Air System Sizing Summary For GDC-CONTROL-ELECTRIC

This document summarizes the air system sizing for a control electric equipment room in Thai Binh, Vietnam. The air system serves one zone covering 65 square meters. Calculations were performed between January and December to size the central cooling coil, central heating coil, supply fan, and outdoor ventilation requirements. The central cooling coil is designed to handle a total load of 1300 kW and sensible load of 1511 L/s at design conditions in July. The central heating coil is sized for a maximum 0.4 kW load in design heating conditions. The supply fan is sized for an actual maximum airflow of 1111 L/s. Outdoor ventilation is designed for 40 L/s or 0.62 L/s per square meter.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views

Air System Sizing Summary For GDC-CONTROL-ELECTRIC

This document summarizes the air system sizing for a control electric equipment room in Thai Binh, Vietnam. The air system serves one zone covering 65 square meters. Calculations were performed between January and December to size the central cooling coil, central heating coil, supply fan, and outdoor ventilation requirements. The central cooling coil is designed to handle a total load of 1300 kW and sensible load of 1511 L/s at design conditions in July. The central heating coil is sized for a maximum 0.4 kW load in design heating conditions. The supply fan is sized for an actual maximum airflow of 1111 L/s. Outdoor ventilation is designed for 40 L/s or 0.62 L/s per square meter.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for GDC-CONTROL-ELECTRIC

Project Name: THAI BINH - HAM RONG Prepared by: pve 04/11/2014 04:27PM

Air System Information


Air System Name Equipment Class Air System Type GDC-CONTROL-ELECTRIC SPLT AHU SZCAV Number of zones Floor Area Location 1 65.0 m Thai Binh, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method: Sum of space airflow rates Zone L/s Individual peak space loads Space L/s Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Sensible coil load Coil L/s at Jul 1300 Max block L/s Sum of peak zone L/s Sensible heat ratio m/kW W/m Water flow @ 5.6 K rise 19.0 15.1 1111 1111 1111 0.798 3.4 291.7 N/A kW kW L/s L/s L/s Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Jul 1300 37.1 / 36.6 25.6 / 18.7 14.3 / 13.7 13.1 0.100 48 12.8 1 of 1 0.0 C C C C % C OK K

Central Heating Coil Sizing Data


Max coil load Coil L/s at Des Htg Max coil L/s Water flow @ 11.1 K drop 0.4 kW 1111 L/s 1111 L/s N/A Load occurs at W/m Ent. DB / Lvg DB Des Htg 5.4 21.5 / 21.8 C

Supply Fan Sizing Data


Actual max L/s Standard L/s Actual max L/(s-m) 1111 L/s 1109 L/s 17.10 L/(s-m) Fan motor BHP Fan motor kW Fan static 0.06 BHP 0.04 kW 20 Pa

Outdoor Ventilation Air Data


Design airflow L/s L/(s-m) 40 L/s 0.62 L/(s-m) L/s/person 10.00 L/s/person

Hourly Analysis Program v.4.3

Page 1 of 1