Air System Sizing Summary for PT7 Oficina 1

Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1


01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 1 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 645,8 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 3,9 Tons Load occurs at .................................................... Oct 1600
Total coil load .......................................................... 46,7 MBH OA DB / WB ...................................................... 82,4 / 71,7 °F
Sensible coil load ................................................... 35,7 MBH Entering DB / WB ............................................. 74,9 / 63,6 °F
Coil CFM at Oct 1600 ............................................ 2002 CFM Leaving DB / WB .............................................. 56,4 / 55,4 °F
Max block CFM ..................................................... 2002 CFM Coil ADP ..................................................................... 54,3 °F
Sum of peak zone CFM ........................................ 2002 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,765 Resulting RH ................................................................. 54 %
CFM/Ton ............................................................... 514,7 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 166,0 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 72,3 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 9,34 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 2002 CFM Fan motor BHP ........................................................... 0,27 BHP
Standard CFM ....................................................... 1788 CFM Fan motor kW ............................................................. 0,22 kW
Actual max CFM/ft² ................................................. 3,10 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 341 CFM CFM/person .............................................................. 28,45 CFM/person
CFM/ft² ................................................................... 0,53 CFM/ft²

Hourly Analysis Program 5.11 Page  1  of  70 


Zone Sizing Summary for PT7 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 1 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 645,8 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 2002 2002 3,10 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 34,8 Dec 1600 2,2 645,8

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 1 1 34,8 Dec 1600 2002 2,2 645,8 3,10

Hourly Analysis Program 5.11 Page  2  of  70 


Air System Design Load Summary for PT7 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Oct 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 82,4 °F / 71,7 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 225 ft² 13993 - 225 ft² - -
Wall Transmission 204 ft² 1866 - 204 ft² 584 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 225 ft² 932 - 225 ft² 1584 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 9 ft² 13 - 9 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 807 W 2397 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2583 W 8304 - 0 0 -
People 12 2464 2460 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2997 123 0% 0 0
>> Total Zone Loads - 32964 2583 - 2168 0
Zone Conditioning - 32009 2583 - -353 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2002 CFM 0 - 2002 CFM 0 -
Ventilation Load 341 CFM 2968 8373 341 CFM 1152 0
Supply Fan Load 2002 CFM 742 - 2002 CFM -742 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 35719 10956 - 57 0
Central Cooling Coil - 35719 10958 - 0 0
>> Total Conditioning - 35719 10958 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  3  of  70 


System Psychrometrics for PT7 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

October DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 82,4 0,01629 341 400 2968 8373
Vent - Return Mixing Outlet 74,9 0,01149 2002 791 - -
Central Cooling Coil Outlet 56,4 0,01020 2002 791 35719 10958
Supply Fan Outlet 56,8 0,01020 2002 791 742 -
Cold Supply Duct Outlet 56,8 0,01020 2002 791 - -
Zone Air - 73,4 0,01051 2002 872 32009 2583
Return Plenum Outlet 73,4 0,01051 2002 872 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 32964 Cooling 32009 73,4 2002 872 0 0

Hourly Analysis Program 5.11 Page  4  of  70 


System Psychrometrics for PT7 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 341 400 -1152 0
Vent - Return Mixing Outlet 60,9 0,01024 2002 442 - -
Central Cooling Coil Outlet 60,9 0,01024 2002 442 0 0
Supply Fan Outlet 61,3 0,01024 2002 442 742 -
Cold Supply Duct Outlet 61,3 0,01024 2002 442 - -
Zone Air - 61,5 0,01024 2002 451 353 0
Return Plenum Outlet 61,5 0,01024 2002 451 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -2168 Deadband 353 61,5 2002 451 0 0

Hourly Analysis Program 5.11 Page  5  of  70 


System Psychrometrics for PT7 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: October DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air
1
0,016

Specific Humidity ( lb/lb )


0,014
2 0,012
34 5
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  6  of  70 


System Psychrometrics for PT7 Oficina 1
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23
4 0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  7  of  70 


Air System Sizing Summary for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 2 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 539,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,8 Tons Load occurs at ................................................... Aug 1500
Total coil load .......................................................... 33,9 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 23,8 MBH Entering DB / WB ............................................. 76,3 / 64,9 °F
Coil CFM at Aug 1500 ........................................... 1243 CFM Leaving DB / WB .............................................. 56,4 / 55,4 °F
Max block CFM ..................................................... 1243 CFM Coil ADP ..................................................................... 54,2 °F
Sum of peak zone CFM ........................................ 1243 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,700 Resulting RH ................................................................. 55 %
CFM/Ton ............................................................... 439,6 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 190,6 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 63,0 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 6,79 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1243 CFM Fan motor BHP ........................................................... 0,17 BHP
Standard CFM ....................................................... 1110 CFM Fan motor kW ............................................................. 0,14 kW
Actual max CFM/ft² ................................................. 2,31 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 285 CFM CFM/person .............................................................. 28,48 CFM/person
CFM/ft² ................................................................... 0,53 CFM/ft²

Hourly Analysis Program 5.11 Page  8  of  70 


Zone Sizing Summary for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 2 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 539,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1243 1243 2,31 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 21,6 Mar 1000 1,1 539,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 2 1 21,6 Mar 1000 1243 1,1 539,0 2,31

Hourly Analysis Program 5.11 Page  9  of  70 


Air System Design Load Summary for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 138 ft² 5825 - 138 ft² - -
Wall Transmission 44 ft² 328 - 44 ft² 126 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 138 ft² 910 - 138 ft² 972 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 674 W 1980 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2156 W 6901 - 0 0 -
People 10 2025 2050 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1797 103 0% 0 0
>> Total Zone Loads - 19765 2153 - 1098 0
Zone Conditioning - 19482 2153 - -533 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1243 CFM 0 - 1243 CFM 0 -
Ventilation Load 285 CFM 3825 8015 285 CFM 1053 0
Supply Fan Load 1243 CFM 461 - 1243 CFM -461 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 23768 10167 - 60 0
Central Cooling Coil - 23768 10166 - 0 0
>> Total Conditioning - 23768 10166 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  10  of  70 


System Psychrometrics for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 285 400 3825 8015
Vent - Return Mixing Outlet 76,3 0,01216 1243 751 - -
Central Cooling Coil Outlet 56,4 0,01023 1243 751 23768 10166
Supply Fan Outlet 56,8 0,01023 1243 751 461 -
Cold Supply Duct Outlet 56,8 0,01023 1243 751 - -
Zone Air - 73,1 0,01064 1243 856 19482 2153
Return Plenum Outlet 73,1 0,01064 1243 856 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 19765 Cooling 19482 73,1 1243 856 0 0

Hourly Analysis Program 5.11 Page  11  of  70 


System Psychrometrics for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 285 400 -1053 0
Vent - Return Mixing Outlet 61,0 0,01024 1243 430 - -
Central Cooling Coil Outlet 61,0 0,01024 1243 430 0 0
Supply Fan Outlet 61,3 0,01024 1243 430 461 -
Cold Supply Duct Outlet 61,4 0,01024 1243 430 - -
Zone Air - 61,8 0,01024 1243 438 533 0
Return Plenum Outlet 61,8 0,01024 1243 438 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -1098 Deadband 533 61,8 1243 438 0 0

Hourly Analysis Program 5.11 Page  12  of  70 


System Psychrometrics for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  13  of  70 


System Psychrometrics for PT7 Oficina 2
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  14  of  70 


Air System Sizing Summary for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 3 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 377,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,6 Tons Load occurs at ................................................... Jun 1600
Total coil load .......................................................... 30,8 MBH OA DB / WB ...................................................... 85,4 / 73,7 °F
Sensible coil load ................................................... 21,5 MBH Entering DB / WB ............................................. 75,8 / 64,6 °F
Coil CFM at Jun 1600 ............................................ 1125 CFM Leaving DB / WB .............................................. 55,9 / 54,9 °F
Max block CFM ...................................................... 1125 CFM Coil ADP ..................................................................... 53,7 °F
Sum of peak zone CFM ......................................... 1125 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,698 Resulting RH ................................................................. 54 %
CFM/Ton ............................................................... 437,9 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 146,7 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 81,8 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 6,17 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1125 CFM Fan motor BHP ........................................................... 0,15 BHP
Standard CFM ....................................................... 1005 CFM Fan motor kW ............................................................. 0,12 kW
Actual max CFM/ft² ................................................. 2,99 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 244 CFM CFM/person .............................................................. 24,43 CFM/person
CFM/ft² ................................................................... 0,65 CFM/ft²

Hourly Analysis Program 5.11 Page  15  of  70 


Zone Sizing Summary for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 3 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 377,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1125 1125 2,99 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 19,5 Mar 1700 0,9 377,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 3 1 19,5 Mar 1700 1125 0,9 377,0 2,99

Hourly Analysis Program 5.11 Page  16  of  70 


Air System Design Load Summary for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 85,4 °F / 73,7 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 118 ft² 7788 - 118 ft² - -
Wall Transmission 9 ft² 76 - 9 ft² 25 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 118 ft² 699 - 118 ft² 834 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 471 W 1399 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1508 W 4847 - 0 0 -
People 10 2053 2050 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1686 103 0% 0 0
>> Total Zone Loads - 18548 2153 - 859 0
Zone Conditioning - 18209 2153 - -523 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1125 CFM 0 - 1125 CFM 0 -
Ventilation Load 244 CFM 2893 7169 244 CFM 968 0
Supply Fan Load 1125 CFM 417 - 1125 CFM -417 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 21519 9321 - 28 0
Central Cooling Coil - 21519 9322 - 0 0
>> Total Conditioning - 21519 9322 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  17  of  70 


System Psychrometrics for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 85,4 0,01743 244 400 2893 7169
Vent - Return Mixing Outlet 75,8 0,01200 1125 797 - -
Central Cooling Coil Outlet 55,9 0,01005 1125 797 21519 9322
Supply Fan Outlet 56,3 0,01005 1125 797 417 -
Cold Supply Duct Outlet 56,3 0,01005 1125 797 - -
Zone Air - 73,1 0,01050 1125 907 18209 2153
Return Plenum Outlet 73,1 0,01050 1125 907 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 18548 Cooling 18209 73,1 1125 907 0 0

Hourly Analysis Program 5.11 Page  18  of  70 


System Psychrometrics for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 244 400 -968 0
Vent - Return Mixing Outlet 61,2 0,01024 1125 435 - -
Central Cooling Coil Outlet 61,2 0,01024 1125 435 0 0
Supply Fan Outlet 61,6 0,01024 1125 435 417 -
Cold Supply Duct Outlet 61,6 0,01024 1125 435 - -
Zone Air - 62,1 0,01024 1125 444 523 0
Return Plenum Outlet 62,1 0,01024 1125 444 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -859 Deadband 523 62,1 1125 444 0 0

Hourly Analysis Program 5.11 Page  19  of  70 


System Psychrometrics for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: June DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  20  of  70 


System Psychrometrics for PT7 Oficina 3
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  21  of  70 


Air System Sizing Summary for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 4 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 377,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,4 Tons Load occurs at ..................................................... Jul 1600
Total coil load .......................................................... 28,9 MBH OA DB / WB ...................................................... 86,4 / 73,8 °F
Sensible coil load ................................................... 19,9 MBH Entering DB / WB ............................................. 76,4 / 65,0 °F
Coil CFM at Jul 1600 ............................................. 1012 CFM Leaving DB / WB .............................................. 56,0 / 55,0 °F
Max block CFM ..................................................... 1012 CFM Coil ADP ..................................................................... 53,7 °F
Sum of peak zone CFM ........................................ 1012 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,688 Resulting RH ................................................................. 54 %
CFM/Ton ............................................................... 420,1 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 156,5 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 76,7 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 5,78 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1012 CFM Fan motor BHP ........................................................... 0,14 BHP
Standard CFM ......................................................... 903 CFM Fan motor kW ............................................................. 0,11 kW
Actual max CFM/ft² ................................................. 2,68 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 244 CFM CFM/person .............................................................. 24,43 CFM/person
CFM/ft² ................................................................... 0,65 CFM/ft²

Hourly Analysis Program 5.11 Page  22  of  70 


Zone Sizing Summary for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 4 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 377,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1012 1012 2,68 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 17,6 Mar 1700 0,7 377,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 4 1 17,6 Mar 1700 1012 0,7 377,0 2,68

Hourly Analysis Program 5.11 Page  23  of  70 


Air System Design Load Summary for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 86,4 °F / 73,8 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 92 ft² 6106 - 92 ft² - -
Wall Transmission 35 ft² 308 - 35 ft² 100 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 92 ft² 597 - 92 ft² 648 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 471 W 1399 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1508 W 4847 - 0 0 -
People 10 2053 2050 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1531 103 0% 0 0
>> Total Zone Loads - 16842 2153 - 748 0
Zone Conditioning - 16388 2153 - -565 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1012 CFM 0 - 1012 CFM 0 -
Ventilation Load 244 CFM 3109 6878 244 CFM 964 0
Supply Fan Load 1012 CFM 375 - 1012 CFM -375 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 19872 9031 - 25 0
Central Cooling Coil - 19872 9031 - 0 0
>> Total Conditioning - 19872 9031 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  24  of  70 


System Psychrometrics for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

July DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 86,4 0,01721 244 400 3109 6878
Vent - Return Mixing Outlet 76,4 0,01217 1012 793 - -
Central Cooling Coil Outlet 56,0 0,01007 1012 793 19872 9031
Supply Fan Outlet 56,4 0,01007 1012 793 375 -
Cold Supply Duct Outlet 56,4 0,01007 1012 793 - -
Zone Air - 73,2 0,01057 1012 919 16388 2153
Return Plenum Outlet 73,2 0,01057 1012 919 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 16842 Cooling 16388 73,2 1012 919 0 0

Hourly Analysis Program 5.11 Page  25  of  70 


System Psychrometrics for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 244 400 -964 0
Vent - Return Mixing Outlet 61,1 0,01024 1012 425 - -
Central Cooling Coil Outlet 61,1 0,01024 1012 425 0 0
Supply Fan Outlet 61,5 0,01024 1012 425 375 -
Cold Supply Duct Outlet 61,5 0,01024 1012 425 - -
Zone Air - 62,1 0,01024 1012 433 565 0
Return Plenum Outlet 62,1 0,01024 1012 433 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -748 Deadband 565 62,1 1012 433 0 0

Hourly Analysis Program 5.11 Page  26  of  70 


System Psychrometrics for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: July DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  27  of  70 


System Psychrometrics for PT7 Oficina 4
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  28  of  70 


Air System Sizing Summary for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 5 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 743,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 5,4 Tons Load occurs at ................................................... Jun 1600
Total coil load .......................................................... 64,5 MBH OA DB / WB ...................................................... 85,4 / 73,7 °F
Sensible coil load ................................................... 49,9 MBH Entering DB / WB ............................................. 75,2 / 63,3 °F
Coil CFM at Jun 1600 ........................................... 2646 CFM Leaving DB / WB .............................................. 55,6 / 54,5 °F
Max block CFM ..................................................... 2646 CFM Coil ADP ..................................................................... 53,4 °F
Sum of peak zone CFM ........................................ 2646 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,774 Resulting RH ................................................................. 51 %
CFM/Ton ............................................................... 492,3 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 138,3 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 86,8 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise .................................... 12,90 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 2646 CFM Fan motor BHP ........................................................... 0,36 BHP
Standard CFM ....................................................... 2362 CFM Fan motor kW ............................................................. 0,29 kW
Actual max CFM/ft² ................................................. 3,56 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 381 CFM CFM/person .............................................................. 29,29 CFM/person
CFM/ft² ................................................................... 0,51 CFM/ft²

Hourly Analysis Program 5.11 Page  29  of  70 


Zone Sizing Summary for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 5 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 743,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 2646 2646 3,56 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 45,9 Jun 1600 3,6 743,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 5 1 45,9 Jun 1600 2646 3,6 743,0 3,56

Hourly Analysis Program 5.11 Page  30  of  70 


Air System Design Load Summary for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 85,4 °F / 73,7 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 413 ft² 22084 - 413 ft² - -
Wall Transmission 228 ft² 1942 - 228 ft² 650 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 413 ft² 2444 - 413 ft² 2916 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 200 ft² 300 - 200 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 929 W 2758 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2972 W 9554 - 0 0 -
People 13 2669 2665 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 4175 133 0% 0 0
>> Total Zone Loads - 45926 2798 - 3566 0
Zone Conditioning - 44541 2798 - -442 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2646 CFM 0 - 2646 CFM 0 -
Ventilation Load 381 CFM 4376 11787 381 CFM 1498 0
Supply Fan Load 2646 CFM 981 - 2646 CFM -981 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 49898 14585 - 76 0
Central Cooling Coil - 49898 14587 - 0 0
>> Total Conditioning - 49898 14587 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  31  of  70 


System Psychrometrics for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

June DESIGN COOLING DAY, 1600

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 85,4 0,01743 381 400 4376 11787
Vent - Return Mixing Outlet 75,2 0,01117 2646 793 - -
Central Cooling Coil Outlet 55,6 0,00987 2646 793 49898 14587
Supply Fan Outlet 56,0 0,00987 2646 793 981 -
Cold Supply Duct Outlet 56,0 0,00987 2646 793 - -
Zone Air - 73,5 0,01012 2646 859 44541 2798
Return Plenum Outlet 73,5 0,01012 2646 859 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 45926 Cooling 44541 73,5 2646 859 0 0

Hourly Analysis Program 5.11 Page  32  of  70 


System Psychrometrics for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 381 400 -1498 0
Vent - Return Mixing Outlet 61,5 0,01024 2646 453 - -
Central Cooling Coil Outlet 61,5 0,01024 2646 453 0 0
Supply Fan Outlet 61,9 0,01024 2646 453 981 -
Cold Supply Duct Outlet 61,9 0,01024 2646 453 - -
Zone Air - 62,1 0,01024 2646 462 442 0
Return Plenum Outlet 62,1 0,01024 2646 462 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -3566 Deadband 442 62,1 2646 462 0 0

Hourly Analysis Program 5.11 Page  33  of  70 


System Psychrometrics for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: June DESIGN COOLING DAY, 1600
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014

2 0,012
34 5
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  34  of  70 


System Psychrometrics for PT7 Oficina 5
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23
4 0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  35  of  70 


Air System Sizing Summary for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 6 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 743,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 5,1 Tons Load occurs at ..................................................... Jul 1500
Total coil load .......................................................... 60,8 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 43,1 MBH Entering DB / WB ............................................. 76,3 / 64,5 °F
Coil CFM at Jul 1500 ............................................. 2166 CFM Leaving DB / WB .............................................. 55,6 / 54,6 °F
Max block CFM ..................................................... 2166 CFM Coil ADP ..................................................................... 53,3 °F
Sum of peak zone CFM ........................................ 2166 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,709 Resulting RH ................................................................. 53 %
CFM/Ton ............................................................... 427,1 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 146,5 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 81,9 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise .................................... 12,18 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 2166 CFM Fan motor BHP ........................................................... 0,30 BHP
Standard CFM ....................................................... 1934 CFM Fan motor kW ............................................................. 0,24 kW
Actual max CFM/ft² ................................................. 2,91 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 486 CFM CFM/person .............................................................. 32,38 CFM/person
CFM/ft² ................................................................... 0,65 CFM/ft²

Hourly Analysis Program 5.11 Page  36  of  70 


Zone Sizing Summary for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 6 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 743,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 2166 2166 2,91 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 37,6 Jun 1500 3,1 743,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 6 1 37,6 Jun 1500 2166 3,1 743,0 2,91

Hourly Analysis Program 5.11 Page  37  of  70 


Air System Design Load Summary for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 367 ft² 14160 - 367 ft² - -
Wall Transmission 179 ft² 1318 - 179 ft² 510 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 367 ft² 2428 - 367 ft² 2592 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 929 W 2729 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2972 W 9512 - 0 0 -
People 15 3038 3075 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 3318 154 0% 0 0
>> Total Zone Loads - 36502 3229 - 3102 0
Zone Conditioning - 35837 3229 - -583 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 2166 CFM 0 - 2166 CFM 0 -
Ventilation Load 486 CFM 6491 14488 486 CFM 1460 0
Supply Fan Load 2166 CFM 803 - 2166 CFM -803 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 43131 17716 - 75 0
Central Cooling Coil - 43131 17717 - 0 0
>> Total Conditioning - 43131 17717 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  38  of  70 


System Psychrometrics for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 486 400 6491 14488
Vent - Return Mixing Outlet 76,3 0,01183 2166 719 - -
Central Cooling Coil Outlet 55,6 0,00990 2166 719 43131 17717
Supply Fan Outlet 56,0 0,00990 2166 719 803 -
Cold Supply Duct Outlet 56,0 0,00990 2166 719 - -
Zone Air - 73,1 0,01025 2166 811 35837 3229
Return Plenum Outlet 73,1 0,01025 2166 811 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 36502 Cooling 35837 73,1 2166 811 0 0

Hourly Analysis Program 5.11 Page  39  of  70 


System Psychrometrics for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 486 400 -1460 0
Vent - Return Mixing Outlet 60,4 0,01024 2166 432 - -
Central Cooling Coil Outlet 60,4 0,01024 2166 432 0 0
Supply Fan Outlet 60,8 0,01024 2166 432 803 -
Cold Supply Duct Outlet 60,8 0,01024 2166 432 - -
Zone Air - 61,1 0,01024 2166 441 583 0
Return Plenum Outlet 61,1 0,01024 2166 441 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -3102 Deadband 583 61,1 2166 441 0 0

Hourly Analysis Program 5.11 Page  40  of  70 


System Psychrometrics for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: July DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  41  of  70 


System Psychrometrics for PT7 Oficina 6
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 234
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  42  of  70 


Air System Sizing Summary for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 7 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 368,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 2,3 Tons Load occurs at ..................................................... Jul 1500
Total coil load .......................................................... 27,9 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 18,1 MBH Entering DB / WB ............................................. 77,5 / 66,5 °F
Coil CFM at Jul 1500 ............................................... 929 CFM Leaving DB / WB .............................................. 57,2 / 56,3 °F
Max block CFM ....................................................... 929 CFM Coil ADP ..................................................................... 55,0 °F
Sum of peak zone CFM .......................................... 929 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,650 Resulting RH ................................................................. 57 %
CFM/Ton ............................................................... 399,4 Design supply temp. ................................................... 55,0 °F
ft²/Ton ................................................................... 158,2 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 75,8 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 5,58 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 929 CFM Fan motor BHP ........................................................... 0,13 BHP
Standard CFM ......................................................... 829 CFM Fan motor kW ............................................................. 0,10 kW
Actual max CFM/ft² ................................................. 2,52 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 292 CFM CFM/person .............................................................. 29,20 CFM/person
CFM/ft² ................................................................... 0,79 CFM/ft²

Hourly Analysis Program 5.11 Page  43  of  70 


Zone Sizing Summary for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 7 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 368,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 929 929 2,52 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 15,2 Mar 1000 0,7 368,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 7 1 15,2 Mar 1000 929 0,7 368,0 2,52

Hourly Analysis Program 5.11 Page  44  of  70 


Air System Design Load Summary for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 92 ft² 3806 - 92 ft² - -
Wall Transmission 31 ft² 228 - 31 ft² 88 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 92 ft² 607 - 92 ft² 648 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 460 W 1352 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1472 W 4711 - 0 0 -
People 10 2025 2050 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1273 103 0% 0 0
>> Total Zone Loads - 14002 2153 - 736 0
Zone Conditioning - 13871 2153 - -355 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 929 CFM 0 - 929 CFM 0 -
Ventilation Load 292 CFM 3916 7625 292 CFM 735 0
Supply Fan Load 929 CFM 344 - 929 CFM -344 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 18131 9778 - 36 0
Central Cooling Coil - 18131 9778 - 0 0
>> Total Conditioning - 18131 9778 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  45  of  70 


System Psychrometrics for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

July DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 292 400 3916 7625
Vent - Return Mixing Outlet 77,5 0,01306 929 700 - -
Central Cooling Coil Outlet 57,2 0,01058 929 700 18131 9778
Supply Fan Outlet 57,6 0,01058 929 700 344 -
Cold Supply Duct Outlet 57,6 0,01058 929 700 - -
Zone Air - 73,1 0,01112 929 837 13871 2153
Return Plenum Outlet 73,1 0,01112 929 837 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 14002 Cooling 13871 73,1 929 837 0 0

Hourly Analysis Program 5.11 Page  46  of  70 


System Psychrometrics for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 292 400 -735 0
Vent - Return Mixing Outlet 59,8 0,01024 929 420 - -
Central Cooling Coil Outlet 59,8 0,01024 929 420 0 0
Supply Fan Outlet 60,2 0,01024 929 420 344 -
Cold Supply Duct Outlet 60,2 0,01024 929 420 - -
Zone Air - 60,6 0,01024 929 428 355 0
Return Plenum Outlet 60,6 0,01024 929 428 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -736 Deadband 355 60,6 929 428 0 0

Hourly Analysis Program 5.11 Page  47  of  70 


System Psychrometrics for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: July DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


2 0,014

5 0,012
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  48  of  70 


System Psychrometrics for PT7 Oficina 7
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  49  of  70 


Air System Sizing Summary for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 8 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 603,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 4,1 Tons Load occurs at ................................................... Aug 1500
Total coil load .......................................................... 48,7 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 35,2 MBH Entering DB / WB ............................................. 75,8 / 64,6 °F
Coil CFM at Aug 1500 ........................................... 1933 CFM Leaving DB / WB .............................................. 56,9 / 55,9 °F
Max block CFM ..................................................... 1933 CFM Coil ADP ..................................................................... 54,8 °F
Sum of peak zone CFM ........................................ 1933 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,724 Resulting RH ................................................................. 55 %
CFM/Ton ............................................................... 476,7 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 148,7 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 80,7 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 9,74 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1933 CFM Fan motor BHP ........................................................... 0,26 BHP
Standard CFM ....................................................... 1726 CFM Fan motor kW ............................................................. 0,21 kW
Actual max CFM/ft² ................................................. 3,21 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 391 CFM CFM/person .............................................................. 32,56 CFM/person
CFM/ft² ................................................................... 0,65 CFM/ft²

Hourly Analysis Program 5.11 Page  50  of  70 


Zone Sizing Summary for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 8 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 603,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1933 1933 3,21 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 33,6 Mar 1000 2,1 603,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 8 1 33,6 Mar 1000 1933 2,1 603,0 3,21

Hourly Analysis Program 5.11 Page  51  of  70 


Air System Design Load Summary for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 276 ft² 11649 - 276 ft² - -
Wall Transmission 47 ft² 352 - 47 ft² 136 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 276 ft² 1821 - 276 ft² 1944 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 387 ft² 580 - 387 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 754 W 2215 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 2412 W 7720 - 0 0 -
People 12 2430 2460 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2677 123 0% 0 0
>> Total Zone Loads - 29444 2583 - 2080 0
Zone Conditioning - 29187 2583 - -835 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1933 CFM 0 - 1933 CFM 0 -
Ventilation Load 391 CFM 5309 10868 391 CFM 1598 0
Supply Fan Load 1933 CFM 717 - 1933 CFM -717 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 35212 13451 - 46 0
Central Cooling Coil - 35212 13456 - 0 0
>> Total Conditioning - 35212 13456 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  52  of  70 


System Psychrometrics for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 391 400 5309 10868
Vent - Return Mixing Outlet 75,8 0,01205 1933 728 - -
Central Cooling Coil Outlet 56,9 0,01041 1933 728 35212 13456
Supply Fan Outlet 57,3 0,01041 1933 728 717 -
Cold Supply Duct Outlet 57,3 0,01041 1933 728 - -
Zone Air - 72,9 0,01072 1933 811 29187 2583
Return Plenum Outlet 72,9 0,01072 1933 811 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 29444 Cooling 29187 72,9 1933 811 0 0

Hourly Analysis Program 5.11 Page  53  of  70 


System Psychrometrics for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 391 400 -1598 0
Vent - Return Mixing Outlet 61,4 0,01024 1933 433 - -
Central Cooling Coil Outlet 61,4 0,01024 1933 433 0 0
Supply Fan Outlet 61,8 0,01024 1933 433 717 -
Cold Supply Duct Outlet 61,8 0,01024 1933 433 - -
Zone Air - 62,2 0,01024 1933 442 835 0
Return Plenum Outlet 62,2 0,01024 1933 442 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -2080 Deadband 835 62,2 1933 442 0 0

Hourly Analysis Program 5.11 Page  54  of  70 


System Psychrometrics for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
34 5

0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  55  of  70 


System Psychrometrics for PT7 Oficina 8
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  56  of  70 


Air System Sizing Summary for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 9 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 150,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 1,1 Tons Load occurs at ................................................... Nov 1500
Total coil load .......................................................... 13,4 MBH OA DB / WB ...................................................... 80,0 / 71,0 °F
Sensible coil load ..................................................... 9,7 MBH Entering DB / WB ............................................. 74,7 / 63,9 °F
Coil CFM at Nov 1500 ............................................. 547 CFM Leaving DB / WB .............................................. 56,2 / 55,3 °F
Max block CFM ....................................................... 547 CFM Coil ADP ..................................................................... 54,2 °F
Sum of peak zone CFM .......................................... 547 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,726 Resulting RH ................................................................. 54 %
CFM/Ton ............................................................... 489,3 Design supply temp. ................................................... 54,0 °F
ft²/Ton ................................................................... 134,2 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 89,4 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 2,68 gpm

Supply Fan Sizing Data

Actual max CFM ...................................................... 547 CFM Fan motor BHP ........................................................... 0,07 BHP
Standard CFM ......................................................... 488 CFM Fan motor kW ............................................................. 0,06 kW
Actual max CFM/ft² ................................................. 3,65 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 118 CFM CFM/person .............................................................. 29,38 CFM/person
CFM/ft² ................................................................... 0,78 CFM/ft²

Hourly Analysis Program 5.11 Page  57  of  70 


Zone Sizing Summary for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name .................................... PT7 Oficina 9 Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 150,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 547 547 3,65 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 9,5 Dec 1400 0,9 150,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Oficina 9 1 9,5 Dec 1400 547 0,9 150,0 3,65

Hourly Analysis Program 5.11 Page  58  of  70 


Air System Design Load Summary for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Nov 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 80,0 °F / 71,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 46 ft² 3405 - 46 ft² - -
Wall Transmission 188 ft² 1169 - 188 ft² 537 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 46 ft² 114 - 46 ft² 324 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 161 ft² 241 - 161 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 188 W 551 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1920 - 0 0 -
People 4 810 820 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 821 41 0% 0 0
>> Total Zone Loads - 9031 861 - 861 0
Zone Conditioning - 8767 861 - -291 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 547 CFM 0 - 547 CFM 0 -
Ventilation Load 118 CFM 765 2820 118 CFM 509 0
Supply Fan Load 547 CFM 203 - 547 CFM -203 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 9735 3681 - 15 0
Central Cooling Coil - 9735 3681 - 0 0
>> Total Conditioning - 9735 3681 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  59  of  70 


System Psychrometrics for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

November DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 80,0 0,01622 118 400 765 2820
Vent - Return Mixing Outlet 74,7 0,01177 547 751 - -
Central Cooling Coil Outlet 56,2 0,01018 547 751 9735 3681
Supply Fan Outlet 56,6 0,01018 547 751 203 -
Cold Supply Duct Outlet 56,6 0,01018 547 751 - -
Zone Air - 73,2 0,01055 547 847 8767 861
Return Plenum Outlet 73,2 0,01055 547 847 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 9031 Cooling 8767 73,2 547 847 0 0

Hourly Analysis Program 5.11 Page  60  of  70 


System Psychrometrics for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 118 400 -509 0
Vent - Return Mixing Outlet 61,5 0,01024 547 436 - -
Central Cooling Coil Outlet 61,5 0,01024 547 436 0 0
Supply Fan Outlet 61,9 0,01024 547 436 203 -
Cold Supply Duct Outlet 61,9 0,01024 547 436 - -
Zone Air - 62,5 0,01024 547 445 291 0
Return Plenum Outlet 62,5 0,01024 547 445 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -861 Deadband 291 62,5 547 445 0 0

Hourly Analysis Program 5.11 Page  61  of  70 


System Psychrometrics for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: November DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 0,018
5. Room Air
1
0,016

Specific Humidity ( lb/lb )


0,014
2
0,012
5
34
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  62  of  70 


System Psychrometrics for PT7 Oficina 9
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  63  of  70 


Air System Sizing Summary for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name ............. PT7 Pasillo de Circulacion Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 807,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Central Cooling Coil Sizing Data

Total coil load ............................................................ 3,6 Tons Load occurs at ................................................... Aug 1500
Total coil load .......................................................... 42,6 MBH OA DB / WB ...................................................... 87,0 / 74,0 °F
Sensible coil load ................................................... 27,5 MBH Entering DB / WB ............................................. 77,7 / 66,9 °F
Coil CFM at Aug 1500 ........................................... 1431 CFM Leaving DB / WB .............................................. 57,8 / 56,9 °F
Max block CFM ..................................................... 1431 CFM Coil ADP ..................................................................... 55,6 °F
Sum of peak zone CFM ........................................ 1431 CFM Bypass Factor .......................................................... 0,100
Sensible heat ratio ............................................... 0,644 Resulting RH ................................................................. 58 %
CFM/Ton ............................................................... 402,8 Design supply temp. ................................................... 57,0 °F
ft²/Ton ................................................................... 227,1 Zone T-stat Check .................................................... 1 of 1 OK
BTU/(hr·ft²) ............................................................. 52,8 Max zone temperature deviation .................................. 0,0 °F
Water flow @ 10,0 °F rise ...................................... 8,53 gpm

Supply Fan Sizing Data

Actual max CFM .................................................... 1431 CFM Fan motor BHP ........................................................... 0,20 BHP
Standard CFM ....................................................... 1278 CFM Fan motor kW ............................................................. 0,16 kW
Actual max CFM/ft² ................................................. 1,77 CFM/ft² Fan static .................................................................... 0,50 in wg

Outdoor Ventilation Air Data


Design airflow CFM ................................................. 482 CFM CFM/person .............................................................. 34,41 CFM/person
CFM/ft² ................................................................... 0,60 CFM/ft²

Hourly Analysis Program 5.11 Page  64  of  70 


Zone Sizing Summary for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Air System Information


Air System Name ............. PT7 Pasillo de Circulacion Number of zones ............................................................. 1
Equipment Class ............................................ CW AHU Floor Area ................................................................. 807,0 ft²
Air System Type ................................................ SZCAV Location ........................................... Caracas, Venezuela

Sizing Calculation Information

Calculation Months ..................................... Jan to Dec Zone CFM Sizing ................. Sum of space airflow rates
Sizing Data .................................................. Calculated Space CFM Sizing ............. Individual peak space loads

Zone Terminal Sizing Data

Reheat Zone Zone


Design Minimum Reheat Coil Htg Unit Htg Unit Mixing
Supply Supply Coil Water Coil Water Box Fan
Airflow Airflow Zone Load gpm Load gpm Airflow
Zone Name (CFM) (CFM) CFM/ft² (MBH) @ 20,0 °F (MBH) @ 20,0 °F (CFM)
Zone 1 1431 1431 1,77 0,0 0,00 0,0 0,00 0

Zone Peak Sensible Loads

Zone Zone Zone


Cooling Time of Heating Floor
Sensible Peak Sensible Load Area
Zone Name (MBH) Cooling Load (MBH) (ft²)
Zone 1 20,7 Mar 1000 0,3 807,0

Space Loads and Airflows

Time of
Cooling Peak Air Heating Floor
Zone Name / Sensible Sensible Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
PT7 Pasillo de Circulaci 1 20,7 Mar 1000 1431 0,3 807,0 1,77

Hourly Analysis Program 5.11 Page  65  of  70 


Air System Design Load Summary for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87,0 °F / 74,0 °F HEATING OA DB / WB 58,0 °F / 56,0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 46 ft² 1942 - 46 ft² - -
Wall Transmission 2 ft² 15 - 2 ft² 6 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 46 ft² 303 - 46 ft² 324 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 560 ft² 840 - 560 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 857 W 2519 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3228 W 10332 - 0 0 -
People 14 2835 2870 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1879 144 0% 0 0
>> Total Zone Loads - 20665 3014 - 330 0
Zone Conditioning - 20441 3014 - -2200 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 1431 CFM 0 - 1431 CFM 0 -
Ventilation Load 482 CFM 6493 12169 482 CFM 2767 0
Supply Fan Load 1431 CFM 531 - 1431 CFM -531 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 27465 15182 - 36 0
Central Cooling Coil - 27465 15183 - 0 0
>> Total Conditioning - 27465 15183 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program 5.11 Page  66  of  70 


System Psychrometrics for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

August DESIGN COOLING DAY, 1500

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 87,0 0,01728 482 400 6493 12169
Vent - Return Mixing Outlet 77,7 0,01333 1431 646 - -
Central Cooling Coil Outlet 57,8 0,01083 1431 646 27465 15183
Supply Fan Outlet 58,2 0,01083 1431 646 531 -
Cold Supply Duct Outlet 58,2 0,01083 1431 646 - -
Zone Air - 73,0 0,01132 1431 770 20441 3014
Return Plenum Outlet 73,0 0,01132 1431 770 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 20665 Cooling 20441 73,0 1431 770 0 0

Hourly Analysis Program 5.11 Page  67  of  70 


System Psychrometrics for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1
01/27/2021
Prepared by: UNICLIMA 01:02

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 58,0 0,01024 482 400 -2767 0
Vent - Return Mixing Outlet 62,0 0,01024 1431 415 - -
Central Cooling Coil Outlet 62,0 0,01024 1431 415 0 0
Supply Fan Outlet 62,3 0,01024 1431 415 531 -
Cold Supply Duct Outlet 62,4 0,01024 1431 415 - -
Zone Air - 64,0 0,01024 1431 423 2200 0
Return Plenum Outlet 64,0 0,01024 1431 423 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1,080; At site altitude = 0,964 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746,6; At site altitude = 4238,4 BTU/(hr-CFM)
Site Altitude = 3100,0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -330 Deadband 2200 64,0 1431 423 0 0

Hourly Analysis Program 5.11 Page  68  of  70 


System Psychrometrics for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: August DESIGN COOLING DAY, 1500
0,020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0,018
5. Room Air

0,016

Specific Humidity ( lb/lb )


2 0,014

5 0,012
34

0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  69  of  70 


System Psychrometrics for PT7 Pasillo de Circulacion
Project Name: PROYECTO DAYCO CARACAS - LAS MERCEDES version 25-1 01/27/2021
Prepared by: UNICLIMA 01:02

Location: Caracas, Venezuela


Altitude: 3100,0 ft.
Data for: WINTER DESIGN HEATING
0,020
1. Outdoor Air
2. Mixed Air
3. Supply Fan Outlet
4. Room Air 0,018

0,016

Specific Humidity ( lb/lb )


0,014

0,012
1 23 4
0,010

0,008

0,006

0,004

0,002

0,000
30 40 50 60 70 80 90 100
Temperature ( °F )

Hourly Analysis Program 5.11 Page  70  of  70 