Air System Sizing Summary For AHU-01G

This document provides an air system sizing summary for AHU-01G serving a 1-zone education college building with 899.2 square meters of floor area. Key details include: The central cooling coil is sized to handle a total load of 152.5 kW and sensible load of 126.6 kW at peak conditions in July. The design supply air temperature is 13.0°C. The supply fan is sized for a maximum airflow of 8228 L/s to serve the peak sensible load. The fan has a 18.39 BHP motor requiring 13.71 kW of power. Outdoor air is provided at a rate of 1420 L/s or 1.58 L/

Uploaded by

Farid Sedeky
Copyright
© © All Rights Reserved
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views

Air System Sizing Summary For AHU-01G

This document provides an air system sizing summary for AHU-01G serving a 1-zone education college building with 899.2 square meters of floor area. Key details include: The central cooling coil is sized to handle a total load of 152.5 kW and sensible load of 126.6 kW at peak conditions in July. The design supply air temperature is 13.0°C. The supply fan is sized for a maximum airflow of 8228 L/s to serve the peak sensible load. The fan has a 18.39 BHP motor requiring 13.71 kW of power. Outdoor air is provided at a rate of 1420 L/s or 1.58 L/

Uploaded by

Farid Sedeky
Copyright
© © All Rights Reserved
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for AHU-01G

Project Name: EDUCATION COLLEGE


Prepared by: ame

10/01/2008
07:20

Air System Information


Air System Name .......................................... AHU-01G
Equipment Class ............................................ CW AHU
Air System Type ..................................................... VAV

Number of zones ............................................................. 1


Floor Area ................................................................. 899.2 m

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s ............................... Peak zone sensible load
Space L/s ...................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ....................................................... 152.5
Sensible coil load ................................................. 126.6
Coil L/s at Jul 1500 ................................................ 6907
Max block L/s at Jul 1500 ...................................... 8228
Sum of peak zone L/s ........................................... 7816
Sensible heat ratio ............................................... 0.831
m/kW ....................................................................... 5.9
W/m ..................................................................... 169.5
Water flow @ 5.6 K rise ........................................ 6.57

kW
kW
L/s
L/s
L/s

L/s

Load occurs at ..................................................... Jul 1500


OA DB / WB ...................................................... 44.5 / 24.7
Entering DB / WB ............................................. 27.7 / 17.6
Leaving DB / WB .............................................. 11.3 / 10.4
Coil ADP ....................................................................... 9.4
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 45
Design supply temp. ................................................... 13.0
Zone T-stat Check .................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

C
C
C
C
%
C
OK
K

Supply Fan Sizing Data


Actual max L/s at Jul 1500 .................................... 8228 L/s
Standard L/s .......................................................... 7613 L/s
Actual max L/(s-m) ................................................ 9.15 L/(s-m)

Outdoor Ventilation Air Data

Fan motor BHP ......................................................... 18.39 BHP


Fan motor kW ........................................................... 13.71 kW
Fan static ................................................................... 1000 Pa
l/s/person .................................................................. 10.00 l/s/person

Design airflow L/s .................................................. 1420 L/s


L/(s-m) ................................................................... 1.58 L/(s-m)

Hourly Analysis Program v.4.1

Page 1 of 1