Air System Sizing Summary For GF-Staff Dining

The document summarizes the air system sizing for a GF-Staff Dining project in Madinah, Saudi Arabia. It includes sizing calculations for the central cooling coil, central heating coil, supply fan, and outdoor ventilation air. The central cooling coil has a total load of 35.7 kW and coil airflow of 1787 L/s. The supply fan has a maximum airflow of 1787 L/s and requires 0.33 kW of power.

Uploaded by

riyasudheenmh
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
31 views

Air System Sizing Summary For GF-Staff Dining

The document summarizes the air system sizing for a GF-Staff Dining project in Madinah, Saudi Arabia. It includes sizing calculations for the central cooling coil, central heating coil, supply fan, and outdoor ventilation air. The central cooling coil has a total load of 35.7 kW and coil airflow of 1787 L/s. The supply fan has a maximum airflow of 1787 L/s and requires 0.33 kW of power.

Uploaded by

riyasudheenmh
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for GF-Staff Dining

Project Name: PS-SA-20-108673 Accommodation A-REV01 19-3-2022 05/11/2022


Prepared by: ASL 02:04PM

Air System Information


Air System Name GF-Staff Dining Number of zones 1
Equipment Class UNDEF Floor Area 162.0 m²
Air System Type SZCAV Location Madinah, Saudi Arabia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 35.7 kW Load occurs at Jul 1500
Sensible coil load 34.5 kW OA DB / WB 46.0 / 20.0 °C
Coil L/s at Jul 1500 1787 L/s Entering DB / WB 29.1 / 17.2 °C
Max block L/s 1787 L/s Leaving DB / WB 11.8 / 10.7 °C
Sum of peak zone L/s 1787 L/s Coil ADP 9.9 °C
Sensible heat ratio 0.968 Bypass Factor 0.100
m²/kW 4.5 Resulting RH 52 %
W/m² 220.1 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise 1.54 L/s Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Central Heating Coil Sizing Data


Max coil load 4.9 kW Load occurs at Des Htg
Coil L/s at Des Htg 1787 L/s W/m² 30.0
Max coil L/s 1787 L/s Ent. DB / Lvg DB 19.4 / 21.8 °C
Water flow @ 11.1 °K drop 0.10 L/s

Supply Fan Sizing Data


Actual max L/s 1787 L/s Fan motor BHP 0.42 BHP
Standard L/s 1653 L/s Fan motor kW 0.33 kW
Actual max L/(s-m²) 11.03 L/(s-m²) Fan static 100 Pa

Outdoor Ventilation Air Data


Design airflow L/s 488 L/s L/s/person 5.42 L/s/person
L/(s-m²) 3.01 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 1