Air System Sizing Summary For TOTAL COOLING LOAD
Air System Sizing Summary For TOTAL COOLING LOAD
Air System Sizing Summary For TOTAL COOLING LOAD
Calculation Months .................................... Jan to Dec Zone CFM Sizing ................... Peak zone sensible load
Sizing Data ................................................ Calculated Space CFM Sizing ........... Individual peak space loads
Total coil load ........................................................ 3.8 Tons Load occurs at .................................................. Jul 2200
Total coil load ....................................................... 45.8 MBH OA DB / WB ................................................... 91.9 / 80.1 °F
Sensible coil load .................................................. 34.0 MBH Entering DB / WB ........................................... 77.5 / 65.1 °F
Coil CFM at Jul 2200 ........................................... 1399 CFM Leaving DB / WB ............................................ 55.0 / 53.9 °F
Max block CFM at Jul 2200 ................................. 1544 CFM Coil ADP .................................................................. 52.5 °F
Sum of peak zone CFM ....................................... 1544 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.741 Resulting RH ............................................................... 50 %
ft²/Ton ................................................................. 211.1 Design supply temp. ................................................. 55.0 °F
BTU/(hr-ft²) ........................................................... 56.9 Zone T-stat Check ................................................. 1 of 1 OK
Water flow @ 10.0 °F rise ..................................... 9.17 gpm Max zone temperature deviation ................................ 0.0 °F
Max coil load ........................................................ 15.1 MBH Load occurs at ................................................... Des Htg
Coil CFM at Des Htg ............................................. 482 CFM BTU/(hr-ft²) ............................................................... 18.8
Max coil CFM ....................................................... 482 CFM Ent. DB / Lvg DB ............................................ 65.9 / 95.0 °F
Water flow @ 20.0 °F drop ................................... 1.51 gpm
Actual max CFM at Jul 2200 ................................ 1544 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ..................................................... 1544 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 1.92 CFM/ft² Fan static ................................................................. 0.00 in wg
Calculation Months .................................... Jan to Dec Zone CFM Sizing ................... Peak zone sensible load
Sizing Data ................................................ Calculated Space CFM Sizing ........... Individual peak space loads
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4744.4 BTU/(hr-CFM)
Site Altitude = 13.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4744.4 BTU/(hr-CFM)
Site Altitude = 13.0 ft
0.016
0.012
23
5 0.010
4
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( °F )