This document summarizes the air system sizing for the control room at the GAYATHI-3 project in Abu Dhabi, United Arab Emirates. The control room has a floor area of 2220 square feet and requires a central cooling coil with a capacity of 12.3 tons to handle a peak cooling load of 147.8 MBH. The required airflow is 6715 CFM based on a July design condition of 110.2°F dry bulb and 85°F wet bulb. Outdoor air ventilation for the space is designed at 50 CFM.
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
87 views
Load Summary
This document summarizes the air system sizing for the control room at the GAYATHI-3 project in Abu Dhabi, United Arab Emirates. The control room has a floor area of 2220 square feet and requires a central cooling coil with a capacity of 12.3 tons to handle a peak cooling load of 147.8 MBH. The required airflow is 6715 CFM based on a July design condition of 110.2°F dry bulb and 85°F wet bulb. Outdoor air ventilation for the space is designed at 50 CFM.
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for Control Room
Project Name: GAYATHI-3
Prepared by: KHAIRALLA CENTRAL A/C
09/04/2011 10:34AM
Air System Information
Air System Name .................................. Control Room Equipment Class ........................................ PKG ROOF Air System Type ................................................ SZCAV
Number of zones ............................................................. 1
Floor Area ............................................................... 2220.0 ft Location .................... Abu Dhabi, United Arab Emirates
Sizing Calculation Information
Zone and Space Sizing Method: Zone CFM ....................... Sum of space airflow rates Space CFM ................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ......................................................... 12.3 Total coil load ....................................................... 147.8 Sensible coil load ................................................. 132.7 Coil CFM at Jul 1800 ............................................. 6715 Max block CFM ..................................................... 6715 Sum of peak zone CFM ........................................ 6715 Sensible heat ratio ............................................... 0.898 ft/Ton ................................................................... 180.2 BTU/(hr-ft) ............................................................. 66.6 Water flow @ 10.0 F rise ....................................... N/A
Tons MBH MBH CFM CFM CFM
Load occurs at ..................................................... Jul 1800
OA DB / WB ................................................... 110.2 / 85.0 Entering DB / WB ............................................. 76.7 / 64.5 Leaving DB / WB .............................................. 58.3 / 57.2 Coil ADP ..................................................................... 56.3 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 52 Design supply temp. ................................................... 58.0 Zone T-stat Check ................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
F F F F % F OK F
Central Heating Coil Sizing Data
Max coil load .......................................................... 51.4 MBH Coil CFM at Dec 0800 ........................................... 6715 CFM Max coil CFM ........................................................ 6715 CFM Water flow @ 20.0 F drop ..................................... N/A
Load occurs at ................................................... Dec 0800
BTU/(hr-ft) ................................................................. 23.1 Ent. DB / Lvg DB .............................................. 60.6 / 67.7 F
Supply Fan Sizing Data
Actual max CFM .................................................... 6715 CFM Standard CFM ....................................................... 6694 CFM Actual max CFM/ft ................................................ 3.02 CFM/ft
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static .................................................................... 0.00 in wg CFM/person .............................................................. 10.00 CFM/person