Air System Sizing Summary For AHU GYM

Download as rtf, pdf, or txt
Download as rtf, pdf, or txt
You are on page 1of 1

Air System Sizing Summary for AHU GYM

Project Name: PRIVATE SCHOOL AT AL KHOUD 03/26/2012


Prepared by: abc 07:42AM

Air System Information


Air System Name ......................................... AHU GYM Number of zones ............................................................. 1
Equipment Class ........................................ PKG ROOF Floor Area ................................................................. 648.0 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ........................................................ 269.3 kW Load occurs at ..................................................... Jul 1200
Sensible coil load ................................................. 222.8 kW OA DB / WB ...................................................... 46.1 / 29.6 C
Coil L/s at Jul 1200 .............................................. 14231 L/s Entering DB / WB ............................................. 25.9 / 18.0 C
Max block L/s ...................................................... 14231 L/s Leaving DB / WB .............................................. 12.9 / 12.2 C
Sum of peak zone L/s ......................................... 14231 L/s Coil ADP ..................................................................... 11.4 C
Sensible heat ratio ............................................... 0.827 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 2.4 Resulting RH ................................................................. 49 %
W/m ..................................................................... 415.6 Design supply temp. ................................................... 12.8 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Supply Fan Sizing Data

Actual max L/s ..................................................... 14231 L/s Fan motor BHP ......................................................... 10.60 BHP
Standard L/s ........................................................ 14206 L/s Fan motor kW ............................................................. 7.91 kW
Actual max L/(s-m) .............................................. 21.96 L/(s-m) Fan static ..................................................................... 300 Pa

Outdoor Ventilation Air Data


Design airflow L/s .................................................. 1069 L/s L/s/person ................................................................... 3.06 L/s/person
L/(s-m) ................................................................... 1.65 L/(s-m)

Hourly Analysis Program v4.50 Page 1 of 1