C3 - Concrete Mix Design
C3 - Concrete Mix Design
C3 - Concrete Mix Design
CONTENT PAGE
1. Topic 1
2. Introduction 1-2
3. Objective 3
5. Procedure 4-8
6. Results 9 - 12
7. Discussion 13
8. Conclusion 14
9. Reference 15
10. Appendix 16 - 23
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
1. TOPIC
2.INTRODUCTION
Mix design can be defined as the process selecting suitable ingredients of concrete
with a specified properties of workability, durability and strength which are cement,
fine and coarse aggregates and water. Workability is the amount of energy to
overcome friction while compacting. Workability also defined as the relative ease
with which concrete can be mixed, transported, moulded and compacted. Meanwhile
durability of cement is defined as its ability to resist weathering action, chemical
attack, abrasion, or any other process of deterioration. Durable concrete will retain its
original form, quality, and serviceability when exposed to environment. The
proportion of the materials need to be in the correct amount to produce a high strength
concrete because the higher the strength of the concrete, the better the concrete is
( American Concrete Institute Method of Mix Design, 1970 )
Mix design can also determine their relatives proportion with the object producing
concrete of certain minimum strength and durability as economically as possible.
Concrete mix design requires complete knowledge of the various properties of the
materials. The concrete mix design involves various steps, calculations and laboratory
testing to find right mix proportions. This process is usually adopted for structures
which requires higher grades of concrete.
Concrete mix design provides the right proportions of materials, thus making the
concrete construction economical in achieving required strength of structural
members. As the quantity of concrete required for large constructions are huge,
economy in quantity of materials such as cement makes the project construction
economical ( AkinOgun, n.d. ).
1
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
The best concrete will pass through the test that need to be done on it such as slump
test. Other tests like hardened concrete for compressive, flexural and splitting tensile
strength and modulus of elasticity using standard samples are normally performed at
the 3rd, 7th, 14th, 21st and 28th days.
Generally, there are 3 type of method to do the mix design which is IS, BS and ASI
method. Every method has its pros and cons, for IS method is applicable for Ordinary
and Standard grades of concrete only. This method does not give guidelines for design
of Light weight and heavy weight concrete. The compressive strength of hardened
concrete is to be specified on the basis of 150 mm cube test, determined at 28 days.
For BS method is applicable for design of normal concrete mixes having 28-days
compressive strength up to 75 MPa. This standard also gives guidelines for design of
light weight and heavy weight concrete. The compressive strength of hardened
concrete is to be specified on the basis of 150 mm cube test determined at 28 days, in
N/mm2 or 150 mm diameter by 300 mm cylinder tests, determined at 28 days, in
N/mm2. For ASI method is applicable for design of normal or heavy concrete, and
mass concrete mixes. This standard is not applicable for Light weight aggregate
concrete and for special admixtures for concrete products manufacture. This method
is also not applicable for using condensed Silica fume. The ACI method of mix
proportioning is applicable for normal and heavy weight concrete having 28-days
cylinder compressive strength of 45 MPa and slump ranges of 25 to 100 mm
( Jeevendra Kumar Chanrakar, S.P. Mishra, 2012 ).
2
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
2. OBJECTIVE
To practice the concrete mix design method and to determine the workability , density
and required strength for normal weight concrete of moderate / severe environmental
condition.
None
3
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
4. PROCEDURE
The value of s is obtained from Figure 1 which is 8 N/mm2 as the sample taken is less
than 20.
4
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Figure 2
From Figure 2, the water / cement ratio for this mix design is 0.58.
5
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Step 2: Selection of free-water content
Table 1
With 100 mm slump and 40mm maximum size aggregate (Crushed), the free-water
content for this mix design is 205 kg/m³.
6
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Step 4: Determination of total aggregate content
The wet density of concrete mix is determined from Figure 3 before the calculation of
total
aggregate content.
Figure 3
From Figure 3, the wet density of concrete mix with 205 kg/m3 and 2.65 (Value from
C2) of relative density of aggregate is 2380 kg/m3.
Total aggregate content = Concrete density – Cement content – Free water content
7
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Figure 4
With 96.9 % (Value from C1) of fine aggregate passing through 600m sieve, the
proportion of fine aggregate is 28 %.
8
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Reference of
Stage Item Values
calculation
25 N/mm2 at 28 days
1 1.1 Characteristic Strength Specified
Proportion defective 5%
5. RESULT / ANALYSIS
9
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
1.2 Standard Deviation Figure 2.4 8 N/mm2 or no data ________ N/mm2
1.3 Margin
Laboratory
C1
Report
or ( k = 1.64 ) 1.64 x 8 = 13.12 N/mm2
specified = 13 N/mm2
1.4 Target Mean Strength C2 25 + 13 = 38 N/mm2
1.5 Cement Type Specified OPC / SRPC / RHPC
1.6 Aggregate type : coarse Crushed / uncrushed
Aggregate type : fine Crushed / uncrushed
Table 2.8, 0.58
1.7 Free – water / cement ratio
figure 2.1
1.8 Maximum free-water/cement ratio Specified
Use the lower value 0.58
CALCULATIONS
10
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
2
= 13.12Report
Laboratory N/mm
Slump = 100 mm
Maximum aggregate size = 40 mm
= 354 kg/m3
11
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Grading of fine aggregate Laboratory % passing 600 μm sieve
= 96.9Report
Proportion of fine
= 28 %
aggregate
12
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Figure 5
The volume of cube:
150mm × 150mm × 150mm = 3.375 × 10-3 m3
Figure 6
The volume of beam:
500mm × 100mm × 100mm = 5x10-3 m3
= 0.0151 m3
Since it is specified that per trail mix is at 0.03 m3, thus, 0.03 m3 is used instead of the
total volume calculated ( 0.0151 m3 ).
6. DISCUSSION
13
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
From the result obtained, we used 10.65 kg of cement, 6.15 kg of water, 15.3 kg
of fine aggregates and 39.3 kg of coarse aggregates with size 10mm to make 3 cubes
with dimension 150mm × 150mm × 150mm and 1 beam with dimension 500mm ×
100mm × 100mm. The characteristic strength that we used in mix design form is 25
N/mm2 at 28 days. The margin that we obtained in mix design form is 13 N/mm2 and
the target mean strength obtain is 38 N/mm2.
For example, when the water / cement ratio is too high the strength of the
concrete will decrease because bleeding and segregation occur. Proper grading of fine
and coarse aggregates is also important to produce a good quality of concrete. The
insufficient of fine or coarse aggregates content will produce harsh mix that will
affect the workability and stability of concrete. On the other hand the excessive in fine
aggregates will produce an over sanded mix.
7. CONCLUSION
14
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
In conclusion, the mix design procedure is to indicate that the concrete will
result in a 25 N/mm2 of strength within 28 days.
8. REFERENCE
15
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
American Concrete Institute Method of Mix Design( 1970 )
Retrieved from
http://www.idc-online.com/technical_references/pdfs/civil_engineering/Concrete
_Mix_Design_Concept.pdf
AkinOgun, Concrete Mix Design Calculation for M20, M25, M30 Concrete with
Procedure & Example
Retrieved from
https://theconstructor.org/concrete/concrete-mix-design-calculation-procedure-ex
ample-m20-m25-m30/13020/
Retrieved from
http://www.academia.edu/25183260/BS_-CONCRETE_MIX_DESIGN_DOE
Jeevendra Kumar Chanrakar, S.P. Mishra ( 2012 ), Comparison of IS, BS and ACI
Methods of Concrete Mix Design
Retrieved from
https://www.researchgate.net/publication/271585894_Comparison_of_IS_BS_an
d_ACI_Methods_of_Concrete_Mix_Design_and_Proposing_Function_Equations
_Based_Design gn and Proposing Function Equations Based Design.
Retrieved from
https://www.itl.nist.gov/div898/handbook/pmd/section3/pmd31.htm
Retrieved from
https://www.wfm.co.in/increase-strength-concrete/
9. APPENDIX
16
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
Appendix 1
17
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
18
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
19
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
20
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
21
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
22
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
23
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
24
FACULTY OF ENGINEERING
KNS 1451 Civil Engineering Laboratory 1
Laboratory Report
25