Load Summary

This document summarizes the air system sizing for the control room at the GAYATHI-3 project in Abu Dhabi, United Arab Emirates. The control room has a floor area of 2220 square feet and requires a central cooling coil with a capacity of 12.3 tons to handle a peak cooling load of 147.8 MBH. The required airflow is 6715 CFM based on a July design condition of 110.2°F dry bulb and 85°F wet bulb. Outdoor air ventilation for the space is designed at 50 CFM.
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views

Load Summary

This document summarizes the air system sizing for the control room at the GAYATHI-3 project in Abu Dhabi, United Arab Emirates. The control room has a floor area of 2220 square feet and requires a central cooling coil with a capacity of 12.3 tons to handle a peak cooling load of 147.8 MBH. The required airflow is 6715 CFM based on a July design condition of 110.2°F dry bulb and 85°F wet bulb. Outdoor air ventilation for the space is designed at 50 CFM.
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for Control Room

Project Name: GAYATHI-3


Prepared by: KHAIRALLA CENTRAL A/C

09/04/2011
10:34AM

Air System Information


Air System Name .................................. Control Room
Equipment Class ........................................ PKG ROOF
Air System Type ................................................ SZCAV

Number of zones ............................................................. 1


Floor Area ............................................................... 2220.0 ft
Location .................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jan to Dec


Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ......................................................... 12.3
Total coil load ....................................................... 147.8
Sensible coil load ................................................. 132.7
Coil CFM at Jul 1800 ............................................. 6715
Max block CFM ..................................................... 6715
Sum of peak zone CFM ........................................ 6715
Sensible heat ratio ............................................... 0.898
ft/Ton ................................................................... 180.2
BTU/(hr-ft) ............................................................. 66.6
Water flow @ 10.0 F rise ....................................... N/A

Tons
MBH
MBH
CFM
CFM
CFM

Load occurs at ..................................................... Jul 1800


OA DB / WB ................................................... 110.2 / 85.0
Entering DB / WB ............................................. 76.7 / 64.5
Leaving DB / WB .............................................. 58.3 / 57.2
Coil ADP ..................................................................... 56.3
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................. 52
Design supply temp. ................................................... 58.0
Zone T-stat Check ................................................... 1 of 1
Max zone temperature deviation .................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load .......................................................... 51.4 MBH
Coil CFM at Dec 0800 ........................................... 6715 CFM
Max coil CFM ........................................................ 6715 CFM
Water flow @ 20.0 F drop ..................................... N/A

Load occurs at ................................................... Dec 0800


BTU/(hr-ft) ................................................................. 23.1
Ent. DB / Lvg DB .............................................. 60.6 / 67.7 F

Supply Fan Sizing Data


Actual max CFM .................................................... 6715 CFM
Standard CFM ....................................................... 6694 CFM
Actual max CFM/ft ................................................ 3.02 CFM/ft

Outdoor Ventilation Air Data


Design airflow CFM ................................................... 50 CFM
CFM/ft ................................................................... 0.02 CFM/ft

Hourly Analysis Program v4.50

Fan motor BHP ........................................................... 0.00 BHP


Fan motor kW ............................................................. 0.00 kW
Fan static .................................................................... 0.00 in wg
CFM/person .............................................................. 10.00 CFM/person