Air System Sizing Summary For Scenario 1: Harmonic Mode
Air System Sizing Summary For Scenario 1: Harmonic Mode
Air System Sizing Summary For Scenario 1: Harmonic Mode
Project Name: ESI Carbon Capture and Storage (CCS) Project 08/26/2015
Prepared by: Prime Electrical 08:39AM
Calculation Months .................................... Jan to Dec Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing .............. Individual peak space loads
Total coil load ..................................................... 102.7 kW Load occurs at .................................................. Jul 1500
Sensible coil load ................................................ 102.5 kW OA DB / WB ................................................... 43.9 / 23.3 C
Coil L/s at Jul 1500 .............................................. 4264 L/s Entering DB / WB ........................................... 35.8 / 21.2 C
Max block L/s ...................................................... 4264 L/s Leaving DB / WB ............................................ 15.9 / 14.5 C
Sum of peak zone L/s .......................................... 4264 L/s Coil ADP .................................................................. 13.6 C
Sensible heat ratio .............................................. 0.998 Bypass Factor ........................................................ 0.100
m/kW .................................................................... 0.5 Resulting RH ............................................................... 27 %
W/m ................................................................ 1975.4 Design supply temp. ................................................. 15.0 C
Water flow @ 5.6 K rise ....................................... N/A Zone T-stat Check ................................................. 0 of 1 OK
Max zone temperature deviation ................................ 0.0 K
Actual max L/s ..................................................... 4264 L/s Fan motor BHP ........................................................ 0.00 BHP
Standard L/s ........................................................ 4251 L/s Fan motor kW .......................................................... 0.00 kW
Actual max L/(s-m) ............................................ 82.00 L/(s-m) Fan static ...................................................................... 0 Pa
Calculation Months .................................... Jan to Dec Zone L/s Sizing .................. Sum of space airflow rates
Sizing Data ................................................ Calculated Space L/s Sizing .............. Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Emirates Steel-Harmonic '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 43.9 C / 23.3 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 35.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 76 m 484 - 76 m 292 -
Roof Transmission 52 m 1042 - 52 m 259 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 10 m 107 - 10 m 162 -
Floor Transmission 52 m -256 - 52 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 360 W 360 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 100680 W 100674 - 0 0 -
People 3 215 180 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 102626 180 - 713 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Emirates Steel-Harmonic '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 13 0.386 - 77 - 50
DOOR 4 1.703 - 47 - 72
W EXPOSURE
WALL 12 0.386 - 112 - 46
DOOR 5 1.703 - 60 - 90
N EXPOSURE
WALL 26 0.386 - 114 - 98
S EXPOSURE
WALL 26 0.386 - 181 - 98
E EXPOSURE
ROOF 26 0.498 - 506 - 129
W EXPOSURE
ROOF 26 0.498 - 536 - 129