Zone Sizing Summary For RF-Staircase 1: Air System Information
Zone Sizing Summary For RF-Staircase 1: Air System Information
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RF-Staircase 1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 367 - 6 m - -
Wall Transmission 9 m 54 - 9 m 27 -
Roof Transmission 36 m 316 - 36 m 72 -
Window Transmission 6 m 236 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 371 - 15 m 0 -
Overhead Lighting 720 W 720 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 540 W 540 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 312 80 0% 0 0
>> Total Zone Loads - 3434 880 - 213 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RF-Staircase 1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 9 0.300 - 54 - 27
WINDOW 1 6 1.900 0.500 236 367 114
H EXPOSURE
ROOF 36 0.200 - 316 - 72
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RF-Staircase 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1400 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 460 - 6 m - -
Wall Transmission 9 m 54 - 9 m 27 -
Roof Transmission 55 m 476 - 55 m 110 -
Window Transmission 6 m 231 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 5 m 0 - 5 m 19 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 366 - 15 m 0 -
Overhead Lighting 1100 W 1100 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 825 W 825 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 403 80 0% 0 0
>> Total Zone Loads - 4435 880 - 270 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RF-Staircase 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
SE EXPOSURE
WALL 9 0.300 - 54 - 27
WINDOW 1 6 1.900 0.500 231 460 114
H EXPOSURE
ROOF 55 0.200 - 476 - 110
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RF-Staircase 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 15 m 80 - 15 m 45 -
Roof Transmission 42 m 368 - 42 m 84 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 5 m 0 - 5 m 19 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 371 - 15 m 0 -
Overhead Lighting 840 W 840 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 630 W 630 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 281 80 0% 0 0
>> Total Zone Loads - 3089 880 - 148 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RF-Staircase 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 15 0.300 - 80 - 45
H EXPOSURE
ROOF 42 0.200 - 368 - 84
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RF-Staircase 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 46.0 C / 29.0 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 443 - 6 m - -
Wall Transmission 31 m 187 - 31 m 93 -
Roof Transmission 37 m 324 - 37 m 74 -
Window Transmission 6 m 236 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 5 m 0 - 5 m 19 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 371 - 15 m 0 -
Overhead Lighting 740 W 740 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 555 W 555 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 337 80 0% 0 0
>> Total Zone Loads - 3712 880 - 300 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RF-Staircase 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NE EXPOSURE
WALL 21 0.300 - 125 - 63
SE EXPOSURE
WALL 10 0.300 - 62 - 30
WINDOW 1 6 1.900 0.500 236 443 114
H EXPOSURE
ROOF 37 0.200 - 324 - 74
Calculation Months .................................... Aug to Aug Zone L/s Sizing ................... Sum of space airflow rates
Sizing Data ................................................. Calculated Space L/s Sizing ............... Individual peak space loads
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' RF-Staircase 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 45.6 C / 28.9 C HEATING OA DB / WB 11.1 C / 6.4 C
OCCUPIED T-STAT 23.0 C OCCUPIED T-STAT 21.1 C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 6 m 667 - 6 m - -
Wall Transmission 44 m 239 - 44 m 132 -
Roof Transmission 49 m 416 - 49 m 98 -
Window Transmission 6 m 235 - 6 m 114 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 5 m 0 - 5 m 19 -
Partitions 0 m 0 - 0 m 0 -
Ceiling 15 m 369 - 15 m 0 -
Overhead Lighting 980 W 980 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 735 W 735 - 0 0 -
People 6 519 800 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 416 80 0% 0 0
>> Total Zone Loads - 4576 880 - 363 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' RF-Staircase 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m) (W/(m-K)) Coeff. (W) (W) (W)
NW EXPOSURE
WALL 35 0.300 - 189 - 105
SW EXPOSURE
WALL 9 0.300 - 50 - 27
WINDOW 1 6 1.900 0.500 235 667 114
H EXPOSURE
ROOF 49 0.200 - 416 - 98