This document summarizes the air system sizing for an equipment room in Thai Binh, Vietnam. It includes:
1) The air system will serve a single 12.9 square meter zone used as an equipment room.
2) Calculations were performed between January to December to size the system to meet peak loads during that period.
3) The central cooling coil was sized to have a total load of 1500 kW and sensible load of 361 kW based on the peak zone loads and design conditions of 35.8/35.5 degrees Celsius outside.
This document summarizes the air system sizing for an equipment room in Thai Binh, Vietnam. It includes:
1) The air system will serve a single 12.9 square meter zone used as an equipment room.
2) Calculations were performed between January to December to size the system to meet peak loads during that period.
3) The central cooling coil was sized to have a total load of 1500 kW and sensible load of 361 kW based on the peak zone loads and design conditions of 35.8/35.5 degrees Celsius outside.
This document summarizes the air system sizing for an equipment room in Thai Binh, Vietnam. It includes:
1) The air system will serve a single 12.9 square meter zone used as an equipment room.
2) Calculations were performed between January to December to size the system to meet peak loads during that period.
3) The central cooling coil was sized to have a total load of 1500 kW and sensible load of 361 kW based on the peak zone loads and design conditions of 35.8/35.5 degrees Celsius outside.
This document summarizes the air system sizing for an equipment room in Thai Binh, Vietnam. It includes:
1) The air system will serve a single 12.9 square meter zone used as an equipment room.
2) Calculations were performed between January to December to size the system to meet peak loads during that period.
3) The central cooling coil was sized to have a total load of 1500 kW and sensible load of 361 kW based on the peak zone loads and design conditions of 35.8/35.5 degrees Celsius outside.
Project Name: THAI BINH - HAM RONG Prepared by: pve 04/11/2014 04:19PM
Air System Information
Air System Name Equipment Class Air System Type LFS - EQUIPMENT SPLT AHU SZCAV Number of zones Floor Area Location 1 12.9 m Thai Binh, Vietnam
Sizing Calculation Information
Zone and Space Sizing Method: Sum of space airflow rates Zone L/s Individual peak space loads Space L/s Calculation Months Sizing Data Jan to Dec Calculated
Central Cooling Coil Sizing Data
Total coil load Sensible coil load Coil L/s at Oct 1500 Max block L/s Sum of peak zone L/s Sensible heat ratio m/kW W/m Water flow @ 5.6 K rise 6.8 4.7 361 361 361 0.699 1.9 523.3 N/A kW kW L/s L/s L/s Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Oct 1500 35.8 / 35.5 25.6 / 19.6 14.7 / 14.2 13.5 0.100 53 12.8 1 of 1 0.0 C C C C % C OK K
Central Heating Coil Sizing Data
Max coil load Coil L/s at Des Htg Max coil L/s Water flow @ 11.1 K drop 0.1 kW 361 L/s 361 L/s N/A Load occurs at W/m Ent. DB / Lvg DB Des Htg 8.5 21.1 / 21.3 C
Supply Fan Sizing Data
Actual max L/s Standard L/s Actual max L/(s-m) 361 L/s 360 L/s 27.98 L/(s-m) Fan motor BHP Fan motor kW Fan static 0.01 BHP 0.01 kW 10 Pa