Air System Sizing Summary For SF-ES-PAC 6
Air System Sizing Summary For SF-ES-PAC 6
Air System Sizing Summary For SF-ES-PAC 6
Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated
Total coil load .......................................................... 64.7 kW Load occurs at ................................................... Aug 1500
Sensible coil load ................................................... 51.8 kW OA DB / WB ...................................................... 48.0 / 30.0 C
Coil L/s at Aug 1500 .............................................. 3775 L/s Entering DB / WB ............................................. 27.3 / 20.0 C
Max block L/s ........................................................ 3775 L/s Leaving DB / WB .............................................. 15.9 / 15.3 C
Sum of peak zone L/s ........................................... 3775 L/s Coil ADP ..................................................................... 14.7 C
Sensible heat ratio ............................................... 0.801 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 5.2 Resulting RH ................................................................. 55 %
W/m ..................................................................... 190.7 Design supply temp. ................................................... 15.1 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K
Actual max L/s ....................................................... 3775 L/s Fan motor BHP ........................................................... 2.81 BHP
Standard L/s .......................................................... 3768 L/s Fan motor kW ............................................................. 2.10 kW
Actual max L/(s-m) .............................................. 11.14 L/(s-m) Fan static ..................................................................... 300 Pa