The document summarizes the air system sizing for a GF-Staff Dining project in Madinah, Saudi Arabia. It includes sizing calculations for the central cooling coil, central heating coil, supply fan, and outdoor ventilation air. The central cooling coil has a total load of 35.7 kW and coil airflow of 1787 L/s. The supply fan has a maximum airflow of 1787 L/s and requires 0.33 kW of power.
The document summarizes the air system sizing for a GF-Staff Dining project in Madinah, Saudi Arabia. It includes sizing calculations for the central cooling coil, central heating coil, supply fan, and outdoor ventilation air. The central cooling coil has a total load of 35.7 kW and coil airflow of 1787 L/s. The supply fan has a maximum airflow of 1787 L/s and requires 0.33 kW of power.
Air System Name GF-Staff Dining Number of zones 1 Equipment Class UNDEF Floor Area 162.0 m² Air System Type SZCAV Location Madinah, Saudi Arabia
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Central Cooling Coil Sizing Data
Total coil load 35.7 kW Load occurs at Jul 1500 Sensible coil load 34.5 kW OA DB / WB 46.0 / 20.0 °C Coil L/s at Jul 1500 1787 L/s Entering DB / WB 29.1 / 17.2 °C Max block L/s 1787 L/s Leaving DB / WB 11.8 / 10.7 °C Sum of peak zone L/s 1787 L/s Coil ADP 9.9 °C Sensible heat ratio 0.968 Bypass Factor 0.100 m²/kW 4.5 Resulting RH 52 % W/m² 220.1 Design supply temp. 11.0 °C Water flow @ 5.6 °K rise 1.54 L/s Zone T-stat Check 1 of 1 OK Max zone temperature deviation 0.0 °K
Central Heating Coil Sizing Data
Max coil load 4.9 kW Load occurs at Des Htg Coil L/s at Des Htg 1787 L/s W/m² 30.0 Max coil L/s 1787 L/s Ent. DB / Lvg DB 19.4 / 21.8 °C Water flow @ 11.1 °K drop 0.10 L/s
Supply Fan Sizing Data
Actual max L/s 1787 L/s Fan motor BHP 0.42 BHP Standard L/s 1653 L/s Fan motor kW 0.33 kW Actual max L/(s-m²) 11.03 L/(s-m²) Fan static 100 Pa