AUTO-mode operation.
SET/ENT
The figure below is an example of the display after a change from the AUTO mode to the MAN
mode.
PV2 PV
ON in MAN. 1
2
3
PRG
RST
HLD
4 LOC
AL MAN
1 CAS
SP = 30.0°C PID: 1
SET/ENT
MODE DISP PTNO: 1 SEGNO: 1/ 3
PT.No RUN RESET
OUT: 40.0%
NOTE
Control output cannot be changed if the controller is in the RESET mode. In this case, the
preset output value (operating parameter PO) will be output.
A control output value is linked with a display value changed using the or key. Note
that the control output changes as displayed without requiring the key. SET/ENT
1. Bring manual operating display into view. For switching to manual operation, see “4.6 Switching
between AUTO and MAN.”
PV2 PV
PVE1
PVE2
ON.
3 HLD
4 LOC
AL MAN
1 CAS
SP = 30.0°C PID: 1
SET/ENT
MODE DISP PTNO: 1 SEGNO: 1/ 3
PT.No RUN RESET
OUT: 30.0%
2. Press the or key to change a control output value. You don’t need to press the SET/ENT
key.
PV2 PV
PVE1
PVE2
ON. 3
4
AL
HLD
LOC
MAN
1 CAS
SP = 30.0°C PID: 1
SET/ENT
MODE DISP PTNO: 1 SEGNO: 1/ 3
PT.No RUN RESET
OUT: 40.0%
PV2 PV
PVE1
PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
ON.
SP = 30.0 °C PID: 1
C = 40.0 % H = 0.0 %
CooL
Cooling-side Heating-side
output Heating/Cooling OUT output
display
Output (%)
Dead band:
Operating parameter DB
-12.4 0 12.4
Cooling-side Heating-side
manipulated output manipulated output
DB=12.4
Change in manipulated output when the dead band is positive
● Controller Behavior and Control Output Manipulation when the Dead Band
is Negative
The following is an example when the DB parameter is set at -12.4%.
If you hold down the key with the heating-side output under manipulation (i.e., cooling-
side output C = 0.0%), the heating-side output (H =) decreases. If the output H falls below
24.8%, the cooling-side output C begins to increase from 0.0%. If you keep the key
held down longer and the output C rises above 24.8%, the output H goes to 0.0% and you
enter the state of manipulating the cooling-side output.
Output (%)
24.8
-12.4 0 12.4
Cooling-side Heating-side
manipulated output manipulated output
DB=-12.4
Change in manipulated output when the dead band is negative
PV2 PV
PVE1
PVE2
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
ON.
SP = 30.0°C PID: 1
PTNO: 1 SEGNO: 1/ 3
Displays the
OUT: 35.0% valve opening
(0 to 100%).
OUT display
SET/ENT
MODE DISP
SP: 80.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 1h20 RCY: 0/ 0
PVE1
PVE2
Blinks during
TME
1
2
PRG
RST
change.
3 HLD
4 LOC
AL MAN
1 CAS
MODE DISPLAY #1
SET/ENT
MODE DISP PROG-hold switch
PT.No RUN RESET
changing!
HOLD : ON
3. Press the
SET/ENT
key once. The controller switches to either hold mode or non-hold mode.
PV2 PV
SET/ENT
MODE DISP
SP: 80.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 0h20 RCY: 0/ 0
1. Set program operation in the hold mode. To do this, see “4.8 Enabling/Disabling Hold Mode of
Program Operation.”
PV2 PV
This symbol appears for
HLD lamp PVE1
PVE2
soak segments only.
TME
ON.
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 80.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 0h20 RCY: 0/ 0
2. Press the
SET/ENT
PV2 PV
Make sure the “ ”
PVE1
PVE2
symbol is shown.
TME
1 PRG
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP: 80.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 0h20 RCY: 0/ 0
SET/ENT
MODE DISP
SP: 85.0 ?
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 0h20 RCY: 0/ 0
4. Press the
SET/ENT
SET/ENT
MODE DISP
SP: 85.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 0h20 RCY: 0/ 0
1. Bring the current operating display for program operation into view.
SET/ENT
MODE DISP
SP: 30.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 1/ 3
TM= 0h17 RCY: 0/ 0
2. Press the MODE key twice to display the ADV:ON mode parameter.
PV2 PV
PVE1
PVE2
TME
Blinks during
1 PRG
2
3
4
RST
HLD
LOC
change.
AL MAN
1 CAS
MODE DISPLAY #2
SET/ENT
MODE DISP PROG-advance switch
PT.No RUN RESET
changing!
ADV : ON
3. Press the
SET/ENT
key once. The controller resumes operation from the target setpoint of segment 1.
SET/ENT
MODE DISP
SP: 80.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 2/ 3
TM= 1h20 RCY: 0/ 0
SET/ENT
MODE DISP
SP: 40.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 1/ 3
TM= 0h14 RCY: 0/ 0
2. Press the MODE key several times to display the LOC:ON mode parameter.
PV2 PV
PVE1
PVE2
Blinks during
TME
1
2
PRG
RST
change.
3 HLD
4 LOC
AL MAN
1 CAS
MODE DISPLAY #3
SET/ENT
MODE DISP local drive switch
PT.No RUN RESET
changing!
LOC : ON
3. Press the key once. The controller begins running with a local setpoint (L.SP).
SET/ENT
The figure below is an example of operating the controller with the local setpoint of 50.0°C.
ON.
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP:
L. 50.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM=------- RCY: 0/ 0
1. Change the controller to local-mode operation. To do this, see “4.11 Switching to Local-mode
(LOCAL) Operation.”
ON.
2 RST
3 HLD
4 LOC
AL MAN
1 CAS
SET/ENT
MODE DISP
SP:
L. 50.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM=------- RCY: 0/ 0
SET/ENT
MODE DISP
SP:
L. 60.0 ?
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM=------- RCY: 0/ 0
3. Press the
SET/ENT
SET/ENT
MODE DISP
SP:
L. 60.0°C
PT.No RUN RESET
PTNO: 1 SEGNO: 0/ 3
TM=------- RCY: 0/ 0
5.1 Troubleshooting
■ Troubleshooting Flow
If the operating display does not appear after turning on the controller’s power, follow the
measures in the procedure below.
If a problem appears complicated, contact our sales representative.
Is the instrument
defective?
Yes
No Is key No No No Is
Totally Is display Is I/O communication
operation
inoperable? faulty? signal faulty? link faulty?
faulty?
Yes Yes Yes Yes Yes
Check wiring on the Check the key lock Turn off power, and Check the Check the
power supply setting. then turn it on instrument’s I/O instrument's suffix
terminals. again. specifications. code.
No
Check the supply Check the specifications Does the code
voltage. of I/O counterpart for include a communication
wrong polarity. option?
No Check the
No communication
Normal? capability.
communication-related
No Is parameters.
key lock
enabled?
Yes Check
Correct the
error(s). communication wiring.
IMPORTANT
Take note of the parameter settings when asking the vendor for repair.
Normal
action Check and
Error code 0% or less set the
2 Parameter error Normal action Normal action Normal action
(See description below.) or OFF initialized
parameters.
Note 1: PV display
2: Setpoint display
Bit No. 6 5 4 3 2 1 0
Parameter to be checked Operation mode/output Operating parameters Setup parameters Range data UP mode – Calibration data
For example, if an error occurs with the operating parameter and calibration data, the error
code will be as follows:
Bit No. – 6 5 4 3 2 1 0
2 1 0 3 2 1 0
Error Code – 2 2 2 2 2 2 2
2 1
Excessive PV
OVER or -OVER -5% or 105% Normal action Check process.
Out of -5 to 105%
Normal Normal
Auto-tuning Action with PID Check process. Press
action action
E200 failure existing before any key to erase error
(Time-out) auto-tuning indication.
Alarm action Continues. Alarm with standby function will enter standby status.
Settig parameter Set contents of each parameter are retained.
Auto-tuning Cancelled.
Control action Action before power failure continues.
● The Controller does not Show the Correct Process Variable (PV).
• The UP550 controllers have a universal input.
The type of PV input can be set/changed using the parameter “IN1”. At this point, the
controller must be wired correctly according to the selected type of PV input. Check
the wiring first if the controller fails to show the correct PV value. To do this, refer to “2.
Initial Settings.”
With the parameters “RH1”, “RL1”, “SDP1”, “SH1” and “SL1”, it is possible to scale the
input signal and change its number of decimal places. Also check that these param-
eters are configured correctly.
● The Controller does not Provide any Control Output or the Control Output
does not Change at all.
• The UP550 controllers have a universal output.
The type of control output can be set/changed using the parameter “OT1”.
At this point, the controller must be wired correctly according to the selected type of
control output. Check the wiring first if the controller provides no control output. To do
this, refer to “1.5 Terminal Wiring Diagrams.”
With the parameters “OH” and “OL”, it is possible to set/change the high and low limits
of control output. The control output may not change at all, however, because of
restrictions on these parameters. Also check the restrictions on these parameters.
• The control output can only be changed when the controller is in the MAN mode.
If the MAN lamp is off (i.e., the controller is in the AUTO mode), you cannot change the
control output using key operation.
● The Control Output does not Change soon after the Target Setpoint SP has
been Changed.
• If this happens, check the setpoint of the parameter “MOD1”. In cases where fixed-
point control is selected as the PID control mode (MOD1 = 1), tracking based on the I-
term works to prevent the control output from changing suddenly even if the target
setpoint SP is varied.
The control output therefore may appear to be working incorrectly at first; however it
gradually adapts itself to the new target setpoint. Be especially careful when the
controller is in the fixed-point control mode; the control output may fail to change and
therefore result in a loss of control if you change the target setpoint SP too frequently.
5.2 Maintenance
This section describes the cleaning and maintenance of the UP550.
5.2.1 Cleaning
The front panel and operation keys should be gently wiped with a dry cloth.
NOTE
Do not use alcohol, benzine, or any other solvents.
SEE ALSO
“1.2 How to Install,” for how to replace brackets.
Do not touch the terminals on the rear panel when power is being supplied to the controller.
Doing so may result in electric shock.
Before attaching the terminal cover, turn off the source circuit breaker and use a tester to
CAUTION check that the power cable is not conducting any electricity.
1. Before attaching the terminal cover, fold it once or twice so that the side which has the
“Handle With Care” symbol ( ), is on the outside.
Fold over.
Grooved
Fold over.
NOTE
Do not fold the terminal cover the wrong way, doing so not only reduces the cover’s
strength but may also cause the hinge to crack, thereby disabling attachment.
2. With the cover properly folded, fit its top and bottom holes to the protrusions of the
mounting brackets.
If any of these parts, except control output relays, cause a controller failure due to deterio-
ration, contact your dealer for replacement at your cost.
Control output relays can be replaced by yourself.
SEE ALSO
“5.2.5 Replacing Control Output Relays,” for how to replace the control output relays.
Always turn off the power before starting the work in order to avoid electric shock.
Do not pull out the internal unit for any other purpose other than to replace the control
output relays.
CAUTION
1. Insert a flat-blade screwdriver (tip width of 6 mm is recommended) into the opening with
the tip in parallel with the front panel, and then turn the screwdriver gently. Take this
procedure to four openings 1, 2, 3 and 4 (see the figure below) on the upper and lower
parts of the bezel, in order.
The bezel slightly moves forward from the housing.
1
2
4
3
2. Push up the center of the bottom gasket of bezel by a finger to release the latch.
Latch (invisible in the panel)
Panel
View from the bottom
3. Insert the flat-blade screwdriver into the four openings and flip the tip forward to move
the bezel more forward.
4. Hold the bezel and pull it along with the internal unit out of the housing.
(Note) Be careful not to damage the RJC sensor.
5. The location and number of the relays differ depending on the model code of the UP550.
Confirm the location of the control output relay to be replaced before pulling out the
relay.
Upper
Relay (UP550-0䊐)
Lower
Insert the new relay in the socket. Use the following relay.
Manufacturer OMRON
Model G6B-2114P-FD-US-P6B
Power supply 12 V DC
6. Parameters
Operating Display
DISP
SET3S
SET1S MODE
SET3S or Main menu
DISP DISP
DISP
HOLD
SELECT
display 1 ADV
PROG AL LP1
LOC
MODE
(A/M1)
SELECT MODE submenu
MODE SET SET SET DISP
display 2 (LSP/
CAS)
SST
SELECT
* display 3 PAR 1.PID 7.PID 8.PID
SET
SET SET SET SET
SELECT
display 4 To program
parameter A1 AT 1.P 7.P 8.P
setting display A2 SC 1.I 7.I 8.I
submenu A3 BS 1.D 7.D 8.D
SELECT *1
[LOC] A4 FL 1.OH 7.OH 8.OH
display 5
on the Program
Parameter Map ORB 1.OL 7.OL 8.OL
ORH 1.MR 7.MR 8.MR
See “3.5 Program Parameter Map” ORL 1.H 7.H 8.H
S.TM 1.DR *2 7.DR 8.DR
1.Pc 7.Pc 8.Pc
1.Ic 7.Ic 8.Ic
*3
1.Dc 7.Dc 8.Dc
1.Hc 7.Hc 8.Hc
1.DB *4 7.DB 8.DB
1.PO 7.PO 8.PO
1.Oc *3 7.Oc 8.Oc
SET/ENT
SET Press the key once.
*5 *6 *7
LP2 USR PYS1 PYS2 STUP
Password
U1 1.a1 2.a1
check display
U2 1.b1 2.b1
U3 1.a2 2.a2
OK
1.b2 2.b2
1.a3 2.a3
1.b3 2.b3 To setup
1.a4 2.a4 parameter
setting display
1.b4 2.b4 main menu
1.a5 2.a5 [PARA]
Same 1.b5 2.b5 on the Setup
1.a6 2.a6 Parameter Map
as LP1
1.b6 2.b6
1.a7 2.a7
1.b7 2.b7
1.a8 2.a8
1.b8 2.b8
1.a9 2.a9 Pressing the DISP key once when a parameter setting display is shown
1.b9 2.b9 retrieves the menu of that parameter setting display.
1.a10 2.a10 Example: Pressing the DISP key once when the [PAR] submenu is displayed,
1.b10 2.b10 will display the [LP1] main menu. Conversely, the [PAR] submenu
1.a11 2.a11 will reappear by pressing the DISP key once when the [PAR]
1.b11 2.b11 submenu’s “FL” parameter display is shown.
1.PMD 2.PMD
* SELECT displays 1 to 5 are shown only when they are registered.
PARA CMLP
Pressing the DISP key once when a parameter setting display is shown retrieves the submenu of that parameter setting display.
*1 *2
CSEL DO DI MD IN OUT R485 VALV
Note: The parameter items shown on the [TEST] submenu of the setup parameter setting display are to be used by
Yokogawa service personnel to check the controller functions. User cannot set or change these parameters.
*1 Submenu R485 is displayed only for the controller with communication function.
*2 Submenu VALV is displayed only for the position proportional controller.
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Pause of program Set as “HOLD = ON” to enable the hold mode of program operation.
HOLD operation
Ref.5.2(5)
Advance of segment Set as “ADV = ON” to advance from the current segment to the next segment.
ADV Ref.5.2(7)
Local-mode Set as “LOC = ON” to switch from program operation or RESET mode to local-mode operation.
LOC operation
Ref.5.2(9)
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Instrument alarm-1 Allows alarm action to be set irrespective of the PV high limit/SP high
A1 setpoint program. limit alarm: 100.0% of
PV input range
Instrument alarm-2 PV alarm / SP alarm: -100.0 to 100.0% of Deviation alarm: 0.0% of
A2 setpoint PV input range PV input range span
Deviation alarm: -100.0 to 100.0% of PV Other PV/SP low limit Ref.3.4(1)
Instrument alarm-3
A3 setpoint
input range span
Output alarm: -5.0 to 105.0%
alarm: 0.0% of PV input range
Output high limit
alarm: 100.0%
Instrument alarm-4
A4 setpoint
Output low limit
alarm: 0.0%
● Operation-related Parameters
Located in: Main menu = LP1 ; Submenu = PAR
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
limit (in heating/cooling 0.0 to 105.0% (1.OL < 1.OH) control: 100.0%
control) SD (shutdown): Set in manual operation in
4-20 mA control output. Output is 0 mA.
Manual reset -5.0 to 105.0% 50.0%
1.MR (enabled when integral time “1.I” is OFF)
The manual reset value equals the output value
when PV = SP is true. For example, if the
manual reset value is 50%, the output value is
50% when PV = SP becomes true.
ON/OFF control hysteresis In ON/OFF control: 0.0 to 100.0% of PV input range span ON/OFF control: 0.5%
1.H Heating-side ON/OFF In position proportional PID control or heating/cooling of PV input range span
control hysteresis control: 0.0 to 100.0% Position proportional
(in heating/cooling control) Hysteresis can be set in the program setpoint when PID control and
the controller is performing ON/OFF control. heating/cooling control:
0.5%
Point of
ON/OFF action
Output (Program setpoint)
On Hysteresis
Off
PV value
Direct/reverse action REVERSE (0): reverse action, DIRECT (1): direct action REVERSE (0)
1.DR switching Control output
100%
Ref.2.1(1)
Reverse Direct
action action
- +
0% Deviation
(PV-SP)
Cooling-side 0.0 to 999.9% of PV input range 5.0%
1.Pc proportional band (Cooling-side ON/OFF control applies when 0.0)
1.b6
Ten-segment
linearizer
1.b5 biasing
1.b3 1.b4
Ten-segment
1.a1 1.a2 1.a3 1.a4 1.a5 1.a6 1.a8 linearizer input
1.a7
linearizer output
1.b4 the parameter 1.b4.
PV input
range after
ten-segment
1.b3
linearizer
approximation
1.b2
1.b1
The parameters 1.a5 to
1.a11 are equalized to
the parameter 1.a4.
1.a1 1.a2 1.a3 1.a4 1.a11
Ten-segment
Actual PV input range linearizer input
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Program setpoint-2 Place limits on the program setpoints when the controller is in 100.0% of PV
SPH2 limiter upper limit program pattern-2 retransmission. input range
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
PV event 6 hysteresis
PEH6 0.0 to 100.0%
PV value
PV event 7 hysteresis
PEH7
PV event 8 hysteresis
PEH8
Instrument alarm-1 OFF (0), 1 to 20, 25 to 31 1
AL1 type 1: PV high limit (energized, no stand-by action)
Instrument alarm-2 2: PV low limit (energized, no stand-by action) 2
AL2 type 3: Deviation high limit (energized, no stand-by action)
4: Deviation low limit (energized, no stand-by action) Ref.3.4(1)
Instrument alarm-3 1
AL3 type
5: Deviation high limit (de-energized, no stand-by action)
6: Deviation low limit (de-energized, no stand-by action)
Instrument alarm-4 For other alarm types, see the next page. 2
AL4 type
Instrument alarm-1 0.0 to 100.0% of PV input range span 0.5% of PV
HY1 hysteresis Output alarm: 0.0 to 100.0% input range
span
Allows margins to be set for an alarm setpoint. Output
Instrument alarm-2 With the hysteresis settings, it is possible to prevent relays from chattering. alarm: 0.5%
HY2 hysteresis
Hysteresis for PV high limit alarm
Point of ON/OFF action
Output (Alarm setpoint) Ref.3.4(3)
Instrument alarm-3
HY3 hysteresis On
Hysteresis Hysteresis
Hysteresis
2 Closed Open Closed 7
Deviation high (lit) (unlit) (lit)
PV low limit Closed (lit) Open (unlit) and low limits
Deviation setpoint PV
12 17
Alarm setpoint PV
Target SP
Hysteresis
Hysteresis
4 9
Deviation low Closed (lit) Open (unlit) De-energized on Closed
limit PV high limit (unlit) Open (lit)
Deviation setpoint
PV 14 19
PV Alarm setpoint
Target SP
Hysteresis
Hysteresis
De-energized on 5 10
Closed Open (lit) De-energized on Closed
deviation high (unlit) Open (lit)
PV low limit (unlit)
limit alarm Deviation
PV setpoint 15 20
Alarm setpoint PV
Target SP
Hysteresis Hysteresis
Closed (lit) Closed (lit)
SP high
28 Output high limit 30
limit Open (unlit) Open (unlit)
Hysteresis Hysteresis
Closed (lit) Closed (lit)
SP low
29 Output low limit 31
limit Open (unlit) Open (unlit)
The following alarm types are used only for “Instrument Alarm.”
25: Sensor grounding alarm
26: Fault diagnosis output (Note 1)
27: FAIL output (Note 2)
Note 1: The fault diagnosis output turns on in case of input burnout, A/D converter failure, or reference junction compensation
(RJC) failure. For input burnout or A/D converter failure, the control output is set to the setpoint of the Preset Output
Value operating parameter (PO).
Note 2: The FAIL output is on during normal operation and turns off case failure.
⬚C
Stand-by Action Treated
Normal Abnormal
as normal The alarm
output turns on.
Low limit of
alarm setpoint
Power-on Time
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Zone PID reference The example below sets reference points 1 and 2 to provide 3 zones to
3.RP1 point-3 switch PID constants automatically.
Ref.5.1(2)
Zone PID reference
4.RP1 point-4
Maximum value of
PV input range
RH1
Zone 3
Setpoint The controller is operated with
the 3rd group of PID constants.
Reference point 2
Zone PID reference
5.RP1 point-5
2.RP1 Zone 2
The controller is operated with
the 2nd group of PID constants.
Reference point 1
1.RP1 PV input
value Zone 1
Zone PID reference The controller is operated with
6.RP1 point-6
Minimum value of
PV input range
RL1
the 1st group of PID constants.
Time
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Minimum value of
PV input range Segment 1 Segment 2
RL1
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Analog input-1 bias Used to correct the PV input value beforehand. 0.0% of PV
A.BS1 When in normal operation, use the PV Input Bias (BS) operating input range
parameter. span
Ref.1.1(6)
-100.0% to 100.0% of PV input range span
Analog input-1 filter OFF (0): Disable OFF (0)
A.FL1 1 to 120 sec.
Analog input-1 Performs square-root computation for the PV input value. OFF (0)
A.SR1 square-root OFF (0): Do not compute the square root
computation ON (1): Compute the square root Ref.1.1(3)
Analog input-1 low 0.0% to 5.0% 1.0%
A.LC1 signal cutoff The slope equals “1” at levels below the low-signal cutoff point.
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Deviation trend scale Allows the deviation axis of the Deviation Trend operating 0.5% of PV
TSC1 display to be rescaled. input range
0.1 to 100.0% of PV input range span span
Ref.6.1(2)
Deviation trend time Allows the time axis of the Deviation Trend operating display 5 sec.
TTM to be rescaled.
1 to 600 sec.
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Relay output flag The following setpoints are registration numbers for single-loop 5705
DO1 registration for DO1 control only.
Relay output flag 5705: PV event 1 output 0: No function 5706
DO2 registration for DO2 5706: PV event 2 output
Relay output flag 5689: Instrument alarm 1 output 5689
DO3 registration for DO3 5129: Time event 1 output
5130: Time event 2 output 5129
Open-collector transistor
DO4 output flag registration
5131: Time event 3 output
5133: Time event 4 output
for DO4
Ref.3.2(2)
Open-collector transistor 5130
DO5 output flag registration
See “External contact output” in “1.5 Terminal Wiring
Diagrams.”
for DO5
Open-collector transistor 5131
DO6 output flag registration
for DO6
Open-collector transistor 5133
DO7 output flag registration
for DO7
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Start of program operation These parameters determine which contact input to use to 5165
PROG (When “DIn” changes from make selections/switches listed on the left.
OFF to ON) DI1: 5161 No function: 0
Stop of program operation DI2: 5162 5166
RST (When “DIn” changes from DI3: 5163
OFF to ON) DI4: 5164
Start of local-mode operation DI5: 5165 5167
LOC (When “DIn” changes from DI6: 5166
OFF to ON) DI7: 5167
DI8: 5168 0
Start of hold-mode operation
HOLD (When “DIn” changes from
The contact inputs are factory-set as shown below.
Contact inputs 1 to 4 (DI1 to DI4): Program pattern number
OFF to ON)
selection (see below)
Advance of segment 0
ADV (When “DIn” changes from
Contact input 5 (DI5): Start of program operation
Contact input 6 (DI6): Stop of program operation
OFF to ON)
Contact input 7 (DI7): Start of local-mode operation
Loop-1 AUTO/MAN switching 0
A/M1 (AUTO when contact input is ON;
Contact input 8 (DI8): ON when using 16 or more of program
patterns
MAN when contact input is OFF)
Loop-2 AUTO/MAN switching Program pattern number selection 0
A/M2
1 2 3 4 5 6 7 8
LOCAL/CASCADE switching 0 Ref.3.1(7)
L/C Not used for single-loop DI1 ON OFF ON OFF ON OFF ON OFF
control. DI2 OFF ON ON OFF OFF ON ON OFF
Bit 0 of program pattern 5161
PTN.0 number
DI3
DI4
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Bit 1 of program pattern 5162
PTN.1 number 9 10 11 12 13 14 15
Bit 2 of program pattern 5163
PTN.2 number
DI1
DI2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Bit 3 of program pattern 5164
PTN.3 number
DI3 OFF OFF OFF ON ON ON ON
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
● Input-related Parameters
Located in: Main menu = UPMD ; Submenu = IN
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
PV input type Specify the type of PV input as a range code. OFF (0)
IN1 (INPUT 1 terminals) See “Instrument Input Range Codes” in “2. Initial Settings.”
Terminals 11 , 12
and 13
PV input unit Select the unit of PV input. Depends on
UNI1 % (0): Percent - (2): No unit the PV
C (1): Degree Celsius F (5): Fahrenheit input type.
Max. value of PV Set the instrument input range (RL1 < RH1). Depends on
RH1 input range the PV
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Auxiliary analog
IN3 input type
Although not used in single-loop control, it is shown on the display.
(INPUT 3 terminals)
Terminals 21 and 22
Auxiliary analog
UNI3 input unit
Although not used in single-loop control, it is shown on the display.
Maximum value of
RH3 auxiliary analog input Although not used in single-loop control, it is shown on the display.
range
Minimum value of
RL3 auxiliary analog input Although not used in single-loop control, it is shown on the display.
range
Auxiliary analog input
SDP3 decimal point Although not used in single-loop control, it is shown on the display.
position
Max. value of auxiliary
SH3 analog input scale
Although not used in single-loop control, it is shown on the display.
Parameter Name of Parameter Setting Range and Description Initial User Target Item
Symbol Value Setting in CD-ROM
Control output 0 Time proportional PID relay contact output (terminals 1 - 2 - 3 ) 0
OT1 type 1 Time proportional PID voltage pulse output (terminals 16 - 17 ) Heating/
cooling
2 Current output (terminals 16 - 17 )
type : 4
3 ON/OFF control relay contact output (terminals 1 - 2 - 3 )
The following 4 to 12 are displayed only for heating/ cooling type
controllers.
4 Heating-side relay output (terminals 1 - 2 - 3 ), cooling-side
relay output (terminals 48 - 49 - 50 )
5 Heating-side pulse output (terminals 16 - 17 ), cooling-side relay
output (terminals 48 - 49 - 50 )
6 Heating-side current output (terminals 16 - 17 ), cooling-side
relay output (terminals 48 - 49 - 50 )
7 Heating-side relay output (terminals 1 - 2 - 3 ), cooling-side
pulse output (terminals 46 - 47 )
8 Heating-side pulse output (terminals 16 - 17 ), cooling-side pulse
output (terminals 46 - 47 )
9 Heating-side current output (terminals 16 - 17 ), cooling-side
pulse output (terminals 46 - 47 )
10 Heating-side relay output (terminals 1 - 2 - 3 ), cooling-side
current output (terminals 46 - 47 )
11 Heating-side pulse output (terminals 16 - 17 ), cooling-side
current output (terminals 46 - 47 )
12 Heating-side current output (terminals 16 - 17 ), cooling-side
current output (terminals 46 - 47 )
Control output cycle 1 to 1000 sec. 30 sec.
CT1 time
Heating-side control
output cycle time On On
The figure below shows an example where both analog outputs-1 and 3 are set to the
current signal of 4 to 20 mA DC. The type of output signal can be determined separately for
each of the analog outputs listed above, using the following three parameters.
Analog output-1: Analog output-1 type (AO1)
Analog output-2: Analog output-2 type (AO2)
Analog output-3: Analog output-3 type (AO3)
Analog output-3
100% segmental Analog output-1
point (A3H) 100% segmental
point (A1H)
mA %
20 100
Analog output-3
Output value after computation
16 75
Analog output-1
12 50
Analog output-3
8 25
0% segmental
Analog output-1 point (A3L)
0% segmental
point (A1L)
4 0
0 25 50 75 100 %
Output value before split computation
The figure below shows an example where both analog outputs-1 and 3 are set to the
current signal of 20 to 0 mA DC. The type of output signal can be determined separately for
each of the analog outputs listed above, using the following three parameters.
Analog output-1: Analog output-1 type (AO1)
Analog output-2: Analog output-2 type (AO2)
Analog output-3: Analog output-3 type (AO3)
Analog output-3
100% segmental Analog output-1
point (A3H) 100% segmental
point (A1H)
mA %
0 100
Output value after computation
Analog output-3
5 75
Analog output-1
10 50
15 25
Analog output-3 Analog output-1
0% segmental 0% segmental
point (A3L) point (A1L)
20 0
0 25 50 75 100 %
Output value before split computation
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
Automatic valve Automatically adjusts the fully-closed and fully-opened OFF (0)
V.AT adjustment positions of a valve. When this function is used, there is no
need for adjustment using the parameters V.RS, V.L and V.H.
OFF (0): -
ON (1): Start automatic adjustment
Valve position setting The parameters V.RS, V.L and V.H are designed for 0
V.RS reset manual adjustment of valve positions.
Setting V.RS to 1 resets the valve adjustment
settings and causes the indication “V.RS” to blink.
Fully-closed valve Pressing the SET/ENT key with valve position Undefined
V.L position setting set to the fully-closed position causes the
adjusted value to be stored. When V.L.
adjustment is complete, V.L. stops blinking.
Fully-opened valve Pressing the SET/ENT key with valve position Undefined
V.H position setting set to the fully-opened position causes the
adjusted value to be stored. When V.H.
adjustment is complete, V.H. stops blinking.
Valve traveling time 5 to 300 sec. 60 sec.
TR.T Used to operate a valve according to the estimated
valve position. Set the time required for the valve to
open fully from a state of being fully closed. Confirm
the valve traveling time by consulting the datasheet of
the valve’s specifications.
The valve traveling time is only effective when Valve
Adjustment Mode (V.MD) is set to 1 or 2.
Valve adjusting mode 0: Valve position feedback type 0
V.MOD 1: Valve position feedback type (moves to the estimating
type if a feedback input error or burnout occurs.)
2: Valve position estimating type
Parameter Name of Parameter Setting Range and Description Initial Value User Target Item
Symbol Setting in CD-ROM
PV SP Communication
0% to 100%
Heating/cooling
computation
Cooling-side Heating-side
output limiter output limiter
Cooling-side MV Heating-side MV
output output
0% to 100% 0% to 100%
Heating/cooling control provides two methods in which either none of the heating- and
cooling-side outputs are presented or both of the heating- and cooling-side outputs are
presented, as shown in the following figures.
Cooling-side Heating-side
Cooling-side Heating-side output output
output output
0 0
0 50 100(%) 0 50 100(%)
Dead band Dead band
Value of control output before split into Value of control output before split into
heating- and cooling-side outputs heating- and cooling-side outputs
Controller
Control computation
Control
Feedback output
input Direct action
Comp-
arator
Valve position Reverse
signal action
M
Slide-wire resistor
Motor-operated
valve
STOP RUN
STOP/RUN switching
15 V loop Retransmission
OT1 power supply output
Control
output RET2 RET1
Heating/cooling
computation
Heating-side Cooling-side
output limiter output limiter
Heating-side Cooling-side
preset output preset output
STOP/RUN switching
15 V loop Retransmission
OT1 OT1 power supply output
Heating-side Cooling-side
output output RET2 RET1
Output limiter
MAN AUTO
A/M
Preset output
STOP RUN
STOP/RUN switching
15 V loop Retransmission
Signal comparison power supply output
L relay H relay
( key) ( key)
RET2 RET1
FEEDBACK OUTPUT
terminals terminals OUTPUT1 OUTPUT3
45 , 46 and 47 48 , 49 and 50
M Motor-driven valve
PV event output
Valve position Time event output
sliding resistor Instrument alarm output
■ PV Input
PV input (INPUT1) is a universal input, which can receive signals from thermocouple, RTD,
or DC voltage signals. The controller is capable of biasing, square root extraction, first-
order lag computation (filtering), ten-segment linearizer approximation, and ten-segment
linearizer biasing on input signals.
Each function can be set by the following parameters.
Setup Parameters
Operating Parameters
For example, set contact input 2 (DI2) only to “ON” to change the program pattern 1 to the
program pattern 2.
Set contact input 1 (DI1) and contact input 2 (DI2) to “ON” to select the program pattern 3.
■ PID
It is possible to use a maximum of eight groups of PID parameters.
Operating Parameters
Setup Parameters
Operating Parameters
■ Contact Output
PV event 1 is outputted via DO1 (contact output 1).
PV event 2 is outputted via DO2 (contact output 2).
Instrument alarm 1 is outputted via DO3 (contact output 3).
Time event 1 is outputted via DO4 (contact output 4).
Time event 2 is outputted via DO5 (contact output 5).
Time event 3 is outputted via DO6 (contact output 6).
Time event 4 is outputted via DO7 (contact output 7).
Setup Parameters
Setup Parameters
Revision Information
● Title : Model UP550 Program Controller User’s Manual for Single-loop Control
● Manual No. : IM 05E01C02-41E