This document provides an air system sizing summary for AHU-01G serving a 1-zone education college building with 899.2 square meters of floor area. Key details include:
The central cooling coil is sized to handle a total load of 152.5 kW and sensible load of 126.6 kW at peak conditions in July. The design supply air temperature is 13.0°C.
The supply fan is sized for a maximum airflow of 8228 L/s to serve the peak sensible load. The fan has a 18.39 BHP motor requiring 13.71 kW of power.
Outdoor air is provided at a rate of 1420 L/s or 1.58 L/
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
15 views
Air System Sizing Summary For AHU-01G
This document provides an air system sizing summary for AHU-01G serving a 1-zone education college building with 899.2 square meters of floor area. Key details include:
The central cooling coil is sized to handle a total load of 152.5 kW and sensible load of 126.6 kW at peak conditions in July. The design supply air temperature is 13.0°C.
The supply fan is sized for a maximum airflow of 8228 L/s to serve the peak sensible load. The fan has a 18.39 BHP motor requiring 13.71 kW of power.
Outdoor air is provided at a rate of 1420 L/s or 1.58 L/
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for AHU-01G
Project Name: EDUCATION COLLEGE
Prepared by: ame
10/01/2008 07:20
Air System Information
Air System Name .......................................... AHU-01G Equipment Class ............................................ CW AHU Air System Type ..................................................... VAV
Number of zones ............................................................. 1
Floor Area ................................................................. 899.2 m
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s ............................... Peak zone sensible load Space L/s ...................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ....................................................... 152.5 Sensible coil load ................................................. 126.6 Coil L/s at Jul 1500 ................................................ 6907 Max block L/s at Jul 1500 ...................................... 8228 Sum of peak zone L/s ........................................... 7816 Sensible heat ratio ............................................... 0.831 m/kW ....................................................................... 5.9 W/m ..................................................................... 169.5 Water flow @ 5.6 K rise ........................................ 6.57
kW kW L/s L/s L/s
L/s
Load occurs at ..................................................... Jul 1500
OA DB / WB ...................................................... 44.5 / 24.7 Entering DB / WB ............................................. 27.7 / 17.6 Leaving DB / WB .............................................. 11.3 / 10.4 Coil ADP ....................................................................... 9.4 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 45 Design supply temp. ................................................... 13.0 Zone T-stat Check .................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
C C C C % C OK K
Supply Fan Sizing Data
Actual max L/s at Jul 1500 .................................... 8228 L/s Standard L/s .......................................................... 7613 L/s Actual max L/(s-m) ................................................ 9.15 L/(s-m)
Outdoor Ventilation Air Data
Fan motor BHP ......................................................... 18.39 BHP
Fan motor kW ........................................................... 13.71 kW Fan static ................................................................... 1000 Pa l/s/person .................................................................. 10.00 l/s/person